Clay_Co_FS24_Purvis_Documents_(2026_01-02)_Bid_Set.pdf
PDF 609 KB Posted
- Attached to
- Construction of Clay County Fire Station No. 24
- Solicitation number
- 25/26-042
- Issued by
- Clay County, Harold CDP, Florida
About this file
This is a technical specification and scope of work document for the PURVIS fire station communication and alert system being installed at Clay County Fire Station No. 24 in Green Cove Springs, Florida. The document outlines the system components, installation requirements, and responsibilities shared between PURVIS Systems Incorporated and the electrical contractor. The project includes installation of 26 interior ceiling speakers (70-volt), 20 interior ceiling speakers with red and white LED indicators, 4 flat panel message boards (sizes 32", 42", and 55"), 15 dorm remotes, 6 emergency buttons, 7 high-power exterior/apparatus bay speakers, 5 volume controls, 3 unit presence detectors, 1 remote touch screen, 1 camera/doorbell system, and associated control equipment. PURVIS Systems is responsible for providing shop drawings, system components, technical support to the electrical contractor, all programming and calibrations, end-user training, and one year of system warranty. The electrical contractor is responsible for providing all permits, wiring materials, wire runs compliant with NFPA 70 code, dedicated electrical power connections, complete system installation including head-end equipment, as-built drawings, and one year of labor and material warranty. The document specifies precise mounting heights ranging from 36 to 95 inches above finished floor, detailed wire specifications including Cat5/6 cable, various gauges of plenum-shielded wire, and microphone cable specifications from manufacturers including Southwest Wire, Canare, West Penn, Charlotte Wire and Cable, and Omni Cable.
The project timeline aligns with the overall Fire Station No. 24 construction schedule, with substantial completion required by March 15, 2027, and final Certificate of Occupancy by March 20, 2027. All wiring must comply with NFPA 70 electrical code and be clearly tagged and labeled. Wire runs are to be installed with appropriate conduit, surface mold, hangers, and wire ties as required. The document specifies single gang 3-inch deep boxes for most connections, with larger boxes required for message boards, strobe lights, and LED lights. The controller equipment includes a Station Control Unit (SCU), Audio Relay Expansion Module (ARXM), network switches (16, 24, or 28 port), dorm remote gateways, amplifier, and uninterruptible power supply (UPS), all requiring rackmount installation at the designated controller location. The project is funded through Federal Emergency Management Agency (FEMA) Public Assistance Grant Program funding and is subject to Davis-Bacon Act prevailing wage requirements and compliance with 2 CFR Part 200 Uniform Guidance and FEMA Field Manual for Public Assistance standards.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FSAS Summary Page
04/13/2023 C
TITLE:
Company Proprietary
PURVIS Proprietary - This document contains information which is the exclusive property of PURVIS Systems
Incorporated. Distribution, reproduction or use by others is not permitted without the written consent of
PURVIS Systems.
DATE:
REV:
PURVIS Systems Incorporated 88 Silva Lane Middletown, RI 02842
WIRE LEGEND
Wire Specifications:
1. Controller Interconnects – Cat5/6, 18/2 Plenum Shielded
2. Remote Touch Screen (RTS) – Cat5/6 (Qty - 2)
3. Remote Microphone – 24/4 Plenum Shielded Microphone cable
4. 25/70v Apparatus Bay, External and Ceiling/Wall Speakers – 18/2 Plenum Shielded
5. Self-Amplified Apparatus Bay, External and Ceiling/Wall Speakers – 18/4 Plenum Shielded
6. LED Speaker Ring wiring – 18/4 Plenum Shielded
7. Message Board – Cat5/6
8. Turn Out Timer – Cat5/6
9. Printer – Cat5/6
10.Pushbuttons – 18/4 Plenum Shielded (Illuminated style button)
11.Dorm Remotes – 18/4 Twisted Pair Plenum Shielded
12.Unit Presence Detector – 18/4 Plenum Shielded
13.WAN connection – Cat5/6
14.Radio Connections – 18/2 Plenum Shielded
15.Bay Door Controller Connection – 18/2 Plenum Shielded
16.Ambient Noise Sensor and Modules – 18/2 Plenum Shielded
17.Camera Control Unit (CCU) – 18/2 Plenum Shielded,Cat5/6,24/4 Microphone Cable
18.Tower Light – 18/8 Plenum
19. Rotating Light – 18/2 Plenum Shielded
20. 3.5" Disc LED Light – 18/2 Plenum Shielded
21. Strobe Light – 18/2 Plenum Shielded
Wire Length for device connections - 16"
Purvis Systems Scope of Work:
1. Provide shop drawings of field devices
2. Provide system components
3. Provide technical support to electrical contractor
4. Provide all programming and calibrations
5. Provide end user training
6. Provide 1 year of system warranty - Elect. Cont. may assist Purvis Systems for payment to make repairs/replacements as needed
Mounting Heights:
All are Above Finished Floor (AFF) to bottom of the box
Remote Touch Screen (RTS) - 54" or Desktop
MIC XLR Plate – Behind RTS or under table top
Apparatus bay speakers to be hung 16' A.F.F.
Volume Controls – 48"
LCDs, LEDs, and power outlets - 80"
Apparatus Bay LCDs & power outlets - 95"
Turn Out timer – To the Left side of each Bay Door and 6' A.F.F
Printer stand/Shelf - 36"
Pushbuttons (Manual/Acknowledgment/Reset/Test/Doorbell) - 48"
Dorm Remotes - 48"
Unit Presence Detector – Centered over each Apparatus front/back, side to side
Camera Control Unit (CCU) – CCU Within 25' of the Camera, Speaker/MIC Box - 48", Camera – TBD
Tower Light - TBD
Single Color Trip Lights – Centered on ceiling
LED Light – Centered on ceiling
Strobe Light - TBD
Audio And Light Zones:
See Floor plan and pull schedule
Required boxes:
All Cat5/6 Locations - single gang 3" deep box
Microphone XLR Plate - Single gang 3" deep box
Volume Control - Single gang 4" deep box
Pushbuttons - Single gang 3" deep box
Dorm Remote - Single gang 3" deep box
Unit Presence Detector – Two Gang 3" deep box
Camera Control Unit (CCU) POE Injector – Single Gang Duplex
Tower Light – Double Gang Box (Gang plate provided with device (Wall or Ceiling)
Single Color Trip Light – Six Square Box
LED Light – Double Gang, Ceiling Octagon (T-Grid Box Hanger)
Strobe Light – Double Gang Box
AC Power: (All Outlets to be within 5' of the device)
Controller Location – 20Amp Dedicated
Remote Touch Screen (RTS) – Single Gang Duplex
Message Board – Single Gang Duplex
Turn Out Timer – Single Gang Duplex
Printer – Single Gang Duplex
Camera Control Unit (CCU) – Single Gang Duplex
Controller Dimensions and Weights:
Station Control Unit (SCU) – 5.2"H x 18.0"D x 17.3"W (32lbs)
Audio Relay Expansion Module (ARXM) – 3.5"H x 18.0"D x 17.3"W (14lbs)
Network Switch 16 Port – 1.75"H x 6.7"D x 11"W (3.15lbs)
Network Switch 24/28 Port – 1.75"H x 7.99"D x 17.35"W (5.05lbs)
Dorm Remote Gateway 2/4 Port (DRG) – .92"H x 3.5"D x 3.6"W (5lbs)
Dorm Remote Gateway 8/16/32 Port (DRG) – 1.75"H x 17.1"D x 10.38"W (7lbs)
Amplifier – 3.5"H x 18.25"D x 17.0"W (41lbs)
UPS - 3.5"H x 15.75"D x 17.25"W (58lbs)
Camera Control Unit – Controller – 12"H x 6"D x 12"W (16lbs)
Camera Intercom – 6.5"L x 4.6"W x 3/1"H (.86lbs)
Camera – 6.4"W x 4.06"H (1.84lbs)
Wire Types:
Cat5/6 - Southwest wire ( 57557401) 24/4 pair 24/4 MIC cable - Canare wire 200M Starquad mic wire(CANL4E5CBLA200M) 18/2 Plenum Shielded - West Penn (WP 25293BGY1000) 18g strd shld Plenum grey(formerly 25293B) 18/4 Plenum Shielded - Charlotte Wire and cable ( CW09423) plenum shielded 18/4 Plenum - WP 25244BGY1000 (formerly 25244B) Plenum Unshielded 18/8 - Omni Cable (G121808) 18G 8C Plen N-shd 18/4 – Twisted Shielded Pair
Surface Mount Options:
Wire Mold – 700 series
Electrical Contractor Scope of Work:
1. Provide permit if needed
2. Provide wire
3. Provide wire runs per NFPA 70 code
4. All wire runs to be clearly tagged & labeled
5. Provide all wiring materials (hangars, conduit, surface mold,wire ties, boxes, etc)
6. Provide high voltage electrical relay connections if needed
7. Provide other high voltage connections if needed
8. Provide electrical power where needed (dedicated/undedicated)
9. Provide complete system installation (including head end equipment)
10. Provide as-built drawings after installation
11. Provide 1 year of warranty on labor and Material
12. Provide an on-site representative when final connections are made
CAT5/6 – 586B
24/4 Microphone Cable (Special)
18/8 (Plenum as required by code)
18/4 Shielded (Plenum as required)
18/2 Twisted Shielded (Plenum as required)
18/4 Two Pair Twisted Shielded (Plen. as required)
0 Tower Light Wall ≥78" AFF or Ceiling
0 LED Light – Red or White Wall ≥78" AFF or Ceiling
0 Strobe Light - (R)ed , (A)mber, Green (G), Blue (B), (C)lear Wall ≥78" AFF or Ceiling
2 Stove / Grill Shutoff Controller Location
0 General Device Relay Control Controller Location
QTYICON DESCRIPTION MOUNT
0 Ambient Noise Module Wall ≥78" AFF or Ceiling
1 SCU/ARXM/DRG/AMP/SWT/UPS location Rackmount
4 Flat Panel Message Board 32" – 1, 42" – 2, 55" - 1 Wall ≥ 60" AFF
1 Remote Touch Screen Wall 54" AFF or Desktop
0 Turnout Timer Wall >54" AFF
1 Microphone (Desktop) Wall 48" AFF or Desktop
0 Reader Board Wall >54" AFF
26 Interior Ceiling Speaker (70v) Ceiling
0 Thermal Printer Shelf 36" AFF or Desktop
20 Interior Ceiling Speaker w/ RED & WHT LED (70v) Ceiling
6 Button – EMER, DOOR, MAN - 1, ACK-5, RESET, TEST Wall 48" AFF
0 Interior Wall Speaker (Self Amplified/70v/25v) Wall 78" AFF
15 Dorm Remote Wall 48" AFF
7 High Power Speaker (Exterior / App Bay) (70v) Wall ≥78" AFF or Ceiling
3 Unit Presence Detector Ceiling
5 Volume Control Wall 48" AFF
1 Bay Door Controller Controller Location
0 Ambient Noise Sensor Wall ≥78" AFF or Ceiling
1 Camera / Doorbell (DB) DB Wall 48" AFF
MB - 32”MB - 32”
TT - 1
RR
RB - 1
MB - 55”MB - 55”MB - 42”MB - 42”
Unit Presence Detector – Future Location (Wiring Only)1
FSAS Clay County Station 24
04/13/2023 C
TITLE:
Company Proprietary
PURVIS Proprietary - This document contains information which is the exclusive property of PURVIS Systems
Incorporated. Distribution, reproduction or use by others is not permitted without the written consent of
PURVIS Systems.
DATE:
REV:
PURVIS Systems Incorporated 88 Silva Lane Middletown, RI 02842
WIRE LEGEND
CAT5/6 – 586B
24/4 Microphone Cable (Special)
18/8 (Plenum as required by code)
18/4 Shielded (Plenum as required)
18/2 Twisted Shielded (Plenum as required)
18/4 Two Pair Twisted Shielded (Plen. as required)
0 Tower Light Wall ≥78" AFF or Ceiling
0 LED Light – Red or White Wall ≥78" AFF or Ceiling
0 Strobe Light - (R)ed , (A)mber, Green (G), Blue (B), (C)lear Wall ≥78" AFF or Ceiling
2 Stove / Grill Shutoff Controller Location
0 General Device Relay Control Controller Location
QTYICON DESCRIPTION MOUNT
0 Ambient Noise Module Wall ≥78" AFF or Ceiling
1 SCU/ARXM/DRG/AMP/SWT/UPS location Rackmount
4 Flat Panel Message Board 32" – 1, 42" – 2, 55" - 1 Wall ≥ 60" AFF
1 Remote Touch Screen Wall 54" AFF or Desktop
0 Turnout Timer Wall >54" AFF
1 Microphone (Desktop) Wall 48" AFF or Desktop
0 Reader Board Wall >54" AFF
26 Interior Ceiling Speaker (70v) Ceiling
0 Thermal Printer Shelf 36" AFF or Desktop
20 Interior Ceiling Speaker w/ RED & WHT LED (70v) Ceiling
6 Button – EMER, DOOR, MAN - 1, ACK-5, RESET, TEST Wall 48" AFF
0 Interior Wall Speaker (Self Amplified/70v/25v) Wall 78" AFF
15 Dorm Remote Wall 48" AFF
7 High Power Speaker (Exterior / App Bay) (70v) Wall ≥78" AFF or Ceiling
3 Unit Presence Detector Ceiling
5 Volume Control Wall 48" AFF
1 Bay Door Controller Controller Location
0 Ambient Noise Sensor Wall ≥78" AFF or Ceiling
1 Camera / Doorbell (DB) DB Wall 48" AFF