This document provides condition assessment guidance for various building equipment and systems. It includes a table of contents listing over 50 meter groups with hyperlinks to individual tabs containing descriptions and condition rating criteria. The condition ratings are green (minimal issues), amber (noticeable problems but functional), and red (significant problems impacting operation). Meter groups cover equipment such as doors, elevators, chillers, boilers, cooling towers, fans, pumps, and electrical systems. Condition meters include components, controls, enclosures, piping and more. This detailed equipment assessment guidance supports ongoing facility management and capital planning activities.
View the file
Other files
Show 40 more
Latest 50 of 52 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Table of Contents
| ATTACHMENT J-1501000-03 | |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE | |
| METER GROUP | HYPERLINK TO EXCEL TAB |
| B2030410 - Overhead Doors | B2030410-Overhead Doors |
| B2030901 - Hangar Doors | B2030901-Hangar Doors |
| D1010110 - Hydraulic Elevators | D1010110-Hydraulic Elevators |
| D1010140 - Traction Geared Elevators | D1010140-Traction Geared Elev |
| D1010150 - Traction Gearless Elevators | D1010150-Traction Gearless Elev |
| D1010901 – Lifts | D1010901 – Lifts |
| D1020110 - Escalators | D1020110-Escalators |
| D1090902 - Cranes and Hoists | D1090902-Cranes and Hoists |
| D3020130 - Boiler, Cast Iron, Hot Water, Gas | D3020130-Boiler,CI,HW,Gas |
| D3020134 - Boiler, Cast Iron, Steam, Gas | D3020134-Boiler,CI,Steam,Gas |
| D3020136 - Boiler, Cast Iron, Hot Water, Gas/Oil | D3020136-Boiler,CI,HW,Gas-Oil |
| D3020138 - Boiler, Cast Iron, Steam, Gas/Oil | D3020138-Boiler,CI,Steam,GasOil |
| D3020901 - Boiler, Cast Iron, HW, Oil | D3020901-Boiler,CI,HW,Oil |
| D3020902 - Boiler, Cast Iron, Steam, Oil | D3020902-Boiler,CI,Steam,Oil |
| D3030130 - Chiller, Reciprocating, Water Cooled | D3030130-Chiller,Recip,WC |
| D3030135 - Chiller, Reciprocating, Air Cooled | D3030135-Chiller,Recip,AC |
| D3030140 - Chiller, Centrifugal, Water Cooled | D3030140-Chiller,Centrifugal,WC |
| D3030145 - Chiller, Gas Absorption, Water Cooled | D3030145-Chiller,Gas Absorp,WC |
| D3030150 - Chiller, Steam Absorption, Water Cooled | D3030150-Chiller,Stm Absorp,WC |
| D3030310 - Cooling Tower, Galvanized | D3030310-CoolingTower, Galv |
| D3030320 - Cooling Tower, Fiberglass | D3030320-CoolingTower,Fiberglas |
| D3030330 - Cooling Tower, Stainless Steel | D3030330-CoolingTower,St Steel |
| D3030902 - Condenser, DX, Evaporative | D3030902-Condenser,DX,Evap |
| D3030903 - Packaged DX Refrigerant System | D3030903-Packaged DX Refrig Sys |
| D3040106 - Air Handling Unit, Field Fabricated | D3040106-AH Unit, Field Fab |
| D3040110 - Air Handling Unit, Central Station | D3040110-AH Unit,Central Sta |
| D3040114 - Air Handling Unit, Rooftop | D3040114-AH Unit,Rooftop |
| D3040220 - Fan System, Centrifugal In-Line | D3040220-Fan Sys, Cent In Line |
| D3040230 - Fan System, Utility Set | D3040230-Fan Sys, Utility Set |
| D3040240 - Fan System, Roof Exhaust | D3040240-Fan Sys, Roof Exhaust |
| D3040330 - Circulating Pump, End Suction | D3040330-Circ Pump,End Suct |
| D3040340 - Circulating Pump, Double Suction | D3040340-Circ Pump,Dbl Suct |
| D3040610 - Heat Exchanger, Plate Type | D3040610-Heat Exch,PlateType |
| D3040620 - Heat Exchanger, Shell Tube | D3040620-Heat Exch,Shell Tube |
| D3050170 - Split Systems With Air Cooled Condensing Units | D3050170-SplitSys,AC Condensing |
| D3050185 - Computer Room Cooling Units | D3050185-ComputerRoom CoolUnts |
| D3050201 - Packaged A/C, Air Cooled, Elec Heat | D3050201-Pkg AC, AirCool ElecHt |
| D3050203 - Packaged A/C, Air Cooled, HW Heat | D3050203-Pkg AC, AirCool HW Ht |
| D3050210 - Packaged A/C, Water Cooled, Elec Heat | D3050210-Pkg AC,WaterCool,EleHt |
| D3050220 - Packaged A/C, Water Cooled, HW Heat | D3050220-Pkg AC,WaterCool,HWHt |
| D3050255 - Thru-Wall A/C Unit | D3050255-Thru-Wall AC Unit |
| D3050260 - Thru-Wall Heat Pump | D3050260-Thru-Wall Heat Pump |
| D5010240 - Switchgear | D5010240-Switchgear |
| D5010901 - Transfer Switch | D5010901-Transfer Switch |
| D5010902 - Transformer | D5010902-Transformer |
| D5010905 - Capacitor Bank | D5010905-Capacitor Bank |
| D5010906 - Panelboards | D5010906-Panelboards |
| D5030910 - Communication/Alarm Systems | D5030910-Comm Alarm Systems |
| D5090210 - Generators | D5090210-Generators |
| D5090901 - Emergency Lighting | D5090901-Emergency Lighting |
| D5090904 - Uninterruptible Power Supply | D5090904-UPS |
B2030410-Overhead Doors
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| B2030410 - Overhead Doors | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Door | GREEN: Door has minimal damage and corrosion, is square and securely fastened | |
| AMBER: Door has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety | ||
| RED: Door has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation | ||
| CR-1000 - Record the condition of the Guides | GREEN: Guides/Stops/Rollers/Pulleys show no signs of wear or damage, and are properly secured and aligned | |
| AMBER: Guides/Stops/Rollers/Pulleys show slight wear, and/or may be slightly loose or misaligned | ||
| RED: Guides/Stops/Rollers/Pulleys have noticeable damage or wear, and are insecurely fastened and/or misaligned | ||
| CR-1000 - Record the condition of the Motor | GREEN: Motor operates properly, free of excessive noise/vibration, or overheating | |
| AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance | ||
| RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired |
Return to: Table of Contents
B2030901-Hangar Doors
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| B2030901 - Hangar Doors | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Brakes | GREEN: Brakes have minimal wear | |
| AMBER: Brakes have noticeable wear, may exhibit unusual noise, but are still operational | ||
| RED: Brakes have significant wear, excessive noise, or may not function properly | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Door | GREEN: Door has minimal damage and corrosion, is square and securely fastened | |
| AMBER: Door has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety | ||
| RED: Door has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation | ||
| CR-1000 - Record the condition of the Guides | GREEN: Guides/Stops/Rollers/Pulleys show no signs of wear or damage, and are properly secured and aligned | |
| AMBER: Guides/Stops/Rollers/Pulleys show slight wear, and/or may be slightly loose or misaligned | ||
| RED: Guides/Stops/Rollers/Pulleys have noticeable damage or wear, and are insecurely fastened and/or misaligned | ||
| CR-1000 - Record the condition of the Motor | GREEN: Motor operates properly, free of excessive noise/vibration, or overheating | |
| AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance | ||
| RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired |
Return to: Table of Contents
D1010110-Hydraulic Elevators
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D1010110 - Hydraulic Elevators | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Car Assembly | GREEN: Car Supporting Platform/Frame has no damage, is structurally sound | |
| AMBER: Car Supporting Platform/Frame has noticeable damage or corrosion, but no loss of structural integrity | ||
| RED: Car Supporting Platform/Frame has significant damage and corrosion, structural integrity significantly impaired | ||
| CR-1000 - Record the condition of the Car Operating Panel (COP) | GREEN: Car Operating Panel/Indicator has minimal damage and corrosion, fully operational | |
| AMBER: Car Operating Panel/Indicator has noticeable damage and corrosion, still operational | ||
| RED: Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired | ||
| CR-1000 - Record the condition of the Door Assembly | GREEN: Car Doors have minimal damage or wear, door operation is smooth | |
| AMBER: Car Doors have noticeable damage or wear, doors are operational but may need adjustments | ||
| RED: Car Doors have significant damage or corrosion, doors are operationally impaired | ||
| CR-1000 - Record the condition of the Elevator Control | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Lifting Assembly/Machine | GREEN: Hydraulic Piston Well has minimal damage, deterioration, no cracks or leaks, fully secured | |
| AMBER: Hydraulic Piston Well has noticeable damage, deterioration, but no cracks or leaks, still operational | ||
| RED: Hydraulic Piston Well has significant damage, deterioration, cracks or leaks, operationally impaired |
Return to: Table of Contents
D1010140-Traction Geared Elev
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D1010140 - Traction Geared Elevators | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Car Assembly | GREEN: Car Supporting Platform/Frame has no damage, is structurally sound | |
| AMBER: Car Supporting Platform/Frame has noticeable damage or corrosion, but no loss of structural integrity | ||
| RED: Car Supporting Platform/Frame has significant damage and corrosion, structural integrity significantly impaired | ||
| CR-1000 - Record the condition of the Car Operating Panel (COP) | GREEN: Car Operating Panel/Indicator has minimal damage and corrosion, fully operational | |
| AMBER: Car Operating Panel/Indicator has noticeable damage and corrosion, still operational | ||
| RED: Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired | ||
| CR-1000 - Record the condition of the Car Safeties | GREEN: Safety Buffers have minimal deterioration or damage, fully operational | |
| AMBER: Safety Buffers have noticeable deterioration or damage, still operational | ||
| RED: Safety Buffers have significant deterioration or damage, operationally impaired | ||
| CR-1000 - Record the condition of the Door Assembly | GREEN: Car Doors have minimal damage or wear, door operation is smooth | |
| AMBER: Car Doors have noticeable damage or wear, doors are operational but may need adjustments | ||
| RED: Car Doors have significant damage or corrosion, doors are operationally impaired | ||
| CR-1000 - Record the condition of the Elevator Control | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Hoisting Machine | GREEN: Motor operates properly, free of excessive noise/vibration, or overheating | |
| AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance | ||
| RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired | ||
| CR-1000 - Record the condition of the Suspension Means | GREEN: Anchors/Cables/Tie Backs show no damage, deterioration and corrosion, fully secure | |
| AMBER: Anchors/Cables/Tie Backs show minimal wear or deterioration, but are still fully secure and stable | ||
| RED: Anchors/Cables/Tie Backs have noticeable damage, deterioration and/or corrosion, loosely secured or unstable, may jeopardize safety |
Return to: Table of Contents
D1010150-Traction Gearless Elev
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D1010150 - Traction Gearless Elevators | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Car Assembly | GREEN: Car Supporting Platform/Frame has no damage, is structurally sound | |
| AMBER: Car Supporting Platform/Frame has noticeable damage or corrosion, but no loss of structural integrity | ||
| RED: Car Supporting Platform/Frame has significant damage and corrosion, structural integrity significantly impaired | ||
| CR-1000 - Record the condition of the Car Operating Panel (COP) | GREEN: Car Operating Panel/Indicator has minimal damage and corrosion, fully operational | |
| AMBER: Car Operating Panel/Indicator has noticeable damage and corrosion, still operational | ||
| RED: Car Operating Panel/Indicator has significant damage and corrosion, operationally impaired | ||
| CR-1000 - Record the condition of the Car Safeties | GREEN: Safety Buffers have minimal deterioration or damage, fully operational | |
| AMBER: Safety Buffers have noticeable deterioration or damage, still operational | ||
| RED: Safety Buffers have significant deterioration or damage, operationally impaired | ||
| CR-1000 - Record the condition of the Door Assembly | GREEN: Car Doors have minimal damage or wear, door operation is smooth | |
| AMBER: Car Doors have noticeable damage or wear, doors are operational but may need adjustments | ||
| RED: Car Doors have significant damage or corrosion, doors are operationally impaired | ||
| CR-1000 - Record the condition of the Elevator Control | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Hoisting Machine | GREEN: Motor operates properly, free of excessive noise/vibration, or overheating | |
| AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance | ||
| RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired | ||
| CR-1000 - Record the condition of the Suspension Means | GREEN: Anchors/Cables/Tie Backs show no damage, deterioration and corrosion, fully secure | |
| AMBER: Anchors/Cables/Tie Backs show minimal wear or deterioration, but are still fully secure and stable | ||
| RED: Anchors/Cables/Tie Backs have noticeable damage, deterioration and/or corrosion, loosely secured or unstable, may jeopardize safety |
Return to: Table of Contents
D1010901 – Lifts
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D1010901 – Lifts | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Drive Assembly | GREEN: Motor operates properly, free of excessive noise/vibration, or overheating | |
| AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance | ||
| RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired | ||
| CR-1000 - Record the condition of the Lift Frame | GREEN: Platform has little to no damage or deterioration, and is structurally sound | |
| AMBER: Platform has noticeable damage or deterioration, but still structurally sound | ||
| RED: Platform has significant damage or deterioration, may be loose or unstable |
Return to: Table of Contents
D1020110-Escalators
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D1020110 - Escalators | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Comb Plates | GREEN: Comb Plates have minimal deterioration and damage, and are not loose or displaced | |
| AMBER: Comb Plates have noticeable deterioration and damage, but are not loose or displaced | ||
| RED: Comb Plates have significant deterioration and damage, may be noticeably loose, displaced, or misaligned | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Drive Assembly | GREEN: Motor operates properly, free of excessive noise/vibration, or overheating | |
| AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance | ||
| RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired | ||
| CR-1000 - Record the condition of the Handrails | GREEN: Handrails have minimal damage or corrosion, and are fully secured | |
| AMBER: Handrails have noticeable damage or corrosion, slightly loose but still operational | ||
| RED: Handrails have significant damage or corrosion, noticeable loose or missing | ||
| CR-1000 - Record the condition of the Lift Frame | GREEN: Platform has little to no damage or deterioration, and is structurally sound | |
| AMBER: Platform has noticeable damage or deterioration, but still structurally sound | ||
| RED: Platform has significant damage or deterioration, may be loose or unstable | ||
| CR-1000 - Record the condition of the Step Risers/Tread | GREEN: Step Risers/Tread have minimal damage or deterioration, fully secured and aligned | |
| AMBER: Step Risers/Tread have noticeable damage or deterioration, are mostly secure and operational | ||
| RED: Step Risers/Tread have significant deterioration, damage, corrosion, or are loose or misaligned |
Return to: Table of Contents
D1090902-Cranes and Hoists
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D1090902 - Cranes and Hoists | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Brakes | GREEN: Brakes have minimal wear | |
| AMBER: Brakes have noticeable wear, may exhibit unusual noise, but are still operational | ||
| RED: Brakes have significant wear, excessive noise, or may not function properly | ||
| CR-1000 - Record the condition of the Chains/Hooks | GREEN: Hook has minimal damage or wear, and is fully secured | |
| AMBER: Hook has noticeable damage or wear, but is still securely fastened | ||
| RED: Hook has significant damage, connections not secure | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Crane Unit | GREEN: Crane Unit shows minimal signs of wear, no loose components, structurally sound, fully operational | |
| AMBER: Crane Unit shows noticeable signs of damage or wear, but no loose or missing components, and still operational | ||
| RED: Crane Unit shows significant signs of damage or wear, may have missing or loose components, comprised structural integrity, or is operationally impaired | ||
| CR-1000 - Record the condition of the Guide Wheels | GREEN: Guide Wheels show little to no wear or damage, are securely fastened, and fully functional | |
| AMBER: Guide Wheels have noticeable wear, may have slight damage, but are secure and still operational | ||
| RED: Guide Wheels have significant damage, may be loose, displaced, missing, or operationally impaired | ||
| CR-1000 - Record the condition of the Hooklift Motor | GREEN: Motor operates properly, free of excessive noise/vibration, or overheating | |
| AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance | ||
| RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired | ||
| CR-1000 - Record the condition of the Structure | GREEN: Structural Frame has minimal damage and corrosion, is square and securely fastened | |
| AMBER: Structural Frame has noticeable damage and corrosion, may be slightly displaced, but does not affect door operation or safety | ||
| RED: Structural Frame has significant damage and/or corrosion, noticeably displaced, and may be structurally unsound or affect door operation | ||
| CR-1000 - Record the condition of the Trolley Drive | GREEN: Trolley Drive has minimal to no damage, operation is smooth, fully functional | |
| AMBER: Trolley Drive has noticeable damage, wear, may require adjustments but is fully functional | ||
| RED: Trolley Drive has significant damage or wear, operation is significantly impaired |
Return to: Table of Contents
D3020130-Boiler,CI,HW,Gas
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3020130 - Boiler, Cast Iron, Hot Water, Gas | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Burner Assembly | GREEN: Burners have minimal damage or corrosion, but is fully operational | |
| AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound | ||
| RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Firebox/Fire Tubes | GREEN: Firebox has minimal damage or corrosion | |
| AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes | ||
| RED: Firebox has significant damage or corrosion, cracks or holes may be present | ||
| CR-1000 - Record the condition of the Flue | GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational | |
| AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational | ||
| RED: Flue has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired | ||
| CR-1000 - Record the condition of the Fuel System | GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational | |
| AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational | ||
| RED: Fuel System has significant damage or corrosion, significant leaking, and/or is operationally impaired | ||
| CR-1000 - Record the condition of the Piping/Fittings/Valves | GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion | |
| AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking | ||
| RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs | ||
| CR-1000 - Record the condition of the Pressure Vessel | GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure | |
| AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure | ||
| RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured | ||
| CR-1000 - Record the condition of the Wiring/Connections | GREEN: Wiring is protected/insulated and connections are secure | |
| AMBER: Wiring is may be frayed but not exposed, connections are generally secure, no noticeable risk of unintentional grounding | ||
| RED: Wiring is significantly deteriorated or frayed, connection(s) are loose, or risk of unintentional grounding |
Return to: Table of Contents
D3020134-Boiler,CI,Steam,Gas
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3020134 - Boiler, Cast Iron, Steam, Gas | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Burner Assembly | GREEN: Burners have minimal damage or corrosion, but is fully operational | |
| AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound | ||
| RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Firebox/Fire Tubes | GREEN: Firebox has minimal damage or corrosion | |
| AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes | ||
| RED: Firebox has significant damage or corrosion, cracks or holes may be present | ||
| CR-1000 - Record the condition of the Pipes/Fittings/Valves | GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion | |
| AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking | ||
| RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs | ||
| CR-1000 - Record the condition of the Pressure Vessel | GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure | |
| AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure | ||
| RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured |
Return to: Table of Contents
D3020136-Boiler,CI,HW,Gas-Oil
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3020136 - Boiler, Cast Iron, Hot Water, Gas/Oil | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Burner Assembly | GREEN: Burners have minimal damage or corrosion, but is fully operational | |
| AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound | ||
| RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Firebox/Fire Tubes | GREEN: Firebox has minimal damage or corrosion | |
| AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes | ||
| RED: Firebox has significant damage or corrosion, cracks or holes may be present | ||
| CR-1000 - Record the condition of the Fuel System | GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational | |
| AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational | ||
| RED: Fuel System has significant damage or corrosion, significant leaking, and/or is operationally impaired | ||
| CR-1000 - Record the condition of the Piping/Fittings/Valves | GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion | |
| AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking | ||
| RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs | ||
| CR-1000 - Record the condition of the Pressure Vessel | GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure | |
| AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure | ||
| RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured | ||
| CR-1000 - Record the condition of the Wiring/Connections | GREEN: Wiring is protected/insulated and connections are secure | |
| AMBER: Wiring is may be frayed but not exposed, connections are generally secure, no noticeable risk of unintentional grounding | ||
| RED: Wiring is significantly deteriorated or frayed, connection(s) are loose, or risk of unintentional grounding |
Return to: Table of Contents
D3020138-Boiler,CI,Steam,GasOil
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3020138 - Boiler, Cast Iron, Steam, Gas/Oil | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Burner Assembly | GREEN: Burners have minimal damage or corrosion, but is fully operational | |
| AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound | ||
| RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Feed Water System | GREEN: Feed Water System has no damage or leaks, fully operational | |
| AMBER: Feed Water System has noticeable damage or corrosion, may have slight leaks but still operational | ||
| RED: Feed Water System has significant damage or corrosion, noticeable leaks, and does not function properly | ||
| CR-1000 - Record the condition of the Firebox/Fire Tubes | GREEN: Firebox has minimal damage or corrosion | |
| AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes | ||
| RED: Firebox has significant damage or corrosion, cracks or holes may be present | ||
| CR-1000 - Record the condition of the Flue | GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational | |
| AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational | ||
| RED: Flue has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired | ||
| CR-1000 - Record the condition of the Piping/Fittings/Valves | GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion | |
| AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking | ||
| RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs | ||
| CR-1000 - Record the condition of the Pressure Vessel | GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure | |
| AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure | ||
| RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured |
Return to: Table of Contents
D3020901-Boiler,CI,HW,Oil
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3020901 - Boiler, Cast Iron, HW, Oil | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Burner Assembly | GREEN: Burners have minimal damage or corrosion, but is fully operational | |
| AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound | ||
| RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Firebox/Fire Tubes | GREEN: Firebox has minimal damage or corrosion | |
| AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes | ||
| RED: Firebox has significant damage or corrosion, cracks or holes may be present | ||
| CR-1000 - Record the condition of the Flue | GREEN: Flue has minimal damage, is secured and aligned properly, and fully operational | |
| AMBER: Flue has noticeable damage and corrosion, may be slightly loose or misaligned, but still operational | ||
| RED: Flue has significant damage and corrosion, noticeably loose, misaligned, or missing, and/or operationally impaired | ||
| CR-1000 - Record the condition of the Fuel System | GREEN: Little to no damage or corrosion, secure connections, no leaks, fully operational | |
| AMBER: Fuel System has noticeable damage or corrosion, but free of leaks, fully operational | ||
| RED: Fuel System has significant damage or corrosion, significant leaking, and/or is operationally impaired | ||
| CR-1000 - Record the condition of the Piping/Fittings/Valves | GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion | |
| AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking | ||
| RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs | ||
| CR-1000 - Record the condition of the Pressure Vessel | GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure | |
| AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure | ||
| RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured | ||
| CR-1000 - Record the condition of the Wiring/Connections | GREEN: Wiring is protected/insulated and connections are secure | |
| AMBER: Wiring is may be frayed but not exposed, connections are generally secure, no noticeable risk of unintentional grounding | ||
| RED: Wiring is significantly deteriorated or frayed, connection(s) are loose, or risk of unintentional grounding |
Return to: Table of Contents
D3020902-Boiler,CI,Steam,Oil
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3020902 - Boiler, Cast Iron, Steam, Oil | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Burner Assembly | GREEN: Burners have minimal damage or corrosion, but is fully operational | |
| AMBER: Burners have noticeable damage or corrosion, flame quality may need adjustment, but still operationally sound | ||
| RED: Burners have significant damage or corrosion, may be loose or displaced, improper flame, and is not operationally sound | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Firebox/Fire Tubes | GREEN: Firebox has minimal damage or corrosion | |
| AMBER: Firebox has noticeable damage or corrosion, but no cracks or holes | ||
| RED: Firebox has significant damage or corrosion, cracks or holes may be present | ||
| CR-1000 - Record the condition of the Pipes/Fittings/Valves | GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion | |
| AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking | ||
| RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs | ||
| CR-1000 - Record the condition of the Pressure Vessel | GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure | |
| AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure | ||
| RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured |
Return to: Table of Contents
D3030130-Chiller,Recip,WC
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3030130 - Chiller, Reciprocating, Water Cooled | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Compressor | GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational | |
| AMBER: Excessive noise, vibration, or overheating noticeable from compressor, but compressor is still functional | ||
| RED: Unacceptable noise, vibration, or overheating from compressor, significant damage, and/or operationally impaired | ||
| CR-1000 - Record the condition of the Condenser | GREEN: Minimal corrosion or fouling of the condenser/coils, no damage | |
| AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational | ||
| RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Enclosure | GREEN: Minimal damage and corrosion on Enclosure, fully secured | |
| AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose, or displaced | ||
| RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing | ||
| CR-1000 - Record the condition of the Evaporator | GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage | |
| AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational | ||
| RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired | ||
| CR-1000 - Record the condition of the Piping/Fittings/Valves | GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion | |
| AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking | ||
| RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs | ||
| CR-1000 - Record the condition of the Receiver Tank | GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure | |
| AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure | ||
| RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured |
Return to: Table of Contents
D3030135-Chiller,Recip,AC
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3030135 - Chiller, Reciprocating, Air Cooled | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Compressor | GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational | |
| AMBER: Excessive noise, vibration, or overheating noticeable from compressor, but compressor is still functional | ||
| RED: Unacceptable noise, vibration, or overheating from compressor, significant damage, and/or operationally impaired | ||
| CR-1000 - Record the condition of the Condenser | GREEN: Minimal corrosion or fouling of the condenser/coils, no damage | |
| AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational | ||
| RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired | ||
| CR-1000 - Record the condition of the Condenser Fan(s) Assembly | GREEN: Motor operates properly, free of excessive noise/vibration, or overheating | |
| AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance | ||
| RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Enclosure | GREEN: Minimal damage and corrosion on Enclosure, fully secured | |
| AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose, or displaced | ||
| RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing | ||
| CR-1000 - Record the condition of the Evaporator | GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage | |
| AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational | ||
| RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired | ||
| CR-1000 - Record the condition of the Pipes/Fittings/Valves | GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion | |
| AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking | ||
| RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs | ||
| CR-1000 - Record the condition of the Receiver Tank | GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure | |
| AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure | ||
| RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured | ||
| CR-1000 - Record the condition of the Wiring/Connections | GREEN: Wiring is protected/insulated and connections are secure | |
| AMBER: Wiring is may be frayed but not exposed, connections are generally secure, no noticeable risk of unintentional grounding | ||
| RED: Wiring is significantly deteriorated or frayed, connection(s) are loose, or risk of unintentional grounding |
Return to: Table of Contents
D3030140-Chiller,Centrifugal,WC
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3030140 - Chiller, Centrifugal, Water Cooled | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Centrifugal Motor | GREEN: Motor operates properly, free of excessive noise/vibration, or overheating | |
| AMBER: Motor exhibits unusual noise/vibration, but still operational, may require maintenance | ||
| RED: Motor exhibits excessive noise/vibration, overheating, and/or operation is significantly impaired | ||
| CR-1000 - Record the condition of the Compressor | GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational | |
| AMBER: Excessive noise, vibration, or overheating noticeable from compressor, but compressor is still functional | ||
| RED: Unacceptable noise, vibration, or overheating from compressor, significant damage, and/or operationally impaired | ||
| CR-1000 - Record the condition of the Condenser | GREEN: Minimal corrosion or fouling of the condenser/coils, no damage | |
| AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational | ||
| RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired | ||
| CR-1000 - Record the condition of the Controls/Sensors | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Enclosure | GREEN: Minimal damage and corrosion on Enclosure, fully secured | |
| AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose, or displaced | ||
| RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing | ||
| CR-1000 - Record the condition of the Evaporator | GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage | |
| AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational | ||
| RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired | ||
| CR-1000 - Record the condition of the Piping/Fittings/Valves | GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion | |
| AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking | ||
| RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs | ||
| CR-1000 - Record the condition of the Receiver Tank | GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure | |
| AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure | ||
| RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured |
Return to: Table of Contents
D3030145-Chiller,Gas Absorp,WC
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3030145 - Chiller, Gas Absorption, Water Cooled | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Absorber | GREEN: Absorber has minimal damage and corrosion, but no leaks | |
| AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational | ||
| RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired | ||
| CR-1000 - Record the condition of the Compressor | GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational | |
| AMBER: Excessive noise, vibration, or overheating noticeable from compressor, but compressor is still functional | ||
| RED: Unacceptable noise, vibration, or overheating from compressor, significant damage, and/or operationally impaired | ||
| CR-1000 - Record the condition of the Condenser | GREEN: Minimal corrosion or fouling of the condenser/coils, no damage | |
| AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational | ||
| RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Enclosure | GREEN: Minimal damage and corrosion on Enclosure, fully secured | |
| AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose, or displaced | ||
| RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing | ||
| CR-1000 - Record the condition of the Evaporator | GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage | |
| AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational | ||
| RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired | ||
| CR-1000 - Record the condition of the Heat Generator | GREEN: Heating Element has little to no damage or corrosion, and is fully operational | |
| AMBER: Heating Element has noticeable damage or corrosion, but still operational | ||
| RED: Heating Element has significant damage or corrosion, operationally impaired | ||
| CR-1000 - Record the condition of the Pipes/Fittings/Valves | GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion | |
| AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking | ||
| RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs | ||
| CR-1000 - Record the condition of the Receiver | GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure | |
| AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure | ||
| RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured |
Return to: Table of Contents
D3030150-Chiller,Stm Absorp,WC
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3030150 - Chiller, Steam Absorption, Water Cooled | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Absorber | GREEN: Absorber has minimal damage and corrosion, but no leaks | |
| AMBER: Absorber has noticeable damage and corrosion, but minimal leaks and is still operational | ||
| RED: Absorber has significant damage and corrosion, and noticeable leaks, operationally impaired | ||
| CR-1000 - Record the condition of the Compressor | GREEN: No excessive noise, vibration, or overheating from compressor, little to no damage and fully operational | |
| AMBER: Excessive noise, vibration, or overheating noticeable from compressor, but compressor is still functional | ||
| RED: Unacceptable noise, vibration, or overheating from compressor, significant damage, and/or operationally impaired | ||
| CR-1000 - Record the condition of the Condenser | GREEN: Minimal corrosion or fouling of the condenser/coils, no damage | |
| AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational | ||
| RED: Significant damage, corrosion or fouling of the condenser/coils, no damage, operationally impaired | ||
| CR-1000- Record the condition of the Controls | GREEN: Controls function properly | |
| AMBER: Controls need calibrating | ||
| RED: Controls are damaged and/or not operational | ||
| CR-1000 - Record the condition of the Enclosure | GREEN: Minimal damage and corrosion on Enclosure, fully secured | |
| AMBER: Noticeable damage/corrosion to Enclosure, Panels may be slightly detached, loose, or displaced | ||
| RED: Significant damage/corrosion to Enclosure, a number of panels are loose, displaced, or missing | ||
| CR-1000 - Record the condition of the Evaporator | GREEN: Minimal corrosion or fouling of the evaporator/coils, no damage | |
| AMBER: Minimal to noticeable signs of corrosion on coils, or coils are clogged, still operational | ||
| RED: Significant damage, corrosion or fouling of the evaporator/coils, operationally impaired | ||
| CR-1000 - Record the condition of the Heat Generator | GREEN: Heating Element has little to no damage or corrosion, and is fully operational | |
| AMBER: Heating Element has noticeable damage or corrosion, but still operational | ||
| RED: Heating Element has significant damage or corrosion, operationally impaired | ||
| CR-1000 - Record the condition of the Pipes/Fittings/Valves | GREEN: Piping/fittings free of leaks, all connections are tight, valves operate properly, insulation is in place, minimal corrosion | |
| AMBER: Piping/Fittings show noticeable signs of corrosion, missing or damaged insulation, but connections are tight and no leaking | ||
| RED: Piping/Fittings are damaged and leaking, valves are not functioning, significant internal scale and corrosion may lead to clogs | ||
| CR-1000 - Record the condition of the Receiver | GREEN: Tank has little to no damage or corrosion, no leaks, insulation is intact where applicable, stable and secure | |
| AMBER: Tank has some damage or corrosion, insulation may be mission, very minor leaks may be present, but overall holds its contents, is stable and secure | ||
| RED: Tank has noticeable damage, punctures, holes, and leaks, may be unstable or not fully secured |
Return to: Table of Contents
D3030310-CoolingTower, Galv
| ATTACHMENT J-1501000-04 |
| METER GROUP DESCRIPTIONS AND DIRECT CONDITION RATING GUIDANCE |
| D3030310 - Cooling Tower, Galvanized | ||
| Meter & Description | Direct Condition Rating Guidance | Condition |
| CR-1000 - Record the condition of the Basin/Sump | GREEN: Sump has minimal damage or corrosion, no leaking | |
| AMBER: Sump has noticeable damage or corrosion, but no leaking |