About this file

This is a specification section for flashing and sheet metal work for the MQ-25 Aircraft Laydown Facilities at Naval Station Norfolk, Virginia, dated August 2023 under FY 24 MCON Project P-222 (eProject Work Order 1737012).

The specification establishes comprehensive requirements for the design, materials, fabrication, and installation of sheet metal assemblies, including exposed coverings, downspouts, expansion joints, gravel stops, flashings, copings, drip edges, conductor heads, and related accessories. Materials permitted include aluminum alloy, stainless steel (Type 302 or 304), zinc-coated steel (minimum 24 gauge with 90 ounces per square foot zinc coating), and zinc sheet per applicable ASTM standards. Exposed exterior sheet metal and aluminum must feature factory-applied fluoropolymer color coatings or siliconized polyester coatings with 0.8 to 1.3 mils dry film thickness. Cool roof finishes must achieve minimum 3-year aged solar reflectance of 0.55 and thermal emittance of 0.75, or Solar Reflectance Index of 64 per ASTM E1980 to comply with ASHRAE 90.1-IP. The specification requires all materials to meet ES-1 wind uplift requirements per ANSI/SPRI/FM 4435/ES-1 using NRCA 0429 details. Sheet metal items must be provided in 8 to 10 foot lengths with factory-fabricated corner pieces featuring minimum 12-inch legs. Installation requirements specify expansion joints at maximum 32-foot intervals for aluminum and 40-foot intervals for other metals, detailed seam specifications (soldered, locked, or mechanically fastened), cleat spacing not exceeding 12 inches on center, and comprehensive flashing details for roof penetrations, base and counterflashing, gravel stops, downspouts, scuppers, and conductor heads. A 20-year manufacturer's warranty on finishes covering color fading beyond 5 Delta E units and chalking exceeding No. 8 rating is required. Submittals require government approval for shop drawings, product data, finish samples, warranties, manufacturer's instructions, and quality control documentation.

View the file

Other files

File Type Posted
Attachment G Individual Small Business Subcontracting Plan.docx DOCX document
Attachment F Small Business Participation Commitment.docx DOCX document
JA ML2650 25R2639 P222 ILDFA Redacted.pdf PDF
Solicitation Amendment N4008525R26390008 SF 30.pdf PDF
K3237099 LP-48 HazMat Report 3.5.26 - signed.pdf PDF
01 31 23.13 20.pdf PDF
Amendment 0007 Continuation Sheet.pdf PDF
Solicitation Amendment N4008525R26390007 SF 30.pdf PDF
REGISTER.pdf PDF
TABLE OF CONTENTS.pdf PDF
13 49 20.00 10.pdf PDF
Solicitation Amendment N4008525R26390006 SF 30.pdf PDF
P222_1737012_01 91 00.15 22.pdf PDF
Crane - LP48 1-DATA SHEET.pdf PDF
P222_1737012_Geotech Report.pdf PDF
P222_1737012_28 31 76.pdf PDF
Attachment H - Price Proposal Form_rev1.pdf PDF
P222_1737012_Drawings_volume II_Rev 001_SIGNED.pdf PDF
Solicitation Amendment N4008525R26390005 SF 30.pdf PDF
P222_1737012_04 20 00.pdf PDF
Amendment 0005 Continuation Sheet.pdf PDF
P222_1737012_32 13 13.06.pdf PDF
P222_1737012_09 29 00.pdf PDF
FY26 Naval Station Norfolk Utility Costs.pdf PDF
P222_1737012_07 21 13.pdf PDF
P222_1737012_REGISTER.pdf PDF
P222_1737012_Drawings_volume I_Rev 001_SIGNED.pdf PDF
P222_1737012_13 34 20.pdf PDF
Crane - LP48 2-DATA SHEET.pdf PDF
Solicitation Amendment N4008525R26390004 SF 30.pdf PDF
JA ML2623 25R2639 P222 ASSA Abloy Redacted.pdf PDF
JA ML2624 25R2639 P222 SRG RF Shielding Redacted.pdf PDF
26R2639 P222 Site Visit Log.pdf PDF
Solicitation Amendment N4008525R26390003 SF 30.pdf PDF
Solicitation Amendment N4008525R26390002 SF 30.pdf PDF
Solicitation Amendment N4008525R26390001 SF 30.pdf PDF
Attachment B - PIEE Vendor Access Instructions.pdf PDF
1737012_dwg 02of02_P222.pdf PDF
Attachment M - P222 Site Visit Map.pdf PDF
1737012_spec 01of04_P222.pdf PDF
1737012_dwg 01of02_P222.pdf PDF
Attachment C- Construction Experience Project Data.docx DOCX document
Attachment D- Past Performance Questionnaire.docx DOCX document
Attachment H - Price Proposal Form.pdf PDF
Attachment E- Historical Small Business Utilization.docx DOCX document
Attachment G- Individual Small Business Subcontracting Plan.docx DOCX document
1737012_spec 04of04_P222.pdf PDF
Attachment F- Small Business Participation Commitment.docx DOCX document
Attachment L - JA ML-26-01 P222 MQ25 Hangar Brand Name or Equal Finishes_Reda.pdf PDF
1737012_spec 03of04_P222.pdf PDF
Show 40 more

Latest 50 of 56 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FY 24 MCON Project P-222 eProject Work Order No: 1737012 MQ-25 Aircraft Laydown Facilities Naval Station, Norfolk, Virginia

SECTION 07 60 00

FLASHING AND SHEET METAL

08/23

PART 1 GENERAL

1.1 REFERENCES

The publications listed below form a part of this specification to the extent referenced. The publications are referred to within the text by the basic designation only.

AMERICAN SOCIETY OF HEATING, REFRIGERATING AND AIR-CONDITIONING

ENGINEERS (ASHRAE)

ASHRAE 90.1 - IP (2019) Energy Standard for Buildings Except Low-Rise Residential Buildings

AMERICAN WELDING SOCIETY (AWS)

AWS D1.2/D1.2M (2014; Errata 1 2014; Errata 2 2020) Structural Welding Code - Aluminum

ASTM INTERNATIONAL (ASTM)

ASTM A480/A480M (2023b) Standard Specification for General Requirements for Flat-Rolled Stainless and Heat-Resisting Steel Plate, Sheet, and Strip

ASTM A653/A653M (2023) Standard Specification for Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed) by the Hot-Dip Process

ASTM B32 (2020) Standard Specification for Solder Metal

ASTM B69 (2021) Standard Specification for Rolled Zinc

ASTM B209/B209M (2021a) Standard Specification for Aluminum and Aluminum-Alloy Sheet and Plate

ASTM B221 (2021) Standard Specification for Aluminum and Aluminum-Alloy Extruded Bars, Rods, Wire, Profiles, and Tubes

ASTM D41/D41M (2011; R 2016) Standard Specification for Asphalt Primer Used in Roofing, Dampproofing, and Waterproofing

ASTM D226/D226M (2017) Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing

ASTM D2244 (2021) Standard Practice for Calculation

SECTION 07 60 00 Page 1 of Color Tolerances and Color Differences from Instrumentally Measured Color Coordinates

ASTM D4214 (2007; R 2015) Standard Test Method for Evaluating the Degree of Chalking of Exterior Paint Films

ASTM D4586/D4586M (2007; R 2018) Asphalt Roof Cement, Asbestos-Free

ASTM E1980 (2011; R 2019) Standard Practice for Calculating Solar Reflectance Index of Horizontal and Low-Sloped Opaque Surfaces

ASTM E2112 (2023) Standard Practice for Installation of Exterior Windows, Doors and Skylights

COOL ROOF RATING COUNCIL (CRRC)

ANSI/CRRC S100 (2016) Standard Test Methods for Determining Radiative Properties of Materials

NATIONAL ROOFING CONTRACTORS ASSOCIATION (NRCA)

NRCA 0429 (2022) The NRCA Roofing Manual:

Architectural Metal Flashing, Condensation and Air Leakage Control and Reroofing

SHEET METAL AND AIR CONDITIONING CONTRACTORS' NATIONAL ASSOCIATION

(SMACNA)

SMACNA 1793 (2012) Architectural Sheet Metal Manual, 7th Edition

SINGLE PLY ROOFING INDUSTRY (SPRI)

ANSI/SPRI RD-1 (2019) Performance Standard for Retrofit Drains

ANSI/SPRI/FM 4435/ES-1 (2017) Test Standard for Edge Systems Used with Low Slope Roofing Systems

1.2 GENERAL REQUIREMENTS

Finished sheet metal assemblies must form a weathertight enclosure without waves, warps, buckles, fastening stresses or distortion, while allowing for expansion and contraction without damage to the system. The sheet metal installer is responsible for cutting, fitting, drilling, and other operations in connection with sheet metal modifications required to accommodate the work of other trades. Coordinate installation of sheet metal items used in conjunction with roofing with roofing work to permit continuous, uninterrupted roofing operations.

1.2.1 General Material Requirements

All materials specified in this Section installed in conjunction with the roofing system must be provided by the roofing system manufacturer, or by

SECTION 07 60 00 Page 2 a manufacturer approved by the roofing system manufacturer for use in the roofing system, and must form a part of the Warranty as required by the applicable roofing system Section.

1.2.2 Additional Wind Uplift Requirements

All flashing and edge materials specified in this Section must be installed in conjunction with the requirements of the roofing system to meet the requirements of ES-1 wind uplift. Details must include but not limited to ANSI/SPRI/FM 4435/ES-1 (ES-1), "Wind Test Design Standard for Edge Systems" used with Low Slope Roofing Systems, Test Methods: RE-1, RE-2 and RE-3 using uplift roofing details of the NRCA 0429.

1.3 SUBMITTALS

Government approval is required for submittals with a "G" or "S" classification. Submittals not having a "G" or "S" classification are for Contractor Quality Control approval. Submit the following in accordance with Section 01 33 00 SUBMITTAL PROCEDURES:

SD-02 Shop Drawings

Exposed Sheet Metal Coverings; G

Downspouts ; G

Expansion Joints ; G

Gravel Stops and fascia ; G

Flashing for Roof Drains ; G

Base Flashing ; G

Counterflashing ; G

Flashing at Roof Penetrations and Equipment Supports ; G

Reglets ; G

Scuppers ; G

Copings ; G

Drip Edges ; G

Conductor Heads ; G

Open Valley Flashing ; G

Recycled Content ; S

Fire Rated Expansion Joints ; G

Bellow Type Building Expansion Joint Cover ; G

SD-03 Product Data

Cool Roof Data; G

SECTION 07 60 00 Page 3

Bellow Type Building Expansion Joint Cover ; G

SD-04 Samples

Finish Samples ; G

SD-07 Certificates

Warranty on Finishes ; G

SD-08 Manufacturer's Instructions

Instructions for Installation ; G

Quality Control Plan ; G

SD-10 Operation and Maintenance Data

Cleaning and Maintenance ; G

1.4 MISCELLANEOUS REQUIREMENTS

1.4.1 Product Data

Indicate thicknesses, dimensions, fastenings, anchoring methods, expansion joints, and other provisions necessary for thermal expansion and contraction. Scaled manufacturer's catalog data may be submitted for factory fabricated items.

1.4.2 Finish Samples

Submit two color charts and two finish sample chips from manufacturer's standard color and finish options for each type of finish indicated.

1.4.3 Operation and Maintenance Data

Submit detailed instructions for installation and quality control during installation, cleaning and maintenance , for each type of assembly indicated.

1.5 DELIVERY, HANDLING, AND STORAGE

Package and protect materials during shipment. Uncrate and inspect materials for damage, dampness, and wet-storage stains upon delivery to the job site. Remove from the site and replace damaged materials that cannot be restored to like-new condition. Handle sheet metal items to avoid damage to surfaces, edges, and ends. Store materials in dry, weather-tight, ventilated areas until installation.

PART 2 PRODUCTS

2.1 RECYCLED CONTENT

Provide products with recycled content. Provide data for each product with recycled content, identifying percentage of recycled content.

SECTION 07 60 00 Page 4

2.2 MATERIALS

Use any metal listed by NRCA 0429 or SMACNA 1793 for a particular item, unless otherwise indicated. Provide materials and configurations in accordance with NRCA 0429 or SMACNA 1793 for each material, while also meeting the minimum thickness requirements specified in this Section.

Different items need not be of the same metal, except that contact between dissimilar metals must be avoided.

Provide sheet metal items in 8 to 10 foot lengths. Single pieces less than 8 feet long may be used to connect to factory-fabricated inside and outside corners, and at ends of runs. Factory fabricate corner pieces with minimum 12 inch legs. Provide accessories and other items essential to complete the sheet metal installation. Provide accessories made of the same or compatible materials as the items to which they are applied.

Fabricate sheet metal items of the materials specified below and to the gage, thickness, or weight shown in Table I at the end of this section.

Provide sheet metal items with mill finish unless specified otherwise.

Where more than one material is listed for a particular item in Table I, each is acceptable and may be used, except as follows:

2.2.1 Exposed Sheet Metal Items

Provide exposed sheet metal items of the same material. Consider the following as exposed sheet metal: including hangers; downspouts; gravel stops and fascia ; cap, valley, steeped, base, and eave flashings and related accessories.

2.2.2 Drainage

Do not use copper for an exposed item if drainage from that item will pass over exposed masonry, stonework or other metal surfaces. In addition to the metals listed in Table I, lead-coated copper may be used for such items.

2.2.3 Steel Sheet, Zinc-Coated (Galvanized)

Provide in accordance with ASTM A653/A653M , a minimum of 24 gauge, and a minimum zinc coat weighting of 90 ounces per square feet.

2.2.4 Zinc Sheet and Strip

Provide in accordance with ASTM B69, Type I, a minimum of 0.024 inch thick.

2.2.5 Stainless Steel

Provide in accordance with ASTM A480/A480M , Type 302 or 304, 2D Finish, fully annealed, dead-soft temper, a minimum of 24 gauge.

2.2.6 Aluminum Alloy Sheet and Plate

Provide in accordance with ASTM B209/B209M color as indicated form alloy, and temper appropriate for use. Provide material not less than 0.065-in in thickness.

2.2.7 Finishes

Provide exposed exterior sheet metal and aluminum with a baked on, factory applied coil fluoropolymer color coating or approved equal siliconized

SECTION 07 60 00 Page 5 polyester coating. Dry film thickness of coatings must be 0.8 to 1.3 mils.

Color to be selected from manufacturer's full range of "cool roof" color choices manufacturer's full range of color choices. Field applications of color coatings are prohibited and will be rejected.

2.2.7.1 Warranty on Finishes

Provide a manufacturer's warranty to repair, or replace, sheet metal flashing and trim that shows evidence of deterioration of factory-applied finishes within 20 years from date of project substantial completion.

Deterioration includes the following:

a. Color fading more than 5 Delta E units when tested in accordance with

ASTM D2244.

b. Chalking in excess of a No. 8 rating when tested in accordance with

ASTM D4214.

c. Cracking, checking, peeling, or failure of paint to adhere to bare metal.

2.2.8 Cool Roof Finishes

Provide roof finishes having a minimum 3-year aged solar reflectance of 0.55, and a minimum 3-year aged thermal emittance of 0.75 when tested in accordance with ANSI/CRRC S100 , or, a minimum 3-year aged Solar Reflectance Index of 64 when determined in accordance with the Solar Reflectance Index method in ASTM E1980 using a convection coefficient of

2.1 BTU per h ft2, to comply with ASHRAE 90.1 - IP .

2.2.9 Aluminum Alloy, Extruded Bars, Rods, Shapes, and Tubes

ASTM B221.

2.2.10 Solder

Provide in accordance with ASTM B32, 95-5 tin-antimony.

2.2.11 Reglets

2.2.11.1 Metal Reglets

Provide factory fabricated caulked type or friction type reglets with a minimum opening of 1/4 inch and a depth of 1-1/4 inch, as approved.

2.2.12 Scuppers

Line interiors of scupper openings with sheet metal. Provide a drip edge at bottom edges with returns of not less than one inch against the face of the outside wall at the top and sides. Provide the perimeter of the lining approximately 1/2 inch less than the perimeter of the scupper.

2.2.13 Conductor Heads

Provide conductor heads and screens in the same material as downspouts.

Provide outlet tubes not less than 4 inches long.

SECTION 07 60 00 Page 6

2.2.14 Copings

Unless otherwise indicated, provide copings 8 or 10 feet long, joined by a 3/4 inch locked and soldered seam.

2.2.15 Bituminous Plastic Cement

Provide in accordance with ASTM D4586/D4586M , Type I.

2.2.16 Roofing Felt

Provide in accordance with ASTM D226/D226M Type II.

2.2.17 Asphalt Primer

Provide in accordance with ASTM D41/D41M.

2.2.18 Fasteners

Use stainless steel fasteners to fasten. Confirm compatibility of fasteners and items to be fastened to avoid galvanic corrosion due to dissimilar materials.

2.3 FIRE RATED EXPANSION JOINTS

Provide fire rated expansion joints as indicated.

2.4 BELLOW TYPE BUILDING EXPANSION JOINT COVER

Where indicated on drawings, provide bellow type building expansion joint cover comprised of 0.018 inch thick stainless steel flanges connected by an EPDM membrane (black). Flanges must be 4 inches wide at flat applications and 2 inches by 2 inches at curb applications. Refer to drawings for flat vs curb applications and for joint sizes.

PART 3 EXECUTION

3.1 INSTALLATION

3.1.1 Cleats

Provide cleats for sheet metal 18 inches and over in width. Space cleats evenly not over 12 inches on center unless otherwise specified or indicated. Unless otherwise specified, provide cleats of 2 inches wide by 3 inches long and of the same material and thickness as the sheet metal being installed. Secure one end of the cleat with two nails and the cleat folded back over the nailheads. Lock the other end into the seam. Where the fastening is to be made to concrete or masonry, use screws and drive in expansion shields set in concrete or masonry. Pre-tin cleats for soldered seams.

3.1.2 Bolts, Rivets, and Screws

Install bolts, rivets, and screws where indicated or required. Provide compatible washers where required to protect surface of sheet metal and to provide a watertight connection. Provide mechanically formed joints in aluminum sheets 0.040 inches or less in thickness.

SECTION 07 60 00 Page 7

3.1.3 Seams

Straight and uniform in width and height with no solder showing on the face.

3.1.3.1 Flat-lock Seams

Finish not less than 3/4 inch wide.

3.1.3.2 Lap Seams

Finish soldered seams not less than one inch wide. Overlap seams not soldered, not less than 3 inches.

3.1.3.3 Loose-Lock Expansion Seams

Not less than 3 inches wide; provide minimum one inch movement within the joint. Completely fill the joints with the specified sealant, applied at not less than 1/8 inch thick bed.

3.1.3.4 Standing Seams

Not less than one inch high, double locked without solder.

3.1.3.5 Flat Seams

Make seams in the direction of the flow.

3.1.4 Soldering

Where soldering is specified, apply to zinc-coated steel, and stainless steel items. Pre-tin edges of sheet metal before soldering is begun.

Seal the joints in aluminum sheets of 0.040 inch or less in thickness with specified sealants. Do not solder aluminum.

3.1.4.1 Edges

Scrape or wire-brush the edges of lead-coated material to be soldered to produce a bright surface. Flux brush the seams in before soldering.

Treat with soldering acid flux the edges of stainless steel to be pre-tinned. Seal the joints in aluminum sheets of 0.040 inch or less in thickness with specified sealants. Do not solder aluminum.

3.1.5 Welding and Mechanical Fastening

Use welding for aluminum of thickness greater than 0.040 inch. Aluminum

0.040 inch or less in thickness must be butted and the space backed with formed flashing plate; or lock joined, mechanically fastened, and filled with sealant as recommended by the aluminum manufacturer.

3.1.5.1 Welding of Aluminum

Use welding of the inert gas, shield-arc type. For procedures, appearance and quality of welds, and the methods used in correcting welding work, conform to AWS D1.2/D1.2M .

3.1.5.2 Mechanical Fastening of Aluminum

Use No. 12, aluminum alloy, sheet metal screws or other suitable aluminum

SECTION 07 60 00 Page 8 alloy or stainless steel fasteners. Drive fasteners in holes made with a No. 26 drill in securing side laps, end laps, and flashings. Space fasteners 12 inches maximum on center. Where end lap fasteners are required to improve closure, locate the end lap fasteners not more than 2 inches from the end of the overlapping sheet.

3.1.6 Protection from Contact with Dissimilar Materials

3.1.6.1 Aluminum

Do not allow aluminum surfaces in direct contact with other metals except stainless steel, zinc, or zinc coating. Where aluminum contacts another metal, paint the dissimilar metal with a primer followed by two coats of aluminum paint. Where drainage from a dissimilar metal passes over aluminum, paint the dissimilar metal with a non-lead pigmented paint.

Aluminum may be used over concrete construction, provided that required reglets are of stainless steel and aluminum surface in contact with concrete or masonry is coated with bituminous paint or zinc chromate primer.

3.1.6.2 Metal Surfaces

Paint surfaces in contact with mortar, concrete, or other masonry materials with alkali-resistant coatings such as heavy-bodied bituminous paint.

3.1.6.3 Wood or Other Absorptive Materials

Paint surfaces that may become repeatedly wet and in contact with metal with two coats of aluminum paint or a coat of heavy-bodied bituminous paint.

3.1.7 Expansion and Contraction

Provide expansion and contraction joints at not more than 32 foot intervals for aluminum and at not more than 40 foot intervals for other metals. Provide an additional joint where the distance between the last expansion joint and the end of the continuous run is more than half the required interval. Space joints evenly. Join extruded aluminum gravel stops and fascia by expansion and contraction joints spaced not more than 12 feet apart.

3.1.8 Base Flashing

Lay the base flashings with each course of the roof covering, shingle fashion, where practicable, where sloped roofs abut curbs, walls, or other vertical surfaces. Extend up vertical surfaces of the flashing not less than 8 inches and not less than 4 inches under the roof covering. Where finish wall coverings form a counterflashing, extend the vertical leg of the flashing up behind the applied wall covering not less than 6 inches.

Overlap the flashing strips with the previously laid flashing not less than 3 inches. Fasten the strips at their upper edge to the deck. Horizontal flashing at vertical surfaces must extend vertically above the roof surface and fastened at their upper edge to the deck a minimum of 6 inches on center with hex headed, galvanized shielded screws a minimum of 2 inch lap of any surface. Solder end laps and provide for expansion and contraction. Extend the metal flashing over crickets at the up-slope side of curbs, and similar vertical surfaces extending through sloping roofs, the metal flashings. Extend the metal flashings onto the roof covering

SECTION 07 60 00 Page 9 not less than 4.5 inches at the lower side of vertical surfaces extending through the roof decks. Install and fit the flashings so as to be completely weathertight. Provide factory-fabricated base flashing for interior and exterior corners. Do not use metal base flashing on built-up roofing.

3.1.9 Counterflashing

Except where indicated or specified otherwise, insert counterflashing in reglets located from 9 to 10 inches above roof decks, extend down vertical surfaces over upturned vertical leg of base flashings not less than 3 inches. Fold the exposed edges of counterflashings 1/2 inch. Where stepped counterflashings are required, they may be installed in short lengths a minimum 8 inches by 8 inches or may be of the preformed single piece type. Provide end laps in counterflashings not less than 3 inches and make it weathertight with plastic cement. Do not make lengths of metal counterflashings exceed 10 feet. Form flashings to the required shapes before installation. Factory form corners not less than 12 inches from the angle. Secure the flashings in the reglets with lead wedges and space not more than 18 inches apart; on stair/elevator towers short runs, place wedges closer together. Fill caulked-type reglets or raked joints which receive counterflashing with caulking compound. Turn up the concealed edge of counterflashings built into masonry or concrete walls not less than 1/4 inch and extend not less than 2 inches into the walls.

Install counterflashing to provide a spring action against base flashing.

Where bituminous base flashings are provided, extend down the counter flashing as close as practicable to the top of the cant strip. Factory form counter flashing to provide spring action against the base flashing.

Utilize two piece counterflashing components to minimize damage of counterflashing and reglets during future reroofing activities.

3.1.10 Metal Reglets

Keep temporary cores in place during installation. Ensure factory fabricated caulked type or friction type, reglets have a minimum opening of 1/4 inch and a minimum depth of 1-1/4 inch, when installed.

3.1.11 Gravel Stops and fascia

Prefabricate in the shapes and sizes indicated and in lengths not less than 8 feet. Extend flange at least 4 inches onto roofing. Provide prefabricated, mitered corners internal and external corners. Install gravel stops and fascia after all plies of the roofing membrane have been applied, but before the flood coat of bitumen is applied. Prime roof flange of gravel stops and fascia on both sides with an asphalt primer.

After primer has dried, set flange on roofing membrane and strip-in. Nail flange securely to wood nailer with large-head, barbed-shank roofing nails

1.5 inch long spaced not more than 3 inches on center, in two staggered rows.

3.1.11.1 Edge Strip

Hook the lower edge of fascia at least 3/4 inch over a continuous strip of the same material bent outward at an angle not more than 45 degrees to form a drip. Nail hook strip to a wood nailer at 6 inches maximum on center. Where fastening is made to concrete or masonry, use screws spaced 12 inches on center driven in expansion shields set in the concrete or masonry. Where horizontal wood nailers are slotted to provide for insulation venting, install strips to prevent obstruction of vent slots.

SECTION 07 60 00 Page 10

Where necessary, install strips over 1/16 inch thick compatible spacer or washers.

3.1.11.2 Joints

Leave open the section ends of gravel stops and fascia 1/4 inch and backed with a formed flashing plate, mechanically fastened in place and lapping each section end a minimum of 4 inches set laps in plastic cement. Face nailing is not permitted. Install prefabricated aluminum gravel stops and fascia in accordance with the manufacturer's printed instructions and details.

3.1.12 Metal Drip Edges

Provide a metal drip edge, designed to allow water run-off to drip free of underlying construction, at eaves and rakes prior to the application of roofing shingles. Apply directly on the wood deck at the eaves and over the underlay along the rakes. Extend back from the edge of the deck not more than 3 inches and secure with compatible nails spaced not more than 10 inches on center along upper edge.

3.1.13 Downspouts

Space supports for downspouts according to the manufacturer's recommendation for the masonry or steel substrate. Types, shapes and sizes are indicated. Provide complete including elbows and offsets.

Provide downspouts in approximately 10 foot lengths. Provide end joints to telescope not less than 1/2 inch and lock longitudinal joints. Provide gutter outlets with wire ball strainers for each outlet. Provide strainers to fit tightly into outlets and be of the same material used for gutters. Keep downspouts not less than one inch away from walls. Fasten to the walls at top, bottom, and at an intermediate point not to exceed 5 feet on center with leader straps or concealed rack-and-pin type fasteners. Form straps and fasteners of metal compatible with the downspouts.

3.1.13.1 Terminations

Neatly fit into the drainage connection the downspouts terminating in drainage lines and fill the joints with a portland cement mortar cap sloped away from the downspout. Provide downspouts terminating in splash blocks with elbow-type fittings. Provide splash pans as specified.

3.1.14 Flashing for Roof Drains

Provide a 30 inches square sheet indicated. Taper insulation to drain from 24 inches out. Set flashing on finished felts in a full bed of asphalt roof cement, ASTM D4586/D4586M . Heavily coat the drain flashing ring with asphalt roof cement. Clamp the roof membrane, flashing sheet, and stripping felt in the drain clamping ring. Secure clamps so that felts and drain flashing are free of wrinkles and folds. Retrofit roof drains must conform to ANSI/SPRI RD-1 .

3.1.15 Scuppers

Extend the scupper liner through and project outside of, the wall it penetrates to form a bottom drip edge against the face of the wall. Fold outside edges under 1/2 inch on all sides. Join the top and sides of the lining on the roof deck side to a closure flange by a locked and soldered

SECTION 07 60 00 Page 11 joint. Join the bottom edge by a locked and soldered joint to the closure flange, where required, form with a ridge to act as a gravel stop around the scupper inlet. Provide surfaces to receive the scupper lining and coat with bituminous plastic cement.

3.1.16 Conductor Heads

Set the depth of the top opening equal to two-thirds of the width or the conductor head. Flat-lock solder seams. Where conductor heads are used in conjunction with scuppers, set the conductor a minimum of 2 inches wider than the scupper. Attach conductor heads to the wall with masonry fasteners. Securely fasten screens to heads.

3.1.17 Open Valley Flashing

Provide valley flashing free of longitudinal seams, of width sufficient to extend not less than 6 inches under the roof covering on each side.

Provide a 1/2 inch fold on each side of the valley flashing. Lap the sheets not less than 6 inches in the direction of flow and secure to roofing construction with cleats attached to the fold on each side. Nail the tops of sheets to roof sheathing. Space the cleats not more than 12 inches on center. Provide exposed flashing not less than 4 inches in width at the top and increase one inch in width for each additional 8 feet in length. Where the slope of the valley is 4.5 inches or less per foot, or the intersecting roofs are on different slopes, provide an inverted V-joint, one inch high, along the centerline of the valley; and extend the edge of the valley sheets 8 inches under the roof covering on each side.

3.1.18 Flashing at Wall Openings

Install pan flashing in the rough opening sill at all penetrations in the exterior wall assemblies, such as windows, louvers, storefronts and curtain walls. Pan sill flashing must have end dams at both jambs a minimum of 2 in high and a rear dam of 2 in high. Flashing must comply with ASTM E2112 and SMACNA 1793.

3.1.19 Sheet Metal Covering on Flat, Sloped, or Curved Surfaces

Except as specified or indicated otherwise, cover and flash all minor flat, sloped, or curved surfaces such as crickets, bulkheads, dormers and small decks with metal sheets of the material used for flashing; maximum size of sheets, 16 by 18 inches. Fasten sheets to sheathing with metal cleats. Lock seams and solder. Lock aluminum seams as recommended by aluminum manufacturer. Provide an underlayment of roofing felt for all sheet metal covering.

3.1.20 Expansion Joints

Provide expansion joints for roofs, walls, and floors as indicated.

Provide evenly spaced joints. Provide an additional joint where the distance between the last expansion joint and the end of the continuous run is more than half the required interval spacing. Conform to the requirements of Table I.

3.1.20.1 Roof Expansion Joints

Consist of curb with wood nailing members on each side of joint, bituminous base flashing, metal counterflashing, and metal joint cover.

Bituminous base flashing is specified in Roofing Section. Provide

SECTION 07 60 00 Page 12 counterflashing as specified in paragraph COUNTERFLASHING, except as follows: Provide counterflashing with vertical leg of suitable depth to enable forming into a horizontal continuous cleat. Secure the inner edge to the nailing member. Make the outer edge projection not less than one inch for flashing on one side of the expansion joint and be less than the width of the expansion joint plus one inch for flashing on the other side of the joint. Hook the expansion joint cover over the projecting outer edges of counterflashing. Provide roof joint with a joint cover of the width indicated. Hook and lock one edge of the joint cover over the shorter projecting flange of the continuous cleat, and the other edge hooked over and loose locked with the longer projecting flange. Joints are specified in Table II.

3.1.20.2 Floor and Wall Expansion Joints

Provide U-shape with extended flanges for expansion joints in concrete and masonry walls and in floor slabs.

3.1.21 Flashing at Roof Penetrations and Equipment Supports

Provide metal flashing for all pipes, ducts, and conduits projecting through the roof surface and for equipment supports, guy wire anchors, and similar items supported by or attached to the roof deck.

3.1.22 Single Pipe Vents

See Table I, footnote (d). Set flange of sleeve in bituminous plastic cement and nail 3 inches on center. Bend the top of sleeve over and extend down into the vent pipe a minimum of 2 inches. For long runs or long rises above the deck, where it is impractical to cover the vent pipe with lead, use a two-piece formed metal housing. Set metal housing with a metal sleeve having a 4 inches roof flange in bituminous plastic cement and nailed 3 inches on center. Extend sleeve a minimum of 8 inches above the roof deck and lapped a minimum of 3 inches by a metal hood secured to the vent pipe by a draw band. Seal the area of hood in contact with vent pipe with an approved sealant.

3.1.23 Stepped Flashing

Provide stepped flashing where sloping roofs surfaced with shingles abut vertical surfaces. Place separate pieces of base flashing in alternate shingle courses.

3.1.24 Copings

Provide coping with locked and soldered seam. Terminate outer edges in edge strips. Install with sealed lap joints cover plate joints as indicated.

3.1.25 Through Wall Flashing

Provide through wall flashing as required in the applicable wall system Sections.

3.2 PAINTING

Touch ups in the field may be applied only after metal substrates have been cleaned and pretreated in accordance with manufacturer's written instructions and products.

SECTION 07 60 00 Page 13

Field-paint dissimilar sheet metals in contact to separate and deter galvanic interactions.

3.2.1 Aluminum Surfaces

Clean with solvent and apply one coat of zinc-molybdate primer and one coat of aluminum paint.

3.3 CLEANING

Clean exposed sheet metal work at completion of installation. Remove grease and oil films, handling marks, contamination from steel wool, fittings and drilling debris, and scrub-clean. Free the exposed metal surfaces of dents, creases, waves, scratch marks, and solder or weld marks.

3.4 REPAIRS TO FINISH

Scratches, abrasions, and minor surface defects of finish may be repaired in accordance with the manufacturer's printed instructions and as approved. Repair damaged surfaces caused by scratches, blemishes, and variations of color and surface texture. Replace items which cannot be repaired.

3.5 FIELD QUALITY CONTROL

Establish and maintain a Quality Control Plan for sheet metal used in conjunction with roofing to assure compliance of the installed sheet metalwork with the Contract requirements. Remove work that is not in compliance with the Contract and replace or correct. Include quality control, but not be limited to, the following:

a. Observation of environmental conditions; number and skill level of sheet metal workers; condition of substrate.

b. Verification that specified material is provided and installed.

c. Inspection of sheet metalwork, for proper size(s) and thickness(es), fastening and joining, and proper installation.

3.5.1 Procedure

Submit for approval prior to start of roofing work. Include a checklist of points to be observed. Document the actual quality control observations and inspections. Provide a copy of the documentation to the Contracting Officer at the end of each day.

SECTION 07 60 00 Page 14

TABLE I. SHEET METAL WEIGHTS, THICKNESSES, AND GAGES

Sheet Metal Items Aluminum, inch Stainless Steel, inch

Zinc-Coated Steel, U.S. Std. Gage

Building Expansion Joints

Cover .032 .015 24

Waterstop-bellows or flanged, U-type.

- .015 -

Covering on minor flat, pitched or curved surfaces

.040 .018 -

Downspouts and leaders .032 .015 24

Downspout clips and anchors .040 clip .125 anchor

Downspout straps, 2-inch .060 .050 -

Conductor heads .032 .015 -

Scupper lining .032 .015 -

Strainers, wire diameter or gage

.144 diameter .109 diameter

Flashings:

Base .040 .018 24

Cap (Counter-flashing) .032 .015 26

Stepped .032 .015 -

Valley .032 .015 -

Roof drain

Pipe vent sleave (d)

Coping - - -

Gravel stops and fascia:

Extrusions .075 - -

SECTION 07 60 00 Page 15

TABLE I. SHEET METAL WEIGHTS, THICKNESSES, AND GAGES

Sheet Metal Items Aluminum, inch Stainless Steel, inch

Zinc-Coated Steel, U.S. Std. Gage

Edge strip .050 .025 -

TABLE II. SHEET METAL JOINTS

TYPE OF JOINT

Item Designation Zinc-Coated Steel and Stainless Steel

Aluminum Remarks

Joint cap for building expansion seam, cleated joint at roof

1.25 inch single lock, standing seam, cleated

1.25 inch single lock, standing

Flashings

Base One inch 3 inch lap for expansion joint

One inch flat locked, soldered;

sealed; 3 inch lap for expansion joint

Aluminum manufacturer's recommended hard setting sealant for locked aluminum joints. Fill each metal expansion joint with a joint sealing compound.

Cap-in reglet 3 inch lap 3 inch lap Seal groove with joint sealing compound.

Reglets Butt joint -- Seal reglet groove with joint sealing compound.

SECTION 07 60 00 Page 16

TABLE II. SHEET METAL JOINTS

TYPE OF JOINT

Item Designation Zinc-Coated Steel and Stainless Steel

Aluminum Remarks

Eave One inch flat locked, cleated. One inch loose locked, sealed expansion joint, cleated.

One inch flat locked, locked, cleated one inch loose locked, sealed expansion joints, cleated

Same as base flashing.

Stepped 3 inch lap 3 inch lap --

Valley 6 inch lap cleated 6 inch lap cleated --

Edge strip Butt Butt --

Gravel stops:

Extrusions -- Butt with 1/2 inch space

Use sheet flashing beneath and a cover plate

Sheet, smooth Butt with 1/4 inch space

Butt with 1/4 inch space

Use sheet flashing backup plate.

Sheet, corrugated Butt with 1/4 inch space

Butt with 1/4 inch space

Use sheet flashing beneath and a cover plate or a combination unit

Gutters 1.5 inch lap, riveted and soldered

One inch flat locked riveted and sealed

Aluminum producers recommended hard setting sealant for locked aluminum joints.

(a) Provide a 3 inch lap elastomeric flashing with manufacturer's recommended sealant.

(b) Seal Polyvinyl chloride reglet with manufacturer's recommended sealant.

-- End of Section --

SECTION 07 60 00 Page 17

THIS PAGE INTENTIONALLY LEFT BLANK

SECTION 07 60 00 Page 18

07 60 00 - FLASHING AND SHEET METAL
PART 1 GENERAL
1.1 REFERENCES
1.2 GENERAL REQUIREMENTS
1.2.1 General Material Requirements
1.2.2 Additional Wind Uplift Requirements
1.3 SUBMITTALS
1.4 MISCELLANEOUS REQUIREMENTS
1.4.1 Product Data
1.4.2 Finish Samples
1.4.3 Operation and Maintenance Data

1.5 DELIVERY, HANDLING, AND STORAGE

PART 2 PRODUCTS
2.1 RECYCLED CONTENT
2.2 MATERIALS
2.2.1 Exposed Sheet Metal Items
2.2.2 Drainage
2.2.3 Steel Sheet, Zinc-Coated Galvanized
2.2.4 Zinc Sheet and Strip
2.2.5 Stainless Steel
2.2.6 Aluminum Alloy Sheet and Plate
2.2.7 Finishes
2.2.7.1 Warranty on Finishes
2.2.8 Cool Roof Finishes
2.2.9 Aluminum Alloy, Extruded Bars, Rods, Shapes, and Tubes
2.2.10 Solder
2.2.11 Reglets
2.2.11.1 Metal Reglets
2.2.12 Scuppers
2.2.13 Conductor Heads
2.2.14 Copings
2.2.15 Bituminous Plastic Cement
2.2.16 Roofing Felt
2.2.17 Asphalt Primer
2.2.18 Fasteners
2.3 FIRE RATED EXPANSION JOINTS
2.4 BELLOW TYPE BUILDING EXPANSION JOINT COVER
PART 3 EXECUTION
3.1 INSTALLATION
3.1.1 Cleats
3.1.2 Bolts, Rivets, and Screws
3.1.3 Seams
3.1.3.1 Flat-lock Seams
3.1.3.2 Lap Seams
3.1.3.3 Loose-Lock Expansion Seams
3.1.3.4 Standing Seams
3.1.3.5 Flat Seams
3.1.4 Soldering
3.1.4.1 Edges
3.1.5 Welding and Mechanical Fastening
3.1.5.1 Welding of Aluminum
3.1.5.2 Mechanical Fastening of Aluminum
3.1.6 Protection from Contact with Dissimilar Materials
3.1.6.1 Aluminum
3.1.6.2 Metal Surfaces
3.1.6.3 Wood or Other Absorptive Materials
3.1.7 Expansion and Contraction
3.1.8 Base Flashing
3.1.9 Counterflashing
3.1.10 Metal Reglets
3.1.11 Gravel Stops and fascia
3.1.11.1 Edge Strip
3.1.11.2 Joints
3.1.12 Metal Drip Edges
3.1.13 Downspouts
3.1.13.1 Terminations
3.1.14 Flashing for Roof Drains
3.1.15 Scuppers
3.1.16 Conductor Heads
3.1.17 Open Valley Flashing
3.1.18 Flashing at Wall Openings
3.1.19 Sheet Metal Covering on Flat, Sloped, or Curved Surfaces
3.1.20 Expansion Joints
3.1.20.1 Roof Expansion Joints
3.1.20.2 Floor and Wall Expansion Joints
3.1.21 Flashing at Roof Penetrations and Equipment Supports
3.1.22 Single Pipe Vents
3.1.23 Stepped Flashing
3.1.24 Copings
3.1.25 Through Wall Flashing
3.2 PAINTING
3.2.1 Aluminum Surfaces
3.3 CLEANING
3.4 REPAIRS TO FINISH
3.5 FIELD QUALITY CONTROL
3.5.1 Procedure

File details come from the government source that posted it. Updated .