S02-RFP Attachment 20-Drawings-Dublin_Part11.pdf

PDF 2 MB Posted

Attached to
Y1DZ--Renovate Building 9A for EHRM Administration- EHRM Project 557-21-703 Carl Vinson VA Medical Center Dublin, GA 31021
Solicitation number
36C77626R0031_1
Issued by

About this file

This document consists of electrical construction drawings and details for the renovation of Building 9A at Carl Vinson VA Medical Center in Dublin, Georgia (Project 557-21-703). The project scope involves renovating space for EHRM (Electronic Health Record Management) administrative functions. The drawings include electrical details, fire alarm systems, telecommunications infrastructure, power distribution, and security systems. Key specifications include installation of dual authentication card readers (HID pivCLASS #RK40 or equivalent) with keypads at 42 inches above finished floor, data racks with fiber distribution cabinets and Cat 6A patch panels, telecommunications rooms with bonding conductors and junction boxes, security door strike systems with electronic control, and fire alarm devices including heat detectors, smoke detectors, and wireless access points. The document references VA standards for telecommunications infrastructure (Version 3.1), requires seismic bracing kits for data racks, and mandates coordination with existing facility systems and the VA station.

The contractor must provide comprehensive shutdown plans, temporary power plans, and phasing plans for VA and engineer review 30 days prior to implementation. All equipment labeling must comply with VA infrastructure standards. The telecommunications bonding system requires primary bonding busbars, telecommunications bonding backbone conductors (minimum 3 AWG), and equipment bonding conductors (minimum 6 AWG) connected to secondary bonding busbars. Fiber optic cabling shall be 24-strand within one-inch innerduct, routed through existing pathways, with fusion splices provided as needed. The design includes extended cabling to new devices throughout the facility, coordination with existing Building 03 switchboard (MS-3LNC1), and preservation of existing detection devices for Building 9 Level 2 outside the renovation scope. General contractor responsibilities include field verification of existing conditions, provision of all required equipment and hardware, coordination with manufacturers and architects for complete system functionality, and proper patching and fireproofing of all construction penetrations.

View the file

Other files

File Type Posted
S05-Tech Questions w responses-Amendment 0006-Dublin.pdf PDF
S06- Addendum 2-Dublin - Specifications.pdf PDF
S06-Amendment 0006 SF 30-Dublin.pdf PDF
S06-Amendment 0005-SF30-Dublin.pdf PDF
S06-Amendment 0004-Addendum-1-Specifications.pdf PDF
S06-Amendment 0004-Addendum-1-Drawings.pdf PDF
S06 - Amendment 0004-Additional Technical Responses -Dublin.pdf PDF
S06-Amendment 0004-SF30.pdf PDF
S06- Amendment 0004-Technical Responses - Dublin.pdf PDF
S06-Amendment 0004- Addendum 1 - Hazardous Materials Survey.pdf PDF
S06-Amendment 0003-due date ext-Dub.pdf PDF
S04-Site Visit Sign In Sheet-Dublin.pdf PDF
S06-36C77626R0031-Amendment 0002.pdf PDF
S06-36C77626R0031-Amendment 0001.pdf PDF
S02-RFP Attachment 24-Specifications- Part 2 of 5 - Section 09 06 00.pdf PDF
S02-RFP Attachment 5- Specifications part 1 of 5.pdf PDF
S02-RFP Attachment 7- Specifications part 3 of 5.pdf PDF
S02-RFP Attachment 15-Drawings-Dublin_Part6.pdf PDF
S02-RFP Attachment 21-Drawings-Dublin_Part12.pdf PDF
S02-RFP Attachment 22-Drawings-Dublin_Part13.pdf PDF
S02 - RFP Attachment 3 - Limitations on Subcontracting - Dublin.docx DOCX document
S02-RFP Attachment 9- Specifications part 5 of 5.pdf PDF
S02-RFP Attachment 12-Drawings-Dublin_Part3.pdf PDF
S02-RFP Attachment 14-Drawings-Dublin_Part5.pdf PDF
S02-RFP Attachment 17-Drawings-Dublin_Part8.pdf PDF
S02-RFP Attachment 18-Drawings-Dublin_Part9.pdf PDF
S02-RFP Attachment 2 Site Visit Information-Dublin.docx DOCX document
S02-RFP Attachment 4 Campus Map-Dublin.pdf PDF
S02-RFP Attachment 8- Specifications part 4 of 5.pdf PDF
S02-RFP Attachment 10- Drawings-Dublin_Part1.pdf PDF
S02-RFP Attachment 11-Drawings-Dublin_Part2.pdf PDF
S02-RFP Attachment 23-Drawings-Dublin_Part14.pdf PDF
S02-36C77626R0031_1-final.pdf PDF
S02-RFP Attachment 1 DBA Rates-Laurens County-Dublin.pdf PDF
S02-RFP Attachment 6- Specifications part 2 of 5.pdf PDF
S02-RFP Attachment 13-Drawings-Dublin_Part4.pdf PDF
S02-RFP Attachment 16-Drawings-Dublin_Part7.pdf PDF
S02-RFP Attachment 19-Drawings-Dublin_Part10.pdf PDF
Show all 38

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CEILING STRUCTURE

THREADED ROD, DIAMETER

DEPENDENT ON J-HOOK SIZE

J-HOOK WITH COLORED ID, SIZE PER

CABLE CAPACITY, EATON B SERIES

COLORED J HOOK OR EQUIVALENT

CABLING PER PLAN

VELCRO CABLE TIE

J-HOOK COLORED ID, ID

COLOR SHALL MATCH VA

CABLING STANDARDS

18" MINIMUM

ACCESSIBLE CEILING

VARIES

DETAIL NOTES:

SPACE J-HOOKS MAXIMUM 4'

APART FROM ONE ANOTHER

FASTENER TO SUSPEND ROD

WIRING TABLE

PIGTAIL-

WIRE COLOR

TERM STRIP -

CONNECTION

CIRCUIT

FUNCTION

YELLOW

ORANGE

BLACK

RED

DRAIN

BROWN

BLUE

GRAY

PINK

GREEN

WHITE

VIOLET

TAN

RED/GREEN

P1-1

P1-2

P1-3

P1-4

P1-5

P1-6

P1-7

P2-1

P2-2

P2-3

P2-4

P2-5

P2-6

P2-7

NO CONNECT

NO CONNECT

RTN

+VDC

NO CONNECT

NO CONNECT

NO CONNECT

RS485 / TXA

RS485 / TXB

NO CONNECT

NO CONNECT

NO CONNECT

RS485 / RXB

RS485 / RXA

PIV ENABLED TWO-FACTOR AUTHENTICATION KEY PAD

AND CONTACTLESS AUTHENTICATION, HID pivCLASS

#RK40 OR EQUIVALENT

BEEP

GRN

RTN

+VDC

SHLD

RED

HOLD

GP101

GP102

OC/TMPR

DATA1

DATA0

GP103

GP104

JUNCTION BOX, 8" x 8" x 4"

MINIMUM

TO SECURE LOCAL

ACCESS CONTROL

PANEL, 1-1/2" CONDUIT

3/4" CONDUIT

ELECTRIC STRIKE / MORTISE LOCK

PER SYSTEM REQUIREMENTS,

PROVIDE BACKBOX AS REQUIRED

BY MANUFACTURER

DUAL AUTHENTICATION CARD

READER AND KEYPAD, 42" AFF,

HID pivCLASS #RK40 OR

EQUIVALENT, PROVIDE

BACKBOX AS REQUIRED BY

MANUFACTURER

SUSPENDED CEILING

FLOOR

120V POWER, 3/4" CONDUIT

REQUEST-TO-EXIT

WIRING, 3/4" CONDUIT

DOOR POSITION

SWITCH AND MAGNET

REQUEST-TO-EXIT

PIR MOTION SENSOR

REQUEST-TO-EXIT,

PUSH BUTTON

MOTION DETECTOR

DETAILS NOTES:

1. DETAIL IS SHOWN FOR GENERAL

DIAGRAMMATICAL PURPOSES. PROVIDE

ALL REQUIRED EQUIPMENT AND

HARDWARE FOR ALL DOOR TYPES

(SINGLE DOOR, DOUBLE DOOR, ETC.) AS

REQUIRED.

2. CONTRACTOR TO FURNISH AND INSTALL

ALL SECURITY AND PACS HARDWARE AS

REQUIRED PER PHYSICAL SECURITY AND

RESILIENCY DESIGN MANUAL AND

ASSOCIATED APPENDICES. COORDINATE

WITH ARCHITECT AND DOOR

MANUFACTURER TO PROVIDE A

COMPLETE AND FULLY FUNCTIONAL

ELECTRIFIED AND SECURED DOOR.

TYP

TYP

TYP

TYP

TYP

TYP

TYP

86"

BOTTOM 3RD SECTION

OF RACK IS

DESIGNATED TO

POWER DISTRIBUTION

EQUIPMENT.

REFERENCE

ELECTRICAL SHEET

EP502 FOR MORE

INFORMATION

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

BOTTOM 3RD SECTION

OF RACK IS

DESIGNATED TO

POWER DISTRIBUTION

EQUIPMENT.

REFERENCE

ELECTRICAL SHEET

EP502 FOR MORE

INFORMATION

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

37 38 39 40 41 42 43 44 45 46 47 4825 26 27 28 29 30 31 32 33 34 35 36

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:4

P

M

A u to d e s k D o c s /5

-2

-7

V

A G

A D u b lin E

H R

M T

A S

S /V

A D

U

G E

N S

H E

E T

S

E L

S

D B

.r v t

E-505

ELECTRICAL DETAILS

JPB/WNM BCL

CONSTRUCTION

DOCUMENT

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

GENERAL NOTES

KEY NOTES

NTS

TYPICAL J-HOOK INSTALLATION DETAIL

ET101

NTS

TYPICAL CONTACTLESS AUTHENTICATION AND PINPAD DEVICE DETAIL

E-402

DATA RACK, 4-POST, WHITE FINISH, ORTRONICS #MM2073038-W, OR

APPROVED EQUAL.

VERTICAL CABLE MANAGER WITH DOOR, 6" WIDE, ORTRONICS

#MM20VMD706, OR APPROVED EQUAL.

FIBER DISTRIBUTION CABINET, ANGLED, 1RU, LEVITON ANGLED OPT-X

UHDX, OR APPROVED EQUAL; CABINET POPULATED WITH (12) CASSETTES,

LEVITON HDX ENTERPRISE MTP, OR APPROVED EQUAL. SIDE-A AND SIDE-B

FIBER BACKBONE SHALL TERMINATE TO SEPARATE SIDES OF

DISTRIBUTION CABINET.

CAT 6A UTP PATCH PANEL, ANGLED, 24-PORT WITH REAR CABLE MANAGER,

LEVITON #E2XHD-BLK, OR APPROVED EQUAL.

BLANKING PANEL, 1RU, LEVITON, OR APPROVED EQUAL.

HORIZONTAL CABLE MANAGER, 1RU OR 2RU AS SHOWN, LEVITON, OR

APPROVED EQUAL.

NETWORK SWITCH. VA PROVIDED, CONTRACTOR INSTALLED.

COORDINATE WITH VA FOR EXACT REQUIREMENTS AS NECESSARY.

DUAL AUTHENTICATION CARD READER AND KEYPAD MUST BE CAPABLE OF

INTERFACING WITH EXISTING VA ACCESS CONTROL SYSTEM.

NTS

SECURITY DOOR CARD READER INSTALLATION DETAIL

ET101

E-402

1. ALL TELECOMMUNICATIONS ROOM (TR) DATA RACK DETAIL ELEVATIONS

ARE SHOWN TO PROVIDE GENERAL LAYOUT REQUIREMENTS. EXACT

QUANTITIES OF UTP PATCH PANELS AND NETWORK SWITCHES PER TR ARE

SHOWN IN THE TELECOMMUNICATIONS WAO AND CABLE TRAY SCHEDULE

LOCATED ON SHEET TN701. IF MORE THAN (1) RACK IS PRESENT IN THE TR

BEING EVALUATED, CONTRACTOR SHALL DIVIDE THE PATCH PANEL AND

NETWORK SWITCH EQUIPMENT EVENLY AMONG THE RACKS [IE: IF (6)

PATCH PANELS AND (6) NETWORK SWITCHES ARE REQUIRED IN A TR THAT

HAS (2) DATA RACKS, PROVIDE EACH DATA RACK WITH (3) PATCH PANELS

AND (3) NETWORK SWITCHES].

2. VA DATA RACKS FOLLOW A RULE OF THIRDS FOR POSITIONING EQUIPMENT

ON THE RACK. THE TOP THIRD IS DESIGNATED FOR FIBER AND UTP PATCH

EQUIPMENT, THE MIDDLE THIRD IS DESIGNATED FOR NETWORK SWITCH

EQUIPMENT, AND THE BOTTOM THIRD IS DESIGNATED FOR DATA RACK

POWER DISTRIBUTION EQUIPMENT.

3. PRIOR TO CONSTRUCTING TR DATA RACKS AND DURING THE SUBMITTAL

PROCESS, CONTRACTOR SHALL SUBMIT ALL TR DATA RACK ELEVATIONS

(FRONT, BACK, AND SIDE VIEWS) FOR ENGINEER AND VA REVIEW AND

APPROVAL. SUBMITTAL SHALL SHOW ALL DIMENSIONS, CABLE

MANAGEMENT EQUIPMENT, LABELING AND ASSOCIATED CUTSHEETS WITH

INDICATED PART NUMBERS AND OPTIONS FOR ALL EQUIPMENT.

4. CONTRACTOR SHALL LABEL EACH PATCH PANEL PORT WITH PORT NUMBER

AND ROOM NUMBER.

5. ALL DATA RACKS SHALL BE PROVIDED WITH SEISMIC BRACING KITS AND

INSTALLED PER MANUFACTURER'S INSTRUCTIONS.

6. ALL EQUIPMENT, CABLING, CONNECTORS AND APPURTENANCES SHALL BE

LABELED PER THE VA STANDARD "INFRASTRUCTURE STANDARD FOR

TELECOMMUNICATIONS SPACE" VERSION 3.1 OR NEWER.

7. WHERE RACK EQUIPMENT IS NOT REQUIRED FOR CABLING REQUIREMENTS

PROVIDE BLANKING PLATES IN ABSENT SPACES.

8. PROVIDE BLANKING PANELS IN ALL TR RACK VACANT SPACES IF NOT

NOTED OTHERWISE.

1 : 30

TR DATA RACK ELEVATION - TWO RACK

E-402

DETAIL IS GENERIC IN NATURE AND SHOWS GENERAL LAYOUT INFORMATION.

REFERENCE GENERAL AND KEY NOTES FOR SPECIFIC INFORMATION

Revisions: Date:

CONSTRUCTION

DOCUMENTS

15 in. (375 mm) min.

6 ft (1.8 m) max.

All switches, lamps and textual displays must be within range

FIRE

FIRE

FIRE

90 in.

(2.29 m) min.

Measured to the top of appliance

Heat Detector Ceiling mounted

6 in.

(150 mm) min.

Measured from each unit doorway from each floor

6 in.

(150 mm) min.

6 in.

(150 mm) min.

90 in.

(2.29 m) min.

Measured to the top of appliance

Smoke Detector Ceiling mounted

90 in.

(2.29 m) min.

Measured to the top of appliance

1'-6"

3'-6"

WIRELESS ACCESS POINT

CEILING MOUNTED

SECURITY HORN/SIREN

8'-0"

CARD READER

FIRE ALARM

STATION

DATA OUTLET

CEILING

EMERGENCY LIGHT

MOTION SENSOR

FINISHED

FLOOR LINE

SWITCH

EPO

EMERGENCY

STOP

BUTTON

BONDING BUSBAR

KEYPAD/CARD

ACCESS

ELECTRICAL PANEL

120VAC

EMERGENCY POWER

L

N

G INTEGRAL BATTERIES

NAC CIRCUIT

DATA

COMMUNICATION

TO CAMPUS FIRE

ALARM MASTER

PANEL

INPUT LOOP

FSFIRE ALARM

CONTROL PANEL

FIBER-OPTIC CABLING

EOL

CHANGE

MGMT

USER

COR

CR11-9

IV

TESTING

IV

TESTING

IV

TESTING

ELECT

ROOM

COR

CR11-9

IV

TESTING

COR

CR11-9

IV

SUPPORT

COR

CR11-9

COR

CR11-9

WAITING

ALCOVE

IV

TESTING

FS

WAITING

ALCOVE

IV

SUPPORT

IV

SUPPORT

COR

CR11-9

COR

CR11-9

COR

CR11-9

COR

CR11-9

COR

CR11-9

COR

CR11-9

COR

CR11-9

FS

WAITING

ALCOVE

COR

CR11-9

IV

TESTING

COR

CR11-9

COR

CR11-9

IV

TESTING

IV

SUPPORT

IV

TESTING

EXTEND EXISTING CABLING TO NEW DEVICES AS SHOWN, TYP.

MECH

MECH

101EXISTING FACP 'NOTIFIER' BY HONEYWELL. ALL

DETECTION AND SIGNALING DEVICES SHALL BE

COMPATIBLE WITH NOTIFIER SYSTEM.

EXTEND EXISTING CABLING TO NEW DEVICES AS SHOWN, TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:5

P

M

A u to d e s k D o c s /5

-2

-7

V

A G

A D u b lin E

H R

M T

A S

S /V

A D

U

G E

N S

H E

E T

S

E L

S

D B

.r v t

E-506

ELECTRICAL DETAILS

JPB/WNM BCL

CONSTRUCTION

DOCUMENT

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

- NTS

1 FIRE ALARM RISER DIAGRAM AND I/O MATRIX

- NTS

2 TYPICAL LOW-VOLTAGE EQUIPMENT MOUNTING HEIGHT DETAIL

DETAIL NOTES(S):

1. THESE TYPICAL MOUNTING HEIGHTS

SHALL BE USED UNLESS OTHERWISE

NOTED ON THE PLANS.

- 3/4" = 1'-0"

3 TYPICAL ELECTRICAL EQUIPMENT MOUNTING HEIGHT DETAIL

DETAIL NOTES(S):

1. REFERENCE SHEET ED103, EF101, & EF102 FOR EXACT DEVICE QUANTITIES AND LOCATIONS.

2. FIRE ALARM RISER DIAGRAM SHOWN FOR INFORMATIONAL PURPOSES ONLY. COORDINATE WITH EXISTING FACILITY

INFRASTRUCTURE, EQUIPMENT, NATIONAL/LOCAL CODES AND MANUFACTURE TO PROVIDE A COMPLETE AND FULLY

FUNCTIONAL SYSTEM AS REQUIRED.

3. PROVIDE FIRE ALARM DEVICES IN FIELD AS REQUIRED. COORDINATE FIELD CONNECTIONS WITH ALL EQUIPMENT;

PROVIDE CONNECTIONS, CABLING AND TERMINATIONS AS REQUIRED.

4. PROVIDE 3/4" CONDUIT FOR ALL NEW CABLE AS REQUIRED. ALL FIRE ALARM CONDUIT SHALL BE PAINTED RED.

5. PRESERVE ALL DETECTION AND INITIATING DEVICES FOR LEVEL 2 OF BUILDING 9 THAT IS OUTSIDE THE SCOPE OF WORK.

COORDINATE ANY SHUTDOWN OF FACP THAT WOULD AFFECT THESE AREAS WITH THE VA STATION AND COR PRIOR

TO BEGINNING WORK.

Revisions: Date:

09-P-10

CONTINUED FROM

MEDIUM VOLTAGE EQUIPMENT

00_TX_T-5A

1500kVA;

5.34%; 4160 V / 480 V

PANELBOARD

'9LCA3'

100A

208/120V

3PH, 4W

10KAIC

DPM

SPD

S

P

S

P

S

P

S

P

E N

87_FB_87HNA2

GE SFLA

250AF 225AT 225AP

87_CBL_87HNA2

(1) 4/0 AWG Copper 5 ft, Magnetic

87_MB_87HNA2

GE SEPA

100AF 100AT 100AP

87_PB_87HNA2

Bldg: 87, ELEC RM 480 V 3P 11325.54 A

S

P

S

P

S

P

S

P

S

P

E N

S

P S

P

S

P

S

P

E N

E N

S

P

S

P

S

P

05_PB_5LEA1

Bldg: 05, Rm: C152 208 V 3P 831.99 A

05_MB_5LEA1

SQUARE D QO

60AF 60AT 60AP

05_CBL_5XEA2 (SEC)

(1) 6 AWG Copper 7 ft, Magnetic

S

P 05_TX_5XEA2

15 kVA;

4.80%; 480 V / 208 V

S

P

05_CBL_5XEA2 (PRI)

(1) 10 AWG Copper 15 ft, Magnetic

05_FB_5XEA2

SQUARE D FC

30AF 30AT 30AP

E N

05_GN_GEN6

RatedVoltage 480 V Rated kW 360 kW Rated kVA 400 kVA

05_FB_GEN 6

CUTLER-HAMMER HMC

800AF 800AT 600AP

05_BS_GEN 6

Bldg: 05, Rm: C153 480 V 3P 0.00 A

05_CBL_5HGA1

(2) 350 kcmil Copper 15 ft, Magnetic

05_PB_5HGA1

Bldg: 05, Rm: C153 480 V 3P 0.00 A

05_FB_ATS-5HCA1 (E)

SQUARE D LH

400AF 400AT 400AP

05_CBL_5HCA1 (E)

(1) 500 kcmil Copper 17 ft, Magnetic

05_FB_87ATS (E)

SQUARE D KA

100AF 100AT 100AP

05_CBL_ATS-5HLA1 (E)

(1) 4/0 AWG Copper 20 ft, Magnetic

05_FB_ATS-5HLA1 (E)

SQUARE D KA

250AF 225AT 225AP

05_FB_ATS-11HCC1 (E)

SQUARE D LH

400AF 400AT 400AP

05_CBL_ATS-11HCC1 (E)

(1) 600 kcmil Copper 25 ft, Magnetic

05_FB_ATS-5HEA1 (E)

SQUARE D LA

400AF 400AT 400AP

05_CBL_ATS-5HEA1 (E)

(1) 500 kcmil Copper 15 ft, Magnetic

05_CBL_T-5A (SEC)

(5) 500 kcmil Copper 50 ft, Magnetic

05_MB_5HNA1

SQUARE D DS 420

2000AF 2000AT 2000AP

05_FB_MCC-5HNA1

SQUARE D ME

250AF 250AT 250AP

05_CBL_MCC-5HNA1

(1) 3/0 AWG Copper 30 ft, Magnetic

05_PB_MCC-5HNA1

Bldg: 05, Rm: C152 480 V 3P 22308.30 A

05_FD_CHILLER 1

Bldg: 05, Rm: C152 480 V 3P 21166.25 A

05_CBL_CHILLER 1

(1) 400 kcmil Copper 55 ft, Magnetic

05_FB_CHILLER 1

SQUARE D ME

400AF 400AT 400AP

05_FF_CHILLER 1

BUSSMANN LPS-RK

400AF 400AT

05_CBL_CHILLER 1 MO

(1) 400 kcmil Copper 10 ft, Magnetic

05_CC_CHILLER 1

Bldg: 05, OUTSIDE 480 V 3P 20354.62 A

05_MO_CHILLER 1

(1) @125 hp

05_CBL_ATS-5HEA1 (L)

(1) 500 kcmil Copper 40 ft, Magnetic

05_SP_ATS-5HEA1 (L)

Bldg: 05 - Outpatient Services, Rm: C153 480 V 3P 24137.79 A

05_AT_ATS-5HEA1

05_CBL_ATS-5HEA1 (N)

(1) 500 kcmil Copper 25 ft, Magnetic

05_FB_ATS-5HEA1 (N)

SQUARE D ME

400AF 400AT 400AP

05_FB_ATS-11HCC1 (N)

SQUARE D ME

400AF 400AT 400AP

05_CBL_ATS-11HCC1 (N)

(1) 600 kcmil Copper 35 ft, Magnetic

05_AT_ATS-11HCC1

05_SP_ATS-11HCC1 (L)

Bldg: 05, Rm: C153 480 V 3P 23049.66 A

11_CBL_11HCC1

(1) 4/0 AWG Copper 510 ft, Magnetic

11_MB_11HCC1

EATON CH HKD

100AF 100AT 100AP

11_PB_11HCC1

Bldg: 11, BLDG 9-11 480 V 3P 5397.75 A

11_FB_11XCC1

EATON FD

175AF 175AT 175AP

11_CBL_11XCC1 (PRI)

(1) 2/0 AWG Copper 5 ft, Magnetic

11_TX_11XCC1

112.5 kVA;

3.56%; 480 V / 208 V

11_CBL_11XCC1 (SEC)

(1) 4/0 AWG Copper 10 ft, Magnetic

11_CBL_11XATTIC(PRI)

(1) 1/0 AWG Copper 5 ft, Magnetic

11_NFD_11XATTIC(PRI)

Bldg: 11, ATTIC 480 V 3P 4795.50 A

11_CBL_11XDS

(1) 1/0 AWG Copper 50 ft, Magnetic

11_FB_11XATTIC

CUTLER-HAMMER GHB

100AF 100AT 100AP

05_FB_ELEV 5B

SQUARE D LA

150AF 125AT 125AP

05_CBL_DISC 5B

(1) 1 AWG Copper 275 ft, Non-Magnetic

05_FD_ELEV 5B

Bldg: 05, Rm: D138 480 V 3P 5300.51 A

05_FF_ELEV 5B

BUSSMANN FRS-R

125AF 125AT

05_CBL_ELEV 5B (PRI)

(1) 1 AWG Copper 7 ft, Magnetic

05_TX_ELEV 5B

75 kVA;

4.87%; 480 V / 208 V

05_CBL_ELEV 5B (SEC)

(1) 1/0 AWG Copper 7 ft, Magnetic

05_EB_ELEV 5B

Bldg: 05, Rm: D138 208 V 3P 4036.54 A

05_FB_EB ELEV 5B

SQUARE D HD

150AF 150AT 150AP

05_CBL_ELEV 5B

(1) 1/0 AWG Copper 5 ft, Magnetic

05_CC_ELEV 5B

Bldg: 05, BASEMENT 208 V 3P 3987.59 A

05_MO_ELEV 5B

(1) @50 hp

05_PB_5LEB1-1

Bldg: 05, Rm: C207 208 V 3P 829.73 A

05_CBL_5LEB1-1

(1) 2 AWG Copper 3 ft, Magnetic

05_FB_5LEB1-1

GE THQB

100AF 60AT 60AP

05_PB_5LEB1-2

Bldg: 05, Rm: C207 208 V 3P 833.34 A

05_MB_5LEB1-2

GE SFHA

250AF 225AT 225AP

05_CBL_5XEA1 (SEC)

(1) 6 AWG Copper 230 ft, Non-Magnetic

05_TX_5XEA1

50 kVA;

4.88%; 480 V / 208 V

05_CBL_5XEA1 (PRI)

(1) 4 AWG Copper 25 ft, Non-Magnetic

05_FB_5XEA1

SQUARE D KA

100AF 100AT 100AP

05_FB_5XEA3

SQUARE D FC

60AF 60AT 60AP

05_CBL_EQX

(1) 6 AWG Copper 25 ft, Magnetic

05_NFD_EQX

Bldg: 05, Rm: C153 480 V 3P 12517.45 A

05_CBL_5XEA3 (PRI)

(1) 6 AWG Copper 5 ft, Magnetic

05_TX_5XEA3

30 kVA;

4.58%; 480 V / 208 V

05_CBL_5LEA2

(1) 2 AWG Copper 5 ft, Magnetic

05_MB_5LEA2

SQUARE D QO

100AF 100AT 100AP

05_PB_5LEA2

Bldg: 05, Rm: C152 208 V 3P 1700.36 A

05_PB_5HEA1

Bldg: 05, Rm: C152 480 V 3P 20559.04 A

05_FB_ELEV 5A

SQUARE D LA

150AF 125AT 125AP

05_CBL_ELEV 5A

(1) 1 AWG Copper 280 ft, Magnetic

05_EB_ELEV 5A EB (PRI)

Bldg: 05, BASEMENT 480 V 3P 5095.88 A

05_FB_ELEV 5A EB (PRI)

SQUARE D FC

60AF 60AT 60AP

05_CBL_ELEV 5A (PRI)

(1) 1 AWG Copper 7 ft, Magnetic

05_TX_ELEV 5A

75 kVA;

5.10%; 480 V / 208 V

05_CBL_ELEV 5A EB (SEC)

(1) 1 AWG Copper 10 ft, Magnetic

05_EB_ELEV 5A EB (SEC)

Bldg: 05, BASEMENT 208 V 3P 3836.10 A

05_FB_ELEV 5A EB (SEC)

SQUARE D HD

150AF 150AT 150AP

05_CBL_ELEV 5A CC

(1) 1 AWG Copper 5 ft, Magnetic

05_CC_ELEV 5A

Bldg: 05, BASEMENT 208 V 3P 3785.31 A

05_MO_ELEV 5A

(1) @50 hp 11_PB_11LCB3

Bldg: 11, Rm: 226 208 V 3P 2212.95 A

11_MB_11LCB3

GE TQD

225AF 225AT 225AP

11_CBL_11LCB3

(1) 4/0 AWG Copper 5 ft, Magnetic

11_PB_11LCB2

Bldg: 11, Rm: 226 208 V 3P 2228.52 A

11_MB_11LCB2

GE TQD

225AF 225AT 225AP

11_CBL_11LCB2

(1) 4/0 AWG Copper 5 ft, Magnetic

11_PB_11LCB1

Bldg: 11, Rm: 226 208 V 3P 2244.30 A

11_MB_11LCB1

GE TQD

225AF 225AT 225AP

11_CBL_11XATTIC (SEC)

(1) 4/0 AWG Copper 160 ft, Magnetic

11_TX_11XCD1

75 kVA;

5.50%; 480 V / 208 V

05_FB_ATS-5HLA1 (N)

SQUARE D ME

250AF 250AT 250AP

05_CBL_ATS-5HLA1 (N)

(1) 4/0 AWG Copper 25 ft, Magnetic

05_AT_ATS-5HLA1

05_FB_11HLC1

SQUARE D HD

150AF 150AT 150AP

11_CBL_11HLC1

(1) 1/0 AWG Copper 400 ft, Magnetic

11_MB_11HLC1

EATON FD

150AF 150AT 150AP

11_PB_11HLC1

Bldg: 11, BLDG 9-11 480 V 3P 4175.83 A

11_FB_11XLC1

EATON FD

50AF 50AT 50AP

11_CBL_11XLC1 (PRI)

(1) 6 AWG Copper 10 ft, Magnetic

11_TX_11XLC1

30 kVA;

4.18%; 480 V / 208 V

11_CBL_11XLC1 (SEC)

(1) 2 AWG Copper 10 ft, Magnetic

11_MB_11LLC1

EATON FD

100AF 100AT 100AP

11_FB_15LLA1

EATON CH BAB

60AF 60AT 60AP

15_CBL_15LLA1

(1) 4 AWG Copper 205 ft, Magnetic

15_MB_15LLA1

SQUARE D QD

225AF 225AT 225AP

15_PB_15LLA1

Bldg: 15, ELEC CLOSET 208 V 3P 1062.04 A

11_PB_11LLA1

Bldg: 11, Rm: 101 208 V 3P 1594.59 A

11_MB_11LLA1

EATON FD

100AF 100AT 100AP

11_CBL_11LLA1

(1) 6 AWG Copper 30 ft, Magnetic

11_FB_11LLA1

EATON CH BAB

60AF 60AT 60AP

19_PB_19LLA1

Bldg: 19, CLEAN UTILITY 110 208 V 3P 776.61 A

19_MB_19LLA1

EATON PDD2_G

100AF 100AT 100AP

19_CBL_19LLA1

(1) 4 AWG Copper 350 ft, Magnetic

11_FB_19LLA1

EATON CH BAB

60AF 60AT 60AP

11_PB_11LLC1

Bldg: 11, BLDG 9-11 208 V 3P 1744.83 A

05_FB_5XLA1

SQUARE D FC

30AF 30AT 30AP

05_CBL_5XLA1 (PRI)

(1) 10 AWG Copper 20 ft, Magnetic

05_TX_5XLA1

15 kVA;

4.80%; 480 V / 208 V

05_CBL_5XLA1 (SEC)

(1) 6 AWG Copper 25 ft, Magnetic

05_MB_5LLA1

SQUARE D QO

60AF 60AT 60AP

05_PB_5LLA1

Bldg: 05, Rm: C152 208 V 3P 799.70 A

05_FB_5HLA1

SQUARE D FC

100AF 100AT 100AP

05_CBL_5HLA1 (2)

(1) 6 AWG Copper 370 ft, Magnetic

05_PB_5HLA1 (2)

Bldg: 05, Rm: C152 480 V 3P 1399.81 A

05_FB_5XLA2

CUTLER-HAMMER GHB

60AF 60AT 60AP

05_CBL_5XLA2 (PRI)

(1) 6 AWG Copper 20 ft, Magnetic

05_TX_5XLA2

30 kVA;

4.58%; 480 V / 208 V

05_CBL_5XLA2 (SEC)

(1) 2 AWG Copper 10 ft, Magnetic

05_MB_5LLA2

SQUARE D QO

100AF 100AT 100AP

05_PB_5LLA2

Bldg: 05, Rm: A141 208 V 3P 1273.58 A

05_PB_5LLA4

Bldg: 05, Rm: C110 208 V 3P 1608.33 A

05_MB_5LLA4

SQUARE D QO

90AF 90AT 90AP

05_CBL_5XLA4(SEC)

(1) 2 AWG Copper 10 ft, Non-Magnetic

05_TX_5XLA4

30 kVA;

4.58%; 480 V / 208 V

05_CBL_5XLA4 (PRI)

(1) 6 AWG Copper 10 ft, Magnetic

05_FB_5XLA4

SQUARE D EH

60AF 60AT 60AP

05_PB_5HLA3

Bldg: 05, Rm: C110 480 V 3P 6034.67 A

05_CBL_5HLA3

(1) 2 AWG Copper 170 ft, Magnetic

05_FB_5HLA3

SQUARE D FC

100AF 100AT 100AP

05_FB_5HLA2

SQUARE D FC

100AF 100AT 100AP

05_CBL_5HLA2

(1) 2 AWG Copper 240 ft, Magnetic

05_PB_5HLA2

Bldg: 05, Rm: B116 480 V 3P 4593.13 A

05_FB_5XLA3

CUTLER-HAMMER GHB

60AF 60AT 60AP

05_CBL_5XLA3 (PRI)

(1) 6 AWG Copper 10 ft, Magnetic

05_TX_5XLA3

30 kVA;

4.58%; 480 V / 208 V

05_CBL_5XLA3 (SEC)

(1) 2 AWG Copper 5 ft, Magnetic

05_PB_5LLA3

Bldg: 05, Rm: B116 208 V 3P 1581.35 A

05_PB_5LLA5

Bldg: 05, Rm: D145 208 V 3P 1633.04 A

05_MB_5LLA5

SQUARE D FA

100AF 100AT 100AP

05_CBL_5XLA5 (SEC)

(1) 2 AWG Copper 10 ft, Magnetic

05_TX_5XLA5

30 kVA;

4.58%; 480 V / 208 V

05_CBL_5XLA5 (PRI)

(1) 6 AWG Copper 10 ft, Magnetic

05_FB_5XLA5

CUTLER-HAMMER GHB

60AF 60AT 60AP

05_PB_5HLA4

Bldg: 05, Rm: D145 480 V 3P 4163.99 A

05_CBL_5HLA4

(1) 2 AWG Copper 270 ft, Magnetic

05_FB_5HLA4

SQUARE D FC

100AF 100AT 100AP

05_PB_5HLA1 (MAIN PB)

Bldg: 05, Rm: A141 480 V 3P 19892.73 A

05_CBL_ATS-5HLA1 (L)

(1) 4/0 AWG Copper 30 ft, Magnetic

05_SP_ATS-5HLA1 (L)

Bldg: 05, Rm: C153 480 V 3P 23378.82 A

87_CBL_87ATS EB (E)

(1) 2 AWG Copper 500 ft, Magnetic

87_EB_ATS EB (E)

Bldg: 87, CHILLER YARD 480 V 3P 0.00 A

87_FB_87ATS EB (E)

GE SELA

100AF 100AT 100AP

87_CBL_87ATS (E)

(1) 2 AWG Copper 4 ft, Magnetic

87_FB_87XNA1

GE SFLA

250AF 125AT 125AP

87_CBL_87XNA1 (PRI)

(1) 2 AWG Copper 8 ft, Magnetic

87_TX_87XNA1

75 kVA;

4.10%; 480 V / 208 V

87_CBL_87XNA1 (SEC)

(1) 4/0 AWG Copper 5 ft, Magnetic

87_MB_87LNA1

GE SFHA

250AF 225AT 225AP

87_PB_87LNA1

Bldg: 87, ELEC RM 208 V 3P 4185.37 A

87_CBL_87LNA2

(1) 4/0 AWG Copper 4 ft, Magnetic

87_PB_87LNA2

Bldg: 87, ELEC RM 208 V 3P 4146.06 A

87_CBL_87LNA3

(1) 4/0 AWG Copper 8 ft, Magnetic

87_PB_87LNA3

Bldg: 87, ELEC RM 208 V 3P 4069.18 A

87_FB_87HNA3

GE SFLA

250AF 225AT 225AP

87_CBL_87HNA3

(1) 2 AWG Copper 10 ft, Magnetic

87_MB_87HNA3

GE SFHA

250AF 225AT 225AP

87_PB_87HNA3

Bldg: 87, ELEC RM 480 V 3P 10893.61 A

87_FB_87XNA2

GE SFHA

250AF 225AT 225AP

87_CBL_87XNA2 (PRI)

(1) 1 AWG Copper 5 ft, Magnetic

87_TX_87XNA2

75 kVA;

4.10%; 480 V / 208 V

87_CBL_87XNA2 (SEC)

(1) 4/0 AWG Copper 5 ft, Magnetic

87_MB_87LNA4

GE SFHA

250AF 225AT 225AP

87_PB_87LNA4

Bldg: 87, ELEC RM 208 V 3P 4164.21 A

87_CBL_87LNA5

(1) 4/0 AWG Copper 5 ft, Magnetic

87_PB_87LNA5

Bldg: 87, ELEC RM 208 V 3P 4115.46 A

87_CBL_87LNA6

(1) 8 AWG Copper 8 ft, Magnetic

87_PB_87LNA6

Bldg: 87, ELEC RM 208 V 3P 3696.05 A

87_PB_87LLA1

Bldg: 87, ELEC RM 208 V 3P 1868.00 A

87_MB_87LLA1

GE SEPA

100AF 100AT 100AP

87_CBL_87XLA1 (SEC)

(1) 6 AWG Copper 5 ft, Magnetic

87_TX_87XLA1

30 kVA;

3.90%; 480 V / 208 V

87_CBL_87XLA1 (PRI)

(1) 6 AWG Copper 5 ft, Magnetic

87_FB_87XLA1

GE SEPA

50AF 50AT 50AP

87_PB_87LLA2

Bldg: 87, ELEC RM 208 V 3P 1750.46 A

87_MB_87LLA2

GE SEPA

100AF 100AT 100AP

87_CBL_87XLA2(SEC)

(1) 6 AWG Copper 5 ft, Magnetic

87_TX_87XLA2

30 kVA;

3.90%; 480 V / 208 V

87_CBL_87XLA2 (PRI)

(1) 8 AWG Copper 5 ft, Magnetic

87_FB_87XLA2

GE SEPA

50AF 50AT 50AP

87_PB_87HLA2

Bldg: 87, ELEC RM 480 V 3P 3915.56 A

87_CBL_87HLA2

(1) 6 AWG Copper 75 ft, Magnetic

87_FB_87HLA2

GE SEPA

60AF 60AT 60AP

87_PB_87HLA1

Bldg: 87, ELEC RM 480 V 3P 7537.90 A

87_MB_87HLA1

GE SEPA

100AF 100AT 100AP

87_CBL_87ATS (L)

(1) 2 AWG Copper 5 ft, Magnetic

87_SP_87ATS (L)

Bldg: 87, ELEC RM 480 V 3P 7725.04 A

87_AT_87ATS

87_CBL_87ATS (N)

(1) 2 AWG Copper 75 ft, Magnetic

87_FB_87ATS (N)

GE SELA

100AF 100AT 100AP

87_CBL_T-87 (SEC)

(2) 350 kcmil Copper 300 ft, Magnetic

87_MB_87HNA1

GE SGLA

600AF 500AT 500AP

87_PB_87HNA1

Bldg: 87, ELEC RM 480 V 3P 11488.19 A

87_FB_87HNA4

GE SFLA

250AF 225AT 225AP

87_CBL_87HNA4

(1) 4/0 AWG Copper 10 ft, Magnetic

87_MB_87HNA4

GE SFHA

250AF 225AT 225AP

87_PB_87HNA4

Bldg: 87, MECH RM 480 V 3P 11287.10 A

87_FB_AHU-2

GE TEY

80AF 80AT 80AP

87_CBL_AHU-2

(1) 4 AWG Copper 50 ft, Magnetic

87_NFD_AHU-2

Bldg: 87, Rm: AHU-2 480 V 3P 8762.23 A

87_FB_87XNA3

GE TEY

50AF 50AT 50AP

87_CBL_87XNA3 (PRI)

(1) 6 AWG Copper 5 ft, Magnetic

87_SP_87XNA3 (PRI)

Bldg: 87, MECH RM 480 V 3P 10702.08 A

87_TX_87XNA3

30 kVA;

3.90%; 480 V / 208 V

87_MO_AHU-2

(1) @301.6 hp

87_CBL_87XNA3 (SEC)

(1) 6 AWG Copper 5 ft, Magnetic

87_MB_87LNA7

GE SEPA

100AF 100AT 100AP

87_PB_87LNA7

Bldg: 87, MECH RM 208 V 3P 1926.31 A

05_CBL_5HCA1 (L)

(1) 500 kcmil Copper 35 ft, Magnetic

05_SP_5HCA1 (L)

Bldg: 05, Rm: C153 480 V 3P 24011.99 A

05_AT_5HCA1

05_CBL_5HCA1 (N)

(1) 500 kcmil Copper 25 ft, Magnetic

05_FB_ATS-5HCA1 (N)

SQUARE D ME

400AF 400AT 400AP

05_SB_5HNA1

Bldg: 05, Rm: C152 480 V 3P 27057.24 A

05_FB_5HNA2-1

SQUARE D PE

2000AF 2000AT 2000AP

05_CBL_5HNA2-1

(5) 500 kcmil Copper 20 ft, Magnetic

FROM TRANSFORMER T-87

TO 05_PB_5HCA1 (MAIN PB) TO 05_PB_5HNA2-1

05_FB_CHILLER 2

SQUARE D ME

400AF 400AT 400AP

05_CBL_CHILLER 2

(1) 400 kcmil Copper 80 ft, Magnetic

05_FD_CHILLER 2

Bldg: 05, OUTSIDE 480 V 3P 19245.12 A

05_FF_CHILLER 2

BUSSMANN LPS-RK

400AF 400AT

05_CBL_CHILLER 2 MO

(1) 400 kcmil Copper 10 ft, Magnetic

05_CC_CHILLER 2

Bldg: 05, OUTSIDE 480 V 3P 18571.54 A

05_MO_CHILLER 2

(1) @125 hp

11_MB_11LCC1

EATON CH DK

400AF 400AT 400AP

09_PB_9LCA1

Bldg: 09., Rm:142 208 V 3P 4368.44 A

09_CBL_9LCA1

(1) 1/0 AWG Copper 35 ft, Magnetic

11_FB_9LCA1

EATON FD

70AF 70AT 70AP

11_FB_15LCD1

EATON CH ED

150AF 150AT 150AP

15_CBL_15LCD1

(1) 1/0 AWG Copper 0 ft, Magnetic

15_MB_15LCD1

CUTLER-HAMMER FD

100AF 100AT 100AP

15_PB_15LCD1

Bldg: 15, ATTIC 208 V 3P 5104.60 A

15_FB_UNK 4 6G

EATON CH BAB

80AF 80AT 80AP

13_CBL_HWP

(1) 4 AWG Copper 0 ft, Magnetic

13_FB_HWP

EATON CH BAB

100AF 100AT 100AP

13_PB_13LCB1

Bldg: 13, Rm. 230 208 V 3P 2478.04 A

13_MB_13LCB1

EATON CH CAH

225AF 125AT 125AP

13_CBL_13LCB1

(1) 1/0 AWG Copper 200 ft, Magnetic

11_FB_13LCB1

EATON HFD

100AF 100AT 100AP

11_FB_13LCA1

EATON FD

70AF 70AT 70AP

13_CBL_13LCA1

(1) 1/0 AWG Copper 170 ft, Magnetic

13_PB_13LCA1

Bldg: 13, ELEV HALL 208 V 3P 2698.30 A

11_FB_15LCB1-1 AND 1-2

EATON EDB

225AF 225AT 225AP

15_CBL_15LCB1-1

(1) 300 kcmil Copper 390 ft, Magnetic

15_MB_15LCB1-1

SQUARE D QD

225AF 225AT 225AP

15_PB_15LCB1-1

Bldg: 15, ELEC CLOSET FL2 208 V 3P 2425.24 A

15_CBL_15LCB1-2

(1) 300 kcmil Copper 5 ft, Magnetic

15_PB_15LCB1-2

Bldg: 15, ELEC CLOSET FL2 208 V 3P 2408.89 A

17_PB_17LCA2

Bldg: 17, Rm:125 208 V 3P 1579.77 A

17_CBL_17LAC2

(1) 2 AWG Copper 20 ft, Magnetic

17_PB_17LCA1

Bldg: 17, CR100-17 208 V 3P 1667.56 A

17_CBL_17LAC1

(1) 1/0 AWG Copper 375 ft, Magnetic

11_FB_17LCA1

EATON EDB

100AF 100AT 100AP

11_FB_9LCB2

EATON EDB

225AF 225AT 225AP

09_CBL_9LCB2

(1) 4/0 AWG Copper 250 ft, Magnetic

09_MB_9LCB2

EATON EDB

225AF 225AT 225AP

09_PB_9LCB2

Bldg: 09, Rm: 235 208 V 3P 2801.75 A

15_PB_15LCA1

Bldg: 15, ELEC CLOSET FL1 208 V 3P 2072.72 A

15_CBL_15LCA1

(1) 2 AWG Copper 185 ft, Magnetic

11_FB_15LCA1

EATON HFD

100AF 100AT 100AP

11_PB_11LCC1

Bldg: 11, BLDG 9-11 208 V 3P 5106.96 A

S

P

100A/3P

PANELBOARD

'9LCA2'

100A

208/120V

3PH, 4W

10KAIC

DPM

SPD

30A/3P

PANELBOARD '9HLS1'

BLDG 9, RM 220,

225A, 480/277V, 3PH, 4W

22KAIC

225A/3P

CONTINUES

TO PANELBOARD

'11HEC1'

S

P

09-P-09A

09-P-09B

09-P-09C

DISCONNECT

'DISC-9LCA2'

30A/3P

XFMR 'TX-9LCA2'

15kVA 480-208/120V

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:5

P

M

A u to d e s k D o c s /5

-2

-7

V

A G

A D u b lin E

H R

M T

A S

S /V

A D

U

G E

N S

H E

E T

S

E L

S

D B

.r v t

EP601

ONE-LINE DIAGRAM - EMERGENCY

POWER -

JPB/WNM BCL

CONSTRUCTION

DOCUMENT

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

KEY NOTES

GENERAL SHEET NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY

DISCREPANCIES FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,

AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30-DAYS

PRIOR TO IMPLEMENTATION.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

METERING NOTES

1 REFERENCE ASSOCIATED PANEL SCHEDULE FOR ADDITIONAL CIRCUITING

INFORMATION.

DEMOLISH (3) SINGLE-POLE 20A SPARE CIRCUIT BREAKERS TO MAKE ROOM FOR

INSTALLATION OF CIRCUIT BREAKER TO SERVE LOAD AS INDICATED. REPLACE

EXISTING DEADFRONT COVER SECTION(S) FOR CIRCUIT BREAKER INSTALLATION AS

REQUIRED.

PROVIDE CIRCUIT BREAKER IN EXISTING SPACE.

- NTS

1 ONE-LINE DIAGRAM - EMERGENCY POWER

EQUIPMENT HAS BEEN METERED DURING DESIGN PHASE. REFERENCE "EQUIPMENT

METERING AND LOAD INFORMATION SCHEDULE" ON SHEET E-703 FOR ADDITIONAL

LOADING INFORMATION.

Revisions: Date:

11_PB_11LNA3

Bldg: 11, Rm: 109 208 V 3P 2172.70 A

11_MB_11LNA3

SQUARE D QO

100AF 100AT 100AP

11_CBL_11LNA3

(1) 2 AWG Copper 210 ft, Magnetic

11_FB_11LNA3

EATON EDB

100AF 100AT 100AP

11_PB_11LNC1

Bldg: 11, CORR-BLDG 9-11 208 V 3P 7776.50 A

11_PB_11LNA2

Bldg: 11, Rm: 108 208 V 3P 2256.45 A

11_MB_11LNA2

SQUARE D QD

100AF 100AT 100AP

11_CBL_11LNA2

(1) 2 AWG Copper 200 ft, Magnetic

11_FB_11LNA2

EATON EDB

100AF 100AT 100AP

11_CBL_11LNB1 TAP

(1) 4/0 AWG Copper 4 ft, Magnetic

11_FB_11LNB1 ECB

GE SFHA

250AF 225AT 225AP

11_EB_11LNB1

Bldg: 11, CORR - BLDG 9-11 208 V 3P 7635.81 A

11_CBL_11LNB1

(1) 4/0 AWG Copper 160 ft, Magnetic

11_MB_11LNB1

GE TQD

225AF 225AT 225AP

11_PB_11LNB1

Bldg: 11, Rm: 226 208 V 3P 4315.40 A

11_CBL_11LNB2

(1) 4/0 AWG Copper 5 ft, Magnetic

11_MB_11LNB2

GE TQD

225AF 225AT 225AP

11_PB_11LNB2

Bldg: 11, Rm: 226 208 V 3P 4255.68 A

11_PB_11LNC2

Bldg: 11, Rm: BM101 208 V 3P 609.96 A

11_MB_11LNC2

EATON CH BAB

100AF 100AT 100AP

11_CBL_11LNC2

(1) 10 AWG Copper 160 ft, Magnetic

11_FB_11LNC2

EATON EDB

100AF 100AT 100AP

11_PB_11LNA1

Bldg: 11, Rm: 123 208 V 3P 4727.95 A

11_MB_11LNA1

SQUARE D QO

100AF 100AT 100AP

11_CBL_11LNA1

(1) 2 AWG Copper 60 ft, Magnetic

11_FB_11LNA1

EATON EDB

100AF 100AT 100AP

11_MB_11LNC1

SQUARE D LA

400AF 400AT 400AP

11_CBL_11LNC1

(1) 500 kcmil Copper 130 ft, Magnetic

03_FB_11LNC1

SQUARE D LA

400AF 400AT 400AP

03_PB_MS-3LNC1

Bldg: 03, Rm: BM116 208 V 3P 14225.53 A

03_FB_3LNA1

SQUARE D KA

250AF 225AT 225AP

03_CBL_3LNA1

(1) 3/0 AWG Copper 90 ft, Magnetic

03_MB_3LNA1

SQUARE D QD

225AF 225AT 225AP

03_PB_3LNA1

Bldg: 03, Rm: 117 208 V 3P 7527.31 A

41_PB_CE-3

Bldg. 41, Rm. 104-41 208 V 3P 8154.31 A

41_MB_CE-3

SIEMENS BLH

100AF 100AT 100AP

41_CBL_CE-3

(1) 2 AWG Copper 40 ft, Magnetic

03_FB_CE-3

SQUARE D KA

100AF 100AT 100AP

03_FB_3LNC7

SQUARE D MX

400AF 400AT 400AP

03_CBL_3LNC7

(2) 4/0 AWG Copper 45 ft, Magnetic

03_MB_3LNC7

EATON CH DK

400AF 400AT 400AP

03_PB_3LNC7

Bldg: 03, CRB100 208 V 3P 12049.38 A

03_FB_3LNC9

EATON CH BAB

100AF 100AT 100AP

03_CBL_3LNC9

(1) 2 AWG Copper 140 ft, Magnetic

03_MB_3LNC9

CUTLER-HAMMER FD

100AF 100AT 100AP

03_PB_3LNC9

Bldg: 03, Rm: BM110A 208 V 3P 3295.44 A

03_PB_3LNC8

Bldg: 03, Rm: BM109 208 V 3P 3119.42 A

03_MB_3LNC8

CUTLER-HAMMER FD

100AF 100AT 100AP

03_CBL_3LNC8

(1) 2 AWG Copper 150 ft, Magnetic

03_FB_3LNC8

EATON CH BAB

100AF 100AT 100AP

03_FB_3LNA2

SQUARE D KA

250AF 200AT 200AP

03_MB_3LNC1

EATON CH MDL

800AF 800AT 800AP

03_CBL_3LNC1

(2) 1/0 AWG Copper 35 ft, Magnetic

03_FB_3LNC1

SQUARE D MX

800AF 800AT 800AP

03_MB_MS-3LNC1

SQUARE D NE

1200AF 1200AT 600AP

03_CBL_T-3 (SEC)

(3) 350 kcmil Copper 30 ft, Magnetic

03_FB_3LNC2 (PNL CMPA)

SQUARE D FA

100AF 100AT 100AP

03_CBL_3LNC2 (CMPA)

(1) 6 AWG Copper 40 ft, Magnetic

03_MB_3LNC2 (CMPA)

SIEMENS BQH

100AF 100AT 100AP

03_PB_3LNC2 (CMPA)

Bldg: 03, CRB100 208 V 3P 4775.24 A

03_FB_UNLABELED BOTTOM

SQUARE D HJ

150AF 150AT 150AP

03_FB_9LNA1

SQUARE D LX / LXI

400AF 400AT 400AP

09_CBL_9LNA1

(1) 500 kcmil Copper 160 ft, Magnetic

09_MB_9LNA1

SIEMENS JXD6-A

400AF 400AT 400AP

09_PB_9LNA4

Bldg: 09, CR12-9 208 V 3P 4117.61 A

09_CBL_9LNA4

(1) 4/0 AWG Copper 160 ft, Magnetic

09_FB_9LNA4

SIEMENS QJ

225AF 225AT 225AP

09_PB_9LNA1

Bldg: 09, Rm: 142 208 V 3P 7032.12 A

09_PB_9LNA2

Bldg: 09, Rm: 142 208 V 3P 6084.39 A

09_MB_9LNA2

SIEMENS BL

100AF 100AT 100AP

09_CBL_9LNA2

(1) 2 AWG Copper 18 ft, Magnetic

09_FB_9LNA2

SIEMENS BQD

100AF 100AT 100AP

09_PB_9LNA3

Bldg: 09, Rm: 126 208 V 3P 2373.22 A

09_MB_9LNA3

SIEMENS BL

100AF 100AT 100AP

09_CBL_9LNA3

(1) 2 AWG Copper 180 ft, Magnetic

09_FB_9LNA3

SIEMENS BQD

100AF 100AT 100AP

03_SB_3LNC1

Bldg: 03, Rm: BM116 208 V 3P 11847.42 A

03_FB_3LNC5

EATON EDB

225AF 225AT 225AP

03_CBL_3LNC5

(1) 4 AWG Copper 140 ft, Magnetic

03_MB_3LNC5

EATON EDB

225AF 225AT 225AP

03_PB_3LNC5

Bldg: 03, Rm: BM110A 208 V 3P 2282.83 A

03_PB_3LNC3

Bldg: 03, CRB100 208 V 3P 8996.61 A

03_CBL_3LNC3

(1) 2 AWG Copper 20 ft, Magnetic

03_FB_3LNC3

EATON CH HFD

100AF 100AT 100AP

03_PB_3LNB2

Bldg: 03, Rm: 213B 208 V 3P 1767.17 A

03_MB_3LNB2

CUTLER-HAMMER FD

100AF 100AT 100AP

03_CBL_3LNB2

(1) 6 AWG Copper 120 ft, Magnetic

03_FB_3LNB2

CUTLER-HAMMER FD

100AF 100AT 100AP

03_FB_3LNB1

EATON CH EDB

225AF 225AT 225AP

03_CBL_3LNB1

(1) 4/0 AWG Copper 115 ft, Magnetic

03_MB_3LNB1

EATON EDB

225AF 225AT 225AP

03_PB_3LNB1

Bldg: 03, CR21-3 208 V 3P 6330.90 A

03_PB_3LNC4

Bldg: 03, Rm: BM110A 208 V 3P 3240.01 A

03_MB_3LNC4

CUTLER-HAMMER FD

100AF 100AT 100AP

03_CBL_3LNC4

(1) 2 AWG Copper 140 ft, Magnetic

03_FB_3LNC4

EATON CH HFD

100AF 100AT 100AP

03_PB_3LNC6

Bldg: 03, Rm: BM110A 208 V 3P 3240.01 A

03_MB_3LNC6

CUTLER-HAMMER FD

100AF 100AT 100AP

03_CBL_3LNC6

(1) 2 AWG Copper 140 ft, Magnetic

03_FB_3LNC6

EATON CH HFD

100AF 100AT 100AP

11_PB_11LNA3

Bldg: 11, Rm: 109 208 V 3P 2172.70 A

11_MB_11LNA3

SQUARE D QO

100AF 100AT 100AP

11_CBL_11LNA3

(1) 2 AWG Copper 210 ft, Magnetic

11_FB_11LNA3

EATON EDB

100AF 100AT 100AP

11_PB_11LNC1

Bldg: 11, CORR-BLDG 9-11 208 V 3P 7776.50 A

11_PB_11LNA2

Bldg: 11, Rm: 108 208 V 3P 2256.45 A

11_MB_11LNA2

SQUARE D QD

100AF 100AT 100AP

11_CBL_11LNA2

(1) 2 AWG Copper 200 ft, Magnetic

11_FB_11LNA2

EATON EDB

100AF 100AT 100AP

11_CBL_11LNB1 TAP

(1) 4/0 AWG Copper 4 ft, Magnetic

11_FB_11LNB1 ECB

GE SFHA

250AF 225AT 225AP

11_EB_11LNB1

Bldg: 11, CORR - BLDG 9-11 208 V 3P 7635.81 A

11_CBL_11LNB1

(1) 4/0 AWG Copper 160 ft, Magnetic

11_MB_11LNB1

GE TQD

225AF 225AT 225AP

11_PB_11LNB1

Bldg: 11, Rm: 226 208 V 3P 4315.40 A

11_CBL_11LNB2

(1) 4/0 AWG Copper 5 ft, Magnetic

11_MB_11LNB2

GE TQD

225AF 225AT 225AP

11_PB_11LNB2

Bldg: 11, Rm: 226 208 V 3P 4255.68 A

11_PB_11LNC2

Bldg: 11, Rm: BM101 208 V 3P 609.96 A

11_MB_11LNC2

EATON CH BAB

100AF 100AT 100AP

11_CBL_11LNC2

(1) 10 AWG Copper 160 ft, Magnetic

11_FB_11LNC2

EATON EDB

100AF 100AT 100AP

11_PB_11LNA1

Bldg: 11, Rm: 123 208 V 3P 4727.95 A

11_MB_11LNA1

SQUARE D QO

100AF 100AT 100AP

11_CBL_11LNA1

(1) 2 AWG Copper 60 ft, Magnetic

11_FB_11LNA1

EATON EDB

100AF 100AT 100AP

11_MB_11LNC1

SQUARE D LA

400AF 400AT 400AP

11_CBL_11LNC1

(1) 500 kcmil Copper 130 ft, Magnetic

03_FB_11LNC1

SQUARE D LA

400AF 400AT 400AP

03_PB_MS-3LNC1

Bldg: 03, Rm: BM116 208 V 3P 14225.53 A

03_FB_3LNA1

SQUARE D KA

250AF 225AT 225AP

03_CBL_3LNA1

(1) 3/0 AWG Copper 90 ft, Magnetic

03_MB_3LNA1

SQUARE D QD

225AF 225AT 225AP

03_PB_3LNA1

Bldg: 03, Rm: 117 208 V 3P 7527.31 A

41_PB_CE-3

Bldg. 41, Rm. 104-41 208 V 3P 8154.31 A

41_MB_CE-3

SIEMENS BLH

100AF 100AT 100AP

41_CBL_CE-3

(1) 2 AWG Copper 40 ft, Magnetic

03_FB_CE-3

SQUARE D KA

100AF 100AT 100AP

03_FB_3LNC7

SQUARE D MX

400AF 400AT 400AP

03_CBL_3LNC7

(2) 4/0 AWG Copper 45 ft, Magnetic

03_MB_3LNC7

EATON CH DK

400AF 400AT 400AP

03_PB_3LNC7

Bldg: 03, CRB100 208 V 3P 12049.38 A

03_FB_3LNC9

EATON CH BAB

100AF 100AT 100AP

03_CBL_3LNC9

(1) 2 AWG Copper 140 ft, Magnetic

03_MB_3LNC9

CUTLER-HAMMER FD

100AF 100AT 100AP

03_PB_3LNC9

Bldg: 03, Rm: BM110A 208 V 3P 3295.44 A

03_PB_3LNC8

Bldg: 03, Rm: BM109 208 V 3P 3119.42 A

03_MB_3LNC8

CUTLER-HAMMER FD

100AF 100AT 100AP

03_CBL_3LNC8

(1) 2 AWG Copper 150 ft, Magnetic

03_FB_3LNC8

EATON CH BAB

100AF 100AT 100AP

03_FB_3LNA2

SQUARE D KA

250AF 200AT 200AP

03_MB_3LNC1

EATON CH MDL

800AF 800AT 800AP

03_CBL_3LNC1

(2) 1/0 AWG Copper 35 ft, Magnetic

03_FB_3LNC1

SQUARE D MX

800AF 800AT 800AP

03_MB_MS-3LNC1

SQUARE D NE

1200AF 1200AT 600AP

03_CBL_T-3 (SEC)

(3) 350 kcmil Copper 30 ft, Magnetic

03_FB_3LNC2 (PNL CMPA)

SQUARE D FA

100AF 100AT 100AP

03_CBL_3LNC2 (CMPA)

(1) 6 AWG Copper 40 ft, Magnetic

03_MB_3LNC2 (CMPA)

SIEMENS BQH

100AF 100AT 100AP

03_PB_3LNC2 (CMPA)

Bldg: 03, CRB100 208 V 3P 4775.24 A

03_FB_UNLABELED BOTTOM

SQUARE D HJ

150AF 150AT 150AP

03_FB_9LNA1

SQUARE D LX / LXI

400AF 400AT 400AP

09_MB_9LNA1

SIEMENS JXD6-A

400AF 400AT 400AP

09_FB_9LNA4

SIEMENS QJ

225AF 225AT 225AP

09_PB_9LNA1

Bldg: 09, Rm: 142 208 V

09_PB_9LNA2

Bldg: 09, Rm: 142 208 V 3P 6084.39 A

09_MB_9LNA2

SIEMENS BL

100AF 100AT 100AP

09_FB_9LNA2

SIEMENS BQD

100AF 100AT 100AP

09_FB_9LNA3

SIEMENS BQD

100AF 100AT 100AP

03_SB_3LNC1

Bldg: 03, Rm: BM116 208 V 3P 11847.42 A

03_FB_3LNC5

EATON EDB

225AF 225AT 225AP

03_CBL_3LNC5

(1) 4 AWG Copper 140 ft, Magnetic

03_MB_3LNC5

EATON EDB

225AF 225AT 225AP

03_PB_3LNC5

Bldg: 03, Rm: BM110A 208 V 3P 2282.83 A

03_PB_3LNC3

Bldg: 03, CRB100 208 V 3P 8996.61 A

03_CBL_3LNC3

(1) 2 AWG Copper 20 ft, Magnetic

03_FB_3LNC3

EATON CH HFD

100AF 100AT 100AP

03_PB_3LNB2

Bldg: 03, Rm: 213B 208 V 3P 1767.17 A

03_MB_3LNB2

CUTLER-HAMMER FD

100AF 100AT 100AP

03_CBL_3LNB2

(1) 6 AWG Copper 120 ft, Magnetic

03_FB_3LNB2

CUTLER-HAMMER FD

100AF 100AT 100AP

03_FB_3LNB1

EATON CH EDB

225AF 225AT 225AP

03_CBL_3LNB1

(1) 4/0 AWG Copper 115 ft, Magnetic

03_MB_3LNB1

EATON EDB

225AF 225AT 225AP

03_PB_3LNB1

Bldg: 03, CR21-3 208 V 3P 6330.90 A

03_PB_3LNC4

Bldg: 03, Rm: BM110A 208 V 3P 3240.01 A

03_MB_3LNC4

CUTLER-HAMMER FD

100AF 100AT 100AP

03_CBL_3LNC4

(1) 2 AWG Copper 140 ft, Magnetic

03_FB_3LNC4

EATON CH HFD

100AF 100AT 100AP

03_PB_3LNC6

Bldg: 03, Rm: BM110A 208 V 3P 3240.01 A

03_MB_3LNC6

CUTLER-HAMMER FD

100AF 100AT 100AP

03_CBL_3LNC6

(1) 2 AWG Copper 140 ft, Magnetic

03_FB_3LNC6

EATON CH HFD

100AF 100AT 100AP

CONTINUED FROM

MEDIUM VOLTAGE EQUIPMENT

00_TX_TB-3

300 kVA;

4.96%; 4160 V / 208 V

3P SPACE 3P SPACE

400A/3P

400A/3P

100A 3P

PANELBOARD

'9LNA5'

400A, 208/120V, 3PH, 4W

42KAIC

225A 3P

PANELBOARD

'9LNA7'

100A

208/120V

3PH, 4W

22kAIC

PANELBOARD

'9LNA6'

225A

208/120V

3PH, 4W

22kAIC

60A/3P

HACR

VFD

PNL

'9LNA3'

225AF, 100AT

208/120V

3PH, 4W

22kAIC

PNL

'9LNA4'

225A

208/120V

3PH, 4W

22kAIC

SPD

DPM

SPD

DPM

09-P-0309-P-0209-P-08

09-P-06 09-P-05

09-P-07

09-P-0409-P-01

SPD

DPM

SPD

DPM

CONTINUED FROM

MEDIUM VOLTAGE EQUIPMENT

00_TX_TB-3

300 kVA;

4.96%; 4160 V / 208 V

DPM SPD

30A 3P

30A 3P

3P SPACE

AIR HANDLING UNIT

"009A-AHU-1"

28FLA, 208V, 3PH

4 4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:5

P

M

A u to d e s k D o c s /5

-2

-7

V

A G

A D u b lin E

H R

M T

A S

S /V

A D

U

G E

N S

H E

E T

S

E L

S

D B

.r v t

EP602

ONE-LINE DIAGRAM - NORMAL

POWER -

JPB/WNM BCL

CONSTRUCTION

DOCUMENT

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

- NTS

1 ONE-LINE DIAGRAM - NORMAL POWER - DEMOLITION

KEY NOTES

GENERAL SHEET NOTES

1. CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS. ANY

DISCREPANCIES FOUND SHALL BE REPORTED TO THE ENGINEER.

2. CONTRACTOR SHALL PROVIDE ALL SHUTDOWN PLANS, TEMPORARY POWER PLANS,

AND PHASING PLANS FOR VA AND ENGINEER REVIEW AND APPROVAL PRIOR TO

COMMENCING WORK. ALL PLANS SHALL BE SUBMITTED FOR REVIEW 30-DAYS

PRIOR TO IMPLEMENTATION.

3. SHORT CIRCUIT CALCULATIONS BASED ON VA PROVIDED AS-BUILTS.

METERING NOTES

1 EXISTING PANELBOARD TO BE RELOCATED. DEMOLISH AND REPLACE EXISTING

FEEDER AS REQUIRED TO REVISED PANELBOARD LOCATION; IDENTIFY, PRESERVE,

AND EXTEND BRANCH CIRCUITS TO REVISED PANELBOARD LOCATION. PROVIDE

JUNCTION BOX(ES) SIZED PER NEC AND SPLICING AS REQUIRED. REFERENCE

SHEETS ED102 AND EP101 FOR ADDITIONAL INFORMATION.

EXISTING PANELBOARD AND ASSOCIATED FEEDER TO BE DEMOLISHED. IDENTIFY

AND PRESERVE BRANCH CIRCUITS TO BE EXTENDED TO REPLACEMENT PANEL

LOCATION. SEE SHEET EP100 AND EP101 FOR FEEDER ROUTING AND PANEL

LOCATIONS.

PROVIDE CIRCUIT BREAKER IN EXISTING PANELBOARD 3P SPACE TO SERVE LOAD AS

INDICATED.

REFERENCE ASSOCIATED PANEL SCHEDULE FOR ADDITIONAL CIRCUITING

INFORMATION.

MECHANICAL UNIT SHALL BE PROVIDED WITH INTEGRAL STARTER AND DISCONNECT;

ELECTRICAL CONTRACTOR SHALL PROVIDE SINGLE POINT CONNECTION.

REPLACEMENT PANEL. EXTEND EXISTING BRANCH CIRCUIT CONDUCTORS AND

RACEWAYS TO REPLACEMENT PANELBOARD; PROVIDE PULLBOXES AND SPLICES AS

REQUIRED. REFERENCE SHEETS ED102, EP100, AND EP101 FOR ADDITIONAL

INFORMATION.

- NTS

2 ONE-LINE DIAGRAM - NORMAL POWER - REVISED

EQUIPMENT HAS BEEN METERED DURING DESIGN PHASE. REFERENCE

"EQUIPMENT METERING AND LOAD INFORMATION SCHEDULE" ON SHEET E-703

FOR ADDITIONAL LOADING INFORMATION.

Revisions: Date:

FIBER OPTIC

PATCH PANEL

TR

RACK

RM TR 220

LEVEL 02

LEVEL 01

CONTINUE TO CAMPUS

DATA CENTER

FIBER OPTIC

PATCH PANEL

TR

RACK

RM TR 100

JUNCTION BOX

"JB-TR100"

BUILDING 09A

CRAWL SPACE

LEVEL 01

LEVEL 02

TR 100

PBB

SWITCHBOARD

"MS-3LNC1"

BUILDING 03

TYP.

9 3

TYP.

TR 220

LEVEL 00

BM116-3

BUILDING 09A

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

ENGINEERING DISCIPLINE:

SPEES DESIGN BUILD

23830 PACIFIC HIGHWAY S. SUITE 203

KENT, WA 98032

(206) 590-2118

RAY SPEES

/1

/2

:5

:5

P

M

A u to d e s k D o c s /5

-2

-7

V

A G

A D u b lin E

H R

M T

A S

S /V

A D

U

G E

N S

H E

E T

S

E L

S

D B

.r v t

ET601

JPB/WNM BCL

CONSTRUCTION

DOCUMENT

06/14/2024

557-21-703RENOVATE BUILDING 9A FOR

EHRM ADMINISTRATIVE SPACE

CARL VINSON VA MEDICAL CENTER _ DUBLIN, GA

FIBER RISER AND

TELECOMMUNICATIONS BONDING

DIAGRAM

GENERAL NOTES

KEY NOTES

1. PRIOR TO CONSTRUCTION, COORDINATE VA STAFF AND OIT FOR PHASING AND

TELECOMMUNICATION SERVICE DISRUPTIONS. CONTRACTOR SHALL EXPECT WORK

TO BE AFTER HOURS.

2. NOT ALL EXISTING FIBER OPTIC TR CONNECTIONS ARE SHOWN FOR CLARITY.

CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS ON SITE.

3. ALL BONDING CONDUCTORS, INCLUDING TBB, SHALL FOLLOW SIZING

REQUIREMENTS SPECIFIED IN ANSI/TIA-607-D.

4. CONTRACTOR SHALL PROVIDE ALL REQUIRED BONDING, CONDUCTORS, AND

PATHWAYS AS REQUIRED. PROVIDE ALL PATCHING, REPAIR AND FIREPROOFING

FOR REMOVAL OF ALL EXISTING EQUIPMENT AND CONDUCTORS AS REQUIRED.

5. ALL BONDING CONDUCTORS SHALL BE COPPER AND BE INSULATED UNLESS

OTHERWISE NOTED.

- NTS

1 FIBER RISER DIAGRAM

PROVIDE FIBER OPTIC CABLING AS SHOWN. UTILIZE EXISTING PATHWAYS AND

SLEEVES AS REQUIRED. PROVIDE (1) 24-STRAND FIBER-OPTIC CABLE WITHIN 1''

INNERDUCT; COORDINATE WITH EXISTING FIBER TYPE AS NEEDED. REFERENCE

KEY NOTE '2' ON THIS SHEET FOR ADDITIONAL INFORMATION.

PROVIDE JUNCTION BOX INTERCEPT AND ROUTE TO TR RACK LOCATED IN TR 100.

IF EXISTING FIBER-OPTIC CABLE IS NOT LONG ENOUGH TO EXTEND TO TR 100,

PROVIDE FUSION SPLICE IN "JB-TR100" AND EXTEND TO TR 100 AS REQUIRED.

REFERENCE SHEET ET101 FOR ADDITIONAL INFORMATION.

PROVIDE PRIMARY BONDING BUSBAR (PBB). WHERE EXISTING PBB EXISTS,

CONTRACTOR SHALL REPLACE; CONTRACTOR TO FIELD VERIFY EXISTING

LOCATION. PROVIDE ALL BONDING CONNECTIONS AS REQUIRED.

PROVIDE TELECOMMUNICATIONS BONDING BACKBONE (TBB) CONDUCTOR AS

INDICATED. CONTRACTOR SHALL ROUTE AND PROVIDE ALL REQUIRED PATHWAYS

FOR TBB AS REQUIRED. EXISTING TBB SHALL BE DEMOLISHED AND REMOVED;

PROVIDE ALL PATCHING, REPAIR AND FIREPROOF SEALING AS REQUIRED.

PROVIDE IRREVERSIBLE CRIMP CONNECTOR, UL LISTED.

TELECOMMUNICATIONS ROOM. REFER TO ENLARGED FLOOR PLANS FOR

ADDITIONAL INFORMATION.

PROVIDE TELECOMMUNICATIONS EQUIPMENT BONDING CONDUCTOR (TEBC) TO

CONNECT THE TBB TO THE SBB. MINIMUM SIZE SHALL BE 6 AWG.

PROVIDE SECONDARY BONDING BUSBAR (SBB). PROVIDE TELECOMMUNICATIONS

EQUIPMENT BONDING CONDUCTOR TO BOND SBB TO THE FOLLOWING EQUIPMENT:

DATA RACK, CABLE TRAY, TR CONDUITS, ELECTRO-STATIC FLOORING, ELECTRICAL

PANEL, ETC. REFERENCE SHEET EP504 FOR ADDITIONAL BONDING INFORMATION.

PROVIDE TELECOMMUNICATIONS BONDING CONDUCTOR (TBC) TO BOND TO

BUILDING ELECTRICAL SERVICE EQUIPMENT GROUNDING BUSBAR. MINIMUM

CONDUCTOR SIZE SHALL BE 3 AWG.

EXISTING TELECOMMUNICATIONS BONDING BUSBAR. PROVIDE BOND TO

TELECOMMUNICATIONS BONDING BACKBONE AS REQUIRED.

- NTS

2 TELECOMMUNICATIONS BONDING RISER DIAGRAM

Revisions: Date: