Addendum_#1_-_Clay_Co_FS24_-_Struct_(2026_02-17).pdf
PDF 964 KB Posted
- Attached to
- Construction of Clay County Fire Station No. 24
- Solicitation number
- 25/26-042
- Issued by
- Clay County, Harold CDP, Florida
About this file
This Addendum #1 document, issued by Dasher Hurst Architects, PA on behalf of Clay County, Florida, provides structural design specifications and construction details for Fire Station No. 24 located at 1075 County Road 226 in Green Cove Springs, Florida. The addendum includes detailed architectural and structural drawings covering foundation and slab plans, well house framing plans, roof framing plans, foundation sections and details, and framing sections and details. The project involves the construction of a new approximately 16,633 square-foot fire station facility with structural elements including steel column base plates, masonry columns, continuous footings, reinforced concrete slabs on grade, CMU walls with horizontal joint reinforcement, steel beams, wood trusses, and various specialized connections and details. The drawings specify concrete reinforcing splice length and development length schedules per ACI 318, steel anchor rod specifications per ASTM F1554 Grade 36, and detailed schedules for masonry columns, concrete footings, beams, and steel columns. The addendum was issued on February 17, 2026, representing revision 5 to the original bid documents dated June 23, 2023, with prior revisions issued on November 3, 2023 (Permit Rev 1), December 11, 2023 (Permit Rev 2), July 19, 2024 (VE Rev 1), and July 25, 2025 (90% IRC Review).
The technical specifications establish construction standards for reinforcing steel with a yield strength of 60 KSI, concrete compressive strength of 3,000 PSI, and compliance with Florida Building Code Chapter 18 and geotechnical investigation reports. The drawings reference sheets S001 through S004 for general notes and design criteria, with foundation work including step footings, depressed slabs, control joints, and detailed lintel reinforcing schedules for masonry openings. The structural engineer of record is G.M. Hill Engineering, Inc., with MEP engineering by Powell & Hinkle Engineering, P.A., and civil engineering by Goodson Bergen & Associates. All specifications incorporate standard construction practices for foundation preparation, slab placement with vapor barriers, masonry wall construction with grouted cells, and structural steel connections with bolted and welded details, establishing the baseline technical requirements for contractor bidding and construction execution.
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T/CONC.
ROD DIA.
("D")
HOLE DIA. PLATE WASHER
3/4" 1 5/16"
7/8" 1 9/16"
1/4"x2"x2"
NOTES:
1. ANCHOR ROD SHALL BE ASTM F1554 (GRADE 36) UNO, THREADED EACH END WITH NUT AT BOTTOM.
PLATE WASHER AT BOTTOM NUT IS NOT REQUIRED. INCREASE FOOTING THICKNESS AT ANCHOR RODS
ONLY TO PROVIDE MIN. 4" COVER.
2. PLATE WASHERS SHALL HAVE HOLE WITH DIAMETER EQUAL TO ROD DIAMETER + 1/16".
CIRCULAR OR SQUARE WASHERS ARE ACCEPTABLE.
3. OPTIONAL: PROVIDE A HEAVY HEX HEAD BOLT IN LIEU OF THE THREADED ROD WITH HEX NUT AT
BOTTOM.
B/CONC.
("D") (ROD DIA.)
PLATE WASHERS
(SEE SCH. FOR SIZE)
HEAVY HEX NUT, TYP.
TACK
AS
R
EQ
D
M
IN
. 5
PR
O
J.
EM
BE
D M
EN
T
"E
2"
M
IN
4"
1 1/4" 2 1/16"
1" 1 13/16"
1 1/2" 2 5/16"
5/16"x2 1/2"x2 1/2"
3/8"x3"x3"
1/2"x3"x3"
1/2"x3 1/2"x3 1/2"
EMBEDMENT
("E")
9"
12"
14"
18"
20"
1/
4" SEE COLUMN BASE
DETAIL FOR GROUT
THICKNESS
1" M
IN
TYPICAL ANCHOR ROD DETAIL
TYPE "A"
GRID
G R
ID HSS COLUMN
BASE PLATE
2" , TYP.
EQUAL EQUAL
"C"
2"
TY
P.
EQ
U
AL
EQ
U
AL
"B
AISC MIN
TYPICAL
TYPE 2 TYPE 3
TYPE 4 TYPE 5
1' - 4" 2' - 0"
2'-8". 3'-4".
SIZE OF BAR
REQUIRED
DEVELOPMENT LENGTH
STRAIGHT BARS
REQUIRED
DEVELOPMENT LENGTH
HOOKED BARS
#3 1'-4" 8 1/4" #4 1'-10" 11 1/2" #5 2'-4" 1'-3 1/4" #6 2'-9" 1'-4 1/2" #7 4'-0" 1'-7 1/4" #8 4'-7" 1'-10" #9 5'-2" 2'-0 3/4" #10 5'-10" 2'-4" #11 6'-6" 2'-7"
SIZE OF BAR. SPLICE (A) SPLICE (B)
#3 1'-1" 1'-5" #4 1'-6" 1'-11" #5 1'-10" 2'-4" #6 2'-2" 2'-10" #7 3'-2" 4'-1" #8 3'-9" 4'-11" #9 4'-8" 6'-1" #10 5'-7" 7'-3" #11 6'-7" 8'-7"
CONCRETE REINFORCING SPLICE
LENGTH SCHEDULE PER ACI 318
CONCRETE REINFORCING DEVELOPMENT
LENGTH SCHEDULE PER ACI 318
REINFORCING YEILD STRENGTH, Fy = 60 KSI CONCRETE COMPRESSIVE STRENGHT, F'c = 3,000 PSI
REINFORCING YEILD STRENGTH, Fy = 60 KSI CONCRETE COMPRESSIVE STRENGHT, F'c = 3,000 PSI
SCALE: = NTS
A4STEEL COLUMN BASE PLATE DETAIL
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
SCHEDULES
22003
06.23.2023
C O
UN
TY
R O
A D
S003
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
MEP ENGINEER
POWELL & HINKLE
ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FL 32073
CIVIL ENGINEER
GOODSON BERGEN &
ASSOC
11555 CENTRAL PARKWAY, SUITE 103
JACKSONVILLE, FL 32224
M4 8" x 16" (4) #5 #2 @ 8" 2 MASONRY
M3 DOUBLE 8" x 40" (10)#5 #2 @ 8" 5 MASONRY
M2 DOUBLE 8" x 32" (8) #5 #2 @ 8" 4 MASONRY
M1 8" x 24" (6) #5 #2 @ 8" 3 MASONRY
COLUMN ID. NO. COLUMN SIZE (WxD INCHES) VERTICAL REINFORCEMENT OR BASE PLATE COLUMN TIES OR CAP PLATE TYPE REMARKS
MASONRY COLUMN SCHEDULE
TD1.0 1'-0" x CONT. x 1'-4" (2) #5 CONT. BOTTOM MONOLITHIC w/ SLAB
TD0.67 0'-8" x CONT. x 0'-8" (1) #5 CONT. BOTTOM MONOLITHIC w/ SLAB
F5.0 5'-0" x 5'-0" x 1'-4" (6) #5 CONT. EACH WAY, BOTTOM
RF5.0x15.0 5'-0" x 15'-0" x 2'-4" (5) #7 LONG WAY TOP AND BOTTOM, (14) #7 SHORT
WAY TOP AND BOTTOM (OUTER BARS IN OUTER... FOOTING NOT USED
CF2.5 2'-6" x CONT. x 1'-0" (3) #5 CONT. BOTTOM #4 @ 24"O.C. TRANSVERSE
CF2.0 2'-0" x CONT. x 1'-0" (3) #5 CONT. BOTTOM #4 @ 24"O.C. TRANSVERSE
CF1.67 1'-8" x CONT. x 1'-0" (2) #5 CONT. BOTTOM
MARK SIZE (WxLxD) REINFORCING REMARKS
FOOTING SCHEDULE
B-3 16'-0" 8" x 24" (2)#5 (2)#5 (2)#5 #3 @ 8"O.C. MASONRY BEAM
B-2 9'-4" 8" x 16" (2)#5 (2)#5 #3 @ 8"O.C. MASONRY BEAM
B-1 10'-8" 8" x 16" (2)#7 (2)#5 #3 @ 8"O.C. MASONRY BEAM
TB-6 10'-8" 8" x 24" (2)#5 (2)#5 - MASONRY TIE BEAM
TB-5 9'-4" 8" x 16" (2)#5 (2)#5 - MASONRY TIE BEAM
TB-4 19'-4" 8" x 16" (2)#5 (2)#5 - MASONRY TIE-BEAM
TB-3 19'-4" 12" x 16" (2)#5 (2)#5 - MASONRY TIE-BEAM
TB-2 10'-8" 12" x 16" (2)#5 (2)#5 - MASONRY TIE-BEAM
TB-1 10'-8" 8" x 16" (2)#5 (2)#5 - MASONRY TIE-BEAM
BOT... TOP "C" "E"
BEAM
MARK TOP OF BEAM ELEV. SIZE (W x D INCHES)
REINFORCING
#3 STIRRUPS REMARKS
MASONRY & CONCRETE BEAM SCHEDULE
C1 HSS 6x6x5/16 3/4" x 14" x 1'-2" - TYPE A 3/4" DIA. - TYPE A 1/4"
COLUMN MARK COLUMN TYPE BASE PLATE SIZE ANCHOR BOLT SIZE AND TYPE CAP PLATE SIZE REMARKS
STEEL COLUMN SCHEDULE
REVISIONS
# DATE DESCRIPTION
1 11/03/23 PERMIT REV 1
3 07/19/24 VE REV 1
4 07/25/25 90% IRC REVIEW
5 02/17/26 ADD #1
1. REFER TO ARCH. FLOOR PLAN FOR ALL OPENINGS, WALL LOCATIONS, DEPRESSED / SLOPING SLABS, ELEVATIONS AND DIMS.
2. REFER TO SHEETS S401, S402, S403 AND S404 FOR FOUNDATION SECTIONS AND DETAILS.
3. FOOTINGS & FOUNDATIONS SHALL BE IN ACCORDANCE WITH FBC CHAPTER 18 AND GEO-TECHNICAL INVESTIGATION REPORT. TOP OF
FOOTING ELEVATION -1'-4" U.N.O.
4. REFER TO S001, S002, S003 AND S004 FOR ADDITIONAL GENERAL NOTES AND DESIGN CRITERIA.
5. THE STRUCTURAL ENGINEER SHALL NOT HAVE CONTROL OR BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS TECHNIQUES, PROCEDURES OR SEQUENCE, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR OR ANY OTHER PERSONS PERFORMING THE WORK, OR THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
6. DENOTES 8" OR 12" CMU WALL ON PLAN. PROVIDE VERTICAL REINFORCEMENT AS INDICATED ON PLAN IN GROUTED FILLED CELLS, GROUT ALL CELLS UP TO SLAB ON GRADE, TYP. U.O.N.
7. S.F. - DENOTES TYPICAL STEP FOOTING ON PLAN REFER TO DETAIL A4/S401
8. - DENOTES GROUT FILLED CELL WITH REINF., SEE PLAN FOR SIZE AND SPACING OF REINF., TYP.
9. PROVIDE (1)#5 x 3'-0" LONG BARS @ RE-ENTRY CORNERS, REFER TO DETAIL B3/S401.
10. CF2.5 STEM WALL FOOTING REINFORCEMENT IS CONTINUOUS THROUGH CANOPY FOUNDATION, WHERE REQUIRED.
COLUMN SYMBOLS
INDICATES COLUMN BELOW
INDICATES COLUMN THRU
INDICATES COLUMN ABOVE
4" CONCRETE SLAB ON GRADE w/ 6x6-W2.1-W2.1 W.W.R. OVER 10 MIL.
VAPOR BARRIER ON COMPACTED FILL.,
TYP. U.N.O. - T/SLAB EL. 0'-0"
8" CONCRETE SLAB ON GRADE w/
#5 @ 12"O.C. EACH WAY AT
MID- DEPTH, TYP.
8" CMU WALLS w/(1)#5 VERTICAL
REINF. @ 48"O.C. CENTERED IN
GROUT FILLED CELLS , TYP. U.O.N.
C1
12" WIDE CONCRETE
CURB w/ #4 @ 12" VERT.
AND HORZ. EACH FACE
58' - 0" OUT/OUT OF CMU
4' - 8" 14' - 0" 3' - 4" 14' - 0" 3' - 4" 14' - 0" 4' - 8"
16' - 8"9' - 0" 20' - 8" 9' - 0" 10' - 0"
48' - 8" OUT/OUT OF CMU
2' - 0"
14' - 0"
58' - 0" OUT/OUT OF CMU 21' - 4"2'-0".
14' - 0" 5' - 4"4' - 8"14' - 0"3' - 4"14' - 0"3' - 4"14' - 0"4' - 8"
79' - 4" OUT/OUT OF CMU
6'
8"
" O
U T/
O U
T O
F C
M U
26' - 8"16' - 4"6' - 0"16' - 4"
38' - 8" OUT/OUT OF CMU 10' - 0"
16' - 8"
/4
/4
2'
0"
9' - 0"
7'
4"
T/FTG.
EL. -2' - 0"
F5.0 FTG.
T/FTG.
EL. -2' - 0"
F5.0 FTG.
C F1
.6
CF1.67 CF1.67
CF1.67
CF1.67
CF2.0
CF2.0
CF2.0
CF2.0
CF1.67
CF1.67
CF1.67
CF1.67
CF1.67
CF1.67
CF1.67
C F1
.6
C F1
.6
C F1
.6
C F2
.0
C F1
.6
C F2
.0
C F2
.0
C F1
.6
C F1
.6
C F1
.6
CF1.67
C F1
.6
CF1.67
CF1.67
CF1.67
CF1.67
CF1.67
CF1.67
CF1.67
CF1.67
5' - 4"
21' - 4"
C.J.
C.J.
C.J.
C.J.
C.J.
C .J
C .J
C .J
C .J
C .J
C.J.
C.J.
C.J.
C.J.
C.J.
C .J
C.J.
C.J.
C.J.
C.J.
C.J.
C .J
C .J
C .J
C
.J
C .J
C F2
.0
5' - 0" 14' - 4"
C.J.
A1 S402
A2 S402
A4 S402
A4 S402
C3 S401
A3 S402
B1 S402
B1 S402
B2 S402
B3 S402
B4 S402
B4 S402
A4 S402
A2 S402
A2 S404
A2 S404
A1 S404
A1 S404
C F2
.5
12" CMU WALLS w/(1)#5
VERTICAL REINF. @ 32"O.C.
CENTERED IN GROUT FILLED
CELLS , TYP. U.O.N.
16" DIA. CONCRETE
ENCASEMENT
T/ENCASEMENT
ELEV. +6'-0"
16" DIA. CONCRETE
ENCASEMENT
T/ENCASEMENT
ELEV. +6'-0"
8"
C1
7'
4"
8'
0"
12' - 3 1/2"
1' - 4"
8' - 8"
2'
0"
C .J
C .J
7' - 0"
4"
RECESS SLAB 2"
SEE ARCH. DWGS.
FOR DIMS.
EXTRACTOR SLAB,
12" THICK SLAB WITH #4
@ 12"O.C. EACH WAY,
TOP AND BOTTOM
RECESS SLAB 2"
SEE ARCH. DWGS.
FOR DIMS.
RECESS SLAB 1 3/4"
SEE ARCH. DWGS.
FOR DIMS.
CANOPY COLUMN
AND FTG. BY CANOPY
SUPPLIER, TYP.
4'
6"
3' - 10"
C.J.C .J
C3 S402
C .J
C.J.
RECESS SLAB 2"
SEE ARCH. DWGS.
FOR DIMS.
A3 S404
C F1
.6
C F1
.6
TD0.67
TD
0.
C3 S401
REFER TO NOTE #10
TD0.67
TD
0.
M3M2 M2M3
M1 M1
M1 M1
M3M2 M2M3TD1.0 TD1.0TD1.0
TD1.0
TD1.0
TD1.0TD1.0TD1.0
TD1.0
TD1.0
5 5 5
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
FOUNDATION
& SLAB PLAN
22003
06.23.2023
C O
UN
TY
R O
A D
S101
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
MEP ENGINEER
POWELL & HINKLE
ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FL 32073
CIVIL ENGINEER
GOODSON BERGEN &
ASSOC
11555 CENTRAL PARKWAY, SUITE 103
JACKSONVILLE, FL 32224
PROJECT
NORTH
SCALE: 1/8" = 1'-0"
1 FOUNDATION/SLAB PLAN
FOUNDATION NOTES:
REVISIONS
# DATE DESCRIPTION
1 11/03/23 PERMIT REV 1
2 12/11/23 PERMIT REV 2
3 07/19/24 VE REV 1
4 07/25/25 90% IRC REVIEW
5 02/17/26 ADD #1
x xx x x
2'
8" 6'
8"
2'
8"
15' - 4" 6' - 0"
CF1.67 CONT.
C F1
.6
C O
N T.
A4 S102
A4 S102
A4 S102
SIM.
CF1.67 CONT.
C F1
.6
C O
N T.
TD
1.
4" CONCRETE SLAB ON GRADE w/ 6x6-W2.1-W2.1 W.W.R. OVER 10 MIL.
VAPOR BARRIER ON COMPACTED FILL. 12
2'
8" 6'
8"
2'
8"
15' - 4"
TB-5
TB-5
TB
-5
TB
-5
PRE-FAB PRE-ENGINEERED WOOD TRUSSES @ 24"0.C.
2x
O U
TR
IG
G
ER
S
4"
O .C
2x
O U
TR
IG
G
ER
S
4"
O .C
BB
-1
B4 S102
B4 S102
C4 S102
D R
O
PP
ED
G
AB
LE
E N
D T
R U
SS
D R
O
PP
ED
G
AB
LE
E N
D T
R U
SS
RIDGE
REFER TO MECH. DWGS.
FOR OPENING SIZE, TYP.
1. REFER TO ARCH. FLOOR PLAN FOR ALL OPENINGS, WALL LOCATIONS, DEPRESSED / SLOPING SLABS, ELEVATIONS AND DIMS.
2. REFER TO SHEETS S401, S402, S403 & S404 FOR FOUNDATION SECTIONS AND DETAILS.
3. FOOTINGS & FOUNDATIONS SHALL BE IN ACCORDANCE WITH FBC CHAPTER 18 AND GEO-TECHNICAL
INVESTIGATION REPORT. TOP OF FOOTING ELEVATION -1'-4" U.N.O.
4. REFER TO S001 AND S002 FOR ADDITIONAL GENERAL NOTES AND DESIGN CRITERIA.
5. THE STRUCTURAL ENGINEER SHALL NOT HAVE CONTROL OR BE RESPONSIBLE FOR CONSTRUCTION MEANS, METHODS TECHNIQUES, PROCEDURES OR SEQUENCE, FOR THE ACTS OR OMISSIONS OF THE CONTRACTOR OR ANY OTHER PERSONS PERFORMING THE WORK, OR THE FAILURE OF ANY OF THEM TO CARRY OUT THE WORK IN ACCORDANCE WITH THE CONTRACT DOCUMENTS.
6. DENOTES 8"/12" CMU WALL ON PLAN. PROVIDE VERTICAL REINFORCEMENT AS INDICATED ON PLAN IN
GROUTED FILLED CELLS, GROUT ALL CELLS UP TO SLAB ON GRADE, TYP. U.O.N.
7. S.F. - DENOTES TYPICAL STEP FOOTING ON PLAN REFER TO DETAIL A4/S401.
8. - DENOTES GROUT FILLED CELL WITH REINF., SEE PLAN FOR SIZE AND SPACING OF REINF., TYP.
9. PROVIDE (1)#5 x 3'-0" LONG BARS @ RE-ENTRY CORNERS, REFER TO DETAIL B3/S401.
CONT. BOND BEAM,
SEE PLAN, TYP.
T/BOND BEAM
ELEV. SEE PLAN
PLYWOOD ROOF SHEATHING, REFER TO
NOTES ON SHEETS S0.1 AND S0.2, TYP.
2x FACIA, REFER TO ARCH.
DWGS., TYP.
WOOD TRUSSES @ 24"O.C.,
TYP. - SEE PLAN
TYPICAL WALL REINF., SEE PLAN
FOR SIZE AND SPACING TYP.
8" CMU SEE PLAN WITH HORIZ. JOINT
REINF @ 16"O.C., TYPICAL
REFER TO
ARCH. DWGS.
TRUSS HOLD-DOWN,
SEE PLAN
T/FTG.
EL. SEE PLAN
CMU, SEE PLAN WITH HORIZ.
JOINT REINF @ 16"O.C.,
TYPICAL
2"
3"
CLR,
TYP.
DOWELS TO MATCH VERT.
REINF. w/ STD. HOOK INTO FTG., TYP.
SEE PLAN
SE
E
PL
AN
SE
E
PL
AN
SLAB ON VAPOR BARRIER
ON COMPACTED FILL, TYP.
T/SLAB
EL. SEE PLAN
TYPICAL WALL REINF.,
SEE PLAN FOR SIZE AND SPACING,
TYP.
FINISHED GRADE
EL. SEE ARCH DWGS
CONT FTG. CENTERED UNDER/CMU
WALL, TYP. - SEE PLAN
1/2" EXP. JOINT. MATERIAL w/
SEALANT TYP.
3"
8"x16" CONT. BOND BEAM, SEE PLAN, TYP.
T/BOND BEAM
ELEV. SEE PLAN
PLYWOOD ROOF SHEATHING, REFER TO
NOTES ON SHEETS S0.1 AND S0.2, TYP.
2x FACIA, REFER TO
ARCH. DWGS., TYP.
WOOD TRUSSES @ 24"O.C.,
TYP. - SEE PLAN
TYPICAL WALL REINF., SEE PLAN
FOR SIZE AND SPACING TYP.
8" CMU SEE PLAN WITH HORIZ. JOINT
REINF @ 16"O.C., TYPICAL
DROPPED GABLE END TRUSS,
SEE PLAN, TYP.
2x OUTRIGGERS @
24"O.C., TYP.
TRUSS HOLD-DOWN,
SEE PLAN
WALL SHEATHING, REFER
TO GENERAL NOTES, TYP.
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
WELL HOUSE
FRAMING
PLANS
22003
06.23.2023
C O
UN
TY
R O
A D
S102
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
MEP ENGINEER
POWELL & HINKLE
ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FL 32073
CIVIL ENGINEER
GOODSON BERGEN &
ASSOC
11555 CENTRAL PARKWAY, SUITE 103
JACKSONVILLE, FL 32224
SCALE: 3/8" = 1'-0"
1 WELL HOUSE - FOUNDATION PLAN
SCALE: 3/8" = 1'-0"
2 WELL HOUSE - ROOF FRAMING PLAN
FOUNDATION NOTES:
SCALE: 3/4" = 1'-0"
B4SECTION AT CMU WALL @ EXTERIOR WALL
SCALE: 3/4" = 1'-0"
A4SECTION AT CMU WALL @ EXTERIOR WALL
SCALE: 3/4" = 1'-0"
C4SECTION AT CMU WALL @ EXTERIOR GABLE END WALL
REVISIONS
# DATE DESCRIPTION
1 11/03/23 PERMIT REV 1
5 02/17/26 ADD #1
xx xx x xx x x xx xx x x x xx x xx x x xx x x x x x x x xx x x
CONT FTG, SEE
PLAN AND SCHD.
FOR SIZE AND
REINF.
ADD CORNER BAR ON ALL
CONT. BARS TO MATCH
SIZE OF FTG. REINF.
STANDARD ACI BAR
DIAIMETER LAP, TYP.
PLAN VIEW AT FTG.
COMPACTED FILL, TYP.
VAPOR BARRIER, TYP.
CONCRETE SLAB SEE
PLAN FOR SIZE & REINF.
CONCRETE SLAB SEE
PLAN FOR SIZE &
REINF.
(1)#4 CONT.,
TYP.
SE
E
PL
AN
SE
E
PL
AN
SAME SIZE & NO. AS FTG.
REINF.
TOP OF FOOTING
EL. SEE PLAN
TOP OF FOOTING
EL. SEE PLAN
SEE PLAN & SCHEDULE
FOR FTG. SIZE & REINF.
S.
F.
LO
C
AT
E
AS
S
H O
W N
O N
P
LA
N S
2' -0
" M
AX
3" C
LR
. M
IN
USE WHERE
APPLICABLE
2'-0" MIN.
WWF, SEE PLAN
T/SLAB EL,
SEE PLAN
SEE PLAN
SE
E
PL
AN
CONT. FTG., SEE PLAN &
SCHEDULE FOR SIZE & REINF.
CONC. SLAB, SEE PLAN
FOR SIZE & REINF.
T/FTG. EL,
SEE PLAN
2"
2"
3"
CLR,
TYP. SEE PLAN
NOTES:
1. DELETE ISOLATION JOINTS WHERE SLAB IS PLACED AFTER COLUMNS ARE SET.
2. FOR SLAB REINF, SEE PLAN.
ISOLATION JOINT w/ BOND
BREAKER, TYP.
SE
E
PL
AN
ALT CIRCULAR
COL BLOCKOUT
2'-0" MIN
HSS TUBE
COLUMN, TYP.
T/SLAB EL,
SEE PLAN
PLAN VIEW
HSS TUBE COL, SEE PLAN, TYP.
SEE PLAN AND SCHED. FOR
FTG. SIZE AND REINF., TYP.
REMOVE ALL STANDING
WATER BEFORE GROUTING
BASE PLATE, TYP.
ANCHOR BOLTS & BASE PLATE,
REFER TO DETAIL ON SHEET
S003, TYP.
WRAP STEEL COLUMN WITH
15# FELT PAPER
1 1/2" GROUT
MINIMUM, SEE PLAN
LAP WITH SLAB
EDGE REINF.
OPENING
SLAB EDGE OR
CONSTRUCTION JOINT
(1) #5 RE-ENTRANT BAR EACH
SIDE OF OPENING AT MID-
DEPTH
135.00°
1' - 6"
3' - 0"
2" CLR.
SE
E
PL
AN
t
1/4" JOINT
WITH SEALANT
COMPACTED FILL VAPOR BARRIER
CONTRUCTION JOINTNOTE:
STOP REINF EACH SIDE OF JOINT,
TYP.
G.C. PROPOSED LOCATIONS TO
EOR
NOTES:
1. REFER TO PLANS FOR SLAB REINF.
2. t = SLAB THICKNESS, SEE PLAN
SE
E
PL
AN
t
1/4" JOINT
WITH SEALANT
COMPACTED FILL VAPOR BARRIER
CONTROL JOINT
NOTES:
1. REFER TO PLANS FOR SLAB REINF.
2. t = SLAB THICKNESS, SEE PLAN.
3. CONTRACTOR SHALL CUT SLAB CONTROL JOINTS WITHIN
8-24 HOURS OF SLAB PLACEMENT.
3/4"
3/
4" t/5 t/3 t/3
SEE
PLUMBING
DWGS
CAST IRON OR STEEL PIPE UNDER
FOOTING AND 3'-0" MIN EACH SIDE
ENCASE IN CONCRETE FOR
FOOTING WIDTH PLUS 2'-0"
EACH SIDE, TYP
COMPACTED EARTH
FOOTING, SEE PLAN
TYPICAL PIPE BENEATH THICKENED SLAB FOOTING
TOSL
SEE PLAN
WALL FRAMING,
SEE PLAN
D
96 DIA.
48 DIA. 48 DIA.
1 1/2"
D /3
D /3
D /3
(IF REQUIRED), TYP.
48 DIA. LAP SPLICE
ALL SCHEDULED LONGITUDINAL
BARS SHALL BE CONTINUOUS
THROUGH JOINT
TOP BARS
(IF REQUIRED)
ADD BARS SAME SIZE
AND SPACING AS
BOTTOM BARS, TYP.
1'
4"
2"
3" CLR,
TYP.
2"
T/SLAB
EL. SEE PLAN
#5 @ 12"O.C.
EACHWAY, TOP &
BOTTOM, TYP.
GENERATOR,
SEE MEP.
ELEVATE PAD
ABOVE ADJACENT
GRADE/SLAB, SEE
MECH. PROVIDE I.J.
AT CONC. SLAB
6" MINIMUM
ALL SIDES
6"
STOREFRONT,
SEE PLAN
T/FTG. EL,
SEE PLAN
2"
3"
CLR,
TYP. SEE PLAN
SE
E
PL
AN
SLAB ON VAPOR
BARRIER ON
COMPACTED FILL
TYP. T/SLAB. EL,
SEE PLAN
CONT FTG SEE
PLAN CENTERED
UNDER/CMU WALL
DOWELS TO MATCH VERT.
REINF w/ STD HOOK INTO FTG
@ 16" O.C. UNDER WINDOW &
DOOR OPENINGS
SE
E
PL
AN8"
CMU, SEE PLAN WITH HORIZ.
JOINT REINF @ 16" O.C., TYPICAL
#4 CONT. TOP
3"
FINISHED GRADE,
TYP.
1" SETBACK, SEE
ARCH. DWGS.
SCALE: = NTS
A2TYP CORNER FTG REINF
SCALE: = NTS
A3TYPICAL DEPRESSED SLAB DETAIL
SCALE: = NTS
A4STEP FOOTING DETAIL
SCALE: = NTS
B1TYP TURNDOWN DETAIL
SCALE: = NTS
B2TYP. INTERIOR COL. DETAIL
SCALE: = NTS
B3SLAB REINF. @ DOOR OPENING DETAIL
SCALE: = NTS
B4SLAB ON GRADE CONTROL JOINT
SCALE: = NTS
A1PIPE SLEEVE DETAIL BELOW FTG.
SCALE: = NTS
C1WALL FTG. OR THICKENED SLAB CONSTRUCTION JOINT
SCALE: 3/4" = 1'-0"
C2GENERATOR PAD DETAIL
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
FOUNDATION
SECTIONS &
DETAILS
22003
06.23.2023
C O
UN
TY
R O
A D
S401
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
MEP ENGINEER
POWELL & HINKLE
ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FL 32073
CIVIL ENGINEER
GOODSON BERGEN &
ASSOC
11555 CENTRAL PARKWAY, SUITE 103
JACKSONVILLE, FL 32224
SCALE: 3/4" = 1'-0"
C3TURNDOWN AT STOREFRONT DETAIL
REVISIONS
# DATE DESCRIPTION
1 11/03/23 PERMIT REV 1
3 07/19/24 VE REV 1
4 07/25/25 90% IRC REVIEW
5 02/17/26 ADD #1
SLAB BLOCKOUT OR
FUTURE IN-FILL
CMU OR
CONCRETE
WALL
ADDED SLAB BARS,
(2-#4x1'-0"+3'-0"
@ 3" OC)
CMU OR CONCRETE
WALL
POTENTIAL CRACK, TYP
SLAB BLOCKOUT OR
FUTURE IN-FILL
ADDED SLAB BARS, TYP
(2-#4x4'-0" @ 3" OC)
TYPICAL RE-ENTRANT CORNER REINFORCING AT SLAB-ON-GRADE
SJ SJ
SJ
SJ
SJ
EJ
EJ
EJ
EJ
SJ
NOTES:
1. A RE-ENTRANT CORNER IS ANY SLAB CORNER WHICH MIGHT INDUCE A CRACK IN THE SLAB.
2. ADDED SLAB BAR REINFORCING IS REQUIRED AT ALL RE-ENTRANT CORNER LOCATIONS.
3. NOT ALL LOCATIONS ARE SHOWN ON PLANS.
4. PLACE ADDED SLAB BARS BENEATH AND TIED TO WWF, 2" FROM TOP OF SLAB, MAX & 1 1/2" FROM
CORNERS.
1/2"
JOINT SEALANT, SEE
SPEC FINISH FLUSH
W/ SURFACE, TYP
1/ 2"
IF REQ'D BY SPECS, PROVIDE
JOINT SEALANT, FINISH FLUSH
W/ SURFACE, TYP
M
IN
"T "/4
SAWCUT
1/8"
"T "/2
WRAP & GREASE THIS
END OF ALL DOWELS
STOP REINF (IF REQ'D)
EACH SIDE OF JOINT
1/8" SAWCUT
1/ 2"
"T "/2
PREMOULDED EXP
JOINT MATERIAL
SMOOTH DOWEL
OR DIAMOND PL,
SEE TABLE
EQ EQ
SEE TABLE
PROVIDE FULL DEPTH
BULKHEAD HELD FIRMLY
IN A VERTICAL POSTION
"T
CONT VAPOR
BARRIER, TYP
CRACK CONTROL
JOINT
CONSTRUCTION JOINT EXPANSION JOINT
AT WALL
DOWEL SIZE & SPACING
"T" ROUND SQUARE RECTANGULAR DIAMOND PLATE
5"-6"
7"-8"
9"-11"
3/4x14" LG @ 12"
1x16" LG @ 12"
1 1/4x18" LG @ 12"
3/4x14" LG @ 14"
1x16" LG @ 14"
1 1/4x32" LG @ 12"
3/8x2x12" LG @ 19"
1/2x2 1/2x12" LG @ 18"
3/4x2 1/2x12" LG @ 18"
1/4x4 1/2x4 1/2 @ 18"
3/8x4 1/2x4 1/2 @ 18"
3/4x4 1/2x4 1/2 @ 20"
NOTES:
1) JOINT SHALL BE SAWCUT BETWEEN 4 AND 12 HOURS AFTER CONCRETE IS PLACED.
2) USE STRAIGHT BULKHEAD, COAT WITH FORM OIL.
3) COAT EXPOSED VERTICAL SURFACE OF CONCRETE WITH FORM OIL BEFORE POURING ADJACENT STRIP.
4) USE CONSTRUCTION JOINT INSTEAD OF CRACK CONTROL JOINT WHEREVER CONSTRUCTION IS STOPPED OR
WHERE CALLED FOR ON PLAN.
NOTES:
1. SEE PLAN FOR LOCATIONS.
2. INTERRUPT HORIZONTAL JOINT REINFORCING & CMU BOND BEAM
REINFORCING AT CONTROL JOINTS.
PREMOLDED DUR-O-WAL RAPID
CONTROL JOINT WITH WIDE
FLANGE, OR APPROVED EQUAL,
TYP.
REINFORCED CELL EACH
SIDE OF CONTROL JOINT, FILL
WITH GROUT, TYP.
SEE PLAN FOR CMU
WALLS & REINFORCING
APPLY SEALANT ON BOTH SIDES, TYP.
CONTROL JOINT -
24'-0" OC, MAX ON EXTERIOR WALLS
28'-0" OC, MAX ON INTERIOR WALLS
DO NOT PLACE OVER OPENINGS OR CONTINUE
THROUGH CAST IN PLACE BEAMS, UNO
PLAN DETAIL
APPLY SEALANT ON BOTH SIDES
REINFORCED CELL EACH SIDE OF
CONTROL JOINT, FILL WITH GROUT
STANDARD SASH BLOCK,
EACH SIDE OF CONTROL JOINT
PREMOLDED DUR-O-WAL RAPID
CONTROL JOINT WITH WIDE FLANGE C
LR4"
C
LR3"
DOWEL W/ STANDARD HOOK OR
TERMINATE VERTICAL WITH A
STANDARD HOOK, TYP.
CONCRETE OR CMU ROOF
BEAM, TYP.
CMU WALL
SLAB ON GRADE
FOOTING OR THICKENED
SLAB, SIM.
DOWEL WITH STANDARD
HOOK, TYP.
NOTES:
1. REFER TO PLANS AND SCHEDULES FOR SIZE, NUMBER AND LOCATION OF VERTICAL REINFORCING.
2. CLEAN-OUTS AND HJR NOT SHOWN BUT ARE REQUIRED, SEE SPECIFICATIONS.
3. SPLICE LOCATIONS ARE DIAGRAMMATIC. SPLICE AS REQUIRED.
DIAGRAMMATIC ELEVATION
AT SINGLE STORY WALL
SCHEDULED REINFORCING,
TYP.
SP
LI
C E
SC
H
ED
U
LE
D
SP
LI
C E
SC
H
ED
U
LE
D
TOW
SEE PLAN
SIM
TOF
SEE PLAN
TOSL
SEE PLAN
CMU WALL
LINTEL
REINFORCING
JAMB
REINFORCING
SILL
REINFORCING
TYP
1'-4"
C
LR2"
SP
LI
C E
SC
H
ED
U
LE
D
SP
LI
C E
SC
H
ED
U
LE
D
REINFORCING SIZE AND
SPACING SAME AS WALL
ADJACENT TO OPENING
(UNO)
MATCH REINFORCING
FROM BELOW OPENING
DIAGRAMMATIC ELEVATION
WINDOW OPENING IN CMU (DOOR SIMILAR)
NOTES:
1. REFER TO PLANS AND SCHEDULES FOR SIZE, NUMBER AND LOCATION OF VERTICAL REINFORCING.
2. CLEAN-OUTS AND HJR NOT SHOWN BUT ARE REQUIRED, ,SEE SPECIFICATIONS.
3. SPLICE LOCATIONS ARE DIAGRAMMATIC. SPLICE AS REQUIRED.
C
LR2"
PREFABRICATE
D CORNER
JOINT
REINFORCING
REINFORCE 3 CELLS @ EACH
CORNER W/ SCHEDULED
WALL REINFORCING
REINFORCE 2 CELLS @ EACH
INTERSECTION W/
SCHEDULED WALL
REINFORCING
PREFABRICATED
TEE JOINT
REINFORCING
WALL REINFORCING
(HOOKS NOT SHOWN),
SEE PLAN
SEE SECTIONS, DETAILS
OR SCHEDULES FOR BEAM
REINFORCING
CONCRETE OR
MASONRY BEAMS
ADD CORNER BARS TO ALL HORIZONTAL
REINFORCING, LAP 48 BAR DIAMETERS
BEAM REINFORCING AT CORNERS / INTERSECTIONS
WALL REINFORCING AT CORNERS / INTERSECTIONS
LA
P, T
YP
B
AR
D
IA
M
ET
ER
WIDTH
SCHEDULED
WIDTH
SCHEDULED
FULL MORTAR
BED
FILL SOLID
WITH
GROUT
REINFORCED CONCRETE MASONRY UNIT (CMU) LINTELS
SCHEDULED TOP
REINFORCING
SCHEDULED
BOTTOM
REINFORCING
SCHEDULED
TIES (WHERE
REQUIRED)
MASONRY
OPENING
WIDTH
8" 12"
UP TO 4'-0" 1-#4 B
UP TO 16'-0"
UP TO 12'-0"
8"
32"
24"
REINFORCED CMU LINTEL SCHEDULE
6"
8"
NOMINAL CMU WIDTH
MINIMUM
END
BEARING
STIRRUP
SIZE &
SPACING
UP TO 6'-0"
UP TO 8'-0"
UP TO 10'-0"
UP TO 14'-0"
8"
8"
8"
16"
16"
16"
16"
#3@8"OC
#3@12"OC
#3@12"OC
16"
16"
1-#5 B & T
1-#5 B & T
16"
16"
24"
32"
REINFORCING
NOMINAL
DEPTH
2-#4 B
2-#4 B & T
2-#4 B & T
2-#5 B & T
2-#5 B & T
2-#5 B & T
2-#5 B & T
8"
32"
24"
16"
16"
24"
32"
2-#4 B
2-#4 B & T
2-#4 B & T
2-#6 B & T
2-#6 B & T
2-#6 B & T
2-#6 B & T
REINFORCED CMU LINTEL SCHEDULE NOTES:
1. MASONRY DIMENSIONS INDICATED ARE NOMINAL RATHER THAN ACTUAL DIMENSIONS.
2. MINIMUM MASONRY STRENGTH f'm SHALL BE 2000 PSI (UNLESS NOTED OTHERWISE).
3. GROUT FILL SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF 3000 PSI AT 28 DAYS OR MEET
ASTM C476.
4. SEE ARCHITECTURAL DRAWINGS FOR SIZE AND LOCATIONS OF OPENINGS IN MASONRY WALLS
REQUIRING LINTELS.
5. TOP AND BOTTOM REINFORCING SHALL EXTEND A MINIMUM OF 16" OVER SUPPORT AT EACH END.
6. HORIZONTAL WALL REINFORCING SHALL CONTINUE THROUGH MASONRY LINTELS. WHERE BOTH HORIZONTAL WALL REINFORCING AND LINTEL REINFORCING WOULD OCCUR IN THE SAME COURSE, THE LARGER BARS SHALL BE USED.
7. EXTEND VERTICAL REINFORCING THROUGH LINTEL AT BEARINGS WHERE END VERTICAL CELL IS
REINFORCED.
8. FOR WALL ABOVE LINTEL, DOWEL VERTICAL REINFORCING INTO FULL DEPTH OF THE LINTEL OR 48
BAR DIAMETERS, WHICHEVER IS LESS.
9. HORIZONTAL JOINT REINFORCING:
A. PROVIDE STANDARD LADDER REINFORCING AT 16" OC IN LINTEL SPANS UP TO 6'.
B. PROVIDE STANDARD LADDER REINFORCING AT 8" OC IN LINTEL SPANS UP TO 12'.
C. PROVIDE HEAVY (W2.8) LADDER REINFORCING AT 8" OC IN LINTEL SPANS OVER 12'.
10. FOR CONTINUOUS LINTEL REINFORCING WHERE SPLICES ARE REQUIRED, SPLICE TOP BARS AT
MID-SPAN OF OPENINGS AND BOTTOM BARS AT PIERS OR SUPPORT LOCATIONS.
11. GROUT MASONRY LINTELS MONOLITHICALLY WITH THE SUPPORT WALL OR COLUMN AT EACH END.
12. TYPICAL LINTELS SHOWN ARE TO BE USED WHERE NO SPECIFIC LINTEL OR CAST-IN-PLACE
CONCRETE BEAM HAVE BEEN DETAILED AND ARE FOR SUPPORT OF WALL LOADS ONLY (UNO).
REINFORCING
NOMINAL
DEPTH REINFORCING
NOMINAL
DEPTH
D
EP
TH
SC
H
ED
U
LE
D
D
EP
TH
SC
H
ED
U
LE
D
2 PER CELL,
SEE SCHEDULE
1 PER CELL,
SEE SCHEDULE
JAMB
OPENING WIDTH
MASONRY JAMB
MASONRY
OPENING
WIDTH
NUMBER OF REINFORCED CELLS PER JAMB
UP TO 3'-4"
JAMB REINFORCING SCHEDULE
2-#5 PER CELL
IN 2 CELLS
OPENING IN
EXTERIOR WALL
OPENING IN
INTERIOR WALL
SPLICE LENGTH
1-#5 PER CELL
IN 1 CELL
45"
UP TO 6'-8" 2-#6 PER CELL
IN 3 CELLS
1-#5 PER CELL
IN 2 CELLS 54"
UP TO 8'-2" 2-#6 PER CELL
IN 4 CELLS N.A. 54"
8"
VA
R
IE
S, S
EE
PL
U
M B.
D W
G S.
AN
D
S
PE
C S.
8" M
IN
8"
SEE PLUMB.
DWGS.
AND SPECS. 8"
#5 @ 12"O.C. MAX., TYP.
36"
TYPICAL TRENCH FRAME,
SEE PLUMBING DWGS FOR
SIZE AND MANUFACTURER
FOR FRAME DETAILS, TYP.
NOTE:
TRENCH DRAIN FLOOR TO SLOPE TO
DRAIN PIPE, SEE PLUMB. DWGS. FOR
LOCATION OF DRAIN PIPE.
SLAB ON VAPOR BARRIER ON
COMPACTED FILL, TYP.
SEE PLAN FOR SLAB REINF.
SLAB ON VAPOR
BARRIER ON COMPACTED
FILL, TYP. SEE PLAN FOR
SLAB REINF.
(4)#5 CONT., TYP.
2" MUD SLAB AS
REQUIRED, TYP.
SETTING RODS
FOR TRENCH
DRAIN, IF
REQUIRED, TYP.
36"
SCALE: = NTS
A1RE-ENTRY CORNER REINFORCING DETAIL
SCALE: = NTS
A2TYP SLAB ON GRADE JOINTS - APPARATUS BAY
SCALE: = NTS
A3WALL CONTRIL JOINT DETAIL
SCALE: = NTS
A4CMU WALL VERTICAL REINFORCING DETAIL
SCALE: = NTS
B4WINDOW OPENING IN CMU DETAIL
SCALE: = NTS
B3WALL & BEAM REINFORCING AT CORNER DETAIL
SCALE: = NTS
B2CAST-PLACE CONCRETE LINTEL DETAIL
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
FOUNDATION
SECTIONS &
DETAILS
22003
06.23.2023
C O
UN
TY
R O
A D
S403
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
MEP ENGINEER
POWELL & HINKLE
ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FL 32073
CIVIL ENGINEER
GOODSON BERGEN &
ASSOC
11555 CENTRAL PARKWAY, SUITE 103
JACKSONVILLE, FL 32224
SCALE: 3/4" = 1'-0"
C3TYP MASONRY WALL REINF PLAN VIEW
SCALE: = NTS
C4TYPICAL TRENCH DETAIL
REVISIONS
# DATE DESCRIPTION
4 07/25/25 90% IRC REVIEW
5 02/17/26 ADD #1
8" CMU WALL WITH HORIZ.
JT. REINF. @ 16"O.C., TYP.
TYP. WALL REINF.,
SEE PLAN
T/BOND BEAM
EL. SEE PLAN
3/16" STIFFENER PLATE
EACH SIDE OF BEAM, TYP.
2"
STEEL BEAM,
SEE PLAN
BEARING PLATE,
REFER TO DETAIL A2/S603,
TYP. - 2" GROUT
GROUT BEAM POCKET SOLID WITH
GROUT SIMILAR TO CMU GROUT,
TYP.
A2/S603A2/S603
8"x16" BOND BEAM, SEE PLAN
CENTERLINE OF 8" CMU AND
ANCHOR BOLTS, TYP.
CONTINUOUS FACE SHELL
OF MASONRY ACROSS SEAT
BLOCKOUT, TYP.
1/
2"
1/
2" STEEL BEAM,
SEE PLAN
BEARING PLATE 3/4"x6"x1'-3" LONG w/ (2) 1" DIA. x 1'-2" LONG ANCHOR BOLTS w/
LEVELING NUTS AND (2) HEAVY WASHERS,
TYP. IN STANDARDS OVERSIZED HOLES
8" CMU WALL WITH HORIZ.
JT. REINF. @ 8"O.C., TYP.
CENTERLINE OF 8" CMU AND
ANCHOR BOLTS, TYP.
TYP.
1/4 1"
8" CMU WALL WITH HORIZ.
JT. REINF. @ 8"O.C., TYP.
TRUSS BEARING
EL. +19'-4"
TRUSS HOLD DOWN,
SEE PLAN
WOOD TRUSSES, SEE PLAN WOOD TRUSSES, SEE PLAN
(1) P.T. 2x8 TOP PLATE w/ (1)
1/2" DIA. A307 BOLTS AT 24"O.C.
STAGGERED, TYP.
STEEL BEAM, SEE PLAN
(2) 2x8 WOOD BLOCKING EACH SIDE OF BEAM WEB w/
1/2" DIA. BOLTS @ 24"O.C., TYP.
STEEL BEAM,
SEE PLANSTEEL BEAM,
SEE PLAN
STEEL COLUMN,
SEE PLAN
3/8" PLATE, TYP.
3" 3"
3" 3"
3/4" DIA. BOLTS, TYP.1/2"
2 1/2" 1 1/2"
4"
5/16
TYP.
CAP PLATE TO MATCH SIZE
AND WALL THICKNESS OF
COLUMN, TYP.
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
FRAMING
SECTIONS &
DETAILS
22003
06.23.2023
C O
UN
TY
R O
A D
S603
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
MEP ENGINEER
POWELL & HINKLE
ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FL 32073
CIVIL ENGINEER
GOODSON BERGEN &
ASSOC
11555 CENTRAL PARKWAY, SUITE 103
JACKSONVILLE, FL 32224
SCALE: 3/4" = 1'-0"
A1SECTION AT STEEL BEAM @ APP BAY
SCALE: 1 1/2" = 1'-0"
A2DETAIL CONNECTION AT STEEL BEAM @ APP BAY
SCALE: 1" = 1'-0"
B1SECTION AT STEEL BEAM @ TRUSS BEARING AT APP BAY
SCALE: 1" = 1'-0"
B2SECTION AT STEEL BEAM AND COLUMN
REVISIONS
# DATE DESCRIPTION
1 11/03/23 PERMIT REV 1
3 07/19/24 VE REV 1
5 02/17/26 ADD #1
| S001 - GENERAL NOTES |
| S002 - GENERAL NOTES |
| S003 - SCHEDULES |
| S004 - WIND PRESSURE DIAGRAMS |
| S101 - FOUNDATION & SLAB PLAN |
| S102 - WELL HOUSE FRAMING PLANS |
| S201 - ROOF FRAMING PLAN |
| S401 - FOUNDATION SECTIONS & DETAILS |
| S402 - FOUNDATION SECTIONS & DETAILS |
| S403 - FOUNDATION SECTIONS & DETAILS |
| S404 - FOUNDATION SECTIONS & DETAILS |
| S601 - FRAMING SECTIONS & DETAILS |
| S602 - FRAMING SECTIONS & DETAILS |
| S603 - FRAMING SECTIONS & DETAILS |
| S604 - FRAMING SECTIONS & DETAILS |