The specification requires a complete, supervised, addressable fire alarm reporting system configured in accordance with NFPA 72. The system must be microcomputer-based with individual addressability for all alarm initiating devices and notification appliances. Key components include a modular control panel (UL 864 compliant) installed in a flush or surface-mounted red steel cabinet; 24 Vdc rechargeable sealed lead-calcium batteries with 72-hour standby capacity plus 15-minute full alarm operation; automatic battery charger; addressable manual fire alarm stations (double-action type, red finish, mounted at 48 inches); fire detecting devices including heat detectors, photoelectric smoke detectors, ionization detectors, combination smoke/heat detectors, flame detectors (IR/UV types), and duct detectors; and notification appliances including alarm bells, horns, chimes, visual strobes (85 dBA minimum output), and voice evacuation systems. The system must support looped conduit design, Class A and B circuit configurations, HVAC shutdown, elevator recall, and fire suppression system integration. All wiring must be solid copper in metallic conduit with color coding; conduit compliance to NFPA 70, UL 6, UL 1242, and UL 797; and surge protection per IEEE C62.41.1/C62.41.2. The contractor must provide qualified personnel including a Registered Professional Engineer with four years' fire protection design experience and NICET Level 4 technician supervision, submit detailed shop drawings signed by a PE or NICET Level 4, and furnish two percent spare detectors (minimum two each type) and spare fuses mounted in the panel. Training requirements include three days total (1 day expansion/modification, 2 days maintenance, 1 day operations) with six copies each of maintenance and operating manuals. Preliminary and acceptance testing per NFPA 72 is mandatory, with 60-day advance submittal of detailed test procedures and final submission of NFPA 72 Certificate of Completion and testing reports documenting all functional and operational performance verification.
View the file
Other files
Show 40 more
50 files listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019
SECTI ON 28 31 64. 00 10
FI RE DETECTI ON AND ALARM SYSTEM, ADDRESSABLE
04/17
PART 1 GENERAL
1. 1 REFERENCES
The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.
ACOUSTI CAL SOCI ETY OF AMERI CA ( ASA)
ASA S3. 41 ( 2015) Audi bl e Emer gency Evacuat i on Si gnal
( ASA 96)
FM GLOBAL ( FM)
FM APP GUI DE ( updat ed on- l i ne) Appr oval Gui de http://www.approvalguide.com/
I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)
I EEE C62. 41. 1 ( 2002; R 2008) Gui de on t he Sur ges Envi r onment i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s
I EEE C62. 41. 2 ( 2002) Recommended Pr act i ce on Char act er i zat i on of Sur ges i n Low- Vol t age ( 1000 V and Less) AC Power Ci r cui t s
NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)
NFPA 1221 ( 2013) St andar d f or t he I nst al l at i on, Mai nt enance and Use of Emer gency Ser vi ces Communi cat i ons Syst ems
NFPA 70 ( 2014; AMD 1 2013; Er r at a 1 2013; AMD 2 2013; Er r at a 2 2013; AMD 3 2014; Er r at a 3- 4 2014; AMD 4- 6 2014) Nat i onal El ect r i cal Code
NFPA 72 ( 2013) Nat i onal Fi r e Al ar m and Si gnal i ng Code
NFPA 90A ( 2015) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems
U. S. NATI ONAL ARCHI VES AND RECORDS ADMI NI STRATI ON ( NARA)
47 CFR 15 Radi o Fr equency Devi ces
UNDERWRI TERS LABORATORI ES ( UL)
UL 1242 ( 2006; Repr i nt Mar 2014) St andar d f or
Apr i l 2019 Page 1 SECTI ON 28 31 64. 00 10
El ect r i cal I nt er medi at e Met al Condui t - - Steel
UL 1971 ( 2002; Repr i nt Oct 2008) Si gnal i ng Devi ces f or t he Hear i ng I mpai r ed
UL 228 ( 2006; Repr i nt Nov 2008) Door Cl oser s- Hol der s, Wi t h or Wi t hout I nt egr al Smoke Det ect or s
UL 268 ( 2016) Smoke Det ect or s f or Fi r e Al ar m Systems
UL 268A ( 2008; Repr i nt Oct 2014) Smoke Det ect or s f or Duct Appl i cat i on
UL 38 ( 2008; Repr i nt Nov 2013) Manual Si gnal i ng Boxes f or Fi r e Al ar m Syst ems
UL 464 ( 2016) St andar d f or Audi bl e Si gnal Appliances
UL 521 ( 1999; Repr i nt Apr 2015) Heat Det ect or s f or Fi r e Pr ot ect i ve Si gnal i ng Syst ems
UL 6 ( 2007; Repr i nt Nov 2014) El ect r i cal Ri gi d Met al Condui t - St eel
UL 797 ( 2007; Repr i nt Dec 2012) El ect r i cal Met al l i c Tubi ng - - St eel
UL 864 ( 2014) St andar d f or Cont r ol Uni t s and Accessor i es f or Fi r e Al ar m Syst ems
1. 2 SUBMITTALS
The f ol l owi ng shal l be submi t t ed i n accor dance wi t h Sect i on 01 33 00, SUBMI TTAL PROCEDURES:
SD- 02 Shop Dr awi ngs
Det ai l Dr awi ngs
SD- 03 Pr oduct Dat a
St or age Bat t er i es
Low Bat t er y Vol t age
Speci al Tool s and Spar e Par t s
Techni cal Dat a and Comput er Sof t war e
Training
Testing
SD- 06 Test Repor t s
Apr i l 2019 Page 2 SECTI ON 28 31 64. 00 10
Testing
SD- 07 Cer t i f i cat es
Equipment
Qualifications
SD- 10 Oper at i on and Mai nt enance Dat a
Oper at i ng and Mai nt enance I nst r uct i ons
1. 3 QUALI TY ASSURANCE
1. 3. 1 Qualifications
Submi t pr oof of qual i f i cat i ons f or r equi r ed per sonnel . The i nst al l er shal l submi t pr oof of exper i ence f or t he Pr of essi onal Engi neer , f i r e al ar m t echni c i an, and t he i nst al l i ng company.
1. 3. 1. 1 Engi neer and Techni c i an
a. Regi st er ed Pr of essi onal Engi neer wi t h ver i f i cat i on of exper i ence and at l east 4 year s of cur r ent exper i ence i n t he desi gn of t he f i r e pr ot ect i on and det ect i on syst ems.
b. Nat i onal I nst i t ut e f or Cer t i f i cat i on i n Engi neer i ng Technol ogi es ( NI CET) qual i f i cat i ons as an engi neer i ng t echni c i an i n f i r e al ar m syst ems pr ogr am wi t h ver i f i cat i on of exper i ence and cur r ent NI CET certificate.
c. The Regi st er ed Pr of essi onal Engi neer may per f or m al l r equi r ed i t ems under t hi s speci f i cat i on. The NI CET Fi r e Al ar m Techni c i an shal l per f or m onl y t he i t ems al l owed by t he speci f i c cat egor y of cer t i f i cat i on hel d.
1. 3. 1. 2 Installer
The i nst al l i ng Cont r act or shal l pr ovi de t he f ol l owi ng: NI CET Fi r e Al ar m Techni c i ans t o per f or m t he i nst al l at i on of t he syst em. A NI CET Level 4 Fi r e Al ar m Techni c i an shal l super vi se t he i nst al l at i on of t he f i r e al ar m syst em. NI CET Level 2 or hi gher Fi r e Al ar m Techni c i an shal l i nst al l and t er mi nat e f i r e al ar m devi ces, cabi net s and panel s. An el ect r i c i an or NI CET Level 1 Fi r e Al ar m Techni c i an shal l i nst al l condui t f or t he f i r e al ar m syst em. The Fi r e Al ar m t echni c i ans i nst al l i ng t he equi pment shal l be f act or y t r ai ned i n t he i nst al l at i on, adj ust ment , t est i ng, and oper at i on of t he equi pment speci f i ed her ei n and on t he dr awi ngs.
1. 3. 1. 3 Fi r e Pr ot ect i on Engi neer
I nst al l at i ons needi ng desi gns or modi f i cat i ons of f i r e det ect i on, f i r e al ar m, or f i r e suppr essi on syst ems r equi r e t he ser vi ces and r evi ew of a qual i f i ed f i r e pr ot ect i on engi neer . For t he pur poses of meet i ng t hi s r equi r ement , a qual i f i ed f i r e pr ot ect i on engi neer i s def i ned as an i ndi v i dual meet i ng one of t he f ol l owi ng condi t i ons:
a. An engi neer havi ng a Bachel or of Sci ence or Mast er s of Sci ence Degr ee i n Fi r e Pr ot ect i on Engi neer i ng f r om an accr edi t ed uni ver si t y engi neer i ng pr ogr am, pl us a mi ni mum of 2 year s ' wor k exper i ence i n
Apr i l 2019 Page 3 SECTI ON 28 31 64. 00 10 f i r e pr ot ect i on engi neer i ng.
b. A r egi st er ed pr of essi onal engi neer ( P. E. ) i n f i r e pr ot ect i on engineering.
c. A r egi st er ed PE i n a r el at ed engi neer i ng di sci pl i ne and member gr ade st at us i n t he Nat i onal Soci et y of Fi r e Pr ot ect i on Engi neer s.
d. An engi neer wi t h a mi ni mum of 10 year s ' exper i ence i n f i r e pr ot ect i on engi neer i ng and member gr ade st at us i n t he Nat i onal Soci et y of Fi r e Pr ot ect i on Engi neer s.
1. 3. 2 Det ai l Dr awi ngs
Submi t det ai l dr awi ngs consi st i ng of a compl et e l i s t of equi pment and mat er i al , i ncl udi ng manuf act ur er ' s descr i pt i ve and t echni cal l i t er at ur e, cat al og cut s, and i nst al l at i on i nst r uct i ons. Not e t hat t he cont r act dr awi ngs show l ayout s based on t ypi cal audi bl e appl i ances. Check t he l ayout based on t he act ual audi bl e devi ces t o be i nst al l ed and make any necessar y r evi s i ons i n t he det ai l dr awi ngs. The det ai l dr awi ngs shal l al so cont ai n compl et e wi r i ng and schemat i c di agr ams f or t he equi pment f ur ni shed, equi pment l ayout , and any ot her det ai l s r equi r ed t o demonst r at e t hat t he syst em has been coor di nat ed and wi l l pr oper l y f unct i on as a uni t . Det ai l dr awi ngs and det ai l ed poi nt - t o- poi nt wi r i ng di agr am shal l be pr epar ed and si gned by a Regi st er ed Pr of essi onal Engi neer or a NI CET Level 4 Fi r e Al ar m Techni c i an showi ng poi nt s of connect i on. Di agr am shal l i ncl ude connect i ons bet ween syst em devi ces, appl i ances, cont r ol panel s, super vi sed devi ces, and equi pment t hat i s act i vat ed or cont r ol l ed by t he panel.
1. 4 TECHNI CAL DATA AND COMPUTER SOFTWARE
Techni cal dat a and comput er sof t war e ( meani ng t echni cal dat a whi ch r el at es t o comput er sof t war e) whi ch i s speci f i cal l y i dent i f i ed i n t hi s pr oj ect , and whi ch may be def i ned/ r equi r ed i n ot her speci f i cat i ons, shal l be del i ver ed, st r i ct l y i n accor dance wi t h t he CONTRACT CLAUSES, and i n accor dance wi t h t he Cont r act Dat a Requi r ement s Li st , DD For m 1423. Dat a del i ver ed shal l be i dent i f i ed by r ef er ence t o t he par t i cul ar speci f i cat i on par agr aph agai nst whi ch i t i s f ur ni shed. Dat a t o be submi t t ed shal l i ncl ude compl et e syst em, equi pment , and sof t war e descr i pt i ons.
Descr i pt i ons shal l show how t he equi pment wi l l oper at e as a syst em t o meet t he per f or mance r equi r ement s of t hi s cont r act . The dat a package shal l al so i ncl ude t he f ol l owi ng:
a. I dent i f i cat i on of pr ogr ammabl e por t i ons of syst em equi pment and capabilities.
b. Descr i pt i on of syst em r evi s i on and expansi on capabi l i t i es and met hods of i mpl ement at i on det ai l i ng bot h equi pment and sof t war e r equi r ement s.
c. Pr ovi s i on of oper at i onal sof t war e dat a on al l modes of pr ogr ammabl e por t i ons of t he f i r e al ar m and det ect i on syst em.
d. Descr i pt i on of Fi r e Al ar m Cont r ol Panel equi pment oper at i on.
e. Descr i pt i on of auxi l i ar y and r emot e equi pment oper at i ons.
f . Li br ar y of appl i cat i on sof t war e.
Apr i l 2019 Page 4 SECTI ON 28 31 64. 00 10
g. Oper at i on and mai nt enance manual s as speci f i ed i n SD- 19 of t he Submi t t al s par agr aph.
1. 5 DELI VERY, STORAGE, AND HANDLI NG
Pr ot ect equi pment del i ver ed and pl aced i n st or age f r om t he weat her , humi di t y and t emper at ur e var i at i on, di r t , dust , and any ot her cont ami nant s.
1. 6 SPECI AL TOOLS AND SPARE PARTS
Fur ni sh sof t war e, connect i ng cabl es, pr opr i et ar y equi pment and t wo spar e f uses of each t ype and si ze r equi r ed, necessar y f or t he mai nt enance, t est i ng, and r epr ogr ammi ng of t he equi pment . Two per cent of t he t ot al number of each di f f er ent t ype of det ect or , but no l ess t han t wo each, shal l be f ur ni shed. Mount spar e f uses i n t he f i r e al ar m panel .
PART 2 PRODUCTS
2. 1 SYSTEM DESCRI PTI ON
The f i r e det ect i on and al ar m syst em and t he cent r al r epor t i ng syst em shal l be a compl et e, super vi sed f i r e al ar m r epor t i ng syst em conf i gur ed i n accor dance wi t h NFPA 72; except i ons ar e accept abl e as di r ect ed by t he Cont r act i ng Of f i cer . Fur ni sh equi pment compat i bl e and UL l i s t ed, FM appr oved, or appr oved or l i s t ed by a nat i onal l y r ecogni zed t est i ng l abor at or y i n accor dance wi t h t he appl i cabl e NFPA st andar ds. Locks shal l be keyed al i ke. Pr ovi de f our keys f or t he syst em. Fur ni sh t ags wi t h st amped i dent i f i cat i on number f or keys and l ocks.
2. 1. 1 Operation
The f i r e al ar m and det ect i on syst em shal l be a compl et e, super vi sed f i r e al ar m r epor t i ng syst em. Act i vat e t he syst em i nt o t he al ar m mode by act uat i on of any al ar m i ni t i at i ng devi ce. The syst em wi l l r emai n i n t he al ar m mode unt i l t he i ni t i at i ng devi ce i s r eset and t he f i r e al ar m cont r ol panel i s r eset and r est or ed t o nor mal . Al ar m and super vi sor y i ni t i at i ng devi ces shal l be i ndi v i dual l y addr essabl e. Al ar m i ni t i at i ng devi ces shal l be connect ed t o i ni t i at i ng devi ce c i r cui t s ( I DC) , Cl ass A, B or X, as speci f i ed, t o s i gnal l i ne c i r cui t s ( SLC) , Cl asse A, B or X, i n accor dance with NFPA 72. Connect al ar m not i f i cat i on appl i ances t o not i f i cat i on appl i ance ci r cui t s ( NAC) , Cl ass A i n accor dance wi t h NFPA 72. Pr ovi de a l ooped condui t syst em so t hat i f t he condui t and al l conduct or s wi t hi n ar e sever ed at any poi nt , al l I DC, NAC and SLC wi l l r emai n f unct i onal . The condui t l oop r equi r ement i s not appl i cabl e t o t he s i gnal t r ansmi ssi on l i nk f r om t he l ocal panel s ( at t he pr ot ect ed pr emi ses) t o t he Super vi s i ng St at i on ( f i r e st at i on, f i r e al ar m cent r al communi cat i on cent er ) . Text ual , audi bl e, and vi sual appl i ances and syst ems shal l compl y wi t h NFPA 72.
Fi r e al ar m syst em component s r equi r i ng power , except f or t he cont r ol panel power suppl y, shal l oper at e on 24 Vol t s dc. Addr essabl e syst em shal l be mi cr ocomput er ( mi cr opr ocessor or mi cr ocont r ol l er ) based wi t h a mi ni mum wor d si ze of ei ght bi t s and shal l pr ovi de t he f ol l owi ng f eat ur es:
a. Suf f i c i ent memor y t o per f or m as speci f i ed and as shown f or addr essabl e system.
b. I ndi v i dual i dent i t y of each addr essabl e devi ce f or t he f ol l owi ng condi t i ons: al ar m; t r oubl e; open; shor t ; and appl i ances mi ssi ng/ f ai l ed r emot e det ect or - sensi t i v i t y adj ust ment f r om t he panel f or smoke detectors.
Apr i l 2019 Page 5 SECTI ON 28 31 64. 00 10
c. Capabi l i t y of each addr essabl e devi ce bei ng i ndi v i dual l y di sabl ed or enabl ed f r om t he panel .
d. Si ze each SLC t o pr ovi de 40 per cent addr essabl e expansi on wi t hout har dwar e modi f i cat i ons t o t he panel .
2. 1. 2 Oper at i onal Feat ur es
The syst em shal l have t he f ol l owi ng oper at i ng f eat ur es:
a. Moni t or el ect r i cal super vi s i on of I DC, SLC, and NAC. Smoke det ect or s shal l have combi ned al ar m i ni t i at i ng and power c i r cui t s.
b. Moni t or el ect r i cal super vi s i on of t he pr i mar y power ( ac) suppl y, bat t er y vol t age, pl acement of al ar m zone modul e ( car d, PC boar d) wi t hi n t he cont r ol panel , and t r ansmi t t er t r i ppi ng ci r cui t i nt egr i t y.
c. A t r oubl e buzzer and t r oubl e LED/ LCD ( l i ght emi t t i ng di ode/ l i qui d cr yst al di ode) t o act i vat e upon a s i ngl e br eak, open, or gr ound f aul t condi t i on whi ch pr event s t he r equi r ed nor mal oper at i on of t he syst em.
The t r oubl e s i gnal shal l al so oper at e upon l oss of pr i mar y power ( ac) suppl y, l ow bat t er y vol t age, r emoval of al ar m zone modul e ( car d, PC boar d) , and di sconnect i on of t he c i r cui t used f or t r ansmi t t i ng al ar m si gnal s of f - pr emi ses. Submi t Vol t age dr op cal cul at i ons f or not i f i cat i on appl i ance ci r cui t s t o i ndi cat e t hat suf f i c i ent vol t age i s avai l abl e f or pr oper appl i ance oper at i on. A t r oubl e al ar m si l ence swi t ch shal l be pr ovi ded whi ch wi l l s i l ence t he t r oubl e buzzer , but wi l l not ext i ngui sh t he t r oubl e i ndi cat or LED/ LCD. Subsequent t r oubl e and super vi sor y al ar ms shal l sound t he t r oubl e s i gnal unt i l s i l enced.
Af t er t he syst em r et ur ns t o nor mal oper at i ng condi t i ons, t he t r oubl e buzzer shal l agai n sound unt i l t he s i l enci ng swi t ch r et ur ns t o nor mal posi t i on, unl ess aut omat i c t r oubl e r eset i s pr ovi ded.
d. A one per son t est mode. Act i vat i ng an i ni t i at i ng devi ce i n t hi s mode wi l l act i vat e an al ar m f or a shor t per i od of t i me, t hen aut omat i cal l y r eset t he al ar m, wi t hout act i vat i ng t he t r ansmi t t er dur i ng t he ent i r e process.
e. A t r ansmi t t er di sconnect swi t ch t o al l ow t est i ng and mai nt enance of t he syst em wi t hout act i vat i ng t he t r ansmi t t er but pr ovi di ng a t r oubl e s i gnal when di sconnect ed and a r est or at i on s i gnal when r econnect ed.
f . Evacuat i on al ar m si l enci ng swi t ch whi ch, when act i vat ed, wi l l s i l ence al ar m devi ces, but wi l l not af f ect t he zone i ndi cat i ng LED/ LCD di spl ays on t he cont r ol panel nor t he oper at i on of t he t r ansmi t t er .
Thi s swi t ch shal l be over - r i dden upon act i vat i on of a subsequent al ar m f r om an unal ar med devi ce and t he NAC devi ces wi l l be act i vat ed.
g. El ect r i cal super vi s i on f or c i r cui t s used f or super vi sor y s i gnal ser vi ces ( i . e. , spr i nkl er syst ems, val ves, et c. ) . Super vi s i on shal l det ect any open, shor t , or gr ound.
h. Conf i r mat i on or ver i f i cat i on of al l smoke det ect or s. The cont r ol panel shal l i nt er r upt t he t r ansmi ssi on of an al ar m si gnal t o t he syst em cont r ol panel f or a f act or y pr eset per i od. Thi s i nt er r upt i on per i od shal l be adj ust abl e f r om 1 t o 60 seconds and be f act or y set at 20 seconds. I mmedi at el y f ol l owi ng t he i nt er r upt i on per i od, a conf i r mat i on per i od shal l be i n ef f ect dur i ng whi ch t i me an al ar m
Apr i l 2019 Page 6 SECTI ON 28 31 64. 00 10 si gnal , i f pr esent , wi l l be sent i mmedi at el y t o t he cont r ol panel .
Fi r e al ar m devi ces ot her t han smoke det ect or s shal l be pr ogr ammed wi t hout conf i r mat i on or ver i f i cat i on.
i . The f i r e al ar m cont r ol panel shal l pr ovi de super vi sed addr essabl e r el ays f or HVAC shut down. An over r i de at t he HVAC panel shal l not be provided.
j . The f i r e al ar m cont r ol panel shal l pr ovi de t he r equi r ed moni t or i ng and super vi sed cont r ol out put s needed t o accompl i sh el evat or r ecal l .
k. The f i r e al ar m cont r ol panel shal l moni t or and cont r ol , as speci f i ed, t he f i r e spr i nkl er syst em, or ot her f i r e pr ot ect i on ext i ngui shi ng system.
l . The cont r ol panel and f i el d panel s shal l be sof t war e r epr ogr ammabl e t o enabl e expansi on or modi f i cat i on of t he syst em wi t hout r epl acement of har dwar e or f i r mwar e. Exampl es of r equi r ed changes ar e: addi ng or del et i ng devi ces or zones; changi ng syst em r esponses t o par t i cul ar i nput s i gnal s; pr ogr ammi ng cer t ai n i nput s i gnal s t o act i vat e auxi l i ar y devices.
n. Zones f or I DC and NAC shal l be as i ndi cat ed on t he cont r act dr awi ngs.
2. 1. 3 Al ar m Funct i ons
An al ar m condi t i on on a c i r cui t shal l aut omat i cal l y i ni t i at e t he f ol l owi ng functions:
a. Tr ansmi ssi on of s i gnal s over t he st at i on r adi o f i r e r epor t i ng syst em.
The si gnal shal l be common f or any devi ce.
b. Vi sual i ndi cat i ons of t he al ar med devi ces on t he f i r e al ar m cont r ol panel di spl ay and on t he r emot e audi bl e/ v i sual di spl ay.
c. Cont i nuous soundi ng or oper at i on of al ar m not i f i cat i on appl i ances onl y i n desi gnat ed ar eas as r equi r ed by ASA S3. 41.
d. Cl osur e of door s hel d open by el ect r omagnet i c devi ces.
e. Oper at i on of t he smoke cont r ol syst em.
f . Deact i vat i on of t he ai r handl i ng uni t s ser vi ng t he al ar med ar ea.
g. Shut down of power t o t he dat a pr ocessi ng equi pment i n t he al ar med ar ea.
h. Aut omat i c di schar ge of t he desi gnat ed f i r e suppr essi on syst ems. A 15 second maxi mum del ay shal l be pr ovi ded f or t he del uge syst em, a 30 second del ay f or t he wet pi pe syst em.
2. 1. 4 Pr i mar y Power
Oper at i ng power shal l be pr ovi ded as r equi r ed by par agr aph Power Suppl y f or t he Syst em. Tr ansf er f r om nor mal t o emer gency power or r est or at i on f r om emer gency t o nor mal power shal l be f ul l y aut omat i c and not cause t r ansmi ssi on of a f al se al ar m. Loss of ac power shal l not pr event t r ansmi ssi on of a s i gnal v i a t he f i r e r epor t i ng syst em upon oper at i on of any i ni t i at i ng c i r cui t .
Apr i l 2019 Page 7 SECTI ON 28 31 64. 00 10
2. 1. 5 Bat t er y Backup Power
Bat t er y backup power shal l be t hr ough use of r echar geabl e, seal ed- t ype st or age bat t er i es and bat t er y char ger .
2. 1. 6 I nt er f ace Wi t h Exi st i ng Fi r e Al ar m Equi pment
The equi pment speci f i ed her ei n shal l oper at e as an ext ensi on t o an exi st i ng conf i gur at i on. Exi st i ng moni t or i ng equi pment shal l be expanded, modi f i ed, or suppl ement ed as necessar y t o ext end t he exi st i ng moni t or i ng f unct i ons t o t he new poi nt s or zones. New component s shal l be capabl e of mer gi ng wi t h t he exi st i ng conf i gur at i on wi t hout degr adi ng t he per f or mance of ei t her syst em. The scope of t he accept ance t est s of par agr aph Test i ng shal l i ncl ude aspect s of oper at i on t hat i nvol ve combi ned use of bot h new and exi st i ng por t i ons of t he f i nal conf i gur at i on.
2. 1. 7 I nt er f ace Wi t h ot her Equi pment
I nt er f aci ng component s shal l be f ur ni shed as r equi r ed t o connect t o subsyst ems or devi ces whi ch i nt er act wi t h t he f i r e al ar m syst em, such as super vi sor y or al ar m cont act s i n suppr essi on syst ems, oper at i ng i nt er f aces f or smoke cont r ol syst ems, door r el eases, et c.
2. 2 STANDARD PRODUCTS
Pr ovi de mat er i al and equi pment whi ch ar e t he st andar d pr oduct s of a manuf act ur er r egul ar l y engaged i n t he manuf act ur e of t he pr oduct s f or at l east 2 year s pr i or t o bi d openi ng. Equi pment shal l be suppor t ed by a ser vi ce or gani zat i on t hat can pr ovi de ser vi ce wi t hi n 24 hour s of notification.
2. 3 NAMEPLATES
Maj or component s of equi pment shal l have t he manuf act ur er ' s name, addr ess, t ype or st y l e, vol t age and cur r ent r at i ng, and cat al og number on a non-cor r osi ve and non- heat - sensi t i ve pl at e whi ch i s secur el y at t ached t o t he equipment.
2. 4 CONTROL PANEL
Cont r ol Panel shal l compl y wi t h t he appl i cabl e r equi r ement s of UL 864.
Panel shal l be modul ar , i nst al l ed i n a f l ush, sur f ace or semi - f l ush mount ed st eel cabi net wi t h hi nged door and cyl i nder l ock, as speci f i ed.
Cont r ol panel shal l be a c l ean, uncl ut t er ed, and or der l y assembl ed panel cont ai ni ng component s and equi pment r equi r ed t o pr ovi de t he speci f i ed oper at i ng and super vi sor y f unct i ons of t he syst em. The panel shal l have pr omi nent r i gi d pl ast i c, phenol i c or met al i dent i f i cat i on pl at es f or LED/ LCDs, zones, SLC, cont r ol s, met er s, f uses, and swi t ches.
a. Namepl at es f or f uses shal l al so i ncl ude amper e r at i ng. The LED/ LCD di spl ays shal l be l ocat ed on t he ext er i or of t he cabi net door or be vi s i bl e t hr ough t he cabi net door . Cont r ol panel swi t ches shal l be wi t hi n t he l ocked cabi net . A sui t abl e means ( s i ngl e oper at i on) shal l be pr ovi ded f or t est i ng t he cont r ol panel v i sual i ndi cat i ng devi ces ( met er s or LEDs/ LCDs) . Met er s and LEDs shal l be pl ai nl y v i s i bl e when t he cabi net door i s c l osed. Si gnal s and LEDs/ LCDs shal l be pr ovi ded t o i ndi cat e by zone any al ar m, super vi sor y or t r oubl e condi t i on on t he system.
Apr i l 2019 Page 8 SECTI ON 28 31 64. 00 10
b. Each I DC shal l be power ed and super vi sed so t hat a s i gnal on one zone does not pr event t he r ecei pt of s i gnal s f r om ot her devi ces. Loss of power , i ncl udi ng bat t er i es, shal l not r equi r e t he manual r el oadi ng of a pr ogr am. Upon r est or at i on of power , st ar t up shal l be aut omat i c, and shal l not r equi r e any manual oper at i on. The l oss of pr i mar y power or t he sequence of appl y i ng pr i mar y or emer gency power shal l not af f ect t he t r ansmi ssi on of al ar m, super vi sor y or t r oubl e s i gnal s.
c. Vi sual annunci at i on shal l be pr ovi ded f or LED/ LCD vi sual di spl ay as an i nt egr al par t of t he cont r ol panel and shal l i dent i f y wi t h a wor d descr i pt i on and i d number each devi ce. Cabi net s shal l be pr ovi ded wi t h ampl e gut t er space t o al l ow pr oper c l ear ance bet ween t he cabi net and l i ve par t s of t he panel equi pment . I f mor e t han one modul ar uni t i s r equi r ed t o f or m a cont r ol panel , t he uni t s shal l be i nst al l ed i n a s i ngl e cabi net l ar ge enough t o accommodat e uni t s. Cabi net s shal l be pai nt ed r ed.
d. Locks shal l be keyed al i ke. Four keys f or t he syst em shal l be provided.
e. Tags wi t h st amped i dent i f i cat i on number shal l be f ur ni shed f or keys and l ocks.
2. 4. 1 Remot e Syst em Audi bl e/ Vi sual Di spl ay
Audi bl e appl i ance shal l have a mi ni mum sound l evel out put r at i ng of 85 dBA at 10 f eet and oper at e i n conj unct i on wi t h t he panel i nt egr al di spl ay.
The audi bl e devi ce shal l be s i l enced by a syst em si l ence swi t ch on t he r emot e syst em. The audi bl e devi ce shal l be s i l enced by t he syst em si l ence swi t ch l ocat ed at t he r emot e l ocat i on, but shal l not ext i ngui sh t he vi sual i ndi cat i on. The r emot e LED/ LCD vi sual di spl ay shal l pr ovi de i dent i f i cat i on, consi st i ng of t he wor d descr i pt i on and i d number f or each devi ce as di spl ayed on t he cont r ol panel . A r i gi d pl ast i c, phenol i c or met al i dent i f i cat i on s i gn whi ch r eads " Fi r e Al ar m Syst em Remot e Di spl ay" shal l be pr ovi ded at t he r emot e audi bl e/ v i sual di spl ay. The r emot e v i sual appl i ance l ocat ed wi t h t he audi bl e appl i ance shal l not be ext i ngui shed unt i l t he t r oubl e or al ar m has been cl ear ed.
2. 4. 2 Ci r cui t Connect i ons
Connect c i r cui t conduct or s ent er i ng or l eavi ng t he panel t o scr ew- t ype t er mi nal s wi t h each conduct or and t er mi nal mar ked f or i dent i f i cat i on.
2. 4. 3 Syst em Expansi on and Modi f i cat i on Capabi l i t i es
Pr ovi de, as par t of t hi s cont r act , any equi pment and sof t war e needed by qual i f i ed t echni c i ans t o i mpl ement f ut ur e changes t o t he f i r e al ar m syst em.
2. 4. 4 Addr essabl e Cont r ol Modul e
The cont r ol modul e shal l be capabl e of oper at i ng as a r el ay ( dr y cont act f or m C) f or i nt er f aci ng t he cont r ol panel wi t h ot her syst ems, and t o cont r ol door hol der s or i ni t i at e el evat or f i r e ser vi ce. The modul e shal l be UL l i s t ed as compat i bl e wi t h t he cont r ol panel . The i ndi cat i ng devi ce or t he ext er nal l oad bei ng cont r ol l ed shal l be conf i gur ed as a Cl ass B not i f i cat i on appl i ance ci r cui t s. The syst em shal l be capabl e of super vi s i ng, audi bl e, v i sual and dr y cont act c i r cui t s. The cont r ol modul e shal l have bot h an i nput and out put addr ess. The super vi s i on shal l det ect a shor t on t he super vi sed ci r cui t and shal l pr event power f r om bei ng
Apr i l 2019 Page 9 SECTI ON 28 31 64. 00 10 appl i ed t o t he c i r cui t . The cont r ol model shal l pr ovi de addr ess set t i ng means compat i bl e wi t h t he cont r ol panel ' s SLC super vi s i on and st or e an i nt er nal i dent i f y i ng code. The cont r ol modul e shal l cont ai n an i nt egr al LED t hat f l ashes each t i me t he cont r ol modul e i s pol l ed. Exi st i ng f i r e al ar m syst em not i f i cat i on appl i ance ci r cui t s shal l be connect ed t o a s i ngl e modul e t o power and super vi se t he c i r cui t .
2. 4. 5 Addr essabl e I ni t i at i ng Devi ce Ci r cui t s Modul e
Conf i gur e t he i ni t i at i ng devi ce bei ng moni t or ed as a Cl ass A or Cl ass B i ni t i at i ng devi ce c i r cui t s, as speci f i ed. The syst em shal l be capabl e of def i ni ng any modul e as an al ar m modul e and r epor t al ar m t r oubl e, l oss of pol l i ng, or as a super vi sor y modul e, and r epor t i ng super vi sor y shor t , super vi sor y open or l oss of pol l i ng. The modul e shal l be UL l i s t ed as compat i bl e wi t h t he cont r ol panel . The moni t or modul e shal l pr ovi de addr ess set t i ng means compat i bl e wi t h t he cont r ol panel ' s SLC super vi s i on and st or e an i nt er nal i dent i f y i ng code. Moni t or modul e shal l cont ai n an i nt egr al LED t hat f l ashes each t i me t he moni t or modul e i s pol l ed. Pul l st at i ons wi t h a moni t or modul e i n a common backbox ar e not r equi r ed t o have an LED. Exi st i ng f i r e al ar m syst em i ni t i at i ng devi ce c i r cui t s shal l be connect ed t o a s i ngl e modul e t o power and super vi se t he c i r cui t .
2. 5 STORAGE BATTERI ES
Submi t subst ant i at i ng bat t er y cal cul at i ons f or super vi sor y and al ar m power r equi r ement s. Amper e- hour r equi r ement s f or each syst em component and each panel component , and t he bat t er y r echar gi ng per i od shal l be i ncl uded.
Pr ovi de st or age bat t er i es whi ch ar e 24 Vdc seal ed, l ead- cal c i um t ype r equi r i ng no addi t i onal wat er wi t h ampl e capaci t y, wi t h pr i mar y power di sconnect ed, t o oper at e t he f i r e al ar m syst em f or a per i od of 72 hour s.
Fol l owi ng t hi s per i od of bat t er y oper at i on, t he bat t er i es shal l have ampl e capaci t y t o oper at e al l component s of t he syst em, i ncl udi ng al l al ar m si gnal i ng devi ces i n t he t ot al al ar m mode f or a mi ni mum per i od of 15 mi nut es. Locat e bat t er i es at t he bot t om of t he panel or i n a separ at e bat t er y cabi net , as speci f i ed. Pr ovi de bat t er i es wi t h over cur r ent pr ot ect i on i n accor dance wi t h NFPA 72. Separ at e bat t er y cabi net s shal l have a l ockabl e, hi nged cover s i mi l ar t o t he f i r e al ar m panel . The l ock shal l be keyed t he same as t he f i r e al ar m cont r ol panel . Pai nt t he cabi net s t o mat ch t he f i r e al ar m cont r ol panel .
2. 6 BATTERY CHARGER
Bat t er y char ger shal l be compl et el y aut omat i c, 24 Vdc wi t h hi gh/ l ow char gi ng r at e, capabl e of r est or i ng t he bat t er i es f r om f ul l di schar ge ( 18 Vol t s dc) t o f ul l char ge wi t hi n 48 hour s. A pi l ot l i ght i ndi cat i ng when bat t er i es ar e manual l y pl aced on a hi gh r at e of char ge shal l be pr ovi ded as par t of t he uni t assembl y, i f a hi gh r at e swi t ch i s pr ovi ded. Locat e char ger i n cont r ol panel cabi net or i n a separ at e bat t er y cabi net .
2. 7 ADDRESSABLE MANUAL FI RE ALARM STATI ONS
Addr essabl e manual f i r e al ar m st at i ons shal l conf or m t o t he appl i cabl e r equi r ement s of UL 38. Manual st at i ons shal l be connect ed i nt o s i gnal l i ne c i r cui t s. St at i ons shal l be i nst al l ed on sur f ace, semi - f l ush or f l ush mount ed out l et boxes, as speci f i ed. Manual st at i ons shal l be mount ed at 48 i nches. St at i ons shal l be doubl e act i on t ype. St at i ons shal l be f i ni shed i n r ed, wi t h r ai sed l et t er oper at i ng i nst r uct i ons of cont r ast i ng col or . St at i ons r equi r i ng t he br eaki ng of gl ass or pl ast i c panel s f or oper at i on ar e not accept abl e. St at i ons empl oyi ng gl ass r ods ar e not
Apr i l 2019 Page 10 SECTI ON 28 31 64. 00 10 accept abl e. The use of a key or wr ench shal l be r equi r ed t o r eset t he st at i on. Gr avi t y or mer cur y swi t ches ar e not accept abl e. Swi t ches and cont act s shal l be r at ed f or t he vol t age and cur r ent upon whi ch t hey oper at e. Addr essabl e pul l st at i ons shal l be capabl e of bei ng f i el d pr ogr ammed, shal l l at ch upon oper at i on and r emai n l at ched unt i l manual l y r eset . St at i ons shal l have a separ at e scr ew t er mi nal f or each conduct or .
Sur f ace mount ed boxes shal l be mat ched and pai nt ed t he same col or as t he f i r e al ar m manual st at i ons.
2. 8 FI RE DETECTI NG DEVI CES
Fi r e det ect i ng devi ces shal l compl y wi t h t he appl i cabl e r equi r ement s of NFPA 72, NFPA 90A, UL 268, UL 268A, and UL 521. The det ect or s shal l be pr ovi ded as i ndi cat ed. Det ect or base shal l have scr ew t er mi nal s f or maki ng connect i ons. No sol der connect i ons wi l l be al l owed. Det ect or s l ocat ed i n conceal ed l ocat i ons ( above cei l i ng, r ai sed f l oor s, et c. ) shal l have a r emot e v i s i bl e i ndi cat or LED/ LCD. Addr essabl e f i r e det ect i ng devi ces, except f l ame det ect or s, shal l be dynami cal l y super vi sed and uni quel y i dent i f i ed i n t he cont r ol panel . Al l f i r e al ar m i ni t i at i ng devi ces shal l be i ndi v i dual l y addr essabl e, except wher e i ndi cat ed.
I nst al l ed devi ces shal l conf or m t o NFPA 70 hazar d c l assi f i cat i on of t he ar ea wher e devi ces ar e t o be i nst al l ed.
2. 8. 1 Heat Det ect or s
Desi gn heat det ect or s f or det ect i on of f i r e by combi nat i on f i xed t emper at ur e and r at e- of - r i se pr i nci pl e. Heat det ect or spaci ng shal l be r at ed i n accor dance wi t h UL 521. Det ect or s l ocat ed i n ar eas subj ect t o moi st ur e, ext er i or at mospher i c condi t i ons, or hazar dous l ocat i ons as def i ned by NFPA 70 and as shown on dr awi ngs, shal l be t ypes appr oved f or such l ocat i ons. Heat det ect or s l ocat ed i n at t i c spaces or s i mi l ar conceal ed spaces bel ow t he r oof shal l be i nt er medi at e t emper at ur e r at ed.
2. 8. 1. 1 Combi nat i on Fi xed- Temper at ur e and Rat e- of - Ri se Det ect or s
Det ect or s shal l be desi gned f or sur f ace or semi - f l ush out l et box mount i ng and suppor t ed i ndependent l y of wi r i ng connect i ons, as speci f i ed. Cont act s shal l be sel f - r eset t i ng af t er r esponse t o r at e- of - r i se pr i nci pl e. Under f i xed t emper at ur e act uat i on, t he det ect or shal l have a per manent ext er nal i ndi cat i on whi ch i s r eadi l y v i s i bl e. Det ect or uni t s l ocat ed i n boi l er r ooms, shower s, or ot her ar eas subj ect t o abnor mal t emper at ur e changes shal l oper at e on f i xed t emper at ur e pr i nci pl e onl y. The UL 521 t est r at i ng f or t he f i xed t emper at ur e por t i on shal l be 135 degr ees F. The UL 521 t est r at i ng f or t he Rat e- of - Ri se det ect or s shal l be r at ed f or 50 by 50 f t .
2. 8. 1. 2 Rat e Compensat i ng Det ect or s
Det ect or s shal l be sur f ace or f l ush mount ed ver t i cal or hor i zont al t ype, as speci f i ed, wi t h out l et box suppor t ed i ndependent l y of wi r i ng connect i ons. Det ect or s shal l be her met i cal l y seal ed and aut omat i cal l y r eset t i ng. Rat e Compensat ed det ect or s shal l be r at ed f or 50 by 50 f t .
2. 8. 1. 3 Fi xed Temper at ur e Det ect or s
Det ect or s shal l be desi gned f or sur f ace, or semi - f l ush, as speci f i ed, out l et box mount i ng and suppor t ed i ndependent l y of wi r i ng connect i ons.
Det ect or s shal l be desi gned t o det ect hi gh heat . The det ect or s shal l have a speci f i c t emper at ur e set t i ng of 135 degr ees F. The UL 521 t est r at i ng f or t he f i xed t emper at ur e det ect or s shal l be r at ed f or 15 by 15 f t .
Apr i l 2019 Page 11 SECTI ON 28 31 64. 00 10
2. 8. 2 Smoke Det ect or s
Desi gn smoke det ect or s f or det ect i on of abnor mal smoke densi t i es. Smoke det ect or s shal l be phot oel ect r i c t ype. Det ect or s shal l cont ai n a v i s i bl e i ndi cat or LED/ LCD t hat shows when t he uni t i s i n al ar m condi t i on.
Det ect or s shal l not be adver sel y af f ect ed by v i br at i on or pr essur e.
Det ect or s shal l be t he pl ug- i n t ype i n whi ch t he det ect or base cont ai ns t er mi nal s f or maki ng wi r i ng connect i ons. Det ect or s t hat ar e t o be i nst al l ed i n conceal ed ( above f al se cei l i ngs, et c. ) l ocat i ons shal l be pr ovi ded wi t h a r emot e i ndi cat or LED/ LCD sui t abl e f or mount i ng i n a f i ni shed, v i s i bl e l ocat i on.
2. 8. 2. 1 I oni zat i on Det ect or s
I oni zat i on det ect or s wi t h a dual chamber shal l be r esponsi ve t o bot h i nvi s i bl e and vi s i bl e par t i c l es of combust i on. One chamber shal l be a r ef er ence chamber and t he second a sampl i ng chamber . Det ect or s cont ai ni ng r adi um shal l not be pr ovi ded. Det ect or s shal l not cause an al ar m condi t i on due t o ant i c i pat ed f l uct uat i ons i n r el at i ve humi di t y. The sensi t i v i t y of t he det ect or shal l be f i el d adj ust abl e t o compensat e f or oper at i ng condi t i ons. Det ect or shal l r equi r e no r epl acement or r eadj ust ment t o r est or e i t t o nor mal oper at i on af t er an al ar m condi t i on.
Each det ect or shal l be capabl e of wi t hst andi ng ambi ent ai r vel oci t y up t o 300 f pm i n accor dance wi t h UL 268. Addr essabl e smoke det ect or s shal l be capabl e of havi ng t he sensi t i v i t y bei ng r emot el y adj ust ed by t he cont r ol panel.
2. 8. 2. 2 Phot oel ect r i c Det ect or s
Det ect or s shal l oper at e on a l i ght scat t er i ng concept usi ng an LED l i ght sour ce. Fai l ur e of t he LED shal l not cause an al ar m condi t i on. Det ect or s shal l be f act or y set f or sensi t i v i t y and shal l r equi r e no f i el d adj ust ment s of any k i nd. Det ect or s shal l have an obscur at i on r at i ng i n accor dance wi t h UL 268. Addr essabl e smoke det ect or s shal l be capabl e of havi ng t he sensi t i v i t y bei ng r emot el y adj ust ed by t he cont r ol panel .
2. 8. 2. 3 Pr oj ect ed Beam Smoke Det ect or s
Det ect or s shal l be desi gned f or det ect i on of abnor mal smoke densi t i es.
Det ect or s shal l consi st of separ at e t r ansmi t t er and r ecei ver uni t s. The t r ansmi t t er uni t shal l emi t an i nf r ar ed beam t o t he r ecei ver uni t . When t he si gnal at t he r ecei ver f al l s bel ow a pr eset sensi t i v i t y, t he det ect or shal l i ni t i at e an al ar m. The r ecei ver shal l cont ai n an LED whi ch i s power ed upon an al ar m condi t i on. Long- t er m changes t o t he r ecei ved si gnal caused by envi r onment al var i at i ons shal l be aut omat i cal l y compensat ed.
Det ect or s shal l i ncor por at e f eat ur es t o assur e t hat t hey ar e oper at i onal ;
a t r oubl e s i gnal shal l be i ni t i at ed i f t he beam i s obst r uct ed, t he l i mi t s of t he compensat i on c i r cui t ar e r eached, or t he housi ng cover i s r emoved.
Det ect or s shal l have mul t i pl e sensi t i v i t y set t i ngs i n or der t o meet UL l i s t i ngs f or t he di f f er ent di st ances cover ed by t he beam. I n t he event of beam i nt er f er ence f or mor e t han t hr ee seconds a t r oubl e al ar m shal l be transmitted.
2. 8. 2. 4 Duct Det ect or s
Duct - mount ed phot oel ect r i c smoke det ect or s shal l be f ur ni shed and i nst al l ed wher e i ndi cat ed and i n accor dance wi t h NFPA 90A. Uni t s shal l consi st of a smoke det ect or as speci f i ed i n par agr aph Phot oel ect r i c
Apr i l 2019 Page 12 SECTI ON 28 31 64. 00 10
Det ect or s, mount ed i n a speci al housi ng f i t t ed wi t h duct sampl i ng t ubes.
Det ect or c i r cui t r y shal l be mount ed i n a met al l i c encl osur e ext er i or t o t he duct . Det ect or s shal l have a manual r eset . Det ect or s shal l be r at ed f or ai r vel oci t i es t hat i ncl ude ai r f l ows bet ween 500 and 4000 f pm.
Det ect or s shal l be power ed f r om t he f i r e al ar m panel . Sampl i ng t ubes shal l r un t he f ul l wi dt h of t he duct . The duct det ect or package shal l conf or m t o t he r equi r ement s of NFPA 90A, UL 268A, and shal l be UL l i s t ed f or use i n ai r - handl i ng syst ems. The cont r ol f unct i ons, oper at i on, r eset , and bypass shal l be cont r ol l ed f r om t he f i r e al ar m cont r ol panel . Li ght s t o i ndi cat e t he oper at i on and al ar m condi t i on; and t he t est and r eset but t ons shal l be v i s i bl e and accessi bl e wi t h t he uni t i nst al l ed and t he cover i n pl ace. Det ect or s mount ed above 6 f eet and t hose mount ed bel ow 6 f eet t hat cannot be easi l y accessed whi l e st andi ng on t he f l oor , shal l be pr ovi ded wi t h a r emot e det ect or i ndi cat or panel cont ai ni ng t est and r eset swi t ches. Remot e l amps and swi t ches as wel l as t he af f ect ed f an uni t s shal l be pr oper l y i dent i f i ed i n et ched pl ast i c pl acar ds. Det ect or s shal l have auxi l i ar y cont act s t o pr ovi de cont r ol , i nt er l ock, and shut down f unct i ons speci f i ed i n Sect i on 23 09 23. 01 LONWORKS DI RECT DI GI TAL CONTROL FOR HVAC AND OTHER BUI LDI NG CONTROL SYSTEMS. The det ect or s shal l be suppl i ed by t he f i r e al ar m syst em manuf act ur er t o ensur e compl et e syst em compatibility.
2. 8. 3 Combi nat i on Smoke and Heat Det ect or s
Combi nat i on smoke and heat det ect or s shal l have an audi bl e devi ce ( sel f - cont ai ned) and be desi gned f or det ect i on of abnor mal smoke densi t i es by t he phot oel ect r i c pr i nci pl e and abnor mal heat by a f i xed t emper at ur e sensor . Smoke det ect or s shal l be pr ovi ded wi t h an LED l i ght sour ce.
Fai l ur e of t he LED shal l not cause an al ar m condi t i on and t he sensi t i v i t y shal l be f act or y set at a nomi nal 3 per cent and r equi r e no f i el d adj ust ment s of any k i nd. Heat det ect or por t i on shal l be f i xed t emper at ur e sensor r at ed at 135 degr ees F. The audi bl e appl i ances shal l have a mi ni mum sound out put of at l east 85 dBA at 10 f eet . Det ect or s shal l cont ai n a v i s i bl e i ndi cat or LED t hat shows when t he uni t i s i n al ar m condi t i on. Det ect or s shal l not be adver sel y af f ect ed by v i br at i on or pr essur e. Heat det ect or s shal l connect t o a cont r ol panel I DC and shal l be sel f r est or abl e.
2. 8. 4 Fl ame Det ect or s
The det ect or s shal l compl y wi t h FM APP GUI DE. The det ect or s shal l be sensi t i ve t o t he mi cr on r ange best sui t ed f or t hei r i nt ended use. The det ect or s shal l oper at e over el ect r i cal l y super vi sed wi r i ng c i r cui t s and t he l oss of power t o t he det ect or shal l r esul t i n a t r oubl e s i gnal . A sel f - t est f eat ur e shal l be pr ovi ded f or each det ect or t o be i ndi v i dual l y tested.
2. 8. 4. 1 I nf r ar ed ( I R) Si ngl e Fr equency Fl ame Det ect or
The det ect or shal l be sensi t i ve i n t he r ange of 0. 185 t o 0. 265 mi cr omet er s only.
2. 8. 4. 2 I nf r ar ed ( I R) Dual Fr equency Fl ame Det ect or
The I R det ect or shal l consi st of t wo or mor e I R sensor s, each sel ect ed f or a di f f er ent I R f r equency. The pr i mar y sensor shal l be sensi t i ve i n t he r ange of 0. 185 t o 0. 265 mi cr omet er s onl y. Secondar y sensor s ar e t uned t o di f f er ent I R wavel engt hs t o nul l out t he ef f ect of bl ack body r adi at i on t o t he pr i mar y sensor .
Apr i l 2019 Page 13 SECTI ON 28 31 64. 00 10
2. 8. 4. 3 Ul t r avi ol et ( UV) Fl ame Det ect or s
UV f l ame det ect or shal l be of t he nar r ow band r esponse t ype whi ch oper at es on r adi at ed ul t r avi ol et ener gy and shal l be sensi t i ve i n t he r ange of
0. 185 t o 0. 265 mi cr omet er s onl y. The cone of v i s i on shal l be 80 degr ees or gr eat er . Each det ect or shal l be compl et el y i nsensi t i ve t o l i ght sour ces i n t he v i s i bl e f r equency r ange.
2. 8. 4. 4 Combi nat i on UV/ I R Fl ame Det ect or
The UV/ I R det ect or shal l pr ovi de di scr i mi nat i on agai nst f al se al ar ms by r equi r i ng bot h UV and I R f l ame det ect i on bef or e an al ar m i s sent . The UV sensor shal l be sensi t i ve i n t he r ange of 0. 185 t o 0. 265 mi cr omet er s onl y. The I R sensor shal l be sensi t i ve i n t he r ange of 0. 185 t o 0. 265 mi cr omet er s onl y. Det ect or s shal l be compl et el y i nsensi t i ve t o l i ght sour ces i n t he v i s i bl e f r equency r ange.
2. 9 NOTI FI CATI ON APPLI ANCES
Audi bl e appl i ances shal l conf or m t o t he appl i cabl e r equi r ement s of UL 464.
Devi ces shal l be connect ed i nt o not i f i cat i on appl i ance ci r cui t s. Devi ces shal l have a separ at e scr ew t er mi nal f or each conduct or . Audi bl e appl i ances shal l gener at e a uni que audi bl e sound f r om ot her devi ces pr ovi ded i n t he bui l di ng and sur r oundi ng ar ea. Sur f ace mount ed audi bl e appl i ances shal l be pai nt ed r ed. Recessed audi bl e appl i ances shal l be i nst al l ed wi t h a gr i l l t hat i s pai nt ed r ed.
2. 9. 1 Al ar m Bel l s
Bel l s shal l be sur f ace mount ed wi t h t he mat chi ng mount i ng back box sur f ace mount ed or r ecessed, as speci f i ed. Bel l s shal l be sui t abl e f or use i n an el ect r i cal l y super vi sed ci r cui t . Bel l s shal l be t he under dome t ype pr oduci ng a mi ni mum out put r at i ng of 85 dBA at 10 f eet . Bel l s used i n ext er i or l ocat i ons shal l be speci f i cal l y l i s t ed or appr oved f or out door use and be pr ovi ded wi t h met al housi ng and pr ot ect i ve gr i l l es. Si ngl e st r oke, el ect r i cal l y oper at ed, super vi sed, sol enoi d bel l s shal l be used f or coded appl i cat i ons.
2. 9. 2 Al ar m Hor ns
Hor ns shal l be sur f ace mount ed, wi t h t he mat chi ng mount i ng back box sur f ace mount ed doubl e pr oj ect or , v i br at i ng t ype sui t abl e f or use i n an el ect r i cal l y super vi sed ci r cui t . Hor ns shal l pr oduce a sound r at i ng of at l east 85 dBA at 10 f eet . Hor ns used i n ext er i or l ocat i ons shal l be speci f i cal l y l i s t ed or appr oved f or out door use and be pr ovi ded wi t h met al housi ng and pr ot ect i ve gr i l l es.
2. 9. 3 Chimes
Chi mes shal l be el ect r i cal l y oper at ed, super vi sed, el ect r oni c t ype, wi t h an adj ust abl e f r equency of 800 t o 1200 Her t z. Chi mes shal l have a mi ni mum sound r at i ng of 80 dBA at 10 f eet . Chi mes shal l r i ng t he bel l codes, as indicated.
2. 9. 4 Vi sual Not i f i cat i on Appl i ances
Vi sual not i f i cat i on appl i ances shal l conf or m t o t he appl i cabl e r equi r ement s of UL 1971 and t he cont r act dr awi ngs. Appl i ances shal l have
Apr i l 2019 Page 14 SECTI ON 28 31 64. 00 10 cl ear hi gh i nt ensi t y opt i c l ens, xenon f l ash t ubes, and out put whi t e l i ght . St r obe f l ash r at e shal l be bet ween 1 t o 3 f l ashes per second and a mi ni mum of 75 candel a. St r obe shal l be sur f ace or semi - f l ush mount ed, as specified.
2. 9. 5 Combi nat i on Audi bl e/ Vi sual Not i f i cat i on Appl i ances
Combi nat i on audi bl e/ v i sual not i f i cat i on appl i ances shal l pr ovi de t he same r equi r ement s as i ndi v i dual uni t s except t hey shal l mount as a uni t i n st andar d backboxes. Uni t s shal l be f act or y assembl ed. Any ot her audi bl e not i f i cat i on appl i ance empl oyed i n t he f i r e al ar m syst ems shal l be appr oved by t he Cont r act i ng Of f i cer .
2. 9. 6 Voi ce Evacuat i on Syst em
The voi ce evacuat i on syst em shal l pr ovi de f or t wo- way voi ce communi cat i ons, r out i ng and pr e- ampl i f i cat i on of di gi t al al ar m t ones and voi ce ( di gi t al and anal og) messages. The syst em shal l be zoned f or messages ( Cust om and pr er ecor ded) and t ones as i ndi cat ed on t he dr awi ngs.
The f ol l owi ng el ect r oni c t ones shal l be avai l abl e f r om t he ampl i f i er :
Sl ow Whoop, Hi gh/ Low, Hor n, Chi me, Beep, St ut t er , Wai l and Bel l . The syst em shal l have a mi cr ophone and al l ow f or gener al pagi ng wi t hi n t he space. Oper at i on shal l be ei t her manual l y f r om a cont r ol swi t ch or aut omat i cal l y f r om t he f i r e al ar m cont r ol panel . Reset shal l be accompl i shed by t he f i r e al ar m cont r ol panel dur i ng panel r eset .
2. 10 FI RE DETECTI ON AND ALARM SYSTEM PERI PHERAL EQUI PMENT
2. 10. 1 El ect r omagnet i c Door Hol d- Open Devi ces
At t ach devi ces t o t he wal l s unl ess ot her wi se i ndi cat ed. Devi ces shal l compl y wi t h t he appr opr i at e r equi r ement s of UL 228. Devi ces shal l oper at e on 24 Vol t dc power . Compat i bl e magnet i c component shal l be at t ached t o t he door . Under nor mal condi t i ons, t he magnet s shal l at t r act and hol d t he door s open. When magnet s ar e de- ener gi zed, t hey shal l r el ease t he door s.
Magnet s shal l have a hol di ng f or ce of 25 pounds. Devi ces shal l be UL or FM appr oved. Housi ng f or devi ces shal l be br ushed al umi num or st ai nl ess st eel . Oper at i on shal l be f ai l saf e wi t h no movi ng par t s.
El ect r omagnet i c door hol d- open devi ces shal l not be r equi r ed t o be hel d open dur i ng bui l di ng power f ai l ur e.
2. 10. 2 Conduit
Condui t and f i t t i ngs shal l compl y wi t h NFPA 70, UL 6, UL 1242, and UL 797.
2. 10. 3 Wiring
Wi r i ng shal l conf or m t o NFPA 70. Wi r i ng f or 120 Vac power shal l be No. 12 AWG mi ni mum. The SLC wi r i ng shal l be f i ber opt i c or copper cabl e i n accor dance wi t h t he manuf act ur er s r equi r ement s, as speci f i ed. Wi r i ng f or f i r e al ar m dc ci r cui t s shal l be No. 14 AWG mi ni mum. Vol t ages shal l not be mi xed i n any j unct i on box, housi ng, or devi ce, except t hose cont ai ni ng power suppl i es and cont r ol r el ays. Wi r i ng shal l conf or m t o NFPA 70.
Syst em f i el d wi r i ng shal l be sol i d copper and i nst al l ed i n met al l i c condui t or el ect r i cal met al l i c t ubi ng, except t hat r i gi d pl ast i c condui t may be used under s l ab- on- gr ade. Conduct or s shal l be col or coded.
Conduct or s used f or t he same f unct i ons shal l be s i mi l ar l y col or coded.
Wi r i ng code col or shal l r emai n uni f or m t hr oughout t he c i r cui t . Pi gt ai l or T- t ap connect i ons t o i ni t i at i ng devi ce c i r cui t s, super vi sor y al ar m
Apr i l 2019 Page 15 SECTI ON 28 31 64. 00 10 ci r cui t s, and not i f i cat i on appl i ance ci r cui t s ar e pr ohi bi t ed. T- t appi ng usi ng scr ew t er mi nal bl ocks i s al l owed f or st y l e 5 addr essabl e syst ems.
2. 11 TRANSMITTERS
2. 11. 1 Radi o Al ar m Tr ansmi t t er s
Tr ansmi t t er s shal l be compat i bl e wi t h pr opr i et ar y super vi s i ng st at i on r ecei v i ng equi pment . Each r adi o al ar m t r ansmi t t er shal l be t he manuf act ur er ' s r ecogni zed commer ci al pr oduct , compl et el y assembl ed, wi r ed, f act or y t est ed, and del i ver ed r eady f or i nst al l at i on and oper at i on.
Tr ansmi t t er s shal l be pr ovi ded i n accor dance wi t h appl i cabl e por t i ons of NFPA 72, NFPA 1221, and 47 CFR 15.