This is a technical specification document for common electrical work results at Tinker Air Force Base in Oklahoma, effective April 2019.

The specification establishes requirements for electrical materials, equipment, installation procedures, and quality control standards. Products required include rigid steel conduit (hot-dipped galvanized or PVC-coated), electrical metallic tubing, flexible metallic conduit, intermediate metal conduit, rigid nonmetallic conduit, wireways, cable trays, copper wire and cable (THHN, THWN, or XHHW types), safety switches (NEMA KS 1), toggle switches (EIA 480 compliant), commercial-grade receptacles (NEMA 5-20R), outlet and junction boxes, circuit breaker panelboards (NEMA PB 1 with bolted breakers), circuit breakers (minimum 10,000 amperes rms), lighting fixtures with high power factor ballasts, dry-type distribution transformers (UL 506 compliant with voltage taps), and warning signage for high-voltage equipment. Installation requirements address conduit routing (maximum three 90-degree bends), EMT grounding, conductor color coding (specific phase colors for 208v and 480v systems, white for neutral, green for grounds), splicing methods, safety switch mounting at six feet height, device plate alignment and labeling, and panelboard installation with top handles not exceeding 72 inches. Field quality control mandates insulation resistance testing (minimum 25 Megohms for 300-volt cable, 100 Megohms for 600-volt cable), continuity testing, phase-rotation testing on three-phase circuits, and submission of test reports before conductor energization. All work must comply with referenced standards including NFPA 70, NEMA standards, IEEE standards, UL standards, and NASA's Reliability Centered Building and Equipment Acceptance Program.

View the file

Other files

File Type Posted
03 39 00.00 10.pdf PDF
03 62 16.pdf PDF
04 20 00.pdf PDF
05 21 00.pdf PDF
06 20 00.pdf PDF
06 61 16.pdf PDF
07 60 00.pdf PDF
07 61 14.00 20.pdf PDF
07 84 00.pdf PDF
07 92 00.pdf PDF
08 11 16.pdf PDF
08 36 13.pdf PDF
08 71 00.pdf PDF
09 68 00.pdf PDF
10 28 13.pdf PDF
13 48 00.pdf PDF
21 13 17.pdf PDF
22 00 00.pdf PDF
23 00 00.pdf PDF
23 08 00.pdf PDF
23 11 25.pdf PDF
23 35 00.pdf PDF
23 64 26.pdf PDF
23 82 16.00 40.pdf PDF
23 82 43.00 40.pdf PDF
26 56 00.pdf PDF
31 23 06.pdf PDF
32 01 14.pdf PDF
32 13 74.pdf PDF
03 11 13.00 10.pdf PDF
03 20 00.00 10.pdf PDF
03 30 00.pdf PDF
07 14 00.pdf PDF
190023 Renovate Restrooms B117 RFIs_FINAL_COR_Signed.pdf PDF
TAFB_Tech_Reqs (Div 02-48).zip ZIP file
Model.zip ZIP file
00 71 00.pdf PDF
01 78 23.pdf PDF
000_TABLE OF CONTENTS.pdf PDF
01 32 16.00 20.pdf PDF
01 33 16.00 10.pdf PDF
01 42 00.pdf PDF
01 78 00.pdf PDF
Tinker General Requirements Specifications_Nov 2022_Change Log.pdf PDF
Initial Site Visit WWYK190023.pdf PDF
Solicitation - FA813726R0030.pdf PDF
Att10_190023_SOW.pdf PDF
EAL List - BLANK to Contractors WWYK190023.xlsx XLSX spreadsheet
Att12_190023_Drawings_Final.pdf PDF
Section L - Instructions to Offerors.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 26 05 00. 00 40

COMMON WORK RESULTS FOR ELECTRI CAL

04/17

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN SOCI ETY OF CI VI L ENGI NEERS ( ASCE)

ASCE 7 ( 2010; Er r at a 2011; Supp 1 2013) Mi ni mum Desi gn Loads f or Bui l di ngs and Ot her Structures

ASTM I NTERNATI ONAL ( ASTM)

ASTM D709 ( 2016) Lami nat ed Ther moset t i ng Mat er i al s

ELECTRONI C I NDUSTRI ES ALLI ANCE ( EI A)

EI A 480 ( 1981) Toggl e Swi t ches

I NSTI TUTE OF ELECTRI CAL AND ELECTRONI CS ENGI NEERS ( I EEE)

I EEE C57. 12. 28 ( 2014) St andar d f or Pad- Mount ed Equi pment

- Encl osur e I nt egr i t y

I EEE C57. 12. 29 ( 2014) St andar d f or Pad- Mount ed Equi pment

- Encl osur e I nt egr i t y f or Coast al Environments

I EEE St ds Di ct i onar y ( 2009) I EEE St andar ds Di ct i onar y: Gl ossar y of Ter ms & Def i ni t i ons

I NTERNATI ONAL CODE COUNCI L ( I CC)

I CC/ ANSI A117. 1 ( 2009) Accessi bl e and Usabl e Bui l di ngs and Facilities

NATI ONAL AERONAUTI CS AND SPACE ADMI NI STRATI ON ( NASA)

RCBEA GUI DE ( 2004) NASA Rel i abi l i t y Cent er ed Bui l di ng and Equi pment Accept ance Gui de

NATI ONAL ELECTRI CAL MANUFACTURERS ASSOCI ATI ON ( NEMA)

ANSI Z535. 1 ( 2006; R 2011) Amer i can Nat i onal St andar d f or Saf et y- - Col or Code

ANSI / NEMA OS 1 ( 2013) Sheet - St eel Out l et Boxes, Devi ce Boxes, Cover s, and Box Suppor t s

ANSI / NEMA OS 2 ( 2013) Nonmet al l i c Out l et Boxes, Devi ce

Apr i l 2019 Page 1 SECTI ON 26 05 00. 00 40

Boxes, Cover s, and Box Suppor t s

NEMA 250 ( 2014) Encl osur es f or El ect r i cal Equi pment ( 1000 Vol t s Maxi mum)

NEMA FB 1 ( 2014) St andar d f or Fi t t i ngs, Cast Met al Boxes, and Condui t Bodi es f or Condui t , El ect r i cal Met al l i c Tubi ng, and Cabl e

NEMA KS 1 ( 2013) Encl osed and Mi scel l aneous Di st r i but i on Equi pment Swi t ches ( 600 V Maximum)

NEMA PB 1 ( 2011) Panel boar ds

NEMA RN 1 ( 2005; R 2013) Pol yvi nyl - Chl or i de ( PVC) Ext er nal l y Coat ed Gal vani zed Ri gi d St eel Condui t and I nt er medi at e Met al Condui t

NEMA TC 2 ( 2013) St andar d f or El ect r i cal Pol yvi nyl Chl or i de ( PVC) Condui t

NEMA TC 3 ( 2015) St andar d f or Pol yvi nyl Chl or i de ( PVC) Fi t t i ngs f or Use Wi t h Ri gi d PVC Condui t and Tubi ng

NEMA VE 1 ( 2009) St andar d f or Met al Cabl e Tr ay Systems

NEMA WD 1 ( 1999; R 2015) St andar d f or Gener al Col or Requi r ement s f or Wi r i ng Devi ces

NEMA WD 6 ( 2016) Wi r i ng Devi ces Di mensi ons Specifications

NATI ONAL FI RE PROTECTI ON ASSOCI ATI ON ( NFPA)

NFPA 70 ( 2014; AMD 1 2013; Er r at a 1 2013; AMD 2 2013; Er r at a 2 2013; AMD 3 2014; Er r at a 3- 4 2014; AMD 4- 6 2014) Nat i onal El ect r i cal Code

TELECOMMUNI CATI ONS I NDUSTRY ASSOCI ATI ON ( TI A)

TIA-222 ( 2009g; Add 1 2007; Add 2 2009; R 2012; R 2013; R 2014) St r uct ur al St andar ds f or Ant enna Suppor t i ng St r uct ur es and Ant ennas

UNDERWRI TERS LABORATORI ES ( UL)

UL 1 ( 2005; Repr i nt Jul 2012) St andar d f or Fl exi bl e Met al Condui t

UL 1242 ( 2006; Repr i nt Mar 2014) St andar d f or El ect r i cal I nt er medi at e Met al Condui t - - Steel

UL 489 ( 2013; Repr i nt Mar 2014) Mol ded- Case Ci r cui t Br eaker s, Mol ded- Case Swi t ches, Apr i l 2019 Page 2 SECTI ON 26 05 00. 00 40 and Ci r cui t - Br eaker Encl osur es

UL 506 ( 2008; Repr i nt Oct 2013) Speci al t y Transformers

UL 6 ( 2007; Repr i nt Nov 2014) El ect r i cal Ri gi d Met al Condui t - St eel

UL 797 ( 2007; Repr i nt Dec 2012) El ect r i cal Met al l i c Tubi ng - - St eel

UL 870 ( 2008; Repr i nt Feb 2013) St andar d f or Wi r eways, Auxi l i ar y Gut t er s, and Associ at ed Fi t t i ngs

1. 2 DEFINITIONS

a. Unl ess ot her wi se speci f i ed or i ndi cat ed, el ect r i cal and el ect r oni cs t er ms used i n t hese speci f i cat i ons, and on t he dr awi ngs, ar e as def i ned i n I EEE St ds Di ct i onar y.

b. The t echni cal sect i ons r ef er r ed t o her ei n ar e t hose speci f i cat i on sect i ons t hat descr i be pr oduct s, i nst al l at i on pr ocedur es, and equi pment oper at i ons and t hat r ef er t o t hi s sect i on f or det ai l ed descr i pt i on of submi t t al t ypes.

c. Ver t i cal assembl y: A ver t i cal assembl y i s a pol e, t ower or ot her such suppor t , mount i ng har dwar e, ar ms, br acket s and t he l oad. Load can be a l umi nai r e, s i r en, l oudspeaker or ot her devi ce. Al l component s of a ver t i cal assembl y wi l l be r at ed by t he manuf act ur er t o wi t hst and 100 mph wi nd l oadi ng i n accor dance wi t h ASCE 7and TIA-222 .

1. 3 SUBMITTALS

Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00 SUBMI TTAL

PROCEDURES:

SD- 01 Pr econst r uct i on Submi t t al s

Mat er i al , Equi pment , and Fi xt ur e Li st s

SD- 03 Pr oduct Dat a

Condui t s and Raceways;

Wi r e and Cabl e;

Spl i ces and Connect or s;

Switches;

Receptacles;

Out l et Boxes, Pul l Boxes and Junct i on Boxes;

Ci r cui t Br eaker s;

Panelboards;

Apr i l 2019 Page 3 SECTI ON 26 05 00. 00 40

Lamps and Li ght i ng Fi xt ur es;

Dr y- Type Di st r i but i on Tr ansf or mer s;

SD- 06 Test Repor t s

Cont i nui t y Test ;

Phase- Rot at i on Test s;

I nsul at i on Resi st ance Test ;

SD- 08 Manuf act ur er ' s I nst r uct i ons

Manuf act ur er ' s I nst r uct i ons

1. 4 QUALI TY CONTROL

1. 4. 1 Pr edi ct i ve Test i ng and I nspect i on Technol ogy Requi r ement s

Thi s sect i on cont ai ns syst ems and equi pment component s r egul at ed by NASA' s Rel i abi l i t y Cent er ed Bui l di ng and Equi pment Accept ance Pr ogr am. Thi s pr ogr am r equi r es t he use of Pr edi ct i ve Test i ng and I nspect i on ( PT&I ) t echnol ogi es i n conf or mance wi t h RCBEA GUI DE t o ensur e bui l di ng equi pment and syst ems i nst al l ed have been i nst al l ed pr oper l y and cont ai n no i dent i f i abl e def ect s t hat shor t en t he desi gn l i f e of a syst em and i t s component s. Sat i sf act or y compl et i on of al l accept ance r equi r ement s i s r equi r ed t o obt ai n Gover nment appr oval and accept ance of t he wor k.

Per f or m PT&I t est s and pr ovi de submi t t al s as speci f i ed i n t he pr oj ect SOW.

PART 2 PRODUCTS

2. 1 EQUIPMENT

Pr ovi de t he st andar d cat al oged mat er i al s and equi pment of manuf act ur er s r egul ar l y engaged i n t he manuf act ur e of t he pr oduct s. For mat er i al , equi pment , and f i xt ur e l i s t s submi t t al s, show manuf act ur er ' s st y l e or cat al og number s, speci f i cat i on and dr awi ng r ef er ence number s, war r ant y i nf or mat i on, and f abr i cat i on s i t e.

2. 1. 1 Condui t s and Raceways

2. 1. 1. 1 Ri gi d St eel Condui t

Pr ovi de hot di pped gal vani zed r i gi d st eel condui t compl yi ng wi t h UL 6.

Except wher e i nst al l ed under gr ound, or i n cor r osi ve ar eas, pr ovi de pol yvi nyl chl or i de ( PVC) , or pai nt ed wi t h bi t umast i c coat ed r i gi d st eel condui t i n accor dance wi t h NEMA RN 1.

Use t hr eaded f i t t i ngs f or r i gi d st eel condui t .

Use sol i d gasket s. Ensur e condui t f i t t i ngs wi t h bl ank cover s have gasket s, except i n c l ean, dr y ar eas or at t he l owest poi nt of a condui t r un wher e dr ai nage i s r equi r ed.

Pr ovi de cover s wi t h capt i ve scr ews and ar e accessi bl e af t er t he wor k has been compl et ed.

Apr i l 2019 Page 4 SECTI ON 26 05 00. 00 40

2. 1. 1. 2 El ect r i cal Met al l i c Tubi ng ( EMT)

Ensur e EMT i s i n accor dance wi t h UL 797 and i s z i nc coat ed st eel . Pr ovi de zi nc- coat ed coupl i ngs and connect or s t hat ar e r ai nt i ght , gl and compr essi on t ype wi t h i nsul at i on t hr oat . Cr i mp, spr i ng, or set scr ew t ype f i t t i ngs ar e not accept abl e.

2. 1. 1. 3 Fl exi bl e Met al l i c Condui t

Ensur e f l exi bl e met al l i c condui t i s gal vani zed st eel and compl i es wi t h UL 1.

Ensur e f i t t i ngs f or f l exi bl e met al l i c condui t ar e speci f i cal l y desi gned f or such condui t .

Pr ovi de l i qui dt i ght f l exi bl e met al l i c condui t wi t h a pr ot ect i ve j acket of PVC ext r uded over a f l exi bl e i nt er l ocked gal vani zed st eel cor e t o pr ot ect wi r i ng agai nst moi st ur e, oi l , chemi cal s, and cor r osi ve f umes.

Ensur e f i t t i ngs f or l i qui dt i ght f l exi bl e met al l i c condui t ar e speci f i cal l y desi gned f or such condui t .

2. 1. 1. 4 I nt er medi at e Met al Condui t

Ensur e i nt er medi at e met al condui t i s gal vani zed st eel and compl i es wi t h

UL 1242.

2. 1. 1. 5 Ri gi d Nonmet al l i c Condui t

Ensur e r i gi d nonmet al l i c condui t compl i es wi t h NEMA TC 2 and NEMA TC 3 wi t h a wal l t hi ckness not l ess t han Schedul e 40.

2. 1. 1. 6 Wi r eways and Auxi l i ar y Gut t er s

Ensur e wi r eways and auxi l i ar y gut t er s ar e a mi ni mum 4 by 4- i nch t r ade si ze conf or mi ng t o UL 870.

2. 1. 1. 7 Sur f ace Raceways and Assembl i es

Ensur e sur f ace met al r aceways and mul t i - out l et assembl i es conf or m t o NFPA 70, and have r ecept acl es conf or mi ng t o NEMA WD 1, Type 5- 20R.

2. 1. 2 Cabl e Tr ays

Pr ovi de l adder t ype cabl e t r ays conf or mi ng t o NEMA VE 1.

2. 1. 3 Wi r e and Cabl e

Use copper 600- vol t t ype THHN, THWN, or XHHW, as speci f i ed f or conduct or s i nst al l ed i n condui t . Ensur e al l conduct or s i zes ar e st r anded. .

Ensur e f l exi bl e cabl e i s Type SO and cont ai ns a gr oundi ng conduct or wi t h gr een i nsul at i on.

Ensur e conduct or s i nst al l ed i n pl enums ar e mar ked pl enum r at ed.

Apr i l 2019 Page 5 SECTI ON 26 05 00. 00 40

2. 1. 4 Switches

2. 1. 4. 1 Saf et y Swi t ches

Ensur e saf et y swi t ches compl y wi t h NEMA KS 1, and ar e t he heavy- dut y t ype wi t h encl osur e, vol t age, cur r ent r at i ng, number of pol es, and f usi ng as i ndi cat ed on t he dr awi ngs. Ensur e swi t ch const r uct i on i s such t hat , when t he swi t ch handl e i n t he " ON" posi t i on, t he cover or door cannot be opened. Cover r el ease devi ce i s coi npr oof and so const r uct ed t hat an ext er nal t ool i s used t o open t he cover . Make pr ovi s i ons t o l ock t he handl e i n t he " OFF" posi t i on. Ensur e t he swi t ch i s not capabl e of bei ng l ocked i n t he " ON" posi t i on.

Pr ovi de swi t ches of t he qui ck- make, qui ck- br eak t ype and t er mi nal l ugs f or use wi t h copper conduct or s.

Ensur e saf et y col or codi ng f or i dent i f i cat i on of saf et y swi t ches conf or ms to ANSI Z535. 1.

2. 1. 4. 2 Toggl e Swi t ches

Ensur e t oggl e swi t ches compl y wi t h EI A 480, cont r ol i ncandescent , mer cur y, and f l uor escent l i ght i ng f i x t ur es and ar e t he heavy dut y, gener al pur pose, noni nt er changeabl e f l ush- t ype.

Pr ovi de commer ci al gr ade t oggl e swi t ches, s i ngl e, doubl e- pol e, t hr ee and f our - way t wo- posi t i on devi ces r at ed 20 amper es at 277 vol t s, 60 her t z al t er nat i ng cur r ent ( ac) onl y, as speci f i ed.

Ensur e al l t oggl e swi t ches ar e pr oduct s of t he same manuf act ur er .

2. 1. 5 Receptacles

Pr ovi de commer ci al gr ade, NEMA 5- 20R r ecept acl es, 20A, 125 VAC, 2- pol e, 3- wi r e dupl ex conf or mi ng t o NEMA WD 6.

2. 1. 6 Out l et Boxes, Pul l Boxes and Junct i on Boxes

Ensur e out l et boxes f or use wi t h condui t syst ems ar e i n accor dance wi t h NEMA FB 1 and ANSI / NEMA OS 1 or ANSI / NEMA OS 2, as speci f i ed and ar e not l ess t han 1- 1/ 2 i nches deep. Fur ni sh al l pul l and j unct i on boxes wi t h scr ew- f ast ened cover s.

2. 1. 7 Panelboards

Pr ovi de ci r cui t br eaker t ype l i ght i ng and appl i ance br anch ci r cui t panel boar ds i n accor dance wi t h NEMA PB 1. Bol t c i r cui t br eaker s t o t he bus. Pl ug- i n c i r cui t br eaker s ar e not accept abl e. Pr ovi de copper buses of t he r at i ng i ndi cat ed on t he dr awi ngs, wi t h mai n l ugs or mai n c i r cui t br eaker . Pr ovi de al l panel boar ds f or use on gr ounded ac syst ems wi t h a f ul l - capaci t y i sol at ed neut r al bus and a separ at e gr oundi ng bus bonded t o t he panel boar d encl osur e. Ensur e panel boar d encl osur es ar e NEMA 250, Type 1, i n accor dance wi t h NEMA PB 1. Pr ovi de encl osur e f r ont s wi t h l at chabl e hi nged door s.

2. 1. 8 Ci r cui t Br eaker s

Ensur e c i r cui t br eaker i nt er r upt i ng r at i ng i s not l ess t han t hose i ndi cat ed and i n no event l ess t han 10, 000 amper es r oot - mean- squar e ( r ms)

Apr i l 2019 Page 6 SECTI ON 26 05 00. 00 40 symmet r i cal at 208 vol t s, r espect i vel y. Pr ovi de mul t i pol e c i r cui t br eaker s of t he common- t r i p t ype wi t h a s i ngl e handl e. Mol ded case ci r cui t br eaker s ar e bol t - on t ype conf or mi ng t o UL 489.

2. 1. 9 Lamps and Li ght i ng Fi xt ur es

Manuf act ur er s and cat al og number s shown on t he dr awi ngs ar e i ndi cat i ve of t he gener al t ype desi r ed and ar e not i nt ended t o r est r i ct t he sel ect i on t o f i x t ur es of any par t i cul ar manuf act ur er . Fi xt ur es wi t h t he same sal i ent f eat ur es and equi val ent l i ght di st r i but i on and br i ght ness char act er i st i cs, of equal f i ni sh and qual i t y, ar e accept abl e. Pr ovi de l amps of t he pr oper t ype and wat t age f or each f i xt ur e.

Ensur e bal l ast s have a hi gh power f act or and ar e ener gy ef f i c i ent .

Pr ovi de bal l ast s wi t h a Cl ass P t er mi nal pr ot ect i ve devi ce f or 120 or 277

- vol t oper at i on, as i ndi cat ed, and ar e r api d- st ar t f l uor escent . Use bal l ast s t hat ar e " A" sound r at ed. Pr ovi de st andar d r educed wat t age t ype f l uor escent l amps.

Pr ovi de hi gh i nt ensi t y di schar ge ( HI D) l i ght i ng f i x t ur es t hat have pr ewi r ed i nt egr al bal l ast s and cast al umi num housi ngs compl et e wi t h t emper ed gl ass l enses sui t abl e f or i nst al l at i on i n damp or wet l ocat i ons.

Pr ovi de f i xt ur es and l amps.

2. 1. 10 Manuf act ur er ' s Namepl at e

Ensur e each i t em of equi pment has a namepl at e bear i ng t he manuf act ur er ' s name, addr ess, model number , and ser i al number secur el y af f i xed i n a conspi cuous pl ace; t he namepl at e of t he di st r i but i ng agent i s not acceptable.

2. 1. 11 War ni ng Si gns

Pr ovi de war ni ng si gns f or t he encl osur es of el ect r i cal equi pment i ncl udi ng subst at i ons, pad- mount ed t r ansf or mer s, pad- mount ed swi t ches, gener at or s, and swi t chgear havi ng a nomi nal r at i ng exceedi ng 600 vol t s.

a. Encl osur e i nt egr i t y t o conf or m wi t h I EEE C57. 12. 28 and I EEE C57. 12. 29, such as f or pad- mount ed t r ansf or mer s. Pr ovi de sel f - adhesi ve war ni ng si gns on t he out si de of t he hi gh vol t age compar t ment door ( s) . Pr ovi de decal s i gns wi t h nomi nal di mensi ons of 7 by 10 i nches. Pr i nt t he l egend " DANGER HI GH VOLTAGE" i n t wo l i nes of nomi nal 2 i nch hi gh l et t er s. Show t he wor d " DANGER" i n whi t e l et t er s on a r ed backgr ound and t he wor ds " HI GH VOLTAGE" i n bl ack l et t er s on a whi t e backgr ound.

Use Pandui t decal No. PPSO710D72 or appr oved equal .

b. When such equi pment i s guar ded by a f ence, mount s i gns on t he f ence.

Pr ovi de met al s i gns havi ng nomi nal di mensi ons of 14 by 10 i nches wi t h t he l egend " DANGER HI GH VOLTAGE KEEP OUT" pr i nt ed i n t hr ee l i nes of nomi nal 3- i nch hi gh whi t e l et t er s on a r ed and bl ack f i el d.

2. 1. 12 Dr y- Type Di st r i but i on Tr ansf or mer s

Ensur e t hat gener al pur pose dr y- t ype t r ansf or mer s wi t h wi ndi ngs 600 vol t s or l ess ar e t wo- wi ndi ng, 60 her t z, and sel f - cool ed i n accor dance wi t h UL 506. Ensur e wi ndi ngs have a mi ni mum of t wo 2- 1/ 2- per cent t aps above and bel ow nomi nal vol t age.

Apr i l 2019 Page 7 SECTI ON 26 05 00. 00 40

PART 3 EXECUTI ON

3. 1 PREPARATION

Submi t manuf act ur er ' s i nst r uct i ons i ncl udi ng speci al pr ovi s i ons r equi r ed t o i nst al l equi pment component s and syst em packages. Speci al pr ovi s i ons i ncl ude i mpedances, hazar ds and saf et y pr ecaut i ons.

Cl ean and pai nt condui t , suppor t s, f i t t i ngs, cabi net s, pul l boxes, and r acks as speci f i ed i n Sect i on 09 90 00 PAI NTS AND COATI NGS.

Do not use al umi num when i n cont act wi t h ear t h or concr et e and, wher e connect ed t o di ssi mi l ar met al , pr ot ect by usi ng appr oved f i t t i ngs and t r eat ment . Except wher e ot her equi val ent pr ot ect i ve t r eat ment i s speci f i cal l y appr oved i n wr i t i ng, pr ovi de hot - di p gal vani zed f er r ous met al s f or i t ems such as, anchor s, bol t s, br aces, boxes, bodi es, c l amps, f i t t i ngs, guar ds, nut s, pi ns, r ods, shi ms, t hi mbl es, washer s, and mi scel l aneous i t ems not made of cor r osi on- r esi st ant st eel .

3. 2 INSTALLATION

3. 2. 1 Condui t s, Raceways and Fi t t i ngs

Ensur e t hat condui t r uns bet ween out l et and out l et , bet ween f i t t i ng and f i t t i ng, or bet ween out l et and f i t t i ng does not cont ai n mor e t han t he equi val ent of t hr ee 90- degr ee bends, i ncl udi ng t hose bends l ocat ed i mmedi at el y at t he out l et or f i t t i ng.

Do not i nst al l cr ushed or def or med condui t . Avoi d t r apped condui t r uns wher e possi bl e. Take car e t o pr event t he l odgment of f or ei gn mat er i al i n t he condui t , boxes, f i t t i ngs, and equi pment dur i ng t he cour se of const r uct i on. Cl ear any cl ogged condui t of obst r uct i ons or r epl ace conduit.

Condui t and r aceway r uns conceal ed i n or behi nd wal l s, above cei l i ngs, or exposed on wal l s and cei l i ngs 5 f eet or mor e above f i ni shed f l oor s and not subj ect t o mechani cal damage may be el ect r i cal met al l i c t ubi ng ( EMT) .

3. 2. 1. 1 Ri gi d St eel Condui t

Make f i el d- made bends and of f set s wi t h appr oved Hi ckey bendi ng t ool or condui t bendi ng machi ne. Use l ong r adi us condui t f or el bows l ar ger t han 2- 1/ 2 i nches.

Pr ovi de a f l ush coupl i ng f or al l condui t st ubbed- up t hr ough concr et e f l oor s f or connect i ons t o f r ee- st andi ng equi pment wi t h t he except i on of mot or - cont r ol cent er s, cubi c l es, and ot her such i t ems of equi pment , when t he f l oor s l ab i s of suf f i c i ent t hi ckness. Ot her wi se, pr ovi de a f l oor box set f l ush wi t h t he f i ni shed f l oor . For condui t s i nst al l ed f or f ut ur e use, t er mi nat e wi t h a coupl i ng and pl ug; set f l ush wi t h t he f l oor .

3. 2. 1. 2 El ect r i cal Met al l i c Tubi ng ( EMT)

Gr ound EMT i n accor dance wi t h NFPA 70, usi ng pr essur e gr oundi ng connect or s especi al l y desi gned f or EMT.

3. 2. 1. 3 Fl exi bl e Met al l i c Condui t

Use f l exi bl e met al l i c condui t t o connect r ecessed f i xt ur es f r om out l et

Apr i l 2019 Page 8 SECTI ON 26 05 00. 00 40 boxes i n cei l i ngs, t r ansf or mer s, and ot her appr oved assembl i es.

Use bondi ng wi r es i n f l exi bl e condui t as speci f i ed i n NFPA 70, f or al l c i r cui t s. Fl exi bl e condui t i s not consi der ed a gr ound conduct or .

Make el ect r i cal connect i ons t o v i br at i on- i sol at ed equi pment wi t h f l exi bl e met al l i c condui t .

Use l i qui dt i ght f l exi bl e met al l i c condui t i n wet and oi l y l ocat i ons and t o compl et e t he connect i on t o mot or - dr i ven equi pment .

3. 2. 1. 4 I nt er medi at e Condui t

Make al l f i el d- made bends and of f set s wi t h appr oved Hi ckey bendi ng t ool or condui t bendi ng machi ne. Use i nt er medi at e met al condui t onl y f or i ndoor installations.

3. 2. 1. 5 Ri gi d Nonmet al l i c Condui t

Ensur e r i gi d PVC condui t i s di r ect bur i ed.

I nst al l a gr een i nsul at ed copper gr oundi ng conduct or i n condui t wi t h conduct or s and sol i dl y connect t o gr ound at each end. Si ze gr oundi ng wi r es i n accor dance wi t h NFPA 70.

3. 2. 1. 6 Wi r eway and Auxi l i ar y Gut t er

Bol t t oget her st r ai ght sect i ons and f i t t i ngs t o pr ovi de a r i gi d, mechani cal connect i on and el ect r i cal cont i nui t y. Cl ose dead ends of wi r eways and auxi l i ar y gut t er s. Pl ug al l unused condui t openi ngs.

Suppor t wi r eways f or over head di st r i but i on and cont r ol c i r cui t s at maxi mum 5- f oot i nt er val s.

Ensur e auxi l i ar y gut t er s used t o suppl ement wi r i ng spaces f or equi pment not cont ai ned i n a s i ngl e encl osur e cont ai ns no swi t ches, over cur r ent devi ces, appl i ances, or appar at us and i s not mor e t han 30 f eet l ong.

3. 2. 1. 7 Sur f ace Raceways and Assembl i es

Mount sur f ace r aceways pl umb and l evel , wi t h t he base and cover secur ed.

Mi ni mum ci r cui t r un i s t hr ee- wi r e, wi t h one wi r e desi gnat ed as gr ound.

3. 2. 1. 8 Cabl e Tr ays

Suppor t cabl e t r ays f r om cei l i ng hanger s, equi pment bays, or f l oor or wal l suppor t s. Cabl e t r ays may be mount ed on equi pment r acks. Pr ovi de suppor t when t he f r ee end ext ends beyond 3 f eet . Maxi mum suppor t spaci ng i s 6 f eet .

Suppor t t r ays 10- i nches wi de or l ess by one hanger . Suppor t t r ays gr eat er t han 10 i nches wi de by t wo hanger s. Bond cabl e t r ays at spl i ces.

3. 2. 1. 9 Spl i ces and Connect or s

Make al l spl i ces i n AWG No. 8 and smal l er wi t h appr oved i ndent or cr i mp- t ype connect or s and compr essi on t ool s.

Make al l spl i ces i n AWG No. 6 and l ar ger wi t h i ndent or cr i mp- t ype connect or s and compr essi on t ool s. Wr ap j oi nt s wi t h an i nsul at i ng t ape t hat has an i nsul at i on and t emper at ur e r at i ng equi val ent t o t hat of t he

Apr i l 2019 Page 9 SECTI ON 26 05 00. 00 40 conductor.

3. 2. 2 Wiring

Col or code f eeder and br anch ci r cui t conduct or s as f ol l ows:

CONDUCTOR COLOR AC

Phase A Bl ack 208v / Br own 480v

Phase B Red 208v / Or ange 480v

Phase C Bl ue 208v / Yel l ow 480v

Neutral White

Equi pment Gr ounds Green

Use conduct or s f or al l s i zes whi ch ar e pr ovi ded wi t h f act or y- appl i ed, col or - i mpr egnat ed i nsul at i ng mat er i al s.

Spl i ce i n accor dance wi t h t he NFPA 70. Pr ovi de conduct or i dent i f i cat i on wi t hi n each encl osur e wher e a t ap, spl i ce, or t er mi nat i on i s made and at t he equi pment t er mi nal of each conduct or . Mat ch t er mi nal and conduct or i dent i f i cat i on as i ndi cat ed.

Wher e sever al f eeder s pass t hr ough a common pul l box, t ag t he f eeder s t o c l ear l y i ndi cat e t he el ect r i cal char act er i st i cs, c i r cui t number , and panel designation.

3. 2. 3 Saf et y Swi t ches

Secur el y f ast en swi t ches t o t he suppor t i ng st r uct ur e or wal l , ut i l i z i ng a mi ni mum of f our 1/ 4 i nch bol t s. Do not use sheet met al scr ews and smal l machi ne scr ews f or mount i ng. Do not mount swi t ches i n an i naccessi bl e l ocat i on or wher e t he passageway t o t he swi t ch may become obst r uct ed.

Mount i ng hei ght 6 f eet above f l oor l evel , when possi bl e.

3. 2. 4 Wi r i ng Devi ces

3. 2. 4. 1 Wal l Swi t ches and Recept acl es

I nst al l wal l swi t ches and r ecept acl es so t hat when devi ce pl at es ar e appl i ed, t he pl at es ar e al i gned ver t i cal l y t o wi t hi n 1/ 16 i nch.

Bond gr ound t er mi nal of each f l ush- mount ed r ecept acl e t o t he out l et box wi t h an appr oved gr een bondi ng j umper when used wi t h dr y wal l t ype construction.

3. 2. 4. 2 Devi ce Pl at es

Ensur e devi ce pl at es f or swi t ches ar e sui t abl y engr aved wi t h a descr i pt i on of t he l oads when not wi t hi n s i ght of t he l oads cont r ol l ed.

Mar k devi ce pl at es and r ecept acl e cover pl at es f or r ecept acl es ot her t han 125- vol t , s i ngl e- phase, dupl ex, conveni ence out l et s. Show t he ci r cui t

Apr i l 2019 Page 10 SECTI ON 26 05 00. 00 40 number , vol t age, f r equency, phasi ng, and amper age avai l abl e at t he r ecept acl e. Use sel f - adhesi ve l abel s havi ng 1/ 4 i nch embossed l et t er s.

Si mi l ar l y mar k devi ce pl at es f or conveni ence out l et s i ndi cat i ng t he suppl y panel and ci r cui t number .

3. 2. 5 Boxes and Fi t t i ngs

Pr ovi de pul l boxes wher e necessar y i n t he condui t syst em t o f aci l i t at e conduct or i nst al l at i on. For condui t r uns l onger t han 100 f eet or wi t h mor e t han t hr ee r i ght - angl e bends, i nst al l a pul l box at a conveni ent i nt er medi at e l ocat i on.

Secur el y mount boxes and encl osur es t o t he bui l di ng st r uct ur e usi ng suppor t s t hat ar e i ndependent of t he condui t ent er i ng or l eavi ng t he boxes.

Sel ect t he mount i ng hei ght of wal l - mount ed out l et and swi t ch boxes, as measur ed bet ween t he bot t om of t he box and t he f i ni shed f l oor , i n accor dance wi t h I CC/ ANSI A117. 1 and as f ol l ows:

LOCATION MOUNTI NG HEI GHT

(inches)

Recept acl es i n of f i ces 18

Recept acl es i n cor r i dor s 18

Recept acl es i n shops and l abor at or i es 48

Recept acl es i n r est r ooms 48

Swi t ches f or l i ght cont r ol 48

3. 2. 6 Lamps and Li ght i ng Fi xt ur es

I nst al l new l amps of t he pr oper t ype and wat t age i n each f i xt ur e.

Secur el y f ast en f i xt ur es and suppor t s t o st r uct ur al member s and i nst al l par al l el and per pendi cul ar t o maj or axes of st r uct ur es.

3. 2. 7 Panelboards

Secur el y mount panel boar ds so t hat t he t op oper at i ng handl e does not exceed 72- i nches above t he f i ni shed f l oor . Do not mount equi pment wi t hi n 36- i nches of t he f r ont of t he panel . Ensur e di r ect or y car d i nf or mat i on i s compl et e and l egi bl e.

3. 2. 8 Dr y- Type Di st r i but i on Tr ansf or mer s

Connect dr y- t ype t r ansf or mer s wi t h f l exi bl e met al l i c condui t .

Mount al l dr y- t ype t r ansf or mer s on vi br at i on i sol at or s i n accor dance wi t h Sect i on 23 05 48. 00 40 VI BRATI ON AND SEI SMI C CONTROLS FOR HVAC PI PI NG AND

EQUIPMENT.

3. 2. 9 Fi el d Fabr i cat ed Namepl at es

Ensur e namepl at es conf or m t o ASTM D709. Pr ovi de l ami nat ed pl ast i c namepl at es f or each equi pment encl osur e, r el ay, swi t ch, and devi ce, as

Apr i l 2019 Page 11 SECTI ON 26 05 00. 00 40 speci f i ed or as i ndi cat ed on t he dr awi ngs. Each namepl at e i nscr i pt i on i dent i f i es t he f unct i on and, when appl i cabl e, t he posi t i on. Pr ovi de namepl at es t hat ar e mel ami ne pl ast i c, 0. 125- i nch t hi ck, whi t e wi t h bl ack cent er cor e and a mat t e f i ni sh sur f ace wi t h squar e cor ner s. Accur at el y al i gn l et t er i ng and engr ave i nt o t he cor e. Mi ni mum si ze of namepl at es i s 1 by 2. 5 i nches. Let t er i ng i s a mi ni mum of 0. 25- i nch hi gh nor mal bl ock style.

3. 2. 10 I dent i f i cat i on Pl at es and War ni ngs

Pr ovi de i dent i f i cat i on pl at es f or l i ght i ng and power panel boar ds, mot or cont r ol cent er s, al l l i ne vol t age heat i ng and vent i l at i ng cont r ol panel s, f i r e det ect or and spr i nkl er al ar ms, door bel l s, pi l ot l i ght s, di sconnect swi t ches, manual st ar t i ng swi t ches, and magnet i c st ar t er s. At t ach i dent i f i cat i on pl at es t o pr ocess cont r ol devi ces and pi l ot l i ght s.

I nst al l i dent i f i cat i on pl at es f or al l l i ne vol t age encl osed ci r cui t br eaker s, i dent i f y i ng t he equi pment ser ved, vol t age, phase( s) and power sour ce. For c i r cui t s 480 vol t s and above, i nst al l conspi cuousl y l ocat ed war ni ng si gns i n accor dance wi t h OSHA r equi r ement s.

3. 2. 11 Post ed Oper at i ng I nst r uct i ons

Pr i nt or engr ave oper at i ng i nst r uct i ons and f r ame under gl ass or i n appr oved l ami nat ed pl ast i c. Post i nst r uct i ons wher e di r ect ed. For oper at i ng i nst r uct i ons exposed t o t he weat her , pr ovi de weat her - r esi st ant mat er i al s or weat her pr oof encl osur es. Ensur e oper at i ng i nst r uct i ons do not f ade when exposed t o sunl i ght . Secur e i nst r uct i ons t o pr event easy r emoval or peel i ng.

Ensur e each syst em and pr i nci pal i t em of equi pment i s as speci f i ed i n t he t echni cal sect i ons f or use by oper at i on and mai nt enance per sonnel .

I ncl ude t he f ol l owi ng i nf or mat i on wi t h t he oper at i ng i nst r uct i ons:

a. Wi r i ng di agr ams, cont r ol di agr ams, and cont r ol sequence f or each pr i nci pal syst em and i t em of equi pment .

b. St ar t up, pr oper adj ust ment , oper at i ng, l ubr i cat i on, and shut down procedures.

c. Saf et y pr ecaut i ons.

d. The pr ocedur e i n t he event of equi pment f ai l ur e.

e. Ot her i t ems of i nst r uct i on as r ecommended by t he manuf act ur er .

3. 3 FI ELD QUALI TY CONTROL

Af t er compl et i on of t he i nst al l at i on and spl i c i ng, and pr i or t o ener gi z i ng t he conduct or s, per f or m wi r e and cabl e cont i nui t y and i nsul at i on t est s as her ei n speci f i ed bef or e t he conduct or s ar e ener gi zed.

Pr ovi de al l necessar y t est equi pment , l abor , and per sonnel t o per f or m t he t est s, as her ei n speci f i ed.

I sol at e compl et el y al l wi r e and cabl e f r om al l ext r aneous el ect r i cal connect i ons at cabl e t er mi nat i ons and j oi nt s. Use subst at i on and swi t chboar d f eeder br eaker s, di sconnect s i n combi nat i on mot or st ar t er s, Apr i l 2019 Page 12 SECTI ON 26 05 00. 00 40 ci r cui t br eaker s i n panel boar ds, and ot her di sconnect i ng devi ces t o i sol at e t he c i r cui t s under t est .

Per f or m i nsul at i on- r esi st ance t est on each f i el d- i nst al l ed conduct or wi t h r espect t o gr ound and adj acent conduct or s. Appl i ed pot ent i al i s 500 vol t s dc f or 300 vol t r at ed cabl e and 1000 vol t s dc f or 600 vol t r at ed cabl e.

Take r eadi ngs af t er 1 mi nut e and unt i l t he r eadi ng i s const ant f or 15 seconds. Mi ni mum i nsul at i on- r esi st ance val ues i s not l ess t han 25 Megohms f or 300 vol t r at ed cabl e and 100 Megohms f or 600 vol t r at ed cabl e. For c i r cui t s wi t h conduct or s i zes AWG No. 8 and smal l er i nsul at i on r esi st ance t est i ng i s not r equi r ed.

Per f or m cont i nui t y t est t o i nsur e cor r ect cabl e connect i on end- t o- end ( i . e cor r ect phase conduct or , gr ounded conduct or , and gr oundi ng conduct or wi r i ng) . Repai r and ver i f y any damages t o exi st i ng or new el ect r i cal equi pment r esul t i ng f r om mi s- wi r i ng. Recei ve appr oval f or al l r epai r s f r om t he Cont r act i ng Of f i cer pr i or t o commencement of t he r epai r .

Conduct phase- r ot at i on t est s on al l t hr ee- phase ci r cui t s usi ng a phase- r ot at i on i ndi cat i ng i nst r ument . Per f or m phase r ot at i on of el ect r i cal connect i ons t o connect ed equi pment i n a c l ockwi se di r ect i on, f aci ng t he sour ce.

Submi t t est r epor t s i n accor dance wi t h r ef er enced st andar ds i n t hi s section.

Fi nal accept ance r equi r es t he successf ul per f or mance of wi r e and cabl e under t est . Do not ener gi ze any conduct or unt i l t he f i nal t est r epor t s ar e r evi ewed and appr oved by t he Cont r act i ng Of f i cer .

- - End of Sect i on - -