Clay_Co_FS24_Plumb_(2026_01-02)_Bid_Set.pdf
PDF 4 MB Posted
- Attached to
- Construction of Clay County Fire Station No. 24
- Solicitation number
- 25/26-042
- Issued by
- Clay County, Harold CDP, Florida
About this file
This is a plumbing bid set document prepared by Powell & Hinkle Engineering, P.A. and Dasher Hurst Architects, P.A. for Clay County Fire Station No. 24 located at 1075 County Road 226 in Green Cove Springs, Florida. The plumbing system design encompasses a comprehensive four-sheet package including floor plans, roof plans, enlarged detailed plans, riser diagrams for sanitary waste, domestic water, and gas piping systems. The project includes fixture installations throughout the approximately 16,633 square-foot fire station facility, featuring multiple restrooms, kitchen facilities, dining areas, bunk rooms, and service areas across floors. Key plumbing components specified include fixtures such as water closets, urinals, lavatories, showers with trench drains, floor drains, mop sinks, water coolers, and equipment connections. Mechanical systems include electric water heaters (80-gallon and 50-gallon models), hot water recirculating pump, grease interceptor rated at 50 GPM with 439.5 lb grease capacity, oil/water/sand separator (minimum 568.48 gallons), and comprehensive piping networks in copper and PVC with sizes ranging from 1/2 inch to 4 inches. The design incorporates backflow preventers, balancing valves, water hammer arrestors, trap primers, and freeze-proof hydrants. Gas piping system is sized for 310 CFH at 2 PSI with equipment connections to kitchen appliances and a gas pressure regulator. The plumbing plans contain detailed specifications for all fixture models, manufacturers, and installation requirements, with revisions dated through September 5, 2025 for 90% IRC review compliance.
The specifications include detailed equipment schedules with brand-specific selections such as American Standard, Kohler, Elkay, Moen, Symmons, and Zurn products. The design incorporates ADA compliance requirements throughout fixture and supply line installations. Drain systems are engineered per Florida Plumbing Code Section 1003.4.2.2 with calculations for oil/water separator sizing based on apparatus bay floor area of 7,061 square feet. The grease interceptor is sized for 72 meals per day with 90-day pump-out intervals and calculated fat, oil, and grease production of 294.84 pounds. Gas piping is designed per the 2003 Florida Fuel Gas Code with total developed length calculations of 300 feet at 2 PSI and 175 feet at 11 inches WC, incorporating pressure relief valves, shut-off solenoid interlocked with the fire alarm system, and gas control valves interlocked with hood fire protection systems. The construction documents require coordination with civil drawings for exterior utility connections, structural drawings for mounting and bracing, HVAC plans for equipment clearance, and electrical plans to avoid conflicts with panels and service equipment. All work must comply with applicable Florida Building Code requirements and be installed in a neat, workmanlike manner by qualified trades professionals.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
TD-1 TD-1 TD-1 TD-1
TD-1TD-1TD-1TD-1
P201
P201
P201
P201
OIL/WATER/SAND SEPARATOR CALCULATIONS:
APPARATUS BAY FLOOR AREA IS 7061 SQ.FT. 7100
SQ.FT. USED FOR OIL/WATER SEPARATOR SIZING. PER
FLORIDA PLUMBING CODE SECTION 1003.4.2.2, PROVIDE
6 CU.FT FOR THE FIRST 100 SQ.FT. AND 1 CU.FT. FOR
EACH ADDITIONAL 100 SQ.FT. MINIMUM 76 CU.FT.
REQUIRED. I CU.FT. = 7.48 GALLONS. MINIMUM
OIL/WATER SEPARATOR SIZE FOR FLOOR AREA IS
568.48 GALLONS.
CO-3
CO-3 CO-3
SEE CIVIL
DWG FOR
CONT.
INV. ELEV.
-2.75'±
SEE CIVIL
DWG FOR
CONT.
INV. ELEV.
-2.75'±
CO-3
FIRE LINE
SHOWN FOR
COORDINATION
SEE CIVIL
DWG FOR
CONT.
SEE CIVIL
DWG FOR
CONT.
TO GREASE
INTERCEPTOR.
SEE CIVIL DWG
FOR CONT.
2 1/2"
CO-3
INV. ELEV.
-2.00'±
3"
TP-2
INV. ELEV.
-5.00'±
CO-3
4" 4" 3"4"4"
CO-2
SEE CIVIL
DWG FOR
CONT.
CO-3
INV. ELEV.
-2.70'±
3"
" 3
3" 3"
CO-2
1 ROOF DRAIN DOWN FROM ROOF.
SEE PLUMBING ROOF PLAN ON SHEET "P1.2" FOR CONT.
HB-1
SHUT-OFF VALVE WITH
VALVE BOX WITH
COVER FLUSH WITH
FINISHED GRADE
LP GAS PIPE BELOW
GRADE TO LP GAS
TANK. MINIMUM 2 PSI.
310 CFH.
SEE CIVIL DWG FOR
CONT.
GAS PRESSURE
REGULATOR
100 CFH @ 11' W.C.
C
F H
' W
.C
/4
1 1/4"
3/4" 2 1/2"
/2
2 1/2"
4"4"
2 1/2"
4"4"
4" 4" 4" 4"
3/4"
/4
3/4" 3/4"
1 1/4"
3/4"
/2
H
W R4
/4
/4
/4
H
W R
/2
2"
4" 4"
2 1/2"
4" 4"
2 1/2"
4" 4" 4"
4"
/2
H
W R
/2
CONNECT TO EQUIPMENT. PROVIDE WITH GAS
PRESSURE REGULATOR AS REQUIRED. COORDINATE
WITH EQUIPMENT MANUFACTURER FOR CONNECTION
REQUIREMENTS.
4 1/2" TRAP PRIMER LINE.
HB-1
HB-1
HB-1
HB-1
HB-1
HB-1
/4
3/4"
1"
/4
/4
HB-1
HB-1
GAS SOLENOID
INTERLOCKED WITH
FIRE ALARM
LOBBY
DAY ROOM
APP BAY
MEN
WOMEN
MEETING
WATCH
UTIL
OFFICE
ELEC
IT
DINING
BUNK1
BUNK2
BUNK3
BUNK4
BUNK5
BUNK6
BUNK8
BUNK9
BUNK10
MAINT
CAPT SUITE
KITCHEN
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
PLUMBING
FLOOR PLAN
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
P101
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1/8" = 1'-0"
PLUMBING FLOOR PLAN
PLUMBING FLOOR PLANP101
SHEET NO.
"TO THE BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE,
THE PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
MINIMUM BUILDING CODES AND THE APPLICABLE FIRE-SAFETY
STANDARDS AS DETERMINED BY THE LOCAL AUTHORITY IN
ACCORDANCE WITH THIS SECTION AND CHANPTER 633, FLORIDA
STATUTES."
SHEET TITLE
P301 RISER DIAGRAMS
PLUMBING SHEET INDEX
LEGEND, SCHEDULE & MISC. DETAILSP401
PLUMBING ROOF PLANP102
P201 ENLARGED PLUMBING PLANS
P302 RISER DIAGRAMS
MISC. DETAILSP402
P303 RISER DIAGRAMS
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 PERMIT REV 1
2 07/19/2024 VE Rev 1
3"VTR 2"VTR
RD-1
40 GPM
RD-1
40 GPM
3"VTR
2"VTR
3"VTR
3"VTR
2"VTR
3"VTR
3"
3"
1 ROOF DRAIN DOWN TO FLOOR BELOW.
SEE PLUMBING FLOOR PLAN ON SHEET "P1.1" FOR CONT.
2 ROOF DRAIN DOWN TO FLOOR BELOW.
SEE ENLARGED PLUMBING PLAN "P1.1A" ON SHEET "P2.1" FOR CONT.
G U
T T
E R
A N
D D
O W
N
S P
O U
T S
S
IZ
E D
F O
R
G
P M
G U
T T
E R
A N
D D
O W
N S
P O
U T
S S
IZ
E
D F
O R
G
P M
G U
T T
E R
A N
D D
O W
N S
P O
U T
S S
IZ
E
D F
O R
G
P M
G U
T T
E R
A N
D D
O
O U
T S
S
IZ
E D
F O
R
G
P M
G U
T T
E R
A N
D D
O
O U
T S
S
IZ
E D
F O
R
G
P M
G U
T T
E R
A N
D D
O W
N S
P O
U T
S S
IZ
E
D F
O R
G
P M
G
U T
T E
R A
N D
D O
W N
S P
O U
T S
S
IZ
E D
F O
R
G
P M
G U
T T
E R
A N
D D
O
O U
T S
S
IZ
E D
F O
R
G
P M
G U
T T
E R
A N
D D
O W
N S
P O
U T
S S
IZ
E
D F
O R
G
P M
G U
T T
E R
A N
D D
O
O U
T S
S
IZ
E D
F O
R
G
P M
GUTTER AND DOWN
SPOUTS SIZED FOR 95 GPM.
GUTTER AND DOWN
SPOUTS SIZED FOR 95 GPM.
G U
T T
E R
A N
D D
O
O U
T S
S
IZ
E D
F O
R
G
P M
G U
T T
E R
A N
D D
O W
N S
P O
U T
IZ
E D
F O
R
G P
M
OVERFLOW SCUPPER
SIZED FOR 40 GPM.
SEE ARCHITECTURAL
PLANS FOR ADDITION
INFORMATION.
OVERFLOW SCUPPER
SIZED FOR 40 GPM.
SEE ARCHITECTURAL
PLANS FOR ADDITION
INFORMATION.
HB-3
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
PLUMBING
ROOF PLAN
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
P102
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
REVISIONS
# DATE DESCRIPTION
2 12/11/2023 PERMIT REV 2
F-1
FD-1
F-4A
F-13
TP-1
F-1
FD-1
F-4A LI-2
TD-2 WH-2 T
P
-1
TP-2
HD-1
CO-2
CO-2
F-6A
BWV
3"
/4
3" 3" 3"
3/4"
/4
/4
/4
/2
/2
/4
/4
/2
3"
" BV-1
F -1
HB-2
C O
-1
C O
-1
/4
3/4"
F-1
FD-1
F-2
F-3
F-5H F-1
F-1
F-2
F-3
F-3
FD-1
F-5
F-5
F-5
F-5H
FD-1
F-3
F-3
F-1
F-1HD-1
BF-1
F-9
F-9
F-9
WH-1
FD-1
F-8
F-12A
BF-1
F-9
FD-1
F-12
HD-1
TP-2
TP-1
TP-1
TP-2
BV-1
BV-1
F-10
F-8
CO-1
CO-1
F -6C
P -1
CO-1
LI-1
1"
/4
1"
1"
3"
/4
3/4"
/2
/4
/4
4"
3"
4"4"
2"
/2
2"
2"1 1/2"
/2
H
W R
BV-1
BV-1
1/2" HWR
1/2" HWR3/4" HWR
1" HWR
H W
R
H W
R
1 1/4"
1 1/4"
3"3"
CO-2
/4
H
W R
1/2" HWR
/2
3"
2" 2"
2"
1"
1"
/2
3/4"
/4
C
F H
W .C
100 CFH @ 11" W.C.
/4
/2
210 CFH @ 11" W.C.
HB-1
F-6A
FD-1
F-1
F-3
TP-1
F-5
3"
2"
3/4"
1 1/4"
2"
/4
F-1
FD-1
F -3 T
P -1
HD-1
BV-1
1 1/4"
3/4"
1/2" HWR
2"
3"
3"
3"
C O
-1
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
ENLARGED
PLUMBING
PLANS
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
P201
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1/4" = 1'-0"
ENLARGED PLUMBING PLAN "P1.1A"
1/4" = 1'-0"
ENLARGED PLUMBING PLAN "P1.1B"
1/4" = 1'-0"
ENLARGED PLUMBING PLAN "P1.1C"
1/4" = 1'-0"
ENLARGED PLUMBING PLAN "P1.1D"
2 STORM DRAIN DOWN FROM ROOF.
SEE PLUMBING ROOF PLAN ON SHEET "P1.2" FOR CONTUATION.
3 STORM DRAIN DOWN FROM ROOF.
SEE PLUMBING ROOF PLAN ON SHEET "P1.2" FOR CONTUATION.
1 1 1 1 1 1 1 1 1
1 SEE PLUMBING FLOOR PLAN ON SHEET "P1.1" FOR CONTUATION.
1 SEE PLUMBING FLOOR PLAN ON SHEET "P1.1" FOR CONTUATION.
1 SEE PLUMBING FLOOR PLAN ON SHEET "P1.1" FOR CONTUATION.
4 1/2" TRAP PRIMER LINE.
2 1/2" TRAP PRIMER LINE.
2 1/2" TRAP PRIMER LINE.
1 SEE PLUMBING FLOOR PLAN ON SHEET "P1.1" FOR CONTUATION.
2 1/2" TRAP PRIMER LINE.
1 1 1 11 1 11
1 1
CONNECT TO EQUIPMENT. PROVIDE WITH GAS PRESSURE
REGULATOR AS REQUIRED. COORDINATE WITH EQUIPMENT
MANUFACTURER FOR CONNECTION REQUIREMENTS.
GAS CONTROL VALVE, INTERLOCK WITH HOOD FIRE PROTECTION
SYSTEM. VALVE FURNISHED BY HOOD FIRE PROTECTION SYSTEM
MANUFACTURER, INSTALLED BY PLUMBING CONTRACTOR.
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 PERMIT REV 1
2 12/11/2023 PERMIT REV 2
3 09/05/2025 90% IRC REVIEW
5 OFFSET VENT IN WALL TO PROVIDE CLEARANCE FOR ELECTRICAL
BOX FOR LIGHT.
5 OFFSET VENT IN WALL TO PROVIDE CLEARANCE FOR ELECTRICAL
BOX FOR LIGHT.
3 OFFSET VENT IN WALL TO PROVIDE CLEARANCE FOR ELECTRICAL
BOX FOR LIGHT.
F-1
FD-1
HD-1
F-3
3"
3"
3"
4" 4"
4"
2"
4"
4"
4"
4"
CO-3
2"VTR
F-3
F-1
FD-1
F-5
SEE CIVIL
DWG. FOR
CONT.
INV. ELEV.
-5.00'±
3" 3"
3" 3"
2"
3"
3"
2"
4"
4"
3"
3"
3" 3"
3"
4"
4"
3"
3"
3"
3"
3"
4"
4"
4"
3" 3"
3"
3"
3"
3"
3"3"
3" 3"
"2
2" 2"
2"
2"
3" 3"
3"
4"
4"
3"
4"
3"
4"
3"
3" 3"
3" 3"
3"
3"
2" 2"
"3
" 3"
SEE CIVIL
DWG. FOR
CONT.
SEE CIVIL
DWG. FOR
CONT.
SEE CIVIL
DWG. FOR
CONT.
SEE CIVIL
DWG. FOR
CONT.
INV. ELEV.
-2.00'±
CO-3
AIR
ADMITTANCE
VALVE
3"
3"
2"VTR
F-5HCO-1
CO-1
CO-3
CO-3
CO-3
CO-2
F-1
F-1
RD-1
HD-1
FD-1
F-1
F-1
F-1
F-2
F-2
FD-1
FD-1
CO-1
CO-1
CO-1
2"
2"
2"
3"2
3"
3"
3"
2"
2"
2"
3"
2"
2" 3
3"
4"
3"
4"
3"
2"
3"
2"
3"
3" 3"
4"
4" 3"
3"4"
3" 3"
3" 2"
"2"
4"
3"
3"
2"
3"
2" 2
F-3
F-3
F-3
F-5
F-5
F-5
F-5H
CO-2
2" 4"
4"
CO-1
CO-1
F-12
TD-1
TD-1
TD-1
TD-1
TD-1
TD-1
TD-1
TD-1
INV. ELEV.
-2.70'±
CO-3
CO-3
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
4"
6"
6"
6"
6"
6"
6"
6"
6"
"3"
3"
CO-2
BWVLI-2
RD-1
2"VTR3"VTR
3"
3"VTR
HD-1
FD-1
F-7
F-6
2"
3"
4"
4"
4"
4"
4"
4"
4"
CO-2
TD-2
CO-1
CO-2
F-11
HD-1
F-6A
4"
3"
3"
3"
3"
2"
3"
2"
2"
3"
3"VTR
CO-2
F-1
F-1
FD-1
FD-1
F-4A
F-4A
F-13
CO-1
F-3
F-3
INV. ELEV.
-2.75'±
INV. ELEV.
-2.75'±
F-8
F-10
FD-1
3"VTR
3"VTR
2"
3"
FD-1
3"
F-6A
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
PLUMBING
RISER
DIAGRAMS
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
P301
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1 1/2" TRAP PRIMER LINE.
SANITARY RISER DIAGRAM
NOT TO SCALE
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 PERMIT REV 1
2 12/11/2023 PERMIT REV 2
3 07/19/2024 VE Rev 1
4 09/05/2025 90% IRC REVIEW
2 OFFSET VENT IN WALL TO PROVIDE CLEARANCE
FOR ELECTRICAL BOX.
HB-1 SA
1"
/4
TP-2
2 1/2"
/2
SEE CIVIL
DWG FOR
CONT.
SHUT-OFF VALVE WITH
VALVE BOX WITH
COVER FLUSH WITH
FINISHED GRADE
HB-1
/4
/4
3/4"
2 1/2"
2 1/2"
2 1/2"
2 1/2"
/4
/4
SASA
SA
F-12
F-3 F-3
F-5H
SA
SASA
/2
/4
TP-2
TP-2
TP-1
F-5H F-5
F-5 F-5
1/2" HWR
1/2" H
WR
3/4" H
WR BV-1
BV-1
TP-2
HB-1
SASA
SA
SA
SA
SA
1" H
WR
1" HWR
1/2" HWR
1/2" HWR
SA
SA
SA
3/4" HWR
E-1
TP-1
WH-2
/4
/4
1 1/4"
3/4" 3/4"
1 1/4" 3/4"3/4"
1 1/4"
/4
/4
/2
/2
/4
/2
"1 /2
1/2"
3/4"
1/2" 1/2"
1/2" H
WR
SA
SA
SA
SA
SA
SA
/2
1/2"
3/4"
3/4"
/4
/4
F-11
F-13
F-1
F-1
F-4A
F-4A
1 1/2"
3/4"
/4
/4
1/2" HWR
SA
SA
TP-1
1"
1 1/2"
/4
"3 /4
/4
/4
1"
1"
1" 1"
1 1/4"
1 1/4"
3/4"
3/4"
/2
/2
/2
/2
/4
/4
/4
/4
F-6A
F-3
F-3
F-3
1/2" H
WR
1/2"
3/4" 1"
1"
1"
1 1/2"
1 1/2" 1 1/2"
2"
2"
2 1/2"
/4
/4
/4
F-1
F-1
F-1
F-6
F-2F-9
F-9
CP-1
WH-1
F-2
BF-1
BF-1
F-9
SA
SA
SA
SA
1/2" HWR
SA
HB-1
F-8
F-10
/4
3/4"
/4
/4
/4
3/4"
3/4" CW & HW
BELOW FINISHED
FLOOR
3/4"
1" 1"
3/4"3/4"
3/4" 3/4"
/4
1"
1 1/2"
2"
2"
1 1/4"
1 1/2"
1 1/2"
2"
/4
/4
1" 1"
2 1/2"
/2
1"
3/4"
3/4" 3/4"
F-1
F-1
1 1/4"1 1/2"
3/4"
1"
1"
2 1/2"
BV-1
2 1/2"
2 1/2"
1/2"
/2
1" 2"
2 1/2"
2 1/2"
BV-1
BV-1
1/2" H
WR
1"
1 1/2"
1 1/4"
1 1/2"
1 1/2"
1" H
WR
/4
/4
1"
1"
/4
/4
/4
/4
F-8
F-12
/4
BV-1
BV-1
3/4" H
WR
1/2" H
WR
1/2" HWR
1/2" HWR
SASA
SA
SA
SA
SA
HB-1
HB-1
3/4"
3/4"
3/4"
1"
3/4"
3/4"
/4
/4 "1
/2
/2
/2
H
W R
3/4" 3/4" 1 1/4"
1 1/4"
1 1/4"
1 1/4"
3/4"
1 1/4"
1 1/2"
1 1/4"
1 1/4"
3/4"
3/4"
/4
/4
/4
/2
/4
/2
H
W R
1"
SA
SA
F-1
F-5
F-3
TP-1
F-1
F-3 TP-1
SA
F-9
HB-1
HB-1
/4
1"
1"
/4
3/4"
/4
/4
1"
1"
/4
/4
HB-1
/4
/4
3/4"
HB-2
3/4"
3/4"
/4
1"
1 1/4"
F-6A
/4
/4
" 3 /4
"3 /4
" 3 /4
/2
HB-3
/4
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
PLUMBING
RISER
DIAGRAMS
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
P302
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1 1/2" TRAP PRIMER LINE.
DOMESTIC WATER RISER DIAGRAM
NOT TO SCALE
2 CONNECT TO EQUIPMENT. PROVIDE WITH GAS PRESSURE
REGULATOR AS REQUIRED. COORDINATE WITH EQUIPMENT
MANUFACTURER FOR CONNECTION REQUIREMENTS.
REVISIONS
# DATE DESCRIPTION
FLOWGAS PIPE MAIN
GAS COCK
GAS PRESSURE REGULATOR PER
SPECIFICATIONS AND SCHEDULE.
INSTALL IN ORIENTATION PER
MANUFACTURER REQUIREMENTS.
PROVIDE RELIEF VENT LINE WERE
NOTED ON PLANS.
PIPE INCREASER
CONNECT BRANCH TO
TOP OF MAIN, TO
ALLOW FOR EXPANSION
AND CONTRACTION OF
MAIN PIPE RUN
REFER TO PLANS FOR PIPE SIZE(S). ARRANGEMENT SHOWN IS SCHEMATIC. ADJUST
TO SUIT FIELD CONDITIONS. PROVIDE CONNECTIONS SHOWN IN EQUIPMENT
MANUFACTURER'S INSTALLATION INSTRUCTIONS. VERIFY CONNECTION LOCATIONS
BEFORE INSTALL PIPE RUNS. REFER TO SPECIFICATIONS FOR PIPE AND FITTING
MATERIALS AND INSTALLATION. PROVIDE GAS COCK, UNION AND DIRT LEG SAME SIZE
AS BRANCH PIPE.
3" LONG LINE SIZE DIRT
LEG WITH MINIMUM 4"
CLEAR BELOW
LINE SIZE TEE, EXIT
THRU SIDE OUTLET
GROUND JOINT PIPE
UNION
INSTALL CAP AND TEE
TEN PIPE DIAMETERS
MINIMUM DOWNSTREAM OF
GAS PRESSURE REGULATOR
PIPE CONTINUATION
TO EQUIPMENT.
PROVIDE REDUCER
AT EQUIPMENT
100 CFH @
11"W
.C.
LP GAS PIPE BELOW
GRADE TO LP GAS
TANK. MINIMUM 2 PSI.
310 CFH.
SEE CIVIL DWG FOR
CONT.
GAS PRESSURE
REGULATOR
C
F H
"W
.C
C
F H
"W
.C
100 CFH @
11"W
.C.
GAS CONTROL VALVE, INTERLOCK WITH HOOD FIRE
PROTECTION SYSTEM. VALVE FURNISHED BY HOOD FIRE
PROTECTION SYSTEM MANUFACTURER, INSTALLED BY
PLUMBING CONTRACTOR.
E-1
E-1
/4
3/4"
3/4"
3/4"
3/4"
1"
EQUIPMENT GAS CONNECTION
SCALE: NTS (KITCHEN EQUIPMMENT ONLY)
GALVANIZED STEEL
GAS MAIN
SEDIMENT TRAP
TO EQUIPMENT
STAINLESS STEEL
FLEX HOSE
QUICK DISCONNECT
GAS
VALVE
EASY
READ
ON/OFF
REQ'D. PIPE SIZE
RANGE
FIXTURE
BUILDING GAS DEMAND
TOTAL CFH
E-1
MARK CONN.
1"
EACH
MBH
EACH
QTY.
ALL
MBH
GRILLEE-1
SYSTEM SIZED FOR 2.0 PSI WITH A PRESSURE DROP OF 1.0 PSI (1.50 SPECIFIC
GRAVITY) AND A DELIVERY OF 11" WC WITH A PRESSURE DROP OF 0.5" WC OR
LESS PER TABLES 402.4(27) AND 402.4(28) OF THE 2003 FLORIDA FUEL GAS CODE.
2 PSI GAS PIPE SIZED FOR A TOTAL DEVELOPED LENGTH (TDL) OF 300'.
11" WC GAS PIPE SIZED FOR A TOTAL DEVELOPED LENGTH (TDL) OF 175'.
MBH RATING FOR EQUIPMENT IS DETERMINED BY THE MANUFACTURER.
WHERE NOT PROVIDED AS PART OF THE GAS APPLIANCE, WHERE REQUIRED BY
EQUIPMENT MANUFACTURER, PLUMBING CONTRACTOR SHALL PROVIDE AND INSTALL
APPLIANCE (LINE) GAS PRESSURE REGULATORS TO REDUCE GAS SUPPLY PRESSURE
DOWN TO MANUFACTURER REQUIRED APPLIANCE OPERATING PRESSURES. APPLIANCE
(LINE) GAS PRESSURE REGULATORS SHALL COMPLY WITH NFPA, SHALL BE LISTED IN
ACCORDANCE WITH NFPA, AND SHALL BE EQUIPPED WITH AND LABELED FOR
UTILIZATION WITH AN APPROVED FACTORY INSTALLED VENT-LIMITING DEVICE IN
ACCORDANCE WITH THE MANUFACTURERS INSTRUCTIONS AND NFPA.
DETAIL - GAS SERVICE ENTRANCE
NOT TO SCALE
GRADEGRADE
GAS PRESSURE
REGULATOR
ELBOW SEISMIC
SWING JOINT (TYP).
UTILITY SERVICE SHUT-OFF
VALVE. LOCKABLE (TYP).
UNION (TYP).
GAS RATED SHUT-OFF
SOLENOID VALVE INTERLOCKED
WITH FIRE ALARM SYSTEM.
GAS METER
SEE SPECIFICATION
SECTION 33-51-15
FOR METER &
REGULATOR
REQUIREMENTS.
GAS PIPING FROM UTILITY, SEE
CIVIL PLANS FOR CONTINUATION. SEE
CIVIL DETAILS REQUIREMENTS
GAS PIPING
TO BUILDING
SCHEDULE 40 STEEL
SLEEVE SIZED TWO
PIPE SIZES LARGER
THAN PIPE LOCATED
WITHIN. SEAL IN
ACCORDANCE WITH
THE 2012
INTERNATIONAL FUEL
GAS CODE.
3/8" GAUGE
VALVE/FITTING WITH
PRESSURE GAGE.
LOCKABLE TYPE.
DIELECTRIC UNION
3/8" GAUGE
VALVE/FITTING WITH
PRESSURE GAGE.
LOCKABLE TYPE.
ELBOW SEISMIC
SWING JOINT (TYP).
CONCRETE
METER PAD
PROVIDE BELOW GRADE PIPE WITH TRACER
WIRE NO. 10 COPPER (THW.)
PROVIDE WARNING TAPE
8" TO 10" BELOW GRADE.
EXTERIOR WALL
SEE ARCHITECTURAL
DRAWINGS FOR WALL
CONSTRUCTION.
GAS METER
(MIN. XXXX MBH
CAPACITY).
DETAIL - GAS PRESSURE REGULATOR
NOT TO SCALE
DETAIL - GAS SERVICE ENTRANCE
NOT TO SCALE
SEE PLAN
FOR
CONT.
METALLIC OR PVC.
TERMINATE SLEEVE
1/2" ABOVE
FINISHED
FLOOR.
SEAL PER ALL
APPLICABLE CODE
REQUIREMENTS.
GAS SERVICE
TO BUILDING
EXTERIOR
WALL
FLOOR
SLEEVE THROUGH
FOUNDATION
WALL.
CONDUIT
VENTED
TO OUTDOORS.
INSECT SCREEN.
SOIL
SEAL PER ALL
APPLICABLE CODE
REQUIREMENTS.
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
PLUMBING
RISER
DIAGRAMS
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
P303
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
GAS PIPING RISER DIAGRAM
1/8" = 1'-0"
DETAILS4
NEW SHEET
REVISIONS
# DATE DESCRIPTION
1 07/19/2024 VE Rev 1
CL of 3" vent
CL of optional 2" oil draw-off
CL of 3" vent
OUTLET
INLET
CL of 3" vents
Engineered inlet and outlet diffuser (see description)
Static water line
CL of inlet & outlet
Inlet and outlet diffusers w/ inspection port
CL of optional 2" oil draw-off
140140
V
VTR
S
GW
LEGEND
VALVE (NORMAL CLOSE)
PRESSURE RELIEF VALVE
COLD WATER
(EXCEPT OTHERWISE NOTED)
BALL VALVE
UNION
S.A. SHOCK ABSORBER
WALL HYDRANT
HOT WATER
VENT LINE
SANITARY SEWER LINE
VENT THRU ROOF
GAS
EXISTING COLD WATER
EXISTING HOT WATER DEMOLITION
GREASE WASTE LINE
HOT WATER RECIRCULATING
140°F HOT WATER140°F HW RECIRCULATING
CONTROL VALVE/REGULATOR
STRAINER/FILTER
CHECK VALVE
ACCESS PANELA.P.
EXISTING VENT
EXISTING SANITARY SEWER
PIPE RISERS (DROP)
PIPE RISERS (UP)
PIPE END (CAPPED)
FLOOR DRAIN
TRAPPED DRAIN
FLOOR CLEANOUT
WALL CLEANOUT
TRAP
INVERT ELEVATIONINV. EL.
PLUMBING GENERAL NOTES
1. SEE SPECIFICATION FOR ADDITIONAL INFORMATION AND REQUIREMENTS.
2. COORDINATE HVAC EQUIPMENT AND DUCT LOCATION WITH HVAC CONTRACTOR. SEE MECH
DWGs. FOR ADDITIONAL INFORMATION.
3. DO NOT INSTALL PIPING ABOVE ELECTRICAL PANELS OR EQUIPMENT. COORDINATE ELECTRICAL
PANEL AND EQUIPMENT LOCATION WITH ELECTRICAL CONTRACTOR.
4. RUN ALL HORIZONTAL COLD & HOT WATER PIPING ABOVE CEILINGS UNLESS OTHERWISE NOTED.
5. EXTERIOR HOSE BIBS TO BE LOCATED 18" ABOVE GRADE UNLESS OTHERWISE NOTED.
6. INSTALL ALL WORK IN A NEAT AND WORKMANLIKE MANNER, USING ONLY WORKMEN
THOROUGHLY QUALIFIED IN THE TRADE OR DUTIES THEY ARE TO PERFORM. ROUGH WORK WILL BE
REJECTED.
7. MAINTAIN A MINIMUM 10' CLEARANCE BETWEEN HVAC EQUIPMENT FRESH AIR INTAKES AND
SANITARY VENTS.
8. FIELD VERIFY ALL EXISTING PIPING AND PIPING CONNECTION SIZES AND LOCATIONS. EXCEPT
OTHERWISE NOTED ON THE DRAWING, EXISTING CONCEALED PIPING NOT CONNECTED TO NEW
PLUMBING SYSTEM OR FIXTURES SHALL BE CAPPED BEHIND FINISHED WALL OR BELOW FLOOR AND
ABANDONED IN PLACE.
9. PROPERLY CONNECT NEW PLUMBING SYSTEM AND FIXTURES TO EXISTING SYSTEM. PROVIDE
NEW FITTINGS AS REQUIRED FOR PROPER CONNECTION.
10.FIELD VERIFY EXISTING BUILDING STRUCTURAL. NOTIFY GENERAL CONTRACTOR FOR
RESOLUTION IF EXISTING BUILDING STRUCTURE IMPEDES PLUMBING INSTALLATION. SEE
STRUCTURAL DRAWINGS FOR ADDITIONAL INFORMATION AND INSTRUCTION.
11.DOMESTIC WATER SHUT-OFF VALVES LOCATED ABOVE DRYWALL CEILINGS SHALL BE GROUPED
TOGETHER TO PROVIDE ACCESS FROM SINGLE ACCESS PANELS IF POSSIBLE. PROVIDE WITH
IDENTIFICATION TAG INDICATING AREAS THE VALVE CONTROLS.
12.CLEANOUTS ON 6" AND SMALLER PIPING SHALL BE PROVIDED WITH A CLEARANCE OF NOT LESS
THAN 18" FOR RODDING. CLEANOUTS ON 8" AND LARGER PIPING SHALL BE PROVIDED WITH A
CLEARANCE OF NOT LESS THAN 36" FOR RODDING.
ALL FIXTURES AND TRIM SELECTIONS SUBJECT TO OWNER/ARCHITECT/INTERIOR DESIGNER FINAL APPROVAL. ALL FIXTURE COLOR AND TRIM FINISH SELECTIONS SUBJECT TO THE OWNER/ARCHITECT/INTERIOR DESIGNER FINAL APPROVAL.
E-1 EQUIPMENT PROVIDED BY OTHER. PLUMBING CONTRACTOR TO PROVIDE AND INSTALL ALL REQUIRED ACCESSORIES (ie. WALL SUPPLIES, SUPPLY
LINES, DRAIN LINES, P-TRAP, ETC.) FOR A COMPLETE FINAL CONNECTION TO EQUIPMENT.
F-1 WHITE VITREOUS CHINA FLOOR MOUNTED FLUSH VALVE WATER CLOSET SYSTEM WITH ELONGATED BOWL FOR HANDICAPPED; AMERICAN STANDARD MADERA FLOWISE MODEL 3043.001. WITH AMERICAN STANDARD SELECTRONIC MODEL 606B.721 WITH DUAL FLUSH(1.28/1.1 GPF) HARD WIRED FLUSH VALVE AND AMERICAN STANDARD MODEL 5901.110 ELONGATED HEAVY DUTY BOWL OPEN FRONT SEAT LESS COVER WITH EVERCLEAN SURFACE. PROVIDE WITH AMERICAN STANDARD MODEL PK00.BBU.MAC POWER KIT BOLT CAPS WITH RETAINERS. INSTALL TO
COMPLY WITH A.D.A. REQUIREMENTS.
F-2 WHITE VITREOUS CHINA WALL HUNG FLUSH VALVE URINAL; AMERICAN STANDARD WASHBROOK FLOWISE MODEL 6590.001 WITH WITH AMERICAN STANDARD SELECTRONIC MODEL 606B.013 WITH FLUSH (0.125 GPF) HARD WIRED FLUSH VALVE. PROVIDE WITH FLOOR MOUNTED HEAVY DUTY
CARRIER.
F-3 WHITE VITREOUS CHINA UNDER COUNTER MOUNT LAVATORY FOR HANDICAPPED. KOHLER BRAZN MODELK-21058-0 WITH AMERICAN STANDARD COLONY PRO SINGLE LEVER 4" CENTER-SET FAUCET MODEL 7075.055, MCGUIRE MODEL 155WC OFFSET GRID DRAIN, 17 GA. POLISHED CHROME CAST BRASS P-TRAP AND LOOSE T-KEY WALL SUPPLIES. PROVIDE WITH LEONARD POINT OF USE MIXING VALVE MODEL 170 WITH RECESS MOUNTED LOCKING VALVE BOX. INSULATE SUPPLY AND DRAIN LINES TO COMPLY WITH A.D.A. REQUIREMENTS.
F-4 WHITE VITREOUS CHINA WALL HUNG LAVATORY FOR HANDICAPPED. AMERICAN STANDARD LUCERNE MODEL 0355.012 WITH AMERICAN STANDARD COLONY PRO SINGLE LEVER 4" CENTER-SET FAUCET MODEL 7075.055, MCGUIRE MODEL 155WC OFFSET GRID DRAIN, 17 GA. POLISHED CHROME CAST BRASS P-TRAP, LOOSE T-KEY WALL SUPPLIES AND HEAVY DUTY CHAIR CARRIER. PROVIDE WITH LEONARD POINT OF USE MIXING VALVE MODEL 170 WITH RECESS MOUNTED LOCKING VALVE BOX. INSULATE SUPPLY AND DRAIN LINES TO COMPLY WITH A.D.A. REQUIREMENTS.
F-4A SAME AS F-4 WITH DIFFERENT FAUCET, AMERICAN STANDARD INNSBROOK BATTERY POWERED SENSOR OPERATED FAUCET MODEL 6055.204 WITH 0.35 GPM SET FOR 7.5 SECOND RUN TIME. PROVIDE WITH 605XTMV1070 THERMOSTATIC MIXING VALVE.
F-5 CUSTOM BUILT CERAMIC TILE SHOWER WITH PRESSURE BALANCE, ANTI-SCALD SHOWER VALVE WITH ADJUSTABLE LIMIT SCREW STOP.
SYMMONS ORIGINS SHOWER SYSTEM MODEL S-9601-PLR-1.5 WITH 1.5 GPM FLOW RESTRICTOR. PROVIDE WITH SCHLUTER - KERDI - LINE DRAIN MODEL KL1V60E90 WITH GRATE KLB19EB90 BRUSHED STAINLESS STEEL TRENCH DRAIN. PROVIDE WITH ALL ACCESSORIES REQUIRED TO
COMPLETE TRENCH DRAIN INSTALLATION.
F-5H CUSTOM BUILT CERAMIC TILE SHOWER WITH PRESSURE BALANCE, ANTI-SCALD SHOWER VALVE WITH ADJUSTABLE LIMIT SCREW STOP AND HAND SPRAY UNIT FOR HANDICAPPED. SYMMONS ORIGINS SHOWER SYSTEM MODEL 9605-PLR-1.5 WITH 1.5 GPM FLOW RESTRICTOR, HAND SPRAY UNIT WITH HOSE, INLINE VACUUM BREAKER, WALL CONNECTION AND 30" SLIDE BAR. PROVIDE WITH SCHLUTER - KERDI - LINE DRAIN MODEL KL1V60E90 WITH GRATE KLB19EB90 BRUSHED STAINLESS STEEL TRENCH DRAIN. PROVIDE WITH ALL ACCESSORIES REQUIRED TO
COMPLETE TRENCH DRAIN INSTALLATION.
F-6 FLOOR MOUNTED OF MOLDED STONE TYPE MOP SINK. FIAT MODEL TSBC1611 WITH 1453-BB STAINLESS STEEL STRAINER DRAIN, MSG-2424 WALL GUARD, 889-CC WALL MOUNTED MOP HANGER AND ELKAY LK-401 FAUCET WITH VACUUM BREAKER AND INTEGRAL STOPS.
F-6A FLOOR MOUNTED OF MOLDED STONE TYPE MOP SINK. FIAT MODEL TSB3003 WITH 1453-BB STAINLESS STEEL STRAINER DRAIN, MSG-24 AND MSG36 WALL GUARDS, 889-CC WALL MOUNTED MOP HANGER AND ELKAY LK-401 FAUCET WITH VACUUM BREAKER AND INTEGRAL STOPS.
F-7 RECESS WAL MOUNTED LAUNDRY MACHINE SUPPLY SUPPLIES AND DRAIN FIXTURE WITH INTEGRAL WATER HAMMER ARRESTORS. PRECISION
PLUMBING PRODUCTS MODEL MM-500 MLB.
F-8 INTEGRAL 18 GA. A.D.A. COMPLIANT DOUBLE COMPARTMENT STAINLESS STEEL SINK FOR HANDICAPPED, WITH MOEN ALIGN MODEL 7565 FAUCET WITH PULL-OUT SPRAY AND STAINLESS STEEL FINISH, LK-35L DRAINS, 17 GA. OFF-SET CAST BRASS P-TRAP AND CAST BRASS WALL SUPPLIES.
INSULATED DRAIN LINE AND SUPPLIES TO COMPLY WITH A.D.A. REQUIREMENTS. PROVIDE WITH HEAVY DUTY ½ HP 120 VOLT GARBAGE DISPOSAL, EMERSON MODEL BADGER 5 WITH DISHWASHER DRAIN CONNECTION, SUPPLY DISPOSER FLANGE, STOPPER AND ALL NECESSARY ACCESSORIES
FOR A COMPLETE INSTALLATION.
F-9 REFRIGERATOR/ICE MAKER WATER SUPPLY BOX WITH INTEGRAL WATER HAMMER ARRESTORS. PRECISION PLUMBING PRODUCTS MODEL
MM-500 MIMB.
F-10 INTEGRAL 18 GA. A.D.A. COMPLIANT SINGLE COMPARTMENT STAINLESS STEEL SINK FOR HANDICAPPED, WITH MOEN ALIGN MODEL 7565 FAUCET WITH PULL-OUT SPRAY AND STAINLESS STEEL FINISH, LK-35L DRAINS, 17 GA. OFF-SET CAST BRASS P-TRAP AND CAST BRASS WALL SUPPLIES.
INSULATED DRAIN LINE AND SUPPLIES TO COMPLY WITH A.D.A. REQUIREMENTS.
F-11 CUSTOM 16 GAGE 304 STAINLESS STEEL SINK AERO MODEL F1L SERIES, SINGLE BOWL SINK WITH LEFT DRAINBOARD. PROVIDE WITH ELKAY 8" CENTERSET WALL MOUNT FAUCET MODEL LK940HA08T6H WITH 8" HIGH ARC SPOUT AND 6" WRISTBLADE HANDLES. PROVIDE WITH STAINLESS
STEEL BASKET STRAINER DRAIN.
F-12 WALL HUNG 14 GA. STAINLESS STEEL SERVICE SINK; ELKAY MODEL ESSW-2319-C WITH ELKAY LK-940C FAUCET AND LK-173 CAST IRON P-TRAP AND DRAIN CONNECTION. PROVIDE FAUCET WITH INTEGRAL STOPS, VACUUM BREAKER AND WALL BRACKET.
12A WHITE LAUNDRY SINK WITH WHITE ENAMEL STEEL LEGS FOR FLOOR MOUNTING. MUSTEE MODEL 19F WITH MODEL 93.600 DECK MOUNT FAUCET, P-TRAP, DRAIN AND WALL SUPPLIES.
F-13 WALL HUNG MULTI-LEVEL BARRIER FREE WATER COOLER WITH BOTTLE FILLER. ONE FOUNTAIN SHALL BE WHEEL CHAIR ACCESSIBLE. ELKAY MODEL LZSTL8WSLK. PROVIDE WATER COOLER WITH STAINLESS STEEL FINISHING AND FLOOR MOUNTED CARRIER. WATER COOLER SHALL BE FOR 120 VOLTS, SINGLE PHASE SERVICE. PROVIDE WITH CANE APRON ELKAY MODEL LKPREZL INSTALLED PER MANUFACTURE INSTRUCTION.
BF-1
DOUBLE CHECK BACKFLOW PREVENTER WITH LEAD FREE CONSTRUCTION, WATTS SERIES LF7. PROVIDE UNIT WITH STRAINER AND SHUT-OFF
VALVES.
BV-1
BALANCING VALVE WITH LEAD FREE CONSTRUCTION, THERM OMEGA TECH MODEL CSUAS WITH UNIONS, STRAINER AND ISOLATION VALVES, PROVIDE PIPE SIZED VALVE. SEE DRAWING FOR PIPE SIZE AND FLOW.
BWV
BACKWATER VALVE, J.R. SMITH 7022. PROVIDE WITH VALVE BOX WITH TOP FLUSH WITH FINISHED GRADE/FLOOR.
CO-1
WALL CLEANOUT, ZURN Z1446-BP-VP WITH VANDAL PROOF SCREW, BRONZE PLUG AND STAINLESS STEEL COVER.
CO-2
FLOOR CLEANOUT, ZURN ZS1400-BP-VP WITH ROUND EXTRA-HEAVY-DUTY STAINLESS STEEL TOP WITH VANDAL PROOF SCREWS AND BRONZE
PLUG.
CO-3
FLOOR CLEANOUT, ZURN ZB1400-BP-HD-VP WITH EXTRA HEAVY DUTY VENEER TOP WITH VANDAL PROOF SCREWS AND BRONZE CLOSURE PLUG.
CP-1
IN-LINE LEAD FREE HOT WATER CIRCULATION PUMP WITH STAINLESS STEEL CONSTRUCTION AND BUILT-IN SPEED CONTROL AND TEMPERATURE SENSOR. BELL AND GOSSETT MODEL ECOCIRC-XL-N-55-45. SYSTEM LUBRICATED CIRCULATOR WITH 208 VOLTS/ 1 PHASE, 1/2 HP MOTOR. PUMP CAPACITY SHALL BE 6 GPM AT 33 FT. HEAD. INSTALL PER MANUFACTURES RECOMMENDATIONS. COORDINATE WITH OWNER TO CONFIRM CONNECTION TO BUILDING MANAGEMENT SYSTEM IS DESIRED. IF SO, PROVIDE ALL ACCESSORIES REQUIRED FOR CONNECTION TO BUILDING
MANAGEMENT SYSTEM.
FD-1
FLOOR DRAIN; ZURN MODEL Z415-S-VP-P-Y WITH 6" X 6" SQUARE NICKLE BRONZE VANDAL-PROOF SECURE TOP, 1/2" TRAP SEAL PRIMER
CONNECTION AND SEDIMENT BUCKET.
FD-2
FLOOR DRAIN WITH HEAVY DUTY NICKEL BRONZE VANDAL-PROOF TOP, ZN505-P-Y-VP 1/2" TRAP PRIMER CONNECTION AND SEDIMENT BUCKET.
HB-1
RECESS WALL MOUNTED FREEZELESS HYDRANT WITH CHROME FINISH, WOODFORD MODEL B65. PROVIDE UNIT WITH LOCKABLE COVER AND
VACUUM BREAKER.
HB-2
WALL MOUNTED FREEZELESS HYDRANT WITH CHROME FINISH, WOODFORD MODEL 65 WITH VACCUM BREAKER.
HB-3
ROOF MOUNTED FREEZELESS HYDRANT, WOODFORD MODEL RHY1-MS WITH 1/8" DRAIN HOLE AND VACUUM BREAKER. TERMINATE DRAIN AT
FLOOR DRAIN IN DECON ROOM.
LI-1
LINT INTERCEPTOR, ENVIRONMENTAL ENHANCEMENTS MODEL LUV-R.
LI-2
ACID RESISTANT COATED INTERIOR AND EXTERIOR FABRICATED STEEL LINT INTERCEPTOR RATED FOR 70 GPM; ZURN MODEL Z1185-130-7-E WITH ACCESS COVER EXTENSION AS REQUIRED, 2" VENT CONNECTION AND 3" INLET/OUTLET CONNECTIONS.
OI-1
FACTORY FABRICATED CONCRETE OIL/SAND INTERCEPTOR WITH MINIMUM 750 GALLONS STORAGE CAPACITY. PROVIDE INTERCEPTOR WITH 6" THICK CONCRETE TOP AND CAST IRON ACCESS MANHOLE WITH COVER. CONSTRUCT AND INSTALL INTERCEPTOR TO MEET LOCAL AND STATE CODES REQUIREMENTS. PROVIDE INTERCEPTOR WITH INLET AND OUTLET PIPING CONNECTION SIZES AS INDICATED ON THE DRAWING.
RD-1
ROOF DRAIN, ZURN MODEL ZA100-AC-VP ROOF DRAIN UNDER DECK CLAMP AND ALUMINUM VANDAL-PROOF SECURED TOP.
RD-2
NOT USED - STAINLESS STEEL DOWNSPOUT COVER, ZURN MODEL ZS-Z199-DC-VP WITH VANDAL-PROOF SECURED TOP.
TD-1
6" WIDE TRENCH DRAIN, ZURN MODEL Z886-HD PERMA- TRENCH DRAIN SYSTEM WITH HEAVY DUTYSTAINLESS STEEL GRATE.
TD-2
12" WITH CATCH BASIN, ZURN MODEL ZF817-12. PROVIDE WITH STAINLESS STEEL SLOTTED BAR GRATE MODEL P12-SBG-L. CUT OPENING IN GRATE TO RECEIVE DISCHARGE FROM EXTRACTOR. SEE EXTRACTOR SHOP DRAWING FOR DISCHARGE SIZE.
TP-1
TRAP PRIMER, PRIME-RITE AS MANUFACTURED BY PRECISION PLUMBING PRODUCT INC. WITH DISTRIBUTION UNITS.
TP-2
SURFACE MOUNTED WITH BOX MINI-PRIME ELECTRONIC TRAP PRIMER, PRIME-RITE MODEL MPB-500-115V AS MANUFACTURED BY PRECISION
PLUMBING PRODUCT INC. PROVIDE DISTRIBUTION UNITS AS REQUIRED
WH-1
UL LISTED COMMERCIAL ELECTRIC WATER HEATER WITH GLASS LINED 80 GALLONS STORAGE TANK. PROVIDE HEATER WITH FOAM INSULATION.
A.O. SMITH CUSTOM Xi SERIES MODEL DSE-80; 30.0 KW, 208 VOLTS/3 PHASE. PROVIDE WITH FACTORY PRE-CHARGED DIAPHRAGM TYPE EXPANSION TANK FOR POTABLE WATER. WATTS MODEL DETA-20. PROVIDE WITH WALL MOUNTING BRACKET AND INSTALL PER MANUFACTURE
INSTRUCTION.
WH-2
UL LISTED COMMERCIAL SHORT ELECTRIC WATER HEATER WITH GLASS LINED 50 GALLONS STORAGE TANK. PROVIDE HEATER WITH FOAM INSULATION. A.O. SMITH DURA-POWER MODEL DEL-50; (SIMULTANEOUS OPERATION 5 KW ELEMENTS) 10.0 KW, 208 VOLTS/3 PHASE. PROVIDE WITH FACTORY PRE-CHARGED DIAPHRAGM TYPE EXPANSION TANK FOR POTABLE WATER. WATTS MODEL DETA-12. PROVIDE WITH WALL
MOUNTING BRACKET AND INSTALL PER MANUFACTURE INSTRUCTION.
PLUMBING EQUIPMENT SCHEDULE
A
B
33-601 5/8 6.57 1/211250XL-C C
NOTES:
1250XL-D
1250XL-E
1250XL-F
E
F
D
10 1/4
10 7/8
9 5/16
2 1/2
2 7/8
1 3/4
22.4
34.4
10.0
114-154
155-330
61-113
(APPROXIMATE)
DIMENSIONS
PDI
A
SIZE
1250XL-A
1250XL-B B
MODEL
THREAD
in.
1/2
3/4 in.
5 1/4
5 5/8
A
MIPS
CHAMBER
in.
1 5/8
1 1/8
B cubic in.
3.5
4.3
VOLUME
AIR
12-32
1-11
FIXTURE UNIT
CAPACITY
2. MODEL NUMBERS, DIMENSIONS AND ASSOCIATED CAPACITIES
INDICATED IN THIS DETAIL WERE DERIVED FROM ZURN/WILKINS WATER
HAMMER ARRESTERS PRODUCT LINE.
3. WATER HAMMER ARRESTERS ARE REQUIRED TO BE "LEAD-FREE"
AND SHALL MEET THE REQUIREMENTS OF BOTH NSF 61 AND NSF 372.
1. "PDI" REFERS TO THE PLUMBING AND DRAINAGE INSTITUTE.
WATER HAMMER ARESTOR
NOT TO SCALE
A
TOP VIEW
AA
SECTION "A-A"
SPECIFICATIONS
NOTES
1. 4" PLAIN END INLET/OUTLET
2. UNIT WEIGHT - W/CAST IRON COVERS: 230 LBS.
3. MAXIMUM OPERATING TEMP: 140°F CONTINUOUS
4. CAPACITIES - LIQUID: 275 GAL.,
GREASE: 1,076 LBS.; SOLIDS: 105 GAL.
5. BUILT-IN FLOW CONTROL. FOR SERIES INSTALLATIONS,
ONLY INSTALL FLOW CONTROL ON THE FIRST UNIT IN
THE SERIES IF NECESSARY.
6. FOR GRAVITY DRAINAGE APPLICATIONS ONLY.
7. DO NOT USE FOR PRESSURE APPLICATIONS.
8. COVER PLACEMENT ALLOWS FULL ACCESS TO TANK
FOR PROPER MAINTENANCE.
9. VENT NOT REQUIRED UNLESS PER LOCAL CODE.
10. ENGINEERED INLET AND OUTLET DIFFUSERS ARE
REMOVABLE TO INSPECT / CLEAN PIPING.
11. INTEGRAL AIR RELIEF / ANTI-SIPHON / SAMPLING ACCESS
DIFFUSION FLOW TECHNOLOGY
THE INLET DIFFUSER REDUCES TURBULENCE, CREATES
LAMINAR FLOW AND ALLOWS THE ENTIRE TANK VALUME
TO BE UTILIZED FOR EFFICIENT GREASE SEPARATION
AND MINIMAL DISTURBANCE TO EXISTING GREASE AND
SEDIMENT LAYERS. THE INLET DIFFUSER CAN BE ATTACHED
TO ANY OF THE THREE INLETS PROVIDED TO EASE JOB SITE
PIPING LAYOUTS. THE INTEGRAL AIR RELIEF / ANTI-SIPHON
AT THE OUTLET DIFFUSER TOP ALLOWS PRESSURE
STABILIZATION WITHIN THE UNIT DURING OPERATION.
THE OUTLET DIFFUSER CAN EASILY BE ATTACHED TO ANY
OF THE THREE OUTLETS PROVIDED TO EASE JOB SITE
PIPING LAYOUTS.
GREASE INTERCEPTOR CALCULATIONS
Reference Project Name: Naples Classical Academy
Step 1: Flow rate to grease interceptor
Fixture flow rate: (cu in / 231) = gal x 0.75 / 2 min = 2 min flow rate
NAME TYPE DIMENSIONS QTY CU IN FLOW RATE
F-8 SINK 19" x 16" x 10" (2) 5 GPM Total 5 GPM
Step 2: Grease Production
Servings per day x Grease production value x Days between pump-outs = Grease output
Number of meals served per day: 72
Grease production value: 0.0455 lbs per serving (Cafeteria : High / flatware)
Days between pump-outs: 90 days
72 x 0.0455 x 90 = 294.84 lbs of FOG
SCHIER MODEL GB-50
Description: Polyethylene Grease Interceptor
SCHIER MODEL GB-50 = 50 GPM WITH 439.5 LB GREASE CAPACITY & 65 GAL. LIQUID CAPACITY
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
LEGEND,
SCHEDULES &
MISC. DETAILS
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
P401
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 PERMIT REV 1
3 09/05/2025 90% IRC REVIEW
DETAIL - LINT INTERCEPTOR
NOT TO SCALE
OFFSET
SECONDARY LINT SCREEN
INLET
STATIC
LINE
WATER
PRIMARY LINT SCREEN
SECURED GASKETED COVER MADE
FROM 1/2" DIAMOND PLATE
OUTLET
M A
X
2" VENT
CONNECTION
PROVIDE WITH TOP EXTENSION.
FLOOR DRAIN DETAIL
SCALE: NTS
DRAIN SUPPORT STRAP
WITH FLOOR
STRAINER, FLUSH
INSIDE CAULK
PIPE
SLOPES)
DRAIN HEAD
ADJUSTABLE
DRAIN BODY
ARCHITECTURAL
FOR FLOOR
TILE FLOOR (SEE
INSIDE CAULK
DETAIL - OIL/SAND INTERCEPTOR
NOT TO SCALE
TO SITE SANITARY.
SEE PLANS FOR
CONNECTION SIZE.
VENT6
OUTLET
4 LIFTING EYES
NOTES:
1: SEE PLANS FOR INLET INVERT ELEVATION AND PIPE SIZES.
2: PROVIDE TWO-WAY CLEANOUTS BEFOR, AND AFTER INTERCEPTOR.
3: LOCAL STANDARD CODE SHALL APPLY IF REQIREMENTS EXCEED THIS DETAIL.
4: BAFFLE PIPE SHALL BE SAME SIZE AS INLET PIPE. MINIMUM SIZE SHALL BE 4".
5: FIELD VERIFY EXACT LOCATION FOR INTERCEPTOR AND COORDINATE ITS INSTALLATION IN
FIELD. CONTRACTOR SHALL BE RESPONSIBLE FOR REPAIRING ALL EXISTING CONCRETE
PAVING AND UTILITIES DAMAGED DURING INSTALLATION.
-1
/2
28 DAYS, TYPE II CEMENT
4,000 P.S.I. CONCRETE @
H-20 TRUCK LOADING
IN-FLOW
(M
IN
#6 @ 12" LONG WAY
#6 @ 6" SHORT WAY
REINFORCING:
BASE AND TOP SLABS
LEVEL
WATER
B A
F F
L E
W A
L L
(M
IN
2 EACH - U.S.F.
#170-E
BRICK OR PRECAST CONC.
ADJUSTMENT RING(S)
18"MINIMUM
24"MAXIMUM
(APPROX)(APPROX)
6'
(APPROX)
4' 2'
(M
IN
B A
F F
L E
W A
L L
VENT
(M A
X
(M A
X
18"MINIMUM
24"MAXIMUM
FROM BUILDING
DRAIN. SEE PLANS
FOR CONNECTION
SIZE. 1
(M A
X
DETAIL - TAIL PIECE TRAP PRIMER
NOT TO SCALE
FLOOR DRAIN
1/2"
FINISHED FLOOR
FINISHED WALL
CONNECT TO LAVATORY
TAIL PIECE TRAP PRIMER
DETAIL - WASHING MACHINE HOOK-UP
NOT TO SCALE
18"MIN.
TO
42"MAX.
P-TRAP
SEWER
DRAIN TO SANITARY
2" VENT
2"STANDPIPE
ROUGH-IN UNIT
WASHING MACHINE
WATER HAMMER
ARRESTOR (TYP.)
DETAIL - WATER SERVICE ENTRANCE
NOT TO SCALE
DOMESTIC WATER SHUT-OFF VALVE.
SEE PLUMBING SPECIFICATION FOR
TYPE AND ADDITIONAL INFORMATION.
CAST IRON VALVE BOX WITH COVER
FLUSH WITH FINISHED GRADE.
COORDINATE LOCATION OF VALVE
BOX WITH CIVIL.
SEE PLAN
FOR CONT.
SEAL PER ALL
APPLICABLE CODE
REQUIREMENTS.
EXTERIOR
WALL
FLOOR
PVC SLEEVE SIZED
TWO PIPE SIZES
LARGER THAN PIPE
LOCATED WITHIN
(UNLESS OTHERWISE
SPECIFIED).
TERMINATE SLEEVE
1/2" ABOVE FINISHED
FLOOR.
WATER SERVICE
SITE UTILITY
(TYP.)
UNION VALVE (TYP.)
BALL
6"(TYP.)
HEATER DIAMETER
AS THE WATER
WIDTH - SAME
DETAIL - WATER HEATER WH-2
NOT TO SCALE
ON BOTH SIDES (TYP. FOR 2 RODS)
NUTS AND LOCK WASHERS
TO MOUNTING FRAME WITH
ATTACH HANGER ROD
AND CONT.
SEE PLAN FOR SIZE
CW/HW SUPPLY
STRUCTURE WITH ANCHOR
HANGER ROD ATTACH TO BLDG
1/2"∅ GALV. THREADED
BOLTS (TYP. FOR 2)
VALVE AT TD-2
FROM T&P RELIEF
TERMINATE DRAIN
AT TD-2
FROM DRAIN PAN
TERMINATE DRAIN
FRAME (WELDED JOINTS)
L2X2X1/8 GALV. MOUNTING
PAN
DRAINATTACH MOUNTING FRAME
TO WALL WITH 1/2"∅ ANCHOR
BOLTS, (TOTAL 4 BOLTS - 2 FOR
EACH SIDE)
BRACING
HEATER
WATER
FINISHED CEILING
AT 1/2 FT. BELOW
MOUNT WATER HEATER
FLOOR SLAB
FLOOR DRAINSLAB
SLEEVE THRU
DISTRIBUTION UNIT
TRAP PRIMER VALVE
DOMESTIC WATER LINE
1/2" TRAP PRIMER LINE
1/2" TRAP PRIMER SUPPLY
ISOLATION VALVE
HEAVY-DUTY SCORIATED
COVER WITH "CO" CAST IN
CLEANOUT PLUG
GASKETED ABS
12"x12"X4" THICK
CONCRETE PAD
ADJUSTABLE
HOUSING
FINISHED GRADE FINISHED FLOOR
HOUSING
ADJUSTABLE
GASKETED ABS
CLEANOUT PLUG
COVER WITH "CO" CAST IN
HEAVY-DUTY SCORIATED
SPIGOT OUTLETSPIGOT OUTLET
SPIGOT OUTLET
HEAVY-DUTY SCORIATED
COVER WITH "CO" CAST IN
CLEANOUT PLUG
GASKETED ABS
12"x12"X4" THICK
CONCRETE PAD
ADJUSTABLE
HOUSING
FINISHED GRADE FINISHED FLOOR
HOUSING
ADJUSTABLE
SEE STRUCTURAL DWG.
CONC. FLOOR SLAB
GASKETED ABS
CLEANOUT PLUG
COVER WITH "CO" CAST IN
HEAVY-DUTY SCORIATED
SPIGOT OUTLET
FOR THICKNESS
F
IN
IS
H
E D
F L O
O R
A B
O V
E
WALL
PIPE SIZE
DIAGRAM FOR
SEE PLAN AND
STEEL COVER PLATE
WITH STAINLESS
WALL CLEANOUT
SEAL BETWEEN PIPE AND
SLAB WITH "THUNDERBOLT"
FINISH FLOOR
FLOOR SLAB
LINK-SEAL
DISCHARGE PIPE
AIR GAP = 2 x "d" d
HUB DRAIN DETAIL
SCALE: NTS
INDIRECT WASTE
FUNNEL WITH ACID
RESISTANT EPOXY
COATED BODY AND
BOTTOM DOME
STRAINER.
DETAIL - TRAP PRIMER "TP-1"
NOT TO SCALE
DETAIL - ONE-WAY CLEANOUT ON GRADE
NOT TO SCALE
DETAIL - ONE-WAY FLOOR CLEANOUT
NOT TO SCALE
DETAIL - 2-WAY CLEANOUT ON GRADE
NOT TO SCALE
DETAIL - 2-WAY FLOOR CLEANOUT
NOT TO SCALE
DETAIL - WALL CLEANOUT
NOT TO SCALE
GATE VALVE
CONTROL OF PUMP
AQUASTAT FOR
REDUCING TEE
BY AQUASTAT. SET TEMPERATURE
PUMP TO BE CONTROLLED
TO 115°F
NOTE
CHECK VALVE
GATE VALVE
PUMP (CP-1)
IN-LINE CIRCULATING
FOR CONTINUATION AND
SIZE, SEE FLOOR PLAN
GAUGE COCK
UNION
DIAL TYPE PRESSURE
GAUGE (0-100 PSIG)
DETAIL - RECIRCULATING PUMP
NOT TO SCALE
COLD WATER
120° HWR
120° HW
TANK
EXPANSION
THERMAL
DRAIN PAN
2" DEEP
VALVE
VACUUM
RELIEF
CHECK VALVE
(TYPICAL)
BALL VALVE
(TYP.)
(TYP.)
UNION
TERMINATE DRAIN FROM
T&P RELIEF VALVE AND
DRAIN PAN AT MOP
SINK OR EXTERIOR
AQUASTAT
DETAIL - ELECTRIC WATER HEATER "WH-1"
NOT TO SCALE
CIRCUIT SETTER VALVE
SWEAT OR SCREWED
FITTINGS
PIPE AS PER SIZED
ON DRAWINGS
ADJUSTMENT SCREW
WITH INDICATOR
TEST PORTS
DETAIL - BALANCING VALVE
NOT TO SCALE
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
MISC. DETAILS
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
P402
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1/8" = 1'-0"
DETAILS1
REVISIONS
# DATE DESCRIPTION
| Sheets |
| P101 - PLUMBING FLOOR PLAN |
| P102 - PLUMBING ROOF PLAN |
| P201 - ENLARGED PLUMBING PLANS |
| P301 - PLUMBING RISER DIAGRAMS |
| P302 - PLUMBING RISER DIAGRAMS |
| P303 - PLUMBING RISER DIAGRAMS |
| P401 - LEGEND, SCHEDULES & MISC. DETAILS |
| P402 - MISC. DETAILS |
File details come from the government source that posted it. Updated .