23 01 30.41.pdf

PDF 46 KB Posted

Attached to
TINKER AFB MAC BOA WWYK190023 Renovate Restrooms B117
Solicitation number
FA813726R0030
Issued by

About this file

This is a technical specification document for HVAC System Cleaning services at Tinker Air Force Base, Oklahoma, issued in April 2019.

The specification requires contractors to perform comprehensive cleaning of all interior surfaces of the facility's air distribution system, including return air grilles and ducts, air handling units (AHU), mixing boxes, coil compartments, condensate drain pans, supply air ducts, fans, fan housings, fan blades, air wash systems, spray eliminators, turning vanes, filters, filter housings, reheat coils, and supply diffusers. The contractor must be a National Air Duct Cleaners Association (NADCA) certified firm operating as an independent first-tier subcontractor and must comply with all current NADCA standards without modification or deviation. The NADCA team must include a supervisor with current NADCA certification and an Air System Cleaning Specialist (ASCS) with minimum three years of full-time field experience in HVAC cleaning, plus team assistants with at least one year of documented field experience. All personnel must be full-time employees of the NADCA firm, with replacements requiring Contracting Officer approval.

Cleaning must employ Source Removal mechanical methods with continuous vacuum collection using HEPA filtration when exhausting inside the building. The contractor must achieve "Visibly Clean" status as defined by NADCA standards, verified through visual inspection and gravimetric analysis testing at contractor expense. Cleanliness verification must occur immediately after mechanical cleaning and before system restoration. Service openings must be created and resealed per NADCA, NAIMA, SMACNA, and UL standards. All debris disposal must comply with federal, state, and local environmental requirements. Contractor must submit preconstruction documentation including NADCA firm certification, personnel qualifications, coordination plans, work execution schedules, Material Safety Data Sheets (MSDS) for all chemical products, and post-project reports documenting cleaning success and any system damage identified. The specification emphasizes occupant safety, preventing hazards in occupied spaces, and maintaining compliance with OSHA requirements and Army Corps of Engineers safety standards (EM 385-1-1).

View the file

Other files

File Type Posted
190023 Reno Restrooms B117 Pre Bid RFI Follow Up_COR_Signed.pdf PDF
02 41 00.pdf PDF
06 10 00.pdf PDF
07 12 00.pdf PDF
07 42 13.pdf PDF
07 42 63.pdf PDF
07 53 23.pdf PDF
07 54 19.pdf PDF
07 62 13.pdf PDF
08 41 13.pdf PDF
08 51 13.pdf PDF
08 51 23.pdf PDF
09 51 00.pdf PDF
09 65 00.pdf PDF
10 14 00.20.pdf PDF
22 05 48.00 20.pdf PDF
23 05 93.pdf PDF
23 36 00.00 40.pdf PDF
23 54 16 .pdf PDF
23 57 10.pdf PDF
23 81 00.pdf PDF
23 82 23.00 40.pdf PDF
23 82 46.00 40.pdf PDF
26 42 14.00 10.pdf PDF
26 51 00.pdf PDF
26 56 20.00 10.pdf PDF
28 31 33.00 10.pdf PDF
31 00 00.pdf PDF
32 01 17.pdf PDF
32 01 18.pdf PDF
32 01 22.pdf PDF
32 12 15.pdf PDF
32 31 13.pdf PDF
03 39 00.00 10.pdf PDF
03 62 16.pdf PDF
04 20 00.pdf PDF
05 21 00.pdf PDF
06 20 00.pdf PDF
06 61 16.pdf PDF
07 60 00.pdf PDF
07 61 14.00 20.pdf PDF
00 72 00.pdf PDF
00 80 00.pdf PDF
00 71 00.pdf PDF
01 78 23.pdf PDF
Att11_190023_Submittal Register_Final.pdf PDF
Wage Determination.pdf PDF
Solicitation - FA813726R0030.pdf PDF
Att10_190023_SOW.pdf PDF
EAL List - BLANK to Contractors WWYK190023.xlsx XLSX spreadsheet
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 23 01 30. 41

HVAC SYSTEM CLEANI NG

04/17

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN SOCI ETY OF HEATI NG, REFRI GERATI NG AND AI R- CONDI TI ONI NG

ENGI NEERS ( ASHRAE)

ASHRAE 62. 1 ( 2013) Vent i l at i on f or Accept abl e I ndoor Ai r Qual i t y

NATI ONAL AI R DUCT CLEANERS ASSOCI ATI ON ( NADCA)

ACR ( 2013) St andar d f or Assessment , Cl eani ng, and Rest or at i on of HVAC Syst ems

NADCA HVAC I nspect i on Manual ( 2005) Pr ocedur es f or Assessi ng t he Cl eanl i ness of Commer ci al HVAC Syst ems

NORTH AMERI CAN I NSULATI ON MANUFACTURERS ASSOCI ATI ON ( NAI MA)

NAI MA AH112 ( 1993) Cl eani ng Fi br ous Gl ass or Li ned Sheet Met al Duct s

NAI MA AH122 ( 2006) Cl eani ng Fi br ous I nsul at ed Duct Syst ems - Recommended Pr act i ces

NAI MA AH127 ( 1999) I mpact of Duct Cl eani ng on I nt er nal Duct I nsul at i on

SHEET METAL AND AI R CONDI TI ONI NG CONTRACTORS' NATI ONAL ASSOCI ATI ON

(SMACNA)

SMACNA 1966 ( 2005) HVAC Duct Const r uct i on St andar ds Met al and Fl exi bl e, 3r d Edi t i on

U. S. ARMY CORPS OF ENGI NEERS ( USACE)

EM 385- 1- 1 ( 2014) Saf et y and Heal t h Requi r ement s Manual

U. S. ENVI RONMENTAL PROTECTI ON AGENCY ( EPA)

EPA 402- C- 01- 001 ( 2001) I AQ Bui l di ng Educat i on and Assessment Tool ( I - BEAM)

EPA 402- F- 91- 102 ( 1991) Bui l di ng Ai r Qual i t y: A Gui de f or Bui l di ng Owner s and Faci l i t y Manager s

Apr i l 2019 Page 1 SECTI ON 23 01 30. 41

UNDERWRI TERS LABORATORI ES ( UL)

UL 181 ( 2013) Fact or y- Made Ai r Duct s and Ai r Connectors

UL 181A ( 2013) St andar d f or Cl osur e Syst ems f or Use wi t h Ri gi d Ai r Duct s and Ai r Connect or s

UL 181B ( 2013) St andar d f or Cl osur e Syst ems f or Use wi t h Fl exi bl e Ai r Duct s and Ai r Connectors

1. 2 DEFINITIONS

1. 2. 1 NADCA St andar ds

Per f or m t he ser vi ces speci f i ed her e i n accor dance wi t h t he cur r ent publ i shed st andar ds of t he Nat i onal Ai r Duct Cl eaner s Associ at i on ( ACR and NADCA HVAC I nspect i on Manual ).

a. Al l t er ms i n t hi s speci f i cat i on ar e def i ned as st at ed i n t he NADCA Standards.

b. Fol l ow NADCA St andar ds wi t hout modi f i cat i on or devi at i on.

1. 3 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval and i nf or mat i on onl y Submi t t al s wi t h an " S" ar e f or i ncl usi on i n t he Sust ai nabi l i t y Not ebook, i n conf or mance t o Sect i on 01 33 29 SUSTAI NABI LI TY REPORTI NG. Submi t t he f ol l owi ng i n accor dance wi t h Sect i on

01 33 00 SUBMI TTAL PROCEDURES:

SD- 01 Pr econst r uct i on Submi t t al s

Recor d of Exi st i ng Condi t i ons; G

Coor di nat i on Pl an; G

NADCA Fi r m; G

NADCA Team Assi st ant s; G

NADCA Ai r Syst em Cl eani ng Speci al i st ( ASCS) ; G

NADCA Super vi sor Qual i f i cat i ons; G

Recor ds of Exper i ence i n t he Fi el d of HVAC Syst em Cl eani ng; G

NADCA Wor k Execut i on Schedul e; G

SD- 03 Pr oduct Dat a

Mat er i al Saf et y Dat a Sheet s ( MSDS) ; G

SD- 06 Test Repor t s

Test i ng Pr ocedur es Summar y; G

Apr i l 2019 Page 2 SECTI ON 23 01 30. 41

Gr avi met r i c Anal ysi s; G

Post - Pr oj ect Repor t ; G

1. 4 QUALI TY CONTROL

1. 4. 1 NADCA Fi r m

Submi t i nf or mat i on cer t i f y i ng t hat t he NADCA f i r m i s a f i r st t i er subcont r act or who i s not af f i l i at ed wi t h any ot her company par t i c i pat i ng i n wor k on t hi s cont r act , i ncl udi ng f ur ni shi ng equi pment . Fur t her , submi t t he f ol l owi ng, f or t he f i r m, t o Cont r act i ng Of f i cer f or appr oval :

a. I ndependent NADCA f i r m:

NADCA Fi r m: NADCA r egi st r at i on number and expi r at i on dat e of cur r ent certification;

NADCA Super vi sor Qual i f i cat i ons: Name and copy of NADCA super vi sor cer t i f i cat e and expi r at i on dat e of cur r ent cer t i f i cat i on.

NADCA Ai r Syst em Cl eani ng Speci al i st ( ASCS) : Name and document ed evi dence t hat t he t eam f i el d l eader has sat i sf act or i l y per f or med f ul l - t i me super vi s i on of HVAC cl eani ng wor k i n t he f i el d f or not l ess t han 3 year s i mmedi at el y pr ecedi ng t hi s cont r act ' s bi d openi ng dat e.

NADCA Team Assi st ant s: Names and document ed evi dence t hat each f i el d t echni c i an has sat i sf act or i l y assi st ed a NADCA t eam f i el d l eader i n per f or mance of HVAC cl eani ng wor k i n t he f i el d f or not l ess t han one year i mmedi at el y pr ecedi ng t hi s cont r act ' s bi d openi ng dat e.

Cur r ent Cer t i f i cat es: Ensur e r egi st r at i ons and cer t i f i cat i ons ar e cur r ent , and val i d f or t he dur at i on of t hi s cont r act . Renew Cer t i f i cat i ons whi ch expi r e pr i or t o compl et i on of t he HVAC cl eani ng wor k, i n a t i mel y manner so t hat t her e i s no l apse i n r egi st r at i on or cer t i f i cat i on. NADCA agency or NADCA t eam per sonnel wi t hout a cur r ent r egi st r at i on or cur r ent cer t i f i cat i on ar e not t o per f or m HVAC cl eani ng wor k on t hi s cont r act .

b. TAB Team Member s: NADCA t eam appr oved t o accompl i sh wor k on t hi s cont r act ar e f ul l - t i me empl oyees of t he NADCA f i r m. No ot her per sonnel i s al l owed t o do HVAC cl eani ng wor k on t hi s cont r act .

c. Repl acement of NADCA Team Member s: Repl acement of member s may occur i f each new member compl i es wi t h t he appl i cabl e per sonnel qual i f i cat i ons and each i s appr oved by t he Cont r act i ng Of f i cer .

1. 4. 2 Experience

Submi t r ecor ds of exper i ence i n t he f i el d of HVAC syst em cl eani ng. Bi ds wi l l onl y be consi der ed f r om f i r ms whi ch ar e r egul ar l y engaged i n HVAC syst em mai nt enance wi t h an emphasi s on HVAC syst em cl eani ng and decontamination.

1. 4. 3 Equi pment , Mat er i al s and Labor

Possess and f ur ni sh al l necessar y equi pment , mat er i al s and l abor t o adequat el y per f or m t he speci f i ed ser vi ces and compl y wi t h t he appl i cabl e

Apr i l 2019 Page 3 SECTI ON 23 01 30. 41 pr ovi s i ons of NADCA Gener al Speci f i cat i ons f or t he Cl eani ng of Commer ci al HVAC Syst ems and ASHRAE 62. 1.

a. Assur e t hat al l empl oyees have r ecei ved saf et y equi pment t r ai ni ng, medi cal sur vei l l ance pr ogr ams, i ndi v i dual heal t h pr ot ect i on measur es, and manuf act ur er ' s pr oduct and Mat er i al Saf et y Dat a Sheet s ( MSDS) as r equi r ed f or t he wor k by t he U. S. Occupat i onal Saf et y and Heal t h Admi ni st r at i on, and as descr i bed by t hi s speci f i cat i on. For wor k per f or med i n count r i es out si de of t he U. S. A. , compl y wi t h appl i cabl e nat i onal saf et y codes and st andar ds.

b. Mai nt ai n a copy of al l cur r ent MSDS document at i on and saf et y cer t i f i cat i ons at t he s i t e at al l t i mes, as wel l as compl y wi t h al l ot her s i t e document at i on r equi r ement s of appl i cabl e OSHA pr ogr ams and t hi s speci f i cat i on.

c. Submi t al l Mat er i al Saf et y Dat a Sheet s ( MSDS) f or al l chemi cal pr oduct s pr oposed used i n t he c l eani ng pr ocess, i ncl udi ng al l VOC ratings.

1. 4. 4 Heal t h And Saf et y

1. 4. 4. 1 Saf et y St andar ds

Compl y wi t h al l appl i cabl e Feder al , St at e, and l ocal r equi r ement s f or pr ot ect i ng t he saf et y of t he cont r act or s ' empl oyees, bui l di ng occupant s, and t he envi r onment . I n par t i cul ar , f ol l ow al l appl i cabl e st andar ds of t he Occupat i onal Saf et y and Heal t h Admi ni st r at i on ( OSHA) when wor ki ng i n accor dance wi t h t hi s speci f i cat i on, and EM 385- 1- 1.

1. 4. 4. 2 Occupant Saf et y

Empl oy no pr ocesses or mat er i al s i n such a manner t hat i nt r oduce addi t i onal hazar ds i nt o occupi ed spaces.

1. 4. 4. 3 Di sposal of Debr i s

Di spose of al l debr i s r emoved f r om t he HVAC Syst em i n accor dance wi t h appl i cabl e Feder al , St at e and l ocal r equi r ement s.

1. 5 PROJECT/ SI TE CONDI TI ONS

1. 5. 1 Mechani cal Dr awi ngs

Obt ai n one copy of t he f ol l owi ng document s:

a. Pr oj ect dr awi ngs and speci f i cat i ons

b. Appr oved const r uct i on r evi s i ons per t ai ni ng t o t he HVAC syst em

c. Any exi st i ng i ndoor ai r qual i t y ( I AQ) assessment s or envi r onment al r epor t s pr epar ed f or t he f aci l i t y .

Submi t a NADCA Wor k Execut i on Schedul e t o t he Cont r act i ng Of f i cer wi t hi n 10 wor ki ng days of t he cont r act awar d.

1. 5. 2 Si t e Condi t i ons

The HVAC syst em i ncl udes any i nt er i or sur f ace of t he f aci l i t y ' s ai r

Apr i l 2019 Page 4 SECTI ON 23 01 30. 41 di st r i but i on syst em f or condi t i oned spaces and/ or occupi ed zones. Thi s i ncl udes t he ent i r e heat i ng, ai r - condi t i oni ng and vent i l at i on syst em f r om t he poi nt s wher e t he ai r ent er s t he syst em t o t he poi nt s wher e t he ai r i s di schar ged f r om t he syst em. The r et ur n ai r gr i l l es, r et ur n ai r duct s ( except cei l i ng pl enums and mechani cal r oom) t o t he ai r handl i ng uni t ( AHU) , t he i nt er i or sur f aces of t he AHU, mi xi ng box, coi l compar t ment , condensat e dr ai n pans, humi di f i er s and dehumi di f i er s, suppl y ai r duct s, f ans, f an housi ng, f an bl ades, ai r wash syst ems, spr ay el i mi nat or s, t ur ni ng vanes, f i l t er s, f i l t er housi ngs, r eheat coi l s, and suppl y di f f user s ar e al l consi der ed par t of t he HVAC syst em. The HVAC syst em may al so i ncl ude ot her component s such as dedi cat ed exhaust and vent i l at i on component s and make- up ai r syst ems.

PART 2 PRODUCTS

Not Used

PART 3 EXECUTI ON

Per f or m t he ser vi ces speci f i ed her e i n accor dance wi t h t he cur r ent publ i shed st andar ds of t he Nat i onal Ai r Duct Cl eaner s Associ at i on ( ACR and NADCA HVAC I nspect i on Manual ).

a. Al l t er ms i n t hi s speci f i cat i on have t hei r meani ng def i ned as st at ed i n t he NADCA St andar ds.

b. Fol l ow NADCA St andar ds wi t h no modi f i cat i ons or devi at i ons bei ng al l owed. Remove vi s i bl e sur f ace cont ami nant s and deposi t s f r om wi t hi n t he HVAC syst em i n st r i ct accor dance wi t h t hese speci f i cat i ons.

3. 1 PREPARATION

3. 1. 1 HVAC Syst em I nspect i ons And Si t e Pr epar at i ons

3. 1. 1. 1 HVAC Syst em Eval uat i on

Pr i or t o t he commencement of any c l eani ng wor k, per f or m a vi sual i nspect i on of t he HVAC syst em i n t he pr esence of t he Cont r act i ng Of f i cer t o det er mi ne appr opr i at e met hods, t ool s, and equi pment r equi r ed t o sat i sf act or i l y compl et e t hi s pr oj ect . Not i f y t he Cont r act i ng Of f i cer 10 days pr i or t o t he pl anned i nspect i on.

Document damaged syst em component s f ound dur i ng t he i nspect i on and submi t t o t he Cont r act i ng Of f i cer , c l ear l y l abel ed " Recor d of Exi st i ng Condi t i ons. "

3. 1. 1. 2 Si t e Eval uat i on and Pr epar at i ons

Conduct a s i t e eval uat i on, and est abl i sh a speci f i c , coor di nat i on pl an whi ch det ai l s how each ar ea of t he bui l di ng i s pr ot ect ed dur i ng t he var i ous phases of t he pr oj ect .

3. 2 APPLICATION

3. 2. 1 Gener al HVAC Syst em Cl eani ng Requi r ement s

3. 2. 1. 1 Containment

Col l ect debr i s r emoved dur i ng c l eani ng and t ake pr ecaut i ons t o ensur e t hat debr i s i s not ot her wi se di sper sed out si de t he HVAC syst em dur i ng t he

Apr i l 2019 Page 5 SECTI ON 23 01 30. 41 cl eani ng pr ocess.

3. 2. 1. 2 Par t i cul at e Col l ect i on

Wher e t he Par t i cul at e Col l ect i on Equi pment ( PCE) i s exhaust i ng i nsi de t he bui l di ng, use HEPA f i l t r at i on wi t h 99. 97 per cent col l ect i on ef f i c i ency f or

0. 3- mi cr on si ze ( or gr eat er ) . When t he PCE i s exhaust i ng out si de t he bui l di ng, under t ake mechani cal c l eani ng oper at i ons onl y wi t h PCE, i ncl udi ng adequat e f i l t r at i on t o cont ai n debr i s r emoved f r om t he HVAC syst em. When t he PCE i s exhaust i ng out si de t he bui l di ng, t ake pr ecaut i ons t o l ocat e t he equi pment down wi nd and away f r om al l ai r i nt akes and ot her poi nt s of ent r y i nt o t he bui l di ng.

3. 2. 1. 3 Cont r ol l i ng Odor s

Take al l r easonabl e measur es t o cont r ol of f ensi ve odor s and/ or mi st vapor s dur i ng t he cl eani ng pr ocess.

3. 2. 1. 4 Component Cl eani ng

Empl oy c l eani ng met hods such t hat al l HVAC syst em component s ar e Vi s i bl y Cl ean as def i ned i n appl i cabl e st andar ds. Upon compl et i on, r et ur n al l component s t o t hose set t i ngs r ecor ded j ust pr i or t o c l eani ng oper at i ons.

3. 2. 1. 5 Ai r - Vol ume Cont r ol Devi ces

Mar k t he posi t i on of damper s and any ai r - di r ect i onal mechani cal devi ces i nsi de t he HVAC syst em pr i or t o c l eani ng and, upon compl et i on, r est or e t o t hei r mar ked posi t i on.

3. 2. 1. 6 Ser vi ce Openi ngs

Ut i l i ze ser vi ce openi ngs, as r equi r ed f or pr oper c l eani ng, at var i ous poi nt s of t he HVAC syst em f or physi cal and mechani cal ent r y, and i nspect i on. Ut i l i ze t he exi st i ng ser vi ce openi ngs al r eady i nst al l ed i n t he HVAC syst em wher e possi bl e.

Cr eat e ot her openi ngs wher e needed, cr eat ed and r eseal ed i n conf or mance wi t h NADCA St andar d 05. Pl ace cl osur es so t hey do not s i gni f i cant l y hi nder , r est r i ct , al t er t he ai r - f l ow wi t hi n t he syst em, or compr omi se t he st r uct ur al i nt egr i t y of t he syst em. Pr oper l y i nsul at e c l osur es t o pr event heat l oss/ gai n or condensat i on on sur f aces wi t hi n t he syst em. Conf or m const r uct i on t echni ques used i n t he cr eat i on of openi ngs t o r equi r ement s of appl i cabl e bui l di ng and f i r e codes, and appl i cabl e NFPA, SMACNA and NADCA St andar ds. Cut t i ng ser vi ce openi ngs i nt o f l exi bl e duct i s not per mi t t ed. Di sconnect f l exi bl e duct at t he ends as needed f or pr oper c l eani ng and i nspect i on.

Reseal r i gi d f i ber gl ass duct boar d duct syst ems i n accor dance wi t h NAI MA r ecommended pr act i ces; NAI MA AH112, NAI MA AH122, and NAI MA AH127. Onl y c l osur e t echni ques whi ch compl y wi t h UL 181, UL 181A, or UL 181B ar e sui t abl e f or f i ber gl ass duct syst em cl osur es.

Cl ear l y mar k al l ser vi ce openi ngs, capabl e of bei ng r e- opened f or f ut ur e i nspect i on or r emedi at i on, and r epor t t hei r l ocat i on i n pr oj ect r epor t documents.

Apr i l 2019 Page 6 SECTI ON 23 01 30. 41

3. 2. 1. 7 Cei l i ng Sect i ons ( Ti l e)

Car ef ul l y r emove and r ei nst al l cei l i ng sect i ons t o gai n access t o HVAC syst ems dur i ng t he cl eani ng pr ocess. Repl ace any damaged cei l i ng sect i ons caused by t he r emoval at no cost t o t he Gover nment .

3. 2. 1. 8 Ai r Di st r i but i on Devi ces ( Regi st er s, Gr i l l es and Di f f user s)

Cl ean al l ai r di st r i but i on devi ces.

3. 2. 1. 9 Ai r Handl i ng Uni t s, Ter mi nal Uni t s, Bl ower s and Exhaust Fans

Ensur e t hat suppl y, r et ur n, and exhaust f ans and bl ower s ar e t hor oughl y c l eaned. Ar eas f or c l eani ng i ncl ude bl ower s, f an housi ngs, pl enums ( except cei l i ng suppl y and r et ur n pl enums) , scr ol l s, bl ades, or vanes, shaf t s, baf f l es, damper s and dr i ve assembl i es. Remove al l v i s i bl e sur f ace cont ami nat i on deposi t s i n accor dance wi t h NADCA St andar ds.

a. Cl ean al l ai r handl i ng uni t ( AHU) i nt er nal sur f aces, component s and condensat e col l ect or s and dr ai ns.

b. Assur e t hat a sui t abl e oper at i ve dr ai nage syst em i s i n pl ace pr i or t o begi nni ng wash down pr ocedur es.

c. Cl ean al l coi l s and r el at ed component s, i ncl udi ng evapor at or f i ns.

3. 2. 1. 10 Duct Syst ems

a. Cr eat e ser vi ce openi ngs i n t he syst em as necessar y i n or der t o accommodat e c l eani ng of ot her wi se i naccessi bl e ar eas.

b. Mechani cal l y c l ean al l duct syst ems t o r emove al l v i s i bl e cont ami nant s, such t hat t he syst ems ar e capabl e of passi ng NADCA Cl eani ng Ver i f i cat i on Test i ngs St andar ds.

3. 2. 2 Mechani cal Cl eani ng Met hodol ogy

3. 2. 2. 1 Sour ce Removal Cl eani ng Met hods

Cl ean t he HVAC syst em usi ng Sour ce Removal mechani cal c l eani ng met hods desi gned t o ext r act cont ami nant s f r om wi t hi n t he HVAC syst em and saf el y r emove cont ami nant s f r om t he f aci l i t y . Sel ect Sour ce Removal met hods whi ch wi l l r ender t he HVAC Syst em Vi si bl y Cl ean and capabl e of passi ng NADCA cl eani ng ver i f i cat i on met hods St andar ds and ot her speci f i ed st andar ds and t est s, i n accor dance wi t h al l gener al r equi r ement s. Use no cl eani ng met hod, or combi nat i on of met hods, whi ch coul d pot ent i al l y damage component s of t he HVAC syst em or negat i vel y al t er t he i nt egr i t y of t he system.

I ncor por at e t he use of vacuum col l ect i on devi ces t hat ar e oper at ed cont i nuousl y dur i ng c l eani ng f or al l met hods used. Connect a vacuum devi ce t o t he downst r eam end of t he sect i on bei ng cl eaned t hr ough a pr edet er mi ned openi ng. Use a vacuum col l ect i on devi ce of suf f i c i ent power t o r ender al l ar eas bei ng cl eaned under negat i ve pr essur e, such t hat cont ai nment of debr i s and t he pr ot ect i on of t he i ndoor envi r onment i s assured.

Equi p al l vacuum devi ces exhaust i ng ai r i nsi de t he bui l di ng, i ncl udi ng hand- hel d vacuums and wet - vacuums, wi t h HEPA f i l t er s ( mi ni mum ef f i c i ency) .

Apr i l 2019 Page 7 SECTI ON 23 01 30. 41

Equi p al l vacuum devi ces exhaust i ng ai r out s i de t he f aci l i t y wi t h Par t i cul at e Col l ect i on i ncl udi ng adequat e f i l t r at i on t o cont ai n Debr i s r emoved f r om t he HVAC syst em, i n a manner t hat does not al l ow cont ami nant s t o r e- ent er t he f aci l i t y . Rel ease of debr i s out door s whi ch v i ol at es any out door envi r onment al st andar ds, codes or r egul at i ons i s not al l owed.

Al l met hods r equi r e mechani cal agi t at i on devi ces t o di s l odge debr i s adher ed t o i nt er i or HVAC syst em sur f aces, such t hat debr i s may be saf el y conveyed t o vacuum col l ect i on devi ces. Accept abl e met hods i ncl ude t hose whi ch wi l l not pot ent i al l y damage t he i nt egr i t y of t he duct wor k, nor damage por ous sur f ace mat er i al s such as l i ner s i nsi de t he duct wor k or syst em component s.

3. 2. 2. 2 Met hods of Cl eani ng Fi br ous Gl ass I nsul at ed Component s

Thor oughl y c l ean gl ass acoust i cal i nsul at i on el ement s pr esent i n any equi pment or duct wor k wi t h HEPA vacuumi ng equi pment . Cl ean whi l e t he HVAC syst em i s under const ant negat i ve pr essur e, and not per mi t t ed t o get wet i n accor dance wi t h appl i cabl e NADCA and NAI MA st andar ds and recommendations.

Do not use cl eani ng met hods t hat cause damage t o f i br ous gl ass component s or r ender s t he syst em capabl e of passi ng Cl eani ng Ver i f i cat i on Test s NADCA Standards.

3. 2. 2. 3 Damaged Fi br ous Gl ass Mat er i al

I f t her e i s any evi dence of damage, det er i or at i on, del ami nat i on, f r i abl e mat er i al , mol d or f ungus gr owt h, or moi st ur e such t hat f i br ous gl ass mat er i al s cannot be r est or ed by c l eani ng or r esur f aci ng wi t h an accept abl e i nsul at i on r epai r coat i ng, i dent i f y t hem t o t he Cont r act i ng Of f i cer f or replacement.

When r equest ed or speci f i ed, r emedi at e exposed damaged i nsul at i on i n ai r handl er s and/ or duct wor k r equi r i ng r epl acement .

3. 2. 2. 4 Repl acement Mat er i al

I f r epl acement of f i ber gl ass mat er i al s i s r equi r ed, conf or m al l mat er i al s t o appl i cabl e i ndust r y codes and st andar ds, i ncl udi ng t hose of UL and

SMACNA 1966.

Repl acement of damaged i nsul at i on i s not cover ed by t hi s speci f i cat i on.

3. 2. 2. 5 Cl eani ng of Coi l s

Use any cl eani ng met hod whi ch r ender s t he coi l v i s i bl y c l ean and capabl e of passi ng NADCA Coi l Cl eani ng Ver i f i cat i on St andar ds. Coi l dr ai n pans ar e subj ect t o Non- Por ous Sur f aces Cl eani ng Ver i f i cat i on. Mai nt ai n oper abi l i t y of t he dr ai n f or t he condensat e at al l t i mes. Do not damage, di spl ace, i nhi bi t heat t r ansf er , or cause er osi on of t he coi l sur f ace or f i ns, and conf or m t o coi l manuf act ur er r ecommendat i ons when avai l abl e.

Thor oughl y r i nse coi l s wi t h c l ean wat er t o r emove any l at ent r esi dues.

3. 2. 2. 6 Ant i mi cr obi al Agent s and Coat i ngs

Onl y appl y ant i mi cr obi al agent s i f act i ve f ungal gr owt h i s r easonabl y suspect ed, or wher e unaccept abl e l evel s of f ungal cont ami nat i on have been

Apr i l 2019 Page 8 SECTI ON 23 01 30. 41 ver i f i ed t hr ough t est i ng.

Per f or m appl i cat i on of any ant i mi cr obi al agent s used t o cont r ol t he gr owt h of f ungal or bact er i ol ogi cal cont ami nant s af t er t he r emoval of sur f ace deposi t s and debr i s.

Use onl y ant i mi cr obi al agent s r egi st er ed by t he U. S. Envi r onment al Pr ot ect i on Agency ( EPA 402- F- 91- 102)( EPA 402- C- 01- 001) speci f i cal l y f or use wi t hi n HVAC syst em.

Appl y ant i mi cr obi al agent s i n st r i ct accor dance wi t h manuf act ur er ' s instructions.

Use onl y ant i mi cr obi al coat i ng pr oduct s, f or bot h por ous and non- por ous sur f aces, whi ch ar e EPA r egi st er ed, wat er sol ubl e sol ut i ons wi t h suppor t i ng ef f i cacy dat a and MSDS r ecor ds.

Appl y ant i mi cr obi al coat i ngs accor di ng t o manuf act ur er ' s i nst r uct i ons.

Spr ay coat i ngs di r ect l y ont o i nt er i or duct wor k sur f aces, r at her t han " f og" downst r eam ont o sur f aces. Achi eve a cont i nuous f i l m on t he sur f ace t r eat ed by t he coat i ng appl i cat i on, and appl y i n st r i ct accor dance wi t h manuf act ur er ' s mi ni mum mi l l age sur f ace appl i cat i on r at e st andar ds f or effectiveness.

3. 3 FI ELD QUALI TY CONTROL

3. 3. 1 CLEANLI NESS VERI FI CATI ON

3. 3. 1. 1 General

Ver i f i cat i on of HVAC Syst em cl eanl i ness i s det er mi ned af t er mechani cal c l eani ng and bef or e t he appl i cat i on of any t r eat ment or i nt r oduct i on of any t r eat ment - r el at ed subst ance t o t he HVAC syst em, i ncl udi ng ant i mi cr obi al agent s and coat i ngs.

3. 3. 1. 2 Vi sual I nspect i on

Vi sual l y i nspect t he HVAC syst em t o ensur e t hat no vi s i bl e cont ami nant s ar e pr esent .

I f no cont ami nant s ar e evi dent t hr ough vi sual i nspect i on, consi der t he HVAC syst em cl ean; however , f ur t her ver i f i cat i on of t he syst em cl eanl i ness t hr ough gr avi met r i c or wi pe t est i ng anal ysi s t est i ng may be r equest ed at t he di scr et i on of t he Cont r act i ng Of f i cer .

I f v i s i bl e cont ami nant s ar e evi dent t hr ough vi sual i nspect i on, r e- c l ean t hose por t i ons of t he syst em wher e cont ami nant s ar e v i s i bl e, and subj ect t o r e- i nspect i on f or c l eanl i ness.

3. 3. 1. 3 Gr avi met r i c Anal ysi s

At t he expense of t he Contractor , t est sect i ons of t he HVAC syst em f or c l eanl i ness usi ng t he NADCA Vacuum Test ( gr avi met r i c anal ysi s) as speci f i ed i n appl i cabl e NADCA St andar ds. Ensur e l evel s of debr i s col l ect ed ar e equal t o or l ess t han accept abl e l evel s def i ned i n appl i cabl e NADCA St andar ds.

I f gr avi met r i c anal ysi s det er mi nes t hat l evel s of debr i s ar e equal t o or l ower t han t hose l evel s speci f i ed, t he syst em i s consi der ed cl ean and t o

Apr i l 2019 Page 9 SECTI ON 23 01 30. 41 have passed cl eanl i ness ver i f i cat i on.

I f gr avi met r i c anal ysi s det er mi nes t hat l evel s of debr i s exceed t hose speci f i ed i n appl i cabl e NADCA st andar ds, t he syst em wi l l not be consi der ed cl ean, and r e- cl eani ng of t hose sect i ons of t he syst em whi ch f ai l ed c l eanl i ness ver i f i cat i on wi l l be r equi r ed at t he expense of t he HVAC syst em cl eani ng cont r act or .

Per f or m cl eanl i ness ver i f i cat i on i mmedi at el y af t er mechani cal c l eani ng and bef or e t he HVAC syst em i s r est or ed t o nor mal oper at i on.

3. 3. 1. 4 Ver i f i cat i on of Coi l Cl eani ng

Cl eani ng i s t o r est or e t he coi l pr essur e dr op t o wi t hi n 10 per cent of t he pr essur e dr op measur ed when t he coi l was f i r st i nst al l ed. I f t he or i gi nal pr essur e dr op i s not known, t he coi l wi l l be consi der ed cl ean onl y i f t he coi l i s f r ee of f or ei gn mat t er and chemi cal r esi due, based on a t hor ough vi sual i nspect i on ( see NADCA HVAC I nspect i on Manual St andar ds) .

3. 3. 2 Post - Pr oj ect Repor t

At t he concl usi on of t he pr oj ect , pr ovi de a Test i ng Pr ocedur es Summar y and Post - Pr oj ect Repor t i ndi cat i ng t he f ol l owi ng:

a. Success of t he c l eani ng pr oj ect , as ver i f i ed t hr ough vi sual i nspect i on or gr avi met r i c anal ysi s.

b. Ar eas of t he syst em f ound t o be damaged and/ or i n need of r epai r .

- - End of Sect i on - -

Apr i l 2019 Page 10 SECTI ON 23 01 30. 41

File details come from the government source that posted it. Updated .