23 31 13.00 40.pdf

PDF 97 KB Posted

Attached to
TINKER AFB MAC BOA WWYK190023 Renovate Restrooms B117
Solicitation number
FA813726R0030
Issued by

About this file

Summary: TAFB Technical Specifications 2019 - Section 23 31 13.00 40 Metal Ducts

This document is a technical specification for metal duct systems at Tinker Air Force Base (AFB), Oklahoma, establishing comprehensive requirements for the design, fabrication, installation, and testing of low-pressure, medium-pressure, and high-pressure ductwork. The specification references industry standards from ASHRAE, SMACNA, NFPA, ASTM, AWS, AISC, UL, SAE, and SSPC to govern all aspects of duct construction and materials. Key materials specified include hot-dip galvanized carbon steel conforming to ASTM A653/A653M Designation G90 for sheet metal, silicon bronze brazing materials per AWS A5.8/A5.8M, and structural steel per ASTM A36/A36M. For low-pressure systems with maximum air velocity of 2,000 feet per minute and 2-inch water gage static pressure, minimum sheet metal thicknesses range from 26-gauge for ducts 0-12 inches wide to 22-gauge for ducts 31-60 inches wide.

The specification mandates shop fabrication of round and rectangular ducts with specific requirements for elbows, fittings, dampers, turning vanes, and sound traps. High-pressure systems must incorporate double-wall construction with 1-inch insulation layers, metal inner liners, and continuous welding or brazing of pressure shells. Installation requirements include airtight fabrication, vibration isolation for 50 feet beyond air handling units, access openings every 20 feet for cleaning purposes, and comprehensive fire damper installation per NFPA 90A. All ductwork must be leakage-tested prior to insulation installation per Section 23 05 93, with operational fire damper tests conducted in the presence of the Contracting Officer. Submittals requiring government approval include material lists, shop drawings, connection diagrams, design calculations, test reports, and record drawings. Operation and maintenance manuals must be submitted 30 calendar days prior to system testing, with final approval required no later than 30 days before contract completion.

View the file

Other files

File Type Posted
03 39 00.00 10.pdf PDF
03 62 16.pdf PDF
04 20 00.pdf PDF
05 21 00.pdf PDF
06 20 00.pdf PDF
06 61 16.pdf PDF
07 60 00.pdf PDF
07 61 14.00 20.pdf PDF
07 84 00.pdf PDF
07 92 00.pdf PDF
08 11 16.pdf PDF
08 36 13.pdf PDF
08 71 00.pdf PDF
09 68 00.pdf PDF
10 28 13.pdf PDF
13 48 00.pdf PDF
21 13 17.pdf PDF
22 00 00.pdf PDF
23 00 00.pdf PDF
23 08 00.pdf PDF
23 11 25.pdf PDF
23 35 00.pdf PDF
23 64 26.pdf PDF
23 82 16.00 40.pdf PDF
23 82 43.00 40.pdf PDF
26 56 00.pdf PDF
31 23 06.pdf PDF
32 01 14.pdf PDF
32 13 74.pdf PDF
03 11 13.00 10.pdf PDF
03 20 00.00 10.pdf PDF
03 30 00.pdf PDF
07 14 00.pdf PDF
190023 Renovate Restrooms B117 RFIs_FINAL_COR_Signed.pdf PDF
TAFB_Tech_Reqs (Div 02-48).zip ZIP file
Model.zip ZIP file
00 71 00.pdf PDF
01 78 23.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
01 32 16.00 20.pdf PDF
01 33 16.00 10.pdf PDF
01 42 00.pdf PDF
01 78 00.pdf PDF
Tinker General Requirements Specifications_Nov 2022_Change Log.pdf PDF
Initial Site Visit WWYK190023.pdf PDF
Solicitation - FA813726R0030.pdf PDF
Att10_190023_SOW.pdf PDF
EAL List - BLANK to Contractors WWYK190023.xlsx XLSX spreadsheet
Att12_190023_Drawings_Final.pdf PDF
Section L - Instructions to Offerors.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 23 31 13. 00 40

METAL DUCTS

PART 1 GENERAL

Sect i on 23 00 00 AI R SUPPLY, DI STRI BUTI ON, VENTI LATI ON, AND EXHAUST SYSTEMS appl y t o wor k speci f i ed i n t hi s sect i on.

Sect i on 23 05 48. 00 40 VI BRATI ON AND SEI SMI C CONTROLS FOR HVAC PI PI NG AND EQUI PMENT appl i es t o wor k i n t hi s sect i on.

Sect i on 40 17 30. 00 40 WELDI NG GENERAL PI PI NG appl i es t o wor k speci f i ed i n t hi s sect i on.

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN I NSTI TUTE OF STEEL CONSTRUCTI ON ( AI SC)

AI SC 325 ( 2011) St eel Const r uct i on Manual

AI SC 360 ( 2010) Speci f i cat i on f or St r uct ur al St eel Buildings

AMERI CAN SOCI ETY OF HEATI NG, REFRI GERATI NG AND AI R- CONDI TI ONI NG

ENGI NEERS ( ASHRAE)

ASHRAE EQUI P I P HDBK ( 2012) Handbook, HVAC Syst ems and Equi pment ( I P Edi t i on)

ASHRAE EQUI P SI HDBK ( 2012) Handbook, HVAC Syst ems and Equi pment ( SI Edi t i on)

ASHRAE FUN I P ( 2013; Addenda and Cor r i gendum 2013) Fundament al s Handbook, I - P Edi t i on

ASHRAE FUN SI ( 2013; Addenda and Cor r i gendum 2013) Fundament al s Handbook, SI Edi t i on

AMERI CAN WELDI NG SOCI ETY ( AWS)

AWS A5. 8/ A5. 8M ( 2011; Amendment 2012) Speci f i cat i on f or Fi l l er Met al s f or Br azi ng and Br aze Wel di ng

ASTM I NTERNATI ONAL ( ASTM)

ASTM A123/ A123M ( 2013) St andar d Speci f i cat i on f or Zi nc ( Hot - Di p Gal vani zed) Coat i ngs on I r on and St eel Pr oduct s

ASTM A36/ A36M ( 2014) St andar d Speci f i cat i on f or Car bon St r uct ur al St eel

Apr i l 2019 Page 1 SECTI ON 23 31 13. 00 40

ASTM A653/ A653M ( 2015; E 2016) St andar d Speci f i cat i on f or St eel Sheet , Zi nc- Coat ed ( Gal vani zed) or Zi nc- I r on Al l oy- Coat ed ( Gal vanneal ed) by t he Hot - Di p Pr ocess

ASTM A924/ A924M ( 2016a) St andar d Speci f i cat i on f or Gener al Requi r ement s f or St eel Sheet , Met al l i c- Coat ed by t he Hot - Di p Pr ocess

ASTM C1071 ( 2016) St andar d Speci f i cat i on f or Fi br ous Gl ass Duct Li ni ng I nsul at i on ( Ther mal and Sound Absor bi ng Mat er i al )

ASTM D257 ( 2014) St andar d Test Met hods f or D- C Resi st ance or Conduct ance of I nsul at i ng Materials

ASTM E90 ( 2009) St andar d Test Met hod f or Labor at or y Measur ement of Ai r bor ne Sound Tr ansmi ssi on Loss of Bui l di ng Par t i t i ons and El ement s

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 90A ( 2015) St andar d f or t he I nst al l at i on of Ai r Condi t i oni ng and Vent i l at i ng Syst ems

SHEET METAL AND AI R CONDI TI ONI NG CONTRACTORS' NATI ONAL ASSOCI ATI ON

(SMACNA)

SMACNA 1966 ( 2005) HVAC Duct Const r uct i on St andar ds Met al and Fl exi bl e, 3r d Edi t i on

SMACNA 1987 ( 2006) HVAC Duct Syst ems I nspect i on Gui de, 3r d Edi t i on

SOCI ETY FOR PROTECTI VE COATI NGS ( SSPC)

SSPC Pai nt i ng Manual ( 2002) Good Pai nt i ng Pr act i ce, St eel St r uct ur es Pai nt i ng Manual , Vol ume 1

SOCI ETY OF AUTOMOTI VE ENGI NEERS I NTERNATI ONAL ( SAE)

SAE AMS 2480 ( 2009; Rev H) Phosphat e Tr eat ment , Pai nt , Base

UNDERWRI TERS LABORATORI ES ( UL)

UL 181 ( 2013) Fact or y- Made Ai r Duct s and Ai r Connectors

UL 555 ( 2006; Repr i nt Aug 2016) UL St andar d f or Saf et y Fi r e Damper s

1. 2 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e For Cont r act or Qual i t y Cont r ol and f or i nf or mat i on onl y. When used, a desi gnat i on f ol l owi ng t he " G" desi gnat i on i dent i f i es t he of f i ce t hat wi l l r evi ew t he submi t t al f or t he

Apr i l 2019 Page 2 SECTI ON 23 31 13. 00 40

Gover nment . Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y Not ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00

SUBMI TTAL PROCEDURES:

SD- 01 Pr econst r uct i on Submi t t al s

Mat er i al , Equi pment , and Fi xt ur e Li st s; G

Recor ds of Exi st i ng Condi t i ons; G

SD- 02 Shop Dr awi ngs

Connect i on Di agr ams; G

Of f set Fi t t i ng Conf i gur at i ons; G

SD- 03 Pr oduct Dat a

Equi pment and Per f or mance Dat a

Gal vani zed St eel Duct wor k Mat er i al s; G

Br azi ng Mat er i al s

Mi l l - Rol l ed Rei nf or ci ng and Suppor t i ng Mat er i al s

Round Sheet Met al Duct Fi t t i ngs; G

Round, Hi gh- Pr essur e, Doubl e- Wal l Sheet Met al Duct s; G

Tur ni ng Vanes; G

Sound Tr aps; G

Fl exi bl e Connect or s; G

Fl exi bl e Duct Mat er i al s

Power Oper at ed Damper s; G

Fi r e Damper s and Wal l Col l ar s; G

Gr avi t y Backdr af t and Rel i ef Damper s; G

Manual Vol ume Damper s; G

SD- 05 Desi gn Dat a

Desi gn Anal ysi s and Cal cul at i ons; G

SD- 06 Test Repor t s

Duct wor k Leakage Test s; G

Oper at i onal Test s; G

SD- 07 Cer t i f i cat es

Apr i l 2019 Page 3 SECTI ON 23 31 13. 00 40

Li st i ng of Pr oduct I nst al l at i ons

Gal vani zed St eel Duct wor k Mat er i al s

Br azi ng Mat er i al s

Mi l l - Rol l ed Rei nf or ci ng and Suppor t i ng Mat er i al s

Round Sheet Met al Duct Fi t t i ngs

Round, Hi gh- Pr essur e, Doubl e- Wal l Sheet Met al Duct s

Tur ni ng Vanes

Dampers

Sound Tr aps

Fl exi bl e Connect or s

SD- 10 Oper at i on and Mai nt enance Dat a

Oper at i on and Mai nt enance Manual s; G

Power Oper at ed Damper s; G

Fi r e Damper s and Wal l Col l ar s; G

SD- 11 Cl oseout Submi t t al s

Recor d Dr awi ngs; G

1. 3 QUALI TY CONTROL

When f ur ni shi ng t he l i s t i ng of pr oduct i nst al l at i ons f or medi um and hi gh pr essur e duct wor k syst ems i ncl ude i dent i f i cat i on of at l east 5 uni t s, s i mi l ar t o t hose pr oposed f or use, t hat have been i n successf ul ser vi ce f or a mi ni mum per i od of 5 year s. I ncl ude pur chaser , addr ess of i nst al l at i on, ser vi ce or gani zat i on, and dat e of i nst al l at i on.

PART 2 PRODUCTS

I ncl ude t he manuf act ur er ' s st y l e or cat al og number s, speci f i cat i on and dr awi ng r ef er ence number s, war r ant y i nf or mat i on, and f abr i cat i on s i t e i nf or mat i on wi t hi n mat er i al , equi pment , and f i xt ur e l i s t s.

2. 1 SYSTEM DESCRI PTI ON

Pr ovi de l ow- pr essur e syst ems duct wor k and pl enums wher e maxi mum ai r vel oci t y i s 2, 000- f eet per mi nut e( f pm) and maxi mum st at i c pr essur e i s 2- i nches wat er gage ( wg) , posi t i ve or negat i ve.

Submi t connect i on di agr ams f or l ow pr essur e duct wor k syst ems i ndi cat i ng t he r el at i on and connect i on of devi ces and appar at us by showi ng t he gener al physi cal l ayout of al l cont r ol s, t he i nt er connect i on of one syst em ( or por t i on of syst em) wi t h anot her , and i nt er nal t ubi ng, wi r i ng, and ot her devi ces.

Hi gh vel oci t y syst ems duct wor k encompass syst ems wher e:

Apr i l 2019 Page 4 SECTI ON 23 31 13. 00 40

a. Mi ni mum ai r vel oci t y exceeds 2, 000- f eet per mi nut e ( f pm) or st at i c pr essur e exceeds 2- i nches wat er gage ( wg) .

b. Medi um st at i c pr essur e r anges f r om over 2- i nches wg t hr ough 3- i nches wg, posi t i ve or negat i ve, or over 3- i nches wg t hr ough 6- i nches wg posi t i ve.

c. Hi gh st at i c pr essur e r anges f r om over 6- i nches wg t hr ough 10- i nches wg, positive.

d. Do not use r i gi d f i br ous- gl ass duct wor k.

2. 1. 1 Desi gn Requi r ement s

Submi t r ecor ds of exi st i ng condi t i ons i ncl udi ng t he r esul t s of a sur vey consi st i ng of wor k ar ea condi t i ons, and f eat ur es of exi st i ng st r uct ur es and f aci l i t i es wi t hi n and adj acent t o t he j obsi t e.

Submi t equi pment and per f or mance dat a f or medi um and hi gh pr essur e duct wor k syst ems consi st i ng of use l i f e, syst em f unct i onal f l ows, saf et y f eat ur es, and mechani cal aut omat ed det ai l s. Submi t t est r esponse and per f or mance char act er i st i cs cur ves f or cer t i f i ed equi pment .

Submi t desi gn anal ysi s and cal cul at i ons f or duct wor k syst ems i ndi cat i ng t he manuf act ur er ' s r ecommended ai r vel oci t i es, maxi mum st at i c pr essur e, and t emper at ur e cal cul at i ons.

2. 2 COMPONENTS

2. 2. 1 Round Sheet Met al Duct Fi t t i ngs

Submi t of f set f i t t i ng conf i gur at i ons f or appr oval . Shop f abr i cat e fittings.

2. 2. 1. 1 Fi t t i ngs Const r uct i on

Manuf act ur e as separ at e f i t t i ngs, not as t ap col l ar s wel ded or br azed i nt o duct sect i ons.

Pr ovi de t wo- pi ece t ype mi t er el bows f or angl es l ess t han 31 degr ees, t hr ee- pi ece t ype f or angl es 31 t hr ough 60 degr ees, and f i ve- pi ece t ype f or angl es 61 t hr ough 90 degr ees. Ensur e cent er l i ne r adi us of el bows i s 1- 1/ 2 t i mes f i t t i ng cr oss sect i on di amet er .

Pr ovi de coni cal t ype cr osses, i ncr easer s, r educer s, r educi ng t ees, and 90- degr ee t ees.

Ensur e cut out s i n f i t t i ng body ar e equal t o br anch t ap di mensi on or , wher e smal l er , excess mat er i al i s f l ar ed and r ol l ed i nt o smoot h r adi us nozzl e configuration.

2. 2. 2 Round, Hi gh- Pr essur e, Doubl e- Wal l Sheet Met al Duct s

Shop f abr i cat e duct s and f i t t i ngs.

Const r uct i on compr i ses of an ai r t i ght , vapor bar r i er , out er pr essur e shel l , a 1 i nch i nsul at i on l ayer , and a met al i nner l i ner t hat compl et el y cover s t he i nsul at i on t hr oughout t he syst em.

Apr i l 2019 Page 5 SECTI ON 23 31 13. 00 40

Pr ovi de i nsul at i on conf or mi ng t o NFPA 90A and ASTM C1071 f or t her mal conduct i v i t y i n accor dance wi t h ASTM D257.

2. 2. 3 Reinforcement

Suppor t i nner l i ner s of bot h duct and f i t t i ngs by met al spacer s wel ded i n posi t i on t o mai nt ai n spaci ng and concent r i c i t y.

2. 2. 4 Fittings

Make di v i ded f l ow f i t t i ngs as separ at e f i t t i ngs, not t ap col l ar s i nt o duct sect i ons, wi t h t he f ol l owi ng const r uct i on r equi r ement s:

a. Sound, ai r t i ght , cont i nuous wel ds at i nt er sect i on of f i t t i ng body and tap

b. Tap l i ner secur el y wel ded t o i nner l i ner , wi t h wel d spaci ng not t o exceed 3- i nches.

c. Pack i nsul at i on ar ound t he br anch t ap ar ea f or compl et e cavi t y f i l l i ng.

d. Car ef ul l y f i t br anch connect i on t o cut out openi ngs i n i nner l i ner wi t hout spaces f or ai r er osi on of i nsul at i on and wi t hout shar p pr oj ect i ons t hat cause noi se and ai r f l ow di st ur bance.

Cont i nuousl y br aze seams i n t he pr essur e shel l of f i t t i ngs. Pr ot ect gal vani zed ar eas t hat have been damaged by wel di ng wi t h manuf act ur er ' s st andar d cor r osi on- r esi st ant coat i ng.

Const r uct t wo- pi ece t ype el bows f or angl es t hr ough 35 degr ees, t hr ee- pi ece t ype f or angl es 36 t hr ough 71 degr ees, and f i ve- pi ece t ype f or angl es 72 t hr ough 90 degr ees.

Pr ovi de coni cal t ype cr osses, i ncr easer s, r educer s, r educi ng t ees, and 90- degr ee t ees.

2. 2. 5 Tur ni ng Vanes

Pr ovi de doubl e- wal l t ype t ur ni ng vanes, commer ci al l y manuf act ur ed f or hi gh- vel oci t y syst em ser vi ce.

2. 2. 6 Dampers

Const r uct l ow pr essur e dr op, hi gh- vel oci t y manual vol ume damper s, and hi gh- vel oci t y f i r e damper s i n accor dance wi t h ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966.

2. 2. 7 Sound Tr aps

Pr ovi de sound t r aps.

Ensur e t he pr essur e dr op at t he r at ed f l ow does not exceed r at i ngs i n accor dance wi t h ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966 or desi gn cr i t er i a.

Ensur e t he sound t r ap i s ai r t i ght when oper at i ng under an i nt er nal pr essur e of 0. 37 pounds per squar e i nch. Pr ovi de an ai r - s i de sur f ace capabl e of wi t hst andi ng ai r vel oci t i es of 10, 000- f eet per mi nut e wi t hout any par t i cul at e mat t er l eavi ng t he t r ap and bei ng car r i ed downst r eam.

Apr i l 2019 Page 6 SECTI ON 23 31 13. 00 40

2. 2. 7. 1 Attenuation

Fact or y f abr i cat e sound t r aps. Conf i r m cat al oged acoust i c at t enuat i on made by an i ndependent l abor at or y i n accor dance wi t h ASTM E90. Conf i r m pr essur e dr op measur ement s i n accor dance wi t h ASHRAE EQUI P I P HDBK, Chapt er 18. For noi se- r educt i on dat a, i ncl ude ef f ect s of f l anki ng pat hs and vi br at i on t r ansmi ssi on. Conduct t est s wi t h st andar d met al i nl et and out l et connect i ons under i ndi cat ed capaci t y f l ow.

Ensur e at t enuat i on i s i n accor dance wi t h ASHRAE FUN I P. I ncl ude a gr aphi c syst em noi se spect r um cer t i f i cat i on i ndi cat i ng pr oposed f an sound power l evel . At t enuat i on of duct i ng syst em pr oposed f or i nst al l at i on i s based on ASHRAE FUN I P f or bends, br anches, and ot her duct syst em const r uct i on noi se cr i t er i a cur ve.

Reduce f an- r at ed sound- power l evel t o not l ess t han 65 deci bel s i n t he 250- her t z t hi r d oct ave band when measur ed at t he sound t r ap di schar ge end.

2. 2. 7. 2 Const r uct i on of Sound Tr aps

Pr ovi de doubl e- met al wal l ed, sound t r aps. Pr ovi de mi l l - gal vani zed sheet met al st eel wi t h commer ci al wei ght of z i nc, conf or mi ng t o ASTM A653/ A653M.

Ext er i or met al act s as a vapor bar r i er . Met al t hi ckness i s not l ess t han t hat r equi r ed f or t he pr essur e ser vi ce, i n accor dance wi t h ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966, but not l ess t han 22- gage. Cover absor bi ng mat er i al , on t he sound- i mpi ngi ng si de, wi t h f or med per f or at ed mi l l - gal vani zed st eel of not l ess t han 24- gage. Ensur e al l ext er i or sheet j oi nt s ar e cont i nuousl y wel ded, or const r uct wi t h l ockset s f i l l ed wi t h chl or opr ene mast i c pr i or t o forming.

Spot wel d i nt er i or sur f aces not mor e t han 3- i nches on cent er . Ensur e al l connect i ons t o duct t r ansi t i ons ar e f l anged wi t h t hr ough- bol t ed 1/ 8- i nch by 1- i nch cont i nuous r ubber gasket i ng. Pr ovi de vi br at i on i sol at ed t r apeze t ype suppor t s.

Pr ovi de f i br ous gl ass absor pt i on mat er i al . Ensur e sur f aces exposed t o ai r st r eam ar e chl or opr ene coat ed or pr ot ect ed wi t h woven f i br ous- gl ass c l ot h conf or mi ng t o ASTM C1071. Ensur e t he t ot al compr essed t hi ckness gi ves t he r equi r ed at t enuat i on, and t her mal i nsul at i on t o pr ecl ude condensat i on on ext er i or sur f ace under nor mal oper at i ng condi t i ons.

Compr essed mat er i al densi t y i s appr oxi mat el y 4. 5 pounds per cubi c f oot .

Sel ect mat er i al s conf or mi ng t o f i r e hazar d r equi r ement s of NFPA 90A.

2. 2. 8 Fl exi bl e Connect or s f or Sheet Met al

Use UL l i s t ed connect or s, 30- ounce per squar e yar d, wat er pr oof , f i r e- r et ar dant , ai r t i ght , woven f i br ous- gl ass c l ot h, doubl e coat ed wi t h chl or opr ene. Cl ear wi dt h, not i ncl udi ng cl ampi ng sect i on, i s 6 t o 8- i nches.

2. 2. 9 Duct Hanger s

For duct hanger s i n cont act wi t h gal vani zed duct sur f aces, pr ovi de gal vani zed st eel pai nt ed wi t h i nor gani c z i nc.

2. 2. 10 Mi l l - Rol l ed Rei nf or ci ng and Suppor t i ng Mat er i al s

Pr ovi de mi l l - r ol l ed st r uct ur al st eel conf or mi ng t o ASTM A36/ A36M.

Apr i l 2019 Page 7 SECTI ON 23 31 13. 00 40

Whenever i n cont act wi t h sheet met al duct i ng, pr ovi de gal vani zed st eel i n accor dance wi t h ASTM A123/ A123M.

I n l i eu of mi l l - r ol l ed st r uct ur al st eel , submi t equi val ent st r engt h, pr opr i et ar y- desi gn, r ol l ed- st eel st r uct ur al suppor t syst ems f or appr oval .

2. 2. 11 Fl exi bl e Duct Mat er i al s

Ensur e f l exi bl e duct connect or s compl y wi t h NFPA 90A, and conf or m wi t h UL 181, Cl ass 1 mat er i al .

2. 2. 12 Manual Vol ume Damper s

Conf or m t o SMACNA 1966 f or vol ume damper const r uct i on.

Equi p damper s wi t h an i ndi cat i ng quadr ant r egul at or wi t h a l ocki ng f eat ur e ext er nal l y l ocat ed and easi l y accessi bl e f or adj ust ment and st andof f br acket s t o al l ow mount i ng out si de ext er nal i nsul at i on. Wher e damper r od l engt hs exceed 30- i nches, pr ovi de a r egul at or at each end of damper shaf t .

2. 2. 12. 1 Damper Const r uct i on

Pr ovi de al l damper shaf t s wi t h t wo- end bear i ngs.

Ensur e spl i t t er damper i s 22 - gage sheet met al . Hi nges ar e 1/ 8- i nch t hi ck door t ype.

Pr ovi de a f ul l l engt h damper shaf t and ext end i t beyond t he damper bl ade.

use a 3/ 8 - i nch squar e shaf t f or damper l engt hs up t o 20 - i nches and a 1/ 2

- i nch squar e shaf t f or damper l engt hs 20 - i nches and l ar ger . Wher e necessar y t o pr event damper v i br at i on or s l i ppage, pr ovi de adj ust abl e suppor t r ods wi t h l ocki ng pr ovi s i ons ext er nal t o duct at damper bl ade end.

Pr ovi de damper s i n duct s havi ng a wi dt h per pendi cul ar t o t he axi s of t he damper t hat i s gr eat er t han 12 - i nches of mul t i bl ade t ype havi ng a subst ant i al f r ame wi t h bl ades f abr i cat ed of 16 - gage met al . Pr ovi de bl ades not exceedi ng 10 - i nches i n wi dt h and 48 - i nches i n l engt h, wel ded t o 1/ 2 - i nch di amet er shaf t s. Ensur e damper s gr eat er t han 48 - i nches i n wi dt h ar e made i n t wo or mor e sect i ons wi t h i nt er medi at e mul l i ons, each sect i on bei ng mechani cal l y i nt er l ocked wi t h t he adj oi ni ng sect i on or sect i ons. Pr ovi de bl ades wi t h gr aphi t e- i mpr egnat ed nyl on bear i ngs and connect so t hat adj oi ni ng bl ades r ot at e i n opposi t e di r ect i ons.

2. 2. 13 Gr avi t y Backdr af t and Rel i ef Damper s

Const r uct f r ames of not l ess t han 1- 1/ 2- by 4- i nch r ei nf or ced 16- gage gal vani zed car bon st eel . Sol i dl y secur e f r ames and mul l i ons i n pl ace and seal wi t h el ast omer caul k i ng agai nst ai r bypass.

Pr ovi de shaf t bear i ngs wi t h gr aphi t e- i mpr egnat ed nyl on .

Equi p count er bal anced damper s wi t h f i xed or adj ust abl e count er bal anci ng weights.

Gr avi t y backdr af t damper s may be equi pment manuf act ur er ' s st andar d const r uct i on i n s i zes 18 by 18 - i nch or smal l er , when f ur ni shed i nt egr al wi t h ai r movi ng equi pment .

Apr i l 2019 Page 8 SECTI ON 23 31 13. 00 40

2. 2. 13. 1 Bl ade Const r uct i on

Maxi mum bl ade wi dt h i s 9 i nches, and maxi mum bl ade l engt h i s 36 - i nches.

Bl ade mat er i al i s 16- gage gal vani zed st eel . Pr ovi de bl ades wi t h mechani cal l y r et ai ned seal s and 90- degr ee l i mi t st ops.

Bl ades l i nked t oget her f or r el i ef ser vi ce damper s ar e t o open not l ess t han 30 degr ees on 0. 05- i nch wg di f f er ent i al pr essur e.

2. 2. 14 Power - Oper at ed Damper s

Ensur e damper s conf or m t o appl i cabl e r equi r ement s speci f i ed under Sect i on

23 09 33. 00 40 ELECTRI C AND ELECTRONI C CONTROL SYSTEM FOR HVAC.

2. 2. 15 Fi r e Damper s and Wal l Col l ar s

Ensur e f i r e damper l ocat i ons ar e i n accor dance wi t h NFPA 90A.

Pr ovi de f i r e damper s i n duct wor k at f i r ewal l bar r i er s.

Const r uct and l abel f i r e damper s i n accor dance wi t h UL 555 t o pr ovi de damper and mount i ng f i r e- r esi st ance t hat equal s or exceeds f i r e- r esi st ance of t he const r uct i on i n whi ch i nst al l ed. For l i nk l oads i n excess of 20 pounds , pr ovi de UL- appr oved quar t zoi d l i nks.

Const r uct wal l col l ar s i n accor dance wi t h UL 555.

2. 3 MATERIALS

2. 3. 1 Gal vani zed St eel Duct wor k Mat er i al s

Pr ovi de hot - di p gal vani zed car bon st eel duct wor k sheet met al of l ock- f or mi ng qual i t y, wi t h r egul ar spangl e- t ype zi nc coat i ng, conf or mi ng to ASTM A924/ A924M and ASTM A653/ A653M, Desi gnat i on G90. Tr eat duct sur f aces t o be pai nt ed by anneal i ng.

Conf or m t o ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966 f or sheet met al gages and r ei nf or cement t hi ckness.

Low pr essur e duct wor k mi ni mum t hi cknesses ar e:

MI NI MUM SHEET METAL THI CKNESS

DUCT WI DTH

INCHES

GAGE

0-12 26

13-30 24

31-60 22

2. 3. 2 Br azi ng Mat er i al s

Pr ovi de si l i con br onze br azi ng mat er i al s conf or mi ng t o AWS A5. 8/ A5. 8M.

2. 3. 3 Mi l l - Rol l ed Rei nf or ci ng and Suppor t i ng Mat er i al s

Conf or m t o ASTM A36/ A36M f or mi l l - r ol l ed st r uct ur al st eel . Wher ever i n cont act wi t h sheet met al duct i ng, gal vani ze t o conf or mi ng wi t h

ASTM A123/ A123M .

Apr i l 2019 Page 9 SECTI ON 23 31 13. 00 40

I n l i eu of mi l l - r ol l ed st r uct ur al st eel , submi t f or appr oval , equi val ent st r engt h, pr opr i et ar y desi gn, r ol l ed- st eel st r uct ur al suppor t syst ems.

PART 3 EXECUTI ON

3. 1 PREPARATION

For sheet met al sur f aces t o be pai nt ed, and sur f aces t o whi ch adhesi ves ar e t o be appl i ed, c l ean sur f ace of oi l , gr ease, and del et er i ous substances.

Ensur e st r engt h i s adequat e t o pr event f ai l ur e under ser vi ce pr essur e or vacuum cr eat ed by f ast c l osur e of duct devi ces. Pr ovi de l eakt i ght , aut omat i c r el i ef devi ces.

3. 1. 1 Const r uct i on St andar ds

Pr ovi de sheet met al const r uct i on i n accor dance wi t h t he r ecommendat i ons f or best pr act i ces i n ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32, SMACNA 1966, and NFPA 90A.

Desi gn and f abr i cat e suppl ement ar y st eel i n accor dance wi t h AI SC 360 and

AI SC 325.

Wher e const r uct i on met hods f or cer t ai n i t ems ar e not descr i bed i n t he r ef er enced st andar ds or her ei n, per f or m t he wor k i n accor dance wi t h r ecommendat i ons f or best pr act i ce def i ned i n ASHRAE EQUI P I P HDBK.

3. 2 INSTALLATION

Fabr i cat e an ai r t i ght syst em. I ncl ude r ei nf or cement s, br aci ng, suppor t s, f r ami ng, gasket i ng, seal i ng, and f ast eni ng t o pr ovi de r i gi d const r uct i on and f r eedom f r om vi br at i on, ai r f l ow- i nduced mot i on and noi se, and excessi ve def l ect i on at speci f i ed maxi mum syst em ai r pr essur e and vel oci t y.

Pr ovi de of f set s and t r ansf or mat i ons as r equi r ed t o avoi d i nt er f er ence wi t h t he bui l di ng const r uct i on, pi pi ng, or equi pment .

Make pl enum anchor age pr ovi s i ons, sheet met al j oi nt s, and ot her ar eas ai r t i ght and wat er t i ght by caul k i ng, mat i ng gal vani zed st eel and concr et e sur f aces wi t h a t wo- component el ast omer .

3. 2. 1 Jointing

Encl ose damper s l ocat ed behi nd ar chi t ect ur al i nt ake or exhaust l ouver s by a r i gi d sheet met al col l ar and seal ed t o bui l di ng const r uct i on wi t h el ast omer s f or compl et e ai r t i ght ness.

Pr ovi de out si de ai r - i nt ake duct s and pl enums made f r om sheet met al wi t h sol der ed wat er t i ght j oi nt s.

3. 2. 2 Ducts

Wher ever duct s pass t hr ough f i r ewal l s or t hr ough wal l s or f l oor s di v i di ng condi t i oned spaces f r om uncondi t i oned spaces, pr ovi de a f l anged segment i n t hat sur f ace dur i ng sur f ace const r uct i on.

Wher e i nt er i or s of duct i ng may be vi ewed t hr ough ai r di f f usi on devi ces, Apr i l 2019 Page 10 SECTI ON 23 31 13. 00 40 const r uct t he v i ewed i nt er i or wi t h sheet met al and pai nt f l at bl ack.

3. 2. 2. 1 Duct wor k Cl eani ng Pr ovi s i ons

Pr ot ect open duct i ng f r om const r uct i on dust and debr i s i n a manner appr oved by t he Cont r act i ng Of f i cer . Cl ean di r t y assembl ed duct i ng by subj ect i ng al l mai n and br anch i nt er i or sur f aces t o ai r st r eams movi ng at vel oci t i es t wo t i mes speci f i ed wor ki ng vel oci t i es, at st at i c pr essur es wi t hi n maxi mum r at i ngs. Thi s may be accompl i shed by: f i l t er - equi pped por t abl e bl ower s whi ch r emai n t he Cont r act or ' s pr oper t y; wheel - mount ed, compr essed- ai r oper at ed per i met er l ances whi ch di r ect t he compr essed ai r and whi ch ar e pul l ed i n t he di r ect i on of nor mal ai r f l ow; or ot her means appr oved by t he Cont r act i ng Of f i cer . Use wat er - and oi l - f r ee compr essed ai r f or c l eani ng duct i ng. Af t er const r uct i on i s compl et e, and pr i or t o accept ance of t he wor k, r emove const r uct i on dust and debr i s f r om ext er i or sur f aces. Cl ean i n conf or mance wi t h SMACNA 1987.

3. 3 APPLICATION

3. 3. 1 Low Pr essur e Sheet Met al Duct s

Wel d angl e i r on f r ames at cor ner s and ends, whenever possi bl e. Ri vet or wel d angl e i r on r ei nf or cement s t o duct s not mor e t han 6- i nches on cent er , wi t h not l ess t han t wo poi nt s of at t achment . Spot wel di ng, wher e used, i s 3- i nches on cent er .

Seal st andar d seam j oi nt s wi t h an el ast omer compound t o compl y wi t h SMACNA 1966 Seal Cl ass A, B or C as appl i cabl e.

Li mi t cr ossbr eaki ng t o 4- f eet and pr ovi de on al l duct s 8- i nches wi de and wi der . Pr ovi de bead r ei nf or cement i n l i eu of cr ossbr eaki ng wher e panel poppi ng may occur . Wher e r i gi d i nsul at i on i s appl i ed, cr ossbr eaki ng i s not r equi r ed.

3. 3. 1. 1 Longi t udi nal Duct Seams

Pr ovi de Pi t t sbur gh l ock cor ner seams.

3. 3. 1. 2 Joi nt s and Gasket s

Bol t compani on angl e f l anges t oget her wi t h 1/ 4 - i nch di amet er bol t s and nut s spaced 6 - i nches on cent er . Gasket f l anged j oi nt s wi t h chl or opr ene f ul l - f ace gasket s 1/ 8 - i nch t hi ck, wi t h Shor e A 40 dur omet er har dness.

Use one pi ece gasket s, vul cani zed at j oi nt s.

3. 3. 1. 3 Fl exi bl e Duct Joi nt s

Bet ween f l exi bl e duct wi t hout sheet met al col l ar s and r ound met al duct wor k connect i ons make j oi nt s by t r i mmi ng t he ends, coat i ng t he i nsi de of t he f l exi bl e duct f or a di st ance equal t o dept h of i nser t i on wi t h el ast omer caul k, and by secur i ng wi t h sheet met al scr ews or bi ndi ng wi t h a st r ap clamp.

3. 3. 1. 4 Squar e El bows

Pr ovi de si ngl e- vane duct t ur ns i n accor dance wi t h SMACNA 1966, use on duct s 12 i nches i n wi dt h and nar r ower .

Apr i l 2019 Page 11 SECTI ON 23 31 13. 00 40

3. 3. 1. 5 Radi us El bows

Conf or m t o SMACNA 1966 f or r adi us el bows. Pr ovi de an i nsi de r adi us equal t o t he wi dt h of t he duct . Wher e i nst al l at i on condi t i ons pr ecl ude use of st andar d el bows, t he i nsi de r adi us may be r educed t o a mi ni mum of 0. 25 t i mes duct wi dt h. I nst al l t ur ni ng vanes i n accor dance wi t h t he f ol l owi ng schedule.

RADI US OF TURNI NG VANES I N PERCENT OF DUCT WI DTH

WI DTH OF ELBOWS

INCHES

VANE NO. 1 VANE NO. 2 VANE NO. 3

Up t o 16 56 -- --

17 t o 48 43 73 --

49 and over 37 55 83

Wher e t wo el bows ar e pl aced t oget her i n t he same pl ane f or duct s 30- i nches wi de and l ar ger , cont i nue t he gui de vanes t hr ough bot h el bows r at her t han spaced i n accor dance wi t h above schedul e.

3. 3. 1. 6 Out l et s, I nl et s, and Duct Br anches

I nst al l br anches, i nl et s, and out l et s so t hat ai r t ur bul ence i s r educed t o a mi ni mum and ai r vol ume pr oper l y appor t i oned. I nst al l adj ust abl e spl i t t er damper s at al l suppl y j unct i ons t o per mi t adj ust ment of t he amount of ai r ent er i ng t he br anch. Wher ever an ai r - di f f usi on devi ce i s shown as bei ng i nst al l ed on t he si de, t op, or bot t om of a duct , and whenever a br anch t ake- of f i s not of t he spl i t t er t ype; pr ovi de a commer ci al l y manuf act ur ed 45 degr ee si de- t ake- of f ( STO) f i t t i ng wi t h manual vol ume damper t o al l ow adj ust ment of t he ai r quant i t y and t o pr ovi de an even f l ow of ai r acr oss t he devi ce or duct i t ser vi ces.

Wher e a duct br anch i s t o handl e mor e t han 25 per cent of t he ai r handl ed by t he duct mai n, use a compl et e 90- degr ee i ncr easi ng el bow wi t h an i nsi de r adi us of 0. 75 t i mes br anch duct wi dt h. Si ze of t he l eadi ng end of t he i ncr easi ng el bow wi t hi n t he mai n duct wi t h t he same r at i o t o t he mai n duct s i ze as t he r at i o of t he r el at ed ai r quant i t i es handl ed.

Wher e a duct br anch i s t o handl e 25 per cent or l ess of t he ai r handl ed by t he duct mai n, const r uct t he br anch connect i on wi t h a 45 degr ee si de t ake- of f ent r y i n accor dance wi t h SMACNA 1966.

3. 3. 1. 7 Duct Tr ansi t i ons

Wher e t he shape of a duct changes, ensur e t he angl e of t he s i de of t he t r ansi t i on pi ece does not exceed 15 degr ees f r om t he st r ai ght r un of duct connect ed t her et o.

Wher e equi pment i s i nst al l ed i n duct wor k, ensur e t he angl e of t he s i de of t he t r ansi t i on pi ece f r om t he st r ai ght r un of duct connect ed t her et o does not exceed 15 degr ees on t he upst r eam si de of t he equi pment and 22- 1/ 2 degr ees on t he downst r eam si de of t he equi pment .

3. 3. 1. 8 Br anch Connect i ons

Const r uct r adi us t ap- i ns i n accor dance wi t h SMACNA 1966.

Apr i l 2019 Page 12 SECTI ON 23 31 13. 00 40

3. 3. 1. 9 Access Openi ngs

Const r uct access door i n accor dance wi t h SMACNA 1966, except t hat s l i di ng door s may be used onl y f or speci al condi t i ons upon pr i or appr oval .

Pr ovi de doubl e- panel t ype door s.

I nst al l access door s and panel s i n duct wor k upst r eam and downst r eam f r om coi l s adj acent t o f i r e damper s at cont r ol s or at any i t em r equi r i ng per i odi c i nspect i on, adj ust ment , mai nt enance, or c l eani ng , and ever y 20- f eet f or i ndoor ai r qual i t y housekeepi ng pur poses.

Mi ni mum access openi ng si ze i s 12 by 18 - i nches, unl ess pr ecl uded by duct di mensi ons or ot her wi se i ndi cat ed.

Make ai r t i ght access door s t hat l eak by addi ng or r epl aci ng hi nges and l at ches or by const r uct i on of new door s adequat el y r ei nf or ced, hi nged, and latched.

3. 3. 1. 10 Duct Access f or Cl eani ng

Make duct access par t i cul ar l y sui t abl e f or commer ci al duct c l eani ng met hods ut i l i z i ng vacuum devi ces. Space access openi ngs wi t h a f r equency and at poi nt s t hat per mi t s r eady access t o duct i nt er nal s wi t h essent i al l y no duct or i nsul at i on cut t i ng. Wher e access t hr ough an ai r - di f f usi on devi ce or t hr ough access door s speci f i ed her ei n i s not avai l abl e at a speci f i c poi nt , pr ovi de 8 - i nch di amet er , 16 - gage access pl at es not mor e t han 10 - f eet on cent er . Wher e duct i s i nsul at ed and vapor - seal ed, pr ovi de mast i c seal s ar ound ci r cumf er ence of access. When access pl at e i s i n pl ace and i nsul at ed, ext er nal l y i dent i f y t he l ocat i on.

3. 3. 1. 11 Pl enum Const r uct i on

Pr ovi de i nt ake and di schar ge pl enum compani on angl e j oi nt s wi t h t he f ol l owi ng mi ni mum t hi ckness of mat er i al s:

LONGEST ANGLES

SI DE

INCHES

SHEET METAL

USS GAGE

ALL SI DES

COMPANI ON ANGLES

INCHES

REINFORCEMENT

24 I NCHES ON

CENTER MAXI MUM

To 48 20 1- 1/ 2 by 1- 1/ 2 by 1/8

1- 1/ 2 by 1- 1/ 2 by 1/ 8

49 t o 84 18 2 by 2 by 1/ 8 2 by 2 by 3/ 16

85 t o 120 16 2 by 2 by 1/ 8 2 by 2 by 1/ 8

121 and l ar ger 14 2 by 2 by 3/ 16 2 by 2 by 3/ 16

At t he f l oor l i ne and ot her poi nt s wher e pl enums j oi n masonr y const r uct i on, bol t panel s 12 - i nches on cent er t o 2- by 2- by 3/ 16 - i nch t hi ck hot - di p gal vani zed st eel angl e t hat has been secur ed t o t he masonr y wi t h masonr y anchor s and bol t s 24- i nches on cent er and caul ked t i ght t o t he masonr y.

Anchor panel s t o cur bi ng wi t h hot - di p gal vani zed st eel angl e i r on of a s i ze not l ess t han 2- by 2- by 3/ 16 - i nch t hi ck. Concr et e cur bi ng i ncl udes angl e i r on nosi ng wi t h wel ded st uds f or t he anchor i ng of panel s.

Level nosi ng at cur b hei ght wi t hi n pl us or mi nus 1/ 16 - i nch.

Apr i l 2019 Page 13 SECTI ON 23 31 13. 00 40

Wel d and gr i nd mi t er cor ner s f or angl e i r on and channel i r on.

3. 3. 1. 12 Pl enum Door Const r uct i on

Const r uct pl enum access door s i n accor dance wi t h SMACNA 1966 except t hat access door s smal l er t han man- access door s have door openi ngs f r amed wi t h angl e i r on t hat i s one commer ci al s i ze smal l er t han t he speci f i ed panel reinforcement.

Ensur e man- access door s i ze conf or ms t o SMACNA 1966 and par agr aph ACCESS OPENI NGS. I nsul at ed and uni nsul at ed const r uct i on i s per SMACNA 1966.

Fr ame door openi ngs wi t h channel i r on. Fr ame door s wi t h angl e i r on.

Si ze channel i r on and angl e i r on appr oxi mat el y t he same si ze as speci f i ed panel r ei nf or cement . Pr ovi de ext er i or door ski n 16 gage. Fabr i cat e l at ches f r om st eel wi t h hi nges at l east 4 - i nches l ong, and bol t s at l east 3/ 8 - i nch di amet er .

3. 3. 1. 13 Manual Vol ume Damper s

Pr ovi de bal anci ng damper s of t he spl i t t er , but t er f l y, or mul t i l ouver t ype, t o bal ance each r espect i ve mai n and br anch duct .

For damper s r egul at ed t hr ough cei l i ngs pr ovi de a r egul at or conceal ed i n a box mount ed i n t he cei l i ng, wi t h a cover f i ni sh aest het i cal l y compat i bl e wi t h cei l i ng sur f ace. Wher e cei l i ng i s of r emovabl e const r uct i on, set r egul at or s above t he cei l i ng, and mar k t he l ocat i on on cei l i ng i n a manner accept abl e t o t he Cont r act i ng Of f i cer .

3. 3. 1. 14 Fl exi bl e Connect or s f or Sheet Met al

Connect ai r handl i ng equi pment , duct s cr ossi ng bui l di ng expansi on j oi nt s, and f an i nl et s and out l et s t o upst r eam and downst r eam component s by t r eat ed woven- cl ot h connect or s.

I nst al l connect or s onl y af t er syst em f ans ar e oper at i ve, and vi br at i on i sol at i on mount i ngs have been adj ust ed. When syst em f ans ar e oper at i ng, ensur e connect or s ar e f r ee of wr i nkl es caused by mi sal i gnment or f an r eact i on. Wi dt h of sur f ace i s cur vi l i near .

3. 3. 2 Rect angul ar Sheet Met al Duct s

3. 3. 2. 1 Medi um- Pr essur e Gages, Joi nt s, and Rei nf or cement

Ensur e mi ni mum sheet met al gages, j oi nt s, and r ei nf or cement s bet ween j oi nt s ar e i n accor dance wi t h ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966.

Ensur e sheet met al mi ni mum t hi ckness, t r ansver se r ei nf or cement bet ween j oi nt s, and j oi nt s of duct s ar e i n accor dance wi t h t he f ol l owi ng:

Apr i l 2019 Page 14 SECTI ON 23 31 13. 00 40

LONGEST

SIDE

(INCHES)

SHEET

METAL

GAGE

ALL SI DES

COMPANI ON ANGLE

(INCHES)

REI NFORCEMENT ANGLES

24 I NCHES ON

CENTER MAXI MUM

( BACK TO BACK)

97 t o 108 16 2 by 2 by 1/ 8, t wo t i e r ods al ong angl e

Two 2 by 2 by 1/ 8, t wo t i e r ods al ong angle

109 t o 132 16 2 by 2 by 3/ 16, t wo t i e r ods al ong angl e

Two 2 by 2 by 3/ 16, t wo t i e r ods al ong angle

133 and l onger 14 2 by 2 by 3/ 16, wi t h t i e r ods ever y 48 i nches

Two 2 by 2 by 3/ 16, wi t h t i e r ods ever y 48 inches

3. 3. 2. 2 Medi um- And Hi gh- Pr essur e Br anches, I nl et s, Out l et s

I nst al l br anches, i nl et s, and out l et s t o mi ni mi ze ai r t ur bul ence and t o ensur e pr oper ai r f l ow.

I nst al l damper s so t hat t he amount of ai r ent er i ng duct mai ns i s adjustable.

Pr ovi de commer ci al l y manuf act ur ed ai r ext r act or s t o al l ow adj ust ment of t he ai r quant i t y and t o pr ovi de an even f l ow of ai r acr oss t he devi ce or duct ser ved.

3. 3. 2. 3 Duct Br anch Tr ansi t i on

Wher e a duct br anch handl es over 25 per cent of t he ai r t r anspor t ed by t he duct mai n, use a compl et e 90- degr ee i ncr easi ng el bow, wi t h an i nsi de r adi us of 0. 75 t i mes duct br anch wi dt h. Ensur e t he s i ze of t he t r ai l i ng end of t he i ncr easi ng el bow wi t hi n t he mai n duct has t he same r at i o t o t he mai n duct s i ze as t he r at i o of t he r el at i ve ai r quant i t i es handl ed.

Wher e a duct br anch i s t o handl e 25 per cent or l ess of t he ai r handl ed by t he duct mai n, pr ovi de a br anch connect i on wi t h an i nsi de r adi us of 0. 75 t i mes br anch duct wi dt h, a mi ni mum ar c l engt h of 45 degr ees, and an out si de r adi us of 1. 75 t i mes duct br anch wi dt h. Pl ace ar c t angent t o duct main.

3. 3. 2. 4 Hi gh- Pr essur e Gages, Joi nt s, and Rei nf or cement

Ensur e sheet met al mi ni mum t hi ckness, j oi nt s, and r ei nf or cement bet ween j oi nt s ar e i n accor dance wi t h ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966.

Use t he f ol l owi ng t ypes of ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966 j oi nt s and seams:

Tr ansver se Joi nt s:

a. Wel ded f l ange j oi nt wi t h angl e

b. Compani on angl e f l anged j oi nt

Longi t udi nal Seams:

Apr i l 2019 Page 15 SECTI ON 23 31 13. 00 40

a. Appr oved l ock seams, back br azed, or cont i nuousl y br azed seams f or duct s wi t h l ar gest di mensi on up t o 72- i nches

b. Cont i nuousl y wel ded or br azed seams f or duct s wi t h l ar gest di mensi on gr eat er t han 72- i nches

Sheet met al mi ni mum t hi ckness, t r ansver se r ei nf or cement bet ween j oi nt s, and compani on angl e j oi nt s of duct s wi t h l ongest s i de gr eat er t han 96 i nches ar e i n accor dance wi t h t he f ol l owi ng:

LONGEST

SIDE

(inches)

SHEET METAL

GAGE

ALL SI DES

COMPANI ON ANGLE

(inches)

REI NFORCEMENT ANGLES

24 I NCHES ON

CENTER MAXI MUM

( BACK TO BACK)

97 t o 108 16 2 by 2 by 1/ 8, t wo t i e r ods al ong angl e

* Two 2 by 2 by 1/ 8, t wo t i e r ods al ong angl e

109 t o 132 16 2 by 2 by 3/ 16, t wo t i e r ods al ong angl e

* Two 2 by 2 by 3/ 16, t wo t i e r ods al ong angl e

133 and l onger 14 2- 1/ 2 by 2- 1/ 2 by 3/ 16, wi t h t i e r ods ever y 24 i nches

* Two 2- 1/ 2 by 2- 1/ 2 by 3/16, wi t h t i e r ods ever y 24 i nches

3. 3. 3 Round Sheet Met al Duct s

3. 3. 3. 1 Duct Gages and Rei nf or cement

Sheet met al mi ni mum t hi ckness, j oi nt s, and r ei nf or cement bet ween j oi nt s shal l be i n accor dance wi t h ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966.

Pr ovi de duct s wi t h suppl ement al gi r t h angl e suppor t s, r i vet ed wi t h sol i d r i vet s 6 i nches on cent er t o duct . Locat e gi r t h angl es as f ol l ows:

DI AMETER, I NCHES REI NFORCEMENT- MAXI MUM SPACI NG

INCHES

25 t o 36 1- 1/ 4 by 1- 1/ 4, 1/ 8 t hi ck, 72 i nches on center

37 t o 50 1- 1/ 4 by 1- 1/ 4, 1/ 8 t hi ck, 60 i nches on center

51 t o 60 1- 1/ 2 by 1- 1/ 2, 1/ 8 t hi ck, 48 i nches on center

Use hex- shaped bol t heads and nut s, 5/ 16- i nch di amet er f or duct s up t o 50- i nch di amet er , and 3/ 8- i nch di amet er f or 51- i nch di amet er duct s and larger.

Cont i nuousl y wel d f l anges t o duct on out si de of duct and i nt er mi t t ent l y wel ded wi t h 1- i nch wel ds ever y 4- i nches on i nsi de j oi nt f ace. Remove

Apr i l 2019 Page 16 SECTI ON 23 31 13. 00 40 excess f i l l er met al f r om i nsi de f ace. Pr ot ect gal vani zed ar eas t hat have been damaged by wel di ng wi t h manuf act ur er ' s st andar d cor r osi on- r esi st ant coating.

3. 3. 3. 2 Duct Joi nt s

Pr ovi de duct j oi nt s manuf act ur ed by machi ne, wi t h spi r al l ockset s up t o and i ncl udi ng 60- i nch di amet er s, and t o di mensi onal t ol er ances compat i bl e wi t h f i t t i ngs pr ovi ded. Dr aw- band gi r t h j oi nt s ar e not accept abl e.

Pr epar e s l i p j oi nt s by coat i ng t he mal e f i t t i ng wi t h el ast omer seal i ng mat er i al s, exer ci s i ng car e t o pr event mast i c f r om ent er i ng f i t t i ng bor e.

Leave onl y a t hi n annul ar mast i c l i ne exposed i nt er nal l y. Use sheet met al scr ews t o make assembl y r i gi d, not l ess t han f our scr ews per j oi nt , maxi mum spaci ng 6- i nches. Do not use pop r i vet s. Tape and heat seal al l joints.

3. 3. 3. 3 Duct Tr ansi t i ons

Wher e t he shape of a duct changes, ensur e t he angl e of t he s i de of t he t r ansi t i on pi ece does not exceed 15 degr ees f r om t he st r ai ght r un of duct connect ed t her et o.

Wher e equi pment i s i nst al l ed i n duct wor k, ensur e t he angl e of t he s i de of t he t r ansi t i on pi ece f r om t he st r ai ght r un of duct connect ed t her et o does not exceed 15 degr ees on t he upst r eam si de of t he equi pment and 22- 1/ 2 degr ees on t he downst r eam si de of t he equi pment .

3. 3. 4 Round, Hi gh Pr essur e, Sheet Met al Duct I nst al l at i on

3. 3. 4. 1 Joints

Pr ovi de an i nner coupl i ng t o al i gn t he i nner l i ni ng t o mai nt ai n good ai r f l ow condi t i ons equi val ent t o st andar d r ound hi gh- pr essur e duct j oi nt s. But t j oi nt s ar e not sui t abl e f or t he i nner l i ner . Accompl i sh t hi s al i gnment by . For duct s over 34- i nches i nsi de di amet er , pr ovi de a separ at e coupl i ng f or i nner al i gnment , wi t h t he pr essur e shel l s j oi ned by angl e- r i ng f l anged connect i ons.

3. 3. 4. 2 I nsul at i on Ends

At t he end of an uni nsul at ed sect i on or r un wher e i nt er nal l y i nsul at ed duct connect s t o uni nsul at ed spi r al duct , f i t t i ng, f i r e damper or f l exi bl e duct , i nst al l an i nsul at ed end- f i t t i ng t o br i ng t he out er pr essur e shel l down t o nomi nal s i ze.

3. 3. 5 Tr ansver se Rei nf or cement Joi nt s

Pr ovi de t r ansver se r ei nf or cement s t hat ar e . Wel d t r ansver se r ei nf or cement at al l cor ner s t o f or m cont i nuous f r ames.

3. 3. 6 Joi nt Gasket s

For f l anged j oi nt s, use chl or opr ene f ul l - f ace gasket s 1/ 8- i nch t hi ck, wi t h Shor e A 40 dur omet er har dness. Use one- pi ece gasket s, vul cani zed at joints.

Apr i l 2019 Page 17 SECTI ON 23 31 13. 00 40

3. 3. 7 Radi us El bows

Fabr i cat e el bow pr opor t i ons and r adi us el bows i n accor dance wi t h ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966.

3. 3. 8 Pl enum Connect i ons

Ensur e r ound duct connect i ons ar e wel ded j oi nt bel l mout h t ype.

Ensur e r ect angul ar duct connect i ons ar e bel l mout h t ype, const r uct ed i n accor dance wi t h ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966.

3. 3. 9 Access Openi ngs

I nst al l access panel s i n duct wor k adj acent t o f i r e damper s.

Mi ni mum si ze of access openi ng i s 12 by 18 i nches, unl ess pr ecl uded by duct di mensi on.

Fr ame access openi ngs wi t h wel ded and gr ound mi t er j oi nt s, 1/ 8- i nch t hi ck angl e i r on, wi t h 1/ 4 - i nch st uds wel ded t o f r ame. Ensur e cover pl at es ar e not l ess t han 16- gage, r ei nf or ced as necessar y f or l ar ger s i zes const r uct ed of 12- gage met al .

I n l i eu of access door s, use r eadi l y accessi bl e f l anged duct sect i ons upon appr oval . Pr ovi de st abl e hanger suppor t s f or di sconnect ed duct t er mi nal .

3. 3. 10 Duct Suppor t s

I nst al l duct suppor t i n accor dance wi t h ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966. Meet t he mi ni mum si ze f or duct hanger s as speci f i ed i n ASHRAE EQUI P I P HDBK, Chapt er 16, ASHRAE FUN I P, Chapt er 32 and SMACNA 1966. Pr ovi de t wo hanger s wher e necessar y t o el i mi nat e sway. Suppor t at t achment t o duct sur f aces by wel di ng 4- i nches on cent er .

Take t he f ol l owi ng i nt o account i n sel ect i on of a hangi ng syst em:

a. Locat i on and pr ecedence of wor k under ot her sect i ons

b. I nt er f er ences of var i ous pi pi ng and el ect r i cal condui t

c. Equi pment , and bui l di ng conf i gur at i on

d. St r uct ur al and saf et y f act or r equi r ement s

e. Vi br at i on, and i mposed l oads under nor mal and abnor mal ser vi ce conditions

Suppor t s i zes, conf i gur at i ons, and spaci ng ar e gi ven t o show t he mi ni mal t ype of suppor t i ng component s r equi r ed. I f i nst al l ed l oads ar e excessi ve f or t he speci f i ed hanger spaci ng, hanger s, and accessor i es pr ovi de heavi er - dut y component s . Af t er syst em st ar t up, r epl ace any duct suppor t devi ce whi ch due t o l engt h, conf i gur at i on, or s i ze, v i br at es or causes possi bl e f ai l ur e of a member . Do not use a duct wor k suppor t syst em t hat al l ows a cascade- t ype f ai l ur e t o occur .

Do not hang duct wor k and equi pment f r om r oof deck, pi pi ng, or ot her duct s

Apr i l 2019 Page 18 SECTI ON 23 31 13. 00 40 or equi pment . Maxi mum span bet ween any t wo poi nt s i s 10- f eet , wi t h l esser spans as r equi r ed by duct assembl i es, i nt er f er ences, and per mi t t ed l oads imposed.

Wher e suppor t f r om met al deck syst ems i s i nvol ved, coor di nat e suppor t r equi r ement s wi t h i nst al l at i on of met al deck.

3. 3. 10. 1 Hangars

At t ach hanger r ods, angl es, and st r aps t o beam cl amps. Recei ve appr oval f r om t he Cont r act i ng Of f i cer f or concr et e i nser t s, masonr y anchor s, and f ast ener s f or t he appl i cat i on.

Har dened hi gh- car bon spr i ng- st eel f ast ener s f i t t ed ont o beams and mi scel l aneous st r uct ur al st eel ar e accept abl e upon pr i or appr oval of each pr oposed appl i cat i on and upon f i el d demonst r at i on of conf or mance t o speci f i cat i on r equi r ement s. Make f ast ener s f r om st eel conf or mi ng t o AI SI Type 1055 1070, t r eat ed and f i ni shed i n conf or mance wi t h SAE AMS 2480, Type Z ( z i nc phosphat e base) , Cl ass 2 ( suppl ement ar y t r eat ment ) . Ver i f y a 72- hour l oad- car r y i ng capaci t y by a cer t i f i ed i ndependent l abor at or y.

Wher e duct wor k syst em cont ai ns heavy equi pment , excl udi ng ai r - di f f usi on devi ces and si ngl e- l eaf damper s, hang such equi pment i ndependent l y of t he duct wor k by means of r ods or angl es of s i zes adequat e t o suppor t t he l oad.

Cr oss- br ace hanger s t o pr ecl ude swayi ng bot h ver t i cal l y and l at er al l y.

3. 3. 10. 2 Installation

Ensur e hanger spaci ng gi ves a 20- t o- 1 saf et y f act or f or suppor t ed l oad.

Maxi mum l oad suppor t ed by any t wo f ast ener s i s 100 pounds.

I nst al l hanger s on bot h s i des of al l duct t ur ns, br anch f i t t i ngs, and transitions.

Fr i ct i on r od assembl i es ar e not accept abl e.

3. 3. 10. 3 St r ap- t ype Hangar s

Suppor t r ect angul ar duct s up t o 36- i nches by st r ap- t ype hanger s at t ached at not l ess t han t hr ee pl aces t o not l ess t han t wo duct sur f aces i n di f f er ent pl anes.

Per f or at ed st r ap hanger s ar e not accept abl e.

3. 3. 10. 4 Tr apeze Hangar s

Suppor t r ect angul ar duct i ng, 36- i nches and l ar ger , by t r apeze hanger s.

Suppor t duct s s i t uat ed i n uncondi t i oned ar eas and r equi r ed t o have i nsul at i on wi t h a vapor - seal ed f aci ng on t r apeze hanger s. Space hanger s f ar enough out f r om t he si de of t he duct t o per mi t t he duct i nsul at i on t o be pl aced on t he duct i nsi de t he t r apeze. Do not penet r at e t he vapor - seal ed f aci ng wi t h duct hanger s.

Wher e t r apeze hanger s ar e used, suppor t t he bot t om of t he duct on angl es s i zed as f ol l ows:

Apr i l 2019 Page 19 SECTI ON 23 31 13. 00 40

WI DTH OF DUCT,

I NCHES

MI NI MUM BOTTOM ANGLE SI ZE,

I NCHES

30 and smal l er 1- 1/ 4 by 1- 1/ 4 by 1/ 8

31 t o 48 1- 1/ 2 by 1- 1/ 2 by 1/ 8

49 t o 72 1- 1/ 2 by 1- 1/ 2 by 3/ 16

73 t o 96 2 by 2 by 1/ 4

97 and wi der 3 by 3 by 1/ 4

3. 3. 10. 5 Purlins

Do not suppor t duct i ng f r om r oof pur l i ns at poi nt s gr eat er t han one- si xt h of t he pur l i n span f r om t he r oof t r uss. Do not exceed 400 pounds l oad per hanger.

I f t he hanger l oad must exceed t he above l i mi t , pr ovi de r ei nf or ci ng of pur l i n( s) or addi t i onal suppor t beam( s) . When an addi t i onal beam i s used, have t he beam bear on t he t op chor d of t he r oof t r usses, and al so bear over t he gusset pl at es of t op chor d. St abi l i ze t he beam by connect i on t o r oof pur l i n al ong bot t om f l ange.

Pur l i ns used f or suppor t i ng f i r e- pr ot ect i on spr i nkl er mai ns, el ect r i cal l i ght i ng f i x t ur es, el ect r i cal power duct s, or cabl e t r ays ar e consi der ed f ul l y l oaded. Pr ovi de suppl ement al r ei nf or ci ng or auxi l i ar y suppor t st eel f or t hese pur l i ns when used t o suppor t duct wor k.

3. 3. 10. 6 Vi br at i on I sol at i on

I sol at e t he st r uct ur e f r om duct suppor t v i br at i on at poi nt s i ndi cat ed.

Ref er t o Sect i on 23 05 48. 00 40 VI BRATI ON AND SEI SMI C CONTROLS FOR HVAC

PI PI NG AND EQUI PMENT.

Pr ovi de vi br at i on i sol at or s i n di schar ge duct i ng syst em f or a di st ance not l ess t han 50- f eet beyond t he ai r handl i ng uni t . Coor di nat e def l ect i on of duct and equi pment mount i ngs.

3. 3. 11 Fl exi bl e Connect or s f or St eel Met al

Connect ai r - handl i ng equi pment , duct s cr ossi ng bui l di ng expansi on j oi nt s, and f an i nl et s and out l et s t o upst r eam and downst r eam component s wi t h t r eat ed woven- cl ot h connect or s.

I nst al l connect or s onl y af t er syst em f ans ar e oper at i ve and al l v i br at i on i sol at i on mount i ngs have been adj ust ed. When syst em f ans ar e oper at i ng, ensur e connect or s ar e f r ee of wr i nkl es caused by mi sal i gnment or f an r eact i on. Wi dt h of sur f ace i s cur vi l i near .

3. 3. 12 I nsul at i on Pr ot ect i on Angl es

Pr ovi de gal vani zed 20- gage sheet , f or med i nt o an angl e wi t h a 2- i nch exposed l ong l eg wi t h a 3/ 8- i nch st i f f eni ng br eak at out er edge, and wi t h a var i abl e conceal ed l eg, dependi ng upon i nsul at i on t hi ckness.

I nst al l angl es over al l i nsul at i on edges t er mi nat i ng by but t i…