S02-RFP Attachment 20-Drawings-Dublin_Part11.pdf
PDF 2 MB Posted
- Solicitation number
- 36C77626R0031_1
About this file
This document consists of electrical construction drawings and details for the renovation of Building 9A at Carl Vinson VA Medical Center in Dublin, Georgia (Project 557-21-703). The project scope involves renovating space for EHRM (Electronic Health Record Management) administrative functions. The drawings include electrical details, fire alarm systems, telecommunications infrastructure, power distribution, and security systems. Key specifications include installation of dual authentication card readers (HID pivCLASS #RK40 or equivalent) with keypads at 42 inches above finished floor, data racks with fiber distribution cabinets and Cat 6A patch panels, telecommunications rooms with bonding conductors and junction boxes, security door strike systems with electronic control, and fire alarm devices including heat detectors, smoke detectors, and wireless access points. The document references VA standards for telecommunications infrastructure (Version 3.1), requires seismic bracing kits for data racks, and mandates coordination with existing facility systems and the VA station.
The contractor must provide comprehensive shutdown plans, temporary power plans, and phasing plans for VA and engineer review 30 days prior to implementation. All equipment labeling must comply with VA infrastructure standards. The telecommunications bonding system requires primary bonding busbars, telecommunications bonding backbone conductors (minimum 3 AWG), and equipment bonding conductors (minimum 6 AWG) connected to secondary bonding busbars. Fiber optic cabling shall be 24-strand within one-inch innerduct, routed through existing pathways, with fusion splices provided as needed. The design includes extended cabling to new devices throughout the facility, coordination with existing Building 03 switchboard (MS-3LNC1), and preservation of existing detection devices for Building 9 Level 2 outside the renovation scope. General contractor responsibilities include field verification of existing conditions, provision of all required equipment and hardware, coordination with manufacturers and architects for complete system functionality, and proper patching and fireproofing of all construction penetrations.
View the file
Other files
Show all 38
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CEILING STRUCTURE
THREADED ROD, DIAMETER
DEPENDENT ON J-HOOK SIZE
J-HOOK WITH COLORED ID, SIZE PER
CABLE CAPACITY, EATON B SERIES
COLORED J HOOK OR EQUIVALENT
CABLING PER PLAN
VELCRO CABLE TIE
J-HOOK COLORED ID, ID
COLOR SHALL MATCH VA
CABLING STANDARDS
18" MINIMUM
ACCESSIBLE CEILING
VARIES
DETAIL NOTES:
SPACE J-HOOKS MAXIMUM 4'
APART FROM ONE ANOTHER
FASTENER TO SUSPEND ROD
WIRING TABLE
PIGTAIL-
WIRE COLOR
TERM STRIP -
CONNECTION
CIRCUIT
FUNCTION
YELLOW
ORANGE
BLACK
RED
DRAIN
BROWN
BLUE
GRAY
PINK
GREEN
WHITE
VIOLET
TAN
RED/GREEN
P1-1
P1-2
P1-3
P1-4
P1-5
P1-6
P1-7
P2-1
P2-2
P2-3
P2-4
P2-5
P2-6
P2-7
NO CONNECT
NO CONNECT
RTN
+VDC
NO CONNECT
NO CONNECT
NO CONNECT
RS485 / TXA
RS485 / TXB
NO CONNECT
NO CONNECT
NO CONNECT
RS485 / RXB
RS485 / RXA
PIV ENABLED TWO-FACTOR AUTHENTICATION KEY PAD
AND CONTACTLESS AUTHENTICATION, HID pivCLASS
#RK40 OR EQUIVALENT
BEEP
GRN
RTN
+VDC
SHLD
RED
HOLD
GP101
GP102
OC/TMPR
DATA1
DATA0
GP103
GP104
JUNCTION BOX, 8" x 8" x 4"
MINIMUM
TO SECURE LOCAL
ACCESS CONTROL
PANEL, 1-1/2" CONDUIT
3/4" CONDUIT
ELECTRIC STRIKE / MORTISE LOCK
PER SYSTEM REQUIREMENTS,
PROVIDE BACKBOX AS REQUIRED
BY MANUFACTURER
DUAL AUTHENTICATION CARD
READER AND KEYPAD, 42" AFF,
HID pivCLASS #RK40 OR
EQUIVALENT, PROVIDE
BACKBOX AS REQUIRED BY
MANUFACTURER
SUSPENDED CEILING
FLOOR
120V POWER, 3/4" CONDUIT
REQUEST-TO-EXIT
WIRING, 3/4" CONDUIT
DOOR POSITION
SWITCH AND MAGNET
REQUEST-TO-EXIT
PIR MOTION SENSOR
REQUEST-TO-EXIT,
PUSH BUTTON
MOTION DETECTOR
DETAILS NOTES:
1. DETAIL IS SHOWN FOR GENERAL
DIAGRAMMATICAL PURPOSES. PROVIDE
ALL REQUIRED EQUIPMENT AND
HARDWARE FOR ALL DOOR TYPES
(SINGLE DOOR, DOUBLE DOOR, ETC.) AS
REQUIRED.
2. CONTRACTOR TO FURNISH AND INSTALL
ALL SECURITY AND PACS HARDWARE AS
REQUIRED PER PHYSICAL SECURITY AND
RESILIENCY DESIGN MANUAL AND
ASSOCIATED APPENDICES. COORDINATE
WITH ARCHITECT AND DOOR
MANUFACTURER TO PROVIDE A
COMPLETE AND FULLY FUNCTIONAL
ELECTRIFIED AND SECURED DOOR.
TYP
TYP
TYP
TYP
TYP
TYP
TYP
86"
BOTTOM 3RD SECTION
OF RACK IS
DESIGNATED TO
POWER DISTRIBUTION
EQUIPMENT.
REFERENCE
ELECTRICAL SHEET
EP502 FOR MORE
INFORMATION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
BOTTOM 3RD SECTION
OF RACK IS
DESIGNATED TO
POWER DISTRIBUTION
EQUIPMENT.
REFERENCE
ELECTRICAL SHEET
EP502 FOR MORE
INFORMATION
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:5
:4
P
M
A u to d e s k D o c s /5
-2
-7
V
A G
A D u b lin E
H R
M T
A S
S /V
A D
U
G E
N S
H E
E T
S
E L
S
D B
.r v t
E-505
ELECTRICAL DETAILS
JPB/WNM BCL
CONSTRUCTION
DOCUMENT
06/14/2024
557-21-703RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA
GENERAL NOTES
KEY NOTES
NTS
TYPICAL J-HOOK INSTALLATION DETAIL
ET101
NTS
TYPICAL CONTACTLESS AUTHENTICATION AND PINPAD DEVICE DETAIL
E-402
DATA RACK, 4-POST, WHITE FINISH, ORTRONICS #MM2073038-W, OR
APPROVED EQUAL.
VERTICAL CABLE MANAGER WITH DOOR, 6" WIDE, ORTRONICS
#MM20VMD706, OR APPROVED EQUAL.
FIBER DISTRIBUTION CABINET, ANGLED, 1RU, LEVITON ANGLED OPT-X
UHDX, OR APPROVED EQUAL; CABINET POPULATED WITH (12) CASSETTES,
LEVITON HDX ENTERPRISE MTP, OR APPROVED EQUAL. SIDE-A AND SIDE-B
FIBER BACKBONE SHALL TERMINATE TO SEPARATE SIDES OF
DISTRIBUTION CABINET.
CAT 6A UTP PATCH PANEL, ANGLED, 24-PORT WITH REAR CABLE MANAGER,
LEVITON #E2XHD-BLK, OR APPROVED EQUAL.
BLANKING PANEL, 1RU, LEVITON, OR APPROVED EQUAL.
HORIZONTAL CABLE MANAGER, 1RU OR 2RU AS SHOWN, LEVITON, OR
APPROVED EQUAL.
NETWORK SWITCH. VA PROVIDED, CONTRACTOR INSTALLED.
COORDINATE WITH VA FOR EXACT REQUIREMENTS AS NECESSARY.
DUAL AUTHENTICATION CARD READER AND KEYPAD MUST BE CAPABLE OF
INTERFACING WITH EXISTING VA ACCESS CONTROL SYSTEM.
NTS
SECURITY DOOR CARD READER INSTALLATION DETAIL
ET101
E-402
1. ALL TELECOMMUNICATIONS ROOM (TR) DATA RACK DETAIL ELEVATIONS
ARE SHOWN TO PROVIDE GENERAL LAYOUT REQUIREMENTS. EXACT
QUANTITIES OF UTP PATCH PANELS AND NETWORK SWITCHES PER TR ARE
SHOWN IN THE TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE
LOCATED ON SHEET TN701. IF MORE THAN (1) RACK IS PRESENT IN THE TR
BEING EVALUATED, CONTRACTOR SHALL DIVIDE THE PATCH PANEL AND
NETWORK SWITCH EQUIPMENT EVENLY AMONG THE RACKS [IE: IF (6)
PATCH PANELS AND (6) NETWORK SWITCHES ARE REQUIRED IN A TR THAT
HAS (2) DATA RACKS, PROVIDE EACH DATA RACK WITH (3) PATCH PANELS
AND (3) NETWORK SWITCHES].
2. VA DATA RACKS FOLLOW A RULE OF THIRDS FOR POSITIONING EQUIPMENT
ON THE RACK. THE TOP THIRD IS DESIGNATED FOR FIBER AND UTP PATCH
EQUIPMENT, THE MIDDLE THIRD IS DESIGNATED FOR NETWORK SWITCH
EQUIPMENT, AND THE BOTTOM THIRD IS DESIGNATED FOR DATA RACK
POWER DISTRIBUTION EQUIPMENT.
3. PRIOR TO CONSTRUCTING TR DATA RACKS AND DURING THE SUBMITTAL
PROCESS, CONTRACTOR SHALL SUBMIT ALL TR DATA RACK ELEVATIONS
(FRONT, BACK, AND SIDE VIEWS) FOR ENGINEER AND VA REVIEW AND
APPROVAL. SUBMITTAL SHALL SHOW ALL DIMENSIONS, CABLE
MANAGEMENT EQUIPMENT, LABELING AND ASSOCIATED CUTSHEETS WITH
INDICATED PART NUMBERS AND OPTIONS FOR ALL EQUIPMENT.
4. CONTRACTOR SHALL LABEL EACH PATCH PANEL PORT WITH PORT NUMBER
AND ROOM NUMBER.
5. ALL DATA RACKS SHALL BE PROVIDED WITH SEISMIC BRACING KITS AND
INSTALLED PER MANUFACTURER'S INSTRUCTIONS.
6. ALL EQUIPMENT, CABLING, CONNECTORS AND APPURTENANCES SHALL BE
LABELED PER THE VA STANDARD "INFRASTRUCTURE STANDARD FOR
TELECOMMUNICATIONS SPACE" VERSION 3.1 OR NEWER.
7. WHERE RACK EQUIPMENT IS NOT REQUIRED FOR CABLING REQUIREMENTS
PROVIDE BLANKING PLATES IN ABSENT SPACES.
8. PROVIDE BLANKING PANELS IN ALL TR RACK VACANT SPACES IF NOT
NOTED OTHERWISE.
1 : 30
TR DATA RACK ELEVATION - TWO RACK
E-402
DETAIL IS GENERIC IN NATURE AND SHOWS GENERAL LAYOUT INFORMATION.
REFERENCE GENERAL AND KEY NOTES FOR SPECIFIC INFORMATION
Revisions: Date:
CONSTRUCTION
DOCUMENTS
15 in. (375 mm) min.
6 ft (1.8 m) max.
All switches, lamps and textual displays must be within range
FIRE
FIRE
FIRE
90 in.
(2.29 m) min.
Measured to the top of appliance
Heat Detector Ceiling mounted
6 in.
(150 mm) min.
Measured from each unit doorway from each floor
6 in.
(150 mm) min.
6 in.
(150 mm) min.
90 in.
(2.29 m) min.
Measured to the top of appliance
Smoke Detector Ceiling mounted
90 in.
(2.29 m) min.
Measured to the top of appliance
1'-6"
3'-6"
WIRELESS ACCESS POINT
CEILING MOUNTED
SECURITY HORN/SIREN
8'-0"
CARD READER
FIRE ALARM
STATION
DATA OUTLET
CEILING
EMERGENCY LIGHT
MOTION SENSOR
FINISHED
FLOOR LINE
SWITCH
EPO
EMERGENCY
STOP
BUTTON
BONDING BUSBAR
KEYPAD/CARD
ACCESS
ELECTRICAL PANEL
120VAC
EMERGENCY POWER
L
N
G INTEGRAL BATTERIES
NAC CIRCUIT
DATA
COMMUNICATION
TO CAMPUS FIRE
ALARM MASTER
PANEL
INPUT LOOP
FSFIRE ALARM
CONTROL PANEL
FIBER-OPTIC CABLING
EOL
CHANGE
MGMT
USER
COR
CR11-9
IV
TESTING
IV
TESTING
IV
TESTING
ELECT
ROOM
COR
CR11-9
IV
TESTING
COR
CR11-9
IV
SUPPORT
COR
CR11-9
COR
CR11-9
WAITING
ALCOVE
IV
TESTING
FS
WAITING
ALCOVE
IV
SUPPORT
IV
SUPPORT
COR
CR11-9
COR
CR11-9
COR
CR11-9
COR
CR11-9
COR
CR11-9
COR
CR11-9
COR
CR11-9
FS
WAITING
ALCOVE
COR
CR11-9
IV
TESTING
COR
CR11-9
COR
CR11-9
IV
TESTING
IV
SUPPORT
IV
TESTING
EXTEND EXISTING CABLING TO NEW DEVICES AS SHOWN, TYP.
MECH
MECH
101EXISTING FACP 'NOTIFIER' BY HONEYWELL. ALL
DETECTION AND SIGNALING DEVICES SHALL BE
COMPATIBLE WITH NOTIFIER SYSTEM.
EXTEND EXISTING CABLING TO NEW DEVICES AS SHOWN, TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:5
:5
P
M
A u to d e s k D o c s /5
-2
-7
V
A G
A D u b lin E
H R
M T
A S
S /V
A D
U
G E
N S
H E
E T
S
E L
S
D B
.r v t
E-506
ELECTRICAL DETAILS
JPB/WNM BCL
CONSTRUCTION
DOCUMENT
06/14/2024
557-21-703RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA
- NTS
1 FIRE ALARM RISER DIAGRAM AND I/O MATRIX
- NTS
2 TYPICAL LOW-VOLTAGE EQUIPMENT MOUNTING HEIGHT DETAIL
DETAIL NOTES(S):
1. THESE TYPICAL MOUNTING HEIGHTS
SHALL BE USED UNLESS OTHERWISE
NOTED ON THE PLANS.
- 3/4" = 1'-0"
3 TYPICAL ELECTRICAL EQUIPMENT MOUNTING HEIGHT DETAIL
DETAIL NOTES(S):
1. REFERENCE SHEET ED103, EF101, & EF102 FOR EXACT DEVICE QUANTITIES AND LOCATIONS.
2. FIRE ALARM RISER DIAGRAM SHOWN FOR INFORMATIONAL PURPOSES ONLY. COORDINATE WITH EXISTING FACILITY
INFRASTRUCTURE, EQUIPMENT, NATIONAL/LOCAL CODES AND MANUFACTURE TO PROVIDE A COMPLETE AND FULLY
FUNCTIONAL SYSTEM AS REQUIRED.
3. PROVIDE FIRE ALARM DEVICES IN FIELD AS REQUIRED. COORDINATE FIELD CONNECTIONS WITH ALL EQUIPMENT;
PROVIDE CONNECTIONS, CABLING AND TERMINATIONS AS REQUIRED.
4. PROVIDE 3/4" CONDUIT FOR ALL NEW CABLE AS REQUIRED. ALL FIRE ALARM CONDUIT SHALL BE PAINTED RED.
5. PRESERVE ALL DETECTION AND INITIATING DEVICES FOR LEVEL 2 OF BUILDING 9 THAT IS OUTSIDE THE SCOPE OF WORK.
COORDINATE ANY SHUTDOWN OF FACP THAT WOULD AFFECT THESE AREAS WITH THE VA STATION AND COR PRIOR
TO BEGINNING WORK.
Revisions: Date:
09-P-10
CONTINUED FROM
MEDIUM VOLTAGE EQUIPMENT
00_TX_T-5A
1500kVA;
5.34%; 4160 V / 480 V
PANELBOARD
'9LCA3'
100A
208/120V
3PH, 4W
10KAIC
DPM
SPD
S
P
S
P
S
P
S
P
E N
87_FB_87HNA2
GE SFLA
250AF 225AT 225AP
87_CBL_87HNA2
(1) 4/0 AWG Copper 5 ft, Magnetic
87_MB_87HNA2
GE SEPA
100AF 100AT 100AP
87_PB_87HNA2
Bldg: 87, ELEC RM 480 V 3P 11325.54 A
S
P
S
P
S
P
S
P
S
P
E N
S
P S
P
S
P
S
P
E N
E N
S
P
S
P
S
P
05_PB_5LEA1
Bldg: 05, Rm: C152 208 V 3P 831.99 A
05_MB_5LEA1
SQUARE D QO
60AF 60AT 60AP
05_CBL_5XEA2 (SEC)
(1) 6 AWG Copper 7 ft, Magnetic
S
P 05_TX_5XEA2
15 kVA;
4.80%; 480 V / 208 V
S
P
05_CBL_5XEA2 (PRI)
(1) 10 AWG Copper 15 ft, Magnetic
05_FB_5XEA2
SQUARE D FC
30AF 30AT 30AP
E N
05_GN_GEN6
RatedVoltage 480 V Rated kW 360 kW Rated kVA 400 kVA
05_FB_GEN 6
CUTLER-HAMMER HMC
800AF 800AT 600AP
05_BS_GEN 6
Bldg: 05, Rm: C153 480 V 3P 0.00 A
05_CBL_5HGA1
(2) 350 kcmil Copper 15 ft, Magnetic
05_PB_5HGA1
Bldg: 05, Rm: C153 480 V 3P 0.00 A
05_FB_ATS-5HCA1 (E)
SQUARE D LH
400AF 400AT 400AP
05_CBL_5HCA1 (E)
(1) 500 kcmil Copper 17 ft, Magnetic
05_FB_87ATS (E)
SQUARE D KA
100AF 100AT 100AP
05_CBL_ATS-5HLA1 (E)
(1) 4/0 AWG Copper 20 ft, Magnetic
05_FB_ATS-5HLA1 (E)
SQUARE D KA
250AF 225AT 225AP
05_FB_ATS-11HCC1 (E)
SQUARE D LH
400AF 400AT 400AP
05_CBL_ATS-11HCC1 (E)
(1) 600 kcmil Copper 25 ft, Magnetic
05_FB_ATS-5HEA1 (E)
SQUARE D LA
400AF 400AT 400AP
05_CBL_ATS-5HEA1 (E)
(1) 500 kcmil Copper 15 ft, Magnetic
05_CBL_T-5A (SEC)
(5) 500 kcmil Copper 50 ft, Magnetic
05_MB_5HNA1
SQUARE D DS 420
2000AF 2000AT 2000AP
05_FB_MCC-5HNA1
SQUARE D ME
250AF 250AT 250AP
05_CBL_MCC-5HNA1
(1) 3/0 AWG Copper 30 ft, Magnetic
05_PB_MCC-5HNA1
Bldg: 05, Rm: C152 480 V 3P 22308.30 A
05_FD_CHILLER 1
Bldg: 05, Rm: C152 480 V 3P 21166.25 A
05_CBL_CHILLER 1
(1) 400 kcmil Copper 55 ft, Magnetic
05_FB_CHILLER 1
SQUARE D ME
400AF 400AT 400AP
05_FF_CHILLER 1
BUSSMANN LPS-RK
400AF 400AT
05_CBL_CHILLER 1 MO
(1) 400 kcmil Copper 10 ft, Magnetic
05_CC_CHILLER 1
Bldg: 05, OUTSIDE 480 V 3P 20354.62 A
05_MO_CHILLER 1
(1) @125 hp
05_CBL_ATS-5HEA1 (L)
(1) 500 kcmil Copper 40 ft, Magnetic
05_SP_ATS-5HEA1 (L)
Bldg: 05 - Outpatient Services, Rm: C153 480 V 3P 24137.79 A
05_AT_ATS-5HEA1
05_CBL_ATS-5HEA1 (N)
(1) 500 kcmil Copper 25 ft, Magnetic
05_FB_ATS-5HEA1 (N)
SQUARE D ME
400AF 400AT 400AP
05_FB_ATS-11HCC1 (N)
SQUARE D ME
400AF 400AT 400AP
05_CBL_ATS-11HCC1 (N)
(1) 600 kcmil Copper 35 ft, Magnetic
05_AT_ATS-11HCC1
05_SP_ATS-11HCC1 (L)
Bldg: 05, Rm: C153 480 V 3P 23049.66 A
11_CBL_11HCC1
(1) 4/0 AWG Copper 510 ft, Magnetic
11_MB_11HCC1
EATON CH HKD
100AF 100AT 100AP
11_PB_11HCC1
Bldg: 11, BLDG 9-11 480 V 3P 5397.75 A
11_FB_11XCC1
EATON FD
175AF 175AT 175AP
11_CBL_11XCC1 (PRI)
(1) 2/0 AWG Copper 5 ft, Magnetic
11_TX_11XCC1
112.5 kVA;
3.56%; 480 V / 208 V
11_CBL_11XCC1 (SEC)
(1) 4/0 AWG Copper 10 ft, Magnetic
11_CBL_11XATTIC(PRI)
(1) 1/0 AWG Copper 5 ft, Magnetic
11_NFD_11XATTIC(PRI)
Bldg: 11, ATTIC 480 V 3P 4795.50 A
11_CBL_11XDS
(1) 1/0 AWG Copper 50 ft, Magnetic
11_FB_11XATTIC
CUTLER-HAMMER GHB
100AF 100AT 100AP
05_FB_ELEV 5B
SQUARE D LA
150AF 125AT 125AP
05_CBL_DISC 5B
(1) 1 AWG Copper 275 ft, Non-Magnetic
05_FD_ELEV 5B
Bldg: 05, Rm: D138 480 V 3P 5300.51 A
05_FF_ELEV 5B
BUSSMANN FRS-R
125AF 125AT
05_CBL_ELEV 5B (PRI)
(1) 1 AWG Copper 7 ft, Magnetic
05_TX_ELEV 5B
75 kVA;
4.87%; 480 V / 208 V
05_CBL_ELEV 5B (SEC)
(1) 1/0 AWG Copper 7 ft, Magnetic
05_EB_ELEV 5B
Bldg: 05, Rm: D138 208 V 3P 4036.54 A
05_FB_EB ELEV 5B
SQUARE D HD
150AF 150AT 150AP
05_CBL_ELEV 5B
(1) 1/0 AWG Copper 5 ft, Magnetic
05_CC_ELEV 5B
Bldg: 05, BASEMENT 208 V 3P 3987.59 A
05_MO_ELEV 5B
(1) @50 hp
05_PB_5LEB1-1
Bldg: 05, Rm: C207 208 V 3P 829.73 A
05_CBL_5LEB1-1
(1) 2 AWG Copper 3 ft, Magnetic
05_FB_5LEB1-1
GE THQB
100AF 60AT 60AP
05_PB_5LEB1-2
Bldg: 05, Rm: C207 208 V 3P 833.34 A
05_MB_5LEB1-2
GE SFHA
250AF 225AT 225AP
05_CBL_5XEA1 (SEC)
(1) 6 AWG Copper 230 ft, Non-Magnetic
05_TX_5XEA1
50 kVA;
4.88%; 480 V / 208 V
05_CBL_5XEA1 (PRI)
(1) 4 AWG Copper 25 ft, Non-Magnetic
05_FB_5XEA1
SQUARE D KA
100AF 100AT 100AP
05_FB_5XEA3
SQUARE D FC
60AF 60AT 60AP
05_CBL_EQX
(1) 6 AWG Copper 25 ft, Magnetic
05_NFD_EQX
Bldg: 05, Rm: C153 480 V 3P 12517.45 A
05_CBL_5XEA3 (PRI)
(1) 6 AWG Copper 5 ft, Magnetic
05_TX_5XEA3
30 kVA;
4.58%; 480 V / 208 V
05_CBL_5LEA2
(1) 2 AWG Copper 5 ft, Magnetic
05_MB_5LEA2
SQUARE D QO
100AF 100AT 100AP
05_PB_5LEA2
Bldg: 05, Rm: C152 208 V 3P 1700.36 A
05_PB_5HEA1
Bldg: 05, Rm: C152 480 V 3P 20559.04 A
05_FB_ELEV 5A
SQUARE D LA
150AF 125AT 125AP
05_CBL_ELEV 5A
(1) 1 AWG Copper 280 ft, Magnetic
05_EB_ELEV 5A EB (PRI)
Bldg: 05, BASEMENT 480 V 3P 5095.88 A
05_FB_ELEV 5A EB (PRI)
SQUARE D FC
60AF 60AT 60AP
05_CBL_ELEV 5A (PRI)
(1) 1 AWG Copper 7 ft, Magnetic
05_TX_ELEV 5A
75 kVA;
5.10%; 480 V / 208 V
05_CBL_ELEV 5A EB (SEC)
(1) 1 AWG Copper 10 ft, Magnetic
05_EB_ELEV 5A EB (SEC)
Bldg: 05, BASEMENT 208 V 3P 3836.10 A
05_FB_ELEV 5A EB (SEC)
SQUARE D HD
150AF 150AT 150AP
05_CBL_ELEV 5A CC
(1) 1 AWG Copper 5 ft, Magnetic
05_CC_ELEV 5A
Bldg: 05, BASEMENT 208 V 3P 3785.31 A
05_MO_ELEV 5A
(1) @50 hp 11_PB_11LCB3
Bldg: 11, Rm: 226 208 V 3P 2212.95 A
11_MB_11LCB3
GE TQD
225AF 225AT 225AP
11_CBL_11LCB3
(1) 4/0 AWG Copper 5 ft, Magnetic
11_PB_11LCB2
Bldg: 11, Rm: 226 208 V 3P 2228.52 A
11_MB_11LCB2
GE TQD
225AF 225AT 225AP
11_CBL_11LCB2
(1) 4/0 AWG Copper 5 ft, Magnetic
11_PB_11LCB1
Bldg: 11, Rm: 226 208 V 3P 2244.30 A
11_MB_11LCB1
GE TQD
225AF 225AT 225AP
11_CBL_11XATTIC (SEC)
(1) 4/0 AWG Copper 160 ft, Magnetic
11_TX_11XCD1
75 kVA;
5.50%; 480 V / 208 V
05_FB_ATS-5HLA1 (N)
SQUARE D ME
250AF 250AT 250AP
05_CBL_ATS-5HLA1 (N)
(1) 4/0 AWG Copper 25 ft, Magnetic
05_AT_ATS-5HLA1
05_FB_11HLC1
SQUARE D HD
150AF 150AT 150AP
11_CBL_11HLC1
(1) 1/0 AWG Copper 400 ft, Magnetic
11_MB_11HLC1
EATON FD
150AF 150AT 150AP
11_PB_11HLC1
Bldg: 11, BLDG 9-11 480 V 3P 4175.83 A
11_FB_11XLC1
EATON FD
50AF 50AT 50AP
11_CBL_11XLC1 (PRI)
(1) 6 AWG Copper 10 ft, Magnetic
11_TX_11XLC1
30 kVA;
4.18%; 480 V / 208 V
11_CBL_11XLC1 (SEC)
(1) 2 AWG Copper 10 ft, Magnetic
11_MB_11LLC1
EATON FD
100AF 100AT 100AP
11_FB_15LLA1
EATON CH BAB
60AF 60AT 60AP
15_CBL_15LLA1
(1) 4 AWG Copper 205 ft, Magnetic
15_MB_15LLA1
SQUARE D QD
225AF 225AT 225AP
15_PB_15LLA1
Bldg: 15, ELEC CLOSET 208 V 3P 1062.04 A
11_PB_11LLA1
Bldg: 11, Rm: 101 208 V 3P 1594.59 A
11_MB_11LLA1
EATON FD
100AF 100AT 100AP
11_CBL_11LLA1
(1) 6 AWG Copper 30 ft, Magnetic
11_FB_11LLA1
EATON CH BAB
60AF 60AT 60AP
19_PB_19LLA1
Bldg: 19, CLEAN UTILITY 110 208 V 3P 776.61 A
19_MB_19LLA1
EATON PDD2_G
100AF 100AT 100AP
19_CBL_19LLA1
(1) 4 AWG Copper 350 ft, Magnetic
11_FB_19LLA1
EATON CH BAB
60AF 60AT 60AP
11_PB_11LLC1
Bldg: 11, BLDG 9-11 208 V 3P 1744.83 A
05_FB_5XLA1
SQUARE D FC
30AF 30AT 30AP
05_CBL_5XLA1 (PRI)
(1) 10 AWG Copper 20 ft, Magnetic
05_TX_5XLA1
15 kVA;
4.80%; 480 V / 208 V
05_CBL_5XLA1 (SEC)
(1) 6 AWG Copper 25 ft, Magnetic
05_MB_5LLA1
SQUARE D QO
60AF 60AT 60AP
05_PB_5LLA1
Bldg: 05, Rm: C152 208 V 3P 799.70 A
05_FB_5HLA1
SQUARE D FC
100AF 100AT 100AP
05_CBL_5HLA1 (2)
(1) 6 AWG Copper 370 ft, Magnetic
05_PB_5HLA1 (2)
Bldg: 05, Rm: C152 480 V 3P 1399.81 A
05_FB_5XLA2
CUTLER-HAMMER GHB
60AF 60AT 60AP
05_CBL_5XLA2 (PRI)
(1) 6 AWG Copper 20 ft, Magnetic
05_TX_5XLA2
30 kVA;
4.58%; 480 V / 208 V
05_CBL_5XLA2 (SEC)
(1) 2 AWG Copper 10 ft, Magnetic
05_MB_5LLA2
SQUARE D QO
100AF 100AT 100AP
05_PB_5LLA2
Bldg: 05, Rm: A141 208 V 3P 1273.58 A
05_PB_5LLA4
Bldg: 05, Rm: C110 208 V 3P 1608.33 A
05_MB_5LLA4
SQUARE D QO
90AF 90AT 90AP
05_CBL_5XLA4(SEC)
(1) 2 AWG Copper 10 ft, Non-Magnetic
05_TX_5XLA4
30 kVA;
4.58%; 480 V / 208 V
05_CBL_5XLA4 (PRI)
(1) 6 AWG Copper 10 ft, Magnetic
05_FB_5XLA4
SQUARE D EH
60AF 60AT 60AP
05_PB_5HLA3
Bldg: 05, Rm: C110 480 V 3P 6034.67 A
05_CBL_5HLA3
(1) 2 AWG Copper 170 ft, Magnetic
05_FB_5HLA3
SQUARE D FC
100AF 100AT 100AP
05_FB_5HLA2
SQUARE D FC
100AF 100AT 100AP
05_CBL_5HLA2
(1) 2 AWG Copper 240 ft, Magnetic
05_PB_5HLA2
Bldg: 05, Rm: B116 480 V 3P 4593.13 A
05_FB_5XLA3
CUTLER-HAMMER GHB
60AF 60AT 60AP
05_CBL_5XLA3 (PRI)
(1) 6 AWG Copper 10 ft, Magnetic
05_TX_5XLA3
30 kVA;
4.58%; 480 V / 208 V
05_CBL_5XLA3 (SEC)
(1) 2 AWG Copper 5 ft, Magnetic
05_PB_5LLA3
Bldg: 05, Rm: B116 208 V 3P 1581.35 A
05_PB_5LLA5
Bldg: 05, Rm: D145 208 V 3P 1633.04 A
05_MB_5LLA5
SQUARE D FA
100AF 100AT 100AP
05_CBL_5XLA5 (SEC)
(1) 2 AWG Copper 10 ft, Magnetic
05_TX_5XLA5
30 kVA;
4.58%; 480 V / 208 V
05_CBL_5XLA5 (PRI)
(1) 6 AWG Copper 10 ft, Magnetic
05_FB_5XLA5
CUTLER-HAMMER GHB
60AF 60AT 60AP
05_PB_5HLA4
Bldg: 05, Rm: D145 480 V 3P 4163.99 A
05_CBL_5HLA4
(1) 2 AWG Copper 270 ft, Magnetic
05_FB_5HLA4
SQUARE D FC
100AF 100AT 100AP
05_PB_5HLA1 (MAIN PB)
Bldg: 05, Rm: A141 480 V 3P 19892.73 A
05_CBL_ATS-5HLA1 (L)
(1) 4/0 AWG Copper 30 ft, Magnetic
05_SP_ATS-5HLA1 (L)
Bldg: 05, Rm: C153 480 V 3P 23378.82 A
87_CBL_87ATS EB (E)
(1) 2 AWG Copper 500 ft, Magnetic
87_EB_ATS EB (E)
Bldg: 87, CHILLER YARD 480 V 3P 0.00 A
87_FB_87ATS EB (E)
GE SELA
100AF 100AT 100AP
87_CBL_87ATS (E)
(1) 2 AWG Copper 4 ft, Magnetic
87_FB_87XNA1
GE SFLA
250AF 125AT 125AP
87_CBL_87XNA1 (PRI)
(1) 2 AWG Copper 8 ft, Magnetic
87_TX_87XNA1
75 kVA;
4.10%; 480 V / 208 V
87_CBL_87XNA1 (SEC)
(1) 4/0 AWG Copper 5 ft, Magnetic
87_MB_87LNA1
GE SFHA
250AF 225AT 225AP
87_PB_87LNA1
Bldg: 87, ELEC RM 208 V 3P 4185.37 A
87_CBL_87LNA2
(1) 4/0 AWG Copper 4 ft, Magnetic
87_PB_87LNA2
Bldg: 87, ELEC RM 208 V 3P 4146.06 A
87_CBL_87LNA3
(1) 4/0 AWG Copper 8 ft, Magnetic
87_PB_87LNA3
Bldg: 87, ELEC RM 208 V 3P 4069.18 A
87_FB_87HNA3
GE SFLA
250AF 225AT 225AP
87_CBL_87HNA3
(1) 2 AWG Copper 10 ft, Magnetic
87_MB_87HNA3
GE SFHA
250AF 225AT 225AP
87_PB_87HNA3
Bldg: 87, ELEC RM 480 V 3P 10893.61 A
87_FB_87XNA2
GE SFHA
250AF 225AT 225AP
87_CBL_87XNA2 (PRI)
(1) 1 AWG Copper 5 ft, Magnetic
87_TX_87XNA2
75 kVA;
4.10%; 480 V / 208 V
87_CBL_87XNA2 (SEC)
(1) 4/0 AWG Copper 5 ft, Magnetic
87_MB_87LNA4
GE SFHA
250AF 225AT 225AP
87_PB_87LNA4
Bldg: 87, ELEC RM 208 V 3P 4164.21 A
87_CBL_87LNA5
(1) 4/0 AWG Copper 5 ft, Magnetic
87_PB_87LNA5
Bldg: 87, ELEC RM 208 V 3P 4115.46 A
87_CBL_87LNA6
(1) 8 AWG Copper 8 ft, Magnetic
87_PB_87LNA6
Bldg: 87, ELEC RM 208 V 3P 3696.05 A
87_PB_87LLA1
Bldg: 87, ELEC RM 208 V 3P 1868.00 A
87_MB_87LLA1
GE SEPA
100AF 100AT 100AP
87_CBL_87XLA1 (SEC)
(1) 6 AWG Copper 5 ft, Magnetic
87_TX_87XLA1
30 kVA;
3.90%; 480 V / 208 V
87_CBL_87XLA1 (PRI)
(1) 6 AWG Copper 5 ft, Magnetic
87_FB_87XLA1
GE SEPA
50AF 50AT 50AP
87_PB_87LLA2
Bldg: 87, ELEC RM 208 V 3P 1750.46 A
87_MB_87LLA2
GE SEPA
100AF 100AT 100AP
87_CBL_87XLA2(SEC)
(1) 6 AWG Copper 5 ft, Magnetic
87_TX_87XLA2
30 kVA;
3.90%; 480 V / 208 V
87_CBL_87XLA2 (PRI)
(1) 8 AWG Copper 5 ft, Magnetic
87_FB_87XLA2
GE SEPA
50AF 50AT 50AP
87_PB_87HLA2
Bldg: 87, ELEC RM 480 V 3P 3915.56 A
87_CBL_87HLA2
(1) 6 AWG Copper 75 ft, Magnetic
87_FB_87HLA2
GE SEPA
60AF 60AT 60AP
87_PB_87HLA1
Bldg: 87, ELEC RM 480 V 3P 7537.90 A
87_MB_87HLA1
GE SEPA
100AF 100AT 100AP
87_CBL_87ATS (L)
(1) 2 AWG Copper 5 ft, Magnetic
87_SP_87ATS (L)
Bldg: 87, ELEC RM 480 V 3P 7725.04 A
87_AT_87ATS
87_CBL_87ATS (N)
(1) 2 AWG Copper 75 ft, Magnetic
87_FB_87ATS (N)
GE SELA
100AF 100AT 100AP
87_CBL_T-87 (SEC)
(2) 350 kcmil Copper 300 ft, Magnetic
87_MB_87HNA1
GE SGLA
600AF 500AT 500AP
87_PB_87HNA1
Bldg: 87, ELEC RM 480 V 3P 11488.19 A
87_FB_87HNA4
GE SFLA
250AF 225AT 225AP
87_CBL_87HNA4
(1) 4/0 AWG Copper 10 ft, Magnetic
87_MB_87HNA4
GE SFHA
250AF 225AT 225AP
87_PB_87HNA4
Bldg: 87, MECH RM 480 V 3P 11287.10 A
87_FB_AHU-2
GE TEY
80AF 80AT 80AP
87_CBL_AHU-2
(1) 4 AWG Copper 50 ft, Magnetic
87_NFD_AHU-2
Bldg: 87, Rm: AHU-2 480 V 3P 8762.23 A
87_FB_87XNA3
GE TEY
50AF 50AT 50AP
87_CBL_87XNA3 (PRI)
(1) 6 AWG Copper 5 ft, Magnetic
87_SP_87XNA3 (PRI)
Bldg: 87, MECH RM 480 V 3P 10702.08 A
87_TX_87XNA3
30 kVA;
3.90%; 480 V / 208 V
87_MO_AHU-2
(1) @301.6 hp
87_CBL_87XNA3 (SEC)
(1) 6 AWG Copper 5 ft, Magnetic
87_MB_87LNA7
GE SEPA
100AF 100AT 100AP
87_PB_87LNA7
Bldg: 87, MECH RM 208 V 3P 1926.31 A
05_CBL_5HCA1 (L)
(1) 500 kcmil Copper 35 ft, Magnetic
05_SP_5HCA1 (L)
Bldg: 05, Rm: C153 480 V 3P 24011.99 A
05_AT_5HCA1
05_CBL_5HCA1 (N)
(1) 500 kcmil Copper 25 ft, Magnetic
05_FB_ATS-5HCA1 (N)
SQUARE D ME
400AF 400AT 400AP
05_SB_5HNA1
Bldg: 05, Rm: C152 480 V 3P 27057.24 A
05_FB_5HNA2-1
SQUARE D PE
2000AF 2000AT 2000AP
05_CBL_5HNA2-1
(5) 500 kcmil Copper 20 ft, Magnetic
FROM TRANSFORMER T-87
TO 05_PB_5HCA1 (MAIN PB) TO 05_PB_5HNA2-1
05_FB_CHILLER 2
SQUARE D ME
400AF 400AT 400AP
05_CBL_CHILLER 2
(1) 400 kcmil Copper 80 ft, Magnetic
05_FD_CHILLER 2
Bldg: 05, OUTSIDE 480 V 3P 19245.12 A
05_FF_CHILLER 2
BUSSMANN LPS-RK
400AF 400AT
05_CBL_CHILLER 2 MO
(1) 400 kcmil Copper 10 ft, Magnetic
05_CC_CHILLER 2
Bldg: 05, OUTSIDE 480 V 3P 18571.54 A
05_MO_CHILLER 2
(1) @125 hp
11_MB_11LCC1
EATON CH DK
400AF 400AT 400AP
09_PB_9LCA1
Bldg: 09., Rm:142 208 V 3P 4368.44 A
09_CBL_9LCA1
(1) 1/0 AWG Copper 35 ft, Magnetic
11_FB_9LCA1
EATON FD
70AF 70AT 70AP
11_FB_15LCD1
EATON CH ED
150AF 150AT 150AP
15_CBL_15LCD1
(1) 1/0 AWG Copper 0 ft, Magnetic
15_MB_15LCD1
CUTLER-HAMMER FD
100AF 100AT 100AP
15_PB_15LCD1
Bldg: 15, ATTIC 208 V 3P 5104.60 A
15_FB_UNK 4 6G
EATON CH BAB
80AF 80AT 80AP
13_CBL_HWP
(1) 4 AWG Copper 0 ft, Magnetic
13_FB_HWP
EATON CH BAB
100AF 100AT 100AP
13_PB_13LCB1
Bldg: 13, Rm. 230 208 V 3P 2478.04 A
13_MB_13LCB1
EATON CH CAH
225AF 125AT 125AP
13_CBL_13LCB1
(1) 1/0 AWG Copper 200 ft, Magnetic
11_FB_13LCB1
EATON HFD
100AF 100AT 100AP
11_FB_13LCA1
EATON FD
70AF 70AT 70AP
13_CBL_13LCA1
(1) 1/0 AWG Copper 170 ft, Magnetic
13_PB_13LCA1
Bldg: 13, ELEV HALL 208 V 3P 2698.30 A
11_FB_15LCB1-1 AND 1-2
EATON EDB
225AF 225AT 225AP
15_CBL_15LCB1-1
(1) 300 kcmil Copper 390 ft, Magnetic
15_MB_15LCB1-1
SQUARE D QD
225AF 225AT 225AP
15_PB_15LCB1-1
Bldg: 15, ELEC CLOSET FL2 208 V 3P 2425.24 A
15_CBL_15LCB1-2
(1) 300 kcmil Copper 5 ft, Magnetic
15_PB_15LCB1-2
Bldg: 15, ELEC CLOSET FL2 208 V 3P 2408.89 A
17_PB_17LCA2
Bldg: 17, Rm:125 208 V 3P 1579.77 A
17_CBL_17LAC2
(1) 2 AWG Copper 20 ft, Magnetic
17_PB_17LCA1
Bldg: 17, CR100-17 208 V 3P 1667.56 A
17_CBL_17LAC1
(1) 1/0 AWG Copper 375 ft, Magnetic
11_FB_17LCA1
EATON EDB
100AF 100AT 100AP
11_FB_9LCB2
EATON EDB
225AF 225AT 225AP
09_CBL_9LCB2
(1) 4/0 AWG Copper 250 ft, Magnetic
09_MB_9LCB2
EATON EDB
225AF 225AT 225AP
09_PB_9LCB2
Bldg: 09, Rm: 235 208 V 3P 2801.75 A
15_PB_15LCA1
Bldg: 15, ELEC CLOSET FL1 208 V 3P 2072.72 A
15_CBL_15LCA1
(1) 2 AWG Copper 185 ft, Magnetic
11_FB_15LCA1
EATON HFD
100AF 100AT 100AP
11_PB_11LCC1
Bldg: 11, BLDG 9-11 208 V 3P 5106.96 A
S
P
100A/3P
PANELBOARD
'9LCA2'
100A
208/120V
3PH, 4W
10KAIC
DPM
SPD
30A/3P
PANELBOARD '9HLS1'
BLDG 9, RM 220,
225A, 480/277V, 3PH, 4W
22KAIC
225A/3P
CONTINUES
TO PANELBOARD
'11HEC1'
S
P
09-P-09A
09-P-09B
09-P-09C
DISCONNECT
'DISC-9LCA2'
30A/3P
XFMR 'TX-9LCA2'
15kVA 480-208/120V
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:5
:5
P
M
A u to d e s k D o c s /5
-2
-7
V
A G
A D u b lin E
H R
M T
A S
S /V
A D
U
G E
N S
H E
E T
S
E L
S
D B
.r v t
EP601
ONE-LINE DIAGRAM - EMERGENCY
POWER -
JPB/WNM BCL
CONSTRUCTION
DOCUMENT
06/14/2024
557-21-703RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA
KEY NOTES
GENERAL SHEET NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY
DISCREPANCIES FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30-DAYS
PRIOR TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
METERING NOTES
1 REFERENCE ASSOCIATED PANEL SCHEDULE FOR ADDITIONAL CIRCUITING
INFORMATION.
DEMOLISH (3) SINGLE-POLE 20A SPARE CIRCUIT BREAKERS TO MAKE ROOM FOR
INSTALLATION OF CIRCUIT BREAKER TO SERVE LOAD AS INDICATED. REPLACE
EXISTING DEADFRONT COVER SECTION(S) FOR CIRCUIT BREAKER INSTALLATION AS
REQUIRED.
PROVIDE CIRCUIT BREAKER IN EXISTING SPACE.
- NTS
1 ONE-LINE DIAGRAM - EMERGENCY POWER
EQUIPMENT HAS BEEN METERED DURING DESIGN PHASE. REFERENCE "EQUIPMENT
METERING AND LOAD INFORMATION SCHEDULE" ON SHEET E-703 FOR ADDITIONAL
LOADING INFORMATION.
Revisions: Date:
11_PB_11LNA3
Bldg: 11, Rm: 109 208 V 3P 2172.70 A
11_MB_11LNA3
SQUARE D QO
100AF 100AT 100AP
11_CBL_11LNA3
(1) 2 AWG Copper 210 ft, Magnetic
11_FB_11LNA3
EATON EDB
100AF 100AT 100AP
11_PB_11LNC1
Bldg: 11, CORR-BLDG 9-11 208 V 3P 7776.50 A
11_PB_11LNA2
Bldg: 11, Rm: 108 208 V 3P 2256.45 A
11_MB_11LNA2
SQUARE D QD
100AF 100AT 100AP
11_CBL_11LNA2
(1) 2 AWG Copper 200 ft, Magnetic
11_FB_11LNA2
EATON EDB
100AF 100AT 100AP
11_CBL_11LNB1 TAP
(1) 4/0 AWG Copper 4 ft, Magnetic
11_FB_11LNB1 ECB
GE SFHA
250AF 225AT 225AP
11_EB_11LNB1
Bldg: 11, CORR - BLDG 9-11 208 V 3P 7635.81 A
11_CBL_11LNB1
(1) 4/0 AWG Copper 160 ft, Magnetic
11_MB_11LNB1
GE TQD
225AF 225AT 225AP
11_PB_11LNB1
Bldg: 11, Rm: 226 208 V 3P 4315.40 A
11_CBL_11LNB2
(1) 4/0 AWG Copper 5 ft, Magnetic
11_MB_11LNB2
GE TQD
225AF 225AT 225AP
11_PB_11LNB2
Bldg: 11, Rm: 226 208 V 3P 4255.68 A
11_PB_11LNC2
Bldg: 11, Rm: BM101 208 V 3P 609.96 A
11_MB_11LNC2
EATON CH BAB
100AF 100AT 100AP
11_CBL_11LNC2
(1) 10 AWG Copper 160 ft, Magnetic
11_FB_11LNC2
EATON EDB
100AF 100AT 100AP
11_PB_11LNA1
Bldg: 11, Rm: 123 208 V 3P 4727.95 A
11_MB_11LNA1
SQUARE D QO
100AF 100AT 100AP
11_CBL_11LNA1
(1) 2 AWG Copper 60 ft, Magnetic
11_FB_11LNA1
EATON EDB
100AF 100AT 100AP
11_MB_11LNC1
SQUARE D LA
400AF 400AT 400AP
11_CBL_11LNC1
(1) 500 kcmil Copper 130 ft, Magnetic
03_FB_11LNC1
SQUARE D LA
400AF 400AT 400AP
03_PB_MS-3LNC1
Bldg: 03, Rm: BM116 208 V 3P 14225.53 A
03_FB_3LNA1
SQUARE D KA
250AF 225AT 225AP
03_CBL_3LNA1
(1) 3/0 AWG Copper 90 ft, Magnetic
03_MB_3LNA1
SQUARE D QD
225AF 225AT 225AP
03_PB_3LNA1
Bldg: 03, Rm: 117 208 V 3P 7527.31 A
41_PB_CE-3
Bldg. 41, Rm. 104-41 208 V 3P 8154.31 A
41_MB_CE-3
SIEMENS BLH
100AF 100AT 100AP
41_CBL_CE-3
(1) 2 AWG Copper 40 ft, Magnetic
03_FB_CE-3
SQUARE D KA
100AF 100AT 100AP
03_FB_3LNC7
SQUARE D MX
400AF 400AT 400AP
03_CBL_3LNC7
(2) 4/0 AWG Copper 45 ft, Magnetic
03_MB_3LNC7
EATON CH DK
400AF 400AT 400AP
03_PB_3LNC7
Bldg: 03, CRB100 208 V 3P 12049.38 A
03_FB_3LNC9
EATON CH BAB
100AF 100AT 100AP
03_CBL_3LNC9
(1) 2 AWG Copper 140 ft, Magnetic
03_MB_3LNC9
CUTLER-HAMMER FD
100AF 100AT 100AP
03_PB_3LNC9
Bldg: 03, Rm: BM110A 208 V 3P 3295.44 A
03_PB_3LNC8
Bldg: 03, Rm: BM109 208 V 3P 3119.42 A
03_MB_3LNC8
CUTLER-HAMMER FD
100AF 100AT 100AP
03_CBL_3LNC8
(1) 2 AWG Copper 150 ft, Magnetic
03_FB_3LNC8
EATON CH BAB
100AF 100AT 100AP
03_FB_3LNA2
SQUARE D KA
250AF 200AT 200AP
03_MB_3LNC1
EATON CH MDL
800AF 800AT 800AP
03_CBL_3LNC1
(2) 1/0 AWG Copper 35 ft, Magnetic
03_FB_3LNC1
SQUARE D MX
800AF 800AT 800AP
03_MB_MS-3LNC1
SQUARE D NE
1200AF 1200AT 600AP
03_CBL_T-3 (SEC)
(3) 350 kcmil Copper 30 ft, Magnetic
03_FB_3LNC2 (PNL CMPA)
SQUARE D FA
100AF 100AT 100AP
03_CBL_3LNC2 (CMPA)
(1) 6 AWG Copper 40 ft, Magnetic
03_MB_3LNC2 (CMPA)
SIEMENS BQH
100AF 100AT 100AP
03_PB_3LNC2 (CMPA)
Bldg: 03, CRB100 208 V 3P 4775.24 A
03_FB_UNLABELED BOTTOM
SQUARE D HJ
150AF 150AT 150AP
03_FB_9LNA1
SQUARE D LX / LXI
400AF 400AT 400AP
09_CBL_9LNA1
(1) 500 kcmil Copper 160 ft, Magnetic
09_MB_9LNA1
SIEMENS JXD6-A
400AF 400AT 400AP
09_PB_9LNA4
Bldg: 09, CR12-9 208 V 3P 4117.61 A
09_CBL_9LNA4
(1) 4/0 AWG Copper 160 ft, Magnetic
09_FB_9LNA4
SIEMENS QJ
225AF 225AT 225AP
09_PB_9LNA1
Bldg: 09, Rm: 142 208 V 3P 7032.12 A
09_PB_9LNA2
Bldg: 09, Rm: 142 208 V 3P 6084.39 A
09_MB_9LNA2
SIEMENS BL
100AF 100AT 100AP
09_CBL_9LNA2
(1) 2 AWG Copper 18 ft, Magnetic
09_FB_9LNA2
SIEMENS BQD
100AF 100AT 100AP
09_PB_9LNA3
Bldg: 09, Rm: 126 208 V 3P 2373.22 A
09_MB_9LNA3
SIEMENS BL
100AF 100AT 100AP
09_CBL_9LNA3
(1) 2 AWG Copper 180 ft, Magnetic
09_FB_9LNA3
SIEMENS BQD
100AF 100AT 100AP
03_SB_3LNC1
Bldg: 03, Rm: BM116 208 V 3P 11847.42 A
03_FB_3LNC5
EATON EDB
225AF 225AT 225AP
03_CBL_3LNC5
(1) 4 AWG Copper 140 ft, Magnetic
03_MB_3LNC5
EATON EDB
225AF 225AT 225AP
03_PB_3LNC5
Bldg: 03, Rm: BM110A 208 V 3P 2282.83 A
03_PB_3LNC3
Bldg: 03, CRB100 208 V 3P 8996.61 A
03_CBL_3LNC3
(1) 2 AWG Copper 20 ft, Magnetic
03_FB_3LNC3
EATON CH HFD
100AF 100AT 100AP
03_PB_3LNB2
Bldg: 03, Rm: 213B 208 V 3P 1767.17 A
03_MB_3LNB2
CUTLER-HAMMER FD
100AF 100AT 100AP
03_CBL_3LNB2
(1) 6 AWG Copper 120 ft, Magnetic
03_FB_3LNB2
CUTLER-HAMMER FD
100AF 100AT 100AP
03_FB_3LNB1
EATON CH EDB
225AF 225AT 225AP
03_CBL_3LNB1
(1) 4/0 AWG Copper 115 ft, Magnetic
03_MB_3LNB1
EATON EDB
225AF 225AT 225AP
03_PB_3LNB1
Bldg: 03, CR21-3 208 V 3P 6330.90 A
03_PB_3LNC4
Bldg: 03, Rm: BM110A 208 V 3P 3240.01 A
03_MB_3LNC4
CUTLER-HAMMER FD
100AF 100AT 100AP
03_CBL_3LNC4
(1) 2 AWG Copper 140 ft, Magnetic
03_FB_3LNC4
EATON CH HFD
100AF 100AT 100AP
03_PB_3LNC6
Bldg: 03, Rm: BM110A 208 V 3P 3240.01 A
03_MB_3LNC6
CUTLER-HAMMER FD
100AF 100AT 100AP
03_CBL_3LNC6
(1) 2 AWG Copper 140 ft, Magnetic
03_FB_3LNC6
EATON CH HFD
100AF 100AT 100AP
11_PB_11LNA3
Bldg: 11, Rm: 109 208 V 3P 2172.70 A
11_MB_11LNA3
SQUARE D QO
100AF 100AT 100AP
11_CBL_11LNA3
(1) 2 AWG Copper 210 ft, Magnetic
11_FB_11LNA3
EATON EDB
100AF 100AT 100AP
11_PB_11LNC1
Bldg: 11, CORR-BLDG 9-11 208 V 3P 7776.50 A
11_PB_11LNA2
Bldg: 11, Rm: 108 208 V 3P 2256.45 A
11_MB_11LNA2
SQUARE D QD
100AF 100AT 100AP
11_CBL_11LNA2
(1) 2 AWG Copper 200 ft, Magnetic
11_FB_11LNA2
EATON EDB
100AF 100AT 100AP
11_CBL_11LNB1 TAP
(1) 4/0 AWG Copper 4 ft, Magnetic
11_FB_11LNB1 ECB
GE SFHA
250AF 225AT 225AP
11_EB_11LNB1
Bldg: 11, CORR - BLDG 9-11 208 V 3P 7635.81 A
11_CBL_11LNB1
(1) 4/0 AWG Copper 160 ft, Magnetic
11_MB_11LNB1
GE TQD
225AF 225AT 225AP
11_PB_11LNB1
Bldg: 11, Rm: 226 208 V 3P 4315.40 A
11_CBL_11LNB2
(1) 4/0 AWG Copper 5 ft, Magnetic
11_MB_11LNB2
GE TQD
225AF 225AT 225AP
11_PB_11LNB2
Bldg: 11, Rm: 226 208 V 3P 4255.68 A
11_PB_11LNC2
Bldg: 11, Rm: BM101 208 V 3P 609.96 A
11_MB_11LNC2
EATON CH BAB
100AF 100AT 100AP
11_CBL_11LNC2
(1) 10 AWG Copper 160 ft, Magnetic
11_FB_11LNC2
EATON EDB
100AF 100AT 100AP
11_PB_11LNA1
Bldg: 11, Rm: 123 208 V 3P 4727.95 A
11_MB_11LNA1
SQUARE D QO
100AF 100AT 100AP
11_CBL_11LNA1
(1) 2 AWG Copper 60 ft, Magnetic
11_FB_11LNA1
EATON EDB
100AF 100AT 100AP
11_MB_11LNC1
SQUARE D LA
400AF 400AT 400AP
11_CBL_11LNC1
(1) 500 kcmil Copper 130 ft, Magnetic
03_FB_11LNC1
SQUARE D LA
400AF 400AT 400AP
03_PB_MS-3LNC1
Bldg: 03, Rm: BM116 208 V 3P 14225.53 A
03_FB_3LNA1
SQUARE D KA
250AF 225AT 225AP
03_CBL_3LNA1
(1) 3/0 AWG Copper 90 ft, Magnetic
03_MB_3LNA1
SQUARE D QD
225AF 225AT 225AP
03_PB_3LNA1
Bldg: 03, Rm: 117 208 V 3P 7527.31 A
41_PB_CE-3
Bldg. 41, Rm. 104-41 208 V 3P 8154.31 A
41_MB_CE-3
SIEMENS BLH
100AF 100AT 100AP
41_CBL_CE-3
(1) 2 AWG Copper 40 ft, Magnetic
03_FB_CE-3
SQUARE D KA
100AF 100AT 100AP
03_FB_3LNC7
SQUARE D MX
400AF 400AT 400AP
03_CBL_3LNC7
(2) 4/0 AWG Copper 45 ft, Magnetic
03_MB_3LNC7
EATON CH DK
400AF 400AT 400AP
03_PB_3LNC7
Bldg: 03, CRB100 208 V 3P 12049.38 A
03_FB_3LNC9
EATON CH BAB
100AF 100AT 100AP
03_CBL_3LNC9
(1) 2 AWG Copper 140 ft, Magnetic
03_MB_3LNC9
CUTLER-HAMMER FD
100AF 100AT 100AP
03_PB_3LNC9
Bldg: 03, Rm: BM110A 208 V 3P 3295.44 A
03_PB_3LNC8
Bldg: 03, Rm: BM109 208 V 3P 3119.42 A
03_MB_3LNC8
CUTLER-HAMMER FD
100AF 100AT 100AP
03_CBL_3LNC8
(1) 2 AWG Copper 150 ft, Magnetic
03_FB_3LNC8
EATON CH BAB
100AF 100AT 100AP
03_FB_3LNA2
SQUARE D KA
250AF 200AT 200AP
03_MB_3LNC1
EATON CH MDL
800AF 800AT 800AP
03_CBL_3LNC1
(2) 1/0 AWG Copper 35 ft, Magnetic
03_FB_3LNC1
SQUARE D MX
800AF 800AT 800AP
03_MB_MS-3LNC1
SQUARE D NE
1200AF 1200AT 600AP
03_CBL_T-3 (SEC)
(3) 350 kcmil Copper 30 ft, Magnetic
03_FB_3LNC2 (PNL CMPA)
SQUARE D FA
100AF 100AT 100AP
03_CBL_3LNC2 (CMPA)
(1) 6 AWG Copper 40 ft, Magnetic
03_MB_3LNC2 (CMPA)
SIEMENS BQH
100AF 100AT 100AP
03_PB_3LNC2 (CMPA)
Bldg: 03, CRB100 208 V 3P 4775.24 A
03_FB_UNLABELED BOTTOM
SQUARE D HJ
150AF 150AT 150AP
03_FB_9LNA1
SQUARE D LX / LXI
400AF 400AT 400AP
09_MB_9LNA1
SIEMENS JXD6-A
400AF 400AT 400AP
09_FB_9LNA4
SIEMENS QJ
225AF 225AT 225AP
09_PB_9LNA1
Bldg: 09, Rm: 142 208 V
09_PB_9LNA2
Bldg: 09, Rm: 142 208 V 3P 6084.39 A
09_MB_9LNA2
SIEMENS BL
100AF 100AT 100AP
09_FB_9LNA2
SIEMENS BQD
100AF 100AT 100AP
09_FB_9LNA3
SIEMENS BQD
100AF 100AT 100AP
03_SB_3LNC1
Bldg: 03, Rm: BM116 208 V 3P 11847.42 A
03_FB_3LNC5
EATON EDB
225AF 225AT 225AP
03_CBL_3LNC5
(1) 4 AWG Copper 140 ft, Magnetic
03_MB_3LNC5
EATON EDB
225AF 225AT 225AP
03_PB_3LNC5
Bldg: 03, Rm: BM110A 208 V 3P 2282.83 A
03_PB_3LNC3
Bldg: 03, CRB100 208 V 3P 8996.61 A
03_CBL_3LNC3
(1) 2 AWG Copper 20 ft, Magnetic
03_FB_3LNC3
EATON CH HFD
100AF 100AT 100AP
03_PB_3LNB2
Bldg: 03, Rm: 213B 208 V 3P 1767.17 A
03_MB_3LNB2
CUTLER-HAMMER FD
100AF 100AT 100AP
03_CBL_3LNB2
(1) 6 AWG Copper 120 ft, Magnetic
03_FB_3LNB2
CUTLER-HAMMER FD
100AF 100AT 100AP
03_FB_3LNB1
EATON CH EDB
225AF 225AT 225AP
03_CBL_3LNB1
(1) 4/0 AWG Copper 115 ft, Magnetic
03_MB_3LNB1
EATON EDB
225AF 225AT 225AP
03_PB_3LNB1
Bldg: 03, CR21-3 208 V 3P 6330.90 A
03_PB_3LNC4
Bldg: 03, Rm: BM110A 208 V 3P 3240.01 A
03_MB_3LNC4
CUTLER-HAMMER FD
100AF 100AT 100AP
03_CBL_3LNC4
(1) 2 AWG Copper 140 ft, Magnetic
03_FB_3LNC4
EATON CH HFD
100AF 100AT 100AP
03_PB_3LNC6
Bldg: 03, Rm: BM110A 208 V 3P 3240.01 A
03_MB_3LNC6
CUTLER-HAMMER FD
100AF 100AT 100AP
03_CBL_3LNC6
(1) 2 AWG Copper 140 ft, Magnetic
03_FB_3LNC6
EATON CH HFD
100AF 100AT 100AP
CONTINUED FROM
MEDIUM VOLTAGE EQUIPMENT
00_TX_TB-3
300 kVA;
4.96%; 4160 V / 208 V
3P SPACE 3P SPACE
400A/3P
400A/3P
100A 3P
PANELBOARD
'9LNA5'
400A, 208/120V, 3PH, 4W
42KAIC
225A 3P
PANELBOARD
'9LNA7'
100A
208/120V
3PH, 4W
22kAIC
PANELBOARD
'9LNA6'
225A
208/120V
3PH, 4W
22kAIC
60A/3P
HACR
VFD
PNL
'9LNA3'
225AF, 100AT
208/120V
3PH, 4W
22kAIC
PNL
'9LNA4'
225A
208/120V
3PH, 4W
22kAIC
SPD
DPM
SPD
DPM
09-P-0309-P-0209-P-08
09-P-06 09-P-05
09-P-07
09-P-0409-P-01
SPD
DPM
SPD
DPM
CONTINUED FROM
MEDIUM VOLTAGE EQUIPMENT
00_TX_TB-3
300 kVA;
4.96%; 4160 V / 208 V
DPM SPD
30A 3P
30A 3P
3P SPACE
AIR HANDLING UNIT
"009A-AHU-1"
28FLA, 208V, 3PH
4 4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:5
:5
P
M
A u to d e s k D o c s /5
-2
-7
V
A G
A D u b lin E
H R
M T
A S
S /V
A D
U
G E
N S
H E
E T
S
E L
S
D B
.r v t
EP602
ONE-LINE DIAGRAM - NORMAL
POWER -
JPB/WNM BCL
CONSTRUCTION
DOCUMENT
06/14/2024
557-21-703RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA
- NTS
1 ONE-LINE DIAGRAM - NORMAL POWER - DEMOLITION
KEY NOTES
GENERAL SHEET NOTES
1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY
DISCREPANCIES FOUND SHALL BE REPORTED TO THE ENGINEER.
2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,
AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO
COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30-DAYS
PRIOR TO IMPLEMENTATION.
3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.
METERING NOTES
1 EXISTING PANELBOARD TO BE RELOCATED. DEMOLISH AND REPLACE EXISTING
FEEDER AS REQUIRED TO REVISED PANELBOARD LOCATION; IDENTIFY, PRESERVE,
AND EXTEND BRANCH CIRCUITS TO REVISED PANELBOARD LOCATION. PROVIDE
JUNCTION BOX(ES) SIZED PER NEC AND SPLICING AS REQUIRED. REFERENCE
SHEETS ED102 AND EP101 FOR ADDITIONAL INFORMATION.
EXISTING PANELBOARD AND ASSOCIATED FEEDER TO BE DEMOLISHED. IDENTIFY
AND PRESERVE BRANCH CIRCUITS TO BE EXTENDED TO REPLACEMENT PANEL
LOCATION. SEE SHEET EP100 AND EP101 FOR FEEDER ROUTING AND PANEL
LOCATIONS.
PROVIDE CIRCUIT BREAKER IN EXISTING PANELBOARD 3P SPACE TO SERVE LOAD AS
INDICATED.
REFERENCE ASSOCIATED PANEL SCHEDULE FOR ADDITIONAL CIRCUITING
INFORMATION.
MECHANICAL UNIT SHALL BE PROVIDED WITH INTEGRAL STARTER AND DISCONNECT;
ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE POINT CONNECTION.
REPLACEMENT PANEL. EXTEND EXISTING BRANCH CIRCUIT CONDUCTORS AND
RACEWAYS TO REPLACEMENT PANELBOARD; PROVIDE PULLBOXES AND SPLICES AS
REQUIRED. REFERENCE SHEETS ED102, EP100, AND EP101 FOR ADDITIONAL
INFORMATION.
- NTS
2 ONE-LINE DIAGRAM - NORMAL POWER - REVISED
EQUIPMENT HAS BEEN METERED DURING DESIGN PHASE. REFERENCE
"EQUIPMENT METERING AND LOAD INFORMATION SCHEDULE" ON SHEET E-703
FOR ADDITIONAL LOADING INFORMATION.
Revisions: Date:
FIBER OPTIC
PATCH PANEL
TR
RACK
RM TR 220
LEVEL 02
LEVEL 01
CONTINUE TO CAMPUS
DATA CENTER
FIBER OPTIC
PATCH PANEL
TR
RACK
RM TR 100
JUNCTION BOX
"JB-TR100"
BUILDING 09A
CRAWL SPACE
LEVEL 01
LEVEL 02
TR 100
PBB
SWITCHBOARD
"MS-3LNC1"
BUILDING 03
TYP.
9 3
TYP.
TR 220
LEVEL 00
BM116-3
BUILDING 09A
TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
ENGINEERING DISCIPLINE:
SPEES DESIGN BUILD
23830 PACIFIC HIGHWAY S. SUITE 203
KENT, WA 98032
(206) 590-2118
RAY SPEES
/1
/2
:5
:5
P
M
A u to d e s k D o c s /5
-2
-7
V
A G
A D u b lin E
H R
M T
A S
S /V
A D
U
G E
N S
H E
E T
S
E L
S
D B
.r v t
ET601
JPB/WNM BCL
CONSTRUCTION
DOCUMENT
06/14/2024
557-21-703RENOVATE BUILDING 9A FOR
EHRM ADMINISTRATIVE SPACE
CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA
FIBER RISER AND
TELECOMMUNICATIONS BONDING
DIAGRAM
GENERAL NOTES
KEY NOTES
1. PRIOR TO CONSTRUCTION, COORDINATE VA STAFF AND OIT FOR PHASING AND
TELECOMMUNICATION SERVICE DISRUPTIONS. CONTRACTOR SHALL EXPECT WORK
TO BE AFTER HOURS.
2. NOT ALL EXISTING FIBER OPTIC TR CONNECTIONS ARE SHOWN FOR CLARITY.
CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS ON SITE.
3. ALL BONDING CONDUCTORS, INCLUDING TBB, SHALL FOLLOW SIZING
REQUIREMENTS SPECIFIED IN ANSI/TIA-607-D.
4. CONTRACTOR SHALL PROVIDE ALL REQUIRED BONDING, CONDUCTORS, AND
PATHWAYS AS REQUIRED. PROVIDE ALL PATCHING, REPAIR AND FIREPROOFING
FOR REMOVAL OF ALL EXISTING EQUIPMENT AND CONDUCTORS AS REQUIRED.
5. ALL BONDING CONDUCTORS SHALL BE COPPER AND BE INSULATED UNLESS
OTHERWISE NOTED.
- NTS
1 FIBER RISER DIAGRAM
PROVIDE FIBER OPTIC CABLING AS SHOWN. UTILIZE EXISTING PATHWAYS AND
SLEEVES AS REQUIRED. PROVIDE (1) 24-STRAND FIBER-OPTIC CABLE WITHIN 1''
INNERDUCT; COORDINATE WITH EXISTING FIBER TYPE AS NEEDED. REFERENCE
KEY NOTE '2' ON THIS SHEET FOR ADDITIONAL INFORMATION.
PROVIDE JUNCTION BOX INTERCEPT AND ROUTE TO TR RACK LOCATED IN TR 100.
IF EXISTING FIBER-OPTIC CABLE IS NOT LONG ENOUGH TO EXTEND TO TR 100,
PROVIDE FUSION SPLICE IN "JB-TR100" AND EXTEND TO TR 100 AS REQUIRED.
REFERENCE SHEET ET101 FOR ADDITIONAL INFORMATION.
PROVIDE PRIMARY BONDING BUSBAR (PBB). WHERE EXISTING PBB EXISTS,
CONTRACTOR SHALL REPLACE; CONTRACTOR TO FIELD VERIFY EXISTING
LOCATION. PROVIDE ALL BONDING CONNECTIONS AS REQUIRED.
PROVIDE TELECOMMUNICATIONS BONDING BACKBONE (TBB) CONDUCTOR AS
INDICATED. CONTRACTOR SHALL ROUTE AND PROVIDE ALL REQUIRED PATHWAYS
FOR TBB AS REQUIRED. EXISTING TBB SHALL BE DEMOLISHED AND REMOVED;
PROVIDE ALL PATCHING, REPAIR AND FIREPROOF SEALING AS REQUIRED.
PROVIDE IRREVERSIBLE CRIMP CONNECTOR, UL LISTED.
TELECOMMUNICATIONS ROOM. REFER TO ENLARGED FLOOR PLANS FOR
ADDITIONAL INFORMATION.
PROVIDE TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR (TEBC) TO
CONNECT THE TBB TO THE SBB. MINIMUM SIZE SHALL BE 6 AWG.
PROVIDE SECONDARY BONDING BUSBAR (SBB). PROVIDE TELECOMMUNICATIONS
EQUIPMENT BONDING CONDUCTOR TO BOND SBB TO THE FOLLOWING EQUIPMENT:
DATA RACK, CABLE TRAY, TR CONDUITS, ELECTRO-STATIC FLOORING, ELECTRICAL
PANEL, ETC. REFERENCE SHEET EP504 FOR ADDITIONAL BONDING INFORMATION.
PROVIDE TELECOMMUNICATIONS BONDING CONDUCTOR (TBC) TO BOND TO
BUILDING ELECTRICAL SERVICE EQUIPMENT GROUNDING BUSBAR. MINIMUM
CONDUCTOR SIZE SHALL BE 3 AWG.
EXISTING TELECOMMUNICATIONS BONDING BUSBAR. PROVIDE BOND TO
TELECOMMUNICATIONS BONDING BACKBONE AS REQUIRED.
- NTS
2 TELECOMMUNICATIONS BONDING RISER DIAGRAM
Revisions: Date: