This file is RFP Attachment 19, consisting of architectural drawings for the EHRM Infrastructure Upgrades project at the Clement J Zablocki VA Medical Center in Milwaukee, Wisconsin. The drawing set includes comprehensive storm plans, profiles, civil details, and floor plans across multiple buildings (03, 04, 05, 06, 07, 20, 43, 70, 97, 102, 107, 108, and 109) with both demolition and new construction layouts. Key technical specifications include profile views of proposed manholes (MH 22-35) with horizontal and vertical scales, storm plan and profile drawings numbered 100-CU126 through 100-CU131, civil details showing concrete construction standards and utility trench specifications, and architectural floor plans indicating areas of work, telecommunications rooms, mechanical systems, and required finishes. The drawings reference design criteria compliant with IBC 2021, ASCE 7-16, and ACI 318-19, specify concrete strength of 5000 PSI with exposure class F3/C2, ground snow loads of 30 PSF, and basic wind speeds of 107 MPH. Floor plans across multiple buildings designate demolition areas, new partition wall construction using 5/8-inch Type X gypsum board, telecommunications room modifications, ceiling heights of 9 feet AFF, and coordination requirements with mechanical, electrical, and plumbing drawings. General notes emphasize contractor responsibility for field verification of dimensions, coordination with all trades, protection of adjacent structures, and adherence to ACI 318 reinforcing steel standards and construction inspection requirements under IBC Chapter 17.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PROFILE VIEW OF 18004375.03 PROPOSED MH 22
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 5'
PROFILE VIEW OF 18004375.03 PROPOSED MH 23
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 5'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
RJJ LKS
Revisions: Date:
FINAL BID DOCUMENTS 695-21-700
of
EHRM INFRASTRUCTURE
UPGRADES - MILWAUKEE, WI
SEPTEMBER 5, 2025
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Romanyk Consulting Focusing on what matters
0' 1'
2' 6" G ra ph ic
S ca le
1"
'-0
0' 1'
2' 6"
G ra ph ic
S ca le
3/ 4"
'-0
0' 2'
4' 1'
G ra ph ic
S ca le
1/ 2"
'-0
0' 2'
1' 4'
G ra ph ic
S ca le
1/ 4"
'-0
0' 8'
4'
G ra ph ic
S ca le
1/ 8"
'-0
0'
8'
G ra ph ic
S ca le
1/
1' -0
0' 4"
8" 1'
2'
G ra ph ic
S ca le
3/
1' -0
0' 1'
6" 3"
1'
G ra ph ic
S ca le
1/
2"
'-0
Sprinklered
Office of Construction and Facilities Management FULLY SPRINKLERED 5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
35% SCHEMATIC DESIGN SUBMISSION 5.17.21
65% DESIGN DEVELOPMENT SUBMISSION 6.15.21
65% DESIGN DEVELOPMENT RESUBMISSION 8.25.21
95% CONSTRUCTION DOCUMENTS 6.23.22
95% CONSTRUCTION DOCUMENTS RESUBMISSION 6.6.23
0' 3'
6'
1'
G ra ph ic
S ca le
/1
6"
'-0
LINNEA K.
SHAW
062-074863
STORM PLAN AND PROFILE 22 & 23
100-CU126
PROFILE VIEW OF 18004375.03 PROPOSED MH 25
VERTICAL SCALE: 1" = 5'
PROFILE VIEW OF 18004375.03 PROPOSED MH 24
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 5'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
RJJ LKS
Revisions: Date:
FINAL BID DOCUMENTS 695-21-700
of
EHRM INFRASTRUCTURE
UPGRADES - MILWAUKEE, WI
SEPTEMBER 5, 2025
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Romanyk Consulting Focusing on what matters
0' 1'
2' 6" G ra ph ic
S ca le
1"
'-0
0' 1'
2' 6"
G ra ph ic
S ca le
3/ 4"
'-0
0' 2'
4' 1'
G ra ph ic
S ca le
1/ 2"
'-0
0' 2'
1' 4'
G ra ph ic
S ca le
1/ 4"
'-0
0' 8'
4'
G ra ph ic
S ca le
1/ 8"
'-0
0'
8'
G ra ph ic
S ca le
1/
1' -0
0' 4"
8" 1'
2'
G ra ph ic
S ca le
3/
1' -0
0' 1'
6" 3"
1'
G ra ph ic
S ca le
1/
2"
'-0
Sprinklered
Office of Construction and Facilities Management FULLY SPRINKLERED 5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
35% SCHEMATIC DESIGN SUBMISSION 5.17.21
65% DESIGN DEVELOPMENT SUBMISSION 6.15.21
65% DESIGN DEVELOPMENT RESUBMISSION 8.25.21
95% CONSTRUCTION DOCUMENTS 6.23.22
95% CONSTRUCTION DOCUMENTS RESUBMISSION 6.6.23
0' 3'
6'
1'
G ra ph ic
S ca le
/1
6"
'-0
LINNEA K.
SHAW
062-074863
STORM PLAN AND PROFILE 24 & 25
100-CU127
PROFILE VIEW OF 18004375.03 PROPOSED MH 28
VERTICAL SCALE: 1" = 5'
PROFILE VIEW OF 18004375.03 PROPOSED MH 26
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 5'
PROFILE VIEW OF 18004375.03 PROPOSED MH 27
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 5'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
RJJ LKS
Revisions: Date:
FINAL BID DOCUMENTS 695-21-700
of
EHRM INFRASTRUCTURE
UPGRADES - MILWAUKEE, WI
SEPTEMBER 5, 2025
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Romanyk Consulting Focusing on what matters
0' 1'
2' 6" G ra ph ic
S ca le
1"
'-0
0' 1'
2' 6"
G ra ph ic
S ca le
3/ 4"
'-0
0' 2'
4' 1'
G ra ph ic
S ca le
1/ 2"
'-0
0' 2'
1' 4'
G ra ph ic
S ca le
1/ 4"
'-0
0' 8'
4'
G ra ph ic
S ca le
1/ 8"
'-0
0'
8'
G ra ph ic
S ca le
1/
1' -0
0' 4"
8" 1'
2'
G ra ph ic
S ca le
3/
1' -0
0' 1'
6" 3"
1'
G ra ph ic
S ca le
1/
2"
'-0
Sprinklered
Office of Construction and Facilities Management FULLY SPRINKLERED 5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
35% SCHEMATIC DESIGN SUBMISSION 5.17.21
65% DESIGN DEVELOPMENT SUBMISSION 6.15.21
65% DESIGN DEVELOPMENT RESUBMISSION 8.25.21
95% CONSTRUCTION DOCUMENTS 6.23.22
95% CONSTRUCTION DOCUMENTS RESUBMISSION 6.6.23
0' 3'
6'
1'
G ra ph ic
S ca le
/1
6"
'-0
LINNEA K.
SHAW
062-074863
STORM PLAN AND PROFILE 26,27 & 28
100-CU128
PROFILE VIEW OF 18004375.03 PROPOSED MH 30
VERTICAL SCALE: 1" = 5'
PROFILE VIEW OF 18004375.03 PROPOSED MH 29
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 5'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
RJJ LKS
Revisions: Date:
FINAL BID DOCUMENTS 695-21-700
of
EHRM INFRASTRUCTURE
UPGRADES - MILWAUKEE, WI
SEPTEMBER 5, 2025
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Romanyk Consulting Focusing on what matters
0' 1'
2' 6" G ra ph ic
S ca le
1"
'-0
0' 1'
2' 6"
G ra ph ic
S ca le
3/ 4"
'-0
0' 2'
4' 1'
G ra ph ic
S ca le
1/ 2"
'-0
0' 2'
1' 4'
G ra ph ic
S ca le
1/ 4"
'-0
0' 8'
4'
G ra ph ic
S ca le
1/ 8"
'-0
0'
8'
G ra ph ic
S ca le
1/
1' -0
0' 4"
8" 1'
2'
G ra ph ic
S ca le
3/
1' -0
0' 1'
6" 3"
1'
G ra ph ic
S ca le
1/
2"
'-0
Sprinklered
Office of Construction and Facilities Management FULLY SPRINKLERED 5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
35% SCHEMATIC DESIGN SUBMISSION 5.17.21
65% DESIGN DEVELOPMENT SUBMISSION 6.15.21
65% DESIGN DEVELOPMENT RESUBMISSION 8.25.21
95% CONSTRUCTION DOCUMENTS 6.23.22
95% CONSTRUCTION DOCUMENTS RESUBMISSION 6.6.23
0' 3'
6'
1'
G ra ph ic
S ca le
/1
6"
'-0
LINNEA K.
SHAW
062-074863
STORM PLAN AND PROFILE 29 & 30
100-CU129
PROFILE VIEW OF 18004375.03 PROPOSED MH 33
VERTICAL SCALE: 1" = 5'
PROFILE VIEW OF 18004375.03 PROPOSED MH 31
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 5'
PROFILE VIEW OF 18004375.03 PROPOSED MH 32
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 5'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
RJJ LKS
Revisions: Date:
FINAL BID DOCUMENTS 695-21-700
of
EHRM INFRASTRUCTURE
UPGRADES - MILWAUKEE, WI
SEPTEMBER 5, 2025
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Romanyk Consulting Focusing on what matters
0' 1'
2' 6" G ra ph ic
S ca le
1"
'-0
0' 1'
2' 6"
G ra ph ic
S ca le
3/ 4"
'-0
0' 2'
4' 1'
G ra ph ic
S ca le
1/ 2"
'-0
0' 2'
1' 4'
G ra ph ic
S ca le
1/ 4"
'-0
0' 8'
4'
G ra ph ic
S ca le
1/ 8"
'-0
0'
8'
G ra ph ic
S ca le
1/
1' -0
0' 4"
8" 1'
2'
G ra ph ic
S ca le
3/
1' -0
0' 1'
6" 3"
1'
G ra ph ic
S ca le
1/
2"
'-0
Sprinklered
Office of Construction and Facilities Management FULLY SPRINKLERED 5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
35% SCHEMATIC DESIGN SUBMISSION 5.17.21
65% DESIGN DEVELOPMENT SUBMISSION 6.15.21
65% DESIGN DEVELOPMENT RESUBMISSION 8.25.21
95% CONSTRUCTION DOCUMENTS 6.23.22
95% CONSTRUCTION DOCUMENTS RESUBMISSION 6.6.23
0' 3'
6'
1'
G ra ph ic
S ca le
/1
6"
'-0
LINNEA K.
SHAW
062-074863
STORM PLAN AND PROFILE 31,32 & 33
100-CU130
PROFILE VIEW OF 18004375.03 PROPOSED MH 34
VERTICAL SCALE: 1" = 5'
PROFILE VIEW OF 18004375.03 PROPOSED MH 35
HORIZONTAL SCALE: 1" = 20'
VERTICAL SCALE: 1" = 5'
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
RJJ LKS
Revisions: Date:
FINAL BID DOCUMENTS 695-21-700
of
EHRM INFRASTRUCTURE
UPGRADES - MILWAUKEE, WI
SEPTEMBER 5, 2025
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Romanyk Consulting Focusing on what matters
0' 1'
2' 6" G ra ph ic
S ca le
1"
'-0
0' 1'
2' 6"
G ra ph ic
S ca le
3/ 4"
'-0
0' 2'
4' 1'
G ra ph ic
S ca le
1/ 2"
'-0
0' 2'
1' 4'
G ra ph ic
S ca le
1/ 4"
'-0
0' 8'
4'
G ra ph ic
S ca le
1/ 8"
'-0
0'
8'
G ra ph ic
S ca le
1/
1' -0
0' 4"
8" 1'
2'
G ra ph ic
S ca le
3/
1' -0
0' 1'
6" 3"
1'
G ra ph ic
S ca le
1/
2"
'-0
Sprinklered
Office of Construction and Facilities Management FULLY SPRINKLERED 5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
35% SCHEMATIC DESIGN SUBMISSION 5.17.21
65% DESIGN DEVELOPMENT SUBMISSION 6.15.21
65% DESIGN DEVELOPMENT RESUBMISSION 8.25.21
95% CONSTRUCTION DOCUMENTS 6.23.22
95% CONSTRUCTION DOCUMENTS RESUBMISSION 6.6.23
0' 3'
6'
1'
G ra ph ic
S ca le
/1
6"
'-0
LINNEA K.
SHAW
062-074863
STORM PLAN AND PROFILE 34 & 35
100-CU131
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
RJJ LKS
Revisions: Date:
FINAL BID DOCUMENTS 695-21-700
of
EHRM INFRASTRUCTURE
UPGRADES - MILWAUKEE, WI
SEPTEMBER 5, 2025
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Romanyk Consulting Focusing on what matters
0' 1'
2' 6" G ra ph ic
S ca le
1"
'-0
0' 1'
2' 6"
G ra ph ic
S ca le
3/ 4"
'-0
0' 2'
4' 1'
G ra ph ic
S ca le
1/ 2"
'-0
0' 2'
1' 4'
G ra ph ic
S ca le
1/ 4"
'-0
0' 8'
4'
G ra ph ic
S ca le
1/ 8"
'-0
0'
8'
G ra ph ic
S ca le
1/
1' -0
0' 4"
8" 1'
2'
G ra ph ic
S ca le
3/
1' -0
0' 1'
6" 3"
1'
G ra ph ic
S ca le
1/
2"
'-0
Sprinklered
Office of Construction and Facilities Management FULLY SPRINKLERED 5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
35% SCHEMATIC DESIGN SUBMISSION 5.17.21
65% DESIGN DEVELOPMENT SUBMISSION 6.15.21
65% DESIGN DEVELOPMENT RESUBMISSION 8.25.21
95% CONSTRUCTION DOCUMENTS 6.23.22
95% CONSTRUCTION DOCUMENTS RESUBMISSION 6.6.23
0' 3'
6'
1'
G ra ph ic
S ca le
/1
6"
'-0
LINNEA K.
SHAW
062-074863
CIVIL DETAILS
100-CK100
CONCRETE HEADER3
MOUNTABLE CONCRETE CURB AND GUTTER4
CONCRETE CURB AND TERMINAL SECTION2
TYPE 2 UTILITY TRENCH PATCH5 TYPE 3 UTILITY TRENCH PATCH6
GENERAL NOTES
SEE PLAN
5" PCC
4" AGGREGATE BASE
(98% STD. DENSITY) (TYPE A)
COMPACTED SUBGRADE
CORE DRILL HOLE
FOR PIPE ENTRY
SEE PLANS FOR
ELEVATIONS
1" CLEAN STONE,
8" DEPTH
6" PERFORATED PIPE
6" PVC
CORE DRILL HOLE
FOR PIPE ENTRY
SEE PLANS FOR
ELEVATIONS
1" CLEAN STONE,
8" DEPTH
SEE TECHNOLOGY
PLANS FOR MANHOLE
SIZE AND DETAILS
PCC SIDEWALK DETAIL1
MANHOLE DRAINAGE DETAIL7
A A
CROSS-SECTION
PLAN
SECTION A-A
PROFILE
ENGINEERING FABRIC
TO
P
O F
PO
N
D
W
ID
TH
, W
ENGINEERING FABRIC
NOTES:
1. DETAIL DERIVED FROM SUDAS
(DWG NO. 9040.111).
T (ft.)
W (FT.) REVETMENT
2.5 MEDIUM RIP RAP
WATER LEVEL
PIPE OUTLET NEAR POND8
L (ft.)
30'-0"
'-0
S001
NEW GENERATOR
8" 8"
SEE PLAN
GRADE - SEE CIVIL
#5 DOWEL @ 12" OC
2'-6"
2'-6"
#5 @ 12" OC VERT
#5 @ 12" OC HORIZ
8" CONCRETE SLAB ON
GRADE REINFORCED WITH
#5 @ 12" OC EACH WAY
GENERATOR - SEE
ELECTRICAL DRAWINGS
TYP
6" MIN
3/4" CHAMFER,
TYP
NOTES:
1. REFER TO ELECTRICAL DRAWINGS FOR SIZE AND LOCATION OF GENERATOR.
2. COORDINATE LOCATION OF NEW GENERATOR PAD AND DIMENSIONS WITH
ELECTRICAL CONTRACTOR AND CIVIL DRAWINGS.
BUILDING 148
KEYPLAN
NO SCALE
S001
N O R
HT
15 SUNNEN DRIVE
SUITE 104
ST. LOUIS, MO 63143
P: 314.645.1132 F: 314.645.1173
The FUTURE. Built Smarter www.imegcorp.com
PROJECT #18004375.03 0
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
/8
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
35% SCHEMATIC DESIGN SUBMISSION 5.17.21
65% DESIGN DEVELOPMENT SUBMISSION 6.15.21
65% DESIGN DEVELOPMENT RESUBMISSION 8.25.21
5000 W. NATIONAL AVENUE MILWAUKEE, WI
fi le s \A c ti v e
\P ro je c ts
\2
\1
.0
\V ir tu a lD e s ig n \R e v it \S tr u c tu ra l R e v it M o d e l\ S
.0
V A
M
IL
W A
U K
E E
E H
R M
C
.r v t
/2
/2
:3
:1
A
M
GENERAL NOTES, EQUIPMENT PLAN AND
DETAIL
KATGOL WALLEW
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES - MILWAUKEE, WI
SEPTEMBER 5, 2025
S001
1/8" = 1'-0"
NEW EQUIPMENT PAD
1 3/4" = 1'-0"
EQUIPMENT PAD SECTION
Revisions: Date:
DESIGN CRITERIA
1. STRUCTURE HAS BEEN DESIGNED TO COMPLY WITH:
IBC 2021
ASCE 7-16
ACI 318-19
2. SNOW:
GROUND SNOW 30 PSF
SNOW EXPOSURE FACTOR 0.9
THERMAL FACTOR 1.0
IMPORTANCE FACTOR 1.0
FLAT-ROOF SNOW 20 PSF
DESIGN SNOW 20 PSF
3. WIND:
BASIC WIND SPEED V ULT = 107 MPH
IMPORTANCE FACTOR 1.0
EXPOSURE CLASS B
MWFRS DESIGN WIND PRESSURE BY EQUIPMENT MANUFACTURER
GENERAL
1. DURING THE CONSTRUCTION PERIOD, THE CONTRACTOR SHALL BE RESPONSIBLE FOR
THE SAFETY OF PERSONNEL AND PROPERTY ON AND AROUND THE JOBSITE. THE
CONTRACTOR SHALL PROVIDE ADEQUATE SHORING, BRACING, GUYS, ETC. IN
ACCORDANCE WITH ALL NATIONAL, STATE, AND LOCAL SAFETY ORDINANCES.
2. ALL DRAWINGS ARE CONSIDERED TO BE A PART OF THE CONTRACT DOCUMENTS. THE
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REVIEW AND COORDINATION
OF ALL DRAWINGS PRIOR TO THE START OF CONSTRUCTION. ANY DISCREPANCIES SHALL
BE BROUGHT TO THE ATTENTION OF THE ARCHITECT PRIOR TO THE START OF
CONSTRUCTION SO A CLARIFICATION CAN BE ISSUED. ANY WORK PERFORMED IN
CONFLICT WITH THE CONTRACT DOCUMENTS OR ANY CODE REQUIREMENTS SHALL BE
CORRECTED BY THE CONTRACTOR AT THEIR OWN EXPENSE AND AT NO EXPENSE TO THE
OWNER OR ARCHITECT.
3. STRUCTURAL SUBSTITUTIONS MAY BE ALLOWED WITH THE APPROVAL OF THE
STRUCTURAL ENGINEER. SUPPLIER SHALL PROVIDE SEALED DESIGN CALCULATIONS OR
SUITABLE PRODUCT LITERATURE FOR THE COMPONENTS.
4. ALL DIMENSIONS AND SITE CONDITIONS SHALL BE VERIFIED BY THE CONTRACTOR AT THE
JOBSITE PRIOR TO CONSTRUCTION, START OF SHOP DRAWINGS, START OF
CONSTRUCTION, AND/OR FABRICATION OF MATERIALS. IF DISCREPANCIES ARE
ENCOUNTERED, OR CONDITIONS DEVELOP THAT ARE NOT COVERED BY THE CONTRACT
DOCUMENTS, THE ARCHITECT SHALL BE NOTIFIED FOR CLARIFICATION.
5. CONTRACTOR SHALL PROVIDE AND BE RESPONSIBLE FOR THE PROTECTION AND REPAIR
OF ADJACENT EXISTING SURFACES AND AREAS WHICH MAY BE DAMAGED AS A RESULT OF
NEW WORK.
6. STRUCTURAL DRAWINGS INCLUDE DESIGN REQUIREMENTS AND DIMENSIONS FOR
STRUCTURAL INTEGRITY BUT DO NOT SHOW ALL DETAIL DIMENSIONS TO FIT INTRICATE
ARCHITECTURAL AND MECHANICAL DETAILS. CONTRACTOR SHALL SO CONSTRUCT THE
WORK SO IT WILL CONFORM TO THE CLEARANCES REQUIRED BY ARCHITECTURAL,
MECHANICAL AND ELECTRICAL DESIGN.
7. ALL SYMBOLS AND ABBREVIATIONS USED ON THE DRAWINGS ARE CONSIDERED TO BE
CONSTRUCTION STANDARDS. IF CLARIFICATION IS REQUIRED, THE CONTRACTOR SHALL
NOTIFY THE ARCHITECT PRIOR TO PROCEEDING WITH THE WORK.
8. DO NOT SCALE DRAWINGS. PRINTED DIMENSIONS HAVE PRECEDENCE OVER SCALED
DRAWINGS AND LARGE-SCALE OVER SMALL-SCALE DRAWINGS. CONTRACTOR TO
DETERMINE FINAL DIMENSION WITH ARCHITECT.
9. TYPICAL DETAILS SHALL APPLY TO SITUATIONS OCCURRING ON THE PROJECT THAT ARE
THE SAME OR SIMILAR TO THOSE SPECIFICALLY REFERENCED. WHERE NO DETAILS ARE
GIVEN, CONSTRUCTION SHALL BE AS SHOWN FOR SIMILAR WORK.
10. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE. THEY DO NOT
INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL
MEASURES NECESSARY TO PROTECT THE STRUCTURE AND SAFETY OF WORKMEN
DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT BE LIMITED TO,
BRACING AND SHORING FOR LOADS DUE TO CONSTRUCTION EQUIPMENT, ETC.
OBSERVATION VISITS TO THE SITE BY THE ARCHITECT OR STRUCTURAL ENGINEER SHALL
NOT INCLUDE INSPECTION OR APPROVAL OF THE ABOVE ITEMS AND DO NOT IN ANY WAY
RELIEVE THE CONTRACTOR OF THEIR RESPONSIBILITIES FOR THE ABOVE.
11. SEE ARCHITECTURAL, ELECTRICAL AND MECHANICAL DRAWINGS FOR DETAILS,
CONDITIONS, PITS, TRENCHES, PADS, DEPRESSIONS, ROOF/FLOOR OPENINGS, STAIRS,
SLEEVES, ITEMS TO BE EMBEDDED OR ATTACHED TO STRUCTURAL ELEMENTS, ETC., NOT
SHOWN ON THE STRUCTURAL DRAWINGS.
12. ESTABLISH AND VERIFY ALL OPENINGS AND INSERTS FOR MECHANICAL, ELECTRICAL AND
PLUMBING WITH APPROPRIATE TRADE CONTRACTORS. OPENING SIZES AND LOCATIONS
SHOWN FOR DUCTS, PIPE, INSERTS AND OTHER PENETRATIONS WHEN SHOWN ARE FOR
GENERAL INFORMATION ONLY AND SHALL BE VERIFIED PRIOR TO FORMING.
13. NO HOLES, NOTCHES, BLOCK-OUTS, ETC. ARE ALLOWED IN STRUCTURAL ELEMENTS
UNLESS SPECIFICALLY DETAILED ON THE STRUCTURAL DRAWINGS OR APPROVED BY THE
STRUCTURAL ENGINEER.
14. PENETRATIONS SHALL BE CAST-IN-PLACE AND SHALL NOT BE PERMITTED EXCEPT AS
SHOWN IN THE STRUCTURAL DRAWINGS.
15. BEFORE SUBMITTING A PROPOSAL FOR THIS WORK, EACH PARTY SHALL VISIT THE
PREMISES AND BECOME FULLY ACQUAINTED WITH CONDITIONS IN FIELD, TEMPORARY
CONSTRUCTION REQUIRED, QUANTITIES AND TYPE OF EQUIPMENT, ETC. THE PROPOSAL
SHALL INCLUDE ALL SUMS REQUIRED TO DO THE WORK.
REINFORCING STEEL
1. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN CONFORMANCE WITH THE
AMERICAN CONCRETE INSTITUTE “ACI DETAILING MANUAL” (SP-066) EXCEPT AS
OTHERWISE SHOWN, NOTED OR SPECIFIED.
2. CONCRETE REINFORCING STEEL SHALL BE HIGH STRENGTH NEW BILLET STEEL
CONFORMING TO THE FOLLOWING STANDARDS:
DEFORMED BARS ASTM A615, GR 60 Fy = 60 KSI
3. MINIMUM CONCRETE COVER SHALL BE PROVIDED AS FOLLOWS TO THE OUTERMOST
REINFORCING BARS:
CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND 3”
EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
#6 BARS OR LARGER 2”
#5 BARS OR SMALLER 1 1/2”
NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
SLABS, JOIST AND WALLS WITH #14 AND #18 BARS 1 1/2”
SLABS, JOISTS AND WALLS WITH #11 BARS OR SMALLER 3/4”
4. SUPPORTS FOR REINFORCEMENT SHALL HAVE CLASS 2 PROTECTION AS DEFINED IN THE
CRSI MANUAL OF STANDARD PRACTICE, UNLESS OTHERWISE NOTED.
5. WHERE REINFORCEMENT LENGTH IS SPECIFIED, NO SPLICES ARE PERMITTED WITHIN THE
SPECIFIED LENGTH WITHOUT APPROVAL BY THE STRUCTURAL ENGINEER.
6. CUTTING OF REINFORCING WHICH CONFLICTS WITH EMBEDDED OBJECTS OR SLEEVES IS
NOT ACCEPTABLE.
7. REINFORCING BARS SHALL BE BENT COLD, AND NO METHOD OF FABRICATION SHALL BE
USED WHICH WOULD BE INJURIOUS TO THE MATERIAL. HEATING OF BARS FOR BENDING IS
NOT PERMITTED.
8. FIELD WELDING OR BENDING OF REINFORCING IS NOT PERMITTED EXCEPT AS INDICATED
ON THE DRAWINGS OR AS APPROVED BY THE STRUCTURAL ENGINEER.
9. ALL CONCRETE NOT OTHERWISE SPECIFIED SHALL BE REINFORCED TO THE MINIMUM
REQUIREMENT OF ACI 318.
EARTHWORK
1. FOUNDATION DESIGN IS IN ACCORDANCE WITH THE BUILDING CODE ALLOWABLE BEARING
PRESSURES. NO NEW GEOTECHNICAL REPORT HAS BEEN PROVIDED BY THE OWNER FOR
THIS PROJECT.
2. SOIL PROPERTIES PER THE GEOTECHNICAL REPORT:
ALLOWABLE NET SOIL BEARING PRESSURE:
FOOTINGS 1500 PSF (ASSUMED)
3. CARE SHALL BE EXERCISED WHEN EXCAVATING OR GRADING ADJACENT TO EXISTING
STRUCTURES OR IMPROVEMENTS TO NOT DAMAGE OR UNDERMINE FOUNDATIONS,
WALLS, SLABS, UTILITIES, ETC.
4. CONTRACTOR SHALL INVESTIGATE SITE DURING CLEARING AND EARTHWORK
OPERATIONS FOR FILL MATERIAL OR BURIED STRUCTURES SUCH AS CESSPOOLS,
CISTERNS AND FOUNDATIONS. IF ANY SUCH MATERIAL OR STRUCTURES ARE FOUND,
ARCHITECT/ENGINEER SHALL BE NOTIFIED IMMEDIATELY. ALL ABANDONED FOUNDATIONS,
UTILITIES AND OTHER STRUCTURES THAT INTERFERE WITH NEW CONSTRUCTION SHALL
BE REMOVED.
5. ALL FOOTINGS AND SLABS ON GRADE SHALL BE PLACED ONTO FIRM UNDISTURBED SOIL
OR CONTROLLED COMPACTED FILL, REMOVING ANY EXISTING FILL, ORGANIC MATERIAL,
OR UNSUITABLE SOILS. EXPOSED NATURAL SOIL SHALL BE PROOF ROLLED BELOW SLABS
ON GRADE.
6. FOUNDATION ELEVATIONS SHOWN DESIGNATE A MINIMUM DEPTH WHERE AN ADEQUATE
SOIL BEARING PRESSURE IS EXPECTED. FOOTINGS, PIERS AND/OR WALLS SHALL BE
LOWERED OR EXTENDED AS REQUIRED TO REACH SOIL MEETING THE DESIGN BEARING
PRESSURE.
7. ALL REQUIRED BACKFILL AND UTILITY TRENCH BACKFILL WITHIN THE BUILDING AREA
SHALL BE MECHANICALLY COMPACTED IN 8” LAYERS TO 95% MAXIMUM DRY DENSITY PER
ASTM D1557 AND TO THE APPROVAL OF THE INSPECTION AGENCY
8. THE MOISTURE CONTENT OF ONSITE CLAYEY SOILS AT THE TIME OF COMPACTION SHALL
BE BETWEEN 2-3% ABOVE OPTIMUM MOISTURE CONTENT.
9. ANY REQUIRED IMPORT FILL SOIL SHALL HAVE A LOW POTENTIAL FOR EXPANSION AND
SHALL BE APPROVED BY THE GEOTECHNICAL ENGINEER PRIOR TO IMPORTING.
CAST-IN-PLACE CONCRETE
1. ALL CONCRETE WORK SHALL CONFORM TO THE CORRESPONDING EDITION OF THE
AMERICAN CONCRETE INSTITUTE PUBLICATIONS: ACI 117, ACI 301, ACI 305.1, ACI 306.1, ACI
308.1, ACI 318 AND SP-066, UNLESS OTHERWISE NOTED.
2. CONCRETE MATERIALS SHALL CONFORM TO:
CEMENT ASTM C150, TYPE I OR II
FLY ASH ASTM C618, TYPE C OR F
FINE AND COARSE AGGREGATE ASTM C33
WATER POTABLE
AIR-ENTRAINING ADMIXTURE ASTM C260
WATER REDUCING ADMIXTURE ASTM C494
CONCRETE STRENGTHS SHALL CONFORM TO:
INTENDED USE STRENGTH (PSI) EXPOSURE
CLASS
UNLESS OTHERWISE NOTED 5000 F3, C2
NORMAL-WEIGHT 28-DAY STRENGTH UNLESS OTHERWISE NOTED.
3. THE MODULUS OF ELASTICITY OF ALL CONCRETE SHALL EXCEED 57,000 SQRT(f’c) FOR NORMAL-WEIGHT CONCRETE OR wc1.5 33 SQRT(f’c).
4. CROSS REFERENCE ARCHITECTURAL AND STRUCTURAL DRAWINGS TO ENSURE PROPER
DIMENSIONS AND PLACEMENT OF ALL ANCHOR BOLTS, INSERTS, NOTCHES, AND EDGES
OF WALLS/FOUNDATIONS PRIOR TO PLACING CONCRETE.
5. UNLESS OTHERWISE NOTED, ALL FOOTINGS SHALL BE CENTERED UNDER WALLS, PIERS
OR COLUMNS.
6. PRIOR TO PLACING CONCRETE, THE CONTRACTOR SHALL ENSURE ALL REINFORCING AND
EMBEDMENTS, INCLUDING COLUMN ANCHOR BOLTS, ARE PROPERLY LOCATED AND
SECURELY TIED IN PLACE.
7. PROVIDE SLEEVES FOR PLUMBING AND ELECTRICAL PENETRATIONS THROUGH
CONCRETE BEFORE PLACING. SECURE SLEEVES TO PREVENT MOVEMENT DURING
PLACING OPERATIONS. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATIONS.
8. CONFIRM WITH ARCHITECT THAT MATERIALS TO BE EMBEDDED ARE SUITABLE FOR
EMBEDMENT IN CONCRETE.
9. CONDUIT, PIPES, AND SLEEVES EMBEDDED IN CONCRETE SHALL CONFORM TO
REQUIREMENTS OF ACI 318, SECTIONS 20.7 AND 26.8.
10. NO ALUMINUM SHALL BE ALLOWED IN THE CONCRETE WORK UNLESS COATED TO
PREVENT ALUMINUM-CONCRETE REACTION.
11. PROJECTING CORNERS OF BEAMS, WALLS, COLUMNS, ETC., SHALL BE FORMED WITH A 3/4
INCH CHAMFER, UNLESS OTHERWISE NOTED ON ARCHITECTURAL DRAWINGS.
12. SLOPE SLABS TO DRAINS OR FOR POSITIVE DRAINAGE IF NO DRAINS ARE PRESENT AND
PROVIDE DEPRESSIONS WHERE SHOWN ON THE STRUCTURAL AND/OR ARCHITECTURAL
DRAWINGS WITHOUT REDUCING THE THICKNESS OF SLAB INDICATED. FOR SLAB-ON-
GRADE DEPRESSIONS GREATER THAN 1 INCH, SEE DETAILS FOR ADDITIONAL
REINFORCING.
13. CONCRETE SHALL NOT BE PERMITTED TO DROP MORE THAN 5 FEET.
14. IF CONCRETE IS PLACED BY PUMPING, SUPPORT SHALL BE PROVIDED FOR THE HOSE. THE
HOSE SHALL NOT BE ALLOWED TO RIDE ON THE REINFORCING AND OTHER EMBEDDED
ITEMS.
15. CONCRETE SLABS SHALL BE CURED BY KEEPING CONTINUOUSLY WET FOR 7 DAYS.
FORMS FOR CONCRETE WALLS SHALL BE LEFT IN PLACE FOR 7 DAYS OR MAY BE
STRIPPED AFTER 3 DAYS AND COATED WITH AN APPROVED CURING COMPOUND.
16. NO LOADS SHALL BE PLACED ON STRUCTURAL CONCRETE SLABS WITHIN 7 DAYS AFTER
CONCRETE IS PLACED. AFTER CONCRETE IS PLACED, IN NO CASE SHALL THE
SUPERIMPOSED CONSTRUCTION LOADS BE GREATER THAN SPECIFIED DESIGN LIVE
LOADS, UNLESS THE WORK IS SHORED.
17. NOTIFY THE ARCHITECT/STRUCTURAL ENGINEER 48 HOURS MINIMUM PRIOR TO ALL
POURS.
18. CONTRACTOR SHALL SURVEY ALL CONCRETE WORK WITHIN 48 HOURS OF PLACING
CONCRETE TO ENSURE PLACEMENT IS IN ACCORDANCE WITH PROJECT REQUIREMENTS.
19. NO CONCRETE SHALL BE PLACED ONTO OR AGAINST SUBGRADES CONTAINING FREE
WATER, FROST, ICE OR SNOW.
20. DURING WINTER CONSTRUCTION, ALL FOOTINGS SHALL BE PROTECTED FROM FROST
PENETRATION UNTIL THE BUILDING IS ENCLOSED AND TEMPORARY HEAT IS PROVIDED.
21. GENERAL CONTRACTOR TO PROVIDE SHOP DRAWINGS FOR SIZE, LOCATION AND HEIGHT
OF MECHANICAL EQUIPMENT PADS ON CONCRETE SLAB ON STEEL DECK AND SLAB-ON-
GRADE.
22. THE PROPOSED MATERIALS AND MIX DESIGN SHALL BE FULLY DOCUMENTED AND
REVIEWED BY THE TESTING AGENCY. RESPONSIBILITY FOR OBTAINING THE REQUIRED
DESIGN STRENGTH IS THE CONTRACTOR’S. SUBMIT TEST DATA ON EACH PROPOSED MIX
FOR REVIEW IN ACCORDANCE WITH THE APPLICABLE CODE. MIX DESIGNS SUBMITTED
WITHOUT THE REQUIRED TEST DATA WILL BE RETURNED WITHOUT REVIEW.
TESTING, INSPECTIONS, AND OBSERVATIONS
1. THE STRUCTURAL ENGINEER DOES NOT PROVIDE INSPECTIONS OF CONSTRUCTION. STRUCTURAL ENGINEER MAY MAKE PERIODIC OBSERVATIONS OF THE CONSTRUCTION. SUCH OBSERVATIONS SHALL NOT REPLACE REQUIRED INSPECTIONS BY THE GOVERNING AUTHORITIES OR SERVE AS “SPECIAL INSPECTIONS” AS MAY BE REQUIRED BY CHAPTER 17 OF THE INTERNATIONAL BUILDING CODE.
2. SEE ARCHITECTURAL, CIVIL, MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS OR SPECIFICATIONS FOR TESTING AND INSPECTION
REQUIREMENTS OF NON-STRUCTURAL COMPONENTS.
3. DUTIES OF THE INSPECTION AGENCY PER IBC CHAPTER 17:
a. SUBMIT A PROPOSED TESTING AND INSPECTION PROGRAM TO THE OWNER, THE ARCHITECT AND THE STRUCTURAL ENGINEER FOR REVIEW AND
APPROVAL AT LEAST TWO WEEKS PRIOR TO COMMENCEMENT OF WORK.
b. PERFORM ALL TESTING AND INSPECTION REQUIRED PER APPROVED TESTING AND INSPECTION PROGRAM.
c. FURNISH INSPECTION REPORT TO THE BUILDING OFFICIAL, THE OWNER, THE ARCHITECT, STRUCTURAL ENGINEER AND THE GENERAL CONTRACTOR. THE REPORTS SHALL BE COMPLETED AND FURNISHED WITHIN 48 HOURS OF INSPECTED WORK.
d. SUBMIT A FINAL SIGNED REPORT STATING WHETHER THE WORK REQUIRING SPECIAL INSPECTION WAS, TO THE BEST OF THE SPECIAL INSPECTION
AGENCY’S KNOWLEDGE, IN CONFORMANCE WITH THE APPROVED PLANS AND SPECIFICATIONS.
4. SPECIAL INSPECTIONS AND TESTS ARE REQUIRED FOR MATERIALS AND SYSTEMS REQUIRED TO BE INSTALLED IN ACCORDANCE WITH ADDITIONAL MANUFACTURER’S INSTRUCTIONS THAT PRESCRIBE REQUIREMENTS NOT CONTAINED IN CHAPTER 17 OF THE IBC OR IN STANDARDS REFERENCED BY
THE IBC. THESE ITEMS INCLUDE:
a. POST-INSTALLED ANCHORS - INSPECTION
5. THE FOLLOWING WORK SHALL BE INSPECTED BY THE SPECIAL INSPECTOR UNLESS SPECIFICALLY WAIVED BY THE BUILDING OFFICIAL.
VERIFICATION AND INSPECTION TASK CONTINUOUS PERIODIC MATERIAL STD
REFERENCE
IBC
REFERENCE
CONCRETE CONSTRUCTION
1. INSPECT REINFORCEMENT, AND VERIFY PLACEMENT X ACI 318: CH 20,
25.2, 25.3, 26.2.1-26.6.3
1908.4
2. MATERIAL IDENTIFICATION OF REINFORCING (TYPE/GRADE) X AISC 341: TABLE
J9.1
3. REINFORCING STEEL HAS NOT BEEN REBENT IN THE FIELD X AISC 341: TABLE
J9.1
4. REINFORCING STEEL HAS BEEN TIED AND SUPPORTED AS REQUIRED X AISC 341: TABLE
J9.1
5. REINFORCING STEEL CLEARANCES HAVE BEEN PROVIDED X AISC 341: TABLE
J9.1
6. INSPECT ANCHORS CAST IN CONCRETE X ACI 318: 17.8.2
7. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE MEMBERS:
a. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS
X ACI 318: 17.8.2.4
b. MECHANICAL ANCHORS AND ADHESIVE ANCHORS NOT DEFINED IN 4.a X ACI 318: 17.8.2
8. VERIFY USE OF REQUIRED DESIGN MIX X ACI 318: CH 19,
26.4.2, 26.4.4
1904.1, 1904.2, 1908.2, 1908.3
9. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH TESTS,
PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE
OF THE CONCRETE
X ASTM C172, ASTM
C31, ACI 318: 26.5,
26.12
1908.10
10. INSPECT CONCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES X ACI 318: 26.5 1908.6, 1908.7, 1908.8
11. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES X ACI 318:
26.5.3-26.5.5
1908.9
12. VERIFY IN-SITU CONCRETE STRENGTH X ACI 318: 26.11.2
13. INSPECT FORMWORK FOR SHAPE, LOCATION, AND DIMENSIONS OF THE CONCRETE
MEMBER BEING FORMED
X ACI 318: 26.11.2(b)
VERIFICATION AND INSPECTION TASK CONTINUOUS PERIODIC MATERIAL STD
REFERENCE
IBC
REFERENCE
SOILS
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE
THE DESIGN BEARING CAPACITY
X
2. VERIFY EXCAVATIONS ARE EXTENDED TO PROPER DEPTH AND HAVE REACHED
PROPER MATERIAL
X
3. PERFORM CLASSIFICATIONS AND TESTING OF COMPACTED FILL MATERIAL X
4. VERIFY USE OF PROPER MATERIALS, DENSITIES, AND LIFT THICKNESSES DURING
PLACEMENT AND COMPACTION OF COMPACTED FILL
X
5. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND VERIFY THAT
SITE HAS BEEN PREPARED PROPERLY
X
8/29/2025
DEMO LEGEND
DEMO KEYNOTES
ENTRY
RCP DEMO LEGEND
DEMO NOTES
RCP KEYNOTES
AREA NOT IN CONTRACT
EXISTING WALL AND ASSOCIATED COMPONENTS
SHALL BE REMOVED - REFER TO DEMOLITION
KEYNOTES FOR ADDITIONAL DETAILS AT SPECIFIC
CONDITIONS.
EXISTING DOOR, FRAME, HARDWARE AND
ASSOCIATED COMPONENTS SHALL BE REMOVED
-REFER TO DEMOLITION KEYNOTES FOR
ADDITIONAL DETAILS AT SPECIFIC CONDITIONS
EXISTING WALL SHALL REMAIN
EXISTING DOOR, FRAME AND HARDWARE
SHALL REMAIN
GRAY AREA NOT IN
PROJECT SCOPE
STORAGE
0031 2
3 4
STORAGE
DEMO ACT CEILING
DEMO HUNG LIGHT FIXTURE
AREA OF WORK
1. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT OF ANY DIMENSIONAL
DISCREPANCIES DISCOVERED DURING CONSTRUCTION.
2. REFER TO MECHANICAL, PLUMBING, ELECTRICAL, AND TECHNOLOGY DRAWINGS
FOR MORE INFORMATION.
3. ALL ABANDONED LINES, PIPES, CONDUITS DISCOVERED AFTER CEILING
REMOVAL ARE ALSO TO BE REMOVED.
4. REFER TO ELECTRICAL DRAWINGS FOR LOCATION OF EMERGENCY LIGHTING.
5. CENTER CEILING AND LIGHTS IN ALL SPACES WHERE POSSIBLE, U.N.O.
6. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF UNDER-CABINET LIGHT
FIXTURES.
7. GYP. BD. SOFFITS ABOVE UPPER CABINETS SHALL EXTEND TO TOP OF CABINET
(7'-0" U.N.O.).
8. THIS SHEET IS FOR LAYOUT ONLY. SEE ELECTRICAL AND MECHANICAL
DRAWINGS FOR EXACT FIXTURE QUANTITY. ALL SWITCHES, OUTLETS, LIGHTS,
DIFFUSERS, ETC. MUST BE LOCATED PER ARCHITECTURAL DRAWINGS WHERE
APPLICABLE.
9. PROVIDE ACCESS PANELS IN GYPSUM CEILINGS WHERE REQUIRED TO ACCESS
ABOVE CEILING EQUIPMENT. (SEE SPECS)
10. ALL CEILINGS SHALL BE 9'-0" AFF U.N.O.
11. REFER TO FINISH DRAWINGS FOR CEILING GRID AND PANEL TYPE AND SIZE.
12. BOTTOM OF GYP. BD. BULKHEADS SHALL BE 8'-6" AFF U.N.O.
13. ALL PARTITION WALLS SHALL EXTEND TO UNDERSIDE OF DECK ABOVE U.N.O.
14. ALL FRAMING MEMBERS SHALL BE ADEQUATELY SIZED FOR THE REQUIRED
SPAN/SPACING. REFER TO SPECS FOR ADDITIONAL GYP. BD. INFORMATION. GYP.
BD. CEILINGS SHALL BE INSTALLED PER ASTM C840.
15. VERIFY IN FIELD ALL DIMENSIONS PRIOR TO PROCEEDING WITH ANY WORK AND
AFTER DEMOLITION SITE SURVEY THE SPACE DIMENSIONS, EQUIPMENT, DOOR,
MECHANICALS, ELECTRICAL, FIRE PROTECTION, ETC. AND COORDINATE WITH NEW
CONSTRUCTION. BRING ANY DISCREPANCIES AND OR QUESTION TO THE AE AND
COR PRIOR TO PROCEEDING FORWARD WITH ANY NEW CONSTRUCTION. USE THIS
DOCUMENT FOR SUBCONTRACTOR REVIEW AS ACCEPTANCE OF CONDITIONS.
NOTE NUMBER NOTE
EXPOSED CEILING
DEMO EXISTING CEILING FINISHES AND FIXTURES
REPLACE CEILING TILES IN AREA OF WORK
REMOVE, SALVAGE, AND REINTSTALL CEILING TILES IN AREA OF WORK
PATCH AND REPAIR EXISTING CEILING
EXPOSED CEILING. PATCH, REPAIR AND PAINT AS REQUIRED.
DEMO EXISTING CEILING FINISHES AND FIXTURES.
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
G ra p h ic S c a le
/1
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3 /2
:3
:3
P
M
BUILDING 03 FIRST FLOOR DEMO PLAN & RCP
RCO HS
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
03-AD101
5000 W. NATIONAL AVENUE MILWAUKEE, WI
1/4" = 1'-0"
BUILDING 03 FIRST FLOOR DEMO PLAN
Note Number Note
1 REMOVE AND SALVAGE FURNITURE, EQUIPMENT AND FIXTURES SECURED TO THE
WALL. STORE AT VA DESIGNATED LOCATION.
2 REMOVE FLOOR FINISH, FLOOR COVERING, WALL BASE, WALL COVERING, WALLS
AND ASSOCIATED COMPONENTS. CLEAN AND PATCH WALLS AND FLOORS AS
REQUIRED TO RECEIVE NEW FINISHES. LEVEL FLOOR AS REQUIRED FOR NEW
FINISH.
3 REMOVE ALL COVERINGS FROM EXISTING WALL PARTITION ASSEMBLIES ON THE
DEMO SIDE ONLY. DO NOT REMOVE FRAMING, SOUND BATTS, GYP.BD ON
NON-DEMO SIDE. REFER TO FINISH SCHEDULE FOR NEW FINISHES. REFER TO THE
FLOOR PLAN FOR NEW WORK.
4 REMOVE EXISTING DOOR, DOOR FRAME, DOOR HARDWARE AND DISPOSE
MATERIALS. PREPARE WALL TO BE INFILLED.
6 EXISTING TELECOMMUNICATIONS ROOM TO REMAIN. REFERENCE TECHNOLOGY
SHEETS FOR MORE INFORMATION.
7 DEMO EXISTING CASEWORK.
8 REMOVE EXISTING TELCOMMUNICATIONS ROOM EQUIPMENT AND STORE IN VA
DESIGNATED AREA.
9 REMOVE EXISTING SINK. REFERENCE PLUMBING DEMOLITION SHEET FOR
ADDITIONAL INFORMATION.
10 DEMO EXISTING SOFFIT.
11 EXISTING WINDOW TO REMAIN. SEAL WINDOW AND TINT FROM INTERIOR OF
WINDOW (TYP.). DEMO EXISTING TRIM AND PREPARE WALL TO BE INFILLED TO
MATCH EXISTING.
12 DEMO EXISTING CEILING FINISHES AND FIXTURES.
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1/4" = 1'-0"
BUIDLING 3 FIRST FLOOR DEMO RCP
NTS
KEY PLAN - BLDG 3
Revisions: Date:
GENERAL NOTES
AREA PLAN LEGEND
KEYNOTES
STORAGE
RCP LEGEND
RCP KEYNOTES
1. G.C. SHALL VERIFY DIMENSIONS OF OWNER FURNISHED
EQUIPMENT AND COORDINATE INSTALLATION WITH ALL
TRADES WHERE REQUIRED.
2. REFER TO FINISH SHEETS FOR PARTITION PROTECTION
INFORMATION INCLUDING BUT NOT LIMITED TO ALL CORNER
GUARD TYPES AND LOCATIONS.
3. G.C. SHALL INSTALL IN-WALL METAL BACKING FOR ALL
PARTITION-MOUNTED EQUIPMENT, ACCESSORIES,
PARTITION STOPS, ETC.
4. G.C. SHALL INSTALL FIRE-RETARDANT WOOD BLOCKING
WITHIN WALLS BASED ON CASEWORK ELEVATIONS AND ALL
INTERIOR PARTITION ELEVATIONS.
5. ALL INTERIOR WALLS SHALL RECEIVE 5/8" TYPE 'X' GYPSUM
BOARD.
6. G.C. SHALL PROVIDE UL APPROVED FIRE-RESISTIVE
PENETRATION SYSTEMS WHERE PLUMBING IS LOCATED IN A
FIRE-RATED PARTITION ASSEMBLY.
7. ALL EXTERIOR WINDOWS OPEN TO THE INTERIOR SHALL
RECEIVE A SOLID SURFACE WINDOW STOOL. REFER TO
FINISH DRAWINGS FOR MATERIAL SELECTION.
8. EXTEND ALL RATED WALLS TO DECK PER UL ASSEMBLY
REQUIREMENTS. REFER TO PARTITION TYPES SHEET FOR
INTERIOR PARTITION TYPES & DETAILS. G.C. SHALL VERIFY
ALL WALLS GO TO STRUCTURE ABOVE.
9. REFER TO PARTITION TYPES SHEET FOR RATED PARTITION
PRIORITY AND RATED PARTITION INTERSECTIONS.
10. ALL RATED WALLS SHOWN ON PLANS TO BE ASSUMED AS
NEW RATED WALLS UNTIL VERIFIED ON SITE.
11. THE ABESTOS REMOVAL REQUIREMENTS, SHOWN FOR
REFENCE ONLY, WERE PERFORMED UNDER A SEPARATE
CONTRACT WITH ALL RELATED DOCUMENTS INCLUDED IN
THE SPECIFICATIONS.
12. G.C.SHALL PATCH AND REPAIR CEILING TO MATCH EXISTING
HEIGHT, MATERIAL AND PATTERN IN CORRIDORS. REFER TO
MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS
FOR CONNECTIONS FROM INTERIOR TELECOMMUNICATIONS
ROOMS ON SIZE AND LAYOUT.
13. G.C.SHALL REFER TO MECHANICAL, ELECTRICAL AND
TECHNOLOGY DRAWINGS TO COORDINATE ABOVE CEILING
WORK.
AREA NOT IN CONTRACT
GRAY AREA NOT IN
PROJECT SCOPE
1 2
TELECOMMUNICATIONS
RM.
P02
AE520
Sim
P01
TELECOMMUNICATIONS
RM.
MECHANICAL SUPPLY DIFFUSER
MECHANICAL RETURN GRILLE
MECHANICAL EXHAUST GRILLE
EXPOSED CEILING
CEILING ELEVATION A.F.F.
X'-X"
CHANGE HUNG LIGHT FIXTURE
NOTE NUMBER NOTE
EXPOSED CEILING
DEMO EXISTING CEILING FINISHES AND FIXTURES
REPLACE CEILING TILES IN AREA OF WORK
REMOVE, SALVAGE, AND REINTSTALL CEILING TILES IN AREA OF WORK
PATCH AND REPAIR EXISTING CEILING
EXPOSED CEILING. PATCH, REPAIR AND PAINT AS REQUIRED.
DEMO EXISTING CEILING FINISHES AND FIXTURES.
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
G ra p h ic S c a
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3 /2
:3
:3
P
M
BUILDING 03 FIRST FLOOR PLAN & RCP
RCO HS
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
03-AE101
5000 W. NATIONAL AVENUE MILWAUKEE, WI
1/4" = 1'-0"
BUILDING 03 FIRST FLOOR PLAN
Note Number Note
1 PATCH, CLEAN, AND REPAIR WALLS AFTER DEMO. TYPICAL IN ALL AREAS.
PAINT NEW WALLS TO MATCH EXISTING WALLS. IF EXISTING WALLS ARE
DAMAGED, CONTRACTOR TO REPAINT EXISTING WALLS.
CLEAN, PATCH, REPAIR, AND SEAL ALL CONCRETE FLOORS AFTER DEMO. LEVEL
FLOOR AS REQUIRED.
INSTALL NEW 5/8" THICK TYPE 'X' GYP. BD. ON INTERIOR SIDE AT THIS LOCATION.
CONTRACTOR TO PATCH AND REPAIR WALL TO MEET R03 WALL TYPE
CONSTRUCTION. SEAL ALL PENETRATIONS AS NEEDED.
PATCH, CLEAN, AND REPAIR FLOORS TO MATCH EXISTING WHERE NEEDED AFTER
DEMO. LEVEL FLOORS WHERE NEEDED. TYPICAL IN ALL AREAS.
EXISTING WINDOW TO REMAIN. WINDOW TO BE WATERPROOFED WITH SEALANT
AND TINTED. NEW WALL TO BE CONSTRUCTED ON THE INTERIOR OF THE EXISTING
WINDOW. PROVIDE PROPER VENTILATION TO VENT ENCLOSED WINDOW.
EXISTING TELECOMMUNICATIONS ROOM TO REMAIN. REFERENCE TECHNOLOGY
DRAWINGS FOR FURTHER INFORMATION.
EXISTING TELECOMMUNICATIONS ROOM TO TURN INTO CABLE RISER ROOM.
REFERENCE TECHNOLOGY SHEETS FOR MORE DETAILS.
9 EXPOSED CEILING. PATCH, REPAIR, AND PAINT AS REQUIRED.
10 EPOXY PAINTED CMU TO BE APPLIED ON EXTERIOR OF CMU
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1/4" = 1'-0"
BUIDLING 3 FIRST FLOOR RCP
RESERVED FOR EHRM PROJECT
DEMO NOTES
AREA NOT IN CONTRACT
EXISTING WALL AND ASSOCIATED COMPONENTS
SHALL BE REMOVED - REFER TO DEMOLITION
KEYNOTES FOR ADDITIONAL DETAILS AT SPECIFIC
CONDITIONS.
EXISTING DOOR, FRAME, HARDWARE AND
ASSOCIATED COMPONENTS SHALL BE REMOVED
-REFER TO DEMOLITION KEYNOTES FOR
ADDITIONAL DETAILS AT SPECIFIC CONDITIONS
EXISTING WALL SHALL REMAIN
EXISTING DOOR, FRAME AND HARDWARE
SHALL REMAIN
GRAY AREA NOT IN
PROJECT SCOPE
CONFERENCE
OFFICE
11 11
AREA OF WORK
1. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT OF ANY DIMENSIONAL
DISCREPANCIES DISCOVERED DURING CONSTRUCTION.
2. REFER TO MECHANICAL, PLUMBING, ELECTRICAL, AND TECHNOLOGY DRAWINGS
FOR MORE INFORMATION.
3. ALL ABANDONED LINES, PIPES, CONDUITS DISCOVERED AFTER CEILING
REMOVAL ARE ALSO TO BE REMOVED.
4. REFER TO ELECTRICAL DRAWINGS FOR LOCATION OF EMERGENCY LIGHTING.
5. CENTER CEILING AND LIGHTS IN ALL SPACES WHERE POSSIBLE, U.N.O.
6. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF UNDER-CABINET LIGHT
FIXTURES.
7. GYP. BD. SOFFITS ABOVE UPPER CABINETS SHALL EXTEND TO TOP OF CABINET
(7'-0" U.N.O.).
8. THIS SHEET IS FOR LAYOUT ONLY. SEE ELECTRICAL AND MECHANICAL
DRAWINGS FOR EXACT FIXTURE QUANTITY. ALL SWITCHES, OUTLETS, LIGHTS,
DIFFUSERS, ETC. MUST BE LOCATED PER ARCHITECTURAL DRAWINGS WHERE
APPLICABLE.
9. PROVIDE ACCESS PANELS IN GYPSUM CEILINGS WHERE REQUIRED TO ACCESS
ABOVE CEILING EQUIPMENT. (SEE SPECS)
10. ALL CEILINGS SHALL BE 9'-0" AFF U.N.O.
11. REFER TO FINISH DRAWINGS FOR CEILING GRID AND PANEL TYPE AND SIZE.
12. BOTTOM OF GYP. BD. BULKHEADS SHALL BE 8'-6" AFF U.N.O.
13. ALL PARTITION WALLS SHALL EXTEND TO UNDERSIDE OF DECK ABOVE U.N.O.
14. ALL FRAMING MEMBERS SHALL BE ADEQUATELY SIZED FOR THE REQUIRED
SPAN/SPACING. REFER TO SPECS FOR ADDITIONAL GYP. BD. INFORMATION. GYP.
BD. CEILINGS SHALL BE INSTALLED PER ASTM C840.
15. VERIFY IN FIELD ALL DIMENSIONS PRIOR TO PROCEEDING WITH ANY WORK AND
AFTER DEMOLITION SITE SURVEY THE SPACE DIMENSIONS, EQUIPMENT, DOOR,
MECHANICALS, ELECTRICAL, FIRE PROTECTION, ETC. AND COORDINATE WITH NEW
CONSTRUCTION. BRING ANY DISCREPANCIES AND OR QUESTION TO THE AE AND
COR PRIOR TO PROCEEDING FORWARD WITH ANY NEW CONSTRUCTION. USE THIS
DOCUMENT FOR SUBCONTRACTOR REVIEW AS ACCEPTANCE OF CONDITIONS.
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3 /2
:3
:4
P
M
BUILDING 04 SECOND FLOOR DEMO PLAN
RCO HS
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
04-AD101
5000 W. NATIONAL AVENUE MILWAUKEE, WI
Note Number Note
1 REMOVE AND SALVAGE FURNITURE, EQUIPMENT AND FIXTURES SECURED TO THE
WALL. STORE AT VA DESIGNATED LOCATION.
2 REMOVE FLOOR FINISH, FLOOR COVERING, WALL BASE, WALL COVERING, WALLS
AND ASSOCIATED COMPONENTS. CLEAN AND PATCH WALLS AND FLOORS AS
REQUIRED TO RECEIVE NEW FINISHES. LEVEL FLOOR AS REQUIRED FOR NEW
FINISH.
3 REMOVE ALL COVERINGS FROM EXISTING WALL PARTITION ASSEMBLIES ON THE
DEMO SIDE ONLY. DO NOT REMOVE FRAMING, SOUND BATTS, GYP.BD ON
NON-DEMO SIDE. REFER TO FINISH SCHEDULE FOR NEW FINISHES. REFER TO THE
FLOOR PLAN FOR NEW WORK.
4 REMOVE EXISTING DOOR, DOOR FRAME, DOOR HARDWARE AND DISPOSE
MATERIALS. PREPARE WALL TO BE INFILLED.
6 EXISTING TELECOMMUNICATIONS ROOM TO REMAIN. REFERENCE TECHNOLOGY
SHEETS FOR MORE INFORMATION.
7 DEMO EXISTING CASEWORK.
8 REMOVE EXISTING TELCOMMUNICATIONS ROOM EQUIPMENT AND STORE IN VA
DESIGNATED AREA.
9 REMOVE EXISTING SINK. REFERENCE PLUMBING DEMOLITION SHEET FOR
ADDITIONAL INFORMATION.
10 DEMO EXISTING SOFFIT.
11 EXISTING WINDOW TO REMAIN. SEAL WINDOW AND TINT FROM INTERIOR OF
WINDOW (TYP.). DEMO EXISTING TRIM AND PREPARE WALL TO BE INFILLED TO
MATCH EXISTING.
12 DEMO EXISTING CEILING FINISHES AND FIXTURES.
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1/4" = 1'-0"
BUILDING 04 SECOND FLOOR DEMO PLAN
NTS
KEY PLAN - BLDG 4
RCP KEYNOTES
RCP LEGEND
DEMO NOTES
CONFERENCE
OFFICE
MECHANICAL SUPPLY DIFFUSER
MECHANICAL RETURN GRILLE
MECHANICAL EXHAUST GRILLE
EXPOSED CEILING
CEILING ELEVATION A.F.F.
X'-X"
CHANGE HUNG LIGHT FIXTURE
AREA OF WORK
1. DO NOT SCALE DRAWINGS. NOTIFY ARCHITECT OF ANY DIMENSIONAL
DISCREPANCIES DISCOVERED DURING CONSTRUCTION.
2. REFER TO MECHANICAL, PLUMBING, ELECTRICAL, AND TECHNOLOGY DRAWINGS
FOR MORE INFORMATION.
3. ALL ABANDONED LINES, PIPES, CONDUITS DISCOVERED AFTER CEILING
REMOVAL ARE ALSO TO BE REMOVED.
4. REFER TO ELECTRICAL DRAWINGS FOR LOCATION OF EMERGENCY LIGHTING.
5. CENTER CEILING AND LIGHTS IN ALL SPACES WHERE POSSIBLE, U.N.O.
6. REFER TO ELECTRICAL DRAWINGS FOR LOCATIONS OF UNDER-CABINET LIGHT
FIXTURES.
7. GYP. BD. SOFFITS ABOVE UPPER CABINETS SHALL EXTEND TO TOP OF CABINET
(7'-0" U.N.O.).
8. THIS SHEET IS FOR LAYOUT ONLY. SEE ELECTRICAL AND MECHANICAL
DRAWINGS FOR EXACT FIXTURE QUANTITY. ALL SWITCHES, OUTLETS, LIGHTS,
DIFFUSERS, ETC. MUST BE LOCATED PER ARCHITECTURAL DRAWINGS WHERE
APPLICABLE.
9. PROVIDE ACCESS PANELS IN GYPSUM CEILINGS WHERE REQUIRED TO ACCESS
ABOVE CEILING EQUIPMENT. (SEE SPECS)
10. ALL CEILINGS SHALL BE 9'-0" AFF U.N.O.
11. REFER TO FINISH DRAWINGS FOR CEILING GRID AND PANEL TYPE AND SIZE.
12. BOTTOM OF GYP. BD. BULKHEADS SHALL BE 8'-6" AFF U.N.O.
13. ALL PARTITION WALLS SHALL EXTEND TO UNDERSIDE OF DECK ABOVE U.N.O.
14. ALL FRAMING MEMBERS SHALL BE ADEQUATELY SIZED FOR THE REQUIRED
SPAN/SPACING. REFER TO SPECS FOR ADDITIONAL GYP. BD. INFORMATION. GYP.
BD. CEILINGS SHALL BE INSTALLED PER ASTM C840.
15. VERIFY IN FIELD ALL DIMENSIONS PRIOR TO PROCEEDING WITH ANY WORK AND
AFTER DEMOLITION SITE SURVEY THE SPACE DIMENSIONS, EQUIPMENT, DOOR,
MECHANICALS, ELECTRICAL, FIRE PROTECTION, ETC. AND COORDINATE WITH NEW
CONSTRUCTION. BRING ANY DISCREPANCIES AND OR QUESTION TO THE AE AND
COR PRIOR TO PROCEEDING FORWARD WITH ANY NEW CONSTRUCTION. USE THIS
DOCUMENT FOR SUBCONTRACTOR REVIEW AS ACCEPTANCE OF CONDITIONS.
NOTE NUMBER NOTE
EXPOSED CEILING
DEMO EXISTING CEILING FINISHES AND FIXTURES
REPLACE CEILING TILES IN AREA OF WORK
REMOVE, SALVAGE, AND REINTSTALL CEILING TILES IN AREA OF WORK
PATCH AND REPAIR EXISTING CEILING
EXPOSED CEILING. PATCH, REPAIR AND PAINT AS REQUIRED.
DEMO EXISTING CEILING FINISHES AND FIXTURES.
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3 /2
:3
:4
P
M
BUILDING 04 SECOND FLOOR RCP DEMO PLAN
RCO HS
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
04-AD102
5000 W. NATIONAL AVENUE MILWAUKEE, WI
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1/4" = 1'-0"
BUILDING 04 SECOND FLOOR RCP DEMO PLAN
NTS
GENERAL NOTESKEYNOTES
RESERVED FOR EHRM PROJECT
1. G.C. SHALL VERIFY DIMENSIONS OF OWNER FURNISHED
EQUIPMENT AND COORDINATE INSTALLATION WITH ALL
TRADES WHERE REQUIRED.
2. REFER TO FINISH SHEETS FOR PARTITION PROTECTION
INFORMATION INCLUDING BUT NOT LIMITED TO ALL CORNER
GUARD TYPES AND LOCATIONS.
3. G.C. SHALL INSTALL IN-WALL METAL BACKING FOR ALL
PARTITION-MOUNTED EQUIPMENT, ACCESSORIES,
PARTITION STOPS, ETC.
4. G.C. SHALL INSTALL FIRE-RETARDANT WOOD BLOCKING
WITHIN WALLS BASED ON CASEWORK ELEVATIONS AND ALL
INTERIOR PARTITION ELEVATIONS.
5. ALL INTERIOR WALLS SHALL RECEIVE 5/8" TYPE 'X' GYPSUM
BOARD.
6. G.C. SHALL PROVIDE UL APPROVED FIRE-RESISTIVE
PENETRATION SYSTEMS WHERE PLUMBING IS LOCATED IN A
FIRE-RATED PARTITION ASSEMBLY.
7. ALL EXTERIOR WINDOWS OPEN TO THE INTERIOR SHALL
RECEIVE A SOLID SURFACE WINDOW STOOL. REFER TO
FINISH DRAWINGS FOR MATERIAL SELECTION.
8. EXTEND ALL RATED WALLS TO DECK PER UL ASSEMBLY
REQUIREMENTS. REFER TO PARTITION TYPES SHEET FOR
INTERIOR PARTITION TYPES & DETAILS. G.C. SHALL VERIFY
ALL WALLS GO TO STRUCTURE ABOVE.
9. REFER TO PARTITION TYPES SHEET FOR RATED PARTITION
PRIORITY AND RATED PARTITION INTERSECTIONS.
10. ALL RATED WALLS SHOWN ON PLANS TO BE ASSUMED AS
NEW RATED WALLS UNTIL VERIFIED ON SITE.
11. THE ABESTOS REMOVAL REQUIREMENTS, SHOWN FOR
REFENCE ONLY, WERE PERFORMED UNDER A SEPARATE
CONTRACT WITH ALL RELATED DOCUMENTS INCLUDED IN
THE SPECIFICATIONS.
12. G.C.SHALL PATCH AND REPAIR CEILING TO MATCH EXISTING
HEIGHT, MATERIAL AND PATTERN IN CORRIDORS. REFER TO
MECHANICAL, ELECTRICAL AND TECHNOLOGY DRAWINGS
FOR CONNECTIONS FROM INTERIOR TELECOMMUNICATIONS
ROOMS ON SIZE AND LAYOUT.
13. G.C.SHALL REFER TO MECHANICAL, ELECTRICAL AND
TECHNOLOGY DRAWINGS TO COORDINATE ABOVE CEILING
WORK.
AREA NOT IN CONTRACT
/2
TELECOMMUNICATIONS
RM
CONFERENCE RM
GRAY AREA NOT IN
PROJECT SCOPE
8' - 0" 16' - 1 1/4"
P01
P02
AREA OF WORK
PLAN NORTH
TRUE NORTH
NORTH
G ra p h ic S ca le
/2
0"
G ra p h ic S ca le
/3 2"
0"
' G ra p h ic S ca le
/1 6"
0"
' G ra p h ic
S ca le
/8
0"
G ra p h ic S ca le
/4
0"
' G ra p h ic
S ca le
/2
0"
G ra p h ic S ca le
/4
0"
G ra p h ic S ca le
0"
Romanyk Consulting Focusing on what matters
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
F
U.S. Department of Veterans Affairs
E
D
C
B
A
F
E
D
C
B
A
910 7 6 5 4 3 2 1
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
8910 7 6 5 4 3 2 1
Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093
Sprinklered
Office of Construction and Facilities Management
FULLY SPRINKLERED
G ra p h ic S c a
A u to d e s k D o c s /O
C F
M E a s t
M ilw a u k e e E
H R
M
R
C o n s o lid a te d M o d e l (R rv t
/3 /2
:3
:4
P
M
BUILDING 04 SECOND FLOOR PLAN
RCO HS
FINAL BID DOCUMENTS 695-21-700
EHRM INFRASTRUCTURE
UPGRADES – MILWAUKEE, WI
SEPTEMBER 5, 2025
04-AE101
5000 W. NATIONAL AVENUE MILWAUKEE, WI
Note Number Note
1 PATCH, CLEAN, AND REPAIR WALLS AFTER DEMO. TYPICAL IN ALL AREAS.
PAINT NEW WALLS TO MATCH EXISTING WALLS. IF EXISTING WALLS ARE
DAMAGED, CONTRACTOR TO REPAINT EXISTING WALLS.
CLEAN, PATCH, REPAIR, AND SEAL ALL CONCRETE FLOORS AFTER DEMO. LEVEL
FLOOR AS REQUIRED.
INSTALL NEW 5/8" THICK TYPE 'X' GYP. BD. ON INTERIOR SIDE AT THIS LOCATION.
CONTRACTOR TO PATCH AND REPAIR WALL TO MEET R03 WALL TYPE
CONSTRUCTION. SEAL ALL PENETRATIONS AS NEEDED.
PATCH, CLEAN, AND REPAIR FLOORS TO MATCH EXISTING WHERE NEEDED AFTER
DEMO. LEVEL FLOORS WHERE NEEDED. TYPICAL IN ALL AREAS.
EXISTING WINDOW TO REMAIN. WINDOW TO BE WATERPROOFED WITH SEALANT
AND TINTED. NEW WALL TO BE CONSTRUCTED ON THE INTERIOR OF THE EXISTING
WINDOW. PROVIDE PROPER VENTILATION TO VENT ENCLOSED WINDOW.
EXISTING TELECOMMUNICATIONS ROOM TO REMAIN. REFERENCE TECHNOLOGY
DRAWINGS FOR FURTHER INFORMATION.
EXISTING TELECOMMUNICATIONS ROOM TO TURN INTO CABLE RISER ROOM.
REFERENCE TECHNOLOGY SHEETS FOR MORE DETAILS.
9 EXPOSED CEILING. PATCH, REPAIR, AND PAINT AS REQUIRED.
10 EPOXY PAINTED CMU TO BE APPLIED ON EXTERIOR OF CMU
15 SUNNEN DR SUITE 104
SAINT LOUIS, MO 63143
314.645.1132 FAX: 314.645.1173
www.imegcorp.com # 17002665.02
1/4" = 1'-0"
BUILDING 04 SECOND FLOOR PLAN
NORTH
NTS
RCP KEYNOTES
GENERAL NOTES#
MECHANICAL SUPPLY DIFFUSER
MECHANICAL RETURN GRILLE
MECHANICAL EXHAUST GRILLE
EXPOSED CEILING
CEILING ELEVATION A.F.F.
X'-X"
CHANGE HUNG LIGHT FIXTURE
TELECOMMUNICATIONS
RM
CONFERENCE RM
GRAY AREA NOT IN
PROJECT SCOPE
AREA OF WORK
1. G.C. SHALL VERIFY DIMENSIONS OF OWNER FURNISHED
EQUIPMENT AND COORDINATE INSTALLATION WITH ALL
TRADES WHERE REQUIRED.
2. REFER TO FINISH SHEETS FOR PARTITION PROTECTION
INFORMATION INCLUDING BUT NOT LIMITED TO ALL CORNER
GUARD TYPES AND LOCATIONS.
3. G.C. SHALL INSTALL IN-WALL METAL BACKING FOR ALL
PARTITION-MOUNTED EQUIPMENT,…