RFP Attachment 22 - Drawings 695-21-700 Part 15.pdf
PDF 9 MB Posted
- Solicitation number
- 36C77626R0002
About this file
This document is a comprehensive set of architectural and engineering design plans for fire protection and plumbing systems at a U.S. Department of Veterans Affairs medical facility complex, prepared by Romanyk Consulting and IMEG Corp.
The fire protection plans (drawings 111-FP101 through 111-FP111, 123-FD101 through 123-FP101) detail automatic sprinkler system installations across Building 111 (basement through Level 10) and Building 123 (Level 01), including calculated clean agent fire suppression systems for telecommunications and IT rooms. Key fire protection requirements include NFPA 13 compliance for ordinary hazard occupancies, clean agent system design per NFPA 2001 with automatic and manual fixed total flooding capability, integration with building fire alarm and HVAC systems, room envelope sealing and pressurization testing, and coordination with smoke detectors, manual activation stations, and discharge strobes. The plumbing plans (P-001 through P-102, PS-101) specify domestic cold/hot water systems, sanitary waste and vent piping, floor drains, medical gas systems (oxygen, medical air, vacuum), and condensate drainage across multiple buildings (111, 123, 3, 4, 5, and 6). Standard details address pipe penetrations through fire-rated assemblies, trap arm lengths, hub drains, floor drain installations, and connections to existing underground infrastructure. All work must comply with VA standards, the International Plumbing Code, and NFPA requirements. General notes emphasize contractor responsibility for field verification, coordination with other trades, complete system operability including commissioning, proper labeling, and daily site cleanliness. The specifications reference VA master construction standards and require skilled tradesman installation in accordance with applicable codes.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
D N
D N
ELECTRICAL
SLIDER FENCE
TRENCH
B0012P
LOADING
DOCK
B0457
LOADING
DOCK
OH D OH D OH D
OH D
OH D
O H
D
F D F D
UP
DN
DN
DN
UP
DN
UP DN
DN
UP
DN
DN
DN
UP
DN
DN
DN
FIRE
PUMP
ROOM
KEY NOTES #
111-FP101
111-FP101
111-FP101
B0622
TELECOMMUNICATIONS
RM.
B0610E
TELECOMMUNICATIONS
RM.
B0423
TELECOMMUNICATIONS
RM.
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:5
A
M
BUILDING 111 BASEMENT - FIRE PROTECTION
FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-FP101
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 111 BASEMENT FLOOR PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. B0622 ENLARGED PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. B0610 ENLARGED PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. B0423 ENLARGED PLAN - FIRE PROTECTION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
IOWA
9/5/25
K N
E E
D O
O R
O. H D OOR
W I N D OW
DN
IT
STAIR
1-13
C H
A R
T
IN
G
T R ASH
C OM PAC T OR
PN EU M AT I C T U BE
GI , N EPH R OL OGY
R H EU M AT OL OGY
N U R SES
EN D OC R I N E AN D
IN F EC TI ON S
D I SEASE N U R SES
PN EU M AT I C T U BE PN EU M AT I C T U BE
DER M AT OL OGY CL I N I C
PN EU M AT I C T U BE
PN EU M AT I C T U BE
F E
OH D
KN EE D OOR
OHD
OHD
OH D
DN
DN
UP
D N
DN
DN
DN
KEYED NOTES TIER PLAN LEGEND
111-FP102
111-FP102
111-FP102
1537B
TELECOMMUNICATIONS
RM. 1
TELECOMMUNICATIONS
RM.
1474J
MCR
1474J
MCR
1474J
MCR
ELECTRICAL ROOM
SUBSTATION ROOM
3" FP (EX)
4" FP (EX)
4" FP
TELECOMMUNICATIONS
RM.
DEMARC ROOM
(TYP)
(TYP)
4" FP
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
2. POWER AND CONTROL PANEL. INTERLOCK CONTROLS WITH THE HVAC CRAC
SYSTEM. THE CLEAN AGENT SYSTEM TO MONITOR THE DUCT DETECTORS. THE
HVAC SYSTEM TO BE SHUT DOWN BY THE BUILDING AUTOMATION SYSTEM UPON
FIRE OR SMOKE ALARM. CONNECT TO BUILDING FIRE ALARM SYSTEM. PROVIDE
120V POWER WITH DISCONNECT.
3. PROVIDE THE DESIGN, INSTALLATION AND TESTING OF A CALCULATED
AUTOMATIC AND MANUAL FIXED TOTAL FLOODING CLEAN AGENT FIRE
EXTINGUISHING SYSTEM AND RELEASING SYSTEM IN ACCORDANCE WITH NFPA
2001, NFPA 72, NFPA 70, AND NFPA 75 AND MANUFACTURER’S WRITTEN
INSTRUCTIONS FOR OVERAGE FOR ABOVE CEILING AND WITHIN ROOM. THE
INSTALLATION SHALL INCLUDE ALL MECHANICAL, PIPING, NOZZLES, SENSORS,
TANKS, CONTROLS AND ELECTRICAL COMPONENTS NECESSARY FOR A
COMPLETE AND OPERATING CLEAN AGENT FIRE SUPPRESSION SYSTEM. REFER
TO SPECIFICATION SECTION 21-22 00 FOR ADDITIONAL DETAILS.
4. GENERAL AREA FOR CLEAN AGENT FIRE SUPPRESSION SYSTEM. EXACT
DIMENSIONS OF AREA AND STORAGE TANKS TO BE DETERMINED THROUGH
SUBMITTAL PROCESS.
5. DISCHARGE PIPING TO ROOM NOZZLES.
6. CLEAN AGENT STORAGE TANKS. FASTEN TO WALL.
7. REFER TO ARCHITECTURAL AND ELECTRICAL SHEETS FOR LOCATIONS OF
SMOKE DETECTORS, MANUAL ACTIVATION STATIONS, PRE-DISCHARGE BELLS,
PRE-DISCHARGE STROBES, DISCHARGE STROBES, AND ANY HELD-OPEN DOOR
CONTROLS.
8. REFER TO ARCHITECTURE PLANS FOR SEALING OF THE ROOM ENVELOPE ABOVE
CEILING, WITHIN ROOM, AND BELOW RAISED FLOOR. SEAL WALLS TO
STRUCTURE. SEAL AROUND ALL PENETRATIONS FOR DUCTS, PIPES, CONDUITS,
AND PROVIDE GASKETING FOR TELECOMMUNICATION SYSTEMS. PERFORM
ROOM ENCLOSURE PRESSURIZATION TEST AS SPECIFIED.
AREA NOT IN CONTRACT
TIER 2 AREA
TIER 1 FIRE PROTECTION
AREA
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:0
A
M
BUILDING 111 LEVEL 01 - FIRE PROTECTION
FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-FP102
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 111 LEVEL 01 FLOOR PLAN - FIRE PROTECTION
1/4" = 1'-0"
RM. 1537B ENLARGED PLAN - FIRE PROTECTION
1/4" = 1'-0"
RM. 1180 ENLARGED PLAN - FIRE PROTECTION
1/4" = 1'-0"
RM. 1659, 1673, & 1674 ENLARGED PLAN - FIRE PROTECTION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
UNDER CONSTRUCTION
IT
IT
IT
IT
IT
IT
IT
ICE
M/C
C H
IM
C H
IM
A
S H C
S H
A
S H C
S H
KEY NOTES #
111-FP103
111-FP103
111-FP103
2428A
TELECOMMUNICATIONS
RM.
TELECOMMUNICATIONS
RM. 1
STORAGE
2605A
TELECOMMUNICATIONS
RM.
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:0
A
M
BUILDING 111 LEVEL 02 - FIRE PROTECTION
FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-FP103
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 111 LEVEL 02 FLOOR PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. 2428 ENLARGED PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. 2235 ENLARGED PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. 2557 ENLARGED PLAN - FIRE PROTECTION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
ITIT
STAGE
UP
UP
UP
UP
UP
UP
P N E U M A T I C T U B E
KEY NOTES #
111-FP104
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:0
A
M
BUILDING 111 LEVEL 03 - FIRE PROTECTION
FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-FP104
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 111 LEVEL 03 FLOOR PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. 3308 ENLARGED PLAN - FIRE PROTECTION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
IT
UP
UP
UP
UP
KEYNOTES
111-FP105
TELECOMMUNICATIONS
RM. 1
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:1
A
M
BUILDING 111 LEVEL 04 - FIRE PROTECTION
FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-FP105
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 111 LEVEL 04 FLOOR PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. 4315 ENLARGED PLAN - FIRE PROTECTION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
KEY NOTES #
111-FP106
TELECOMMUNICATIONS
RM.
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:1
A
M
BUILDING 111 LEVEL 05 - FIRE PROTECTION
FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-FP106
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 111 LEVEL 05 FLOOR PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. 5311 ENLARGED PLAN - FIRE PROTECTION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
RAMP UP
F D
2 LOCKERS
DN
KEY NOTES #
111-FP107
6410A
TELECOMMUNICATIONS
RM. 1
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:1
A
M
BUILDING 111 LEVEL 06 - FIRE PROTECTION
FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-FP107
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 111 LEVEL 06 FLOOR PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. 6410A ENLARGED PLAN - FIRE PROTECTION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
UP
TYP.
UP
ROOF
KEY NOTES #
111-FP108
TELECOMMUNICATIONS
RM.
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:2
A
M
BUILDING 111 LEVEL 07 - FIRE PROTECTION
FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-FP108
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 111 LEVEL 07 FLOOR PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. 7412 ENLARGED PLAN - FIRE PROTECTION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
IT
IT
IT
IT
IT
IT
IT
DN
KEY NOTES #
111-FP109
TELECOMMUNICATIONS
RM.
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:2
A
M
BUILDING 111 LEVEL 08 - FIRE PROTECTION
FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-FP109
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 111 LEVEL 08 FLOOR PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. 8409 ENLARGED PLAN - FIRE PROTECTION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
IT IT
IT IT
RAMP DN
KEYNOTES
111-FP110
TELECOMMUNICATIONS
RM.
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:2
A
M
BUILDING 111 LEVEL 09 - FIRE PROTECTION
FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-FP110
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 111 LEVEL 09 FLOOR PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. 9409 ENLARGED PLAN - FIRE PROTECTION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
METAL DOOR
IN WALL
DN
DN
KEY NOTES #
111-FP111
10409
TELECOMMUNICATIONS
RM.
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:3
A
M
BUILDING 111 LEVEL 10 - FIRE PROTECTION
FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
111-FP111
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 111 LEVEL 10 FLOOR PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. 10409 ENLARGED PLAN - PLUMBING
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
OV E R H E A D D OO R
L O U V E R WI N D O W
L O U V E R WI N D O W
UNDER CONSTRUCTION
OV E R H E A D D OO R
L O U V E R WI N D O W
L O U V E R WI N D O W
KEY NOTES #
123-FD101
123-FD101
123-FD101
123-FD101
123-FD101
TELECOMMUNICATIONS RM.
B113
TELECOMMUNICATIONS ROOM
A107
CIO
D113
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER
DEMOLITION WORK. COORDINATE SYSTEM SHUT DOWN, FIRE WATCH, AND
DEMOLITION WITH NFPA REQUIREMENTS & VA SITE REQUIREMENTS. REMOVE
EXISTING SPRINKLER HEADS, FITTINGS, & SHORT SECTIONS OF PIPE, AS NEEDED
FOR INSTALLATION OF NEW BRANCH PIPE AND SPRINKLER HEADS.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:3
A
M
BUILDING 123 LEVEL 01 OVERALL AND
ENLARGED - FIRE PROTECTION DEMOLITION
PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
123-FD101
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 123 LEVEL 01 FLOOR PLAN - FIRE PROTECTION DEMOLITION
1/2" = 1'-0"
RM. B113 ENLARGED PLAN -
FIRE PROTECTION DEMOLITION
3/8" = 1'-0"
RM. A107 ENLARGED PLAN -
FIRE PROTECTION DEMOLITION
1/2" = 1'-0"
RM. C113 ENLARGED PLAN -
FIRE PROTECTION DEMOLITION
1/2" = 1'-0"
RM. D113 ENLARGED PLAN -
FIRE PROTECTION DEMOLITION
1/2" = 1'-0"
RM. E105E ENLARGED PLAN -
FIRE PROTECTION DEMOLITION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
OV E R H E A D D OO R
L O U V E R WI N D O W
L O U V E R WI N D O W
UNDER CONSTRUCTION
OV E R H E A D D OO R
L O U V E R WI N D O W
L O U V E R WI N D O W
KEY NOTES #
123-FP101
123-FP101
123-FP101
123-FP101
123-FP101
B113
TELECOMMUNICATIONS
RM.
A107
TELECOMMUNICATIONS
RM.
TELECOMMUNICATIONS RM.
C113
D113
TELECOMMUNICATIONS
RM.
E105E
TELECOMMUNICATIONS
RM.
1. AREA SHOWN CROSS-HATCHED INDICATES SCOPE OF FIRE SPRINKLER WORK.
RECONFIGURE PIPING FOR PROPER HEAD PLACEMENT & INSTALL UPRIGHT
SPRINKLER HEADS IN THIS AREA PER NFPA 13 ORDINARY HAZARD GROUP 1
OCCUPANCY. DO NOT PLACE SPRINKLER HEADS ABOVE IT OR ELECTRICAL
EQUIPMENT. ROOM PLANNED AS ANSI/TIA-942-B RATING 1.
0' 15' 30' 60'
Graphic Scale : 1" = 30'-0"
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:5
:4
A
M
BUILDING 123 LEVEL 01 OVERALL AND
ENLARGED - FIRE PROTECTION FLOOR PLAN
AW DAW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
123-FP101
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1" = 30'-0"
BUILDING 123 LEVEL 01 PLAN - FIRE PROTECTION
1/2" = 1'-0"
RM. B113 ENLARGED PLAN -
FIRE PROTECTION
1/2" = 1'-0"
RM. A107 ENLARGED PLAN -
FIRE PROTECTION
1/2" = 1'-0"
RM. C113 ENLARGED PLAN -
FIRE PROTECTION
1/2" = 1'-0"
RM. D113 ENLARGED PLAN -
FIRE PROTECTION
1/2" = 1'-0"
RM. E105E ENLARGED PLAN -
FIRE PROTECTION
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
GENERAL DEMOLITION NOTES
GENERAL PLUMBING NOTES
SYMBOLS - PLUMBING
AREA PLAN LEGEND
1. ALL PIPING AND DUCTWORK IS SHOWN SCHEMATICALLY BASED ON EXISTING PLANS. CONTRACTORS SHALL BE RESPONSIBLE FOR COORDINATION OF VERIFYING ROUTES OF ALL EXISTING CONDITIONS AND EXISTING UTILITIES PRIOR TO BIDDING AND STARTING OF WORK. IF CONDITIONS DIFFER GREATLY CONTACT ENGINEER.
2. CONDUCT A PRECONSTRUCTION AIR AND WATER FLOW TEST OF EXISTING SYSTEMS AND MAINS SERVING EACH AREA AND FLOOR BEFORE STARTING ANY DEMOLITION WORK. SUBMIT REPORT
OF FLOWS AND FINDINGS TO ENGINEER AND OWNER.
3. COORDINATE SCHEDULE OF WORK WITH OWNER AND PROVIDE SUFFICIENT NOTICE BEFORE ANY SHUTDOWNS, TO MINIMIZE DISRUPTIONS TO ANY CONCURRENT OPERATIONS.
4. COMPLY WITH SITE SAFETY PROCEDURES OF OWNER, GENERAL CONTRACTOR, AND OSHA.
5. DEMOLISH MATERIALS, EQUIPMENT, AND ASSOCIATED SYSTEMS AS SHOWN WITHIN SCOPE OF WORK AREA AS DESIGNATED/NOTED. DEMOLISH ALL BRANCH DUCT AND PIPE, SUPPORTS, ACCESSORIES, EQUIPMENT, TERMINAL DEVICES, CONTROLS, WIRING, CONDUITS, AND ASSOCIATED ITEMS BACK TO RESPECTIVE MAINS. THEN CAP, SEAL, REPAIR, REINSULATE MAIN CONNECTIONS AS REQUIRED. NOTHING SHALL BE ABANDONED IN PLACE UNLESS NOTED OTHERWISE. REMOVE ALL DEMOLISHED ITEMS FROM SITE AND DISPOSE PROPERLY PER LOCAL LAWS.
6. HATCHED OR GRAYED OUT AREAS ARE NOT WITHIN CONTRACT BOUNDARY. COORDINATE WITH OWNER IF SUCH AREAS REQUIRE ACCESS TO COMPLETE SCOPE OF WORK, SUCH AS REMOVING A
BRANCH MAIN BACK TO LARGER MAIN TO ELIMINATE DEAD LEGS.
7. INFILL AND REPAIR TO MATCH EXISTING CONDITIONS ALL WALL, FLOOR, AND CEILING PENETRATIONS RESULTING FROM DEMOLISHED ITEMS, AND INSTALLATION OF NEW SYSTEMS. COORDINATE
WITH GENERAL CONTRACTOR FOR COVERAGE OF THIS SCOPE.
8. SAVE NOTED ITEMS FOR REUSE OR OWNERS SALVAGE. STORE NOTED ITEMS AND OTHER ITEMS IDENTIFIED BY OWNER IN OWNER’S DESIGNATED STORAGE AREA.
9. PROTECT EXISTING TO REMAIN EQUIPMENT, MATERIALS, AND SURROUND SITE FROM DAMAGE DURING DEMOLITION. REPAIRS AND REPLACEMENT OF EXISTING TO REMAIN CONDITIONS SHALL BE
THE CONTRACTOR’S RESPONSIBILITY.
10. REFER TO SPECIFICATION MANUAL FOR FURTHER DETAILS.
1. THE COMPLETE INSTALLATION SHALL BE IN ACCORDANCE WITH THE DEPARTMENT OF VETERANS AFFAIRS (VA) STANDARDS.
2. ALL WORK SHALL BE IN CONFORMANCE WITH THE INTERNATIONAL PLUMBING CODE - LATEST EDITION ADOPTED BY THE VA. THE VA SERVES AS AUTHORITY HAVING JURISDICTION.
3. THESE DOCUMENTS ARE INTENDED TO COMPLY WITH APPLICABLE CODES. WHERE DISCREPANCIES OCCUR, NOTIFY THE ENGINEER/ARCHITECT IN WRITING FOR INTERPRETATION. CORRECT ANY INSTALLATION THAT FAILS TO COMPLY WITH THE CODES AND STANDARDS AT NO ADDITIONAL COST TO THE OWNER.
4. CONTRACTOR SHALL PROVIDE ALL WORK NECESSARY INCLUDING ALL LABOR, MATERIALS, PERMITS, TAXES, FEES, INSPECTIONS, HARDWARE, AND COST FOR INSTALLATION FOR A COMPLETE
AND OPERATIONAL SYSTEM.
5. ALL MATERIALS FURNISHED BY THE CONTRACTOR SHALL BE NEW, COMPLETE WITH MANUFACTURER’S GUARANTEE OR WARRANTY AND SHALL BE LISTED BY A NATIONALLY RECOGNIZED
TESTING LABORATORY.
6. PENETRATIONS THROUGH FIRE RATED WALLS SHALL BE SEALED WITH APPROPRIATE FIRE PROOFING MATERIALS TO RESTORE FIRE RATING. REFER TO ARCHITECTURAL DRAWINGS FOR FIRE
RATED WALLS.
7. CONTRACTOR SHALL KEEP THE WORK AREA CLEAN OF ALL DEBRIS ON A DAILY BASIS. ALL NEW MATERIALS AWAITING INSTALLATION SHALL BE KEPT IN AREAS DESIGNATED BY THE OWNER.
8. DRAWINGS SHALL NOT BE SCALED FOR DIMENSIONS. REFER TO DIMENSIONED ARCHITECTURAL FLOOR PLANS. IF THE DIMENSIONS CANNOT BE DETERMINED BY THE INFORMATION GIVEN, CONTRACTOR SHALL CONTACT THE ENGINEER FOR ADDITIONAL INFORMATION.
9. PERIODIC SITE OBSERVATION BY THE ENGINEER IS SOLELY FOR THE PURPOSE OF DETERMINING IF THE WORK OF THE CONTRACTOR IS PROCEEDING IN ACCORDANCE WITH THE CONTRACT DOCUMENTS. THIS LIMITED SITE OBSERVATION SHOULD NOT BE CONSTRUED AS EXHAUSTIVE OR CONTINUOUS TO CHECK THE QUALITY OR QUANTITY OF THE WORK, BUT RATHER PERIODIC IN AN EFFORT TO GUARD THE OWNER AGAINST DEFECTS OR DEFICIENCIES IN THE WORK OF THE CONTRACTOR.
10. INFORMATION CONTAINED ON THE DRAWINGS IS IN ITSELF INCOMPLETE AND VOID UNLESS USED IN CONJUNCTION WITH ALL OTHER DISCIPLINE DRAWINGS, THE SPECIFICATIONS, TRADE PRACTICES, OR APPLICABLE STANDARDS, CODES, ETC., AND SHALL BE CONSIDERED THE CONTRACT DOCUMENTS AND WITH ALL THEREIN BY REFERENCE, WHICH THE CONTRACTOR CERTIFIES
KNOWLEDGE OF BY SIGNING THE CONTRACT.
11. CONTRACTOR IS TO ASSUME FULL RESPONSIBILITY, UNRELIEVED BY REVIEW OF SHOP DRAWINGS OR PERIODIC OBSERVATION OF CONSTRUCTION, FOR COMPLIANCE WITH THE CONTRACT DOCUMENTS, FOR DIMENSIONS TO BE CONFIRMED AND CORRELATED ON THE JOB SITE AND BETWEEN INDIVIDUAL DRAWINGS OR SETS OF DRAWINGS FOR FABRICATION PROCESSES AND CONSTRUCTION TECHNIQUES (INCLUDING EXCAVATION, SHORING, SCAFFOLDING, BRACING, ERECTION, FORM WORK, ETC.), FOR COORDINATION OF THE VARIOUS TRADES, AND FOR SAFE CONDITIONS ON THE JOB SITE. VARIATIONS IN FIELD CONDITIONS RELATIVE TO THE CONTRACT DOCUMENTS SHALL BE REPORTED TO THE ENGINEER AS SOON AS THEY ARE FOUND. WORK
SHALL NOT PROGRESS UNTIL WRITTEN PERMISSION FROM THE ENGINEER IS OBTAINED.
12. ALL EQUIPMENT AND ACCESSORIES SHALL BE INSTALLED SO AS TO BE EASILY ACCESSIBLE. ALL CLEARANCES FOR EQUIPMENT PER MANUFACTURERS GUIDELINES AND CODE COMPLIANCE
SHALL BE REQUIRED.
13. CONTRACTOR SHALL BE RESPONSIBLE FOR ALL CONSTRUCTION ASSOCIATED WITH PERMITS, METERS, AND WATER MAINS.
14. WALL CLEANOUTS, ACCESS PANELS, ETC. TO BE LOCATED IN BACK OF- HOUSE AREAS UNLESS CONDITIONS DICTATE OTHERWISE. COORDINATE WITH GENERAL CONTRACTOR PRIOR TO
INSTALLATION.
15. PROVIDE ACCESS PANELS FOR VALVES, ETC. THAT ARE LOCATED IN CONCEALED AREAS. COORDINATE WITH GENERAL CONTRACTOR FOR EXACT LOCATION AND WITH ARCHITECTURAL PLANS
FOR FINISHES.
16. ALL COMPONENTS OF SYSTEMS SHALL BE PROVIDED FOR A COMPLETELY OPERATIONAL, UNDERSTANDABLE, SAFE, AND CLEAN SYSTEM; INCLUDING BUT NOT LIMITED TO EXTRANEOUS FIXTURE TRIM AS SPECIFIED, MEDICAL GAS OUTLETS, LABELS, SERVICE AND COMMISSIONING INTO OPERATION, TESTING AND CLEANING, FIRE AND LIFE SAFETY REQUIREMENTS, AND CONSIDERING THE
REQUESTS OF OWNERS PERSONNEL.
17. ELECTRICAL PANELS SHOWN FOR REFERENCE. DO NOT ROUTE ANY COMPONENTS ABOVE OR IN FRONT OF ELECTRICAL EQUIPMENT. MAINTAIN CODE REQUIRED CLEARANCES.
18. PLANS ARE DIAGRAMMATIC AND INTENDED TO CONVEY SCOPE OF WORK AND GENERAL LOCATIONS OF EQUIPMENT, MATERIALS, ETC. NOT ALL RISERS, DROPS, OFFSETS, VALVES, ETC. ARE SHOWN. PROVIDE RISERS, DROPS, OFFSETS, VALVES, ETC. AS REQUIRED TO MEET SPACE REQUIREMENTS AND TO AVOID INTERFERENCES WITH OTHER TRADES. MAKE FINAL CONNECTIONS TO
FIXTURES, EQUIPMENT, ETC. AS REQUIRED AND/OR PER MANUFACTURER'S RECOMMENDATIONS.
19. CONTRACTOR SHALL FIELD VERIFY ALL DIMENSIONS AND LAYOUT OWN WORK ACCORDINGLY AND IS RESPONSIBLE FOR DETERMINING EXACT LOCATIONS FOR EQUIPMENT, MATERIALS, ETC.
20. THE EXISTING PLUMBING SYSTEMS SHALL BE MODIFIED PER SPECIFIED PLANS AND SPECIFICATIONS. FIELD VERIFY EXISTING PLUMBING SYSTEMS REQUIREMENTS PRIOR TO BIDDING.
21. COORDINATE SCOPE OF WORK WITH THE WORK OF OTHER TRADES PRIOR TO INSTALLATION. ISSUES DUE TO LACK OF COORDINATION EFFORT WILL BE CORRECTED AT NO ADDITIONAL COST TO
THE OWNER.
22. COORDINATE LOCATION OF SYSTEM COMPONENTS WITHIN LIMITS OF STRUCTURE AND OTHER ENGINEERED SYSTEMS. ROUTE ALL PIPING IN CONCEALED SPACES AND INSTALL PIPING AS HIGH AS POSSIBLE. OFFSET SYSTEMS ROUTING AS REQUIRED, PROVIDING REQUIRED MATERIALS. PIPE SHALL NOT BE ROUTED IN EXTERIOR WALLS UNLESS NOTED. COORDINATE ROUTING OF PIPING TO MAINTAIN REQUIRED SERVICE CLEARANCES AROUND ANY EQUIPMENT AND ELECTRICAL ITEMS.
INFILL AND REPAIR TO MATCH EXISTING CONDITIONS ALL WALL, FLOOR, AND CEILING PENETRATIONS RESULTING FROM DEMOLISHED ITEMS, AND INSTALLATION OF NEW SYSTEMS. COORDINATE
WITH GENERAL CONTRACTOR FOR COVERAGE OF THIS SCOPE.
23. ALL ELEMENTS OF CONSTRUCTION SHALL BE INSTALLED BY SKILLED TRADESMEN OF THERE PARTICULAR TRADE, AND INSTALLED IN A NEAT WORKMANLIKE MANNER KEEPING WITH THE HIGHEST
STANDARDS OF THE TRADE.
24. COORDINATE SCOPE OF WORK WITH PROJECT SCHEDULES AGREED UPON BY OWNER AND ALL CONTRACTORS.
25. REFER TO SPECIFICATION MANUAL FOR FURTHER DETAILS ABOUT DESIGN STANDARDS, PRODUCTS, DRAWINGS, SUBMITTALS, DOCUMENTATION, COORDINATION, AND INSTALLATION.
VALVE - BALL, NORMALLY CLOSED
VALVE - BALL, NORMALLY OPEN
VALVE - CHECK
VALVE - PPRESSURE REDUCING VALVE (PRV)
VALVE - SHUT-OFF, NORMALLY CLOSED
VALVE - SHUT-OFF, NORMALLY OPEN
?"SYS (EX) GENERAL PIPING - EXISTING TO REMAIN
?" GENERAL PIPING - TO BE DEMOLISHED
?"SYS GENERAL PIPING - NEW WORK
SYSTEM LABEL SYSTEM DESCRIPTION
CD CONDENSATE DRAIN
CW DOMESTIC COLD WATER
HW DOMESTIC HOT WATER
HWR DOMESTIC HOT WATER RETURN
SAN SANITARY WASTE
SAN SANITARY WASTE BELOW GRADE/SLAB
ST (1,000) STORM DRAINAGE (SQ.F.T TOTAL)
V VENT
W WATER (DOMESTIC POTABLE WATER SERVICE)
BOTTOM CONNECTION
END DROP / DOWN
END UP / RISER
HEADER FLANGE CAP
PIPE END CAP
RISE / DROP IN-LINE
TEE DOWN
TEE UP
TOP CONNECTION
UP & DN / RISER
NEW CONNECTION TO EXISTING
DEMOLISH TO THIS POINT
BACKFLOW PREVENTER (BFP-RPZ)
CONTINUATION BREAK
COUPLING
DIRECTION OF FLOW
DIRECTION OF PITCH
REDUCER
UNION
SYSTEM LABEL SYSTEM DESCRIPTION SYSTEM LABEL SYSTEM DESCRIPTION
MA MEDICAL AIR
VAC MEDICAL VACUUM
O₂ OXYGEN
MH100
MH100
DRAWING SYMBOLS
01-SF-3
08-TU-1-1
DETAIL NUMBER (VIEW # ON SHEET SHOWN)
TYPICAL UNIT NO.
BUILDING NO. WHERE EQUIPMENT IS LOCATED
EQUIPMENT ABBREVIATION (SUPPLY FAN)
ITEM NUMBER (TERMINAL UNIT NO. 1)
EQUIPMENT ABBREVIATION (TERMINAL UNIT)
SERVED BY (AIR HANDLER UNIT NO. 1)
DRAWING NUMBER ON SHEET SHOWN
BUILDING NO. WHERE EQUIPMENT IS LOCATED
SECTION NUMBER (VIEW # ON SHEET SHOWN)
DRAWING NUMBER ON SHEET SHOWN
ITEM NUMBER (SUPPLY FAN NO. 1)
AREA NOT IN CONTRACT
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3
/2
:1
:5
A
M
PLUMBING LEGENDS, SCHEDULES, AND
ABBREVIATIONS
AW DAW
FINAL BID DOCUMENTS 695-21-700EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
P-001
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
WSFU WATER SUPPLY FIXTURE UNITS
WHA WATER HAMMER ARRESTER
WHE WATER HEATER
WH WALL HYDRANT
WCO WALL CLEANOUT
WC WATER CLOSET
W WASTE
VTR VENT THROUGH ROOF
VAC VACUUM
V VENT
TSTAT THERMOSTAT
TP TRAP PRIMER
TMV THERMOSTATIC MIXING VALVE
TCV TEMPERATURE CONTROL VALVE
ST STORM WATER DRAINAGE
SPR SPRINKLER LINE
SCH SCHEDULE
SAN SANITARY SEWER
RP RECIRCULATION PUMP
REF REFRIGERANT
RD ROOF DRAIN
O² OXYGEN
N²0 NITROUS OXIDE
N² NITROGEN
MV MEDICAL VENT
MSB MOP SERVICE BASIN
MED MEDICAL
MA MEDICAL AIR
LV LAB VENT
LA LAB AIR
INV INVERT
IE INVERT ELEVATION
HYD HYDRANT
HWR HOT WATER RECIRCULATION (DOMESTIC/POTABLE)
HW HOT WATER (DOMESTIC/POTABLE)
HS HAND SINK
HD HUB DRAIN
HB HOSE BIBB
H&CW HOT AND COLD WATER
G GAS
FU FIXTURE UNITS
FS FLOW SWITCH
FD FLOOR DRAIN
FCO FLOOR CLEANOUT
EWS EYE WASH STATION
DWV DRAIN WASTE VENT
DN DOWN
DHWS DOMESTIC HOT WATER SUPPLY
DHWR DOMESTIC HOT WATER RETURN (POTABLE)
DHW DOMESTIC HOT WATER (POTABLE)
DFU DRAINAGE FIXTURE UNITS
DCW DOMESTIC COLD WATER (POTABLE)
CW COLD WATER (DOMESTIC/POTABLE)
CV CONTROL VALVE
CS CLINICAL SINK
CO CLEANOUT
AP ACCESS PANEL
AG AIR GAP
PLUMBING ABBREVIATIONS
WB WET-BULB (TEMPERATURE)
W WATTS
TSP TOTAL STATIC PRESSURE
TD TEMPERATURE DIFFERENCE
SQ M SQUARE METER
SQ FT SQUARE FOOT (FEET)
SP GR SPECIFIC GRAVITY
SCFM STANDARD CUBIC FEET PER MINUTE
SAT SUPPLY AIR TEMPERATURE
SI SQUARE INCHES
RPM REVOLUTIONS PER MINUTE
RAT RETURN AIR TEMPERATURE
PSIG POUNDS PER SQUARE INCH-GAGE
PSIA POUNDS PER SQUARE INCH ATMOSPHERE
PSI POUNDS PER SQUARE INCH
PPM PARTS PER MILLION
PA PASCAL
NPLV NON-STANDARD PART LOAD VALUE
Nm NEWTON-METER
NC NOISE CRITERIA
MTD MEAN TEMPERATURE DIFFERENCE
M/S METERS PER SECOND
MM MILLIMETER
MIN MINIMUM
MHP MOTOR HORSEPOWER
MERV MINIMUM EFFICIENCY REPORTING VALUE
MCA MULTICHANNEL ANALYZER
MCA MAXIMUM CURRENT AMPACITY
MBH 1000 BTUH
MAX MAXIMUM
M METER
LWT LEAVING WATER TEMPERATURE
LVG LEAVING
LH LATENT HEAT
LGT LEAVING GLYCOL TEMPERATURE
LF LINEAR FOOT (FEET)
LBS/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
L/S LITERS PER SECOND
L/M LITERS PER MINUTE
L/H LITERS PER HOUR
LF LINEAR FEET (FOOT)
L LITER
kWH KILOWATT HOUR kW KILOWATT kPA KILO PASCAL
KG/HR KILOGRAM PER HOUR
KG KILOGRAM
IPLV INTEGRATED PART LOAD VALUE
IN-LB INCH-POUND
IN WG INCH WATER GAUGE
IN HG INCHES OF MERCURY
IN INCHES
HZ HERTZ
HT HEIGHT
HP HORSEPOWER
GPM GALLONS PER MINUTE
GPH GALLONS PER HOUR
GPD GALLONS PER DAY
GAL GALLONS
GA GAUGE
FT-WC FEET OF WATER COLUMN
FT-LB FOOT-POUND
FT FEET
FPS FEET PER SECOND
FPM FEET PER MINUTE
F FAHRENHEIT
EWT ENTERING WATER TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
ENT ENTERING
EGT ENTERING GLYCOL TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EAT ENTERING AIR TEMPERATURE
DP DEWPOINT
DIA DIAMETER
DEG DEGREE
dB DECIBEL
DB DRY-BULB TEMPERATURE
COP COEFFICIENT OF PERFORMANCE
CM/S CENTIMETER PER SECOND
CM CUBIC METER
CFT CUBIC FEET
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
C CENTIGRADE (CELSIUS)
BTUH BRITISH THERMAL UNIT PER HOUR
BTU BRITISH THERMAL UNIT
BHP BRAKE HORSE POWER
APD AIR SIDE PRESSURE DROP
UNITS OF MEASURE
XFER TRANSFER
WCPU WATER-COOLED PACKAGED UNIT
VAMCS VA MASTER CONSTRUCTION SPECIFICATIONS
VAHBS VA HOSPITAL BUILDING SYSTEM
VBA VETERANS BENEFITS ADMINISTRATION
VHA VETERANS HEALTH ADMINISTRATION
VA DEPARTMENT OF VETERANS AFFAIRS
UTIL UTILITY
UPC UNIVERSAL PLUMBING CODE
UL UNDERWRITER'S LABORATORY
TEMP TEMPERATURE
TYP TYPICAL
SS STAINLESS STEEL
SPEC SPECIFICATION
SMACNA SHEET METAL AND AIR CONDITIONING CONTRACTORS...
SI INTERNATIONAL SYSTEM OF UNITS
SHT SHEET
SEN SENSIBLE HEAT
SCI SPINAL CODE INJURY
SA SUPPLY AIR
RM ROOM
RO REVERSE OSMOSIS
RDS ROOM DATA SHEETS
REQD REQUIRED
RA RETURN AIR
R/E RETURN OR EXHAUST
PSS PRIMARY SECONDARY SYSTEM
PGW PROPYLENE GLYCOL-WATER SOLUTION
OR OPERATING ROOM
OD OUTSIDE DIAMETER
OC ON CENTER
OA OUTSIDE AIR
NTS NOT TO SCALE
NSPC NATIONAL STANDARD PLUMBING CODE
NOM NOMINAL
NOAA NATIONAL OCEANIC & ATMOSPHERIC ADMINISTRATION
NO NORMALLY OPEN
NIC NOT IN CONTRACT
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
NFC NATIONAL FIRE CODES
NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NEC NATIONAL ELECTRICAL CODE
NC NORMALLY CLOSED
NA NOT APPLICABLE (ALSO N/A)
MRI MAGNETIC RESONANCE IMAGING
MIN MINIMUM
MH MANHOLE
MER MECHANICAL EQUIPMENT ROOM
MECH MECHANICAL
MAX MAXIMUM
LPG LIQUID PROPANE GAS
ITAC INFORMATION TECHNOLOGY AIR CONDITIONING
IPC INTERNATIONAL PLUMBING CODE
ID INSIDE DIAMETER
ICU INTENSIVE CARE UNIT
I/O INPUT/OUTPUT
IESNA ILLUMINATION ENGINEERING SOCIETY OF NORTH...
IBC INTERNATIONAL BUILDING CODE
HAC HOUSEKEEPING AIDE’S CLOSET
GS GALVANIZED STEEL
GA GAUGE
EX EXISTING (OR EXIST)
EPACT ENERGY POLICY ACT
EPA ENVIROMENTAL PROTECTION AGENCY
ELEC ELECTRIC OR ELECTRICAL
EL ELEVATION
ESMT EASEMENT
ETO ETHYLENE OXIDE
EA EXHAUST AIR
DWG DRAWING
DEMO DEMOLITION
CO2 CARBON DIOXIDE
CENT CENTRIFUGAL
BMT BONE MARROW TRANSPLANT
BLDG BUILDING
ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
ASHRAE
AMERICAN SOCIETY OF HEATING REFRIGERATION AIR
CONDITIONING ENGINEERS
ASHP AIR SOURCE HEAT PUMP
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE
AMB AMBIENT
AFG ABOVE FINISHED GRADE
AFF ABOVE FINISHED FLOOR
ADA AMERICANS WITH DISABILITIES ACT
A/E ARCHITECTS AND ENGINEERS
GENERAL ABBREVIATIONS
5. SEE SPECIFICATIONS FOR MORE INFORMATION.
4. PLUMBING CONTRACTOR TO PROVIDE MATERIALS AND LABOR TO MAKE ALL REQUIRED FINAL CONNECTIONS FOR A COMPLETE
AND OPERABLE SYSTEM.
3. PROVIDE MOUNTING HARDWARE, SUPPORTS, BRACKETS, ETC. AS REQUIRED BY THE FIXTURE MANUFACTURER FOR PROPER
INSTALLATION.
2. CONTRACTOR SHALL VERIFY DRAIN COMPATIBILITY WITH CONSTRUCTION TYPE PRIOR TO INSTALLATION OR PROCUREMENT.
1. COMPLIANCE WITH PROJECT ACCESSIBILITY REQUIREMENTS FOR FIXTURES WITHIN THIS SCHEDULE TO BE CONFIRMED BY
ARCHITECT AND/OR ACCESSIBILITIY CONSULTANT.
NOTES:
HD-1 HUB DRAIN - - 2 1-1/2 2 - N/A NO 1,2,3,4,5
FCO FLOOR CLEANOUT - - PLANS - - - N/A NO 1,3,4,5
FD-C MEDIUM-DUTY FLOOR DRAIN - - 2 1-1/2 2 - N/A NO 2,3,4,5
P-502 FLOOR-MOUNTED SERVICE SINK 3/4 3/4 3 2 2 3 N/A NO 1,3,4,5
(IN.) (IN.) (IN.) (IN.)
MARK DESCRIPTION
CW HW SAN V
DFU WSFU
WRIST
BLADE
HANDLES
ELECTRIC
SENSOR
NOTES
PLUMBING FIXTURE SCHEDULE
BASEMENT 002 TELECOMMUNICATIONS ROOM No No
BUILDING 148
BASEMENT 002 TELECOMMUNICATIONS ROOM No No
BUILDING 147
BASEMENT 005 EXISTING TELECOMMUNICATION RM. No No
BUILDING 146
LEVEL 01 E105E TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 D113 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 C113 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 B113 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 A107 TELECOMMUNICATIONS ROOM Yes Yes
BUILDING 123
BASEMENT 106 REFRIGERATION ROOM No No
BUILDING 113
LEVEL 01 108 EXISTING TELECOMMUNICATION RM. No Yes
BUILDING 112
LEVEL 10 10409 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 09 9409 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 08 8409 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 07 7412 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 06 6410A TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 05 5311 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 04 4315 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 03 3308 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 02 2557 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 02 2528A TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 02 2235 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 1537B TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 1473 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 1472 ELECTRICAL ROOM Yes Yes
LEVEL 01 1471 SUBSTATION ROOM Yes Yes
LEVEL 01 1470 DEMARC ROOM Yes Yes
LEVEL 01 1180 TELECOMMUNICATIONS ROOM Yes Yes
BASEMENT B0423 TELECOMMUNICATIONS ROOM Yes Yes
BASEMENT B0622 TELECOMMUNICATIONS ROOM Yes Yes
BASEMENT B0610E TELECOMMUNICATIONS ROOM Yes Yes
BUILDING 111
BASEMENT B001 TELECOMMUNICATIONS ROOM No Yes
BUILDING 109
LEVEL 02 200 TELECOMMUNICATIONS ROOM No Yes
BUILDING 108
LEVEL 02 200 TELECOMMUNICATIONS ROOM No Yes
BUILDING 107
LEVEL 01 144 TELECOMMUNICATIONS ROOM Yes Yes
BASEMENT B100FC TELECOMMUNICATIONS ROOM Yes Yes
BUILDING 102
LEVEL 01 005 TELECOMMUNICATIONS ROOM No Yes
BUILDING 97
LEVEL 01 E-104 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 D-125 EXISTING TELECOMMUNICATION RM. Yes Yes
LEVEL 01 C-126 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 B-159 TELECOMMUNICATIONS ROOM Yes Yes
BUILDING 70
LEVEL 02 A201 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 A156 TELECOMMUNICATIONS ROOM Yes Yes
BUILDING 43
LEVEL 01 20-1-030 TELECOMMUNICATIONS ROOM No Yes
BUILDING 20
BASEMENT B09 EXISTING TELECOMMUNICATION RM. Yes Yes
BUILDING 07
LEVEL 03 C302 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 02 D203 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 B103 EXISTING TELECOMMUNICATION RM. Yes Yes
LEVEL 01 A104 EXISTING TELECOMMUNICATION RM. Yes Yes
LEVEL 01 6-1-C102 TELECOMMUNICATIONS ROOM Yes Yes
BUILDING 06
LEVEL 02 204 TELECOMMUNICATIONS ROOM Yes Yes
LEVEL 01 117 TELECOMMUNICATIONS ROOM Yes Yes
BUILDING 05
LEVEL 02 2110 TELECOMMUNICATIONS ROOM Yes Yes
BUILDING 04
LEVEL 01 1454 TELECOMMUNICATIONS ROOM No Yes
BUILDING 03
LEVEL NUMBER NAME
PLUMBING
DEMO
REQUIRED
PLUMBING NEW
REQUIRED
ROOMS IN SCOPE - PLUMBING
Revisions: Date:
PROFESSIONAL ENGINEER
WISCONSIN
ARLO G.
WIECZOREK
#42666-6
SWISHER
KEYNOTES
GAS PRESSURE
REGULATOR
INSULATING UNION
PLUGGED TEE W/BUSHING
AND 3/8" PLUG
TEE
W/BUSHING
SWING JOINT
OUTLET
GAS MAIN
GAS COCK(TYP)
ANNODELESS RISER
TO BUILDING
SUPPLY CAST IRON EXTENSION
TYPE SERVICE BOX
BUTT WELDED
SERVICE TEE
(POLY)SERVICE SHUT-
OFF VALVE WITH 2" SQ.
OPERATING NUT
HOT TAP VALVE
FINISHED GRADE
FLASHING MEMBRANE, MIN. 24" [600mm] SQUARE 2 1/2 LB. [1.1kg] TO 4 LB. [1.8kg] LEAD OR 16 OZ. [0.45kg] COPPER.
ADJUSTABLE NICKEL
BRONZE STRAINER WITH
4" [100mm] FLANGE (FLUSH
WITH FINISHED FLOOR)
WEEP HOLES
COMPOSITION FLOORING
NOTES:
1. SLOPE MEMBRANE LINER 2% TO DRAIN.
2. PROVIDE FLASHING MEMBRANE WHEN DRAIN IS INSTALLED IN A NON MEMBRANE FLOOR
INVERTIBLE FLASHING
COLLAR
LOOSE GRAVEL AT
WEEP HOLES 3mm TO 6mm GRAVEL SIZE
CAULKED, NO-HUB OR
THREADED CONNECTION
WIDE FLANGE
TRAP ARM LENGTH
D
1-1/4"
FROM FLOOR DRAIN
OR STANDPIPE
VENT
SAN LINE
MIN.
2"
3"
1-1/2"
4" & UP
MAX.
2-1/2"
4"
6"
3"
8"
2' - 6"
5' - 0"
6' - 0"
3' - 6"
10'-0"
DIRECTION OF FLOW
(SEE CHART)
MAX. TRAP ARM LENGTH
"D" (NOM. PIPE SIZE)
(SEE CHART)
MIN. TRAP ARM LENGTH
DRAW THRU
2" [51mm]
PLUS X
X
UNIT TYPE A B
WHERE X = STATIC PRESSURE IN PAN
DRAIN LINE SHALL BE AT LEAST THE SAME
SIZE AS THE NIPPLE ON THE DRAIN PAN
PITCH DOWN
TOWARD DRAIN
CLEAN OUT
OPEN DRAIN
DRAIN PAN
A
IR
G A
P
A B
[2 m m
OPEN STUB FOR VENTING
NOTE 5
NOTE 6
NON-FIRE RATED WALL
(CONSTRUCTION VARIES)
1. CONCRETE/CONCRETE BLOCK FLOOR OR WALL ASSEMBLY:
A. MIMIMUM 5 IN. THICK REINFORCED NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY
ALSO BE CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS. MAXIMUM
DIAMETER OF OPENING IS 6 IN.
B. FLOOR OR WALL ASSEMBLY - MINIMUM 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PCF) CONCRETE FLOOR OR MIN 5 IN. THICK REINFORCED
LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE WALL. WALL MAY ALSO BE
CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS.
C. FLOOR OR WALL ASSEMBLY - MINIMUM 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PCF) CONCRETE FLOOR OR MIN 5 IN. THICK REINFORCED
LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE WALL. WALL MAY ALSO BE
CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS. MAXIMUM AREA OF OPENING
IS 45 SQ IN. WITH A MAXIMUM DIMENSION OF 9 IN.
D. FLOOR OR WALL ASSEMBLY - MINIMUM 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT OR
NORMAL WEIGHT (100-150 PCF) CONCRETE FLOOR OR MIN 5 IN. THICK REINFORCED
LIGHTWEIGHT OR NORMAL WEIGHT (100-150 PCF) CONCRETE WALL. WALL MAY ALSO BE
CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS. MAXIMUM AREA OF OPENING
IS 192 SQ IN. WITH A MAXIMUM DIMENSION OF 24 IN.
2. METALLIC SLEEVE (OPTIONAL) – NOMINAL 6 IN. DIAM (OR SMALLER) ELECTRICAL METALLIC
TUBING, STEEL CONDUIT OR CAST IRON PIPE CAST OR GROUTED INTO FLOOR OR WALL
ASSEMBLY, FLUSH WITH FLOOR OR WALL SURFACES.
3. THROUGH PENETRANTS – ONE METALLIC PIPE OR CONDUIT TO BE CENTERED WITHIN THE
FIRESTOP SYSTEM. A NOMINAL ANNULAR SPACE OF 3/4 IN. IS REQUIRED WITHIN THE
FIRESTOP SYSTEM. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR
OR WALL ASSEMBLY.
4. PACKING MATERIAL – MIMIMUM 3 IN. THICKNESS OF MIMIMUM 4 PCF MINERAL WOOL BATT
INSULATION FIRMLY PACKED INTO OPENING AS A PERMANENT FORM. PACKING MATERIAL TO
BE RECESSED FROM TOP SURFACE OF FLOOR AS REQUIRED TO ACCOMMODATE THE
REQUIRED THICKNESS OF FILL MATERIAL. PACKING MATERIAL TO BE CENTERED IN WALLS
MID DEPTH AND RECESSED TO ALLOW FOR INSTALLATION OF FILL MATERIAL.
5. FILL, VOID, OR CAVITY SEALANT - MINIMUM 5/8 IN. THICKNESS OF FILL MATERIAL APPLIED WITH
THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL. AT THE POINT OF CONTINUOUS
CONTACT LOCATIONS BETWEEN PENETRANT AND WALL, A MINIMUM OF 1/2 IN. DIAMETER
BEAD OF FILL MATERIAL SHALL BE APPLIED AT THE PENETRANT WALL INTERFACE ON BOTH
SURFACES OF WALL.
6. WALL ASSEMBLY THE ONE (1) OR TWO (2) HOUR OF FIRE RATED GYPSUM WALLBOARD/STUD
WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER
SPECIFIED IN THE INDIVIDUAL U300 OR U400 SERIES WALL AND PARTITION DESIGNS IN THE UL
FIRE RESISTANCE DIRECTORY IN JUL INCLUDE FOLLOWING CONSTRUCTION FEATURES:
7. GYPSUM BOARD - 5/8 IN. THICK, 4 FT. WIDE WITH SQUARE TAPERED EDGES. GYPSUM BOARD
TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE, AND SHEET ORIENTATION SHALL
BE AS SPECIFIED IN THE INDIVIDUAL U300 OR ARE U400 SERIES DESIGN IN THE UL FIRE
RESISTANCE DIRECTORY.
8. STUD WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS.
OPENING IN THE WALL SHALL BE 4 TO 6 IN. WIDER, AND 4 TO 6 IN. HIGHER THAN THE
DIAMETER OF THE OPENING ITEM SUCH THAT, WHEN THE PENETRATING ITEM IS INSTALLED IN
THE OPENING, A 2 IN. TO 3 IN. CLEARANCE IS PRESENT BETWEEN THE PENETRATING ITEM
AND THE FRAMING ON ALL FOUR SIDES.
A. WOOD CONSTRUCTION - SHALL CONSIST OF NOMINAL 2 IN. X 4 IN. LUMBER, SPACED
16 IN. ON CENTER. MAXIMUM DIAMETER OF…
This is the start of the file's text. The full file is on GovTribe.