RFP Attachment 28 - Drawings 695-21-700 Part 21.pdf
PDF 9 MB Posted
- Solicitation number
- 36C77626R0002
About this file
This file is a set of electrical construction drawings for the EHRM Infrastructure Upgrades project at the U.S. Department of Veterans Affairs facility in Milwaukee, Wisconsin. The drawings (numbered 695-21-700, sheets 111-ED109 through 111-EP105) are part of the final bid documents issued September 5, 2025, and prepared by Romanyk Consulting Corp. and IMEG Corp. The drawings depict electrical demolition and new work across multiple floors and areas of Building 111 at 5000 W. National Avenue, Milwaukee, WI.
The demolition work includes disconnecting and removing electrical panels, lighting fixtures, wall power outlets, service disconnect switches, abandoned panels, and cable trays on the eighth, ninth, and tenth floors. The new electrical work encompasses installation of new medium voltage feeders, transformers, panelboards, disconnect switches, receptacles, conduit systems, cable trays, and related electrical equipment throughout the basement and multiple floors. Specific work includes new bi-fuel generators with diesel and natural gas capability, generator distribution panels, underground concrete-encased ductbanks with multiple conduits, telecommunications room upgrades with new critical power distribution panels, and fire alarm relay connections. The drawings provide detailed keynotes, general notes, branch circuiting information, and equipment schedules with specific feeder sizes, conduit specifications, and coordination requirements with mechanical and other trades. All work must comply with fire-stop requirements at fire-rated wall penetrations and include lightning protection connections where applicable.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IT
IT
IT
IT
IT
IT
IT
DN
ELEC. DEMO GENERAL NOTES
ELEC. DEMO KEYNOTES
111-ED109
TRASH ROOM
1. SEE SHEET E-001 FOR GENERAL DEMOLITION NOTES.
2. NOT ALL KEYNOTES ARE USED ON THE SHEET.
3. FULL TONE, DASHED OR HATCHED ITEMS INDICATE TO BE DEMOED. HALF TONE
ITEMS INDICATE TO REMAIN.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/2
/2
:2
:3
A
M
BLDG 111 - EIGHTH FLOOR OVERALL &
ENLARGED - ELECTRICAL DEMOLITION
YW SM
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-ED109
5000 W. NATIONAL AVENUE MILWAUKEE, WI
1" = 30'-0"
BLDG 111 - EIGHTH FLOOR - OVERALL ELECTRICAL DEMOLITION
1/2" = 1'-0"
BLDG 111 - EIGHTH FLOOR - ENLARGED ELECTRICAL DEMOLITION - 8409
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1 EXISTING PANEL TO REMAIN.
2 DISCONNECT AND REMOVE PANEL.
3 NO WORK IN SPACE.
4 REMOVE LIGHTING AND WALL POWER OUTLETS IN ROOM.
5 DEVICES ON EXISTING WALLS NOT IMPACTED BY DEMOLITION SHALL REMAIN AND BE
PROTECTED DURING DEMOLITION.
6 DISCONNECT AND REMOVE SERVICE DISCONNECT SWITCH, INCOMING FEEDERS TO
REMAIN.
7 LIGHTING FIXTURE WILL BE RELOCATED, PROTECT DURING CONSTRUCTION. SEE
NEW WORK PLAN OF CORRESPONDING AREA FOR NEW LOCATION.
8 CONTRACTOR TO VERIFY CONDUIT PATH AND DESTINATION. REROUTE CONDUITS TO
MAKE SPACE FOR NEW EQUIPMENT AND INSTALLATION.
9 DATA CABLES WILL NEED TO BE RELOCATED OUTSIDE OF ELECTRICAL SPACES.
10 PULLBOX AND CONDUIT TO REMAIN.
11 DISCONNECT AND REMOVE ABANDONED PANELS.
12 EXISTING CABLE TRAY, REFER TO TN SHEETS FOR ADDITIONAL REQUIREMENTS.
Revisions: Date:
IT IT
IT IT
RAMP DN
ELEC. DEMO GENERAL NOTES
ELEC. DEMO KEYNOTES
111-ED110
TRASH ROOM
UL-94-1,2 (EX)
1. SEE SHEET E-001 FOR GENERAL DEMOLITION NOTES.
2. NOT ALL KEYNOTES ARE USED ON THE SHEET.
3. FULL TONE, DASHED OR HATCHED ITEMS INDICATE TO BE DEMOED. HALF TONE
ITEMS INDICATE TO REMAIN.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/2
/2
:2
:3
A
M
BLDG 111 - NINTH FLOOR OVERALL &
ENLARGED - ELECTRICAL DEMOLITION
YW SM
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-ED110
5000 W. NATIONAL AVENUE MILWAUKEE, WI
1" = 30'-0"
BLDG 111 - NINTH FLOOR - OVERALL ELECTRICAL DEMOLITION
1/2" = 1'-0"
BLDG 111 - NINTH FLOOR - ENLARGED ELECTRICAL DEMOLITION - 9409
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1 EXISTING PANEL TO REMAIN.
2 DISCONNECT AND REMOVE PANEL.
3 NO WORK IN SPACE.
4 REMOVE LIGHTING AND WALL POWER OUTLETS IN ROOM.
5 DEVICES ON EXISTING WALLS NOT IMPACTED BY DEMOLITION SHALL REMAIN AND BE
PROTECTED DURING DEMOLITION.
6 DISCONNECT AND REMOVE SERVICE DISCONNECT SWITCH, INCOMING FEEDERS TO
REMAIN.
7 LIGHTING FIXTURE WILL BE RELOCATED, PROTECT DURING CONSTRUCTION. SEE
NEW WORK PLAN OF CORRESPONDING AREA FOR NEW LOCATION.
8 CONTRACTOR TO VERIFY CONDUIT PATH AND DESTINATION. REROUTE CONDUITS TO
MAKE SPACE FOR NEW EQUIPMENT AND INSTALLATION.
9 DATA CABLES WILL NEED TO BE RELOCATED OUTSIDE OF ELECTRICAL SPACES.
10 PULLBOX AND CONDUIT TO REMAIN.
11 DISCONNECT AND REMOVE ABANDONED PANELS.
UNDER CONSTRUCTION
ITIT
IT
IT
WOOD
METAL DOOR
IN WALL
DN
DN
ELEC. DEMO GENERAL NOTES
ELEC. DEMO KEYNOTES
111-ED111
TRASH ROOM
10409
HAC
10412
1. SEE SHEET E-001 FOR GENERAL DEMOLITION NOTES.
2. NOT ALL KEYNOTES ARE USED ON THE SHEET.
3. FULL TONE, DASHED OR HATCHED ITEMS INDICATE TO BE DEMOED. HALF TONE
ITEMS INDICATE TO REMAIN.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/2
/2
:2
:3
A
M
BLDG 111 - TENTH FLOOR OVERALL &
ENLARGED - ELECTRICAL DEMOLITION
YW SM
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-ED111
5000 W. NATIONAL AVENUE MILWAUKEE, WI
1" = 30'-0"
BLDG 111 - TENTH FLOOR - OVERALL ELECTRICAL DEMOLITION
1/2" = 1'-0"
BLDG 111 - TENTH FLOOR - ENLARGED ELECTRICAL DEMOLITION - 10409
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1 EXISTING PANEL TO REMAIN.
2 DISCONNECT AND REMOVE PANEL.
3 NO WORK IN SPACE.
4 REMOVE LIGHTING AND WALL POWER OUTLETS IN ROOM.
5 DEVICES ON EXISTING WALLS NOT IMPACTED BY DEMOLITION SHALL REMAIN AND BE
PROTECTED DURING DEMOLITION.
6 DISCONNECT AND REMOVE SERVICE DISCONNECT SWITCH, INCOMING FEEDERS TO
REMAIN.
7 LIGHTING FIXTURE WILL BE RELOCATED, PROTECT DURING CONSTRUCTION. SEE
NEW WORK PLAN OF CORRESPONDING AREA FOR NEW LOCATION.
8 CONTRACTOR TO VERIFY CONDUIT PATH AND DESTINATION. REROUTE CONDUITS TO
MAKE SPACE FOR NEW EQUIPMENT AND INSTALLATION.
9 DATA CABLES WILL NEED TO BE RELOCATED OUTSIDE OF ELECTRICAL SPACES.
10 PULLBOX AND CONDUIT TO REMAIN.
11 DISCONNECT AND REMOVE ABANDONED PANELS.
ELEC. NEW WORK GENERAL NOTES ELEC. NEW WORK KEYNOTES
NEW MEDIUM VOLTAGE FEEDER IN
EXISTING 5" SPARE UNDERGROUND
CONDUIT
EXISTING ELECTRICAL VAULT
EXISTING MANHOLE
1. FIRE STOP SHALL BE PROVIDED AT ALL LOCATIONS WHERE ELECTRICAL EQUIPMENT OR
SYSTEMS PENETRATE FIRE RATED WALLS. SEE ARCHITECTURAL PLANS FOR RATED WALL
LOCATIONS.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. ONE-LINE DIAGRAMS ARE MEANT TO SHOW ONLY ELECTRICAL RELATIONSHIPS AND
THEREFORE MAY NOT INCLUDE ALL REQUIRED EQUIPMENT, DEVICES AND ACCESSORIES.
4. CONTRACTOR TO VERIFY EXISTING EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
5. EXISTING FIRE ALARM AND OTHER LOW VOLTAGE SYSTEM EQUIPMENT IN THE EXISTING
TR ROOMS OR SPACES IMPACTED BY THE NEW TR ROOMS SHALL BE COORDINATED WITH
THE VA COR FOR WORK REQUIRED.
6. NOT ALL KEYNOTES ARE USED ON THE SHEET.
7. PROVIDE 200% NEUTRAL FOR ALL BRANCH CIRCUITS FEEDING RACKS AND FEEDERS
DOWN STREAM FROM K-13 RATED TRANSFORMERS.
8. FOR MECHANICAL INDOOR AND OUTDOOR UNITS FOR TR ROOMS, PROVIDE (1)3/4"
CONDUIT FOR CONTROL WIRING BETWEEN INDOOR AND OUTDOOR UNITS. CONTROL
WIRING BY MECHANICAL CONTROL CONTRACTOR.
9. FULL TONE, DASHED OR HATCEHD ITEMS INDICATE TO BE DEMOED. HALF TONE ITEMS
INDICATE TO REMAIN.
10. PANELBOARDS SERVING LOADS LOCATED ON ROOF AND BUILDING EXTERIOR SHALL BE
PROVIDED WITH SURGE PROTECTION DEVICES.
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/2
/2
:2
:3
A
M
BLDG 111 - SITE - ELECTRICAL NEW WORK
YW SM
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-EP100
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
NTS
BUILDING 111 - ELECTRICAL SITE PLAN
1 NEMA L21-20R MOUNT ON CABLE TRAY ABOVE RACK. COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. FEEDER: (3) #12, (1) #10N, (1) #12G
3/4"C.
2 NEMA L21-30R MOUNT ON CABLE TRAY ABOVE RACK. COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. FEEDER: (3)#10, (1) #8N, (1) #10G, 3/4"C.
3 SURFACE MOUNT J-BOX (60A) FOR POWER TO RACK PDU. FEEDER: (3)#4, (1)#1/0N,
(1)#8G, 2"C. MOUNT J-BOX ON CABLE TRAY ABOVE RACK, COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. SEE E-500 FOR MORE INFORMATION.
4 FIRE ALARM RELAY FOR CONNECTION TO ACCESS CONTROL PANEL IN ROOM.
COORDINATE EXACT LOCATION WITH ACCESS CONTROL CONTRACTOR.
5 J-BOX FOR POWER TO ACCESS CONTROL POWER SUPPLY AT DOOR. COORDINATE
EXACT LOCATION WITH DOOR ACCESS CONTROL AND DOOR HARDWARE.
6 MOUNT J-BOX (60A) ON CABLE TRAY ABOVE RACK FOR POWER TO RACK PDU.
FEEDER: (3)#4, (1)#1/0N, (1)#8G, 2"C. MOUNT J-BOX ON CABLE TRAY ABOVE RACK,
COORDINATE EXACT LOCATION/PLACEMENT WITH OTHER TRADES. SEE E-500 FOR
MORE INFORMATION.
7 NEW PANEL IN EXISTING PANEL LOCATION. RECONNECT ALL EXISTING CIRCUITS TO
NEW CIRCUIT BREAKERS IN PANEL. VERIFY EXACT LOAD AND LOCATION IN FIELD.
8 CONNECT NEW RECEPTACLE TO EXISTING POWER PANEL SERVING THE AREA. USE
20AMP SPARE CIRCUIT BREAKER OR PROVIDE NEW AS NEEDED.
9 CONNECT NEW PANEL TO BUILDING DISTRIBUTION PANEL. PROVIDE NEW CIRCUIT
BREAKER IN EXISTING PANEL. NEW BREAKER TYPE TO MATCH EXISTING.
10 RELOCATED PANEL. RECONNECT ALL CIRCUITS TO EXISTING LOADS. COORDINATE
EXACT BRANCH CIRCUIT INFORMATION IN FIELD AND COORDINATE
LOCATION/PLACEMENT WITH THE COR.
11 PROVIDE NEW CIRCUIT BREAKER IN AVAILABLE SPACES IN EXISTING DISTRIBUTION.
PROVIDE SEPARATE CIRCUIT BREAKER ENCLOSURE IF SPACES ARE NOT AVAILABLE.
12 INDOOR UNIT POWERED BY OUTDOOR UNIT. PROVIDE 20A/2P MOTOR RATED MANUAL
TOGGLE CONTROLLER FOR CONTROL OF EQUIPMENT.
15 60AS/NF/2P, NEMA 3R DISCONNECT SWITCH. FEEDER: (3) #10, #10G, 3/4"C. PROVIDE
(2) 3/4" CONDUIT FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
16 30AS/NF/2P, NEMA 3R DISCONNECT SWITCH. FEEDER: (2) #10, #10G, 3/4"C. PROVIDE
(2) 3/4" CONDUITS FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
18 SEE EQUIPMENT SCHEDULE FOR FEEDER AND DISCONNECT INFORMATION.
20 NEW PANEL AT EXISTING PANEL LOCATION. EXTEND AND RECONNECT EXISTING
INCOMING AND OUTGOING FEEDERS. NEW CIRCUIT BREAKER RATING TO MATCH
EXISTING.
21 NEW MEDIUM VOLTAGE FEEDER IN EXISTING SPARE CONDUIT BETWEEN THE
EXISTING VAULT AND BUILDING 115. PROVIDE NEW CONDUIT IN BUILDING 115 TO THE
NEW CIRCUIT BREAKER IN EXISTING MEDIUM VOLTAGE SWITCHGEAR. SEE SHEET
111-EP114 FOR ADDITIONAL INFORMATION.
22 ROUTE CONDUIT ON WALL TO A NEW PULLBOX 24"X18"X12" ON CEILING.
23 STUB CONDUIT TO ROOM. SEE SHEET 111-EP114 FOR ADDITIONAL INFORMATION.
24 L5-30R RECEPTACLE MOUNTED ON WALL. COORDINATE LOCATION AND MOUNTING
HEIGHT WITH WALL ENCLOSURE PLACEMENT. FEEDER: 2#10, #8N, #10G, 3/4"C.
25 NEW BI-FUEL GENERATOR WITH DIESEL AND NATURAL GAS. SEE MECHANICAL FOR
GAS LINE INFORMATION. BASE MOUNTED DIESEL STORAGE TANK AND
WEATHERPROOF ENCLOSURE. PROVIDE PLATFORM AND LADDER FOR ACCESS AND
MAINTENANCE.
26 SEE CIVIL AND STRUCTURAL FOR FENCE AND PAD DETAILS.
27 UNISTRUT MOUNT PORTABLE GENERATOR AND LOAD BANK CONNECTION BOX.
COORDINATE EXACT LOCATION WITH VA COR.
28 NEW NEMA 3R RATED EQUIPMENT MOUNT ON CONCRETE PAD. EXTEND EXISTING
CONCRETE PAD.
29 MOUNT GENERATOR DISTRIBUTION PANEL ON CONCRETE PAD.
30 SEE EQUIPMENT SCHEDULE FOR FEEDER AND DISCONNECT INFORMATION. PROVIDE
(2) 3/4" CONDUITS FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
32 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (9) 4" AND (3) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
33 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (6) 4" AND (2) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
34 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (3) 4" AND (1) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
35 RECEPTACLE MOUNTED ON ROOF ADJACENT TO MECHANICAL EQUIPMENT
DISCONNECT.
36 ROUTE CONDUIT IN ABOVE CEILING SPACE AND SUPPORT FROM STRUCTURE.
39 CONTRACTOR TO REMOVE CEILING TILES AND/OR CEILING MOUNTED DEVICES AS
NEEDED TO ALLOW NEW CONDUIT INSTALLATION. REINSTALL CEILING TILES AND
DEVICES AFTER COMPLETE CONDUIT INSTALLATION.
40 MOUNT RECEPTACLE ON EXISTING CABLE TRAY.
41 PROVIDE CONNECTION TO EXISTING LIGHTNING PROTECTION SYSTEM ON ROOF.
BONDING CONDUCTOR TO MATCH EXISTING.
42 PROVIDE LIGHTNING PROTECTION ON GENERATOR ENCLOSURE AND BOND TO
FENCE/POST WHERE APPLICABLE. SEE SPECIFICATION SECTION FOR DETAILS.
43 PROVIDE LIGHTNING PROTECTION ON GENERATOR ENCLOSURE AND BOND TO
FENCE/POST WHERE APPLICABLE. SEE SPECIFICATION SECTION FOR DETAILS.
44 INSTALL BOTH OUTLETS IN COMMON BACKBOX AND COVERPLATE.
45 PENDANT MOUNT TRANSFORMER FROM CEILING. PROVIDE NECESSARY MOUNTING
BRACKETS. ELECTRICAL CONTRACTOR TO DETERMINE BEST LOCATION FOR
MOUNTING.
46 CONDUITS UP TO CEILING. COORDINATE EXACT LOCATION IN FIELD.
47 CONDUITS ROUTED ABOVE CEILING SPACES. COORDINATE EXACT LOCATION IN
FIELD.
49 ROUTE CONDUIT FROM ELEC E-34EC THROUGH BASEMENT CEILING TO BENEATH
THE TR AND STUB UP FROM BELOW.
50 STUB UP CONDUITS FROM ELECTRICAL ROOM BELOW TO CEILING OF FIRST FLOOR
AND ROUTE TO TELECOM ROOMS.
51 CONDUITS ARE ROUTED UP THE COLUMN TO THE TR ON THE FLOOR ABOVE.
52 ROUTE CONDUITS ON EXTERIOR ROOF AND WALLS. COORDINATE EXACT LOCATION
IN FIELD.
53 CONTRACTOR SHALL PROVIDE GENERATOR ENCLOURE AND SETBACK PER VA
PSRDM REQUIREMENTS.
D N
D N
ELECTRICAL
SLIDER FENCE
TRENCH
B0012P
LOADING
DOCK
B0457
LOADING
DOCK
OH D OH D OH D
OH D
OH D
O H
D
F D F D
UP
DN
DN
DN
UP
DN
UP DN
DN
UP
DN
DN
DN
UP
DN
DN
DN
FIRE
PUMP
ROOM
S
M FAR
J
S M
FAR
J
S M
FAR
J
ELEC. NEW WORK GENERAL NOTES ELEC. NEW WORK KEYNOTES
BRANCH CIRCUITING NOTES
111-EP101
111-EP101
111-EP101
TELECOMMUNICATIONS
RM.
B0622
CORRIDOR
C0C25C2J
TELECOMMUNICATIONS
RM.
B0610E
TELECOMMUNICATIONS
RM.
B0423
EUL-TR-B06-1 (NEW) EUL-TR-B06-2 (NEW)
A,C1-7
A,C2-7 A,C1-7
C1-1,3,5 C2-1,3,5
C1-2C2-2
C1-4
C2-4
C1-6 C2-6
C1-8
C2-8
C1-9a,D ba b a
C1-10
A,C2-7
111-AC-B0610E
C2-9,11 b,D
EUL-TR-B06-3 (NEW)EUL-TR-B06-4 (NEW)
A,C2-7
C2-1,3,5C1-1,3,5
A,C1-18
C1-2
C1-4
C1-6
C2-2 C1-8
C1-10
C2-4
C1-12 C1-14
111-AC-B0622
C1-16
A,C2-7 a,D a b
LV
a b
B,C1-18 a B,C2-7
C1-20 b A,C1-18
C2-12,14 b,D
EUL-TR-B04-1 (NEW) EUL-TR-B04-2 (NEW)
C1-1,3,5
C2-1,3,5
C2-8
C1-8
C2-6
C1-6
C2-4
C1-4
C2-2C1-2
C1-9 a,D bb
C1-10
B,C2-7 a a
111-AC-B0423
C2-9,11
A,C1-7A,C1-7
A,C2-7 b,D
1. FIRE STOP SHALL BE PROVIDED AT ALL LOCATIONS WHERE ELECTRICAL EQUIPMENT OR
SYSTEMS PENETRATE FIRE RATED WALLS. SEE ARCHITECTURAL PLANS FOR RATED WALL
LOCATIONS.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. ONE-LINE DIAGRAMS ARE MEANT TO SHOW ONLY ELECTRICAL RELATIONSHIPS AND
THEREFORE MAY NOT INCLUDE ALL REQUIRED EQUIPMENT, DEVICES AND ACCESSORIES.
4. CONTRACTOR TO VERIFY EXISTING EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
5. EXISTING FIRE ALARM AND OTHER LOW VOLTAGE SYSTEM EQUIPMENT IN THE EXISTING
TR ROOMS OR SPACES IMPACTED BY THE NEW TR ROOMS SHALL BE COORDINATED WITH
THE VA COR FOR WORK REQUIRED.
6. NOT ALL KEYNOTES ARE USED ON THE SHEET.
7. PROVIDE 200% NEUTRAL FOR ALL BRANCH CIRCUITS FEEDING RACKS AND FEEDERS
DOWN STREAM FROM K-13 RATED TRANSFORMERS.
8. FOR MECHANICAL INDOOR AND OUTDOOR UNITS FOR TR ROOMS, PROVIDE (1)3/4"
CONDUIT FOR CONTROL WIRING BETWEEN INDOOR AND OUTDOOR UNITS. CONTROL
WIRING BY MECHANICAL CONTROL CONTRACTOR.
9. FULL TONE, DASHED OR HATCEHD ITEMS INDICATE TO BE DEMOED. HALF TONE ITEMS
INDICATE TO REMAIN.
10. PANELBOARDS SERVING LOADS LOCATED ON ROOF AND BUILDING EXTERIOR SHALL BE
PROVIDED WITH SURGE PROTECTION DEVICES.
1. UNLESS OTHERWISE NOTED, EXTEND BRANCH CIRCUITS IN THE TR ROOM TO
THE FOLLOWING BRANCH PANELBOARDS.
208/120V PANEL:
EUL-TR-B04-1 - CRITICAL POWER
EUL-TR-B04-2 - CRITICAL POWER
EUL-TR-B06-1 - CRITICAL POWER
EUL-TR-B06-2 - CRITICAL POWER
EUL-TR-B06-3 - CRITICAL POWER
EUL-TR-B06-4 - CRITICAL POWER
111-HM-1-1 - EQUIPMENT
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/2
/2
:2
:3
A
M
BLDG 111 - BASEMENT OVERALL & ENLARGED -
ELECTRICAL NEW WORK
YW SM
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-EP101
5000 W. NATIONAL AVENUE MILWAUKEE, WI
1" = 30'-0"
BLDG 111 - BASEMENT - OVERALL ELECTRICAL NEW WORK
1/2" = 1'-0"
BLDG 111 - BASEMENT - ENLARGED ELECTRICAL NEW WORK - ROOM B0610E
3/8" = 1'-0"
BLDG 111 - BASEMENT - ENLARGED ELECTRICAL NEW WORK - ROOM B0622
1/2" = 1'-0"
BLDG 111 - BASEMENT - ENLARGED ELECTRICAL NEW WORK - ROOM B0423
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1 NEMA L21-20R MOUNT ON CABLE TRAY ABOVE RACK. COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. FEEDER: (3) #12, (1) #10N, (1) #12G
3/4"C.
2 NEMA L21-30R MOUNT ON CABLE TRAY ABOVE RACK. COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. FEEDER: (3)#10, (1) #8N, (1) #10G, 3/4"C.
3 SURFACE MOUNT J-BOX (60A) FOR POWER TO RACK PDU. FEEDER: (3)#4, (1)#1/0N,
(1)#8G, 2"C. MOUNT J-BOX ON CABLE TRAY ABOVE RACK, COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. SEE E-500 FOR MORE INFORMATION.
4 FIRE ALARM RELAY FOR CONNECTION TO ACCESS CONTROL PANEL IN ROOM.
COORDINATE EXACT LOCATION WITH ACCESS CONTROL CONTRACTOR.
5 J-BOX FOR POWER TO ACCESS CONTROL POWER SUPPLY AT DOOR. COORDINATE
EXACT LOCATION WITH DOOR ACCESS CONTROL AND DOOR HARDWARE.
6 MOUNT J-BOX (60A) ON CABLE TRAY ABOVE RACK FOR POWER TO RACK PDU.
FEEDER: (3)#4, (1)#1/0N, (1)#8G, 2"C. MOUNT J-BOX ON CABLE TRAY ABOVE RACK,
COORDINATE EXACT LOCATION/PLACEMENT WITH OTHER TRADES. SEE E-500 FOR
MORE INFORMATION.
7 NEW PANEL IN EXISTING PANEL LOCATION. RECONNECT ALL EXISTING CIRCUITS TO
NEW CIRCUIT BREAKERS IN PANEL. VERIFY EXACT LOAD AND LOCATION IN FIELD.
8 CONNECT NEW RECEPTACLE TO EXISTING POWER PANEL SERVING THE AREA. USE
20AMP SPARE CIRCUIT BREAKER OR PROVIDE NEW AS NEEDED.
9 CONNECT NEW PANEL TO BUILDING DISTRIBUTION PANEL. PROVIDE NEW CIRCUIT
BREAKER IN EXISTING PANEL. NEW BREAKER TYPE TO MATCH EXISTING.
10 RELOCATED PANEL. RECONNECT ALL CIRCUITS TO EXISTING LOADS. COORDINATE
EXACT BRANCH CIRCUIT INFORMATION IN FIELD AND COORDINATE
LOCATION/PLACEMENT WITH THE COR.
11 PROVIDE NEW CIRCUIT BREAKER IN AVAILABLE SPACES IN EXISTING DISTRIBUTION.
PROVIDE SEPARATE CIRCUIT BREAKER ENCLOSURE IF SPACES ARE NOT AVAILABLE.
12 INDOOR UNIT POWERED BY OUTDOOR UNIT. PROVIDE 20A/2P MOTOR RATED MANUAL
TOGGLE CONTROLLER FOR CONTROL OF EQUIPMENT.
15 60AS/NF/2P, NEMA 3R DISCONNECT SWITCH. FEEDER: (3) #10, #10G, 3/4"C. PROVIDE
(2) 3/4" CONDUIT FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
16 30AS/NF/2P, NEMA 3R DISCONNECT SWITCH. FEEDER: (2) #10, #10G, 3/4"C. PROVIDE
(2) 3/4" CONDUITS FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
18 SEE EQUIPMENT SCHEDULE FOR FEEDER AND DISCONNECT INFORMATION.
20 NEW PANEL AT EXISTING PANEL LOCATION. EXTEND AND RECONNECT EXISTING
INCOMING AND OUTGOING FEEDERS. NEW CIRCUIT BREAKER RATING TO MATCH
EXISTING.
21 NEW MEDIUM VOLTAGE FEEDER IN EXISTING SPARE CONDUIT BETWEEN THE
EXISTING VAULT AND BUILDING 115. PROVIDE NEW CONDUIT IN BUILDING 115 TO THE
NEW CIRCUIT BREAKER IN EXISTING MEDIUM VOLTAGE SWITCHGEAR. SEE SHEET
111-EP114 FOR ADDITIONAL INFORMATION.
22 ROUTE CONDUIT ON WALL TO A NEW PULLBOX 24"X18"X12" ON CEILING.
23 STUB CONDUIT TO ROOM. SEE SHEET 111-EP114 FOR ADDITIONAL INFORMATION.
24 L5-30R RECEPTACLE MOUNTED ON WALL. COORDINATE LOCATION AND MOUNTING
HEIGHT WITH WALL ENCLOSURE PLACEMENT. FEEDER: 2#10, #8N, #10G, 3/4"C.
25 NEW BI-FUEL GENERATOR WITH DIESEL AND NATURAL GAS. SEE MECHANICAL FOR
GAS LINE INFORMATION. BASE MOUNTED DIESEL STORAGE TANK AND
WEATHERPROOF ENCLOSURE. PROVIDE PLATFORM AND LADDER FOR ACCESS AND
MAINTENANCE.
26 SEE CIVIL AND STRUCTURAL FOR FENCE AND PAD DETAILS.
27 UNISTRUT MOUNT PORTABLE GENERATOR AND LOAD BANK CONNECTION BOX.
COORDINATE EXACT LOCATION WITH VA COR.
28 NEW NEMA 3R RATED EQUIPMENT MOUNT ON CONCRETE PAD. EXTEND EXISTING
CONCRETE PAD.
29 MOUNT GENERATOR DISTRIBUTION PANEL ON CONCRETE PAD.
30 SEE EQUIPMENT SCHEDULE FOR FEEDER AND DISCONNECT INFORMATION. PROVIDE
(2) 3/4" CONDUITS FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
32 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (9) 4" AND (3) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
33 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (6) 4" AND (2) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
34 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (3) 4" AND (1) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
35 RECEPTACLE MOUNTED ON ROOF ADJACENT TO MECHANICAL EQUIPMENT
DISCONNECT.
36 ROUTE CONDUIT IN ABOVE CEILING SPACE AND SUPPORT FROM STRUCTURE.
39 CONTRACTOR TO REMOVE CEILING TILES AND/OR CEILING MOUNTED DEVICES AS
NEEDED TO ALLOW NEW CONDUIT INSTALLATION. REINSTALL CEILING TILES AND
DEVICES AFTER COMPLETE CONDUIT INSTALLATION.
40 MOUNT RECEPTACLE ON EXISTING CABLE TRAY.
41 PROVIDE CONNECTION TO EXISTING LIGHTNING PROTECTION SYSTEM ON ROOF.
BONDING CONDUCTOR TO MATCH EXISTING.
42 PROVIDE LIGHTNING PROTECTION ON GENERATOR ENCLOSURE AND BOND TO
FENCE/POST WHERE APPLICABLE. SEE SPECIFICATION SECTION FOR DETAILS.
43 PROVIDE LIGHTNING PROTECTION ON GENERATOR ENCLOSURE AND BOND TO
FENCE/POST WHERE APPLICABLE. SEE SPECIFICATION SECTION FOR DETAILS.
44 INSTALL BOTH OUTLETS IN COMMON BACKBOX AND COVERPLATE.
45 PENDANT MOUNT TRANSFORMER FROM CEILING. PROVIDE NECESSARY MOUNTING
BRACKETS. ELECTRICAL CONTRACTOR TO DETERMINE BEST LOCATION FOR
MOUNTING.
46 CONDUITS UP TO CEILING. COORDINATE EXACT LOCATION IN FIELD.
47 CONDUITS ROUTED ABOVE CEILING SPACES. COORDINATE EXACT LOCATION IN
FIELD.
49 ROUTE CONDUIT FROM ELEC E-34EC THROUGH BASEMENT CEILING TO BENEATH
THE TR AND STUB UP FROM BELOW.
50 STUB UP CONDUITS FROM ELECTRICAL ROOM BELOW TO CEILING OF FIRST FLOOR
AND ROUTE TO TELECOM ROOMS.
51 CONDUITS ARE ROUTED UP THE COLUMN TO THE TR ON THE FLOOR ABOVE.
52 ROUTE CONDUITS ON EXTERIOR ROOF AND WALLS. COORDINATE EXACT LOCATION
IN FIELD.
53 CONTRACTOR SHALL PROVIDE GENERATOR ENCLOURE AND SETBACK PER VA
D N
F D F D
DN
DN
UP
DN
DN
UP
DN
DN
D N
1. FIRE STOP SHALL BE PROVIDED AT ALL LOCATIONS WHERE ELECTRICAL EQUIPMENT OR
SYSTEMS PENETRATE FIRE RATED WALLS. SEE ARCHITECTURAL PLANS FOR RATED WALL
LOCATIONS.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. ONE-LINE DIAGRAMS ARE MEANT TO SHOW ONLY ELECTRICAL RELATIONSHIPS AND
THEREFORE MAY NOT INCLUDE ALL REQUIRED EQUIPMENT, DEVICES AND ACCESSORIES.
4. CONTRACTOR TO VERIFY EXISTING EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
5. EXISTING FIRE ALARM AND OTHER LOW VOLTAGE SYSTEM EQUIPMENT IN THE EXISTING
TR ROOMS OR SPACES IMPACTED BY THE NEW TR ROOMS SHALL BE COORDINATED WITH
THE VA COR FOR WORK REQUIRED.
6. NOT ALL KEYNOTES ARE USED ON THE SHEET.
7. PROVIDE 200% NEUTRAL FOR ALL BRANCH CIRCUITS FEEDING RACKS AND FEEDERS
DOWN STREAM FROM K-13 RATED TRANSFORMERS.
8. FOR MECHANICAL INDOOR AND OUTDOOR UNITS FOR TR ROOMS, PROVIDE (1)3/4"
CONDUIT FOR CONTROL WIRING BETWEEN INDOOR AND OUTDOOR UNITS. CONTROL
WIRING BY MECHANICAL CONTROL CONTRACTOR.
9. FULL TONE, DASHED OR HATCEHD ITEMS INDICATE TO BE DEMOED. HALF TONE ITEMS
INDICATE TO REMAIN.
10. PANELBOARDS SERVING LOADS LOCATED ON ROOF AND BUILDING EXTERIOR SHALL BE
PROVIDED WITH SURGE PROTECTION DEVICES.
ROUTE CONDUIT ON CEILING.
SEE RISER DIAGRAM ON SHEET
111-EP114 FOR CONDUITS AND
FEEDER INFORMATION.
TO BUILDING 115
SWITCHGEAR
SEE SHEET 111-EP100
AND 111-EP114
XFMR 1 XFMR 2 XFMR 3 XFMR 4
EDH-211-CR-7
DH-B02-4
EDH-106-LS-1ATS-
1LS
ATS-
2CR
ATS-
4EQ
ATS-
3EQ
SG-1LS SG-1N
SG-2CR SG-2N
EDH-108-LS-6
EDH-108-LS-6
EDH-108-LS-6
DH-B02-1
DH-B02-2
EDH-304-Q-3
SG-4N SG-3N
SG-4EQ SG-3EQ
EDH-204-CR-5 EDH-307-Q-4PULLBOX
PULL BOX
EPH-CR-B02-2
EPH-LS-B02-1
EPL-CR-B02-1
EPH-CR-B02-1 TS-X TS-XX
ATS-11 ATS-8 ATS-7 ATS-10 ATS-9
UP TO LEVEL 01 RM. 1288
SEE LEVEL 1 PLAN ON
THIS SHEET
B0245
MER ROOM
B0280B
GENERATOR
ROOM
B0280
CORRIDOR
B0280A
SWITCHGEAR
ROOM
B0255A
SWITCHBOARD
ROOM
B0255
TRANSFORMER
ROOM
COORDINATE EXACT CONDUIT
ENTRY LOCATION
UP TO LEVEL 1 RM 1237
SEE LEVEL 1 PLAN ON
THIS SHEET
PB
ROUTE CONDUIT
TIGHT ON STRUCTURE
CEILING
EXISTING PULLBOX ON WALL
PROVIDE CONDUIT ON WALL
FROM PULLBOX TO CEILING
FOR NEW FEEDERS
PB
SEE BASEMENT PLAN
ON THIS SHEET
PB
PB
STORAGE
SEE BASEMENT PLAN
ON THIS SHEET
PB
CLINICAL
SUPPLIES
ROUTE CONDUIT
IN CEILING SPACE
MINIMUM 12" FROM
OTHER POWER
CONDUITS
PB
ELECTRICAL ROOM
MCR
1474J
DEMARC ROOM
TELECOMMUNICATIONS
RM.
VERIFY DOORS AND WALLS
TO MAKE SURE THERE ARE
ADEQUATE HEIGHT AND
WIDTH PRIOR TO EQUIPMENT
INSTALLATION, CUT
WALLS/REMOVE DOORS AS
NEEDED
EQUIPMENT PULLOUT PATH
SUBSTATION ROOM
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/2
/2
:2
:3
A
M
BLDG 111 - BASEMENT AND FIRST FLOOR -
ELECTRICAL CONDUIT NEW WORK
YW SM
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-EP102
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
3/32" = 1'-0"
BLDG 111 - BASEMENT - OVERALL ELECTRICAL CONDUIT NEW WORK
1 NEMA L21-20R MOUNT ON CABLE TRAY ABOVE RACK. COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. FEEDER: (3) #12, (1) #10N, (1) #12G
3/4"C.
2 NEMA L21-30R MOUNT ON CABLE TRAY ABOVE RACK. COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. FEEDER: (3)#10, (1) #8N, (1) #10G, 3/4"C.
3 SURFACE MOUNT J-BOX (60A) FOR POWER TO RACK PDU. FEEDER: (3)#4, (1)#1/0N,
(1)#8G, 2"C. MOUNT J-BOX ON CABLE TRAY ABOVE RACK, COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. SEE E-500 FOR MORE INFORMATION.
4 FIRE ALARM RELAY FOR CONNECTION TO ACCESS CONTROL PANEL IN ROOM.
COORDINATE EXACT LOCATION WITH ACCESS CONTROL CONTRACTOR.
5 J-BOX FOR POWER TO ACCESS CONTROL POWER SUPPLY AT DOOR. COORDINATE
EXACT LOCATION WITH DOOR ACCESS CONTROL AND DOOR HARDWARE.
6 MOUNT J-BOX (60A) ON CABLE TRAY ABOVE RACK FOR POWER TO RACK PDU.
FEEDER: (3)#4, (1)#1/0N, (1)#8G, 2"C. MOUNT J-BOX ON CABLE TRAY ABOVE RACK,
COORDINATE EXACT LOCATION/PLACEMENT WITH OTHER TRADES. SEE E-500 FOR
MORE INFORMATION.
7 NEW PANEL IN EXISTING PANEL LOCATION. RECONNECT ALL EXISTING CIRCUITS TO
NEW CIRCUIT BREAKERS IN PANEL. VERIFY EXACT LOAD AND LOCATION IN FIELD.
8 CONNECT NEW RECEPTACLE TO EXISTING POWER PANEL SERVING THE AREA. USE
20AMP SPARE CIRCUIT BREAKER OR PROVIDE NEW AS NEEDED.
9 CONNECT NEW PANEL TO BUILDING DISTRIBUTION PANEL. PROVIDE NEW CIRCUIT
BREAKER IN EXISTING PANEL. NEW BREAKER TYPE TO MATCH EXISTING.
10 RELOCATED PANEL. RECONNECT ALL CIRCUITS TO EXISTING LOADS. COORDINATE
EXACT BRANCH CIRCUIT INFORMATION IN FIELD AND COORDINATE
LOCATION/PLACEMENT WITH THE COR.
11 PROVIDE NEW CIRCUIT BREAKER IN AVAILABLE SPACES IN EXISTING DISTRIBUTION.
PROVIDE SEPARATE CIRCUIT BREAKER ENCLOSURE IF SPACES ARE NOT AVAILABLE.
12 INDOOR UNIT POWERED BY OUTDOOR UNIT. PROVIDE 20A/2P MOTOR RATED MANUAL
TOGGLE CONTROLLER FOR CONTROL OF EQUIPMENT.
15 60AS/NF/2P, NEMA 3R DISCONNECT SWITCH. FEEDER: (3) #10, #10G, 3/4"C. PROVIDE
(2) 3/4" CONDUIT FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
16 30AS/NF/2P, NEMA 3R DISCONNECT SWITCH. FEEDER: (2) #10, #10G, 3/4"C. PROVIDE
(2) 3/4" CONDUITS FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
18 SEE EQUIPMENT SCHEDULE FOR FEEDER AND DISCONNECT INFORMATION.
20 NEW PANEL AT EXISTING PANEL LOCATION. EXTEND AND RECONNECT EXISTING
INCOMING AND OUTGOING FEEDERS. NEW CIRCUIT BREAKER RATING TO MATCH
EXISTING.
21 NEW MEDIUM VOLTAGE FEEDER IN EXISTING SPARE CONDUIT BETWEEN THE
EXISTING VAULT AND BUILDING 115. PROVIDE NEW CONDUIT IN BUILDING 115 TO THE
NEW CIRCUIT BREAKER IN EXISTING MEDIUM VOLTAGE SWITCHGEAR. SEE SHEET
111-EP114 FOR ADDITIONAL INFORMATION.
22 ROUTE CONDUIT ON WALL TO A NEW PULLBOX 24"X18"X12" ON CEILING.
23 STUB CONDUIT TO ROOM. SEE SHEET 111-EP114 FOR ADDITIONAL INFORMATION.
24 L5-30R RECEPTACLE MOUNTED ON WALL. COORDINATE LOCATION AND MOUNTING
HEIGHT WITH WALL ENCLOSURE PLACEMENT. FEEDER: 2#10, #8N, #10G, 3/4"C.
25 NEW BI-FUEL GENERATOR WITH DIESEL AND NATURAL GAS. SEE MECHANICAL FOR
GAS LINE INFORMATION. BASE MOUNTED DIESEL STORAGE TANK AND
WEATHERPROOF ENCLOSURE. PROVIDE PLATFORM AND LADDER FOR ACCESS AND
MAINTENANCE.
26 SEE CIVIL AND STRUCTURAL FOR FENCE AND PAD DETAILS.
27 UNISTRUT MOUNT PORTABLE GENERATOR AND LOAD BANK CONNECTION BOX.
COORDINATE EXACT LOCATION WITH VA COR.
28 NEW NEMA 3R RATED EQUIPMENT MOUNT ON CONCRETE PAD. EXTEND EXISTING
CONCRETE PAD.
29 MOUNT GENERATOR DISTRIBUTION PANEL ON CONCRETE PAD.
30 SEE EQUIPMENT SCHEDULE FOR FEEDER AND DISCONNECT INFORMATION. PROVIDE
(2) 3/4" CONDUITS FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
32 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (9) 4" AND (3) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
33 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (6) 4" AND (2) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
34 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (3) 4" AND (1) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
35 RECEPTACLE MOUNTED ON ROOF ADJACENT TO MECHANICAL EQUIPMENT
DISCONNECT.
36 ROUTE CONDUIT IN ABOVE CEILING SPACE AND SUPPORT FROM STRUCTURE.
39 CONTRACTOR TO REMOVE CEILING TILES AND/OR CEILING MOUNTED DEVICES AS
NEEDED TO ALLOW NEW CONDUIT INSTALLATION. REINSTALL CEILING TILES AND
DEVICES AFTER COMPLETE CONDUIT INSTALLATION.
40 MOUNT RECEPTACLE ON EXISTING CABLE TRAY.
41 PROVIDE CONNECTION TO EXISTING LIGHTNING PROTECTION SYSTEM ON ROOF.
BONDING CONDUCTOR TO MATCH EXISTING.
42 PROVIDE LIGHTNING PROTECTION ON GENERATOR ENCLOSURE AND BOND TO
FENCE/POST WHERE APPLICABLE. SEE SPECIFICATION SECTION FOR DETAILS.
43 PROVIDE LIGHTNING PROTECTION ON GENERATOR ENCLOSURE AND BOND TO
FENCE/POST WHERE APPLICABLE. SEE SPECIFICATION SECTION FOR DETAILS.
44 INSTALL BOTH OUTLETS IN COMMON BACKBOX AND COVERPLATE.
45 PENDANT MOUNT TRANSFORMER FROM CEILING. PROVIDE NECESSARY MOUNTING
BRACKETS. ELECTRICAL CONTRACTOR TO DETERMINE BEST LOCATION FOR
MOUNTING.
46 CONDUITS UP TO CEILING. COORDINATE EXACT LOCATION IN FIELD.
47 CONDUITS ROUTED ABOVE CEILING SPACES. COORDINATE EXACT LOCATION IN
FIELD.
49 ROUTE CONDUIT FROM ELEC E-34EC THROUGH BASEMENT CEILING TO BENEATH
THE TR AND STUB UP FROM BELOW.
50 STUB UP CONDUITS FROM ELECTRICAL ROOM BELOW TO CEILING OF FIRST FLOOR
AND ROUTE TO TELECOM ROOMS.
51 CONDUITS ARE ROUTED UP THE COLUMN TO THE TR ON THE FLOOR ABOVE.
52 ROUTE CONDUITS ON EXTERIOR ROOF AND WALLS. COORDINATE EXACT LOCATION
IN FIELD.
53 CONTRACTOR SHALL PROVIDE GENERATOR ENCLOURE AND SETBACK PER VA
PSRDM REQUIREMENTS.
1" = 20'-0"
BLDG 111 - FIRST FLOOR - OVERALL ELECTRICAL CONDUIT NEW WORK
O. H D OOR
W I N D OW
DN
IT
DN
DN
UP
D N
DN
DN
DN
J J
S M
FAR
J
J J
S M
FARJ
S M
FAR
J
ELEC. NEW WORK GENERAL NOTES ELEC. NEW WORK KEYNOTES
BRANCH CIRCUITING NOTES
S M
J J
FAR
J
S M
111-EP103
4111-EP103
111-EP103
SUBSTATION ROOM
TELECOMMUNICATIONS
RM.
1537B
TELECOMMUNICATIONS
RM.
111-EP102
DEMARC ROOM
TELECOMMUNICATIONS
RM.
111-EP103
ELECTRICAL ROOM
TO INDOOR UNIT SERVING ROOM,
SEE EQUIPMENT SCHEDULE FOR
CONNECTIONS AND FEEDER
SIZING
TO INDOOR UNIT SERVING ROOM,
SEE EQUIPMENT SCHEDULE FOR
CONNECTIONS AND FEEDER
SIZING
TO INDOOR UNIT SERVING ROOM,
SEE EQUIPMENT SCHEDULE FOR
CONNECTIONS AND FEEDER SIZING
EUL-TR-16-2 (NEW)EUL-TR-16-1 (NEW)
C2-8
C1-7
C2-14
C2-2,4,6
C1-2,4,6
C1-8
C2-10C1-9
C1-10
C1-11
C2-12
A,C1-19
111-AC-1473
TELECOMMUNICATIONS
RM.
C1-18 a,D b b a a
C1-20
A,C2-5
A,C2-5
A,C1-19
C2-1,3 b,D
EUL-TR-15-2 (NEW) EUL-TR-15-1 (NEW)
C1-6
C2-10
C1-8
C1-2
C2-6
C1-4
C2-8
C2-12
A,C1-9
A,C1-9
C1-1,3,5 C2-1,3,5
C2-4
C2-2
A,C2-7
111-AC-1537B
12 6
C1-7 a,D a a b b
C1-10
C2-9,11 b,D
EUL-TR-11-1 (NEW)
EUL-TR-11-2 (NEW)
C2-2,4,6 C1-2,4,6
C2-8
C1-7
C2-10 C1-8
C2-5
C2-7
C1-10 A,C2-9
111-AC-1180
A,C1-1
2 2
C1-11
A,C1-1
C1-12
C2-1,3 a,Db,D b a b
1. FIRE STOP SHALL BE PROVIDED AT ALL LOCATIONS WHERE ELECTRICAL EQUIPMENT OR
SYSTEMS PENETRATE FIRE RATED WALLS. SEE ARCHITECTURAL PLANS FOR RATED WALL
LOCATIONS.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. ONE-LINE DIAGRAMS ARE MEANT TO SHOW ONLY ELECTRICAL RELATIONSHIPS AND
THEREFORE MAY NOT INCLUDE ALL REQUIRED EQUIPMENT, DEVICES AND ACCESSORIES.
4. CONTRACTOR TO VERIFY EXISTING EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
5. EXISTING FIRE ALARM AND OTHER LOW VOLTAGE SYSTEM EQUIPMENT IN THE EXISTING
TR ROOMS OR SPACES IMPACTED BY THE NEW TR ROOMS SHALL BE COORDINATED WITH
THE VA COR FOR WORK REQUIRED.
6. NOT ALL KEYNOTES ARE USED ON THE SHEET.
7. PROVIDE 200% NEUTRAL FOR ALL BRANCH CIRCUITS FEEDING RACKS AND FEEDERS
DOWN STREAM FROM K-13 RATED TRANSFORMERS.
8. FOR MECHANICAL INDOOR AND OUTDOOR UNITS FOR TR ROOMS, PROVIDE (1)3/4"
CONDUIT FOR CONTROL WIRING BETWEEN INDOOR AND OUTDOOR UNITS. CONTROL
WIRING BY MECHANICAL CONTROL CONTRACTOR.
9. FULL TONE, DASHED OR HATCEHD ITEMS INDICATE TO BE DEMOED. HALF TONE ITEMS
INDICATE TO REMAIN.
10. PANELBOARDS SERVING LOADS LOCATED ON ROOF AND BUILDING EXTERIOR SHALL BE
PROVIDED WITH SURGE PROTECTION DEVICES.
1. UNLESS OTHERWISE NOTED, EXTEND BRANCH CIRCUITS IN THE TR ROOM TO
THE FOLLOWING BRANCH PANELBOARDS.
208/120V PANEL:
EUL-TR-11-1 - CRITICAL POWER
EUL-TR-11-2 - CRITICAL POWER
EUL-TR-15-1 - CRITICAL POWER
EUL-TR-15-2 - CRITICAL POWER
EUL-TR-16-1 - CRITICAL POWER
EUL-TR-16-2 - CRITICAL POWER
111-ICC-PDUA - CRITICAL POWER
111-ICC-PDUB - CRITICAL POWER
111-HM-B-1 - EQUIPMENT
PA-1,3,5 PB-1,3,5
6 6
111-ICC PDU-A (NEW)
111-ICC PDU-B (NEW)
PA-2PB-2PA-4
A,PB-12 A,PB-12
A,PA-7
PA-9
PB-6PA-10
A,PA-7
PB-8
PA-8
PB-10
A,PA-7
A,PB-12
PA-6
PB-4
111-AC-1470-A
111-AC-1470-B
a,D bab a b a
PA-11
PB-7,9
PB-11,13
b,D
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/2
/2
:2
:4
A
M
BLDG 111 - FIRST FLOOR OVERALL & ENLARGED
- ELECTRICAL NEW WORK
YW SM
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-EP103
5000 W. NATIONAL AVENUE MILWAUKEE, WI
1" = 30'-0"
BLDG 111 - FIRST FLOOR - OVERALL ELECTRICAL NEW WORK
3/8" = 1'-0"
BLDG 111 - FIRST FLOOR - ENLARGED ELECTRICAL NEW WORK -
ROOM 1473
3/8" = 1'-0"
BLDG 111 - FIRST FLOOR - ENLARGED ELECTRICAL NEW WORK -
ROOM 1537B
3/8" = 1'-0"
BLDG 111 - FIRST FLOOR - ENLARGED ELECTRICAL NEW WORK -
ROOM 1180
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1 NEMA L21-20R MOUNT ON CABLE TRAY ABOVE RACK. COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. FEEDER: (3) #12, (1) #10N, (1) #12G
3/4"C.
2 NEMA L21-30R MOUNT ON CABLE TRAY ABOVE RACK. COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. FEEDER: (3)#10, (1) #8N, (1) #10G, 3/4"C.
3 SURFACE MOUNT J-BOX (60A) FOR POWER TO RACK PDU. FEEDER: (3)#4, (1)#1/0N,
(1)#8G, 2"C. MOUNT J-BOX ON CABLE TRAY ABOVE RACK, COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. SEE E-500 FOR MORE INFORMATION.
4 FIRE ALARM RELAY FOR CONNECTION TO ACCESS CONTROL PANEL IN ROOM.
COORDINATE EXACT LOCATION WITH ACCESS CONTROL CONTRACTOR.
5 J-BOX FOR POWER TO ACCESS CONTROL POWER SUPPLY AT DOOR. COORDINATE
EXACT LOCATION WITH DOOR ACCESS CONTROL AND DOOR HARDWARE.
6 MOUNT J-BOX (60A) ON CABLE TRAY ABOVE RACK FOR POWER TO RACK PDU.
FEEDER: (3)#4, (1)#1/0N, (1)#8G, 2"C. MOUNT J-BOX ON CABLE TRAY ABOVE RACK,
COORDINATE EXACT LOCATION/PLACEMENT WITH OTHER TRADES. SEE E-500 FOR
MORE INFORMATION.
7 NEW PANEL IN EXISTING PANEL LOCATION. RECONNECT ALL EXISTING CIRCUITS TO
NEW CIRCUIT BREAKERS IN PANEL. VERIFY EXACT LOAD AND LOCATION IN FIELD.
8 CONNECT NEW RECEPTACLE TO EXISTING POWER PANEL SERVING THE AREA. USE
20AMP SPARE CIRCUIT BREAKER OR PROVIDE NEW AS NEEDED.
9 CONNECT NEW PANEL TO BUILDING DISTRIBUTION PANEL. PROVIDE NEW CIRCUIT
BREAKER IN EXISTING PANEL. NEW BREAKER TYPE TO MATCH EXISTING.
10 RELOCATED PANEL. RECONNECT ALL CIRCUITS TO EXISTING LOADS. COORDINATE
EXACT BRANCH CIRCUIT INFORMATION IN FIELD AND COORDINATE
LOCATION/PLACEMENT WITH THE COR.
11 PROVIDE NEW CIRCUIT BREAKER IN AVAILABLE SPACES IN EXISTING DISTRIBUTION.
PROVIDE SEPARATE CIRCUIT BREAKER ENCLOSURE IF SPACES ARE NOT AVAILABLE.
12 INDOOR UNIT POWERED BY OUTDOOR UNIT. PROVIDE 20A/2P MOTOR RATED MANUAL
TOGGLE CONTROLLER FOR CONTROL OF EQUIPMENT.
15 60AS/NF/2P, NEMA 3R DISCONNECT SWITCH. FEEDER: (3) #10, #10G, 3/4"C. PROVIDE
(2) 3/4" CONDUIT FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
16 30AS/NF/2P, NEMA 3R DISCONNECT SWITCH. FEEDER: (2) #10, #10G, 3/4"C. PROVIDE
(2) 3/4" CONDUITS FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
18 SEE EQUIPMENT SCHEDULE FOR FEEDER AND DISCONNECT INFORMATION.
20 NEW PANEL AT EXISTING PANEL LOCATION. EXTEND AND RECONNECT EXISTING
INCOMING AND OUTGOING FEEDERS. NEW CIRCUIT BREAKER RATING TO MATCH
EXISTING.
21 NEW MEDIUM VOLTAGE FEEDER IN EXISTING SPARE CONDUIT BETWEEN THE
EXISTING VAULT AND BUILDING 115. PROVIDE NEW CONDUIT IN BUILDING 115 TO THE
NEW CIRCUIT BREAKER IN EXISTING MEDIUM VOLTAGE SWITCHGEAR. SEE SHEET
111-EP114 FOR ADDITIONAL INFORMATION.
22 ROUTE CONDUIT ON WALL TO A NEW PULLBOX 24"X18"X12" ON CEILING.
23 STUB CONDUIT TO ROOM. SEE SHEET 111-EP114 FOR ADDITIONAL INFORMATION.
24 L5-30R RECEPTACLE MOUNTED ON WALL. COORDINATE LOCATION AND MOUNTING
HEIGHT WITH WALL ENCLOSURE PLACEMENT. FEEDER: 2#10, #8N, #10G, 3/4"C.
25 NEW BI-FUEL GENERATOR WITH DIESEL AND NATURAL GAS. SEE MECHANICAL FOR
GAS LINE INFORMATION. BASE MOUNTED DIESEL STORAGE TANK AND
WEATHERPROOF ENCLOSURE. PROVIDE PLATFORM AND LADDER FOR ACCESS AND
MAINTENANCE.
26 SEE CIVIL AND STRUCTURAL FOR FENCE AND PAD DETAILS.
27 UNISTRUT MOUNT PORTABLE GENERATOR AND LOAD BANK CONNECTION BOX.
COORDINATE EXACT LOCATION WITH VA COR.
28 NEW NEMA 3R RATED EQUIPMENT MOUNT ON CONCRETE PAD. EXTEND EXISTING
CONCRETE PAD.
29 MOUNT GENERATOR DISTRIBUTION PANEL ON CONCRETE PAD.
30 SEE EQUIPMENT SCHEDULE FOR FEEDER AND DISCONNECT INFORMATION. PROVIDE
(2) 3/4" CONDUITS FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
32 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (9) 4" AND (3) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
33 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (6) 4" AND (2) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
34 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (3) 4" AND (1) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
35 RECEPTACLE MOUNTED ON ROOF ADJACENT TO MECHANICAL EQUIPMENT
DISCONNECT.
36 ROUTE CONDUIT IN ABOVE CEILING SPACE AND SUPPORT FROM STRUCTURE.
39 CONTRACTOR TO REMOVE CEILING TILES AND/OR CEILING MOUNTED DEVICES AS
NEEDED TO ALLOW NEW CONDUIT INSTALLATION. REINSTALL CEILING TILES AND
DEVICES AFTER COMPLETE CONDUIT INSTALLATION.
40 MOUNT RECEPTACLE ON EXISTING CABLE TRAY.
41 PROVIDE CONNECTION TO EXISTING LIGHTNING PROTECTION SYSTEM ON ROOF.
BONDING CONDUCTOR TO MATCH EXISTING.
42 PROVIDE LIGHTNING PROTECTION ON GENERATOR ENCLOSURE AND BOND TO
FENCE/POST WHERE APPLICABLE. SEE SPECIFICATION SECTION FOR DETAILS.
43 PROVIDE LIGHTNING PROTECTION ON GENERATOR ENCLOSURE AND BOND TO
FENCE/POST WHERE APPLICABLE. SEE SPECIFICATION SECTION FOR DETAILS.
44 INSTALL BOTH OUTLETS IN COMMON BACKBOX AND COVERPLATE.
45 PENDANT MOUNT TRANSFORMER FROM CEILING. PROVIDE NECESSARY MOUNTING
BRACKETS. ELECTRICAL CONTRACTOR TO DETERMINE BEST LOCATION FOR
MOUNTING.
46 CONDUITS UP TO CEILING. COORDINATE EXACT LOCATION IN FIELD.
47 CONDUITS ROUTED ABOVE CEILING SPACES. COORDINATE EXACT LOCATION IN
FIELD.
49 ROUTE CONDUIT FROM ELEC E-34EC THROUGH BASEMENT CEILING TO BENEATH
THE TR AND STUB UP FROM BELOW.
50 STUB UP CONDUITS FROM ELECTRICAL ROOM BELOW TO CEILING OF FIRST FLOOR
AND ROUTE TO TELECOM ROOMS.
51 CONDUITS ARE ROUTED UP THE COLUMN TO THE TR ON THE FLOOR ABOVE.
52 ROUTE CONDUITS ON EXTERIOR ROOF AND WALLS. COORDINATE EXACT LOCATION
IN FIELD.
53 CONTRACTOR SHALL PROVIDE GENERATOR ENCLOURE AND SETBACK PER VA
PSRDM REQUIREMENTS.
3/8" = 1'-0"
BLDG 111 - FIRST FLOOR - ENLARGED ELECTRICAL NEW WORK -
ROOM 1470
S M
PB
S M
S M
S M
1. FIRE STOP SHALL BE PROVIDED AT ALL LOCATIONS WHERE ELECTRICAL EQUIPMENT OR
SYSTEMS PENETRATE FIRE RATED WALLS. SEE ARCHITECTURAL PLANS FOR RATED WALL
LOCATIONS.
2. SEE MECHANICAL SHEETS FOR CONTROL WIRING TO MECHANICAL EQUIPMENT.
3. ONE-LINE DIAGRAMS ARE MEANT TO SHOW ONLY ELECTRICAL RELATIONSHIPS AND
THEREFORE MAY NOT INCLUDE ALL REQUIRED EQUIPMENT, DEVICES AND ACCESSORIES.
4. CONTRACTOR TO VERIFY EXISTING EQUIPMENT AND DEVICE LOCATIONS PRIOR TO BID.
5. EXISTING FIRE ALARM AND OTHER LOW VOLTAGE SYSTEM EQUIPMENT IN THE EXISTING
TR ROOMS OR SPACES IMPACTED BY THE NEW TR ROOMS SHALL BE COORDINATED WITH
THE VA COR FOR WORK REQUIRED.
6. NOT ALL KEYNOTES ARE USED ON THE SHEET.
7. PROVIDE 200% NEUTRAL FOR ALL BRANCH CIRCUITS FEEDING RACKS AND FEEDERS
DOWN STREAM FROM K-13 RATED TRANSFORMERS.
8. FOR MECHANICAL INDOOR AND OUTDOOR UNITS FOR TR ROOMS, PROVIDE (1)3/4"
CONDUIT FOR CONTROL WIRING BETWEEN INDOOR AND OUTDOOR UNITS. CONTROL
WIRING BY MECHANICAL CONTROL CONTRACTOR.
9. FULL TONE, DASHED OR HATCEHD ITEMS INDICATE TO BE DEMOED. HALF TONE ITEMS
INDICATE TO REMAIN.
10. PANELBOARDS SERVING LOADS LOCATED ON ROOF AND BUILDING EXTERIOR SHALL BE
PROVIDED WITH SURGE PROTECTION DEVICES.
ETRT-1472-2
ETRT-1472-1
111-ATS-CRB (NEW)
ELECTRICAL ROOM
SUBSTATION ROOM
3,b
3,a
3,b
3,b
3,a3,a
3,a b b b b b b ba a aa a a a
D, EUL-LP-1
(NEW)-1
D, EUL-LP-2
(NEW)-1
D, EUL-LP-1
(NEW)-1
D, EUL-LP-2
(NEW)-1
D, EUL-LP-2
(NEW)-1
D, EUL-LP-2
(NEW)-1
D, EUL-LP-2
(NEW)-1
D, EUL-LP-1
(NEW)-1
D, EUL-LP-2
(NEW)-1
D, EUL-LP-1
(NEW)-1
D, EUL-LP-2
(NEW)-1
D, EUL-LP-1
(NEW)-1
D, EUL-LP-1
(NEW)-1
D, EUL-LP-1
(NEW)-1
D, EUL-LP-2
(NEW)-2
D, EUL-LP-1
(NEW)-1
D, EUL-LP-2
(NEW)-2
D, EUL-LP-1
(NEW)-1
D, EUL-LP-2
(NEW)-2
D, EUL-LP-1
(NEW)-1
D, EUL-LP-2
(NEW)-2
111-ATS-CRA (NEW)
D2, EUL-LP-1
(NEW)-1
D2, EUL-LP-1
(NEW)-1
b b b a a baa a baa b a a baa a b b a b
D, EUL-LP-1
(NEW)-2
D, EUL-LP-2
(NEW)-3
D, EUL-LP-1
(NEW)-2
D, EUL-LP-2
(NEW)-3
D, EUL-LP-2
(NEW)-3
D, EUL-LP-1
(NEW)-2
D, EUL-LP-2
(NEW)-3
D, EUL-LP-2
(NEW)-3
D, EUL-LP-1
(NEW)-2
D, EUL-LP-1
(NEW)-2
D, EUL-LP-2
(NEW)-3
D, EUL-LP-2
(NEW)-3
D, EUL-LP-1
(NEW)-2
D, EUL-LP-2
(NEW)-3
D, EUL-LP-2
(NEW)-3
D, EUL-LP-2
(NEW)-3
D, EUL-LP-1
(NEW)-2
D, EUL-LP-2
(NEW)-3
D, EUL-LP-2
(NEW)-3
MCR
1474J
111-EP103
111-EP103
EDH-TR-16-A (NEW)
111-AC-1472-A
EUL-PP-1
(NEW)-3
EUL-PP-1
(NEW)-3
EUL-PP-1
(NEW)-5
EUL-PP-1
(NEW)-5
EUL-PP-1
(NEW)-3
EUL-PP-1
(NEW)-1
EUL-PP-1
(NEW)-7
EUL-PP-1
(NEW)-7
EUL-PP-1
(NEW)-1
D, EUL-LP-2
(NEW)-3
D, EUL-LP-2
(NEW)-3
D, EUL-LP-1
(NEW)-2
a a b
EUL-PP-1
(NEW)-9
EDH-TR-16-B (NEW)
EDL-TR-16-2 (NEW)
EDL-TR-16-1 (NEW)
SG-5N (NEW)
EUL-PP-1 (NEW) EUL-LP-2 (NEW)
EUL-LP-1 (NEW)
a b a a ab b111-AC-1471-A
3,b
111-AC-1472-B 111-AC-1471-B
EUL-PP-1
(NEW)-11,13
EUL-PP-1
(NEW)-15,17
EUL-PP-1
(NEW)-14,16
EUL-PP-1
(NEW)-10,12
D, EUL-LP-1
(NEW)-2
D, EUL-LP-1
(NEW)-2
b b
D, EUL-LP-2
(NEW)-3
D, EUL-LP-2
(NEW)-3
a a
EUL-PP-1
(NEW)-18
EUL-PP-1
(NEW)-18
EUL-PP-1
(NEW)-18
EUL-PP-1
(NEW)-18
EUL-PP-1
(NEW)-18
EUL-PP-1
(NEW)-18
EUL-PP-1
(NEW)-18
EUL-PP-1
(NEW)-20
EUL-PP-1
(NEW)-20
EUL-PP-1
(NEW)-20
EUL-PP-1
(NEW)-20
EUL-PP-1
(NEW)-20
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/2
/2
:2
:4
A
M
BLDG 111 - FIRST FLOOR ENLARGED -
ELECTRICAL NEW WORK
YW SM
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-EP104
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1 NEMA L21-20R MOUNT ON CABLE TRAY ABOVE RACK. COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. FEEDER: (3) #12, (1) #10N, (1) #12G
3/4"C.
2 NEMA L21-30R MOUNT ON CABLE TRAY ABOVE RACK. COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. FEEDER: (3)#10, (1) #8N, (1) #10G, 3/4"C.
3 SURFACE MOUNT J-BOX (60A) FOR POWER TO RACK PDU. FEEDER: (3)#4, (1)#1/0N,
(1)#8G, 2"C. MOUNT J-BOX ON CABLE TRAY ABOVE RACK, COORDINATE EXACT
LOCATION/PLACEMENT WITH OTHER TRADES. SEE E-500 FOR MORE INFORMATION.
4 FIRE ALARM RELAY FOR CONNECTION TO ACCESS CONTROL PANEL IN ROOM.
COORDINATE EXACT LOCATION WITH ACCESS CONTROL CONTRACTOR.
5 J-BOX FOR POWER TO ACCESS CONTROL POWER SUPPLY AT DOOR. COORDINATE
EXACT LOCATION WITH DOOR ACCESS CONTROL AND DOOR HARDWARE.
6 MOUNT J-BOX (60A) ON CABLE TRAY ABOVE RACK FOR POWER TO RACK PDU.
FEEDER: (3)#4, (1)#1/0N, (1)#8G, 2"C. MOUNT J-BOX ON CABLE TRAY ABOVE RACK,
COORDINATE EXACT LOCATION/PLACEMENT WITH OTHER TRADES. SEE E-500 FOR
MORE INFORMATION.
7 NEW PANEL IN EXISTING PANEL LOCATION. RECONNECT ALL EXISTING CIRCUITS TO
NEW CIRCUIT BREAKERS IN PANEL. VERIFY EXACT LOAD AND LOCATION IN FIELD.
8 CONNECT NEW RECEPTACLE TO EXISTING POWER PANEL SERVING THE AREA. USE
20AMP SPARE CIRCUIT BREAKER OR PROVIDE NEW AS NEEDED.
9 CONNECT NEW PANEL TO BUILDING DISTRIBUTION PANEL. PROVIDE NEW CIRCUIT
BREAKER IN EXISTING PANEL. NEW BREAKER TYPE TO MATCH EXISTING.
10 RELOCATED PANEL. RECONNECT ALL CIRCUITS TO EXISTING LOADS. COORDINATE
EXACT BRANCH CIRCUIT INFORMATION IN FIELD AND COORDINATE
LOCATION/PLACEMENT WITH THE COR.
11 PROVIDE NEW CIRCUIT BREAKER IN AVAILABLE SPACES IN EXISTING DISTRIBUTION.
PROVIDE SEPARATE CIRCUIT BREAKER ENCLOSURE IF SPACES ARE NOT AVAILABLE.
12 INDOOR UNIT POWERED BY OUTDOOR UNIT. PROVIDE 20A/2P MOTOR RATED MANUAL
TOGGLE CONTROLLER FOR CONTROL OF EQUIPMENT.
15 60AS/NF/2P, NEMA 3R DISCONNECT SWITCH. FEEDER: (3) #10, #10G, 3/4"C. PROVIDE
(2) 3/4" CONDUIT FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
16 30AS/NF/2P, NEMA 3R DISCONNECT SWITCH. FEEDER: (2) #10, #10G, 3/4"C. PROVIDE
(2) 3/4" CONDUITS FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
18 SEE EQUIPMENT SCHEDULE FOR FEEDER AND DISCONNECT INFORMATION.
20 NEW PANEL AT EXISTING PANEL LOCATION. EXTEND AND RECONNECT EXISTING
INCOMING AND OUTGOING FEEDERS. NEW CIRCUIT BREAKER RATING TO MATCH
EXISTING.
21 NEW MEDIUM VOLTAGE FEEDER IN EXISTING SPARE CONDUIT BETWEEN THE
EXISTING VAULT AND BUILDING 115. PROVIDE NEW CONDUIT IN BUILDING 115 TO THE
NEW CIRCUIT BREAKER IN EXISTING MEDIUM VOLTAGE SWITCHGEAR. SEE SHEET
111-EP114 FOR ADDITIONAL INFORMATION.
22 ROUTE CONDUIT ON WALL TO A NEW PULLBOX 24"X18"X12" ON CEILING.
23 STUB CONDUIT TO ROOM. SEE SHEET 111-EP114 FOR ADDITIONAL INFORMATION.
24 L5-30R RECEPTACLE MOUNTED ON WALL. COORDINATE LOCATION AND MOUNTING
HEIGHT WITH WALL ENCLOSURE PLACEMENT. FEEDER: 2#10, #8N, #10G, 3/4"C.
25 NEW BI-FUEL GENERATOR WITH DIESEL AND NATURAL GAS. SEE MECHANICAL FOR
GAS LINE INFORMATION. BASE MOUNTED DIESEL STORAGE TANK AND
WEATHERPROOF ENCLOSURE. PROVIDE PLATFORM AND LADDER FOR ACCESS AND
MAINTENANCE.
26 SEE CIVIL AND STRUCTURAL FOR FENCE AND PAD DETAILS.
27 UNISTRUT MOUNT PORTABLE GENERATOR AND LOAD BANK CONNECTION BOX.
COORDINATE EXACT LOCATION WITH VA COR.
28 NEW NEMA 3R RATED EQUIPMENT MOUNT ON CONCRETE PAD. EXTEND EXISTING
CONCRETE PAD.
29 MOUNT GENERATOR DISTRIBUTION PANEL ON CONCRETE PAD.
30 SEE EQUIPMENT SCHEDULE FOR FEEDER AND DISCONNECT INFORMATION. PROVIDE
(2) 3/4" CONDUITS FOR CONTROL WIRING AND POWER TO INDOOR UNIT.
32 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (9) 4" AND (3) 1" CONDUITS.
SEE SHEET 148-EP101 FOR EXACT CONNECTIONS.
33 UNDERGROUND CONCRETE ENCASED DUCTBANK WITH (6) 4" AND (2) 1"…