This is a technical specification document for gravity-type roof ventilators at Tinker Air Force Base, Oklahoma, issued in April 2019.

The specification establishes design and product requirements for three types of roof ventilators: ridge ventilators, stationary ventilators, and turbine ventilators. All ventilators must be designed for wind speeds of not less than 80 mph per ASCE 7, provide uniform continuous airflow, protect against rain and snow, and be self-cleaning with no internal obstructions or moving parts requiring maintenance. Materials must comply with referenced ASTM standards: aluminum extrusions must be alloy 6063 temper T5; aluminum sheets may be alloy 5005 temper H15 or alloy 3003 temper H14; and galvanized steel sheets must meet ASTM A653/A653M with minimum G90 coating thickness. Ridge ventilators require splice plates that telescope without fasteners and must include manually-operated single-leaf dampers or UL-labeled fire-actuated damper systems with urethane gaskets and insect/bird screens. Stationary ventilators must feature seamless spun conical weathercaps with straight-through drainage. Turbine ventilators require pre-lubricated ball-bearing action, 360-degree operating surfaces with rotor head anchoring, and damper options including manual pull-chain, push-button electric, or thermostat-controlled electric operation. All ventilators require factory finishing with rust-resistant primer and acrylic coats for galvanized steel or aluminum finishing to match the metal roof finish and color. Installation must coordinate with roofing work per SMACNA 1793 Chapter 8 and maintain watertight, vibration-free installations. Manufacturer must specialize in roof ventilator design and manufacture with minimum five years of documented experience.

View the file

Other files

File Type Posted
03 11 13.00 10.pdf PDF
03 20 00.00 10.pdf PDF
03 30 00.pdf PDF
07 14 00.pdf PDF
07 19 00.pdf PDF
07 21 16.pdf PDF
07 22 00.pdf PDF
07 31 13.pdf PDF
07 52 00.pdf PDF
08 34 01.pdf PDF
08 34 19.10 20.pdf PDF
08 52 00.pdf PDF
09 29 00.pdf PDF
10 21 13.pdf PDF
10 22 13.pdf PDF
13 34 19.pdf PDF
21 13 13.pdf PDF
23 03 00.pdf PDF
23 05 48.00 40.pdf PDF
23 07 00.pdf PDF
23 09 23.01.pdf PDF
23 34 23.00 40.pdf PDF
23 52 00.pdf PDF
23 65 00.pdf PDF
23 70 03.pdf PDF
26 00 00.00 20.pdf PDF
26 05 48.00 10.pdf PDF
26 29 23.pdf PDF
26 32 14.00 10.pdf PDF
31 23 15.pdf PDF
31 23 16.pdf PDF
32 01 13.pdf PDF
32 11 11.pdf PDF
32 11 29.pdf PDF
32 12 10.1.pdf PDF
32 12 10.2.pdf PDF
32 13 14.pdf PDF
32 13 73.pdf PDF
190023 Renovate Restrooms B117 RFIs_FINAL_COR_Signed.pdf PDF
TAFB_Tech_Reqs (Div 02-48).zip ZIP file
Model.zip ZIP file
000_TABLE OF CONTENTS.pdf PDF
01 32 16.00 20.pdf PDF
01 33 16.00 10.pdf PDF
01 42 00.pdf PDF
01 78 00.pdf PDF
Tinker General Requirements Specifications_Nov 2022_Change Log.pdf PDF
Initial Site Visit WWYK190023.pdf PDF
Att12_190023_Drawings_Final.pdf PDF
Section L - Instructions to Offerors.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 07 72 20

GRAVI TY- TYPE ROOF VENTI LATORS

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN SOCI ETY OF CI VI L ENGI NEERS ( ASCE)

ASCE 7 ( 2010; Er r at a 2011; Supp 1 2013) Mi ni mum Desi gn Loads f or Bui l di ngs and Ot her Structures

ASTM I NTERNATI ONAL ( ASTM)

ASTM A653/ A653M ( 2015; E 2016) St andar d Speci f i cat i on f or St eel Sheet , Zi nc- Coat ed ( Gal vani zed) or Zi nc- I r on Al l oy- Coat ed ( Gal vanneal ed) by t he Hot - Di p Pr ocess

ASTM B209 ( 2014) St andar d Speci f i cat i on f or Al umi num and Al umi num- Al l oy Sheet and Pl at e

ASTM B209M ( 2014) St andar d Speci f i cat i on f or Al umi num and Al umi num- Al l oy Sheet and Pl at e ( Met r i c)

ASTM B221 ( 2014) St andar d Speci f i cat i on f or Al umi num and Al umi num- Al l oy Ext r uded Bar s, Rods, Wi r e, Pr of i l es, and Tubes

ASTM B221M ( 2013) St andar d Speci f i cat i on f or Al umi num and Al umi num- Al l oy Ext r uded Bar s, Rods, Wi r e, Pr of i l es, and Tubes ( Met r i c)

SHEET METAL AND AI R CONDI TI ONI NG CONTRACTORS' NATI ONAL ASSOCI ATI ON

(SMACNA)

SMACNA 1793 ( 2012) Ar chi t ect ur al Sheet Met al Manual , 7t h Edi t i on

1. 2 DESI GN REQUI REMENTS

Desi gn vent i l at or s f or use wi t h t he speci f i c t ype of pr oj ect r oof i ng syst em, and t o pr ovi de uni f or m and cont i nuous ai r f l ow. Vent i l at or desi gn shal l pr ovi de pr ot ect i on agai nst r ai n and snow, and shal l be pr ovi ded wi t h a cont i nuous weep al ong t he bot t om of bot h s i des of wi nd band. Uni t s shal l be sel f - c l eani ng by t he act i on of t he el ement s, and shal l have pr ovi s i ons f or car r y i ng wat er and nor mal wi nd- t r anspor t ed soi l mat t er t o t he out si de. Desi gn uni t s f or wi ndspeeds of not l ess t han 80 mph i n accor dance wi t h ASCE 7. Vent i l at or s shal l be f r ee of i nt er nal obst r uct i ons or movi ng par t s whi ch wi l l r equi r e mai nt enance, and shal l be

Apr i l 2019 Page 1 SECTI ON 07 72 20 compl et e wi t h t ype of mount i ng i ndi cat ed on dr awi ngs.

1. 3 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00

SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

Roof Vent i l at or s; G

1. 4 QUALI TY ASSURANCE

Manuf act ur er shal l speci al i ze i n desi gn and manuf act ur e of t he t ype of r oof vent i l at or s speci f i ed i n t hi s sect i on, and shal l have a mi ni mum of 5 year s of document ed successf ul exper i ence. Pr ovi de a vent i l at or i nst al l er exper i enced i n t he i nst al l at i on of vent i l at or t ypes speci f i ed.

1. 5 DELI VERY, STORAGE, AND HANDLI NG

Roof vent i l at or s shal l be car t oned or cr at ed pr i or t o shi pment . Pr ot ect vent i l at or s f r om moi st ur e and damage. Remove damaged i t ems f r om t he si t e.

PART 2 PRODUCTS

2. 1 MATERIALS

2. 1. 1 Al umi num Ext r usi ons

Al umi num ext r usi ons shal l be al l oy 6063, t emper T5 i n compl i ance wi t h

ASTM B221.

2. 1. 2 Al umi num Sheet s

Al umi num sheet s shal l be al l oy 5005, t emper H15 or al l oy 3003, t emper H14 i n compl i ance wi t h ASTM B209.

2. 1. 3 Gal vani zed St eel Sheet s

St eel sheet s shal l be commer ci al qual i t y, z i nc- coat ed st eel ( hot - di p gal vani zed) of qual i t y est abl i shed by ASTM A653/ A653M, mi ni mum G90 coat i ng thickness.

2. 2 RI DGE VENTI LATORS

Pr ovi de r oof r i dge vent i l at or s f abr i cat ed of gal vani zed st eel or al umi num ( as i ndi cat ed) , and assembl ed t o any desi r ed l engt h. Cont i nuous- r un r i dge vent i l at or s shal l be connect ed wi t h spl i ce pl at es of t ype whi ch wi l l t el escope t oget her and not r equi r e f ast ener s, sol der i ng or wel di ng.

Pr ovi de vent i l at or s wi t h manual l y- oper at ed si ngl e- l eaf damper s compl et e wi t h accessor i es t o meet desi gn and per f or mance r equi r ement s; or a UL l abel ed f i r e- act uat ed damper syst em compl et e wi t h accessor i es t o meet bui l di ng code r equi r ement s. Damper s and ai r shaf t s shal l be compl et e wi t h ur et hane gasket i ng f or ext r a- t i ght encl osur es. Pr ovi de met al c l osur e st r i ps, whi ch mat ch t he panel r oof r i b cont our s, t o c l ose out weat her and pr ovi de a secur e seat f or vent i l at or s. I nsect or Bi r d scr eens shal l be provided.

Apr i l 2019 Page 2 SECTI ON 07 72 20

2. 3 STATI ONARY VENTI LATORS

Pr ovi de st at i onar y r oof vent i l at or s f abr i cat ed of gal vani zed st eel or al umi num wi t h seaml ess spun coni cal - shaped weat her cap, and havi ng st r ai ght - t hr ough dr ai nage f or el i mi nat i ng t he possi bi l i t y of ai r - bor ne debr i s col l ect i ng i n t he vent i l at or openi ngs. I nsect or Bi r d scr eens shal l be pr ovi ded.

2. 4 TURBI NE VENTI LATORS

Pr ovi de t ur bi ne vent i l at or s f abr i cat ed of gal vani zed st eel or al umi num, cor r ugat ed or f l at sheet s, compl et e wi t h sensi t i ve bal l - bear i ng act i on t o enabl e t he s l i ght est mot i on of ai r t o move t he r ot or head wher e suct i on i s mai nt ai ned at l ow wi nd vel oci t i es. Vent i l at or s shal l have 360 degr ee oper at i ng sur f ace t o assur e access of wi nd cur r ent s r egar dl ess of wi nd vel oci t i es. Rot or head shal l be anchor ed t o pr event head f r om l i f t i ng or j umpi ng of f t he r ot or i n hi gh wi nds. Rot or cr own pl at e shal l be seaml ess. Bi r d or I nsect scr eens shal l be pr ovi ded.

2. 4. 1 Dampers

Tur bi ne vent i l at or s shal l be pr ovi ded wi t h damper s manual l y- oper at ed wi t h di r ect pul l - chai n or r ack and pi ni on; push- but t on cont r ol el ect r i c gear mot or - oper at ed damper s; or t her most at cont r ol el ect r i c gear mot or - oper at ed damper s ( as i ndi cat ed i n dr awi ngs) .

2. 4. 2 Rot or Shaf t

Rot or shaf t bear i ngs shal l be ent i r el y shi el ded i n cor r osi on- r esi st ant al umi num casi ng. Bear i ngs shal l be pr e- l ubr i cat ed and shal l have l i f e- t i me war r ant y. Bear i ngs shal l be at t op and bot t om t o assur e accur at e al i gnment . Shaf t and bear i ngs shal l be easi l y r epl aceabl e as a uni t . Rot or col l ar shal l be r ol l ed and wel ded.

2. 5 FABRICATION

Vent i l at or s shal l be f abr i cat ed i n accor dance wi t h appr oved shop dr awi ngs. Wel ds, sol der ed seams, r i vet s and f ast ener s shal l be c l ean, secur e, wat er t i ght , and smoot h. Edges shal l be wi r ed or beaded, wher e necessar y, t o ensur e r i gi di t y. Joi nt s bet ween sect i ons shal l be wat er t i ght and shal l al l ow f or expansi on and cont r act i on. Gal vani c act i on bet ween di f f er ent met al s i n di r ect cont act shal l be pr event ed by nonconduct i ve separ at or s.

2. 6 CURB BASES

Vent i l at or bases f or cur b- mount ed i nst al l at i ons shal l be of s i ze i ndi cat ed on dr awi ngs, and shal l be desi gned speci f i cal l y f or t he t ype of vent i l at or and r oof i ng syst em appr oved f or t hi s pr oj ect . Cur b bases shal l be f act or y- f or med and f l ashed f or a wat er t i ght i nst al l at i on. Cur b bases shal l be f abr i cat ed of mat er i al and f i ni sh t o mat ch t he vent i l at or .

2. 7 SCREENS

Scr eens shal l be f ur ni shed by vent i l at or manuf act ur er as par t of vent i l at or assembl y. Scr een ( wi t h f r ames) shal l be manuf act ur ed of mat er i al t o mat ch vent i l at or s, and shal l be desi gned t o be easi l y r emoved f or c l eani ng pur poses.

Apr i l 2019 Page 3 SECTI ON 07 72 20

2. 8 FINISH

2. 8. 1 Gal vani zed St eel Fi ni sh

Gal vani zed st eel r oof vent i l at or s shal l be f act or y- coat ed wi t h r ust - r esi st ant pr i mer and baked- on f i ni sh coat s of acr yl i c .

2. 8. 2 Al umi num Fi ni sh

Al umi num r oof vent i l at or s shal l be f act or y- f i ni shed t o mat ch met al r oof f i ni sh and col or .

2. 8. 3 Color

Col or shal l be i n accor dance wi t h Sect i on 09 06 00 SCHEDULES FOR FI NI SHES .

PART 3 EXECUTI ON

3. 1 PREPARATION

Pr epar e r ough openi ngs and ot her r oof condi t i ons i n accor dance wi t h appr oved shop dr awi ngs and manuf act ur er ' s r ecommendat i ons. Rough openi ngs shal l be f i el d- measur ed and r ecor ded on shop dr awi ngs pr i or t o f abr i cat i on of r oof vent i l at or s. Bef or e st ar t i ng t he vent i l at or wor k, pr ot ect sur r oundi ng r oof sur f aces f r om damage. Coor di nat e f abr i cat i on wi t h const r uct i on schedul e. Submi t di mensi oned dr awi ngs i ndi cat i ng l ocat i on of each t ype of vent i l at or i ncl udi ng det ai l s of const r uct i on, gauges of met al , and met hods of oper at i on of damper s and cont r ol s.

3. 2 INSTALLATION

Coor di nat e r oof vent i l at or i nst al l at i on wi t h r oof i ng wor k, and i n accor dance wi t h appr oved shop dr awi ngs, manuf act ur er ' s publ i shed i nst r uct i ons, and chapt er 8 of SMACNA 1793. The vent i l at or i nst al l at i on shal l be wat er t i ght and f r ee of v i br at i on noi se. Pr ot ect al umi num sur f aces f r om di r ect cont act wi t h i ncompat i bl e mat er i al s. Al umi num sur f aces whi ch wi l l be i n cont act wi t h seal ant shal l not be coat ed wi t h a pr ot ect i ve mat er i al . Al umi num shal l not be used wi t h copper or wi t h wat er whi ch f l ows over copper sur f aces. Cl ean r oof vent i l at or s i n accor dance wi t h vent i l at or manuf act ur er ' s r ecommendat i ons.

3. 3 PROTECTION

Pr ot ect exposed vent i l at or f i ni sh sur f aces agai nst t he accumul at i on of pai nt , gr i me, mast i c, di sf i gur ement , di scol or at i on and damage f or dur at i on of const r uct i on act i v i t i es.

- - End of Sect i on - -