Clay_Co_FS24_Struct_(2026_01-02)_Bid_Set.pdf

PDF 2 MB Posted

Attached to
Construction of Clay County Fire Station No. 24
Solicitation number
25/26-042
Issued by
Clay County, Harold CDP, Florida

About this file

Summary

This file consists of structural design bid documents for the construction of Clay County Fire Station No. 24, prepared by Dasher Hurst Architects in Jacksonville, Florida, with structural engineering by G.M. Hill Engineering, Inc. The documents include comprehensive general notes, design criteria, schedules, wind pressure diagrams, and detailed sections for the foundation, framing, and connections of the fire station facility located at 1075 County Road 226 in Green Cove Springs, Florida. The project utilizes the Florida Building Code 2023, 8th Edition, and incorporates design standards including ASCE 7-22 for loads, TMS 402/602-16 for masonry, AISC 360-16 for structural steel, and ACI 318-19 for concrete. The structural design includes concrete masonry unit (CMU) walls with reinforcement, reinforced concrete foundations with footings ranging from continuous wall footings to spread footings, pre-fabricated wood trusses at 24-inch on-center spacing, and structural steel elements including columns and beams with detailed connection specifications. The design accommodates ultimate wind speeds of 143 miles per hour, gravity loads with roof live loads of 20 psf and floor live loads of 100 psf, and incorporates proper control joints, expansion joints, and construction sequencing requirements throughout the structure.

The structural documents establish minimum concrete compressive strength of 3,000 psi for normal-weight concrete with air entrainment for weather-exposed surfaces, masonry grout minimum compressive strength of 2,000 psi, and reinforcing steel with minimum yield strength of 60,000 psi. All structural steel conforms to ASTM A572, A992, A36, A500, or A53 standards as specified, with structural bolts meeting ASTM A325 or A490 requirements and all bolting tightened to snug-tight condition. Contractor submittals are required for concrete mix designs, reinforcing steel shop drawings, soil density and compressive strength test results, masonry product data, and wood truss calculations sealed by a specialty engineer. The foundation design is based on net allowable soil bearing pressures of 2,500 psf for spread footings and 2,000 psf for continuous wall footings, with design verification required from the on-site soils engineer for engineered fill materials. The documents include extensive technical specifications for masonry construction, including grout placement in 4-foot maximum lifts, horizontal joint reinforcement spacing requirements, control joint locations at maximum 25-foot intervals, and detailed reinforcing placement tolerances. All work must comply with the geotechnical investigation report prepared by Terracon dated January 27, 2023, with more stringent criteria applied where conflicts exist between the engineer's specifications and the geotechnical report.

View the file

Other files

File Type Posted
Construction_of_Clay_County_Fire_Station_No._24_(Addendum_#2_Revision).pdf PDF
Demolition_Asbestos_Survey_Report_.pdf PDF
Tile_Image_.jpg JPG image
07410-STANDING_SEAM_MTL_ROOFING_(Per_Addendum_1).pdf PDF
01260-CONTRACT_MOD_(per_Addendum_1).pdf PDF
01100_Owner_Furnished_Items_(Per_Addendum_1).pdf PDF
@TOC_(Per_Addendum_1).pdf PDF
266612-ASCO_ATS_ELEC_(per_Addendum_1).pdf PDF
Addendum_#1_-_266301-ELEC_TANK_SPEC_(per_Addendum_1).pdf PDF
Addendum_#1_-_266120-ELEC_GENSET_.pdf PDF
Addendum_#1_-_230000-HVAC_.pdf PDF
Addendum_#1_-_12511-Window_Blinds_.pdf PDF
Addendum_#1_-_11452-Appliances_.pdf PDF
Addendum_#1_-_10500-Mobile_PPE_Lockers_.pdf PDF
Addendum_#1_-_10425-Signs.pdf PDF
Addendum_#1_-_Clay_Co_FS24_-_Arch_(2026_02-17)_.pdf PDF
Addendum_#1_-_Clay_Co_FS_24_-_Plum_(2026_02-17)_.pdf PDF
Addendum_#1_-_Clay_Co_FS_24_-_Mech_(2026_02-17).pdf PDF
Addendum_#1_-_Clay_Co_FS_24_-_FP_(2026_02-17).pdf PDF
Addendum_#1_-_Clay_Co_FS_24_-_Civil_(2026_02-17)_.pdf PDF
Addendum_#1_-_Clay_Co_FS24_-_Struct_(2026_02-17).pdf PDF
Addendum_#1_-_Clay_Co_FS24_-_Landscape_(2026_02-17).pdf PDF
Addendum_#1_-_Clay_Co_FS24_-_Elec_(2026_02-17).pdf PDF
Construction_of_Clay_County_Fire_Station_No._24.pdf PDF
Standard_Protection_Measures-Eastern_Indigo_Snake.pdf PDF
Indigo_Snake_Poster.pdf PDF
Clay_Co_Fire_Station_24_(2026_01-02)_Specifications-Bid_Set.pdf PDF
Clay_Co_FS24_AV_Documents_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Purvis_Documents_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Plumb_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Mech_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_FP_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Elec_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Arch_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Landscape_Arch_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Civil_(2026_01-02)_Bid_Set.pdf PDF
Owner_Direct_Purchase_Program.pdf PDF
Appendix_II_for_2_CFR_Part_200.pdf PDF
FEMA_Field_Manual.pdf PDF
Subgrant-Agreement-226-SR-DR-4283-Executed-Funding-Agreement-Clay-County-460634-53096.pdf PDF
W-9_(2024).pdf PDF
Certificate_of_final_payment.pdf PDF
Certificate_of_partial_payment.pdf PDF
Chapter_8_Section_I.pdf PDF
EFT_FORM.pdf PDF
Warranty_Letter_.pdf PDF
Performance_&_Paymt_Bond.doc DOC document
Show all 47

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL NOTES:

1. GENERAL INFORMATION

3. EARTHWORK/FOUNDATION NOTES

6. REINFORCING STEEL

5. CONCRETE MASONRY

2. DESIGN CRITERIA

4. CONCRETE

1. THE STRUCTURAL ENGINEER SHALL NOT HAVE CONTROL OR BE RESPONSIBLE FOR THE CONSTRUCTION MEANS AND METHOD, TECHNIQUES, PROCEDURES OR SEQUENCES OR THE ACTS OF OMISSIONS OF THE CONTRACTOR OR ANY OTHER PERSONS PERFORMING THE WORK OR FOR THE FAILURE FOR ANY OF THEM TO CONSTRUCT THE WORK IN ACCORDANCE WITH THE

CONTRACT DOCUMENTS.

2. IF THE DRAWINGS AND SPECIFICATIONS ARE IN CONFLICT, THE MORE STRINGENT RESTRICTIONS AND REQUIREMENTS SHALL

GOVERN.

3. PLAN NOTES, DETAILS AND SECTIONS SHALL TAKE PRECEDENCE OVER GENERAL STRUCTURAL NOTES. TYPICAL DETAILS AND

SECTIONS NOT CUT ON THE PLANS SHALL APPLY UNLESS NOTED OTHERWISE.

4. REFER TO ARCHITECTURAL DRAWINGS FOR DIMENSIONS NOT SHOWN ON THE STRUCTURAL DRAWINGS.

5. CONTRACTORS ARE REQUIRED TO COORDINATE THEIR RESPECTIVE WORK WITH ALL OTHER DISCIPLINES TO AVOID ANY CONFLICTS DURING CONSTRUCTION. IT IS THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE THE STRUCTURAL DRAWINGS

WITH ALL OTHER CONSTRUCTION DOCUMENTS.

6. LOCATION, SIZES AND QUANTITY OF ALL OPENINGS MAY NOT BE COMPLETELY INDICATED ON THE STRUCTURAL DRAWINGS.

CONTRACTOR IS RESPONSIBLE TO COORDINATE ALL OPENINGS WITH ALL OTHER DISCIPLINES PRIOR TO ANY FABRICATION.

7. CONTRACTORS ARE REQUIRED TO VERIFY EXISTING CONDITIONS PRIOR TO ANY FABRICATION OR CONSTRUCTION. IF EXISTING CONDITIONS ARE DIFFERENT THAN SHOWN, NOTIFY A/E IMMEDIATELY FOR MODIFICATIONS TO THE DRAWINGS.

8. THE CONTRACT DOCUMENTS REPRESENT THE FINISHED STRUCTURE AND DO NOT INDICATE THE METHOD OF CONSTRUCTION. THE CONTRACTOR SHALL PROVIDE ALL MEASURES NECESSARY TO PROTECT THE STRUCTURE DURING CONSTRUCTION. SUCH MEASURES SHALL INCLUDE, BUT NOT LIMITED TO, BRACING, SHORING, UNDERPINNING, ETC. THE A/E IS NOT RESPONSIBLE FOR THE CONTRACTOR'S MEANS, METHODS, TECHNIQUES,SEQUENCES OR SAFETY PROCEDURES DURING CONSTRUCTION.

9. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL TEMPORARY BRACING THAT IS REQUIRED DURING CONSTRUCTION TO KEEP THE STRUCTURE SAFE AND PLUMB UNTIL THE ENTIRE STRUCTURE IS COMPLETE. ANY BRACING INDICATED OR CALLED FOR ON

THESE DRAWINGS ARE DESIGNED FOR THE FINAL AND COMPLETED STRUCTURE ONLY.

10. GENERAL CONTRACTOR MUST REVIEW AND APPROVE SHOP DRAWINGS PRIOR TO SUBMITTAL TO ARCHITECT/ENGINEER.

1. BUILDING CODE: THE FLORIDA BUILDING CODE 2023, 8TH EDITION.

2. DESIGN CODES: (LATEST EDITION, U.O.N.):

- MINIMUM DESIGN LOADS FOR BUILDINGS AND OTHER STRUCTURES (ASCE 7-22)

- BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES (TMS 402-16)

- SPECIFICATION FOR MASONRY STRUCTURES (TMS 602-16)

- SPECIFICATIONS FOR STRUCTURAL STEEL BUILDINGS (ANSI/AISC 360-16)

- NATIONAL DESIGN SPECIFICATION FOR WOOD CONSTRUCTION (AFPA / AF&PA NDS-2018)

- AMERICAN CONCRETE INSTITUTE (ACI 318-19)

- CONCRETE REINFORCING STEEL INSTITUTE (CRSI)

- STRUCTURAL WELDING CODE (D1.1-2020)

3. DESIGN LOAD CRITERIA:

GRAVITY LOADS:

- DEAD LOADS ROOF:

1. TOTAL SYSTEM .................................................................................................................. 20 PSF

- LIVE LOAD ROOF:....................................................................................................................... 20 PSF

- DEAD LOADS FLOOR:

1. SUPER IMPOSED................................................................................................................. 100 PSF

WIND LOAD CRITERIA:

- ULTIMATE DESIGN WIND SPEED ......................................................: Vult = 143 MPH (3 SECOND GUST)

- NOMINAL DESIGN WIND SPEED .......................................................: Vasd = 111 MPH

- RISK CATEGORY ..................................................................................: IV

- ENCLOSURE CLASSIFICATION ...........................................................: ENCLOSED

- WIND EXPOSURE CATEGORY ............................................................: C

- INTERNAL PRESSURE COEFFICIENT .................................................: ± 0.18

REFER TO SHEET S-004 FOR COMPONENTS AND CLADDING TABLES.

1. ALL CONCRETE, UNLESS OTHERWISE NOTED IN SCHEDULES OR DETAILS, SHALL HAVE A MINIMUM 28 DAY CONCRETE COMPRESSIVE STRENGTH OF 3000 PSI.

ALL CONCRETE SHALL BE NORMAL WEIGHT (145 PCF).

2. ALL CONCRETE EXPOSED TO THE WEATHER SHALL BE AIR-ENTRAINED. FOR SURFACE FINISHES AND OTHER REQUIREMENTS, REFER TO THE CONCRETE

SPECIFICATIONS.

3. DETAILS OF FABRICATION OF REINFORCEMENT, HANDLING AND PLACEMENT OF THE CONCRETE, CONSTRUCTION OF FORMS AND PLACEMENT OF REINFORCEMENT, NOT OTHERWISE COVERED BY THE PLANS AND SPECIFICATIONS, SHALL COMPLY WITH THE LATEST EDITION OF THE A.C.I. CODE AND

C.R.S.I.REQUIREMENTS.

4. PROVIDE 3/4" CHAMFERS ON ALL EXPOSED EDGES OF CONCRETE AND THE EXPOSED CORNERS OF BEAMS, GIRDERS AND COLUMNS UNLESS OTHERWISE

SHOWN OR NOTED. SEE ARCHITECTURAL DRAWINGS FOR ADDITIONAL DETAILS.

5. ALL MISCELLANEOUS ITEMS TO BE INSTALLED IN ANY CONCRETE WORK, SUCH AS PIPES, ELECTRICAL CONDUITS, DOVETAIL ANCHOR SLOTS, RELETS, ETC., SHALL BE PROPERLY LOCATED, INSTALLED AND CHECKED PRIOR TO PLACEMENT OF CONCRETE. REFER TO ARCHITECTURAL AND MEP DRAWINGS FOR THE EXACT EXTENT AND LOCATION OF THESE ITEMS THAT ARE NOT SPECIFICALLY SHOWN ON THE STRUCTURAL DRAWINGS.

6. PROVIDE SLEEVES FOR ALL PIPE AND CONDUIT PENETRATIONS IN FOUNDATION WALLS, GRADE BEAMS, WALL FOOTINGS AND TRENCH FOOTINGS TO TOTALLY

SEPARATE THE PIPES FROM THE CONCRETE.

7. THE CONTRACTOR SHALL CONSULT WITH THE ENGINEER BEFORE STARTING CONCRETE WORK TO ESTABLISH A SATISFACTORY PLACING SCHEDULE AND TO DETERMINE THE LOCATION OF CONSTRUCTION JOINTS SO AS TO MINIMIZE THE EFFECTS OF SHRINKAGE.

8. NO HORIZONTAL CONSTRUCTION JOINTS SHALL BE MADE IN CONCRETE WALLS, FOOTINGS, BEAMS OR SLABS UNLESS SHOWN OR NOTED IN THE CONTRACT DRAWINGS. VERTICAL JOINTS ARE PERMITTED IN CONCRETE SLABS, WALLS, WALL FOOTINGS, TRENCH FOOTINGS AND GRADE BEAMS. REFER TO TYPICAL

DETAILS.

9. ALL CONSTRUCTION JOINTS IN CONCRETE WALLS, FOOTINGS, BEAMS OR SLABS SHALL BE PROVIDED WITH A KEY WAY. THE SURFACE OF THE CONCRETE SHALL BE THOROUGHLY CLEANED AND ALL LATIANCE REMOVED. IN ADDITION, THE JOINT SHALL BE THOROUGHLY WETTED AND SLUSHED WITH A COAT OF

CEMENT GROUT OR A BONDING AGENT IMMEDIATELY BEFORE PLACING CONCRETE.

10. CONTROL JOINTS, IF NOT SHOWN ON DRAWINGS, SHALL BE PROVIDED IN ALL SLABS-ON-GRADE THAT ARE EXPOSED OR THAT SUPPORT BRITTLE FINISHES SUCH AS CERAMIC TILE OR TERRAZZO. JOINTS SHALL BE LOCATED ON EACH COLUMN LINE AND NOT TO EXCEED 15' IN EITHER DIRECTION U.O.N. SEE TYPICAL

SLAB-ON-GRADE DETAILS.

11. THE SAW CUTTING OF CONTROL JOINTS IN A SLAB-ON-GRADE MAY BEGIN WHEN THE CUTTING ACTION WILL NOT TEAR, ABRADE, OR OTHERWISE DAMAGE THE SURFACE AND BEFORE THE CONCRETE DEVELOPS RANDOM SHRINKAGE CRACKING. SAW CUTTING MAY BEGIN AND FINISH WITHIN 4 TO 12 HOURS AFTER

SURFACE FINISHING IS COMPLETE.

12. REFER TO CONCRETE SPECIFICATIONS FOR FLOOR FLATNESS REQUIREMENTS AT THE SLAB-ON-GRADE.

13. MAINTAIN A MAXIMUM SLOPE OF 1 VERTICAL TO 2 HORIZONTAL BETWEEN BEARING ELEVATIONS OF ADJACENT FOOTINGS TO AVOID UNDERMINING

FOUNDATIONS UNLESS NOTED OTHERWISE IN PLANS.

14. SET ANCHOR BOLTS WITH 3/4" THICK PLYWOOD TEMPLATES OR 1/4" THICK STEEL PLATE TEMPLATES AND BRACE AGAINST DISPLACEMENT.

1. ALL MASONRY CONSTRUCTION SHALL COMPLY WITH "TMS 402/602-16 BUILDING CODE REQUIREMENTS FOR MASONRY STRUCTURES", LATEST EDITION.

2. CONCRETE MASONRY UNITS SHALL BE ASTM C 90, HOLLOW LOAD BEARING UNITS, TYPE 1, NORMAL WEIGHT, WITH A MINIMUM COMPRESSIVE STRENGTH OF 2,000 PSI (f'm = 2,000 PSI).

3. GROUT SHALL CONFORM TO ASTM C476 WITH A MINIMUM 28 DAY COMPRESSIVE STRENGTH OF 2,000 PSI PER ASTM C1019. GROUT SHALL BE MIXED TO

PROVIDE A SLUMP BETWEEN 8" TO 11".

4. MORTAR SHALL CONFORM TO ASTM C270 TYPE M OR S.

5. LAP VERTICAL BARS MINIMUM OF 48 BAR DIAMETERS WITH WIRE TIES.

6. GROUT ALL CELLS CONTAINING VERTICAL REINFORCEMENT IN 4'-0" LIFTS MAXIMUM. DO NOT BEGIN PLACEMENT OF GROUT UNTIL ALIGNMENT OF CELLS ARE

INSPECTED AND APPROVED.

7. ALL CELLS SHALL BE FULLY GROUTED WHERE VERTICAL REINFORCEMENT IS INDICATE ON THESE DRAWINGS.

8. FILL ALL CELLS BELOW FINISHED GRADE.

9. PROVIDE #9 GALV. HORIZONTAL JOINT REINFORCEMENT IN WALLS AT 16"O.C. VERTICALLY, UNLESS NOTED OTHERWISE. PROVIDE HORIZONTAL JOINT REINFORCEMENT IN BOND BEAMS AT 8"O.C. VERTICALLY. LAP JOINT REINFORCEMENT @ 12"O.C. MINIMUM.

10. PROVIDE HORIZONTAL JOINT REINFORCEMENT AT 32"O.C. ACROSS VERTICAL CONTROL JOINTS IN WALLS AT 16"O.C. AND ACROSS VERTICAL CONTROL JOINTS IN BOND BEAMS. TOP AND BOTTOM REINFORCEMENT IN SPANDREL BEAMS SHALL BE CONTINUOUS ACROSS CONTROL JOINTS.

11. PROVIDE 8"x16" BOND BEAM @ TOP OF WALLS. REINFORCE BOND BEAM WITH (2) #5 PER 8" OF DEPTH U.O.N.

12. PROVIDE (1) #5 BAR VERTICAL MINIMUM AT ALL CORNERS, INTERSECTIONS AND EACH SIDE OF CONTROL JOINTS.

13. PROVIDE (2) #5 BARS VERTICAL AT 8"O.C. AT END WALLS. PROVIDE #5 @ 48"O.C. MINIMUM VERTICAL REINFORCEMENT, TYPICAL U.O.N. ON PLAN.

14. PROVIDE (2) #5 BAR VERTICAL MINIMUM EACH SIDE OF OPENINGS.

15. ALL REINFORCED HOLLOW UNIT MASONRY SHALL BE BUILT TO PRESERVE THE UNOBSTRUCTED VERTICAL CONTINUITY OF THE CELLS TO BE FILLED. WALLS AND CROSS WEBS FORMING SUCH CELLS TO BE FILLED SHALL BE FULL-BEDDED IN MORTAR TO PREVENT LEAKAGE OF GROUT. ALL HEAD (OR END) JOINTS SHALL BE SOLIDLY FILLED WITH MORTAR FOR A DISTANCE IN FROM THE FACE OF THE WALL OR UNIT NOT LESS THAN THE THICKNESS OF THE LONGITUDINAL FACE SHELLS. BOND SHALL BE PROVIDED BY LAPPING UNITS IN SUCCESSIVE VERTICAL COURSES OR BY EQUIVALENT MECHANICAL ANCHORAGE.

16. VERTICAL CELLS TO BE FILLED SHALL HAVE VERTICAL ALIGNMENT SUFFICIENT TO MAINTAIN A CLEAR, UNOBSTRUCTED, CONTINUOUS, VERTICAL CELL

MEASURING NOT LESS THAN 3" AND HAVING A CLEAR AREA OF 10 SQUARE INCHES.

17 .VERTICAL REINFORCEMENT SHALL BE HELD IN POSITION AT TOP AND BOTTOM AND AT INTERVALS NOT EXCEEDING 10 FEET.

18. WHEN THE GROUTING IS STOPPED FOR ONE HOUR OR LONGER, HORIZONTAL CONSTRUCTION JOINTS SHALL BE FORMED BY STOPPING THE POUR OF

GROUT NOT LESS THAN 1/2" BELOW THE TOP OF THE UPPERMOST UNIT GROUTED.

19. WHERE LINTELS BEAR ON MASONRY WALLS, THEY SHALL BEAR ON EITHER A BOND BEAM COURSE OR CORES GROUTED SOLID. ALL LINTELS SHALL HAVE AT

LEAST 8" OF BEARING AT EACH END UNLESS NOTED OTHERWISE.

20. ALL GROUT PLACED SHALL BE VIBRATED BY MECHANICAL VIBRATORS.

21. PROVIDE CONTROL JOINTS IN MASONRY WALLS AT A MAXIMUM OF 25'-0". COORDINATE LOCATION WITH ARCHITECTURAL DRAWINGS.

1. ALL REINFORCING STEEL SHALL BE DETAILED AND PLACED IN ACCORDANCE WITH THE LATEST EDITION OF ACI 315, ACI 318, AND CRSI.

2. REINFORCEMENT SHALL HAVE DEFORMED SURFACES IN ACCORDANCE WITH ASTM A615 WITH MINIMUM YIELD STRENGTH OF 60,000 PSI.

3. WELDED WIRE FABRIC SHALL BE SMOOTH CONFORMING TO ASTM A185.

4. ALL REINFORCING STEEL SHALL BE HELD SECURELY IN POSITION WITH STANDARD ACCESSORIES IN CONFORMANCE WITH CRSI MANUAL

OF STANDARD PRACTICE.

5. PROVIDE CORNER BARS AT ALL WALL CORNERS AND INTERSECTIONS PER TYPICAL DETAILS.

6. REINFORCING STEEL SHALL HAVE THE FOLLOWING CONCRETE PROTECTION (CLEAR COVER) UNLESS OTHERWISE NOTED:

- SURFACES NOT FORMED AND IN CONTACT WITH SOIL ...............: 3"

- FORMED SURFACES IN CONTACT WITH SOIL OR WEATHER .........: 2"

- BEAMS, GIRDERS AND COLUMNS .................................................: 1 1/2"

- WALLS AND JOISTS .......................................................................: 3/4"

- SLABS ON GROUND ......................................................................: 2" FROM TOP

7. CONTINUOUS REINFORCING STEEL IN CONCRETE SHALL BE LAP SPLICED PER CONCRETE LAP TABLE, CLASS "B", OR MASONRY LAP

TABLE. TYP. U.O.N., WWF WIRE SPLICE SHALL BE ONE FULL MESH SPACING + 6".

8. OPENINGS THROUGH CONCRETE WALLS, SLABS OR OTHER STRUCTURAL ELEMENTS NOT DETAILED ON THE STRUCTURAL DRAWINGS MUST BE LOCATED AND SHOWN ON THE APPLICABLE REINFORCING STEEL SHOP DRAWINGS. THE FINAL LOCATION OF ALL OPENINGS

MUST BE REVIEWED BY THE A/E BEFORE THE CONCRETE IS POURED.

9. WELDED WIRE FABRIC IN THE CONCRETE SLAB-ON-GRADE SHALL BE SUPPORTED TO PROVIDE REQUIRED COVER/PLACEMENT DEPTH;

AND PREVENT DISPLACEMENT DURING CONCRETE PLACEMENT OPERATIONS.

10. ALL HOOKS IN REINFORCING BARS SHALL BE AN ACI STANDARD HOOK, U.O.N.

11. AT CHANGE IN DIRECTION OF CONCRETE WALLS, BEAMS AND STRIP FOOTINGS PROVIDE CORNER BARS OF SAME SIZE AND SPACING AS

HORIZONTAL REINFORCING.

12. EPOXY ADHESIVE ANCHORS SHALL BE INSTALLED WITH HILTI HIT HY 500 V3 UNLESS OTHERWISE NOTED ON PLANS AND INSTALLED

ACCORDING TO MANUFACTURER'S RECOMMENDATIONS BY SIMPSON OR APPROVED EQUAL.

13. REINFORCING STEEL SHOP DRAWINGS SHALL BE SUBMITTED TO ENGINEER FOR APPROVAL PRIOR TO FABRICATION. CONTRACTOR SHALL CAREFULLY CHECK AND "APPROVED" BEFORE STAMP SUBMITTING TO THE EOR. NO SPLICES OR OTHER DETAILS ARE TO BE

ADDED WITHOUT SUBMITTAL.

7. STRUCTURAL STEEL

1. DETAILS FOR DESIGN, FABRICATION AND ERECTION OF ALL STRUCTURAL STEEL SHALL BE IN ACCORDANCE WITH THE LATEST A.I.S.C.

STANDARDS UNLESS OTHERWISE NOTED OR SPECIFIED.

2. ALL STRUCTURAL STEEL SHALL CONFORM TO THE FOLLOWING U.O.N. ON THE STRUCTURAL DRAWINGS:

-WIDE FLANGE SHAPES ............................... ASTM A572 OR ASTM A992 (Fy =50 KSI)

-CHANNELS, ANGLES, PLATES, BARS ......... ASTM A36 (Fy = 36 KSI) -RECTANGULAR TUBES (HSS) ..................... ASTM A500 GRADE B (Fy = 46 KSI) -STRUCTURAL PIPE ..................................... ASTM A53 GRADE B (Fy = 35 KSI)

3. ALL STRUCTURAL BOLTS (INCLUDING WASHERS AND NUTS) SHALL CONFORM TO THE REQUIREMENTS OF ASTM A325 OR A490. ALL BOLTS SHALL BE TIGHTENED TO THE SNUG TIGHT CONDITION U.O.N. BOLTING OF STRUCTURAL STEEL SHALL CONFORM TO THE PROVISIONS OF RCSC "SPECIFICATIONS" FOR STRUCTURAL JOINTS USING ASTM A325 AND A490 BOLTS.

4. MINIMUM SIZE OF BOLTS SHALL BE 3/4" DIAMETER, AND EACH CONNECTION SHALL HAVE A MINIMUM OF 2 BOLTS WITH ONE

HARDENED WASHER PER BOLT.

5. ANCHOR BOLTS SHALL CONFORM TO ASTM F-1554, GRADE 36, AS NOTED ON THE DRAWINGS. REFER TO TYPICAL DETAIL FOR SIZE

AND LENGTH.

6. PERMANENT MACHINE BOLTS, USING AN APPROVED TYPE OF SELF ANCHORING HEX NUT, MAY BE USED FOR SUCH MINOR

CONNECTIONS AS SHELF ANGLES, CLOSURES, ETC.

7. EXPANSION BOLTS SHALL BE A MINIMUM OF 3/4" DIAMETER (HILTI KWIK BOLT II OR APPROVED EQUAL) WITH A MINIMUM EMBEDMENT

OF 31/4" INTO CONCRETE AND 51/4" INTO GROUT FILLED CONCRETE MASONRY UNITS.

8. EPOXY ANCHOR BOLTS SHALL BE A MINIMUM OF HILTI HIT HY 500 V3 (OR APPROVED EQUAL). MINIMUM EMBEDMENT SHALL BE 12" TIMES BAR DIAMETER U.O.N. FOLLOW ALL WRITTEN MANUFACTURER'S INSTRUCTIONS FOR INSTALLATION.

9. WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN WELDING SOCIETY'S (AWS) STRUCTURAL

WELDING CODES. ALL WELDING SHALL BE PERFORMED BY PREQUALIFIED WELDERS.

10. WELDED CONNECTIONS FOR STEEL MEETING ASTM A992 OR A572 SHALL BE MADE WITH E70XX LOW HYDROGEN ELECTRODES.

OTHER WELDED CONNECTIONS TO BE MADE WITH REGULAR E70XX ELECTRODES.

11. WELDS NOT OTHERWISE NOTED ON DRAWINGS SHALL BE CONTINUOUS FILLET WELDS. THE MINIMUM SIZE SHALL BE 1/4", (MINIMUM

2"-12") OR AS REQUIRED BY THE AISC SPECIFICATIONS, WHICHEVER IS LARGER.

12. MINIMUM THICKNESS OF ALL CONNECTION MATERIAL SHALL BE 5/16".

13. UNLESS NOTED OTHERWISE, ALL SIMPLE BEAM SHEAR CONNECTIONS SHALL BE MADE USING DOUBLE ANGLE CONNECTIONS.

CONNECTIONS SHALL BE HIGH STRENGTH BOLT BEARING TYPE WITH THREADED PARTS INCLUDED IN THE SHEAR PLANE. ALL CONNECTIONS, UNLESS FULLY DETAILED ON THE STRUCTURAL DRAWINGS, SHALL BE DESIGNED AND DETAILED BY THE STRUCTURAL STEEL FABRICATOR TO MEET BOTH AISC AND OSHA REQUIREMENTS. REFER TO TYPICAL DETAILS FOR TYPE OF SIMPLE BEAM

CONNECTION AND MINIMUM BOLT REQUIREMENTS.

14. PROVIDE TEMPORARY ERECTION BRACING OF THE STRUCTURE UNTIL ALL PERMANENT LATERAL SUPPORT IS IN PLACE. FIELD PAINT, WHERE APPLICABLE, ALL FIELD WELDS, ABRASIONS, RUST SPOTS AND FIELD BOLTS ON STRUCTURAL STEEL, JOISTS AND

DECKING AFTER ERECTION.

15. ALL EDGE ANGLES OR BENT PLATES SHALL BE FIELD APPLIED TO THE BEAMS WITH ±1/8" HORIZONTAL AND VERTICAL TOLERANCE TO

FACILITATE OTHER INSTALLATIONS.

16. REFER TO PROJECT SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS FOR ARCHITECTURALLY EXPOSED STEEL.

17. ALL INTERIOR & EXTERIOR EXPOSED STEEL SHALL RECEIVE ONE SHOP COAT OF RED OXIDE PRIMER. INTERIOR STEEL BEAMS, COLUMNS, ANGLES ETC. ARE REQUIRED TO BE SHOP PRIMED PRIOR TO PAINTING EXPOSED STEEL.

1. BUILDING FOUNDATION DESIGN BASED ON NET ALLOWABLE SOIL BEARING PRESSURE OF 2,500 PSF FOR COLUMN SPREAD

FOOTINGS AND 2,000 PSI FOR CONTINUOUS WALL FOOTINGS.

2. BUILDING FOUNDATION SHALL BE PLACED ON FIRM, UNDISTURBED NATURAL SOILS OR ON ENGINEERED FILL MATERIAL. FOR AREAS REQUIRING ENGINEERED FILL, THIS MATERIAL SHALL CONSIST OF CLEAN GRANULAR FILL COMPACTED AND PLACED IN LIFTS AS RECOMMENDED BY THE SOILS ENGINEER ON SITE. SOIL BEARING PRESSURE OF ENGINEERED FILL TO BE FIELD VERIFIED

BY THE SOILS ENGINEER ON SITE PRIOR TO CONSTRUCTION.

3. SUBBASE MATERIAL UNDER SLABS-ON-GRADE TO BE CLEAN GRANULAR FILL COMPACTED AS RECOMMENDED BY THE SOILS

ENGINEER ON SITE.

4. BACKFILL AGAINST GRADE BEAMS AND SITE WALLS SHALL BE PLACED EVENLY ON BOTH SIDES.

5. UNDERCUTTING OF THE SOIL FOR FOUNDATION AND/OR PLACEMENT MAY BE REQUIRED. THE STRUCTURAL DRAWINGS MAY NOT INDICATE THE ENTIRE SCOPE OF UNDERCUTTING, FILL, BAD SOIL OR ROCK REMOVAL THAT MAY BE REQUIRED TO ATTAIN THE DESIGN SOIL BEARING PRESSURES. IT IS THE CONTRACTOR'S RESPONSIBILITY, BEFORE BIDDING, TO ASSESS THE EXTENT OF

EXCAVATION AND COMPACTION THAT MAY BE REQUIRED TO MEET THE DESIGN CRITERIA.

6. IF DEWATERING IS REQUIRED, SUMPS SHALL NOT BE PLACED WITHIN THE FOUNDATION EXCAVATION.

7. REFER TO GEO-TECHNICAL REPORT AS PREPARED BY TERRACON, PROJECT No. EQ225049, DATED JANUARY 27, 2023. FOR ADDITIONAL FOUNDATION REQUIREMENTS. IF CONFLICT BETWEEN EOR AND GEO-TECHNICAL INVESTIGATION REPORT MORE

STRINGENT CRITERIA SHALL BE FOLLOWED.

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M

GENERAL

NOTES

22003

06.23.2023

C O

UN

TY

R O

A D

S001

BID DOCUMENTS

C

LA

Y C

O

UN

TY

C

LA

Y C

O F

IR

E

ST

A

TIO

N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

MEP ENGINEER

POWELL & HINKLE

ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FL 32073

CIVIL ENGINEER

GOODSON BERGEN &

ASSOC

11555 CENTRAL PARKWAY, SUITE 103

JACKSONVILLE, FL 32224

REVISIONS

# DATE DESCRIPTION

4 07/25/25 90% IRC REVIEW

: ABBREVIATIONS

12. ROOFING & WATERPROOFING

L - ANGLE

LG

LW

- LONG

- METAL

- PLATE

NTS

PLF

PSF

OC

OPNG

PART

PL

MTL

MIN

MISC

NIC

NS

MFR

MAT'L

MAX

MECH'L

MAS

MO

PCJ

- MATERIAL

- MINIMUM

- MECHANICAL

- MAXIMUM

- MASONRY

- NEAR SIDE

- ON CENTER

- OPENING

- PARTITION

- MANUFACTURER

- MASONRY OPENING

- MISCELLANEOUS

- NOT TO SCALE

- NOT IN CONTRACT

- POUNDS PER LINEAR FOOT

- POUNDS PER SQUARE FOOT

- PRECAST CONCRETE JOIST

- LONG WAY

REM

- SLOPE

- ROOM

- SIMILAR

- SPIRAL

- STEEL

SW

STL

STRUCT'L

SECT

SIM

STD

SQ

SP

SL

REQ'D

REV

SCHED

RM

RO

- RISER/RADIUS

REINF

R

PT

- REMAINDER

- ROUGH OPENING

- REQUIRED

- STANDARD

- SECTION

- SQUARE

- SCHEDULE

- STRUCTURAL

- REVISED/REVISION

- SHEARWALL/SHORT WAY

- REINFORCING

- POST TENSIONED/PRESSURE TREATED

- WITH

WWF

UON

VERT

WP

W/

- TREAD/TRUSS

T/

TEMP

TYP

TR

T/O

TC

- UNLESS OTHERWISE NOTED

- VERTICAL

- WORK POINT

- WELDED WIRE FABRIC

- TIE COLUMN/TOP CHORD

- TOP OF

- THRU OUT

- TYPICAL

- TEMPERATURE

- TIE BEAMTB

- POUNDS PER SQUARE INCHPSI

- APPROXIMATELY

- ALTERNATE

- ANCHOR BOLTAB

APPROX

ALT

- BUILDING

- ARCHITECTURAL

- CONTRACTOR

- CONTINUOUS

- CONFIGURATION

- CONCRETE

- CENTERLINE

- CAST IN PLACE

CJ

CL

CIP

CMU

COL

CONC

CONFIG

CONT

CONTR

CLR

CTR - CENTER

- COLUMN

- CLEAR

BM

B/

ARCH'L

BLDG

BOTT

BRG

C/C

- BOTTOM

- BEAM

- BEARING

- BOTTOM OF

DET - DETAIL

- ELEVATION/ELEVATOR

- ELEVATION

- EXPANSION JOINT

- EACH FACE

- DIMENSION

- DIAMETER

- EXPANSION

- EACH WAYEW

FIN

EXIST

EXP

FLR - FLOOR

- FINISH

- EXISTING

DIA

DN

DIM

EA

EJ

EL

EF

DWG

ELEV

DR

EQ

- EACH

- EQUAL

- DRAWING

- DOOR/DRAIN

- DOWN

EE - EACH END

- FAR SIDE

- INTERIOR

- INFORMATION

- ISOLATION JOINT

- HIGH POINT

- HORIZONTAL

- HOLLOW CORE

- GALVANIZED

HC

HP

IJ

HORIZ

INT

JT

KJ

INFO

- JOINT

FS

GA

FT

FOM

FTG

GALV

- GAGE

- FOOTING

- FOOT

HDG

- FOUNDATIONFND

DBL - DOUBLE

- FACE OF MASONRY

- CONSTRUCTION JOINT

- CONTROL JOINT

- CENTER TO CENTER

- CONCRETE MASONRY UNIT

- HOT DIPPED GALVANIZED

LP - LOW POINT

- ARCHITECTARCH

W/O - WITHOUT

TJ - TIE JOIST

- SLAB-ON-GRADESOG

JR - JAMB REINFORCING WD - WOOD

- HIP GIRDERHG

- GIRDER TRUSSGT

OH - OPPOSITE HAND

PART'L - PARTIAL

EOS - EDGE OF SLAB

BC - BOTTOM CHORD

PAF - POWDER ACTUATED FASTENERS

EXT - EXTERIOR

- HOLLOW CORE PLANKHCP

- ENGINEERENGR

- IRREGULARIRR

- HOOKHK

RQMTS - REQUIREMENTS

- REGULARREG

LLV - LONG LEG VERTICAL

LLH - LONG LEG HORIZONTAL

- HIGH STRENGTHHS

SS - STAINLESS STEEL

- GENERAL CONTRACTORGC

EOR - ENGINEER OF RECORD

KLF - KIPS PER LINEAR FOOT

KIP(s) - 1000 POUNDS K - KIP(s)

1. THE ARCHITECT SHALL BE RESPONSIBLE FOR THE DESIGN OF THE ROOF COVERING SYSTEM AND FLASHING AND VALLEY MATERIAL.

2. THE ARCHITECT SHALL BE RESPONSIBLE FOR THE DESIGN OF ALL WATERPROOFING AND FLASHING.

11. SUBMITTALS

CONTRACTOR SHALL SUBMIT THE FOLLOWING FOR APPROVAL PRIOR TO FABRICATION AND ERECTION:

1. CONCRETE MIX DESIGNS.

2. STEEL REINFORCEMENT SHOP DRAWINGS.

3. TESTING LAB RESULTS FOR SOIL DENSITY AND CONCRETE COMPRESSIVE STRENGTH.

4. MASONRY PRODUCT DATA AND REINFORCING.

5. STRUCTURAL STEEL ERECTION AND DETAIL SHOP DRAWINGS.

6. WOOD TRUSS LAYOUT AND CALCULATIONS, SIGNED AND SEALED BY SPECIALTY ENGINEER.

9. WOOD FRAMING

1. ALL WOOD MEMBERS EXPOSED TO EARTH OR IN CONTACT WITH CONCRETE MASONRY OR EARTH SHALL BE TREATED WITH A PRESERVATIVE

SUITABLE FOR THE SITE, AWPA UC2 MINIMUM AT TREATED MEMBER.

2. NAILS AND FASTENERS ARE REQUIRED TO BE HOT-DIPPED GALVANIZED AFTER FABRICATION MEETING ASTM A 153, CLASS C OR ASTM B695.

3. ALL EXPOSED EXTERIOR HARDWARE TO BE HOT-DIPPED GALVANIZED AFTER FABRICATION MEETING ASTM A 153, CLASS C OR ASTM B695.

4. ALL FRAMING CONNECTORS AND HARDWARE NOTED ON DRAWINGS SHALL BE MANUFACTURED BY SIMPSON STRONG TIE OR APPROVED EQUAL.

5. WOOD FRAMING SHALL BE IN ACCORDANCE WITH FBC EXCEPT AS NOTED WITHIN THESE PLANS.

6. ALL MANUFACTURED LUMBER SHALL BE PRESSURE TREATED TO A SERVICE LEVEL UC3A TREATMENT FOR EXTERIOR CONDITIONS, U.O.N.

7. PRE-FABRICATED WOOD TRUSSES SHALL COMPLY WITH NDS AND ANSI/TIP 1-02. THE DESIGN OF PRE-FABRICATED WOOD TRUSSES AND ASSOCIATED CONNECTIONS SHALL BE DESIGNED BY A SPECIALITY ENGINEER REGISTERED IN THE STATE OF FLORIDA. DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED FOR REVIEW AND APPROVAL AND BEAR THE SEAL AND SIGNATURE OF THE SPECIALTY ENGINEER. DESIGN CRITERIA SHALL BE CLEARLY LABELED WITH RATED LOAD CAPACITY OF ALL TRUSS TO TRUSS CONNECTOR, REACTIONS, SIZES OF ALL

MEMBERS, DEAD, LIVE AND WIND LOADINGS WITH SPECIFIED SPACING.

8. JOBSITE HANDLING AND ERECTION AND TEMPORARY TRUSS BRACING DURING INSTALLATION OF TRUSSES SHALL BE CLEARLY LABELED AND

COMPLY WITH TPI/WTCA BCSI 1.

9. PROVIDE CONTINUOUS LATERAL BOTTOM CHORD TRUSS BRACING W/ A MIN. OF SYP #2 2X4'S AT 4'-0" ON CENTER, ATTACH w/(3)-16d .148x31/4"

COMMONS EA.TRUSS MEMBER TYP. U.O.N.

10. ALL PRE-FABRICATED TRUSSES SHALL BE FASTENED TO THEIR SUPPORTING MEMBERS I.E. WALLS, BEAMS WITH CONNECTOR PER UPLIFT

INDICATED ON TRUSS DRAWINGS. SEE SCHEDULE FOR CONNECTOR VALUES.

11. PROVIDE SEAT PLATES AT ALL BEARING POINTS.

8. TREATED WOOD

1. LUMBER AND TIMBER SHALL CONFORM TO THE SOUTHERN PINE INSPECTION BUREAU "STANDARD GRADING RULES", CURRENT EDITION.

2. ALL LUMBER AND TIMBER SHALL BE DRESSED S4S AND GRADE STAMPED BY AN AGENCY CERTIFIED BY THE AMERICAN LUMBER STANDARDS COMMITTEE'S BOARD OF REVIEW AND MANUFACTURED IN ACCORDANCE WITH PS 20, LATEST REVISION. PROVIDE NOMINAL SIZES AS INDICATED ON DESIGN PLANS. WANES ARE NOT ACCEPTABLE IN EXPOSED MATERIAL.

3. ALL EXTERIOR WOOD, NO. 2 SOUTHERN YELLOW PINE K.D. AFTER TREATMENT. TREATMENT SHALL BE IN ACCORDANCE WITH AWPA STANDARDS FOR MCQ .40P/CF. FOR ABOVE GROUND, .60P/CF. FOR PERMANENT FOUNDATION USE.

4. CUT SURFACES OF TREATED WOOD SHALL BE TREATED WITH PRESERVATIVE IN ACCORDANCE WITH AWPA STANDARD M4. COPPER

NAPHTHENATE SOLUTION SHALL BE BRUSHED INTO ALL BOLT HOLES.

10. ROOF SHEATHING AND DIAPHRAGM ATTACHMENT

1. ROOF SHEATHING- USE A MINIMUM OF EXP. 1 APA RATED 5/8" THICK SHEATHING WITH A SPAN RATING NOT LESS THAN 32/16. ALL PANELS SHALL BE

CONTINUOUS OVER A MINIMUM OF 3 SUPPORTS. END JOINTS SHALL BE STAGGERED. TYPICAL U.O.N. ON PLAN.

2. ROOF ATTACHMENTS SHALL BE 6" ON CENTER SPACING AT PANEL EDGES AND 6" AT INTERMEDIATE SUPPORTS UTILIZING 8d RING-SHANK NAILS.

REDUCE NAIL SPACING TO 3" ON CENTER AROUND ALL OPENINGS. TYPICAL U.N.O. ON PLAN.

3. ALL ROOF DIAPHRAGMS SHALL BE BLOCKED (SYP#2 2X4 BLOCKING) 4'-0" FROM GABLED ENDS. TYPICAL U.N.O. ON PLAN. ROOF ATTACHMENTS SHALL BE 4" ON CENTER SPACING AT PANEL EDGES AND 6" ON CENTER SPACING AT INTERMEDIATE SUPPORTS AND BLOCKING UTILIZING 8d RING-SHANK

NAILS. REDUCE NAIL SPACING TO 3" ON CENTER AROUND ALL OPENINGS.

13. MASONRY CONSTRUCTION

DEFINITIONS:

1. GROUT POUR HEIGHT- THE TOTAL HEIGHT OF THE MASONRY TO BE GROUTED PRIOR TO ERECTION OF ADDITIONAL MASONRY.

2. GROUT POUR- CONSISTS OF ONE OR MORE GROUT LIFTS

3. GROUT LIFT- THE LAYER OF GROUT PLACED IN A SINGLE CONTINUOUS OPERATION AND IS LIMITED TO 8 FEET.

4. RODDING- THE ACT OF COMPACTING FRESHLY POURED CONCRETE OR GROUT IN ITS FORM BY FREEING THE MASS OF AIR POCKETS.

5. PUDDLING- THE PROCESS OF INDUCING COMPACTION OF GROUT BY USE OF A TAMPING ROD.

6. PUDDLE- THE ACT OF WORKING CONCRETE TO ELIMINATE HONEYCOMBS, AND IT PRODUCE A DENSER MASS.

7. PUDDLE STICK- A STICK OR ROD USED TO CONSOLIDATE GROUT BY HAND.

MASONRY CONSTRUCTION AND INSPECTION GUIDELINES:

1. LAY UP MASONRY IN RUNNING BOND FOR SIZES AND REINFORCING SEE PLANS AND ELEVATIONS.

2. FACE SHELLS OF BED JOINT SHALL BE MORTARED.

3. WEBS SHALL BE MORTARED AT CELLS TO BE GROUTED.

4. VERTICAL CELLS ARE TO BE ALIGNED WHERE THEY ARE TO BE GROUT FILLED UNLESS BOND IS SHIFTED DUE TO SITE CONDITIONS.

5. INSTALL HORIZONTAL JOINT REINFORCING AT 16" ON CENTER SPACING STARTING FIRST BLOCK ABOVE FOUNDATION, U.N.O.

6. MAINTAIN MIN. OF ½" COVER ON JOINT REINFORCING TO EXTERIOR AND REINFORCING SHALL BE EMBEDDED IN MORTAR.

7. GROUT SPACES BOTH VERTICAL AND HORIZONTAL ARE TO BE SUBSTANTIALLY FREE OF DROPPINGS, DEBRIS, LOOSE AGGREGATE AND ANY DELETERIOUS

TO MASONRY GROUT.

8. INSTALL REINFORCING IN GROUT CELLS PRIOR TO GROUTING.

9. GROUT SPACES ARE TO BE INSPECTED PRIOR TO PLACING GROUT.

10. FILL CELLS AS NOTED ON THE PLANS, ELEVATIONS AND DETAILS.

11. A REINFORCING BAR MAY BE USED TO ROD GROUT IN CELL, TO ENSURE THAT ARE NO VOIDS IN GROUT.

13. GROUT SHOULD SET IN APPROXIMATELY 90 MINUTES DEPENDING ON GROUT SLUMP AND WEATHER CONDITIONS.

14. DO NOT BEND OR MOVE REINFORCEMENT AFTER GROUT HAS SET.

15. FILL ALL CELLS SOLID BELOW FINISH FLOOR ELEVATION.

TOLERANCES:

1. CENTER REINFORCING:

a. CENTERLINE LOCATION SHOULD BE ½" OF CENTER OF MASONRY.

b. HORIZONTAL LOCATION SHALL BE WITHIN 2" OF THE CENTER OF THE CELL.

c. REINFORCING SHALL MAINTAIN POSITION WITHOUT BEING TIED.

d. DO NOT MOVE REINFORCING AFTER INITIAL SET OF GROUT.

2. REINFORCING AT EACH FACE:

a. MAINTAIN AT LEAST 1/4" CLEAR OF MASONRY FOR FINE GROUT AND ½"

b. REINFORCING SHALL BE PLACED 1" CLEAR TO THE SIDE OF THE DOWELS.

3. BOND BEAMS:

a. HORIZONTAL REINFORCING SHALL BE ¼" CLEAR OF MASONRY FOR FINE GROUT AND ½" COURSE GROUT.

b. KNOCK OUT WEB BLOCKS SHALL BE USED FOR BLOCK AT THE TOP AND/OR THE BOTTOM OF THE BOND BEAMS, DEPENDING ON THE LOCATION.

c. WIRE MESH OR SOME OTHER MEANS SHALL BE USED TO PREVENT GROUT FROM ESCAPING

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M

GENERAL

NOTES

22003

06.23.2023

C O

UN

TY

R O

A D

S002

BID DOCUMENTS

C

LA

Y C

O

UN

TY

C

LA

Y C

O F

IR

E

ST

A

TIO

N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

MEP ENGINEER

POWELL & HINKLE

ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FL 32073

CIVIL ENGINEER

GOODSON BERGEN &

ASSOC

11555 CENTRAL PARKWAY, SUITE 103

JACKSONVILLE, FL 32224

REVISIONS

1 11/03/23 PERMIT REV 1

4" M

IN

C

O V

E R

T/CONC.

COL. BEARING

BASE PLATE W/

OVERSIZED HOLE, PER

SCHEDULE

ANCHOR ROD SIZE, SEE

COLUMN SCHEDULE

FULLY TIGHTENED

DOUBLE NUTS OR HEAVY

HEX BOLT HEAD

NOMINAL NON-SHRINK

GROUT THICKNESS PER

SCHEDULE

TYPICAL ANCHOR ROD ASSEMBLY

M

IN2"

MINIMUM ANCHOR ROD

PROJECTION ABOVE BASE

PLATE PER SCHEDULE

MINIMUM SPECIFIED

EMBEDMENT LENGTH,

SEE SCHEDULE.

BOTTOM PL WASHER

PER SCHEDULE

THREAD LENGTH

SQUARE OR ROUND PLATE

WASHER W/ STANDARD HOLE

SIZE AND THICKNESS PER

SCHEDULE

HEAVY HEX NUT

SETTING NUT AND PLATE

WASHER (1/2" MIN WASHER

THICKNESS) OR SHIM STACK

AT CONTRACTORS OPTION

BOTTOM OF

FOOTING OR

MAT

FOUNDATION

ANCHOR ROD SCHEDULE

ANCHOR

ROD SIZE

BASE PLATE

HOLE DIA.

MIN.

WASHER

SIZE

MIN.

WASHER

THICK

MIN. PROJ.

ABOVE

BASE

PLATE

NOMINAL

GROUT

THICKNESS

3/4"ø 1 5/16"

1"ø 1 13/16"

1 1/2"ø 2 5/16"

2"

3"

3 1/2"

1/4"

3/8"

1/2"

3"

3 1/2"

4"

2"

2"

3"

"A"

ANCHOR ROD ASSEMBLY NOTES:

1. ANCHOR ROD SHALL BE HEAVY HEX ASTM 1554 GRADE 36.

2. SEE COLUMN SCHEDULE AND BASE PLATE DETAILS FOR BASE PLATE AND ANCHOR ROD LAYOUT

PATTERNS, SIZES AND EMBEDMENTS.

3. REFER TO ANCHOR ROD SCHEDULE FOR ROD PROJECTIONS, WASHERS AND BASE PLATE HOLE

SIZES.

4. WHERE WELD 'A' IS NOT SCHEDULED, TACK WELD AS REQUIRED FOR ERECTION.

WELD "A"

SIZE

1/8"

3/16"

1/4"

B/COL.

SEE SCHEDULE

FOR WELD "A"

SIZE

SEE BASE

PLATE

DETAILS

MIN.

EMBED.

DEPTH

9"

12"

18"

TYPE "A"

GRID

G R

ID HSS COLUMN

BASE PLATE

2" , TYP.

EQUAL EQUAL

"C"

2"

TY

P.

EQ

U

AL

EQ

U

AL

"B

AISC MIN

TYPICAL

TYPE "B"

GRID

G R

ID

WF COLUMN

BASE PLATE

2" , TYP.

EQUAL EQUAL

"C"

2"

TY

P.

EQ

U

AL

EQ

U

AL

"B

AISC MIN

TYPICAL

TYPE 2 TYPE 3

TYPE 4 TYPE 5

1' - 4" 2' - 0"

2'-8". 3'-4".

SIZE OF BAR

REQUIRED

DEVELOPMENT LENGTH

STRAIGHT BARS

REQUIRED

DEVELOPMENT LENGTH

HOOKED BARS

#3 1'-4" 8 1/4" #4 1'-10" 11 1/2" #5 2'-4" 1'-3 1/4" #6 2'-9" 1'-4 1/2" #7 4'-0" 1'-7 1/4" #8 4'-7" 1'-10" #9 5'-2" 2'-0 3/4" #10 5'-10" 2'-4" #11 6'-6" 2'-7"

SIZE OF BAR. SPLICE (A) SPLICE (B)

#3 1'-1" 1'-5" #4 1'-6" 1'-11" #5 1'-10" 2'-4" #6 2'-2" 2'-10" #7 3'-2" 4'-1" #8 3'-9" 4'-11" #9 4'-8" 6'-1" #10 5'-7" 7'-3" #11 6'-7" 8'-7"

CONCRETE REINFORCING SPLICE

LENGTH SCHEDULE PER ACI 318

CONCRETE REINFORCING DEVELOPMENT

LENGTH SCHEDULE PER ACI 318

REINFORCING YEILD STRENGTH, Fy = 60 KSI CONCRETE COMPRESSIVE STRENGHT, F'c = 3,000 PSI

REINFORCING YEILD STRENGTH, Fy = 60 KSI CONCRETE COMPRESSIVE STRENGHT, F'c = 3,000 PSI

SCALE: = NTS

A4STEEL COLUMN BASE PLATE DETAIL

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M

SCHEDULES

22003

06.23.2023

C O

UN

TY

R O

A D

S003

BID DOCUMENTS

C

LA

Y C

O

UN

TY

C

LA

Y C

O F

IR

E

ST

A

TIO

N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

MEP ENGINEER

POWELL & HINKLE

ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FL 32073

CIVIL ENGINEER

GOODSON BERGEN &

ASSOC

11555 CENTRAL PARKWAY, SUITE 103

JACKSONVILLE, FL 32224

M4 8" x 16" (4) #5 #2 @ 8" 2 MASONRY

M3 DOUBLE 8" x 40" (10)#5 #2 @ 8" 5 MASONRY

M2 DOUBLE 8" x 32" (8) #5 #2 @ 8" 4 MASONRY

M1 8" x 24" (6) #5 #2 @ 8" 3 MASONRY

COLUMN ID. NO. COLUMN SIZE (WxD INCHES) VERTICAL REINFORCEMENT OR BASE PLATE COLUMN TIES OR CAP PLATE TYPE REMARKS

MASONRY COLUMN SCHEDULE

TD1.33 1'-4" x CONT. x 1'-4" (2) #5 CONT. BOTTOM MONOLITHIC w/ SLAB

TD1.0 1'-0" x CONT. x 1'-4" (2) #5 CONT. BOTTOM MONOLITHIC w/ SLAB

TD0.67 0'-8" x CONT. x 0'-8" (1) #5 CONT. BOTTOM MONOLITHIC w/ SLAB

F5.0 5'-0" x 5'-0" x 1'-4" (6) #5 CONT. EACH WAY, BOTTOM

RF5.0x15.0 5'-0" x 15'-0" x 2'-4" (5) #7 LONG WAY TOP AND BOTTOM, (14) #7 SHORT

WAY TOP AND BOTTOM (OUTER BARS IN OUTER... FOOTING NOT USED

CF2.5 2'-6" x CONT. x 1'-0" (3) #5 CONT. BOTTOM #4 @ 24"O.C. TRANSVERSE

CF2.0 2'-0" x CONT. x 1'-0" (3) #5 CONT. BOTTOM #4 @ 24"O.C. TRANSVERSE

CF1.67 1'-8" x CONT. x 1'-0" (2) #5 CONT. BOTTOM

MARK SIZE (WxLxD) REINFORCING REMARKS

FOOTING SCHEDULE

B-3 16'-0" 8" x 24" (2)#5 (2)#5 (2)#5 #3 @ 8"O.C. MASONRY BEAM

B-2 9'-4" 8" x 16" (2)#5 (2)#5 #3 @ 8"O.C. MASONRY BEAM

B-1 10'-8" 8" x 16" (2)#7 (2)#5 #3 @ 8"O.C. MASONRY BEAM

TB-6 10'-8" 8" x 24" (2)#5 (2)#5 - MASONRY TIE BEAM

TB-5 9'-4" 8" x 16" (2)#5 (2)#5 - MASONRY TIE BEAM

TB-4 19'-4" 8" x 16" (2)#5 (2)#5 - MASONRY TIE-BEAM

TB-3 19'-4" 12" x 16" (2)#5 (2)#5 - MASONRY TIE-BEAM

TB-2 10'-8" 12" x 16" (2)#5 (2)#5 - MASONRY TIE-BEAM

TB-1 10'-8" 8" x 16" (2)#5 (2)#5 - MASONRY TIE-BEAM

BOT... TOP "C" "E"

BEAM

MARK TOP OF BEAM ELEV. SIZE (W x D INCHES)

REINFORCING

#3 STIRRUPS REMARKS

MASONRY & CONCRETE BEAM SCHEDULE

C3 HSS 4x4x1/4 1/2" x 6 1/2" x 1'-0" (4) 3/4" A325 - TYPE C 1/4" SPACE BOLTS @ BEAM GAGE - SEE A3/S502

C2 W8x31 1" x 14" x 1'-2" 1" DIA. - TYPE B 1/2" NOT USED

C1 HSS 6x6x5/16 3/4" x 14" x 1'-2" 3/4" DIA. - TYPE A 1/4"

COLUMN MARK COLUMN TYPE BASE PLATE SIZE ANCHOR BOLT SIZE AND TYPE CAP PLATE SIZE REMARKS

STEEL COLUMN SCHEDULE

WF COLUMN

NOT USED

REVISIONS

# DATE DESCRIPTION

1 11/03/23 PERMIT REV 1

3 07/19/24 VE REV 1

WIND PRESSURE DIAGRAMS

TYPICAL GABLE ROOFS

REFER TO COMPONENTS AND CLADDING WIND

LOAD DESIGN PRESSURE SCHEDULE' ON THIS SHEET

a1 a1

PLAN VIEW

SIMPLIFIED TYPICAL FLAT ROOF

PLAN VIEW

(NOTE: DOES NOT APPLY @ ATTACHED CANOPIES)

SHORT DIRECTION

LO

N

G D

IR

EC

TI

O

N

TYPICAL WALLS

(GABLE AND FLAT ROOF)

a1 OR a2 a1 OR a2 a1 OR a2 a1 OR a2

1 2 2

"a 1"

O R

"a 2"

"a 1"

O R

"a 2"

"a1"OR"a2" "a1"OR"a2"

2"a 1"

"a 1" 3

PLAN VIEW

3 < 0 < 27 27 < 0 < 45

"a1" "a1"

"a1" "a1"

ZONE

10 S.F. OR LESS

50 S.F.

100 S.F.

500 OR LARGER

+44,-80

ROOF SURFACES VERTICAL SURFACE

+35,-52

+31,-40

EFFECTIVE

WIND AREA

10"/12" HIGH SLOPE ROOF ULTIMATE DESIGN PRESSURES (PSF)

FOR COMPONENTS AND CLADDING SURFACES:

1. "a1", = 4'-6" (TYP. AT ALL ROOF AREAS, UNO), "a2" = 6'-8" (4"/12" ROOF AREAS).

2. THE PROPOSED STRUCTURE IS LOCATED WITHIN A WIND BORNE DEBRIS AREA GLAZED OPENINGS SHALL BE MISSILE IMPACT RATED OR PROTECTED.

3. DESIGN PRESSURE VALUES FOR OTHER EFFECTIVE TRIBUTARY AREAS SHALL BE LINEARLY INTERPOLATEDBETWEEN VALUES SHOWN.

4. ULTIMATE DESIGN WIND LOADS PROVIDED SHALL BE USED WITH LOAD COMBINATIONS PER ASCE 7-22, CHAPTER 2.

5. DESIGN WIND PRESSURES PROVIDED TO BE USED FOR EXTERIOR COMPONENT AND CLADDING MATERIALS NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE PER SECTION 1603.1.4 OF THE 2018 IBC.

NOTES:

+28,-40

4 5

+48,-52

+43,-47

+42,-45

+36,-40

OVERHANG

10"/12" HIGH SLOPE ROOF NOMINAL DESIGN PRESSURES (PSF)

FOR COMPONENTS AND CLADDING SURFACES:

2" TO 4"/12" SLOPE ROOF ULTIMATE DESIGN PRESSURES (PSF)

FOR COMPONENTS AND CLADDING SURFACES:

2" TO 4"/12" SLOPE ROOF NOMINAL DESIGN PRESSURES (PSF)

FOR COMPONENTS AND CLADDING SURFACES:

ZONE

10 S.F. OR LESS

50 S.F.

100 S.F.

500 OR LARGER

ROOF SURFACES VERTICAL SURFACE

EFFECTIVE

WIND AREA

FLAT ROOF ULTIMATE DESIGN PRESSURES (PSF)

FOR COMPONENTS AND CLADDING SURFACES:

3 4 5

+41,-45

+37,-42

+35,-39

+31,-35

OVERHANG2

+19,-94

+16,-80

+16,-74

+16,-60

+19,-128

+16,-100

+16,-88

+16,-60

-122

-89

-75

-42

+41,-55

+37,-47

+35,-43

+31,-34

ZONE

10 S.F. OR LESS

50 S.F.

100 S.F.

500 OR LARGER

ROOF SURFACES VERTICAL SURFACE

EFFECTIVE

WIND AREA

FLAT ROOF NOMINAL DESIGN PRESSURES (PSF)

FOR COMPONENTS AND CLADDING SURFACES:

3 4 5

+25,-27

+23,-26

+21,-24

+19,-21

OVERHANG2

+11,-57

+10,-48

+10,-45

+10,-36

-74

-54

-45

-26

+11,-77

+10,-60

+10,-53

+10,-36

+25,-33

+23,-29

+21,-26

+19,-21

10 S.F. OR LESS

50 S.F.

100 S.F. LARGER

ROOF SURFACES

PRESSURES (NET)EFFECTIVE

WIND AREA

ATTACHED CANOPY ROOF ULTIMATE

DESIGN PRESSURES (PSF) FOR

COMPONENTS AND CLADDING SURFACES:

+37,-57

+30,-48

+27,-45

10 S.F. OR LESS

50 S.F.

100 S.F. LARGER

ROOF SURFACES

PRESSURES (NET)EFFECTIVE

WIND AREA

ATTACHED CANOPY ROOF NOMINAL DESIGN

PRESSURES (PSF) FOR COMPONENTS AND

CLADDING SURFACES:

+22,-35

+18,-29

+16,-27

2 3 1

-117

2 3

+44,-88

+35,-66

+31,-57

+28,-48

+44,-108

+35,-76

+31,-62

+28,-48

-84

-70

-65

-125

-98

-87

-73

-157

-115

-97

-73

+48,-64

+43,-54

+42,-50

+36,-40

ZONE

10 S.F. OR LESS

50 S.F.

100 S.F.

500 OR LARGER

+26,-48

ROOF SURFACES VERTICAL SURFACE

+21,-32

+19,-24

EFFECTIVE

WIND AREA

+17,-24

4 5

+29,-32

+26,-29

+26,-27

+22,-24

OVERHANG

2 3 1

-71

2 3

-51

-42

-39

-75

-59

-53

-44

-95

-69

-59

-44

+26,-53

+21,-40

+19,-35

+17,-29

+26,-65

+21,-46

+19,-38

+17,-29

+29,-39

+26,-33

+26,-30

+22,-24

ZONE

10 S.F. OR LESS

50 S.F.

100 S.F.

500 OR LARGER

+33,-92

ROOF SURFACES VERTICAL SURFACE

+26,-62

+23,-49

EFFECTIVE

WIND AREA

+21,-29

4 5

+50,-54

+45,-49

+42,-47

+37,-42

OVERHANG

2 3 1

-130

2 3

-95

-80

-55

-172

-124

-103

-76

-197

-139

-115

-109

+50,-67

+45,-56

+42,-52

+37,-42

ZONE

10 S.F. OR LESS

50 S.F.

100 S.F.

500 OR LARGER

+20,-56

ROOF SURFACES VERTICAL SURFACE

+16,-38

+14,-30

EFFECTIVE

WIND AREA

+13,-18

4 5

+30,-33

+27,-30

+26,-29

+23,-26

OVERHANG

2 3 1

-78

2 3

-57

-48

-33

-104

-75

-62

-46

-119

-84

-69

-66

+30,-41

+27,-34

+26,-32

+23,-26

+33,-121

+26,-83

+23,-66

+21,-50

+33,-159

+26,-106

+23,-83

+21,-83

+20,-73

+16,-50

+14,-40

+13,-30

+20,-96

+16,-64

+14,-50

+13,-50

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M

WIND

PRESSURE

DIAGRAMS

22003

06.23.2023

C O

UN

TY

R O

A D

S004

BID DOCUMENTS

C

LA

Y C

O

UN

TY

C

LA

Y C

O F

IR

E

ST

A

TIO

N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

MEP ENGINEER

POWELL & HINKLE

ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FL 32073

CIVIL ENGINEER

GOODSON BERGEN &

ASSOC

11555 CENTRAL PARKWAY, SUITE 103

JACKSONVILLE, FL 32224

REVISIONS

1. REFER TO ARCH. FLOOR PLAN FOR ALL OPENINGS, WALL LOCATIONS, DEPRESSED / SLOPING SLABS, ELEVATIONS AND DIMS.

2. REFER TO SHEETS S401, S402, S403 AND S404 FOR FOUNDATION SECTIONS AND DETAILS.

3. FOOTINGS & FOUNDATIONS SHALL BE IN ACCORDANCE WITH FBC CHAPTER 18 AND GEO-TECHNICAL INVESTIGATION REPORT. TOP OF

FOOTING ELEVATION -1'-4" U.N.O.

4. REFER TO S001, S002, S003 AND S004 FOR ADDITIONAL GENERAL NOTES AND DESIGN CRITERIA.

5. THE STRUCTURAL ENGINEER SHALL NOT HAVE CONTROL OR BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS TECHNIQUES, PROCEDURES OR SEQUENCE, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR OR ANY OTHER PERSONS PERFORMING THE WORK, OR THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.

6. DENOTES 8" OR 12" CMU WALL ON PLAN. PROVIDE VERTICAL REINFORCEMENT AS INDICATED ON PLAN IN GROUTED FILLED CELLS, GROUT ALL CELLS UP TO SLAB ON GRADE, TYP. U.O.N.

7. S.F. - DENOTES TYPICAL STEP FOOTING ON PLAN REFER TO DETAIL A4/S401

8. - DENOTES GROUT FILLED CELL WITH REINF., SEE PLAN FOR SIZE AND SPACING OF REINF., TYP.

9. PROVIDE (1)#5 x 3'-0" LONG BARS @ RE-ENTRY CORNERS, REFER TO DETAIL B3/S401.

10. CF2.5 STEM WALL FOOTING REINFORCEMENT IS CONTINUOUS THROUGH CANOPY FOUNDATION, WHERE REQUIRED.

COLUMN SYMBOLS

INDICATES COLUMN BELOW

INDICATES COLUMN THRU

INDICATES COLUMN ABOVE

4" CONCRETE SLAB ON GRADE w/ 6x6-W2.1-W2.1 W.W.R. OVER 10 MIL.

VAPOR BARRIER ON COMPACTED FILL.,

TYP. U.N.O. - T/SLAB EL. 0'-0"

8" CONCRETE SLAB ON GRADE w/

#5 @ 12"O.C. EACH WAY AT

MID- DEPTH, TYP.

8" CMU WALLS w/(1)#5 VERTICAL

REINF. @ 48"O.C. CENTERED IN

GROUT FILLED CELLS , TYP. U.O.N.

C1

12" WIDE CONCRETE

CURB w/ #4 @ 12" VERT.

AND HORZ. EACH FACE

58' - 0" OUT/OUT OF CMU

4' - 8" 14' - 0" 3' - 4" 14' - 0" 3' - 4" 14' - 0" 4' - 8"

16' - 8"9' - 0" 20' - 8" 9' - 0" 10' - 0"

48' - 8" OUT/OUT OF CMU

2' - 0"

14' - 0"

58' - 0" OUT/OUT OF CMU 21' - 4"2'-0".

14' - 0" 5' - 4"4' - 8"14' - 0"3' - 4"14' - 0"3' - 4"14' - 0"4' - 8"

79' - 4" OUT/OUT OF CMU

6'

8"

" O

U T/

O U

T O

F C

M U

26' - 8"16' - 4"6' - 0"16' - 4"

38' - 8" OUT/OUT OF CMU 10' - 0"

16' - 8"

/4

/4

2'

0"

9' - 0"

7'

4"

T/FTG.

EL. -2' - 0"

F5.0 FTG.

T/FTG.

EL. -2' - 0"

F5.0 FTG.

C F1

.6

CF1.67 CF1.67

CF1.67

CF1.67

CF2.0

CF2.0

CF2.0

CF2.0

CF1.67

CF1.67

CF1.67

CF1.67

CF1.67

CF1.67

CF1.67

C F1

.6

C F1

.6

C F1

.6

C F2

.0

C F1

.6

C F2

.0

C F2

.0

C F1

.6

C F1

.6

C F1

.6

CF1.67

C F1

.6

CF1.67

CF1.67

CF1.67

CF1.67

CF1.67

CF1.67

CF1.67

CF1.67

5' - 4"

21' - 4"

C.J.

C.J.

C.J.

C.J.

C.J.

C .J

C .J

C .J

C .J

C .J

C.J.

C.J.

C.J.

C.J.

C.J.

C .J

C.J.

C.J.

C.J.

C.J.

C.J.

C .J

C .J

C .J

C

.J

C .J

C F2

.0

5' - 0" 14' - 4"

C.J.

A1 S402

A2 S402

A4 S402

A4 S402

C3 S401

A3 S402

B1 S402

B1 S402

B2 S402

B3 S402

B4 S402

B4 S402

A4 S402

A2 S402

A2 S404

A2 S404

A1 S404

A1 S404

C F2

.5

12" CMU WALLS w/(1)#5

VERTICAL REINF. @ 32"O.C.

CENTERED IN GROUT FILLED

CELLS , TYP. U.O.N.

16" DIA. CONCRETE

ENCASEMENT

T/ENCASEMENT

ELEV. +6'-0"

16" DIA. CONCRETE

ENCASEMENT

T/ENCASEMENT

ELEV. +6'-0"

8"

C1

7'

4"

8'

0"

12' - 3 1/2"

1' - 4"

8' - 8"

2'

0"

C .J

C .J

7' - 0"

4"

RECESS SLAB 2"

SEE ARCH. DWGS.

FOR DIMS.

EXTRACTOR SLAB,

12" THICK SLAB WITH #4

@ 12"O.C. EACH WAY,

TOP AND BOTTOM

RECESS SLAB 2"

SEE ARCH. DWGS.

FOR DIMS.

RECESS SLAB 1 3/4"

SEE ARCH. DWGS.

FOR DIMS.

CANOPY COLUMN

AND FTG. BY CANOPY

SUPPLIER, TYP.

4'

6"

3' - 10"

C.J.C .J

C3 S402

C .J

C.J.

RECESS SLAB 2"

SEE ARCH. DWGS.

FOR DIMS.

A3 S404

C F1

.6

C F1

.6

TD0.67

TD

0.

C3 S401

REFER TO NOTE #10

TD0.67

TD

0.

M3M2 M2M3

M1 M1

M1 M1

M3M2 M2M3

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M

FOUNDATION

& SLAB PLAN

22003

06.23.2023

C O

UN

TY

R O

A D

S101

BID DOCUMENTS

C

LA

Y C

O

UN

TY

C

LA

Y C

O F

IR

E

ST

A

TIO

N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

MEP ENGINEER

POWELL & HINKLE

ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FL 32073

CIVIL ENGINEER

GOODSON BERGEN &

ASSOC

11555 CENTRAL PARKWAY, SUITE 103

JACKSONVILLE, FL 32224

PROJECT

NORTH

SCALE: 1/8" = 1'-0"

1 FOUNDATION/SLAB PLAN

FOUNDATION NOTES:

REVISIONS

# DATE DESCRIPTION

1 11/03/23 PERMIT REV 1

2 12/11/23 PERMIT REV 2

x xx x x

2'

8" 6'

8"

2'

8"

15' - 4" 6' - 0"

CF1.67 CONT.

C F1

.6

C O

N T.

A4 S103

A4 S103

A4 S103

SIM.

CF1.67 CONT.

C F1

.6

C O

N T.

TD

1.

4" CONCRETE SLAB ON GRADE w/ 6x6-W2.1-W2.1 W.W.R. OVER 10 MIL.

VAPOR BARRIER ON COMPACTED FILL. 12

2'

8" 6'

8"

2'

8"

15' - 4"

TB-5

TB-5

TB

-5

TB

-5

PRE-FAB PRE-ENGINEERED WOOD TRUSSES @ 24"0.C.

2x

O U

TR

IG

G

ER

S

4"

O .C

2x

O U

TR

IG

G

ER

S

4"

O .C

BB

-1

B4 S103

B4 S103

C4 S103

D R

O

PP

ED

G

AB

LE

E N

D T

R U

SS

D R

O

PP

ED

G

AB

LE

E N

D T

R U

SS

RIDGE

REFER TO MECH. DWGS.

FOR OPENING SIZE, TYP.

1. REFER TO ARCH. FLOOR PLAN FOR ALL OPENINGS, WALL LOCATIONS, DEPRESSED / SLOPING SLABS, ELEVATIONS AND DIMS.

2. REFER TO SHEETS S401, S402, S403 & S404 FOR FOUNDATION SECTIONS AND DETAILS.

3. FOOTINGS & FOUNDATIONS SHALL BE IN ACCORDANCE WITH FBC CHAPTER 18 AND GEO-TECHNICAL

INVESTIGATION REPORT. TOP OF FOOTING ELEVATION -1'-4" U.N.O.

4. REFER TO S001 AND S002 FOR ADDITIONAL GENERAL NOTES AND DESIGN CRITERIA.

5. THE STRUCTURAL ENGINEER SHALL NOT HAVE CONTROL OR BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS TECHNIQUES, PROCEDURES OR SEQUENCE, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR OR ANY OTHER PERSONS PERFORMING THE WORK, OR THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.

6. DENOTES 8"/12" CMU WALL ON PLAN. PROVIDE VERTICAL REINFORCEMENT AS INDICATED ON PLAN IN

GROUTED FILLED CELLS, GROUT ALL CELLS UP TO SLAB ON GRADE, TYP. U.O.N.

7. S.F. - DENOTES TYPICAL STEP FOOTING ON PLAN REFER TO DETAIL A4/S401.

8. - DENOTES GROUT FILLED CELL WITH REINF., SEE PLAN FOR SIZE AND SPACING OF REINF., TYP.

9. PROVIDE (1)#5 x 3'-0" LONG BARS @ RE-ENTRY CORNERS, REFER TO DETAIL B3/S401.

CONT. BOND BEAM,

SEE PLAN, TYP.

T/BOND BEAM

ELEV. SEE PLAN

PLYWOOD ROOF SHEATHING, REFER TO

NOTES ON SHEETS S0.1 AND S0.2, TYP.

2x FACIA, REFER TO ARCH.

DWGS., TYP.

WOOD TRUSSES @ 24"O.C.,

TYP. - SEE PLAN

TYPICAL WALL REINF., SEE PLAN

FOR SIZE AND SPACING TYP.

8" CMU SEE PLAN WITH HORIZ. JOINT

REINF @ 16"O.C., TYPICAL

REFER TO

ARCH. DWGS.

TRUSS HOLD-DOWN,

SEE PLAN

T/FTG.

EL. SEE PLAN

CMU, SEE PLAN WITH HORIZ.

JOINT REINF @ 16"O.C.,

TYPICAL

2"

3"

CLR,

TYP.

DOWELS TO MATCH VERT.

REINF. w/ STD. HOOK INTO FTG., TYP.

SEE PLAN

SE

E

PL

AN

SE

E

PL

AN

SLAB ON VAPOR BARRIER

ON COMPACTED FILL, TYP.

T/SLAB

EL. SEE PLAN

TYPICAL WALL REINF.,

SEE PLAN FOR SIZE AND SPACING,

TYP.

FINISHED GRADE

EL. SEE ARCH DWGS

CONT FTG. CENTERED UNDER/CMU

WALL, TYP. - SEE PLAN

1/2" EXP. JOINT. MATERIAL w/

SEALANT TYP.

3"

8"x16" CONT. BOND BEAM, SEE PLAN, TYP.

T/BOND BEAM

ELEV. SEE PLAN

PLYWOOD ROOF SHEATHING, REFER TO

NOTES ON SHEETS S0.1 AND S0.2, TYP.

2x FACIA, REFER TO

ARCH. DWGS., TYP.

WOOD TRUSSES @ 24"O.C.,

TYP. - SEE PLAN

TYPICAL WALL REINF., SEE PLAN

FOR SIZE AND SPACING TYP.

8" CMU SEE PLAN WITH HORIZ. JOINT

REINF @ 16"O.C., TYPICAL

DROPPED GABLE END TRUSS,

SEE PLAN, TYP.

2x OUTRIGGERS @

24"O.C., TYP.

TRUSS HOLD-DOWN,

SEE PLAN

WALL SHEATHING, REFER

TO GENERAL NOTES, TYP.

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M

WELL HOUSE

FRAMING

PLANS

22003

06.23.2023

C O

UN

TY

R O

A D

S103

BID DOCUMENTS

C

LA

Y C

O

UN

TY

C

LA

Y C

O F

IR

E

ST

A

TIO

N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

MEP ENGINEER

POWELL & HINKLE

ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FL 32073

CIVIL ENGINEER

GOODSON BERGEN &

ASSOC

11555 CENTRAL PARKWAY, SUITE 103

JACKSONVILLE, FL 32224

SCALE: 3/8" = 1'-0"

1 WELL HOUSE - FOUNDATION PLAN

SCALE: 3/8" = 1'-0"

2 WELL HOUSE - ROOF FRAMING PLAN

FOUNDATION NOTES:

SCALE: 3/4" = 1'-0"

B4SECTION AT CMU WALL @ EXTERIOR WALL

SCALE: 3/4" = 1'-0"

A4SECTION AT CMU WALL @ EXTERIOR WALL

SCALE: 3/4" = 1'-0"

C4SECTION AT CMU WALL @ EXTERIOR GABLE END WALL

REVISIONS

1. REFER TO ARCH. FLOOR PLAN FOR ALL OPENINGS, WALL AND FLOOR LOCATIONS, DEPRESSED / SLOPING SLABS, ELEVATIONS

AND DIMS.

2. REFER TO S001, S002, S003 AND S004 FOR ADDITIONAL GENERAL NOTES AND DESIGN CRITERIA.

3. THE STRUCTURAL ENGINEER SHALL NOT HAVE CONTROL OR BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS TECHNIQUES, PROCEDURES OR SEQUENCE, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR OR ANY OTHER PERSONS PERFORMING THE WORK, OR THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE

CONTRACT DOCUMENTS.

4. TB-1, B-1, ETC., DENOTES MASONRY TIE BEAM, SEE PLAN AND SCHEDULE ON SHEET S003.

5. REFER TO S003 FOR SCHEDULES AND WIND PRESSURE DIAGRAMS ON SHEET S004.

6. DESIGN FLAT TRUSSES FOR ADDITIONAL LIVE LOAD OF 30 PSF FOR MECHANICAL UNITS. (TOTAL LIVE LOAD = 50 PSF).

7. WL-1 - DENOTES (2) 2x10 P.T. LEDGER w/ (2) ROWS OF 5/8" DIA. EXPANSION BOLTS AT 16"O.C., TYP.

COLUMN SYMBOLS

INDICATES COLUMN BELOW

INDICATES COLUMN THRU

INDICATES COLUMN ABOVE

GABLE TRUSS

GABLE TRUSS

GABLE TRUSS

GABLE TRUSS

GABLE TRUSS

GABLE TRUSS

GABLE TRUSS

GABLE TRUSS

GABLE TRUSS

GABLE TRUSS

G

AB

LE

T

R U

SS

G

AB

LE

T R

U

SS

GIRDER TRUSS

VALLEY TRUSSES

PRE-ENGINEERED

PR

E-

EN

G

IN

EE

R

ED

T R

U

SS

ES

4"

O .C

. M

AX

S

PA

C

IN

G

PR

E-

EN

G

IN

EE

R

ED

T R

U

SS

ES

4"

O .C

. M

AX

S

PA

C

IN

G

VALLEY TRUSSES

PRE-ENGINEERED

TB-1 TB-1

TB

-1

TB

-1

TB-1

TB

-6

TB

-1

TB

-6

B-

B-

TB

-6

TB

-1

TB

-1

TB

-1

W L-

TB

-3

(3 ) 2

X1

W L-

TB

-2

W L-

TB-1 WL-1 TB-1

B-2

TB-1

TB-1

TB-1

TB-1

TB-1

TB-1

TB-1

TB-1

GIRDER TRUSS

B-3

B-3

B-3

B-3

B-3

B-3

TB-4

TB-4

W x4

'-2

/2

W x5

'-2

/2

W x4

'-2

/2

B-3

B-3

TB

-3

TB

-3

TB

-3

B-3

B-3

TB-4

B-3

B-3

B-3

B-3

B-3

B-3

TB-4

TB-4

B2 S602

B2 S602

C4 S602

C4 S602

B3 S602

B1 S602

B1 S602

A4 S602

A3 S602

A3 S602

A2 S602

A1 S602

A3 S601

A3 S601

B3 S601

B1 S601

A4 S601

B1 S601

A1 S601

A2 S601

A1 S601

A2 S601

A1 S601

A2 S601

A1 S603

A1 S603

C1

C1

MGT

MGT

MGT

MGT

MTS16 AT

EACH TRUSS, TYP.

HETAL16 TRUSS

HOLD-DOWN AT EACH

TRUSS, TYP. UNO

C4 S601

B2 S601

B2 S601

AL

U

M

IN

U M

C

AN

O

PY

BY

S

PE

C

IA

LT

Y

EN

G

IN

EE

R

R

EF

ER

T O

A R

C H

. D W

G S.

7' - 0"

R

ID

G E

R

ID

G E

R

ID

G E

ALUMINUM CANOPY

BY SPECIALTY ENGINEER,

REFER TO ARCH. DWGS.

2x6 OUTRIGGERS @ 24"O.C.

DROPPED GABLE END TRUSS

DROPPED GABLE

END TRUSS

58' - 0"

2x6 OUTRIGGERS @ 24"O.C., TYP.

21' - 4"

7'

4" 7'

4"

58' - 0" 21' - 4"

2x6 OUTRIGGERS @ 24"O.C., TYP.

DROPPED GABLE

END TRUSS

DROPPED GABLE

END TRUSS

HOOD #1

200lbs.

38' - 8" 10' - 0"

16' - 8"

RTU-04 1700lbs.

MAXIMUM, REFER

TO MECH. DWGS., TYP.

RACK MOUNTED

CU-3 AND CU-4,

REFER TO MECH.

DWGS., TYP.

RACK MOUNTED

CU-1 AND CU-2,

REFER TO MECH.

DWGS., TYP.

16' - 8"38' - 8" 10' - 0"

WL-1

B1 S603

ROOF HATCH

OPENING, REFER TO

ARCH. AND MECH.

DWGS., TYP.

DROPPED

GABLE END

TRUSS

B2 S601

B2 S601

MECHANICAL PENETRATIONS,

REFER TO ARCH. AND MECH.

DWGS., TYP.

MECHANICAL PENETRATIONS,

REFER TO ARCH. AND MECH.

DWGS., TYP.

2x

O U

TR

IG

G

ER

S

4"

O .C

DROPPED

GABLE END

TRUSS

2x

O U

TR

IG

G

ER

S

4"

O .C

.C3 S602

C3 S602

2x6 OUTRIGGERS @ 24"O.C.

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M

ROOF

FRAMING

PLAN

22003

06.23.2023

C O

UN

TY

R O

A D

S201

BID DOCUMENTS

C

LA

Y C

O

UN

TY

C

LA

Y C

O F

IR

E

ST

A

TIO

N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

MEP ENGINEER

POWELL & HINKLE

ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FL 32073

CIVIL ENGINEER

GOODSON BERGEN &

ASSOC

11555 CENTRAL PARKWAY, SUITE 103

JACKSONVILLE, FL 32224

PROJECT

NORTH

SCALE: 1/8" = 1'-0"

1 ROOF FRAMING PLAN

REVISIONS

# DATE DESCRIPTION

1 11/03/23 PERMIT REV 1

2 12/11/23 PERMIT REV 2

xx xx x xx x x xx xx x x x xx x xx x x xx x x x x x x x xx x x

CONT FTG, SEE

PLAN AND SCHD.

FOR SIZE AND

REINF.

ADD CORNER BAR ON ALL

CONT. BARS TO MATCH

SIZE OF FTG. REINF.

STANDARD ACI BAR

DIAIMETER LAP, TYP.

PLAN VIEW AT FTG.

COMPACTED FILL, TYP.

VAPOR BARRIER, TYP.

CONCRETE SLAB SEE

PLAN FOR SIZE & REINF.

CONCRETE SLAB SEE

PLAN FOR SIZE &

REINF.

(1)#4 CONT.,

TYP.

SE

E

PL

AN

SE

E

PL

AN

SAME SIZE & NO. AS FTG.

REINF.

TOP OF FOOTING

EL. SEE PLAN

TOP OF FOOTING

EL. SEE PLAN

SEE PLAN & SCHEDULE

FOR FTG. SIZE & REINF.

S.

F.

LO

C

AT

E

AS

S

H O

W N

O N

P

LA

N S

2' -0

" M

AX

3" C

LR

. M

IN

USE WHERE

APPLICABLE

2'-0" MIN.

WWF, SEE…

This is the start of the file's text. The full file is on GovTribe.