This solicitation is for the construction of two 4 million liter (25,000 barrel) cut-and-cover bulk fuel storage tanks at Royal Australian Air Force Base Tindal in Northern Territory, Australia. The project includes support infrastructure such as two pump houses, a liquid fuel truck fill stand, fuel stand unloading facility, and a filter building. Additional site work includes utilities, automatic tank gauging systems, site improvements, pavements, and communications infrastructure. A backup generator and all other work required to provide a complete and usable fuel storage facility is included. There are also three pre-priced options for different pavement types, a fuel transfer line crossover pit, and a hydrant-hose checkout station. The solicitation is issued by the United States Department of the Navy, Naval Facilities Engineering Command.

View the file

Other files

Show all 32

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FY20 MCON Project PAF180200 APR - Jet Fuel Storage Tanks 1606003 Royal Australian Air Force (RAAF) Base Tindal, Australia

SECTION 28 31 63.00 20

ANALOG/ADDRESSABLE INTERIOR FIRE ALARM SYSTEM

10/07

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AUSTRALIAN GOVERNMENT DEPARTMENT OF DEFENCE (AUS DOD)

MFPE Australian Government Department of Defence, Manual of Fire Protection Engineering (MFPE) - Latest Edition

ACTIVFIRE Register of Fire Protection Equipment Latest Edition

AS1603.1 Automatic Fire Detection and Alarm Systems Heat Detectors

AS1603.11 Automatic Fire Detection and Alarm Systems Visual Warning Devices

AS1670.1 Fire Detection, Warning, Control and Intercom Systems - Systems Design,Installation, and Commissioning

AS3786 Smoke Alarms Using Scattered Light, Transmitted Light or Ionization

AS4428.5 Fire Detection, Warning, Control and Intercom Systems - Control and Indicating Equipment Power Supply Units

AS7240.4 Fire Detection and Alarm Systems Power Supply Equipment

AS7240.5 Fire Detection and Alarm Systems Point Type Heat Detectors

AS7240.7 Fire Detection and Alarm Systems Point Type Smoke Detectors Using Scattered Light, Transmitted Light or Ionization

AS/NZS3000 Electrical Installations (known as the Australian/New Zealand Wiring Rules)

AS/NZS60079.14 Explosive Atmospheres Design Selection, Erection and Initial Inspection

SECTION 28 31 63.00 20 Page 1

AMD 008

1.2 RELATED REQUIREMENTS

Section 26 00 00.00 20 BASIC ELECTRICAL MATERIALS AND METHODS, applies to this section, with the additions and modifications specified herein.

1.3 DESCRIPTION OF WORK

1.3.1 Scope

This work includes designing and providing a new, complete, analog/addressable fire alarm system as described herein and on the contract drawings for the RAAF Base Tindal, PAF180200 APR - Jet Fuel Storage Tanks project as indicated on the drawings. The system shall include wiring, raceways, pull boxes, terminal cabinets, outlet and mounting boxes, control equipment, alarm, and supervisory signal initiating devices, alarm notification appliances, supervising station fire alarm system transmitter, and other accessories and miscellaneous items required for a complete operating system even though each item is not specifically mentioned or described. Provide system complete and ready for operation.

Equipment, materials, installation, workmanship, inspection, and testing shall be in strict accordance with the required and advisory provisions of MFPE and except as modified herein. The system layout on the drawings show the intent of coverage and are shown in suggested locations. Final quantity, layout, and coordination is the responsibility of the Contractor.

All fire alarm initiating devices, notification appliances, and conduit located in the Pump Vaults, Filter Building and Gantry shall be explosion proof.

1.4 SUBMITTALS

Government approval is required for submittals with a "G" designation;

submittals not having a "G" designation are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00

SUBMITTAL PROCEDURES:

Provide six complete sets of submittals. Partial submittals will not be acceptable and will be returned without review. The NAVFAC Pacific Fire Protection Engineer delegates the authority to the Accredited Building Surveyor for review and approval of submittals required by this section.

The Accredited Building Surveyor shall base the review and approval on plans and specifications. Submit to the NAVFAC Pacific Fire Protection Engineer and building certifier two sets of all approved submittals, including but not limited to shop drawings, catalog cuts, supporting calculations, etc. immediately after approval but no later than 5 working days prior to final inspection.

SD-02 Shop Drawings

Provide point-to-point wiring diagrams showing the points of connection and terminals used for electrical field connections in the system, including interconnections between the equipment or systems which are supervised or controlled by the system.

Diagrams shall show connections from field devices to the FDCIE and remote fire alarm control units, initiating circuits, switches, relays and terminals.

Provide plan view drawing showing device locations, terminal cabinet locations, junction boxes, other related equipment, conduit routing, wire counts, circuit identification in each

SECTION 28 31 63.00 20 Page 2 conduit, and circuit layouts for all floors.

Provide a complete description of the system operation in matrix format on the drawings.

Provide a complete list of device addresses and corresponding messages.

Provide detailed drawings of the graphic annunciator.

Include annotated catalog data, in table format on the drawings, showing manufacturer's name, model, voltage, and catalog numbers for equipment and components.

Provide complete riser diagrams indicating the wiring sequence of devices and their connections to the control equipment. Include a color code schedule for the wiring. Include floor plans showing the locations of devices and equipment.

Battery power calculations

Submit shop drawings not smaller than 600 by 900 mm. As a minimum, the shop drawing submittal shall include the items listed above.

SD-03 Product Data

Fire Detection Control and Indicating Equipment (FDCIE) Terminal cabinets/assemblies Manual stations Transmitters (including housing) Batteries Battery chargers Smoke sensors Thermal sensors Wiring and cable Notification appliances Addressable interface devices Amplifiers Tone generators Digitalized voice generators Optical Flame Detection; G Smoke sensor testing procedures Fire Alarm Interface Panels

Submit data on proposed equipment, including, but not limited to the items listed above. Include ACTIVFIRE listing cards for equipment provided.

SD-06 Test Reports

Furnish preliminary test results to the Contracting Officer.

Include the control panel and initiating and indicating devices, a unique identifier for each device with an indication of test results, and signature of the factory-trained technician of the control panel manufacturer and equipment installer. With reports on preliminary tests, include printer information.

SD-07 Certificates

SECTION 28 31 63.00 20 Page 3

Qualifications of installer

SD-10 Operation and Maintenance Data

INTERIOR FIRE ALARM SYSTEM, Data Package 5; G

Submit in accordance with Section 01 78 23 OPERATION AND

MAINTENANCE DATA.

Record drawing software

SD-11 Closeout Submittals

Prepare and submit to the Contracting Officer six sets of detailed as-built drawings. The drawings shall include complete wiring diagrams showing connections between devices and equipment, both factory and field wired. Include a riser diagram and drawings showing the as-built location of devices and equipment. The drawings shall show the system as installed, including deviations from both the project drawings and the approved shop drawings.

The drawings shall be prepared on uniform sized mylar sheets not less than 760 by 1065 mm with 200 by 100 mm title block similar to contract drawings. These drawings shall be submitted within 2 weeks after the final acceptance test of the system. At least one set of as-built (marked-up) drawings shall be provided at the time of, or prior to the final acceptance test.

Submit the installer’s training history for the employees involved with this contract.

1.5 ADDITIONAL SUBMITTAL REQUIREMENTS

1.5.1 Battery Power Calculations

Verify that battery capacity exceeds supervisory and alarm power requirements.

a. Provide complete battery calculations for both the alarm and supervisory power requirements. Ampere hour requirements for each system component shall be submitted with the calculations.

b. Provide data on each circuit to indicate that there is at least 25 percent spare capacity for notification appliances, 25 percent spare capacity for initiating devices. Annotate data for each circuit on the drawings.

c. Provide data to indicate that the amplifiers have sufficient capacity to simultaneously drive fire alarm speakers at their 1/2 watt tap plus 50 percent spare capacity. Annotate data for each circuit on the drawings.

d. Provide a detailed description of the final acceptance testing procedures (including equipment necessary for testing smoke detectors using real smoke).

1.5.2 Qualifications of Installer

Design shall be in accordance with the MFPE. Installer shall be approved

SECTION 28 31 63.00 20 Page 4 and licensed by the NTFRS and Northern Territory Electrical Workers and Contractors Licensing Board. Installer shall have an office, which has been in existence for at least 3 years. Installation shall be accomplished by an electrical contractor with a minimum of 5 years' experience in the installation of fire alarm systems. The Contracting Officer may reject any proposed installer who cannot show evidence of such qualifications. The services of a technician provided by the control equipment manufacturer shall be provided to supervise installation, adjustments, and tests of the system. The Contractor shall furnish evidence that the fire alarm equipment supplier has an experienced and effective service organization which carries a stock of repair parts for the system to be furnished. The Contractor shall guarantee labor, materials, and equipment provided under this contract against defects for a period of one year after the date of final acceptance of this work by the Contracting Officer and the receipt of as-built drawings and schematics of all equipment. Prior to installation, submit data for approval by the Accredited Building Surveyor, showing that the Contractor has successfully installed addressable, analog intelligent interior fire alarm systems of the same type as specified herein, or that the Contractor has a firm contractual agreement with a subcontractor having such required experience. Include the names and locations of at least three installations where the Contractor, or the subcontractor referred to above, has installed such systems. Indicate the type and design of each system and certify that each system has performed satisfactorily in the manner intended for a period of not less than 18 months. Submit names and phone numbers of points of contact at each site.

1.5.3 Record Drawing Software

Furnish one set of CD or DVD discs containing software back-up and CAD based drawings in latest version of AutoCAD and DXF format of as-built drawings and schematics.

1.6 QUALITY ASSURANCE

Equipment and devices shall be compatible and operable with existing station fire alarm system and shall not impair reliability or operational functions of existing supervising station fire alarm system.

1.6.1 Regulatory Requirements

Devices and equipment for fire alarm service shall be listed by ACTIVFIRE.

1.6.1.1 Requirements for Fire Protection Service

Equipment and material shall have been tested by and listed by ACTIVFIRE.

Where the terms "listed" or "approved" appear in this specification, they shall mean listed in MFPE and ACTIVFIRE. The omission of these terms under the description of any item of equipment described shall not be construed as waiving this requirement.

1.6.1.2 Testing Services or Laboratories

Fire alarm and fire detection equipment shall be constructed in accordance with ACTIVEFIRE.

1.6.2 Standard Products

Provide materials, equipment, and devices that have been tested by ACTIVEFIRE and listed or approved for fire protection service when so

SECTION 28 31 63.00 20 Page 5 required by the MFPE or this specification. Select material from one manufacturer, where possible, and not a combination of manufacturers, for any particular classification of materials.

1.6.3 Modification of References

a. In MFPE referred to herein, consider advisory provisions to be mandatory, as though the word "shall" had been substituted for "should" wherever it appears; interpret reference to "authority having jurisdiction" to mean the Accredited Building Surveyor.

b. The recommended practices stated in the manufacturer's literature or documentation shall be considered as mandatory requirements.

1.7 DELIVERY, STORAGE, AND HANDLING

Protect equipment delivered and placed in storage from the weather, humidity, and temperature variation, dirt and dust, and other contaminants.

1.8 SPARE PARTS AND TOOLS

1.8.1 Interchangeable Parts

Spare parts furnished shall be directly interchangeable with the corresponding components of the installed system. Spare parts shall be suitably packaged and identified by nameplate, tagging, or stamping. Spare parts shall be delivered to the Contracting Officer at the time of the final acceptance testing.

1.8.2 Spare Parts

Furnish the following spare parts and accessories:

a. 4 audiovisual devices of each type installed

b. 4 fuses for each fused circuit

c. 1 manual stations

d. 2 smoke sensors and base of each type installed

e. 2 heat sensors and base of each type installed

1.8.3 Parts List

Furnish a list, in duplicate, of all other parts and accessories which the manufacturer of the system recommends to be stocked for maintenance.

1.9 KEYS

Keys and locks for equipment shall be identical. Provide not less than six keys of each type required. Keys shall be the manufacturer's standard keys.

SECTION 28 31 63.00 20 Page 6

PART 2 PRODUCTS

2.1 INTERIOR FIRE ALARM SYSTEM DESIGN

2.1.1 Definitions

Wherever mentioned in this specification or on the drawings, the equipment, devices, and functions shall be defined as follows:

a. Analog/Addressable System: A system in which multiple signals are transmitted via the same conduction path to a remote fire alarm control unit and fire alarm control panel, decoded and separated so that each signal will initiate the specified response.

b. Hard Wired System: A system in which alarm and supervisory initiating devices are directly connected, through individual dedicated conductors, to a central control panel without the use of analog/addressable circuits or devices.

c. Interface Device: An addressable device which interconnects hard wired systems or devices to an analog/addressable system.

d. Fire Alarm Control Unit (also known as Sub Indicator Panel, SIP): A control panel, remote from the fire alarm control panel, that receives inputs from automatic and manual fire alarm devices; may supply power to detection devices and interface devices; may provide transfer of power to the notification appliances; may provide transfer of condition to relays or devices connected to the control unit; and reports to and receives signals from the fire alarm control panel.

e. Fire Alarm Detection Control and Indicating Equipment (FDCIE, also knwon as Fire Indicator Panel, FIP): A master control panel having the features of a fire alarm control unit and to which fire alarm control units are interconnected. The panel has central processing, memory, input and output terminals.

f. Terminal Cabinet: A steel cabinet with locking, hinge-mounted door in which terminal strips are securely mounted.

2.1.2 System Operation

The system shall be a complete, supervised, noncoded, analog/addressable fire alarm system conforming to the MFPE and AS1670.1. The system shall operate in the alarm mode upon actuation of any alarm initiating device.

The system shall remain in the alarm mode until initiating device(s) are reset and the fire alarm control panel is manually reset and restored to normal. All devices and junction boxes shall be IECEx or ANZEx scheme certified and installed in compliance with AS/NZS60079.14. The system shall provide the following functions and operating features:

a. The FDCIE, if used, shall provide power, annunciation, supervision, and control for the system.

b. Provide Class "B" initiating device circuits.

c. Provide Class "B" signaling line circuits for each floor.

d. Provide Class "B" notification appliance circuits. The visual alarm notification appliances shall have the flash rates synchronized.

SECTION 28 31 63.00 20 Page 7

e. Provide electrical supervision of the primary power (AC) supply, presence of the battery, battery voltage, and placement of system modules within the control panel.

f. Provide an audible and visual trouble signal to activate upon a single break or open condition, or ground fault. The trouble signal shall also operate upon loss of primary power (AC) supply, absence of a battery supply, low battery voltage, or removal of alarm or supervisory panel modules. Provide a trouble alarm silence feature which shall silence the audible trouble signal, without affecting the visual indicator. After the system returns to normal operating conditions, the trouble signal shall again sound until the trouble is acknowledged. A smoke sensor in the process of being verified for the actual presence of smoke shall not initiate a trouble condition.

g. Provide a notification appliance silencing switch which, when activated, will silence the audible signal appliance, but will not affect the visual alarm indicator, the liquid crystal display, or the automatic notification of the fire department . This switch shall be overridden upon activation of a subsequent alarm.

h. Provide alarm verification capability for smoke sensors. Alarm verification shall initially be set for 30 seconds.

i. Provide program capability via switches via programming in a locked portion of the FDCIE to bypass the automatic notification appliance circuits. Operation of this programming shall indicate this action on the FDCIE display and printer output.

j. Alarm, supervisory, and/or trouble signals shall be automatically transmitted to the fire department.

k. Alarm functions shall override trouble or supervisory functions.

Supervisory functions shall override trouble functions.

l. The system shall be capable of being programmed from the panel’s keyboard. Programmed information shall be stored in non-volatile memory.

m. The system shall be capable of operating, supervising, and/or monitoring both addressable and non-addressable alarm and supervisory devices.

n. There shall be no limit, other than maximum system capacity, as to the number of addressable devices which may be in alarm simultaneously.

o. An alarm signal shall automatically initiate the following functions:

(1) Transmission of an alarm signal to the fire department.

(2) Visual indication of the device operated on the Fire Alarm Detection Control and Indicating Equipment (FDCIE)

p. A supervisory signal shall automatically initiate the following functions:

(1) Visual indication of the device operated on the FDCIE.

SECTION 28 31 63.00 20 Page 8

(2) Transmission of a supervisory signal to the fire department.

q. A trouble condition shall automatically initiate the following functions:

(1) Visual indication of the system trouble on the FDCIE.

(2) Transmission of a trouble signal to the fire department.

r. The maximum permissible elapsed time between the actuation of an initiating device and its indication at the FDCIE shall be 10 seconds.

s. The maximum elapsed time between the occurrence of the trouble condition and its indication at the FDCIE shall not exceed 100 seconds.

2.1.3 Overvoltage and Surge Protection

a. Signaling Line Circuit Surge Protection: For systems having circuits located outdoors, communications equipment shall be protected against surges induced on any signaling line circuit and shall comply with the applicable requirements of the MFPE and AS/NZS3000. Cables and conductors, which serve as communications links, shall have surge protection circuits installed at each end that meet the following waveforms:

(1) An 8 microsecond by 20 microsecond waveform with a surge rating of 100 kA per phase and a maximum working voltage between 275 V a.c. to 320 V a.c. Protection shall be provided at the equipment.

Fuses shall not be used for surge protection.

b. Sensor Wiring Surge Protection: Digital and analog inputs and outputs shall be protected against surges induced by sensor wiring installed outdoors and as shown. The inputs and outputs shall be tested with the following waveforms:

(1) An 8 by 20 microsecond waveform with a surge rating of 100 kA per phase and a maximum working voltage between 275 V a.c. to 320 V a.c.

Fuses shall not be used for surge protection.

2.1.4 Addressable Interface Devices

The addressable interface (AI) device shall provide an addressable input interface to the FDCIE for monitoring normally open or normally closed contact devices such as waterflow switches, valve supervisory switches, fire pump monitoring, independent smoke detection systems, relays for output function actuation, etc.

2.1.5 Smoke Sensors

2.1.5.1 Photoelectric Smoke Sensors

Provide addressable photoelectric smoke sensors as follows:

a. Provide analog/addressable photoelectric smoke sensors utilizing the photoelectric light scattering principle for operation in accordance with ACTIVFIRE and shall comply with AS3786 or AS7240.7. Smoke sensors shall be listed for use with the fire alarm control panel.

b. Provide self-restoring type sensors which do not require any

SECTION 28 31 63.00 20 Page 9 readjustment after actuation at the FDCIE to restore them to normal operation. Sensors shall be ACTIVFIRE listed as smoke-automatic fire sensors.

c. Components shall be rust and corrosion resistant. Vibration shall have no effect on the sensor's operation. Protect the detection chamber with a fine mesh metallic screen which prevents the entrance of insects or airborne materials. The screen shall not inhibit the movement of smoke particles into the chamber.

d. Provide twist lock bases for the sensors. The sensors shall maintain contact with their bases without the use of springs. Provide companion mounting base with screw terminals for each conductor. Terminate field wiring on the screw terminals. The sensor shall have a visual indicator to show actuation.

e. The sensor address shall identify the particular unit, its location within the system, and its sensitivity setting. Sensors shall be of the low voltage type rated for use on a 24 VDC system.

f. An operator at the control panel, having a proper access level, shall have the capability to manually access the following information for each initiating device.

(1) Primary status

(2) Device type

(3) Present average value

(4) Present sensitivity selected

(5) Sensor range (normal, dirty, etc.)

2.1.5.2 Smoke Sensor Testing

Smoke sensors shall be tested in accordance with manufacturer's recommended calibrated test method. Submit smoke sensor testing procedures for approval.

2.1.6 Thermal Sensors

a. Thermal sensors shall be combination rate-of-rise/fixed temperature sensing. Heat detectors must comply with AS1603.1 or AS7240.5. The alarm condition shall be determined by comparing sensor values with the stored values.

b. A moving average of the sensor’s heat sensing value to automatically compensate for conditions that could affect detection operations.

System shall automatically maintain a constant heat sensing sensitivity from each sensor by compensating for environmental factors.

c. Automatic self-test routines shall be performed on each sensor which will functionally check sensor sensitivity electronics and ensure the accuracy of the value being transmitted. Any sensor that fails this test shall indicate a trouble condition with the sensor location at the control panel.

d. An operator at the control panel, having the proper access level, shall have the capability to manually access the following information for each heat sensor:

(1) Primary status

SECTION 28 31 63.00 20 Page 10

(2) Device type

(3) Present average value

(4) Sensor range

e. An operator at the control panel, having the proper access level, shall have the capability to manually control the following information for each heat sensor:

(1) Alarm detection sensitivity values

(2) Enable or disable the point/device

(3) Control sensor’s relay driver output

2.1.7 Electric Power

2.1.7.1 Primary Power

Provide primary power for the FDCIE from the normal AC service to the building where shown on the electrical drawings. Power shall be 230 VAC service, transformed through a two-winding, isolation type transformer and rectified to low voltage DC for operation of circuits and devices. Make the service connection for the FDCIE where shown on the electrical drawings.

Provide appropriate equipment to protect against power surges. Provide a separate NEMA 1 "general purpose enclosure" for the circuit breaker. The circuit breaker enclosure shall be painted red, marked "FIRE ALARM SYSTEM," provided with a red and white engraved plastic sign permanently affixed to the face of the switch, and provided with a lockable handle or cover.

2.1.8 Emergency Power Supply

Provide for system operation in the event of primary power source failure.

Transfer from normal to auxiliary (secondary) power or restoration from auxiliary to normal power shall be automatic and shall not cause transmission of a false alarm.

2.1.8.1 Batteries

Provide sealed, maintenance-free, sealed lead acid batteries as the source for emergency power to the FDCIE. Batteries shall contain suspended electrolyte. The battery system shall be maintained in a fully charged condition by means of a solid state battery charger. Provide an automatic transfer switch to transfer the load to the batteries in the event of the failure of primary power.

2.1.8.2 Capacity

Provide the batteries with sufficient capacity to operate the system under quiescent (supervisory and trouble) conditions, including audible trouble signal devices for 24 hours and audible and visual signal devices under alarm conditions for an additional 30 minutes. The battery must be sized to have a minimum of 25 percent spare capacity.

2.1.8.3 Battery Chargers

Provide a solid state, fully automatic, variable charging rate battery

SECTION 28 31 63.00 20 Page 11 charger. The charger shall be capable of providing 150 percent of the connected system load and shall maintain the batteries at full charge. In the event the batteries are fully discharged, the charger shall recharge the batteries back to 80 percent of full charge within 24 hours in accordance with AS7240.4 or recharge back to support 5 hours of quiescent and 30 minutes of alarm operation in accordance with AS4428.5. Provide pilot light to indicate when batteries are manually placed on a high rate of charge as part of the unit assembly if a high rate switch is provided.

2.1.9 System Field Wiring

2.1.9.1 Wiring Within Cabinets, Enclosures, Boxes, Junction Boxes, and Fittings

Provide wiring installed in a neat and workmanlike manner and installed parallel with or at right angles to the sides and back of any box, enclosure, or cabinet. Conductors which are terminated, spliced, or otherwise interrupted in any enclosure, cabinet, mounting, or junction box shall be connected to terminal blocks. Mark each terminal in accordance with the wiring diagrams of the system. Make connections with approved pressure type terminal blocks, which are securely mounted. The use of wire nuts or similar devices shall be prohibited. Where cabinets, enclosures, or junction boxes are provided to join wires, the cabinets, enclosures or junction boxes shall be marked with "FIRE".

2.1.9.2 Terminal Cabinets

Provide a terminal cabinet at the base of any circuit riser, on each floor at each riser, and where indicated on the drawings. Terminal size shall be appropriate for the size of the wiring to be connected. Conductor terminations shall be labeled and a drawing containing conductors, their labels, their circuits, and their interconnection shall be permanently mounted in the terminal cabinet. Minimum size is 200 mm by 200 mm.

2.1.9.3 Alarm Wiring

All wiring must be stranded and outer sheath of wires must be red. Wiring in hazardous areas must conform to AS/NZS60079.14. Signaling line circuits and initiating device circuit field wiring shall be copper, 1.5 square mm size conductors at a minimum. Notification appliance circuit conductors, that contain audible alarm devices, other than speakers, shall be solid copper 2.5 square mm size conductors at a minimum. Speaker circuits shall be copper 1.5 square mm. Wire size shall be sufficient to prevent voltage drop problems. Circuits operating at 24 VDC shall not operate at less than

21.6 volts. Circuits operating at any other voltage shall not have a voltage drop exceeding 10 percent of nominal voltage. Power wiring, operating at 120 VAC minimum, shall be 4.0 square mm solid copper having similar insulation. Provide all wiring in rigid metal conduit or intermediate metal conduit. Electrical metallic tubing conduit is acceptable in dry locations not enclosed in concrete or where not subject to mechanical damage. Conceal conduit in finished areas of new construction and wherever practicable in existing construction. The use of flexible conduit not exceeding a 1830 mm length shall be permitted in initiating device circuits. Run conduit or tubing concealed unless specifically shown otherwise on the drawings. Shielded wiring shall be utilized where recommended by the manufacturer. For shielded wiring, the shield shall be grounded at only one point, which shall be in or adjacent to the FDCIE.

T-taps are not permitted. Color coding is required for circuits and shall be maintained throughout the circuit. Wiring shall be in accordance with

SECTION 28 31 63.00 20 Page 12

AS/NZS3000.

2.1.9.4 Conductor Terminations

Labeling of conductors at terminal blocks in terminal cabinets, FDCIE, and remote fire alarm control units shall be provided at each conductor connection. Each conductor or cable shall have a shrink-wrap label to provide a unique and specific designation. Each terminal cabinet, FDCIE, and fire alarm control unit shall contain a laminated drawing which indicates each conductor, its label, circuit, and terminal. The laminated drawing shall be neat, using 12 point lettering minimum size, and mounted within each cabinet, panel, or unit so that it does not interfere with the wiring or terminals. Maintain existing color code scheme where connecting to existing equipment.

2.1.10 Fire Detection Control and Indicating Equipment (FDCIE)

FDCIE must comply with AS7240.2 or AS4428.1. Provide a complete control panel fully enclosed in a lockable steel enclosure as specified herein.

Operations required for testing or for normal care and maintenance of the systems shall be performed from the front of the enclosure. If more than a single unit is required at a location to form a complete control panel, the unit enclosures shall match exactly. Each control unit shall provide power, supervision, control, and logic for the entire system, utilizing solid state, modular components, internally mounted and arranged for easy access. Each control unit shall be suitable for operation on a 230 volt, 50 hertz, normal building power supply. Provide each panel with supervisory functions for power failure, internal component placement, and operation.

Visual indication of alarm, supervisory, or trouble initiation on the fire alarm control panel shall be by liquid crystal display or similar means with a minimum of 80 characters of which at least 32 are field changeable.

2.1.10.1 Cabinet

Install control panel components in cabinets large enough to accommodate all components and also to allow ample gutter space for interconnection of panels as well as field wiring. The enclosure shall be identified by an engraved laminated phenolic resin nameplate. Lettering on the nameplate shall say "Fire Alarm Control Panel" and shall not be less than one inch high. Provide prominent rigid plastic or metal identification plates for lamps, circuits, meters, fuses, and switches. The cabinet shall be provided in a sturdy steel housing, complete with back box, hinged steel door with cylinder lock, and surface mounting provisions.

2.1.10.2 Control Modules

Provide power and control modules to perform all functions of the FDCIE.

Provide audible signals to indicate any alarm, supervisory, or trouble condition. The alarm signals shall be different from the trouble signal.

Connect circuit conductors entering or leaving the panel to screw-type terminals with each terminal marked for identification. Locate diodes and relays, if any, on screw terminals in the FDCIE. Circuits operating at 24 VDC shall not operate at less than 21.6 volts. Circuits operating at any other voltage shall not have a voltage drop exceeding 10 percent of nominal voltage.

2.1.10.3 Silencing Switches

a. Alarm Silencing Switch: Provide an alarm silencing switch at the FDCIE

SECTION 28 31 63.00 20 Page 13 which shall silence the audible signal but not affect the visual alarm indicator. This switch shall be overridden upon activation of a subsequent alarm.

b. Supervisory/Trouble Silencing Switch: Provide supervisory and trouble silencing switch which shall silence the audible trouble and supervisory signal, but not extinguish the visual indicator. This switch shall be overridden upon activation of a subsequent alarm, supervision, or trouble condition.

2.1.10.4 Non-Interfering

Power and supervise each circuit such that a signal from one device does not prevent the receipt of signals from any other device. Circuits shall be manually resettable by switch from the FDCIE after the initiating device or devices have been restored to normal.

2.1.10.5 Fire Alarm Voice Message

A fire alarm shall activate notification appliance circuits. Textual audible appliances shall produce a slow whoop tone for three cycles followed by a voice message which is repeated until the control panel is reset or silenced. A live voice message shall override the automatic audible output through use of a microphone input at the control panel.

When using the microphone, live messages shall be broadcast through speakers in stairs, in elevator cabs, and throughout a selected floor or floors. The system shall be capable of operating all speakers at the same time. The digitalized voice message shall consist of a non-volatile (EPROM) microprocessor based input to the amplifiers. The microprocessor shall actively interrogate circuitry, field wiring, and digital coding necessary for the immediate and accurate rebroadcasting of the stored voice data into the appropriate amplifier input. Loss of operating power, supervisory power, or any other malfunction which could render the digitalized voice module inoperative shall automatically cause the slow whoop tone to take over all functions assigned to the failed unit.

Messages shall utilize a female voice and shall be as follows:

"May I have your attention, please. May I have your attention, please. A fire has been reported which may affect your floor. Please walk to the nearest exit and evacuate the building." (Provide a 2 second pause.) "May I have your attention, please...(repeat the message)." The alert tone shall be in accordance with the MFPE and be the accepted Australian Evacuation Tone.

2.1.10.6 Memory

Provide each control unit with non-volatile memory and logic for all functions. The use of long life batteries, capacitors, or other age-dependent devices shall not be considered as equal to non-volatile processors, PROMS, or EPROMS.

2.1.10.7 Field Programmability

Provide control units and control panels that are fully field programmable for control, initiation, notification, supervisory, and trouble functions of both input and output. The system program configuration shall be menu driven. System changes shall be password protected and shall be accomplished using personal computer based equipment.

SECTION 28 31 63.00 20 Page 14

2.1.10.8 Input/Output Modifications

The FDCIE shall contain features which allow the bypassing of input devices from the system or the modification of system outputs. These control features shall consist of a panel mounted keypad. Any bypass or modification to the system shall indicate a trouble condition on the FDCIE.

2.1.10.9 Resetting

Provide the necessary controls to prevent the resetting of any alarm, supervisory, or trouble signal while the alarm, supervisory or trouble condition on the system still exists.

2.1.10.10 Instructions

Provide a typeset printed or typewritten instruction card mounted behind a Lexan plastic or glass cover in a stainless steel or aluminum frame.

Install the instructions on the interior of the FDCIE. The card shall show those steps to be taken by an operator when a signal is received as well as the functional operation of the system under all conditions, normal, alarm, supervisory, and trouble. The instructions shall be approved by the Contracting Officer before being posted.

2.1.10.11 Walk Test

The FDCIE shall have a walk test feature. When using this feature, operation of initiating devices shall result in limited system outputs, so that the notification appliances operate for only a few seconds and the event is indicated on the system printer, but no other outputs occur. A yellow indicator light must be provided to indicate when a zone is under test conditions.

2.1.10.12 History Logging

In addition to the required printer output, the control panel shall have the ability to store a minimum of 400 events in a log. These events shall be stored in a battery-protected memory and shall remain in the memory until the memory is downloaded or cleared manually. Resetting of the control panel shall not clear the memory.

2.1.10.13 RS-232-C Output

Each local control panel shall be capable of operating remote service type cathode ray tubes (CRTs), printers, and/or modems. The output shall be paralleled ASCII from an EIA RS-232-C connection with a baud rate of 1200 or 2400 to allow use of any commonly available CRT, printer, or modem.

2.1.11 Amplifiers, Preamplifiers, Tone Generators

Any amplifiers, preamplifiers, tone generators, digitalized voice generators, and other hardware necessary for a complete, operational, textual audible circuit conforming to MFPE shall be housed in a fire alarm control unit, terminal cabinet, or in the fire alarm control panel. The system shall automatically operate and control all building fire alarm speakers except those installed in the stairs and within elevator cabs. The speakers in the stairs and elevator cabs shall operate only when the microphone is used to deliver live messages. Each amplifier shall have two channels; one to broadcast a message and the other for paging.

SECTION 28 31 63.00 20 Page 15

2.1.11.1 Construction

Amplifiers shall utilize computer grade solid state components and shall be provided with output protection devices sufficient to protect the amplifier against any transient up to 10 times the highest rated voltage in the system.

2.1.11.2 Inputs

Each system shall be equipped with separate inputs from the tone generator, digitalized voice driver and panel mounted microphone. Microphone inputs shall be of the low impedance, balanced line type. Both microphone and tone generator input shall be operational on any amplifier.

2.1.11.3 Tone Generator

The tone generator shall be of the modular, plug-in type with securely attached labels to identify the component as a tone generator and to identify the specific tone it produces. The tone generator shall produce a slow whoop tone, which shall slowly ascend from low (500 hertz) to high (1200 hertz), and shall be constantly repeated until interrupted by either the digitalized voice message, the microphone input, or the alarm silence mode as specified. Each slow whoop cycle shall last approximately 4 seconds. The tone generator shall be single channel with an automatic backup generator per channel such that failure of the primary tone generator causes the backup generator to automatically take over the functions of the failed unit and also causes transfer of the common trouble relay.

2.1.11.4 Protection Circuits

Each amplifier shall be constantly supervised for any condition which could render the amplifier inoperable at its maximum output. Failure of any component shall cause automatic transfer to a designated backup amplifier, illumination of a visual "amplifier trouble" indicator on the control panel, appropriate logging of the condition on the system printer, and other actions for trouble conditions as specified.

2.1.12 Manual Stations

Provide metal or plastic, semi-flush mounted, double action, addressable manual stations, which are not subject to operation by jarring or vibration. Stations shall be equipped with screw terminals for each conductor. Stations which require the replacement of any portion of the device after activation are not permitted. Stations shall be finished in fire-engine red with molded raised lettering operating instructions of contrasting color. The use of a key or wrench shall be required to reset the station.

2.1.13 Notification Appliances

2.1.13.1 Fire Alarm Speakers

a. Provide fire alarm speakers conforming to the MFPE and ACTIVEFIRE having a minimum of three tap settings and separate terminations for each in and out connection. Tap settings shall include taps of 1/4, 1/2, 1 and 2 watt. Speakers shall utilize the 1/2 watt tap in the system.

Speakers shall have an output rating of 84 dBA at 3050 mm as determined by the reverberant room test; data on peak output as determined in an

SECTION 28 31 63.00 20 Page 16 anechoic chamber is not suitable. Speakers shall be capable of installation on standard 100 mm square electrical boxes. Where speakers and strobes are provided in the same location, they may be combined into a single wall mounted unit.

b. Provide speaker mounting plates constructed of cold rolled steel having a minimum thickness of 16 gage and equipped with mounting holes and other openings as needed for a complete installation. Fabrication marks and holes shall be ground and finished to provide a smooth and neat appearance for each plate. Each plate shall be primed and painted.

2.1.13.2 Visual Alarm Signals

Provide strobe light visual alarm signals which operate on a supervised 24 volt DC circuit. The strobe lens shall comply with ACTIVFIRE and the MFPE.

The light pattern shall be disbursed so that it is visible above and below the strobe and from a 90 degree angle on both sides of the strobe. The strobe flash output shall be a minimum of 15 candela based on the MFPE and ACTIVEFIRE requirements. The strobe shall have a xenon flash tube.

Visible appliances may be part of an audio-visual assembly. Provide synchronized operation of all strobes in the facility. The visual alarm devices must comply with AS1603.11.

2.1.13.3 Connections

Provide screw terminals for each notification appliance. Terminals shall be designed to accept the size conductors used in this project without modification.

2.1.14 OPTICAL FLAME DETECTION

Optical flame detection will be the X3301 Multispectrum IR Flame Detector manufactured by Det-Tronics. Optical flame detection system will use triple infrared (IR)flame detectors listed/approved for the expected fuel hazards in the building and meet EN54-10 standard. The detectors will be immune to radar and radio frequency emissions. Provide shielding for the detectors and their circuits from radio frequency interference. All circuiting from the FDCIE or FSCP to the detectors will be shielded, and shielding will be grounded at one end. Optical flame detector alarm signals to the FDCIE or FSCP will be latching.

Detectors must be mounted in accordance with their listing at approximately 8 ft. (2.4 m) above the finished floor of the room. The specifics for each design must take into account facility construction, piping and equipment configuration and positioning, fixed and mobile equipment within the area, and all other relevant factors. Do not mount optical detectors in inaccessible locations. The detectors will be angled and blinds will be provided such that the cone-of-vision does not extend more than 5 ft.

(1.5m) outside the area being protected. The horizontal and vertical axis of the detector determined during commissioning will be permanently marked on each detector. The optical flame detectors will be installed with 5 ft.

(1.5 m) of flexible conduit to allow for any minor adjustments during testing or changes in mission. Provide a sufficient number of optical flame detectors such that a fire at any position within the area being protected will be within the range and cone-of vision of at least one detector.

SECTION 28 31 63.00 20 Page 17

2.1.15 Automatic Transmitters

2.1.15.1 Fire Alarm Interface Panels

Provide an interface with the existing Tindal Fire Department base receiving equipment via ROMTECK RM3118-IP-WIP-ASE-F fire alarm communicator. Wire interface cabling between FDCIE and fire alarm communicator to provide voltage free, clean contact signaling, (note all signal wiring to the communicator inputs must be volt free). Interface cabling shall be stranded data-type cable with a total cross-sectional area of all the conductors within the cable not less than 1.5 sq. mm and terminated using correctly sized bootlace ferrules. Where signal wiring is required to be joined at the FDCIE provide a clearly labelled fixed terminal strips utilising clamp-type connectors.

2.1.15.2 Signals To Be Transmitted to the Base Receiving Station

The signals shall be as indicated on the drawings.

2.2 NAMEPLATES

Major components of equipment shall have the manufacturer's name, address, type or style, model or serial number, catalog number, date of installation, installing Contractor's name and address, and the contract number provided on a new plate permanently affixed to the item or equipment. Major components include, but are not limited to, the following:

a. FDCIEs

b. Automatic transmitter

Furnish to obtain approval by the Contracting Officer before installation.

Obtain approval by the Contracting Officer for installation locations.

Nameplates shall be etched metal or plastic, permanently attached by screws to panels or adjacent walls.

2.3 WIRING

Provide wiring materials under this section as specified in Section 26 20 00 INTERIOR DISTRIBUTION SYSTEM with the additions and modifications specified herein.

PART 3 EXECUTION

3.1 INSTALLATION OF FIRE ALARM INITIATING AND INDICATING DEVICES

a. FDCIE: Locate the FDCIE where indicated on the drawings. Surface mount the enclosure with the top of the cabinet 1830 mm above the finished floor or center the cabinet at 1525 mm, whichever is lower. Conductor terminations shall be labeled and a drawing containing conductors, their labels, their circuits, and their interconnection shall be permanently mounted in the FDCIE.

b. Manual Stations: Locate manual stations as required by the MFPE, and where shown on the drawings. Mount stations so that their operating handles are 1220 mm above the finished floor. Mount stations so they are located no farther than 1525 mm from the exit door they serve, measured horizontally.

SECTION 28 31 63.00 20 Page 18

c. Notification Appliance Devices: Locate notification appliance devices as required by the MFPE and where shown on the drawings. Mount assemblies on walls 2030 mm above the finished floor or 150 mm below the ceiling whichever is lower. Ceiling mounted speakers shall conform to MFPE requirements.

d. Smoke and Heat Sensors: Locate sensors as required by the MFPE and their listings and as shown on the drawings on a mounting box. Sensors located on the ceiling shall be installed not less than 100 mm from a side wall to the near edge. Those located on the wall shall have the top of the sensor at least 100 mm below the ceiling, but not more than 300 mm below the ceiling. In raised floor spaces, the smoke sensors shall be installed to protect 20.9 square meters per sensor. Install smoke sensors no closer than 1525 mm from air handling supply outlets.

e. Water Flow Detectors and Tamper Switches: Locate water flow detectors and tamper switches where shown on the drawings

3.2 CONNECTION OF NEW SYSTEM

The following new system connections shall be made during the last phase of construction, at the beginning of the preliminary tests. New system connections shall include:

a. Connection of new system transmitter to existing base fire reporting system.

Once these connections are made, system shall be left energized and new audio/visual devices deactivated. Report immediately to the Contracting Officer, coordination and field problems resulting from the connection of the above components.

3.3 PAINTING

Paint exposed electrical, fire alarm conduit, and surface metal raceway to match adjacent finishes in exposed areas. Paint junction boxes, conduit and surface metal raceways red in unfinished areas. Painting shall comply with Section 09 90 00 PAINTS AND COATINGS.

3.4 FIELD QUALITY CONTROL

3.4.1 Tests

a. Megger Tests: After wiring has been installed, and prior to making any connections to panels or devices, wiring shall be megger tested for insulation resistance, grounds, and/or shorts. Conductors with 300 volt rated insulation shall be tested at a minimum of 250 VDC.

Conductors with 600 volt rated insulation shall be tested at a minimum of 500 VDC. The tests shall be witnessed by the Contracting Officer and test results recorded for use at the final acceptance test.

b. Loop Resistance Tests: Measure and record the resistance of each circuit with each pair of conductors in the circuit short-circuited at the farthest point from the circuit origin. The tests shall be witnessed by the Contracting Officer and test results recorded for use at the final acceptance test.

c. Preliminary Testing: Conduct preliminary tests to ensure that devices and circuits are functioning properly. Tests shall meet the

SECTION 28 31 63.00 20 Page 19 requirements of paragraph entitled "Minimum System Tests." After preliminary testing is complete, provide a letter certifying that the installation is complete and fully operable. The letter shall state that each initiating and indicating device was tested in place and functioned properly. The letter shall also state that panel functions were tested and operated properly. The letter shall include the names and titles of the witnesses to the preliminary tests. The Contractor and an authorized representative from each supplier of equipment shall be in attendance at the preliminary testing to make necessary adjustments.

d. Request for Formal Inspection and Tests: When tests have been…