This is a technical specification document for steel standing seam roofing systems at Tinker Air Force Base, Oklahoma, dated April 2019.

The specification requires a complete standing seam metal roof system (SSMRS) from a single manufacturer with a minimum five-year history manufacturing similar systems and involvement in at least five comparable projects. Roofing panels must be continuous lengths with no joints except at specified locations, fabricated from zinc-coated steel (ASTM A653/A653M, G90) or aluminum-zinc alloy-coated steel (ASTM A792/A792M, AZ55) with minimum thickness of 0.023 inch (24 gage), or 0.030 inch (22 gage) if mid-field experiences wind uplift of 60 psf or greater. Steel roofing materials must contain minimum 30 percent recycled content and be Energy Star labeled with initial solar reflectance greater than or equal to 0.25. Panels require factory-applied thermally cured coatings with 70 percent resin polyvinylidene fluoride exterior finish at 0.2 mil dry film thickness minimum. The system must resist wind loads based on 120 mph basic wind speed with design uplift factors of 3.0 for single fasteners and 2.25 for multiple fasteners per connection, support 20 psf minimum live load, accommodate thermal movement across 10°F to 140°F temperature range, and limit deflection to L/180 of span. Installation requires manufacturer's technical representative field inspections during first 20 squares and substantial completion, with a manufacturer's 20-year no-dollar-limit materials and workmanship warranty plus contractor two-year installation warranty. All components including clips, closures, fasteners, sealants, and accessories must be from the same manufacturer system. Submittals require government approval for shop drawings, product data, design calculations, field inspection reports, and manufacturer certifications.

View the file

Other files

File Type Posted
03 39 00.00 10.pdf PDF
03 62 16.pdf PDF
04 20 00.pdf PDF
05 21 00.pdf PDF
06 20 00.pdf PDF
06 61 16.pdf PDF
07 60 00.pdf PDF
07 84 00.pdf PDF
07 92 00.pdf PDF
08 11 16.pdf PDF
08 36 13.pdf PDF
08 71 00.pdf PDF
09 68 00.pdf PDF
10 28 13.pdf PDF
13 48 00.pdf PDF
21 13 17.pdf PDF
22 00 00.pdf PDF
23 00 00.pdf PDF
23 08 00.pdf PDF
23 11 25.pdf PDF
23 35 00.pdf PDF
23 64 26.pdf PDF
23 82 16.00 40.pdf PDF
23 82 43.00 40.pdf PDF
26 56 00.pdf PDF
31 23 06.pdf PDF
32 01 14.pdf PDF
32 13 74.pdf PDF
02 41 00.pdf PDF
06 10 00.pdf PDF
07 12 00.pdf PDF
07 42 13.pdf PDF
07 42 63.pdf PDF
07 53 23.pdf PDF
07 54 19.pdf PDF
07 62 13.pdf PDF
08 41 13.pdf PDF
08 51 13.pdf PDF
08 51 23.pdf PDF
09 51 00.pdf PDF
09 65 00.pdf PDF
00 71 00.pdf PDF
01 78 23.pdf PDF
00 72 00.pdf PDF
00 80 00.pdf PDF
Solicitation - FA813726R0030.pdf PDF
Att10_190023_SOW.pdf PDF
EAL List - BLANK to Contractors WWYK190023.xlsx XLSX spreadsheet
Att11_190023_Submittal Register_Final.pdf PDF
Wage Determination.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 07 61 14. 00 20

STEEL STANDI NG SEAM ROOFI NG

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN I RON AND STEEL I NSTI TUTE ( AI SI )

AI SI SG03- 3 ( 2002; Suppl 2001- 2004; R 2008) Col d- For med St eel Desi gn Manual Set

ASTM I NTERNATI ONAL ( ASTM)

ASTM A1008/ A1008M ( 2015) St andar d Speci f i cat i on f or St eel , Sheet , Col d- Rol l ed, Car bon, St r uct ur al , Hi gh- St r engt h Low- Al l oy and Hi gh- St r engt h Low- Al l oy wi t h I mpr oved For mabi l i t y , Sol ut i on Har dened, and Bake Har dened

ASTM A1011/ A1011M ( 2015) St andar d Speci f i cat i on f or St eel , Sheet , and St r i p, Hot - Rol l ed, Car bon, St r uct ur al , Hi gh- St r engt h Low- Al l oy and Hi gh- St r engt h Low- Al l oy wi t h I mpr oved For mabi l i t y and Ul t r a- Hi gh St r engt h

ASTM A36/ A36M ( 2014) St andar d Speci f i cat i on f or Car bon St r uct ur al St eel

ASTM A653/ A653M ( 2015; E 2016) St andar d Speci f i cat i on f or St eel Sheet , Zi nc- Coat ed ( Gal vani zed) or Zi nc- I r on Al l oy- Coat ed ( Gal vanneal ed) by t he Hot - Di p Pr ocess

ASTM A792/ A792M ( 2010) St andar d Speci f i cat i on f or St eel Sheet , 55% Al umi num- Zi nc Al l oy- Coat ed by t he Hot - Di p Pr ocess

ASTM B117 ( 2016) St andar d Pr act i ce f or Oper at i ng Sal t Spr ay ( Fog) Appar at us

ASTM D1654 ( 2008) Eval uat i on of Pai nt ed or Coat ed Speci mens Subj ect ed t o Cor r osi ve Environments

ASTM D2244 ( 2015a) Cal cul at i on of Col or Tol er ances and Col or Di f f er ences f r om I nst r ument al l y Measur ed Col or Coor di nat es

ASTM D2247 ( 2015) Test i ng Wat er Resi st ance of Coat i ngs i n 100% Rel at i ve Humi di t y

Apr i l 2019 Page 1 SECTI ON 07 61 14. 00 20

ASTM D226/ D226M ( 2009) St andar d Speci f i cat i on f or Asphal t - Sat ur at ed Or gani c Fel t Used i n Roof i ng and Wat er pr oof i ng

ASTM D4214 ( 2007; R 2015) St andar d Test Met hod f or Eval uat i ng t he Degr ee of Chal k i ng of Ext er i or Pai nt Fi l ms

ASTM D522/ D522M ( 2014) Mandr el Bend Test of At t ached Or gani c Coat i ngs

ASTM D523 ( 2014) St andar d Test Met hod f or Specul ar Gloss

ASTM D714 ( 2002; R 2009) Eval uat i ng Degr ee of Bl i st er i ng of Pai nt s

ASTM D968 ( 2015) Abr asi on Resi st ance of Or gani c Coat i ngs by Fal l i ng Abr asi ve

ASTM E1592 ( 2005; R 2012) St r uct ur al Per f or mance of Sheet Met al Roof and Si di ng Syst ems by Uni f or m St at i c Ai r Pr essur e Di f f er ence

ASTM E84 ( 2015b) St andar d Test Met hod f or Sur f ace Bur ni ng Char act er i st i cs of Bui l di ng Materials

ASTM G152 ( 2013) Oper at i ng Open Fl ame Car bon Ar c Li ght Appar at us f or Exposur e of Nonmet al l i c Mat er i al s

ASTM G153 ( 2013) Oper at i ng Encl osed Car bon Ar c Li ght Appar at us f or Exposur e of Nonmet al l i c Materials

SHEET METAL AND AI R CONDI TI ONI NG CONTRACTORS' NATI ONAL ASSOCI ATI ON

(SMACNA)

SMACNA 1793 ( 2012) Ar chi t ect ur al Sheet Met al Manual , 7t h Edi t i on

U. S. DEPARTMENT OF ENERGY ( DOE)

Ener gy St ar ( 1992; R 2006) Ener gy St ar Ener gy Ef f i c i ency Label i ng Syst em ( FEMP)

1. 2 DEFINITIONS

1. 2. 1 Fi el d- For med Seam

Seams of panel s so conf i gur ed t hat when adj acent sheet s ar e i nst al l ed t he seam i s seal ed ut i l i z i ng mechani cal or hand seamer s. Cr i mped ( 45 degr ee bend) , r ol l f or med ( 180 degr ee bend) , doubl e r ol l f or med ( 2 - 180 degr ee bends) , and r ol l and l ock syst ems ar e t ypes of f i el d- f or med seam syst ems.

1. 2. 2 Snap Toget her Seam

Panel s so conf i gur ed t hat t he mal e and f emal e por t i ons of t he seam

Apr i l 2019 Page 2 SECTI ON 07 61 14. 00 20 i nt er l ock t hr ough t he appl i cat i on of f oot pr essur e or t ampi ng wi t h a mal l et . Snap- on cap conf i gur at i ons ar e a t ype of snap t oget her syst em.

1. 2. 3 Pre-Formed

For med t o t he f i nal , l ess f i el d- f or med seam, pr of i l e and conf i gur at i on i n t he f act or y.

1. 2. 4 Field-Formed

For med t o t he f i nal , l ess f i el d- f or med seam, pr of i l e and conf i gur at i on at t he s i t e of wor k pr i or t o i nst al l at i on.

1. 2. 5 Roof i ng Syst em

The r oof i ng syst em i s def i ned as t he assembl y of r oof i ng component s, i ncl udi ng r oof i ng panel s, f l ashi ng, f ast ener s, and accessor i es whi ch, when assembl ed pr oper l y r esul t i n a wat er t i ght i nst al l at i on.

1. 2. 6 SSMRS

St andi ng Seam Met al Roof Syst em ( SSMRS) i s abbr evi at i on of t he ent i r e r oof syst em speci f i ed her ei n wi t h al l component s and par t s comi ng f r om a si ngl e manuf act ur er ' s syst em.

1. 3 SYSTEM DESCRI PTI ON

1. 3. 1 Desi gn Requi r ement s

a. Panel s must be cont i nuous l engt hs up t o manuf act ur er ' s st andar d l ongest l engt hs, wi t h no j oi nt s or seams, except wher e i ndi cat ed or speci f i ed. Ri bs of adj oi ni ng sheet s must be i n cont i nuous cont act f r om eave t o r i dge. I ndi v i dual panel s of snap t oget her t ype syst ems must be r emovabl e f or r epl acement of damaged mat er i al .

b. Ther e must be no exposed or penet r at i ng f ast ener s except wher e shown on appr oved shop dr awi ngs. Fast ener s i nt o st eel must be st ai nl ess st eel , z i nc cast head, or cadmi um pl at ed st eel scr ews i nser t ed i nt o pr edr i l l ed hol es. Ther e must be a mi ni mum of t wo f ast ener s per c l i p.

Si ngl e f ast ener s wi l l be al l owed when suppor t i ng st r uct ur al member s ar e pr epunched or pr edr i l l ed.

c. Snap t oget her t ype syst ems must have a capi l l ar y br eak and a posi t i ve s i de l ap l ocki ng devi ce. Fi el d- f or med seam t ype syst ems must be mechani cal l y l ocked cl osed by t he manuf act ur er ' s l ocki ng t ool . The seam must i ncl ude a cont i nuous f act or y appl i ed seal ant when r equi r ed by t he manuf act ur er t o wi t hst and t he wi nd l oads speci f i ed.

d. Roof panel anchor c l i ps must be conceal ed and desi gned t o al l ow f or l ongi t udi nal t her mal movement of t he panel s, except wher e speci f i c f i xed poi nt s ar e i ndi cat ed. Pr ovi de f or l at er al t her mal movement i n panel conf i gur at i on or wi t h c l i ps desi gned f or l at er al and l ongi t udi nal movement .

1. 3. 2 Desi gn Condi t i ons

Desi gn t he syst em t o r esi st posi t i ve and negat i ve l oads speci f i ed her ei n i n accor dance wi t h t he AI SI SG03- 3. Panel s must suppor t wal k i ng l oads wi t hout per manent di st or t i on or t el egr aphi ng of t he st r uct ur al suppor t s.

Apr i l 2019 Page 3 SECTI ON 07 61 14. 00 20

1. 3. 2. 1 Wi nd Upl i f t

Comput e and appl y t he desi gn upl i f t pr essur es f or t he r oof syst em usi ng a basi c wi nd speed of 120 mi l es per hour ( mph) . Roof syst em and at t achment s must r esi st t he f ol l owi ng wi nd l oads, i n pounds per squar e f oot ( psf ) :

At eaves, r akes, r i dge, bui l di ng cor ner s and cent r al ar eas as shown on t he drawings.

The desi gn upl i f t f or ce f or each connect i on assembl y must be t hat pr essur e gi ven f or t he ar ea under consi der at i on, mul t i pl i ed by t he t r i but ar y l oad ar ea of t he connect i on assembl y, and mul t i pl i ed by t he appr opr i at e f act or of saf et y, as f ol l ows:

a. Si ngl e f ast ener i n a connect i on: 3. 0

b. Two or mor e f ast ener s i n each connect i on: 2. 25

1. 3. 2. 2 Roof Li ve Loads

Loads must be appl i ed on t he hor i zont al pr oj ect i on of t he r oof st r uct ur e.

The mi ni mum r oof desi gn l i ve l oad must be 20 psf .

1. 3. 2. 3 Ther mal Movement

Syst em must be capabl e of wi t hst andi ng t her mal movement based on a t emper at ur e r ange of 10 degr ees F bel ow _0____ degr ees F and140 degr ees F.

1. 3. 2. 4 Deflection

Panel s must be capabl e of suppor t i ng desi gn l oads bet ween unsuppor t ed spans wi t h def l ect i on of not gr eat er t han L/ 180 of t he span.

1. 3. 3 St r uct ur al Per f or mance

The st r uct ur al per f or mance t est met hods and r equi r ement s of t he St andi ng Seam Roof i ng Syst ems ( SSRS) must be i n accor dance wi t h ASTM E1592.

1. 4 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00

SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

Roof i ng; G

SD- 03 Pr oduct Dat a

Roof i ng Panel s; G

At t achment Cl i ps; G

Cl osur es; G

Accessories

Apr i l 2019 Page 4 SECTI ON 07 61 14. 00 20

Fasteners

Sealants

I nsul at i on, i ncl udi ng Joi nt Seal i ng Measur es f or Vapor Bar r i er Facing

Sampl e War r ant y Cer t i f i cat e/ assembl y l et t er ; G

Submi t f or mat er i al s t o be pr ovi ded. Submi t dat a suf f i c i ent t o i ndi cat e conf or mance t o speci f i ed r equi r ement s.

SD- 04 Sampl es

Roof i ng Panel

Submi t a 12 i nch l ong by f ul l wi dt h sect i on of t ypi cal panel .

For col or sel ect i on, submi t 2 by 4 i nch met al sampl es i n col or , f i ni sh and t ext ur e speci f i edor sel ect ed. When col or s ar e not i ndi cat ed, submi t sampl es of not l ess t han si x di f f er ent manuf act ur er ' s st andar d col or s f or sel ect i on.

Accessories

Submi t each t ype of accessor y i t em used i n t he pr oj ect i ncl udi ng, but not l i mi t ed t o each t ype of anchor c l i p, c l osur e, f ast ener , and l eg c l amp.

Sealants

I nt er medi at e Suppor t Sect i on

Submi t f ul l s i ze sampl es of each i nt er medi at e suppor t sect i on, 12 i nches l ong.

SD- 05 Desi gn Dat a

Desi gn Cal cul at i ons

SD- 06 Test Repor t s

Fi el d I nspect i on; G

Submi t manuf act ur er ' s t echni cal r epr esent at i ve' s f i el d i nspect i on r epor t s as speci f i ed i n par agr aph MANUFACTURER' S FI ELD

INSPECTION.

St r uct ur al Per f or mance Test s

Fi ni sh Test s

SD- 07 Cer t i f i cat es

Manuf act ur er ' s Techni cal Repr esent at i ve' s Qual i f i cat i ons

St at ement of I nst al l er ' s Qual i f i cat i ons

Apr i l 2019 Page 5 SECTI ON 07 61 14. 00 20

Submi t document at i on f r om r oof i ng manuf act ur er pr ovi ng t he manuf act ur er ' s t echni cal r epr esent at i ve meet s bel ow speci f i ed r equi r ement s. I ncl ude name, addr ess, t el ephone number , and exper i ence r ecor d.

Submi t document at i on pr ovi ng t he i nst al l er i s f act or y- t r ai ned, has t he speci f i ed exper i ence, and aut hor i zed by t he manuf act ur er t o i nst al l t he pr oduct s speci f i ed.

Coi l St ock Compat i bi l i t y ; G

Pr ovi de cer t i f i cat i on of coi l compat i bi l i t y wi t h r ol l f or mi ng machi ner y t o be used f or f or mi ng panel s wi t hout war pi ng, wavi ness, and r i ppl i ng not par t of panel pr of i l e; t o be done wi t hout damage, abr asi on or mar ki ng of f i ni sh coat i ng.

SD- 08 Manuf act ur er ' s I nst r uct i ons

I nst al l at i on Manual ; G

Submi t manuf act ur er s pr i nt ed i nst al l at i on manual , i nst r uct i ons, and st andar d det ai l s.

SD- 11 Cl oseout Submi t t al s

I nf or mat i on Car d

For each r oof i ng i nst al l at i on, submi t a t ypewr i t t en car d or phot oengr aved al umi num car d cont ai ni ng t he i nf or mat i on l i s t ed on For m 1 l ocat ed at t he end of t hi s sect i on.

Ener gy St ar Label f or St eel Roof i ng Pr oduct ; S

Recycl ed Cont ent f or St eel Roof i ng Pr oduct ; S

Heat I s l and Reduct i on; S

Warranty

1. 5 DESI GN CALCULATI ONS

Pr ovi de desi gn cal cul at i ons pr epar ed by a pr of essi onal engi neer speci al i z i ng i n st r uct ur al engi neer i ng ver i f y i ng t hat syst em suppl i ed and any addi t i onal f r ami ng meet s desi gn l oad cr i t er i a i ndi cat ed. Coor di nat e cal cul at i ons wi t h manuf act ur er ' s t est r esul t s. I ncl ude cal cul at i ons f or :

Wi nd l oad upl i f t desi gn pr essur e at r oof l ocat i ons speci f i ed i n par agr aph WI ND UPLI FT.

Cl i p spaci ng and al l owabl e l oad per c l i p.

Fast eni ng of c l i ps t o st r uct ur e or i nt er medi at e suppor t s.

I nt er medi at e suppor t spaci ng and f r ami ng and f ast eni ng t o st r uct ur e when r equi r ed.

Al l owabl e panel span at anchor age spaci ng i ndi cat ed.

Saf et y f act or used i n desi gn l oadi ng.

Apr i l 2019 Page 6 SECTI ON 07 61 14. 00 20

Gover ni ng code r equi r ement s or cr i t er i a.

Edge and t er mi nat i on det ai l s.

1. 6 QUALI TY ASSURANCE

1. 6. 1 Pr er oof i ng Conf er ence

Af t er submi t t al s ar e r ecei ved and appr oved but bef or e r oof i ng and i nsul at i on wor k, i ncl udi ng associ at ed wor k, i s pr ef or med, t he Cont r act i ng Of f i cer wi l l hol d a pr er oof i ng conf er ence t o r evi ew t he f ol l owi ng:

a. The dr awi ngs and speci f i cat i ons

b. Pr ocedur e f or on si t e i nspect i on and accept ance of t he r oof i ng subst r at e and per t i nent st r uct ur al det ai l s r el at i ng t o t he r oof i ng system

c. Cont r act or ' s pl an f or coor di nat i on of t he wor k of t he var i ous t r ades i nvol ved i n pr ovi di ng t he r oof i ng syst em and ot her component s secur ed t o t he r oof i ng

d. Saf et y r equi r ement s

The pr er oof i ng conf er ence must be at t ended by t he Cont r act or and per sonnel di r ect l y r esponsi bl e f or t he r oof i ng and i nsul at i on i nst al l at i on, mechani cal and el ect r i cal wor k, and t he r oof i ng manuf act ur er ' s t echni cal r epr esent at i ve. Conf l i c t s among t hose at t endi ng t he pr er oof i ng conf er ence must be r esol ved and conf i r med i n wr i t i ng bef or e r oof i ng wor k, i ncl udi ng associ at ed wor k, i s begun. Pr epar e wr i t t en mi nut es of t he pr er oof i ng conf er ence and submi t t o t he Cont r act i ng Of f i cer .

1. 6. 2 Manufacturer

The SSMRS must be t he pr oduct of a met al r oof i ng i ndust r y - r ecogni zed manuf act ur er who has been i n t he pr act i ce of manuf act ur i ng SSMRS f or a per i od of not l ess t han 5 year s and who has been i nvol ved i n at l east 5 pr oj ect s s i mi l ar i n s i ze and compl exi t y t o t hi s pr oj ect .

1. 6. 3 Manuf act ur er ' s Techni cal Repr esent at i ve

The r epr esent at i ve must have aut hor i zat i on f r om manuf act ur er t o appr ove f i el d changes and be t hor oughl y f ami l i ar wi t h t he pr oduct s and wi t h i nst al l at i ons i n t he geogr aphi cal ar ea wher e const r uct i on wi l l t ake pl ace. The manuf act ur er ' s r epr esent at i ve must be an empl oyee of t he manuf act ur er wi t h at l east 5 year s exper i ence i n i nst al l i ng t he r oof syst em. The r epr esent at i ve must be avai l abl e t o per f or m f i el d i nspect i ons and at t end meet i ngs as r equi r ed her ei n, and as r equest ed by t he Cont r act i ng Of f i cer .

1. 6. 4 I nst al l er ' s Qual i f i cat i ons

The r oof i ng syst em i nst al l er must be f act or y- t r ai ned, appr oved by t he st eel r oof i ng syst em manuf act ur er t o i nst al l t he syst em, and must have a mi ni mum of t hr ee year s exper i ence as an appr oved appl i cat or wi t h t hat manuf act ur er . The appl i cat or must have appl i ed f i ve i nst al l at i ons of s i mi l ar s i ze and scope as t hi s pr oj ect wi t hi n t he pr evi ous 3 year s.

Apr i l 2019 Page 7 SECTI ON 07 61 14. 00 20

1. 6. 5 Si ngl e Sour ce

Roof i ng panel s, c l i ps, c l osur es, and ot her accessor i es must be st andar d pr oduct s of t he same manuf act ur er ; must be t he l at est desi gn by t he manuf act ur er ; and must have been desi gned by t he manuf act ur er t o oper at e as a compl et e syst em f or t he i nt ended use.

1. 6. 6 Labor at or y Test s For Panel Fi ni sh

The t er m " appear ance of base met al " r ef er s t o t he met al coat i ng on st eel .

Panel s must meet t he f ol l owi ng t est r equi r ement s:

a. For mabi l i t y Test : When subj ect ed t o a 180 degr ee bend over a 1/ 8 i nch di amet er mandr el i n accor dance wi t h ASTM D522/ D522M, ext er i or coat i ng f i l m may show onl y s l i ght mi cr ochecki ng and no l oss of adhesi on.

b. Accel er at ed Weat her i ng Test : Wi t hst and a weat her i ng t est f or a mi ni mum of 2000 hour s i n accor dance wi t h ASTM G152 and ASTM G153, Met hod 1 wi t hout cr acki ng, peel i ng, bl i s t er i ng, l oss of adhesi on of t he pr ot ect i ve coat i ng, or cor r osi on of t he base met al . Pr ot ect i ve coat i ng t hat can be r eadi l y r emoved f r om t he base met al wi t h a penkni f e bl ade or s i mi l ar i nst r ument wi l l be consi der ed t o i ndi cat e l oss of adhesi on.

c. Chal k i ng Resi st ance: Af t er t he 2000- hour weat her omet er t est , ext er i or coat i ng may not chal k gr eat er t han No. 8 r at i ng when measur ed i n accor dance wi t h ASTM D4214 t est pr ocedur es.

d. Col or Change Test :

Af t er t he 2000- hour weat her omet er t est , ext er i or coat i ng col or change must not exceed 2 NBS uni t s when measur ed i n accor dance wi t h ASTM D2244 t est pr ocedur e.

e. Sal t Spr ay Test : Wi t hst and a sal t spr ay t est f or a mi ni mum of 1000 hour s i n accor dance wi t h ASTM B117, i ncl udi ng t he scr i be r equi r ement i n t he t est . I mmedi at el y upon r emoval of t he panel f r om t he t est , t he coat i ng must r ecei ve a r at i ng of 8, f ew bl i st er s i n f i el d as det er mi ned by ASTM D714; and an aver age r at i ng of 6, 1/ 8 i nch f ai l ur e at scr i be, as det er mi ned by ASTM D1654. Rat i ng Schedul e No. 1.

f . Abr asi on Resi st ance Test f or Col or Coat i ng: When subj ect ed t o t he f al l i ng sand t est i n accor dance wi t h ASTM D968, coat i ng syst em must wi t hst and a mi ni mum of 50 l i t er s of sand per mi l t hi ckness bef or e appear ance of base met al .

g. Humi di t y Test : When subj ect ed t o a humi di t y cabi net t est i n accor dance wi t h ASTM D2247 f or 1000 hour s, a scor ed panel must show no si gns of bl i s t er i ng, cr acki ng, cr eepage, or cor r osi on.

h. Gl oss Test : The gl oss of t he f i ni sh must be 30 pl us or mi nus 5 at an angl e of 60 degr ees, when measur ed i n accor dance wi t h ASTM D523.

i . Gl ar e Resi st ance Test :

Sur f aces of panel s t hat wi l l be exposed t o t he ext er i or must have a specul ar r ef l ect ance of not mor e t han 10 when measur ed i n accor dance with ASTM D523 at an angl e of 85 degr ees. Specul ar r ef l ect ance may be obt ai ned wi t h st r i at i ons or embossi ng. Requi r ement s speci f i ed under

Apr i l 2019 Page 8 SECTI ON 07 61 14. 00 20

FORMABI LI TY TEST wi l l be wai ved i f necessar y t o conf or m t o t hi s requirement.

1. 6. 7 Shop Dr awi ng Requi r ement s

Submi t r oof i ng dr awi ngs t o suppl ement t he i nst r uct i ons and di agr ams.

I ncl ude desi gn and er ect i on dr awi ngs cont ai ni ng an i somet r i c v i ew of t he r oof showi ng t he desi gn upl i f t pr essur es and di mensi ons of edge, r i dge and cor ner zones; and show t ypi cal and speci al condi t i ons i ncl udi ng f l ashi ngs, mat er i al s and t hi ckness, di mensi ons, f i x i ng l i nes, anchor i ng met hods, seal ant l ocat i ons, seal ant t ape l ocat i ons, f ast ener l ayout , s i zes, and spaci ng, t er mi nat i ons, penet r at i ons, at t achment s, and pr ovi s i ons f or t her mal movement . Det ai l s of i nst al l at i on must be i n accor dance wi t h t he manuf act ur er ' s St andar d I nst r uct i ons and det ai l s or t he SMACNA 1793.

Pr i or t o submi t t i ng shop dr awi ngs, have dr awi ngs r evi ewed and appr oved by t he manuf act ur er ' s t echni cal engi neer i ng depar t ment .

1. 7 WARRANTY

Fur ni sh manuf act ur er ' s no- dol l ar - l i mi t mat er i al s and wor kmanshi p war r ant y f or t he r oof i ng syst em. The war r ant y per i od must be not l ess t han 20 year s f r om t he dat e of Gover nment accept ance of t he wor k. The war r ant y must be i ssued di r ect l y t o t he Gover nment . The war r ant y must pr ovi de t hat i f wi t hi n t he war r ant y per i od t he met al r oof i ng syst em becomes non- wat er t i ght or shows evi dence of cor r osi on, per f or at i on, r upt ur e or excess weat her i ng due t o det er i or at i on of t he r oof i ng syst em r esul t i ng f r om def ect i ve mat er i al s or i nst al l ed wor kmanshi p t he r epai r or r epl acement of t he def ect i ve mat er i al s and cor r ect i on of t he def ect i ve wor kmanshi p must be t he r esponsi bi l i t y of t he r oof i ng syst em manuf act ur er . Repai r s t hat become necessar y because of def ect i ve mat er i al s and wor kmanshi p whi l e r oof i ng i s under war r ant y must be per f or med wi t hi n 7 days af t er not i f i cat i on, unl ess addi t i onal t i me i s appr oved by t he Cont r act i ng Of f i cer . Fai l ur e t o per f or m r epai r s wi t hi n t he speci f i ed per i od of t i me wi l l const i t ut e gr ounds f or havi ng t he r epai r s per f or med by ot her s and t he cost bi l l ed t o t he manuf act ur er . I n addi t i on, pr ovi de a 2 year cont r act or i nst al l at i on war r ant y.

1. 8 DELI VERY, STORAGE AND HANDLI NG

Del i ver , st or e, and handl e pr ef or med panel s, bul k r oof i ng pr oduct s and ot her manuf act ur ed i t ems i n a manner t o pr event damage or def or mat i on.

1. 8. 1 Delivery

Pr ovi de adequat e packagi ng t o pr ot ect mat er i al s dur i ng shi pment . Cr at ed mat er i al s must not be uncr at ed unt i l r eady f or use, except f or i nspect i on.

I mmedi at el y upon ar r i val of mat er i al s at t he j obsi t e, i nspect mat er i al s f or damage, dampness, and st ai ni ng. Repl ace damaged or per manent l y st ai ned mat er i al s t hat cannot be r est or ed t o l i ke- new condi t i on wi t h sat i sf act or y mat er i al . I f mat er i al s ar e wet , r emove t he moi st ur e and r e- st ack and pr ot ect t he panel s unt i l used.

1. 8. 2 Storage

St ack mat er i al s on pl at f or ms or pal l et s and cover wi t h t ar paul i ns or ot her sui t abl e weat her t i ght cover i ng whi ch pr event s wat er t r appi ng or condensat i on. St or e mat er i al s so t hat wat er whi ch mi ght have accumul at ed dur i ng t r ansi t or st or age wi l l dr ai n of f . Do not st or e t he panel s i n cont act wi t h mat er i al s t hat mi ght cause st ai ni ng, such as mud, l i me, Apr i l 2019 Page 9 SECTI ON 07 61 14. 00 20 cement , f r esh concr et e or chemi cal s. Pr ot ect st or ed panel s f r om wi nd damage.

1. 8. 3 Handling

Handl e mat er i al car ef ul l y t o avoi d damage t o sur f aces, edges and ends.

PART 2 PRODUCTS

2. 1 PRODUCT SUSTAI NABI LI TY CRI TERI A

For pr oduct s i n t hi s sect i on, wher e appl i cabl e and t o ext ent al l owed by per f or mance cr i t er i a, pr ovi de and document t he f ol l owi ng:

2. 1. 1 Ener gy Ef f i c i ent St eel Roof i ng Pr oduct s

Ener gy St ar Label r equi r ement i s i dent i f i ed f or some pr oduct s i n t hi s sect i on; pr ovi de document at i on i n accor dance wi t h Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG par agr aph ENERGY EFFI CI ENT EQUI PMENT. Ot her pr oduct s l i s t ed i n t hi s sect i on may be avai l abl e wi t h Ener gy St ar Label ;

i dent i f y t hose pr oduct s t hat meet pr oj ect r equi r ement s f or ener gy ef f i c i ent equi pment , and pr ovi de document at i on i n accor dance wi t h Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG par agr aph ENERGY EFFI CI ENT EQUI PMENT.

2. 1. 2 Recycl ed Cont ent of St eel Roof i ng Pr oduct s

Recycl ed cont ent i s i dent i f i ed f or some pr oduct s i n t hi s sect i on; pr ovi de document at i on i n accor dance wi t h Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG par agr aph RECYCLED CONTENT. Ot her pr oduct s l i s t ed i n t hi s sect i on may be avai l abl e wi t h r ecycl ed cont ent ; i dent i f y t hose pr oduct s t hat meet pr oj ect r equi r ement s f or r ecycl ed cont ent , and pr ovi de document at i on i n accor dance wi t h Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG par agr aph RECYCLED CONTENT.

2. 2 ROOFI NG PANELS

Pr ovi de panel s wi t h i nt er l ocki ng r i bs f or secur i ng adj acent sheet s and wi t h conceal ed cl i p f ast eni ng syst em f or secur i ng t he r oof cover i ng t o st r uct ur al f r ami ng member s. Fast ener s must not penet r at e t he panel s except at t he r i dge, eave, r akes, penet r at i ons, and end l aps. Backi ng pl at es and ends of panel s at end l aps must be pr edr i l l ed or pr epunched.

Fact or y pr epar e ends of panel s t o be l apped by t r i mmi ng par t of seam, di e- set t i ng, or swagi ng ends of panel s. I ndi v i dual sheet s must be suf f i c i ent l y l ong t o cover t he ent i r e l engt h of any unbr oken r oof s l ope when such sl ope i s 30 f eet or l ess. Pr ovi de panel s t hat ext end over t wo or mor e spans when l engt h of r un exceeds 30 f eet . Obt ai n Cont r act i ng Of f i cer ( KO) appr oval f or sheet s l onger t han 30 f eet bef or e submi t t i ng shop dr awi ngs. Sheet s must pr ovi de not l ess t han 12 i nches of cover age ( wi dt h) i n pl ace. Pr ovi de panel s wi t h a mi ni mum cor r ugat i on hei ght of

2. 25 i nches ( nomi nal ) . Make pr ovi s i ons f or expansi on and cont r act i on at ei t her r i dge or eave, consi st ent wi t h t he t ype of syst em t o be used. For m panel s f r om coi l st ock wi t hout war pi ng, wavi ness or r i ppl es not par t of t he panel pr of i l e, and f r ee of damage t o t he f i ni sh coat i ng syst em.

Pr ovi de st eel r oof i ng pr oduct t hat i s Ener gy St ar l abel ed. Pr ovi de dat a identifying Ener gy St ar l abel f or st eel r oof i ng pr oduct . Pr ovi de sol ar r ef l ect ance pr oduct wi t h an i ni t i al sol ar r ef l ect ance gr eat er t han or equal t o 0. 25 and a sol ar r ef l ect ance gr eat er t han or equal t o 0. 15 t hr ee year s af t er i nst al l at i on under nor mal condi t i ons.

Apr i l 2019 Page 10 SECTI ON 07 61 14. 00 20

2. 2. 1 Material

Zi nc- coat ed st eel conf or mi ng t o ASTM A653/ A653M, G90 coat i ng desi gnat i on or al umi num- zi nc al l oy coat ed st eel conf or mi ng t o ASTM A792/ A792M, AZ 55 coat i ng. Pr ovi de mat er i al wi t h a mi ni mum t hi ckness of 0. 023 i nch t hi ck ( 24 gage) mi ni mum except when mi d f i el d of r oof i s subj ect t o desi gn wi nd upl i f t pr essur es of 60 psf or gr eat er , ent i r e r oof syst em must have a mi ni mum t hi ckness of 0. 030 i nch ( 22 gage) . St eel r oof i ng mat er i al s must cont ai n a mi ni mum of 30 per cent t ot al r ecycl ed cont ent . Pr ovi de dat a i dent i f y i ng per cent age of r ecycl ed cont ent f or st eel r oof i ng pr oduct .

2. 2. 2 Finish

Fact or y col or f i ni sh.

2. 2. 2. 1 Fact or y Col or Fi ni sh

Pr ovi de f act or y appl i ed, t her mal l y cur ed coat i ng t o ext er i or and i nt er i or of met al r oof and wal l panel s and met al accessor i es. Pr ovi de ext er i or f i ni sh t op coat of 70 per cent r esi n pol yvi nyl i dene f l uor i de wi t h not l ess t han 0. 2 mi l dr y f i l m t hi ckness. Pr ovi de ext er i or pr i mer st andar d wi t h panel manuf act ur er dr y f i l m t hi ckness. I nt er i or f i ni sh must consi st of

0. 2 mi l t he same coat i ng and dr y f i l m t hi ckness as t he ext er i or coat i ng.

Pr ovi de ext er i or and i nt er i or coat i ng meet i ng t est r equi r ement s speci f i ed bel ow. Test s must have been per f or med on t he same f act or y f i ni sh and t hi ckness pr ovi ded.

2. 3 I NTERMEDI ATE SUPPORTS

Fabr i cat e panel subgi r t s, subpur l i ns, T- bar s, Z- bar s and t r acks f r om gal vani zed st eel conf or mi ng t o ASTM A653/ A653M, G90, Gr ade D ( 16 gage and heavi er ) , Gr ade A ( 18 gage and l i ght er ) ; or st eel conf or mi ng t o ASTM A36/ A36M, ASTM A1011/ A1011M , or ASTM A1008/ A1008M pr i me pai nt ed wi t h z i nc- r i ch pr i mer . Si ze, shape, t hi ckness and capaci t y as r equi r ed t o meet t he l oad, i nsul at i on t hi ckness and def l ect i on cr i t er i a speci f i ed.

2. 4 ATTACHMENT CLI PS

Fabr i cat e c l i ps f r om ASTM A1011/ A1011M, or ASTM A1008/ A1008M st eel hot - di p gal vani zed i n accor dance wi t h ASTM A653/ A653M, G 90, or Ser i es 300 st ai nl ess st eel . Si ze, shape, t hi ckness and capaci t y as r equi r ed t o meet t he l oad, i nsul at i on t hi ckness and def l ect i on cr i t er i a speci f i ed.

2. 5 ACCESSORIES

Sheet met al f l ashi ngs, gut t er s, downspout s, t r i m, mol di ngs, c l osur e st r i ps, pr e- f or med cr i cket s, caps, equi pment cur bs, and ot her s i mi l ar sheet met al accessor i es used i n conj unct i on wi t h pr ef or med met al panel s must be of t he same mat er i al as used f or t he panel s. Pr ovi de met al accessor i es wi t h a f act or y col or f i ni sh t o mat ch t he r oof i ng panel s, except t hat such i t ems whi ch wi l l be conceal ed af t er i nst al l at i on may be pr ovi ded wi t hout t he f i ni sh i f t hey ar e st ai nl ess st eel . Met al must be of a t hi ckness not l ess t han t hat used f or t he panel s. Ther mal spacer bl ocks and ot her t her mal bar r i er s at conceal ed cl i p f ast ener s must be as r ecommended by t he manuf act ur er except t hat wood spacer bl ocks ar e not allowed.

Apr i l 2019 Page 11 SECTI ON 07 61 14. 00 20

2. 5. 1 Closures

2. 5. 1. 1 Ri b Cl osur es

Cor r osi on r esi st i ng st eel , c l osed- cel l or sol i d- cel l synt het i c r ubber , neopr ene or pol yvi nyl chl or i de pr e- mol ded t o mat ch conf i gur at i on of r i b openi ng. Mat er i al f or c l osur es must not absor b wat er .

2. 5. 1. 2 Ri dge Cl osur es

Met al - c l ad f oam or met al c l osur e wi t h f oam secondar y c l osur e mat chi ng panel conf i gur at i on f or i nst al l at i on on sur f ace of r oof panel bet ween panel r i bs at r i dge and headwal l r oof panel f l ashi ng condi t i ons and t er mi nat i ons. Foam mat er i al must not absor b wat er .

2. 5. 2 Fasteners

Zi nc- coat ed st eel , cor r osi on r esi st i ng st eel , z i nc cast head, or nyl on capped st eel , t ype and si ze speci f i ed bel ow or as ot her wi se appr oved f or t he appl i cabl e r equi r ement s. Desi gn t he f ast eni ng syst em t o wi t hst and t he desi gn l oads speci f i ed. Exposed f ast ener s must be gasket ed or have gasket ed washer s on t he ext er i or s i de of t he cover i ng t o wat er pr oof t he penet r at i on. Washer mat er i al must be compat i bl e wi t h t he cover i ng; have a mi ni mum di amet er of 3/ 8 i nch f or st r uct ur al connect i ons; and gasket ed por t i on of f ast ener s or washer s must be neopr ene or ot her equal l y dur abl e el ast omer i c mat er i al appr oxi mat el y 1/ 8 i nch t hi ck.

2. 5. 2. 1 Screws

Not smal l er t han No. 14 di amet er i f sel f - t appi ng t ype and not smal l er t han No. 12 di amet er i f sel f - dr i l l i ng and sel f - t appi ng.

2. 5. 2. 2 Bolts

Not smal l er t han 1/ 4 i nch di amet er , shoul der ed or pl ai n shank as r equi r ed, wi t h pr oper nut s.

2. 5. 2. 3 Aut omat i c End- Wel ded St uds

Aut omat i c end- wel ded st uds must be shoul der ed t ype wi t h a shank di amet er of not smal l er t han 3/ 16 i nch and cap or nut f or hol di ng cover i ng agai nst t he shoul der .

2. 5. 2. 4 Expl osi ve Dr i ven Fast ener s

Fast ener s f or use wi t h expl osi ve act uat ed t ool s must have a shank di amet er of not smal l er t han 0. 145 i nch wi t h a shank l engt h of not smal l er t han 1/ 2 i nch f or f ast eni ng t o st eel and not smal l er t han 1 i nch f or f ast eni ng t o concrete.

2. 5. 2. 5 Rivets

Bl i nd r i vet s must be st ai nl ess st eel wi t h 1/ 8 i nch nomi nal di amet er shank.

Ri vet s must be t hr eaded st em t ype i f used f or ot her t han t he f ast eni ng of t r i m. Ri vet s wi t h hol l ow st ems must have cl osed ends.

2. 5. 3 Sealants

El ast omer i c t ype cont ai ni ng no oi l or asphal t . Exposed seal ant must cur e

Apr i l 2019 Page 12 SECTI ON 07 61 14. 00 20 t o a r ubber l i ke consi st ency. Conceal ed seal ant must be t he non- har deni ng t ype. Seam seal ant must be f act or y- appl i ed, non- ski nni ng, non- dr yi ng, and must conf or m t o t he r oof i ng manuf act ur er ' s r ecommendat i ons.

Si l i cone- based seal ant s must not be used i n cont act wi t h f i ni shed met al panel s and component s unl ess appr oved ot her wi se by t he Cont r act i ng Of f i cer .

2. 5. 4 GASKETS AND I NSULATI NG COMPOUNDS

Nonabsor pt i ve and sui t abl e f or i nsul at i ng cont act poi nt s of i ncompat i bl e mat er i al s. I nsul at i ng compounds must be nonr unni ng af t er dr y i ng.

2. 6 THERMAL I NSULATI ON

Fl exi bl e bl anket , r i gi d, or semi - r i gi d f aced wi t h a f l exi bl e vapor r et ar der . I nsul at i on and f aci ng must have a f l ame- spr ead r at i ng of 50 or l ess i n accor dance wi t h ASTM E84. Vapor r et ar der f aci ng must have a per meance r at i ng of 0. 05 per m or l ess. Pr ovi de a t her mal r esi st ance " R" val ue of 24 when usi ng a cool r oof and 33 or mor e when a cool r oof i s not speci f i ed. Faci ngs and f i ni shes must be f act or y- appl i ed.

2. 7 UNDERLAYMENT FOR WOOD SUBSTRATES

ASTM D226/ D226M, Type I per f or at ed, cover ed by wat er - r esi st ant r osi n s i zed bui l di ng paper .

2. 8 LI NER PANELS

Fabr i cat e l i ner panel s of t he same mat er i al as r oof panel s, and f or med or pat t er ned t o pr event wavi ness and di st or t i on. Li ner panel s must have a f act or y appl i ed, one mi l t hi ck mi ni mum pai nt ed coat i ng on t he i nsi de f ace and a pr i me coat on t he l i ner s i de.

PART 3 EXECUTI ON

Do not i nst al l bui l di ng const r uct i on mat er i al s t hat show vi s i bl e evi dence of bi ol ogi cal gr owt h.

3. 1 EXAMINATION

Exami ne sur f aces t o r ecei ve st andi ng seam met al r oof i ng and f l ashi ng.

Ensur e t hat sur f aces ar e pl umb and t r ue, c l ean, even, smoot h, as dr y and f r ee f r om def ect s and pr oj ect i ons whi ch mi ght af f ect t he i nst al l at i on.

3. 2 PROTECTI ON FROM CONTACT WI TH DI SSI MI LAR MATERI ALS

3. 2. 1 Cement i t i ous Mat er i al s

Pai nt met al sur f aces whi ch wi l l be i n cont act wi t h mor t ar , concr et e, or ot her masonr y mat er i al s wi t h one coat of al kal i - r esi st ant coat i ng such as heavy- bodi ed bi t umi nous pai nt .

3. 2. 2 Cont act wi t h Wood

Wher e met al wi l l be i n cont act wi t h wood or ot her absor bent mat er i al subj ect t o wet t i ng, seal j oi nt s wi t h seal i ng compound and appl y one coat of heavy- bodi ed bi t umi nous pai nt .

Apr i l 2019 Page 13 SECTI ON 07 61 14. 00 20

3. 3 INSTALLATION

I nst al l i n accor dance wi t h t he appr oved manuf act ur er ' s er ect i on i nst r uct i ons, shop dr awi ngs, and di agr ams. Panel s must be i n f ul l and f i r m cont act wi t h at t achment c l i ps. Wher e pr ef i ni shed panel s ar e cut i n t he f i el d, or wher e any of t he f act or y appl i ed cover i ngs or coat i ngs ar e abr aded or damaged i n handl i ng or i nst al l at i on, t hey must , af t er necessar y r epai r s have been made wi t h mat er i al of t he same col or as t he weat her coat i ng, be appr oved bef or e bei ng i nst al l ed. Seal compl et el y openi ngs t hr ough panel s. Cor r ect def ect s or er r or s i n t he mat er i al s. Repl ace mat er i al s whi ch cannot be cor r ect ed i n an appr oved manner wi t h nondef ect i ve mat er i al s. Pr ovi de mol ded cl osur e st r i ps wher e i ndi cat ed and wher e necessar y t o pr ovi de weat her t i ght const r uct i on. Use shi ms as r equi r ed t o ensur e at t achment c l i p l i ne i s t r ue. Use a spaci ng gage at each r ow of panel s t o ensur e t hat panel wi dt h i s not st r et ched or shor t ened. Pr ovi de one l ayer of asphal t - i ce and wat er shi el d pl aced per pendi cul ar t o r oof s l ope, Over l ap s i de and end l aps 3 i nches, of f set seams i n bui l di ng paper wi t h seams i n i ce and wat er shi el d.

3. 3. 1 Roof Panel s

Appl y r oof i ng panel s wi t h t he st andi ng seams par al l el t o t he s l ope of t he r oof . Pr ovi de r oof i ng panel s i n l ongest pr act i cal l engt hs f r om r i dge t o eaves ( t op t o eaves on shed r oof s) , wi t h no t r ansver se j oi nt s except at t he j unct i on of vent i l at or s, cur bs, skyl i ght s, chi mneys, and si mi l ar openi ngs. I nst al l f l ashi ng t o assur e posi t i ve wat er dr ai nage away f r om r oof penet r at i ons. Locat e panel end l aps such t hat f ast ener s do not engage suppor t s or ot her wi se r est r ai n t he l ongi t udi nal t her mal movement of panel s. For m f i el d- f or med seam t ype syst em seams i n t he f i el d wi t h an aut omat i c mechani cal seamer appr oved by t he manuf act ur er . At t ach panel s t o t he st r uct ur e wi t h conceal ed cl i ps i ncor por at ed i nt o panel seams. Cl i p at t achment must al l ow r oof t o move i ndependent l y of t he st r uct ur e, except at f i xed poi nt s as i ndi cat ed.

3. 3. 2 I nsul at i on I nst al l at i on

I nst al l bet ween cover i ng and suppor t i ng member s t o pr esent a neat appear ance. Fol d and st apl e and t ape seams unl ess appr oved ot her wi se by t he Cont r act i ng Of f i cer .

3. 3. 2. 1 Ri gi d or Semi - Ri gi d I nsul at i on

I nst al l i n ar eas wher e i nsul at i on i s exposed t o v i ew. Fast en secur el y wi t hout l oose j oi nt s or unsi ght l y sags.

3. 3. 2. 2 Bl anket I nsul at i on

May be used i n conceal ed l ocat i ons. Lap f aci ng at j oi nt s and f ast en i n a manner t hat wi l l pr ovi de t i ght j oi nt s.

3. 3. 3 Flashings

Pr ovi de f l ashi ng, r el at ed cl osur es and accessor i es as i ndi cat ed and as necessar y t o pr ovi de a weat her t i ght i nst al l at i on. I nst al l f l ashi ng t o ensur e posi t i ve wat er dr ai nage away f r om r oof penet r at i ons. Fl ash and seal t he r oof at t he r i dge, eaves and r akes, and pr oj ect i ons t hr ough t he r oof . Pl ace cl osur e st r i ps, f l ashi ng, and seal i ng mat er i al i n an appr oved manner t hat wi l l assur e compl et e weat her t i ght ness. Det ai l s of i nst al l at i on whi ch ar e not i ndi cat ed must be i n accor dance wi t h t he

Apr i l 2019 Page 14 SECTI ON 07 61 14. 00 20

SMACNA 1793, panel manuf act ur er ' s appr oved pr i nt ed i nst r uct i ons and det ai l s, or t he appr oved shop dr awi ngs. Al l ow f or expansi on and cont r act i on of f l ashi ng.

3. 3. 4 Fl ashi ng Fast ener s

Fast ener spaci ngs must be i n accor dance wi t h t he panel manuf act ur er ' s r ecommendat i ons and as necessar y t o wi t hst and t he desi gn l oads i ndi cat ed.

I nst al l f ast ener s i n r oof val l eys as r ecommended by t he manuf act ur er of t he panel s. I nst al l f ast ener s i n st r ai ght l i nes wi t hi n a t ol er ance of 1/ 2 i nch i n t he l engt h of a bay. Dr i ve exposed penet r at i ng t ype f ast ener s nor mal t o t he sur f ace and t o a uni f or m dept h t o seat gasket ed washer s pr oper l y and dr i ve so as not t o damage f act or y appl i ed coat i ng. Exer ci se ext r eme car e i n dr i l l i ng pi l ot hol es f or f ast eni ngs t o keep dr i l l s per pendi cul ar and cent er ed. Do not dr i l l t hr ough seal ant t ape. Af t er dr i l l i ng, r emove met al f i l i ngs and bur r s f r om hol es pr i or t o i nst al l i ng f ast ener s and washer s. Tor que used i n appl y i ng f ast ener s must not exceed t hat r ecommended by t he manuf act ur er . Remove panel s def or med or ot her wi se damaged by over - t or qued f ast eni ngs, and pr ovi de new panel s.

3. 3. 5 Ri b and Ri dge Cl osur e/ Cl osur e St r i ps

Set c l osur e/ c l osur e st r i ps i n j oi nt seal ant mat er i al and appl y seal ant t o mat i ng sur f aces pr i or t o addi ng panel .

3. 4 PROTECTI ON OF APPLI ED ROOFI NG

Do not per mi t st or i ng, wal k i ng, wheel i ng, and t r ucki ng di r ect l y on appl i ed r oof i ng mat er i al s. Pr ovi de t empor ar y wal kways, r unways, and pl at f or ms of smoot h c l ean boar ds or pl anks as necessar y t o avoi d damage t o appl i ed r oof i ng mat er i al s, and t o di st r i but e wei ght t o conf or m t o i ndi cat ed l i ve l oad l i mi t s of r oof const r uct i on.

3. 5 CLEANING

Cl ean exposed sheet met al wor k at compl et i on of i nst al l at i on. Remove met al shavi ngs, f i l i ngs, nai l s, bol t s, and wi r es f r om r oof s. Remove gr ease and oi l f i l ms, excess seal ant s, handl i ng mar ks, cont ami nat i on f r om st eel wool , f i t t i ngs and dr i l l i ng debr i s and scr ub t he wor k c l ean.

Exposed met al sur f aces must be f r ee of dent s, cr eases, waves, scr at ch mar ks, sol der or wel d mar ks and damage t o t he f i ni sh coat i ng.

3. 6 MANUFACTURER' S FI ELD I NSPECTI ON

Manuf act ur er ' s t echni cal r epr esent at i ve must v i s i t t he s i t e as necessar y dur i ng t he i nst al l at i on pr ocess t o assur e panel s, f l ashi ngs, and ot her component s ar e bei ng i nst al l ed i n a sat i sf act or y manner . Manuf act ur er ' s t echni cal r epr esent at i ve must per f or m a f i el d i nspect i on dur i ng t he f i r st 20 squar es of r oof panel i nst al l at i on and at subst ant i al compl et i on pr i or t o i ssuance of war r ant y, as a mi ni mum, and as ot her wi se r equest ed by t he Cont r act i ng Of f i cer . Addi t i onal i nspect i ons must not exceed one f or 100 squar es of t ot al r oof ar ea wi t h t he except i on t hat f ol l ow- up i nspect i ons of pr evi ousl y not ed def i c i enci es or appl i cat i on er r or s must be per f or med as r equest ed by t he Cont r act i ng Of f i cer . Each i nspect i on v i s i t must i ncl ude a r evi ew of t he ent i r e i nst al l at i on t o dat e. Af t er each i nspect i on, submi t a r epor t , s i gned by t he manuf act ur er ' s t echni cal r epr esent at i ve, t o t he Cont r act i ng Of f i cer not i ng t he over al l qual i t y of wor k, def i c i enci es and any ot her concer ns, and r ecommended cor r ect i ve act i ons i n det ai l . Not i f y Cont r act i ng Of f i cer a mi ni mum of 2 wor ki ng days

Apr i l 2019 Page 15 SECTI ON 07 61 14. 00 20 pr i or t o s i t e v i s i t by manuf act ur er ' s t echni cal r epr esent at i ve.

3. 7 COMPLETED WORK

Compl et ed wor k must be pl umb and t r ue wi t hout oi l canni ng, dent s, r i ppl es, abr asi on, r ust , st ai ni ng, or ot her damage det r i ment al t o t he per f or mance or aest het i cs of t he compl et ed r oof assembl y.

3. 8 I NFORMATI ON CARD

For each r oof , pr ovi de a t ypewr i t t en car d, l ami nat ed i n pl ast i c and f r amed f or i nt er i or di spl ay or a phot oengr aved 0. 032 i nch t hi ck al umi num car d f or ext er i or di spl ay. Car d t o be 8 1/ 2 by 11 i nches mi ni mum and cont ai n t he i nf or mat i on l i s t ed on For m 1 at end of t hi s sect i on. I nst al l car d near poi nt of access t o r oof , or wher e i ndi cat ed.

Apr i l 2019 Page 16 SECTI ON 07 61 14. 00 20