07 53 23.pdf

PDF 79 KB Posted

Attached to
TINKER AFB MAC BOA WWYK190023 Renovate Restrooms B117
Solicitation number
FA813726R0030
Issued by

About this file

This is a technical specification document for ethylene-propylene-diene-monomer (EPDM) roofing systems at Tinker Air Force Base, Oklahoma, issued in April 2019.

The specification establishes requirements for a fully adhered EPDM roof membrane system applied over insulation, recovery board, and substrate. Key material specifications include ASTM D4637/D4637M Type III EPDM sheet at 0.090 inch nominal thickness with fabric or fleece backing for fully adhered applications, complemented by seam tape, bonding adhesive, lap splice adhesive, and low-VOC products. Membrane flashing must be minimum 0.045 inch cured EPDM or 0.055 inch uncured EPDM per ASTM D4811/D4811M, with cured material preferred. Pre-manufactured accessories include 18-gauge G90 galvanized curbs (minimum 4-inch flange, 10-inch height), preformed rubber walkboards, and corrosion-resistant fasteners with stress plates. The roof system must achieve Class A fire rating per ASTM E108, FM 4470, or UL 790, and wind uplift resistance per FM testing procedures based on 90 mph design wind speed per ASCE 7. The EPDM sheet manufacturer must have minimum five years' experience, and the applicator must be approved/authorized/licensed by the manufacturer with minimum three years' experience. A 30-year no-dollar-limit roof system warranty from the manufacturer and a two-year installer warranty are required. Shop drawings must include wind load calculations, enhanced perimeter boundaries, fastener spacing, and drain locations. Manufacturer technical representatives must conduct minimum three site inspections during installation. All roofing installation must immediately follow insulation application on the same day and be watertight, with post-completion roof drain testing required for eight hours at drain sumps to verify watertightness.

View the file

Other files

File Type Posted
000_TABLE OF CONTENTS Technical.pdf PDF
05 05 23.16.pdf PDF
05 12 00.pdf PDF
05 30 00.pdf PDF
05 40 00.pdf PDF
05 50 13.pdf PDF
06 41 16.00 10.pdf PDF
07 24 00.pdf PDF
07 41 13.pdf PDF
07 51 13.pdf PDF
08 11 13.pdf PDF
08 14 00.pdf PDF
08 33 23.pdf PDF
08 56 53.pdf PDF
08 81 00.pdf PDF
09 22 00.pdf PDF
09 30 10.pdf PDF
09 72 00.pdf PDF
09 90 00.pdf PDF
10 14 00.10.pdf PDF
10 22 39.pdf PDF
10 26 00.pdf PDF
10 44 16.pdf PDF
23 05 15.pdf PDF
23 08 01.00 20.pdf PDF
23 23 00.pdf PDF
23 25 00.pdf PDF
23 31 13.00 40.pdf PDF
23 64 10.pdf PDF
23 81 23.pdf PDF
23 82 01.pdf PDF
26 05 00.00 40.pdf PDF
26 08 00.pdf PDF
26 20 00.pdf PDF
26 23 00.pdf PDF
26 28 01.00 10.pdf PDF
26 36 00.00 10.pdf PDF
26 41 00.pdf PDF
28 31 00.00 10.pdf PDF
28 31 64.00 10.pdf PDF
32 01 16.pdf PDF
32 01 17.62.pdf PDF
32 01 19.pdf PDF
00 70 00.pdf PDF
00 80 05.pdf PDF
01 33 00.pdf PDF
01 45 00.00 10.pdf PDF
01 50 00.pdf PDF
WWYK20190023_REV02_19MAY2026.pdf PDF
Section M - Evaluation Factors for Award.pdf PDF
Show 40 more

50 files listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Ti nker AFB, OK TAFB Techni cal Spr ci f i cat i ons 2019

SECTI ON 07 53 23

ETHYLENE- PROPYLENE- DI ENE- MONOMER ROOFI NG

PART 1 GENERAL

1. 1 REFERENCES

The publ i cat i ons l i s t ed bel ow f or m a par t of t hi s speci f i cat i on t o t he ext ent r ef er enced. The publ i cat i ons ar e r ef er r ed t o wi t hi n t he t ext by t he basi c desi gnat i on onl y.

AMERI CAN SOCI ETY OF CI VI L ENGI NEERS ( ASCE)

ASCE 7 ( 2010; Er r at a 2011; Supp 1 2013) Mi ni mum Desi gn Loads f or Bui l di ngs and Ot her Structures

ASTM I NTERNATI ONAL ( ASTM)

ASTM D448 ( 2012) Si zes of Aggr egat e f or Road and Br i dge Const r uct i on

ASTM D4637/ D4637M ( 2015) EPDM Sheet Used i n Si ngl e- Pl y Roof Membrane

ASTM D4811/ D4811M ( 2006; E 2013; R 2013) Nonvul cani zed ( Uncur ed) Rubber Sheet Used as Roof Flashing

ASTM D6369 ( 1999; R 2006) Desi gn of St andar d Fl ashi ng Det ai l s f or EPDM Roof Membr anes

ASTM E108 ( 2011) Fi r e Test s of Roof Cover i ngs

FM GLOBAL ( FM)

FM 4470 ( 2010) Si ngl e- Pl y, Pol ymer - Modi f i ed Bi t umen Sheet , Bui l t - up Roof ( BUR) , and Li qui d Appl i ed Roof Assembl i es f or Use i n Cl ass 1 and Noncombust i bl e Roof Deck Construction

FM APP GUI DE ( updat ed on- l i ne) Appr oval Gui de http://www.approvalguide.com/

NATI ONAL ROOFI NG CONTRACTORS ASSOCI ATI ON ( NRCA)

NRCA Roof Man ( 2011 t hr u 2014) The NRCA Roof i ng Manual

SI NGLE PLY ROOFI NG I NDUSTRY ( SPRI )

ANSI / SPRI RD- 1 ( 2009) Per f or mance St andar d f or Ret r of i t Drains

Apr i l 2019 Page 1 SECTI ON 07 53 23

UNDERWRI TERS LABORATORI ES ( UL)

UL 790 ( 2004; Repr i nt Jul 2014) St andar d Test Met hods f or Fi r e Test s of Roof Cover i ngs

UL RMSD ( 2012) Roof i ng Mat er i al s and Syst ems Directory

1. 2 DESCRI PTI ON OF ROOF MEMBRANE SYSTEM

Ful l y adher ed EPDM r oof membr ane syst em appl i ed over i nsul at i on, r ecover y boardandsubstrate.

1. 3 SUBMITTALS

Gover nment appr oval i s r equi r ed f or submi t t al s wi t h a " G" desi gnat i on;

submi t t al s not havi ng a " G" desi gnat i on ar e f or Cont r act or Qual i t y Cont r ol appr oval . Submi t t he f ol l owi ng i n accor dance wi t h Sect i on 01 33 00

SUBMI TTAL PROCEDURES:

SD- 02 Shop Dr awi ngs

Roof Pl an Dr awi ng

Wi nd Load Cal cul at i ons

Boundar i es of Enhanced Per i met er

Cor ner At t achment s of Roof Syst em Component s

Locat i on of Per i met er Hal f - Sheet s

Spaci ng of Per i met er , Cor ner , and I nf i el d Fast ener s

Sl opes and Dr ai n Locat i ons

SD- 03 Pr oduct Dat a

Cement

EPDM Sheet ; G

Seam Tape

Bondi ng Adhesi ve

Lap Spl i ce Adhesi ve

Wat er Cut of f Mast i c/ Wat er Bl ock

Lap Cl eaner , Lap Seal ant , and Edge Tr eat ment

Flashings

Fl ashi ng Accessor i es

Fl ashi ng Tape

Fast ener s and Pl at es

Apr i l 2019 Page 2 SECTI ON 07 53 23

Roof I nsul at i on

Wal k Pads

Pr e- Manuf act ur ed Accessor i es

Sampl e war r ant y/ Assembl y l et t er ; G

Submi t al l dat a r equi r ed t oget her wi t h r equi r ement s of t hi s sect i on. I ncl ude a wr i t t en accept ance by t he r oof membr ane manuf act ur er of t he i nsul at i on and ot her pr oduct s and accessor i es t o be pr ovi ded. Li st pr oduct s i n t he appl i cabl e wi nd upl i f t and f i r e r at i ng c l assi f i cat i on l i s t i ngs, unl ess appr oved ot her wi se by t he Cont r act i ng Of f i cer .

SD- 05 Desi gn Dat a

Wi nd Upl i f t Cal cul at i ons; G

Engi neer i ng cal cul at i ons val i dat i ng t he wi nd r esi st ance of r oof system.

SD- 07 Cer t i f i cat es

Qual i f i cat i on of Manuf act ur er

Cer t i f y t hat t he manuf act ur er of t he r oof membr ane meet s r equi r ement s speci f i ed under par agr aph ent i t l ed " Qual i f i cat i on of Manufacturer."

Qual i f i cat i on of Appl i cat or

Cer t i f y t hat t he appl i cat or meet s r equi r ement s speci f i ed under par agr aph ent i t l ed " Qual i f i cat i on of Appl i cat or . "

Wi nd Upl i f t Resi st ance cl assi f i cat i on, as appl i cabl e; G

Fi r e Resi st ance cl assi f i cat i on; G

Submi t t he r oof syst em assembl y wi nd upl i f t and f i r e r at i ng c l assi f i cat i on l i s t i ngs.

SD- 08 Manuf act ur er ' s I nst r uct i ons

Appl i cat i on; G

Appl i cat i on Met hod; G, i ncl udi ng pat t er n and f r equency of mechani cal at t achment s r equi r ed i n t he f i el d of r oof , cor ner s, and per i met er s t o pr ovi de f or t he speci f i ed wi nd r esi st ance

Membr ane Fl ashi ng; G

Seam Tape

Tape Seams / Lap Spl i ces

Apr i l 2019 Page 3 SECTI ON 07 53 23

Adhesi ve Seams / Lap Spl i ces

Per i met er At t achment

Primer

Fasteners

Wal k Pads

Pr e- Manuf act ur ed Accessor i es

Col d Weat her I nst al l at i on; G

I ncl ude det ai l ed appl i cat i on i nst r uct i ons and st andar d manuf act ur er dr awi ngs al t er ed as r equi r ed by t hese speci f i cat i ons.

Expl i c i t l y i dent i f y i n wr i t i ng, di f f er ences bet ween manuf act ur er ' s pr i nt ed i nst r uct i ons and t he speci f i ed r equi r ement s.

SD- 11 Cl oseout Submi t t al s

Warranty

I nf or mat i on Car d

I nst r uct i ons To Gover nment Per sonnel

I ncl ude copi es of Mat er i al Saf et y Dat a Sheet s f or mai nt enance/ r epai r mat er i al s.

1. 3. 1 Shop Dr awi ngs

Roof pl an dr awi ng depi ct i ng wi nd l oad cal cul at i ons and boundar i es of enhanced per i met er and cor ner at t achment s of r oof syst em component s, , spaci ng of per i met er , cor ner , and i nf i el d f ast ener s, as appl i cabl e. The dr awi ng must r ef l ect t he pr oj ect r oof pl an of each r oof l evel and condi t i ons i ndi cat ed. Pr ovi de al l s l opes and dr ai n l ocat i ons.

1. 4 QUALI TY ASSURANCE

1. 4. 1 Qual i f i cat i on of Manuf act ur er

EPDM sheet r oof i ng membr ane manuf act ur er must have at l east 5 year s exper i ence i n manuf act ur i ng EPDM r oof i ng pr oduct s.

1. 4. 2 Qual i f i cat i on of Appl i cat or

Roof i ng syst em appl i cat or must be appr oved, aut hor i zed, or l i censed i n wr i t i ng by t he r oof membr ane manuf act ur er and must have a mi ni mum of t hr ee year s exper i ence as an appr oved, aut hor i zed, or l i censed appl i cat or wi t h t hat manuf act ur er and be appr oved at a l evel capabl e of pr ovi di ng t he speci f i ed war r ant y. The appl i cat or must suppl y t he names, l ocat i ons and cl i ent cont act i nf or mat i on of 5 pr oj ect s of s i mi l ar s i ze and scope t hat t he appl i cat or has const r uct ed usi ng t he manuf act ur er ' s r oof i ng pr oduct s submi t t ed f or t hi s pr oj ect wi t hi n t he pr evi ous t hr ee year s.

1. 4. 3 Qual i f i cat i ons of Phot ovol t ai cs ( PV) Roof t op Appl i cat or

The PV r oof t op appl i cat or must be appr oved, aut hor i zed, or cer t i f i ed by a

Apr i l 2019 Page 4 SECTI ON 07 53 23

Roof I nt egr at ed Sol ar Ener gy ( RI SE) Cer t i f i ed Sol ar Roof i ng Pr of essi onal ( CSRP) , and compl y wi t h appl i cabl e codes, st andar ds, and r egul at or y r equi r ement s t o mai nt ai n t he weat her pr oof i ng abi l i t i es of bot h t he i nt egr at ed r oof syst em and phot ovol t ai c syst em.

1. 4. 4 Fi r e Resi st ance

Compl et e r oof cover i ng assembl y must :

a. Be Cl ass A r at ed i n accor dance wi t h ASTM E108, FM 4470, or UL 790; and

b. Be l i s t ed as par t of Fi r e- Cl assi f i ed r oof deck const r uct i on i n t he UL RMSD or Cl ass I r oof deck const r uct i on i n t he FM APP GUI DE.

FM or UL appr oved component s of t he r oof cover i ng assembl y must bear t he appr opr i at e FM or UL l abel .

1. 4. 5 Wi nd Upl i f t Resi st ance

The compl et e r oof syst em assembl y shal l be r at ed and i nst al l ed t o r esi st wi nd l oads cal cul at ed i n accor dance wi t h ASCE 7 and val i dat ed by upl i f t r esi st ance t est i ng i n accor dance wi t h Fact or y Mut ual ( FM) t est pr ocedur es. Do not i nst al l non- r at ed syst ems except as appr oved by t he Cont r act i ng Of f i cer . Submi t l i censed engi neer ' s wi nd upl i f t cal cul at i ons and subst ant i at i ng dat a t o val i dat e any non- r at ed r oof syst em. Base wi nd upl i f t measur ement s based on a desi gn wi nd speed of 90 mph i n accor dance with ASCE 7 and/ or ot her appl i cabl e bui l di ng code r equi r ement s

1. 4. 6 Pr er oof i ng Conf er ence

Af t er appr oval of submi t t al s and bef or e per f or mi ng r oof i ng and i nsul at i on syst em i nst al l at i on wor k, hol d a pr er oof i ng conf er ence t o r evi ew t he following:

a. Dr awi ngs, speci f i cat i ons and submi t t al s r el at ed t o t he r oof wor k;

b. Roof syst em component s i nst al l at i on;

c. Pr ocedur e f or t he r oof manuf act ur er ' s t echni cal r epr esent at i ve' s onsi t e i nspect i on and accept ance of t he r oof i ng subst r at e, t he name of t he manuf act ur er ' s t echni cal r epr esent at i ves, t he f r equency of t he onsi t e v i s i t s, di st r i but i on of copi es of t he i nspect i on r epor t s f r om t he manuf act ur er ' s t echni cal r epr esent at i ve;

d. Cont r act or ' s pl an f or coor di nat i on of t he wor k of t he var i ous t r ades i nvol ved i n pr ovi di ng t he r oof i ng syst em and ot her component s secur ed t o t he r oof i ng; and

e. Qual i t y cont r ol pl an f or t he r oof syst em i nst al l at i on;

f . Saf et y r equi r ement s.

Coor di nat e pr er oof i ng conf er ence schedul i ng wi t h t he Cont r act i ng Of f i cer .

The conf er ence must be at t ended by t he Cont r act or , t he Cont r act i ng Of f i cer ' s desi gnat ed per sonnel , per sonnel di r ect l y r esponsi bl e f or t he i nst al l at i on of r oof i ng and i nsul at i on, f l ashi ng and sheet met al wor k, mechani cal and el ect r i cal wor k, ot her t r ades i nt er f aci ng wi t h t he r oof wor k, and r epr esent at i ve of t he r oof i ng mat er i al s manuf act ur er . Bef or e begi nni ng r oof i ng wor k, pr ovi de a copy of meet i ng not es and act i on i t ems

Apr i l 2019 Page 5 SECTI ON 07 53 23 t o al l at t endi ng par t i es. Not e act i on i t ems r equi r i ng r esol ut i on pr i or t o st ar t of r oof wor k.

1. 5 DELI VERY, STORAGE, AND HANDLI NG

1. 5. 1 Delivery

Del i ver mat er i al s i n t hei r or i gi nal , unopened cont ai ner s or wr appi ngs wi t h l abel s i nt act and l egi bl e. Wher e mat er i al s ar e cover ed by a r ef er enced speci f i cat i on number , t he l abel s must bear t he speci f i cat i on number , t ype, c l ass, and shel f l i f e expi r at i on dat e wher e appl i cabl e. Del i ver mat er i al s i n suf f i c i ent quant i t y t o al l ow cont i nui t y of wor k.

1. 5. 2 Storage

St or e and pr ot ect mat er i al s f r om damage and weat her i n accor dance wi t h manuf act ur er ' s pr i nt ed i nst r uct i ons, except as speci f i ed ot her wi se. Keep mat er i al s c l ean and dr y. St or e and mai nt ai n adhesi ves, seal ant s, pr i mer s and ot her l i qui d mat er i al s above 60 degr ees F. I nsul at ed hot boxes or ot her encl osed war mi ng devi ces must be r equi r ed i n col d weat her . Mar k and r emove damaged mat er i al s f r om t he si t e. Use pal l et s t o suppor t and canvas t ar paul i ns t o compl et el y cover mat er i al mat er i al s st or ed out door s. Do not use pol yet hyl ene as a cover i ng. Locat e mat er i al s t empor ar i l y st or ed on t he r oof i n appr oved ar eas, and di st r i but e t he l oad t o st ay wi t hi n t he l i ve l oad l i mi t s of t he r oof const r uct i on. Remove unused mat er i al s f r om t he r oof at t he end of each days wor k.

1. 5. 3 Handling

Pr event damage t o edges and ends of r ol l mat er i al s. Do not i nst al l damaged mat er i al s i n t he wor k. Sel ect and oper at e mat er i al handl i ng equi pment so as not t o damage mat er i al s or appl i ed r oof i ng. Do not use mat er i al s cont ami nat ed by exposur e or moi st ur e. Remove cont ami nat ed mat er i al s f r om t he si t e. When hazar dous mat er i al s ar e i nvol ved, adher e t o t he speci al pr ecaut i ons of t he manuf act ur er . Adhesi ves may cont ai n pet r ol eum di st i l l at es and may be ext r emel y f l ammabl e; pr event per sonnel f r om br eat hi ng vapor s, and do not use near spar ks or open f l ame.

1. 6 ENVI RONMENTAL REQUI REMENTS

Do not i nst al l EPDM sheet r oof i ng dur i ng hi gh wi nds or i ncl ement weat her , or when t her e i s i ce, f r ost , moi st ur e, or v i s i bl e dampness on t he subst r at e sur f ace, or when condensat i on devel ops on sur f aces dur i ng appl i cat i on. Unl ess r ecommended ot her wi se by t he EPDM sheet manuf act ur er and appr oved by t he Cont r act i ng Of f i cer , do not i nst al l EPDM sheet when ai r t emper at ur e i s bel ow 40 degr ees F or wi t hi n 5 degr ees F of t he dewpoi nt . Fol l ow manuf act ur er ' s pr i nt ed i nst r uct i ons f or i nst al l at i on dur i ng col d weat her condi t i ons.

1. 7 SEQUENCING

Coor di nat e t he wor k wi t h ot her t r ades t o ensur e t hat component s whi ch ar e t o be secur ed t o or st r i pped i nt o t he r oof i ng syst em ar e avai l abl e and t hat per manent f l ashi ng and count er f l ashi ng ar e i nst al l ed as t he wor k pr ogr esses. Ensur e t empor ar y pr ot ect i on measur es ar e i n pl ace t o pr ecl ude moi st ur e i nt r usi on or damage t o i nst al l ed mat er i al s. Appl i cat i on of r oof i ng must i mmedi at el y f ol l ow appl i cat i on of i nsul at i on as a cont i nuous oper at i on. Coor di nat e r oof i ng oper at i ons wi t h i nsul at i on wor k so t hat al l r oof i nsul at i on appl i ed each day i s cover ed wi t h r oof membr ane

Apr i l 2019 Page 6 SECTI ON 07 53 23 i nst al l at i on t he same day and i s wat er t i ght .

1. 8 WARRANTY

Pr ovi de r oof syst em mat er i al and wor kmanshi p war r ant i es meet i ng speci f i ed r equi r ement s. Pr ovi de r evi s i on or amendment t o st andar d membr ane manuf act ur er war r ant y as r equi r ed t o compl y wi t h t he speci f i ed r equi r ement s. Mi ni mum manuf act ur er war r ant y shal l have no dol l ar l i mi t , cover f ul l syst em wat er - t i ght ness, and shal l have a mi ni mum dur at i on of 20 years.

1. 8. 1 Roof Membr ane Manuf act ur er War r ant y

Fur ni sh t he r oof membr ane manuf act ur er ' s 30 year no dol l ar l i mi t r oof syst em mat er i al s and i nst al l at i on wor kmanshi p war r ant y, i ncl udi ng f l ashi ng, i nsul at i on, and accessor i es necessar y f or a wat er t i ght r oof syst em const r uct i on. The war r ant y must r un di r ect l y t o t he Gover nment and commence at t i me of Gover nment ' s accept ance of t he r oof wor k. The war r ant y must st at e t hat :

a. I f wi t hi n t he war r ant y per i od t he r oof syst em, as i nst al l ed f or i t s i nt ended use i n t he nor mal c l i mat i c and envi r onment al condi t i ons of t he f aci l i t y , becomes non- wat er t i ght , shows evi dence of moi st ur e i nt r usi on wi t hi n t he assembl y, spl i t s, t ear s, cr acks, del ami nat es, separ at es at t he seams, shr i nks t o t he poi nt of br i dgi ng or t ent i ng membr ane at t r ansi t i ons, or shows evi dence of excessi ve weat her i ng due t o def ect i ve mat er i al s or i nst al l at i on wor kmanshi p, t he r epai r or r epl acement of t he def ect i ve and damaged mat er i al s of t he r oof syst em assembl y and cor r ect i on of def ect i ve wor kmanshi p must be t he r esponsi bi l i t y of t he r oof membr ane manuf act ur er . The r oof membr ane manuf act ur er i s r esponsi bl e f or al l cost s associ at ed wi t h t he r epai r or r epl acement wor k.

b. When t he manuf act ur er or hi s appr oved appl i cat or f ai l t o per f or m t he r epai r s wi t hi n 72 hour s of not i f i cat i on, emer gency t empor ar y r epai r s per f or med by ot her s does not voi d t he war r ant y.

1. 8. 2 Roof i ng Syst em I nst al l er War r ant y

The r oof syst em i nst al l er must war r ant f or a per i od of t wo year s t hat t he r oof syst em, as i nst al l ed, i s f r ee f r om def ect s i n i nst al l at i on wor kmanshi p, t o i ncl ude t he r oof membr ane, f l ashi ng, i nsul at i on, accessor i es, at t achment s, and sheet met al i nst al l at i on i nt egr al t o a compl et e wat er t i ght r oof syst em assembl y. Wr i t e t he war r ant y di r ect l y t o t he Gover nment . The r oof syst em i nst al l er i s r esponsi bl e f or cor r ect i on of def ect i ve wor kmanshi p and r epl acement of damaged or af f ect ed mat er i al s. The r oof syst em i nst al l er i s r esponsi bl e f or al l cost s associ at ed wi t h t he r epai r or r epl acement wor k.

1. 8. 3 Cont i nuance of War r ant y

Appr ove r epai r or r epl acement wor k t hat becomes necessar y wi t hi n t he war r ant y per i od and accompl i sh i n a manner so as t o r est or e t he i nt egr i t y of t he r oof syst em assembl y and val i di t y of t he r oof membr ane manuf act ur er war r ant y f or t he r emai nder of t he manuf act ur er war r ant y per i od.

1. 9 CONFORMANCE AND COMPATI BI LI TY

The ent i r e r oof i ng and f l ashi ng syst em must be i n accor dance wi t h

Apr i l 2019 Page 7 SECTI ON 07 53 23 speci f i ed and i ndi cat ed r equi r ement s, i ncl udi ng f i r e and wi nd r esi st ance r equi r ement s. Wor k not speci f i cal l y addr essed and any devi at i on f r om speci f i ed r equi r ement s must be i n gener al accor dance wi t h r ecommendat i ons of t he NRCA Roof Man, membr ane manuf act ur er publ i shed r ecommendat i ons and details, ASTM D6369, and compat i bl e wi t h sur r oundi ng component s and const r uct i on. Submi t any devi at i on f r om speci f i ed or i ndi cat ed r equi r ement s t o t he Cont r act i ng Of f i cer f or appr oval pr i or t o i nst al l at i on.

PART 2 PRODUCTS

2. 1 MATERIALS

Coor di nat e wi t h ot her speci f i cat i on sect i ons r el at ed t o t he r oof wor k.

Fur ni sh a combi nat i on of speci f i ed mat er i al s t hat compr i se a r oof syst em accept abl e t o t he r oof membr ane manuf act ur er and meet i ng speci f i ed r equi r ement s. Pr ot ect mat er i al s pr ovi ded f r om def ect s and make sui t abl e f or t he ser vi ce and cl i mat i c condi t i ons of t he i nst al l at i on.

2. 1. 1 EPDM Sheet

Et hyl ene Pr opyl ene Di ene Ter pol ymer ( EPDM) , ASTM D4637/ D4637M, Type I I I , f abr i c or f l eece back, 0. 090 i nch nomi nal t hi ckness f or f ul l y adher ed appl i cat i on. The mi ni mum t hi ckness must not be l ess t han mi nus 10 per cent of t he speci f i ed t hi ckness val ue. EPDM membr ane t hi ckness speci f i ed i s excl usi ve of backi ng mat er i al on t he EPDM membr ane. Pr i nci pal pol ymer used i n manuf act ur e of t he membr ane sheet must be gr eat er t han 95 per cent EPDM. Wi dt h and l engt h of sheet must be as r ecommended by t he manuf act ur er .

2. 1. 2 Seam Tape

Seam t ape as r equi r ed by t he manuf act ur er t o achi eve t he speci f i ed warranty.

2. 1. 3 Lap Spl i ce Adhesi ve

Low vol at i l e or gani c compound ( VOC) synt het i c r ubber adhesi ve as suppl i ed by r oof membr ane manuf act ur er and r ecommended by t he manuf act ur er ' s pr i nt ed dat a f or f or mi ng wat er t i ght bond of EPDM sheet membr ane mat er i al s t o each ot her .

2. 1. 4 Bondi ng Adhesi ve

Low vol at i l e or gani c compound ( VOC) adhesi ve as suppl i ed by r oof membr ane manuf act ur er and r ecommended by t he manuf act ur er ' s pr i nt ed dat a f or bondi ng EPDM membr ane mat er i al s t o i nsul at i on, wood, met al , concr et e or ot her subst r at e mat er i al s. Do not use bondi ng adhesi ve t o bond membr ane mat er i al s t o each ot her .

2. 1. 5 Lap Cl eaner , Lap Seal ant , and Edge Tr eat ment

As suppl i ed by t he r oof membr ane manuf act ur er and r ecommended by t he manuf act ur er ' s pr i nt ed dat a.

2. 1. 6 Wat er Cut of f Mast i c/ Wat er Bl ock

As suppl i ed by t he r oof membr ane manuf act ur er and r ecommended by t he manuf act ur er ' s pr i nt ed dat a.

Apr i l 2019 Page 8 SECTI ON 07 53 23

2. 1. 7 Membr ane Fl ashi ngs and Fl ashi ng Accessor i es

Membr ane f l ashi ng, i ncl udi ng sel f - adher i ng membr ane f l ashi ng, per i met er f l ashi ng, f l ashi ng ar ound r oof penet r at i ons, and pr ef abr i cat ed pi pe seal s, must be mi ni mum 0. 045 i nch mi ni mum cur ed EPDM, as r ecommended by t he r oof membr ane manuf act ur er or mi ni mum 0. 055 i nch t hi ck uncur ed EPDM sheet i n compl i ance wi t h ASTM D4811/ D4811M, Type I . Use cur ed EPDM membr ane t o t he maxi mum ext ent r ecommended by t he r oof membr ane manuf act ur er . Li mi t uncur ed f l ashi ng mat er i al t o r ei nf or ci ng i nsi de and out si de cor ner s and angl e changes i n pl ane of membr ane, and t o f l ash scupper s, pour abl e seal er pocket s, and ot her f or med penet r at i ons or unusual l y shaped condi t i ons as r ecommended by t he r oof membr ane manuf act ur er wher e t he use of cur ed mat er i al i s i mpr act i cal .

2. 1. 7. 1 Fl ashi ng Tape

EPDM- backed synt het i c r ubber t ape, mi ni mum 6 i nch wi de and 12 i nch as suppl i ed by t he r oof membr ane manuf act ur er and r ecommended by t he manuf act ur er ' s pr i nt ed dat a.

2. 1. 8 Membr ane Fast ener s and Pl at es

Coat ed, cor r osi on- r esi st ant f ast ener s as r ecommended by t he r oof membr ane manuf act ur er and meet i ng t he r equi r ement s of FM 4470 and FM APP GUI DE f or Cl ass I r oof deck const r uct i on and t he wi nd upl i f t r esi st ance speci f i ed.

As suppl i ed and war r ant ed f or t he subst r at e t ype( s) by EPDM sheet manuf act ur er and r ecommended by EPDM sheet manuf act ur er ' s pr i nt ed dat a.

2. 1. 8. 1 St r ess Pl at es f or Fast ener s

Fl at cor r osi on- r esi st ant r ound st r ess pl at es as r ecommended by t he r oof membr ane manuf act ur er ' s pr i nt ed i nst r uct i ons and meet i ng t he r equi r ement s of FM 4470; not l ess t han 2 i nch i n di amet er . Pr ovi de pr e- f or med di scs t o pr event di shi ng or cuppi ng.

2. 1. 8. 2 Auxi l i ar y Fast ener s

Cor r osi on r esi st ance scr ews, nai l s, or anchor s sui t abl e f or i nt ended at t achment pur pose and as r ecommended by t he r oof membr ane manuf act ur er .

2. 1. 8. 3 Powder - Dr i ven Fast ener s

Powder - dr i ven f ast ener s may be used onl y when appr oved i n wr i t i ng.

2. 1. 8. 4 Met al Di sks

Pr ovi de f l at met al di sks of mi ni mum 1 i nch i n di amet er . Met al di sks must be of nonf er r ous mat er i al compat i bl e wi t h t he nai l s or f ast ener s.

2. 1. 9 Pr e- Manuf act ur ed Accessor i es

Pr e- manuf act ur ed accessor i es must be manuf act ur er ' s st andar d f or i nt ended pur pose, compat i bl e wi t h t he membr ane r oof syst em and appr oved f or use by t he r oof membr ane manuf act ur er .

2. 1. 9. 1 Pr e- f abr i cat ed Cur bs

Pr ovi de 18 gauge G90 gal vani zedcur bs wi t h mi ni mum 4 i nch f l ange f or at t achment t o r oof nai l er s. Pr ovi de mi ni mum hei ght of 10 i nch above t he

Apr i l 2019 Page 9 SECTI ON 07 53 23 f i ni shed r oof membr ane sur f ace.

2. 1. 10 Rubber Wal kboar ds

Pr ovi de t he f ol l owi ng:

2. 1. 10. 1 Rubber Wal kboar ds

Pr ef or med r epr ocessed r ubber , compat i bl e wi t h t he EPDM sheet , 1/ 4 i nch mi ni mum t hi ckness, and wei ghi ng not l ess t han 1- 1/ 2 pounds per squar e f oot .

2. 1. 11 Wood Pr oduct s

Do not al l ow f i r e r et ar dant t r eat ed mat er i al s be i n cont act wi t h EPDM membr ane or EPDM accessor y pr oduct s, unl ess appr oved by t he membr ane manuf act ur er and t he Cont r act i ng Of f i cer .

2. 1. 12 Membr ane Li ner

EPDM membr ane l i ner conf or mi ng t o ASTM D4637/ D4637M, or ot her wat er pr oof membr ane l i ner mat er i al as appr oved by t he r oof membr ane manuf act ur er and t he Cont r act i ng Of f i cer .

2. 2 FLASHI NG CEMENT

Pr ovi de a sel f - vul cani z i ng but yl compound f l ashi ng cement f or spl i c i ng l aps and f or f l ashi ngs wor kabl e at 20 degr ees F. Obt ai n a r ecommendat i on f or such f l ashi ng cement f r om t he r oof i ng membr ane manuf act ur er .

PART 3 EXECUTI ON

3. 1 EXAMINATION

Ensur e t hat t he f ol l owi ng condi t i ons exi st pr i or t o appl i cat i on of t he r oof i ng mat er i al s:

a. Dr ai ns, cur bs, cont r ol j oi nt s, expansi on j oi nt s, per i met er wal l s, r oof penet r at i ng component s, and equi pment suppor t s ar e i n pl ace and ar e of pr oper hei ght t o r eci eve new r oof i ng.

b. Sur f aces ar e r i gi d, c l ean, dr y, smoot h, and f r ee f r om cr acks, hol es, and shar p changes i n el evat i on.

c. The pl ane of t he subst r at e does not var y mor e t han 1/ 4 i nch wi t hi n an ar ea 10 by 10 f eet when checked wi t h a 10 f oot st r ai ght edge pl aced anywher e on t he subst r at e.

d. Subst r at e i s s l oped t o pr ovi de posi t i ve dr ai nage.

e. Wal l s and ver t i cal sur f aces ar e const r uct ed t o r ecei ve count er f l ashi ng, and wi l l per mi t mechani cal f ast eni ng of t he base f l ashi ng mat er i al s.

f . Tr eat ed wood nai l er s ar e i n pl ace on non- nai l abl e sur f aces, t o per mi t nai l i ng of base f l ashi ng at mi ni mum hei ght of 8 i nch above f i ni shed r oof i ng sur f ace.

g. Pr essur e- pr eser vat i ve t r eat ed wood nai l er s ar e f ast ened i n pl ace at eaves, gabl e ends, openi ngs, and i nt er sect i ons wi t h ver t i cal sur f aces

Apr i l 2019 Page 10 SECTI ON 07 53 23 f or secur i ng of membr ane, edgi ng st r i ps, at t achment f l anges of sheet met al , and r oof f i x t ur es. Sur f ace- appl i ed nai l er s ar e t he same t hi ckness as t he r oof i nsul at i on.

h. Avoi d cont act of EPDM mat er i al s wi t h f i r e r et ar dant t r eat ed wood, except as appr oved by t he r oof membr ane manuf act ur er and Cont r act i ng Officer.

i . Cant s ar e secur el y f ast ened i n pl ace i n t he angl es f or med by wal l s and ot her ver t i cal sur f aces. The angl e of t he cant i s 45 degr ees and t he hei ght of t he ver t i cal l eg i s not l ess t han 3- 1/ 2 i nch.

j . Vent i ng i s pr ovi ded i n accor dance wi t h t he f ol l owi ng:

( 1) Edge Vent i ng: Per i met er nai l er s ar e ker f ed acr oss t he wi dt h of t he nai l er s t o per mi t escape of gaseous pr essur e at r oof edges.

( 2) Under si de Vent i ng: Vent openi ngs ar e pr ovi ded i n st eel f or m decki ng f or cast - i n- pl ace concr et e subst r at e.

( 3) Vapor pr essur e r el i ef vent s: Hol es equal t o t he out si de di amet er of vent s ar e pr ovi ded t hr ough t he i nsul at i on wher e vent s ar e r equi r ed. Space vent s i n accor dance wi t h membr ane manuf act ur er ' s recommendations.

k. Exposed nai l heads i n wood subst r at es ar e pr oper l y set . War ped and spl i t boar ds and sheet s have been r epl aced. Ther e ar e no cr acks or end j oi nt s 1/ 4 i nch i n wi dt h or gr eat er . Joi nt s i n pl ywood subst r at es ar e t aped or ot her wi se seal ed t o pr event ai r l eakage f r om t he underside.

l . I nsul at i on boar ds ar e i nst al l ed smoot hl y and evenl y, and ar e not br oken, cr acked, or cur l ed. Ther e ar e no gaps i n i nsul at i on boar d j oi nt s exceedi ng 1/ 4 i nch i n wi dt h. I nsul at i on i s bei ng r oof ed over on t he same day t he i nsul at i on i s i nst al l ed.

3. 2 APPLICATION

Appl y ent i r e EPDM sheet ut i l i z i ng f ul l y adher ed appl i cat i on met hod. Appl y r oof i ng mat er i al s as speci f i ed her ei n unl ess appr oved ot her wi se by t he Cont r act i ng Of f i cer .

3. 2. 1 Speci al Pr ecaut i ons

a. Do not di l ut e coat i ngs or seal ant s unl ess speci f i cal l y r ecommended by t he mat er i al s manuf act ur er ' s pr i nt ed appl i cat i on i nst r uct i ons. Do not t hi n l i qui d mat er i al s wi t h c l eaner s used f or c l eani ng EPDM sheet .

b. Keep l i qui ds i n ai r t i ght cont ai ner s, and keep cont ai ner s c l osed except when r emovi ng mat er i al s.

c. Use l i qui d component s, i ncl udi ng adhesi ves, wi t hi n t hei r shel f l i f e per i od. St or e adhesi ves at 60 t o 80 degr ees F pr i or t o use. Avoi d excessi ve adhesi ve appl i cat i on and adhesi ve spi l l s , as t hey can be dest r uct i ve t o some el ast omer i c sheet s and i nsul at i ons; f ol l ow adhesi ve manuf act ur er ' s pr i nt ed appl i cat i on i nst r uct i ons. Mi x and use l i qui d component s i n accor dance wi t h l abel di r ect i ons and manuf act ur er ' s pr i nt ed i nst r uct i ons.

Apr i l 2019 Page 11 SECTI ON 07 53 23

d. Pr ovi de cl ean, dr y c l ot hs or pads f or appl y i ng membr ane cl eaner s and cl eani ng of membr ane

e. Do not use heat guns or open f l ame t o expedi t e dr yi ng of adhesi ves or primers.

f . Requi r e wor kmen and ot her s who wal k on t he membr ane t o wear c l ean, sof t - sol ed shoes t o avoi d damage t o r oof i ng mat er i al s.

g. Do not use equi pment wi t h shar p edges whi ch coul d punct ur e t he EPDM sheet.

h. Shut down ai r i nt akes and any r el at ed mechani cal syst ems and seal open vent s and ai r i nt akes when appl y i ng sol vent - based mat er i al s i n t he ar ea of t he openi ng or i nt ake. Coor di nat e shut downs wi t h t he Cont r act i ng Of f i cer .

3. 2. 2 EPDM Sheet Roof i ng

Pr ovi de a wat er t i ght r oof membr ane sheet f r ee of cont ami nant s and def ect s t hat mi ght af f ect ser vi ceabi l i t y . Pr ovi de a uni f or m, st r ai ght , and f l at edge. Unr ol l EPDM sheet r oof i ng i n posi t i on wi t hout st r et chi ng membr ane.

I nspect f or hol es. Remove sect i ons of EPDM sheet r oof i ng t hat ar e damaged. Al l ow sheet s t o r el ax mi ni mum 30 mi nut es bef or e seami ng. Lap sheet s as speci f i ed, t o shed wat er , and as r ecommended by t he r oof membr ane manuf act ur er ' s publ i shed i nst al l at i on i nst r uct i ons f or t he appl i cat i on r equi r ed but not l ess t han 3 i nch i n any case.

3. 2. 3 Appl i cat i on Met hod

3. 2. 3. 1 Ful l y Adher ed Membr ane Appl i cat i on

Layout membr ane and si de l ap adj oi ni ng sheet s i n accor dance wi t h membr ane manuf act ur er ' s pr i nt ed i nst al l at i on i nst r uct i ons. Al l ow f or suf f i c i ent membr ane t o f or m pr oper membr ane t er mi nat i ons. Remove dust i ng agent s and di r t f r om membr ane and subst r at e ar eas wher e bondi ng adhesi ves ar e t o be appl i ed. Appl y speci f i ed adhesi ve evenl y and cont i nuousl y t o subst r at e and under si de of sheet s at r at es r ecommended by t he r oof membr ane manuf act ur er ' s pr i nt ed appl i cat i on i nst r uct i ons. When adhesi ve i s spr ay appl i ed, r ol l wi t h a pai nt r ol l er t o ensur e pr oper cont act and cover age.

Do not appl y bondi ng adhesi ve t o sur f aces of membr ane i n seam or l ap ar eas. Al l ow adhesi ve t o f l ash of f or dr y t o consi st ency pr escr i bed by manuf act ur er bef or e adher i ng sheet s t o t he subst r at e. Rol l each sheet i nt o adhesi ve s l owl y and evenl y t o avoi d wr i nkl es; br oom or r ol l t he membr ane t o r emove ai r pocket s and f i shmout hs and t o ensur e f ul l , cont i nuous bondi ng of sheet t o subst r at e. For m f i el d l ap spl i ces or seams as speci f i ed. Check al l seams and ensur e f ul l l ap seal . Appl y l ap seal ant t o al l adhesi ve f or med seams and al l cut edges of r ei nf or ced membr ane mat er i al s.

3. 2. 4 Tape Seams / Lap Spl i ces

Fi el d f or m seams, or l ap spl i ces, wi t h seam t ape i n accor dance wi t h membr ane manuf act ur er ' s pr i nt ed i nst r uct i ons and as speci f i ed. Cl ean and pr i me mat i ng sur f aces i n t he seam ar ea. Af t er pr i mer has dr i ed or set i n accor dance wi t h membr ane manuf act ur er ' s i nst r uct i ons, appl y seam t ape t o bot t om membr ane and r ol l wi t h a 3 i nch t o 4 i nch wi de smoot h s i l i cone or st eel hand r ol l er , or ot her manuf act ur er appr oved r ol l i ng devi ce, t o ensur e f ul l cont act and adhesi on of t ape t o bot t om membr ane. Tape end

Apr i l 2019 Page 12 SECTI ON 07 53 23 l aps must be mi ni mum 1 i nch. Rol l t op membr ane i nt o posi t i on t o check f or pr oper over l ap and al i gnment . Remove r el ease paper f r om t op of seam t ape and f or m seam spl i ce. Ensur e t op membr ane cont act wi t h seam t ape as r el ease paper i s r emoved. Rol l t he c l osed seam wi t h a smoot h s i l i cone or st eel hand r ol l er , r ol l i ng f i r st acr oss t he wi dt h of t he seam t hen al ong t he ent i r e l engt h, bei ng car ef ul not t o damage t he membr ane. Appl y membr ane- backed f l ashi ng t ape over T- i nt er sect i ons of r oof membr ane as r equi r ed by t he Manuf act ur er . Rol l t ape t o ensur e f ul l adhesi on and seal over T- j oi nt .

3. 2. 5 Adhesi ve Seams / Lap Spl i ces

Use onl y f i el d- appl i ed adhesi ve f or med seams i n f l ashi ng ar eas wher e appr oved by t he membr ane manuf act ur er and t he Cont r act i ng Of f i cer . Do not use adhesi ve f or med seams f or f i el d of r oof membr ane seami ng, except as appr oved by t he membr ane manuf act ur er and t he Cont r act i ng Of f i cer .

Thor oughl y and compl et el y c l ean mat i ng sur f aces of mat er i al s t hr oughout t he l ap ar ea. Remove al l di r t , dust , and cont ami nant s and al l ow t o dr y.

Appl y pr i mer as r ecommended by t he membr ane manuf act ur er . Appl y spl i ce adhesi ve wi t h a 3 i nch t o 4 i nch wi de, 1/ 2 i nch t hi ck, sol vent - r esi st ant br ush i n a smoot h, even coat wi t h l ong br ush st r okes. Bl eed out br ush mar ks. Do not appl y adhesi ve i n a c i r cul ar mot i on. Si mul t aneousl y appl y adhesi ve t o bot h mat i ng sur f aces i n an appr oxi mat e 0. 025 t o 0. 030 i nch wet f i l m t hi ckness, or ot her t hi ckness as r ecommended by t he r oof membr ane manuf act ur er ' s pr i nt ed i nst r uct i ons.

Al l ow t he spl i ce adhesi ve t o set - up i n accor dance wi t h membr ane manuf act ur er ' s pr i nt ed i nst r uct i ons. Per f or m manuf act ur er r ecommended f i el d check t o t est f or adhesi ve r eadi ness pr i or t o c l osi ng seam. Appl y a 1/ 8 i nch t o 1/ 4 i nch bead of i n- seam seal ant appr oxi mat el y 1/ 2 i nch f r om t he i nsi de edge of t he l ower membr ane sheet pr i or t o c l osi ng t he seam.

Ensur e t he i n- seam seal ant does not ext end ont o t he spl i ce adhesi ve.

Mai nt ai n t he f ul l adher ed seam wi dt h r equi r ed. Rol l t he t op membr ane ont o t he mat i ng sur f ace. Rol l t he seam ar ea wi t h a 2 i nch t o 3 i nch wi de, smoot h s i l i cone or st eel hand r ol l er . A mi ni mum of 2 hour s af t er j oi ni ng sheet s and when t he l ap edge i s dr y, c l ean t he l ap edge wi t h membr ane manuf act ur er ' s r ecommended cl eaner and appl y a 1/ 4 i nch t o 3/ 8 i nch bead of l ap seal ant cent er ed on t he seam edge. Wi t h a f eat her i ng t ool , i mmedi at el y f eat her t he l ap seal ant t o compl et el y cover t he spl i ce edge, l eavi ng a mound of seal ant over t he seam edge. Appl y l ap seal ant t o al l adhesi ve f or med seams.

3. 2. 6 Per i met er At t achment

Adhesi ve bond or mechani cal l y secur e r oof membr ane sheet at r oof per i met er i n a manner t o compl y wi t h wi nd r esi st ance r equi r ement s and i n accor dance wi t h membr ane manuf act ur er ' s pr i nt ed appl i cat i on i nst r uct i ons. When adhesi vel y bondi ng a mechani cal l y f ast ened syst em i n per i met er ar eas, t he per i met er boundar y of t he adhesi ve bond must be t he same as t he boundar y r equi r ed f or addi t i onal per i met er mechani cal f ast eni ng t o meet wi nd r esi st ance r equi r ement s.

3. 2. 7 Secur ement at Base Ti e- I n Condi t i ons

Mechani cal l y f ast en t he r oof membr ane at penet r at i ons, at base of cur bs and wal l s, and at al l l ocat i ons wher e t he membr ane t ur ns and angl e gr eat er t han 4 degr ees ( 1: 12) . Space f ast ener s a maxi mum of 12 i nch on cent er , except wher e mor e f r equent at t achment i s r equi r ed t o meet speci f i ed wi nd

Apr i l 2019 Page 13 SECTI ON 07 53 23 r esi st ance or wher e r ecommended by t he r oof membr ane manuf act ur er . Fl ash over f ast ener s wi t h a f ul l y adher ed l ayer of mat er i al as r ecommended by t he r oof membr ane manuf act ur er ' s pr i nt ed dat a.

3. 3 FLASHINGS

3. 3. 1 General

Pr ovi de f l ashi ngs i n t he angl es f or med at wal l s and ot her ver t i cal sur f aces and wher e r equi r ed t o make t he wor k wat er t i ght , except wher e met al f l ashi ngs ar e i ndi cat ed.

Pr ovi de a one- pl y f l ashi ng membr ane, as speci f i ed f or t he syst em used, and i nst al l i mmedi at el y af t er t he r oof i ng membr ane i s pl aced and pr i or t o f i ni sh coat i ng wher e a f i ni sh coat i ng i s r equi r ed. Fl ashi ngs must be st epped wher e ver t i cal sur f aces abut s l oped r oof sur f aces. Pr ovi de sheet met al r egl et i n whi ch sheet met al cap f l ashi ngs ar e i nst al l ed of not mor e t han 16 i nch nor l ess t han 8 i nch above t he r oof i ng sur f aces. Exposed j oi nt s and end l aps of f l ashi ng membr ane must be made and seal ed i n t he manner r equi r ed f or r oof i ng membr ane.

3. 3. 2 Membr ane Fl ashi ng

I nst al l f l ashi ng and f l ashi ng accessor i es as t he r oof membr ane i s i nst al l ed. Appl y f l ashi ng t o c l eaned sur f aces and as r ecommended by t he r oof membr ane manuf act ur er and as speci f i ed. Ut i l i ze cur ed EPDM membr ane f l ashi ng and pr ef abr i cat ed accessor y f l ashi ngs t o t he maxi mum ext ent r ecommended by t he r oof membr ane manuf act ur er . Li mi t uncur ed f l ashi ng mat er i al t o r ei nf or ci ng i nsi de and out si de cor ner s and angl e changes i n pl ane of membr ane, and t o f l ashi ng scupper s, pour abl e seal er pocket s, and ot her f or med penet r at i ons or unusual l y shaped condi t i ons as r ecommended by t he r oof membr ane manuf act ur er wher e t he use of cur ed mat er i al i s i mpr act i cal . Ext end base f l ashi ng not l ess t han 8 i nch above r oof i ng sur f ace and as necessar y t o pr ovi de f or seami ng over l ap on r oof membr ane as r ecommended by t he r oof membr ane manuf act ur er .

Seal f l ashi ng membr ane f or a mi ni mum of 3 i nch on each si de of f ast eni ng devi ce used t o anchor r oof membr ane t o nai l er s. Compl et el y adher e f l ashi ng sheet s i n pl ace. Seam f l ashi ng membr ane i n t he same manner as r oof membr ane, except as ot her wi se r ecommended by t he membr ane manuf act ur er ' s pr i nt ed i nst r uct i ons and appr oved by t he Cont r act i ng Of f i cer . Rei nf or ce al l cor ner s and angl e t r ansi t i ons by appl y i ng uncur ed membr ane t o t he ar ea i n accor dance wi t h r oof membr ane manuf act ur er r ecommendat i ons. Mechani cal l y f ast en t op edge of base f l ashi ng wi t h manuf act ur er r ecommended t er mi nat i on bar f ast ened at maxi mum 12 i nch on cent er . I nst al l sheet met al f l ashi ng over t he t er mi nat i on bar i n t he compl et ed wor k. Mechani cal l y f ast en t op edge of base f l ashi ng f or al l ot her t er mi nat i ons i n a manner r ecommended by t he r oof membr ane manuf act ur er . Appl y membr ane l i ner over t op of exposed nai l er s and bl ocki ng and t o over l ap t op edge of base f l ashi ng i nst al l at i on at cur bs, par apet wal l s, expansi on j oi nt s and as ot her wi se i ndi cat ed t o ser ve as wat er pr oof l i ni ng under sheet met al f l ashi ng component s.

3. 3. 3 Fl ashi ng at Roof Dr ai n

Pr ovi de a f act or y edge t aper ed i nsul at i on sump i nt o t he dr ai n bowl ar ea.

Do not exceed t aper ed sl ope of 18 degr ees f or unr ei nf or ced membr ane and 5 degr ees f or r ei nf or ced membr ane. Pr ovi de t aper ed i nsul at i on wi t h sur f ace sui t abl e f or adher i ng membr ane i n t he dr ai n sump ar ea. Avoi d f i el d seams

Apr i l 2019 Page 14 SECTI ON 07 53 23 r unni ng t hr ough or wi t hi n 24 i nch of r oof dr ai n, or as ot her wi se r ecommended by t he r oof membr ane manuf act ur er . Adher e t he membr ane t o t he t aper ed i n t he dr ai n sump ar ea. Appl y wat er bl ock mast i c and ext end membr ane sheet s over edge of dr ai n bowl openi ng at t he r oof dr ai n deck f l ange i n accor dance wi t h membr ane manuf act ur er ' s pr i nt ed appl i cat i on i nst r uct i ons. I nsur e membr ane f r ee of wr i nkl es and f ol ds i n t he dr ai n ar ea. Secur el y c l amp membr ane i n t he f l ashi ng cl ampi ng r i ng. Ensur e membr ane i s cut t o wi t hi n 3/ 4 i nch of i nsi de r i m of c l ampi ng r i ng t o mai nt ai n dr ai nage capaci t y. Do not cut back t o bol t hol es. Ret r of i t r oof dr ai ns must conf or m t o ANSI / SPRI RD- 1.

3. 3. 4 PRE- FABRI CATED CURBS

Secur el y anchor pr ef abr i cat ed cur bs t o nai l er or ot her base subst r at e and f l ashed wi t h EPDM membr ane f l ashi ng mat er i al s.

3. 3. 5 Set - On Accessor i es

Wher e pi pe or condui t bl ocki ng, suppor t s and si mi l ar r oof accessor i es, or i sol at ed paver bl ock, ar e set on t he membr ane, adher e r ei nf or ced membr ane or wal kpad mat er i al , as r ecommended by t he r oof membr ane manuf act ur er , t o bot t om of accessor i es pr i or t o set t i ng on r oof i ng membr ane. Speci f i c met hod of i nst al l i ng set - on accessor i es must per mi t nor mal movement due t o expansi on, cont r act i on, v i br at i on, and si mi l ar occur r ences wi t hout damagi ng r oof i ng membr ane. Do not mechani cal l y secur e set - on accessor i es t hr ough r oof i ng membr ane i nt o r oof deck subst r at e.

3. 3. 6 Li ght ni ng Pr ot ect i on

Fl ash l i ght ni ng pr ot ect i on syst em component s or at t ach t o t he r oof membr ane i n a manner accept abl e t o t he r oof membr ane manuf act ur er .

3. 4 ROOF WALKPADS

I nst al l wal kpads at r oof access poi nt s and wher e ot her wi se i ndi cat ed f or t r af f i c ar eas and f or access t o mechani cal equi pment , i n accor dance wi t h t he r oof membr ane manuf act ur er ' s pr i nt ed i nst r uct i ons. Pr ovi de mi ni mum 6 i nch separ at i on bet ween adj acent wal kpads t o accommodat e dr ai nage.

3. 5 CORRECTI ON OF DEFI CI ENCI ES

Wher e any f or m of def i c i ency i s f ound, addi t i onal measur es must be t aken as deemed necessar y by t he Cont r act i ng Of f i cer t o det er mi ne t he ext ent of t he def i c i ency and cor r ect i ve act i ons must be as di r ect ed by t he Cont r act i ng Of f i cer .

3. 6 CLEAN UP

Remove debr i s, scr aps, cont ai ner s and ot her r ubbi sh and t r ash r esul t i ng f r om i nst al l at i on of t he r oof i ng syst em f r om j ob si t e each day.

3. 7 PROTECTI ON OF APPLI ED ROOFI NG

At t he end of t he day' s wor k and when pr eci pi t at i on i s i mmi nent , pr ot ect appl i ed membr ane r oof i ng syst em f r om wat er i nt r usi on.

3. 7. 1 Wat er Cut of f s

St r ai ght en i nsul at i on l i ne usi ng l oose- l ai d cut i nsul at i on sheet s and seal

Apr i l 2019 Page 15 SECTI ON 07 53 23 t he t er mi nat ed edge of t he r oof membr ane syst em i n an ef f ect i ve manner .

Seal of f f l ut es i n met al decki ng al ong t he cut of f edge. Remove t he wat er cut - of f s t o expose t he i nsul at i on when r esumi ng wor k, and r emove t he i nsul at i on sheet s used f or f i l l - i n.

3. 7. 2 Tempor ar y Fl ashi ng f or Per manent Roof i ng

Pr ovi de t empor ar y f l ashi ng at dr ai ns, cur bs, wal l s and ot her penet r at i ons and t er mi nat i ons of r oof i ng sheet s unt i l per manent f l ashi ngs can be appl i ed. Remove t empor ar y f l ashi ng bef or e appl y i ng per manent f l ashi ng.

3. 7. 3 Tempor ar y Wal kways, Runways, and Pl at f or ms

Do not per mi t st or i ng, wal k i ng, wheel i ng, and t r ucki ng di r ect l y on appl i ed r oof i ng mat er i al s. Pr ovi de t empor ar y wal kways, r unways, and pl at f or ms of smoot h c l ean boar ds, mat s or pl anks as necessar y t o avoi d damage t o appl i ed r oof i ng mat er i al s, and t o di st r i but e wei ght t o conf or m t o l i ve l oad l i mi t s of r oof const r uct i on. Use r ubber - t i r ed equi pment f or r oof i ng work.

3. 8 FI ELD QUALI TY CONTROL

3. 8. 1 Const r uct i on Moni t or i ng

Dur i ng pr ogr ess of t he r oof wor k, Cont r act or must make vi sual i nspect i ons as necessar y t o ensur e compl i ance wi t h speci f i ed par amet er s. Addi t i onal l y, ver i f y t he f ol l owi ng:

a. Equi pment i s i n wor ki ng or der . Met er i ng devi ces ar e accur at e.

b. Mat er i al s ar e not i nst al l ed i n adver se weat her condi t i ons.

c. Subst r at es ar e i n accept abl e condi t i on, i n compl i ance wi t h speci f i cat i on, pr i or t o appl i cat i on of subsequent mat er i al s.

Nai l er s and bl ocki ng ar e pr ovi ded wher e and as needed.

I nsul at i on subst r at e i s smoot h, pr oper l y secur ed t o i t s subst r at e, and wi t hout excessi ve gaps pr i or t o membr ane appl i cat i on.

The pr oper number , t ype, and spaci ng of f ast ener s ar e i nst al l ed.

Mat er i al s compl y wi t h t he speci f i ed r equi r ement s.

Al l mat er i al s ar e pr oper l y st or ed, handl ed and pr ot ect ed f r om moi st ur e or ot her damages. Li qui d component s ar e pr oper l y mi xed pr i or t o application.

Membr ane i s al l owed t o r el ax pr i or t o seami ng. Adhesi ves ar e appl i ed uni f or ml y t o bot h mat i ng sur f aces and checked f or pr oper set pr i or t o bondi ng mat i ng mat er i al s. Mechani cal at t achment s ar e spaced as r equi r ed, i ncl udi ng addi t i onal f ast eni ng of membr ane i n cor ner and per i met er ar eas as r equi r ed.

Membr ane i s pr oper l y over l apped.

Membr ane seami ng i s as speci f i ed and seams ar e hand r ol l ed t o ensur e f ul l adhesi on and bond wi dt h. I n- seam seal ant i s appl i ed when adhesi ve seams ar e used i n t he f i el d of t he r oof . Al l seams ar e

Apr i l 2019 Page 16 SECTI ON 07 53 23 checked at t he end of each wor k day.

Appl i ed membr ane i s i nspect ed and r epai r ed as necessar y pr i or t o bal l ast i nst al l at i on.

Membr ane i s f ul l y adher ed wi t hout r i dges, wr i nkl es, k i nks, f i shmout hs.

I nst al l er adher es t o speci f i ed and det ai l ed appl i cat i on par amet er s.

Associ at ed f l ashi ngs and sheet met al ar e i nst al l ed i n a t i mel y manner i n accor d wi t h t he speci f i ed r equi r ement s.

Bal l ast i s wi t hi n t he speci f i ed wei ght r ange.

Tempor ar y pr ot ect i on measur es ar e i n pl ace at t he end of each wor k shift.

3. 8. 2 Manuf act ur er ' s I nspect i on

Manuf act ur er ' s t echni cal r epr esent at i ve must v i s i t t he s i t e a mi ni mum of t hr ee t i mes dur i ng t he i nst al l at i on f or pur poses of r evi ewi ng mat er i al s i nst al l at i on pr act i ces and adequacy of wor k i n pl ace. I nspect i ons must occur dur i ng t he f i r st 20 squar es of membr ane i nst al l at i on, at mi d- poi nt of t he i nst al l at i on, and at subst ant i al compl et i on, at a mi ni mum. Af t er each i nspect i on, submi t a r epor t s i gned by t he manuf act ur er ' s t echni cal r epr esent at i ve t o t he Cont r act i ng Of f i cer wi t hi n 3 wor ki ng days. Not e over al l qual i t y of wor k, def i c i enci es and any ot her concer ns, and r ecommended cor r ect i ve act i on.

3. 8. 3 Roof Dr ai n Test

Af t er compl et i ng r oof i ng but pr i or t o Gover nment accept ance, per f or m t he f ol l owi ng t est f or wat er t i ght ness. Pl ug r oof dr ai ns and f i l l wi t h wat er t o edge of dr ai n sump f or 8 hour s. Ret r of i t r oof dr ai ns must conf or m t o ANSI / SPRI RD- 1. Do not pl ug secondar y over f l ow dr ai ns at t he same t i me as adj acent pr i mar y dr ai n. To ensur e some dr ai nage f r om r oof , do not t est al l dr ai ns at same t i me. Measur e wat er at begi nni ng and end of t he t est per i od. When pr eci pi t at i on occur s dur i ng t est per i od, r epeat t est . When wat er l evel f al l s , r emove wat er , t hor oughl y dr y, and i nspect i nst al l at i on;

r epai r or r epl ace r oof i ng at dr ai n t o pr ovi de f or a pr oper l y i nst al l ed wat er t i ght f l ashi ng seal . Repeat t est unt i l t her e i s no wat er l eakage.

3. 9 I NSTRUCTI ONS TO GOVERNMENT PERSONNEL

Fur ni sh wr i t t en and ver bal i nst r uct i ons on pr oper mai nt enance pr ocedur es t o desi gnat ed Gover nment per sonnel . Fur ni sh i nst r uct i ons by a compet ent r epr esent at i ve of t he r oof membr ane manuf act ur er and i ncl ude a mi ni mum of 4 hour s on mai nt enance and emer gency r epai r of t he membr ane. I ncl ude a demonst r at i on of membr ane r epai r , and gi ve sour ces of r equi r ed speci al t ool s. Fur ni sh i nf or mat i on on saf et y r equi r ement s dur i ng mai nt enance and emer gency r epai r oper at i ons.

3. 10 I NFORMATI ON CARD

For each r oof , f ur ni sh a t ypewr i t t en i nf or mat i on car d f or f aci l i t y r ecor ds anda phot oengr aved 0. 032 i nch t hi ck al umi num car d f or ext er i or di spl ay.

Car d must be 8- 1/ 2 by 11 i nch mi ni mum. I nf or mat i on car d must i dent i f y f aci l i t y name and number ; l ocat i on; cont r act number ; appr oxi mat e r oof ar ea; det ai l ed r oof syst em descr i pt i on, i ncl udi ng deck t ype, membr ane, Apr i l 2019 Page 17 SECTI ON 07 53 23 number of pl i es, met hod of appl i cat i on, manuf act ur er , i nsul at i on and cover boar d syst em and t hi ckness; pr esence of t aper ed i nsul at i on f or pr i mar y dr ai nage, pr esence of vapor r et ar der ; dat e of compl et i on; i nst al l i ng cont r act or i dent i f i cat i on and cont act i nf or mat i on; membr ane manuf act ur er war r ant y expi r at i on, war r ant y r ef er ence number , and cont act i nf or mat i on.

I nst al l car d at r oof t op or access l ocat i on as di r ect ed by t he Cont r act i ng Of f i cer and pr ovi de a paper copy t o t he Cont r act i ng Of f i cer .

- - End of Sect i on - -

Apr i l 2019 Page 18 SECTI ON 07 53 23

File details come from the government source that posted it. Updated .