Clay_Co_FS24_Mech_(2026_01-02)_Bid_Set.pdf
PDF 21 MB Posted
- Attached to
- Construction of Clay County Fire Station No. 24
- Solicitation number
- 25/26-042
- Issued by
- Clay County, Harold CDP, Florida
About this file
This is a mechanical HVAC bid set containing detailed floor plans, schedules, and specifications for Clay County Fire Station No. 24, a new approximately 16,633 square-foot, four-bay fire station facility located at 1075 County Road 226 in Green Cove Springs, Florida. The HVAC system design includes multiple air handling units (AHU-1 through AHU-6), rooftop condensing units (CU-1 through CU-6), an outside air rooftop unit (RTU-OA), exhaust fans (EF-1, EF-2, EF-3, EF-HOOD, EF-WELL), mini-split systems for IT room and fitness areas, electric unit heaters for freeze protection, and a gas detection system for monitoring carbon monoxide and nitrogen dioxide in the apparatus bay. The design encompasses supply and return air ductwork with diffusers and grilles serving various spaces including decontamination, lobbies, meeting rooms, offices, bunk rooms, kitchen, dining, fitness, and apparatus bays. The mechanical system specifications detail equipment manufacturers (Qmark, Loren Cook, Price, Ruskin), refrigerant line routing, condensate drainage, duct sizing and routing requirements, manual and motorized balance dampers, and fire dampers. The project includes a DDC (Direct Digital Controls) system similar to Carrier IVu for monitoring and controlling the primary HVAC units, with remote monitoring capabilities in the IT room. The sealed bid deadline is March 2, 2026, at 4:00 p.m., with a mandatory pre-bid meeting on February 6, 2026, at 10:00 a.m. Substantial completion is required by March 15, 2027, with final Certificate of Occupancy by March 20, 2027, to meet grant deadline requirements.
The project is subject to Davis-Bacon Act prevailing wage requirements and must comply with federal regulations including 2 CFR Part 200 (Uniform Guidance) and the FEMA Field Manual for Public Assistance, as the construction is supported by Federal Emergency Management Agency (FEMA) Public Assistance Grant Program funding. Bidders must be Florida-licensed General Contractors in good standing with the Florida Construction Industry Licensing Board and must have been in business for a minimum of five years performing similar work. All bids require a five percent bid bond, 100 percent Performance and Payment Bond per Florida Statute 255.05, and comprehensive insurance including Commercial General Liability of $1,000,000 per occurrence and $2,000,000 aggregate, Workers' Compensation at statutory limits, and Builder's Risk coverage equal to 100 percent of project value with a maximum $25,000 deductible. Liquidated damages of $1,000 per day are assessed for delays beyond the final completion date. No specific set-asides for disadvantaged enterprises are identified. The site contains protected species including Eastern Indigo Snakes and Tri-Colored Bats, requiring implementation of specific protective measures in coordination with qualified environmental professionals and compliance with Florida Fish and Wildlife Conservation Commission and U.S. Fish and Wildlife Service guidelines. A strict no-contact rule prohibits all communications with Board members, County employees, or Evaluation Committee members regarding the Request for Bid from publication through 72 hours after bid decision.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DECON
CORR
LOBBY
CORR
MEETING
WATCH
IT
ELEC
QUIET RM
OFFICE
PPE STOR
MEDICAL
CORR
WOMEN
LAUNDRY
SHOWER RM
LOCKERS
FITNESS
VESTIBULE
CORR
CAPT SUITE
CAPT RR
CAPT OFF
AHU-1
AHU-2
T
TO AHU-1
T TO AHU-2
AHU-3 AHU-4
T
TO AHU-3
T TO AHU-4
AHU-5
T
TO AHU-5
x 1
RA
G-6, 4'0" LONG, ONE 2" SLOT,
300 CFM - 10"⌀ FLEX
CONNECTION TO PLENUM
(TYP. FOR 4)
G-1, 6"⌀
20 CFM
(TYP. FOR 2)
G-1, 12"⌀
350 CFM
ø
SA
x 12 SA 12 x 12 SA 8
G-7, 24X24 G-2, 12X12 x 1
RA
x 12 RA 14
BD
BD
G-1, 10"⌀
265 CFM
(TYP. FOR 2)
G-1, 10"⌀
285 CFM
(TYP. FOR 2)
G-1, 10"⌀
240 CFM
(TYP. FOR 2)
G-1, 10"⌀
290 CFM
BD
BD
BD
x 1
SA
ø
SA
x 1
SA
x 1
SA
x 1
SA
x 1
SA
BD
G-2, 22X22 x 1
SA
x 10 SA 6
G-2, 8X8
(TYP. FOR 2)
BD
x 1
RA
G-1, 8"⌀
140 CFM
G-1, 8"⌀
200 CFM
G-1, 8"⌀
160 CFM
G-1, 8"⌀
100 CFM
G-1, 8"⌀
100 CFM
G-1, 6"⌀
25 CFM
G-1, 8"⌀
120 CFM
G-2, 10X10
G-2, 8X8 G-2, 8X8
G-2, 8X8
G-1, 6"⌀
90 CFM
G-1, 6"⌀
50 CFM
G-1, 6"⌀
60 CFM
x 1
SA
ø SA8" x 1
SA
BD
x 1
SA
x 1
SA
x 10 SA 10 x 8 SA 8
BD
BD
x 1
SA
x 1
SA
ø SA6" x 1
RA
x 12 RA 14
BD
x 8 RA 12 x 1
RA
x 8 RA 8
KITCHEN
DINING
HVAC NOTES:
EXHAUST DUCTWORK SERVING HOOD SHALL BE LISTED, PRE-FABRICATED SINGLE-WALL LIQUID-TIGHT GREASE DUCT
SEE HOOD DRAWINGS ON SHEETS M301 THRU M307.
RUN 4"⌀ DRYER EXHAUST DUCT UP ALONG WALL BEHIND DRYER, THEN ACROSS TO EXTERIOR WALL ABOVE CEILING TO DRYER WALL CAP (WITH BACKDRAFT DAMPER AND NO INSECT SCREEN). DUCT MUST BE RUN IN AS DIRECT A ROUTE AS
POSSIBLE BECAUSE OF DRYER DUCT LENGTH LIMITATIONS.
SEE WALL ELEVATION ON ARCHITECTURAL SHEETS FOR ARRANGEMENT OF SUPPLY DIFFUSERS AND RETURN GRILLES IN MEETING-102. RETURN GRILLE SHOULD BE CENTERED WITH PEAK OF SLOPING CEILING, MOUNTED WITH BOTTOM AT APPROX 12'0" A.F.F.. SUPPLY DIFFUSERS SHOULD BE MOUNTED WITH CENTER AT APPROX 10'6" A.F.F., WITH POSITIONS ON
LEFT AND RIGHT MIRRORING EACH OTHER.
NOT USED
RUN 4"⌀ DRYER EXHAUST DUCT UP INSIDE WALL BEHIND DRYER, STRAIGHT UP TO DRYER VENT CAP (WITH BACKDRAFT DAMPER AND NO INSECT SCREEN) ON ROOF. DUCT MUST BE RUN IN AS DIRECT A ROUTE AS POSSIBLE BECAUSE OF DRYER
DUCT LENGTH LIMITATIONS.
DIFFUSER/GRILLE NOTES:
G-5, 8X6, 150 CFM
G-3, 6X6, 100 CFM
G-5, 6X6, 80 CFM
G-5, 8X6, 120 CFM
G-3, 6X6, 30 CFM
G-5, 6X6, 70 CFM
NOT USED
G-1, 8"⌀, 185 CFM
G-1, 6"⌀, 50 CFM
G-1, 10"⌀, 330 CFM
G-1, 8"⌀, 120 CFM
G-2, 12X12 ø SA6" ø SA6"
BD
BD
BD
ø EA10" ø EA10"
HOOD #1
x 16 OA 16
G-5, 6X6
50 CFM
(TYP. FOR 2)
NO2
CO
x 12 EA 14
AHU-IT
10X6 EA DOWN
FROM EF-1
x 6 E
A
G-3, 6X6
75 CFM
G-3, 8X8
175 CFM
10"⌀ EA DOWN
FROM EF-HOOD
14X12 EA DOWN
FROM RTU-OA
16X16 OA DOWN
FROM RTU-OA
TS
TO AHU-FITNESS
T
TO AHU-IT
AHU-FITNESS
MEN
WOMEN
x 6 E
A ø
EA
4"
DRYER
WALL CAP
G-6, 4'0" LONG, ONE 2" SLOT,
310 CFM - 10"⌀ FLEX
CONNECTION TO PLENUM
x 14 SA 16x 12 SA 10 x 1
SA
x 12 RA 22
G-2, 12X12
BD
GENERAL NOTES:
AT EACH AIR HANDLER WITH OUTSIDE AIR CONNECTION TO
THE RETURN, A MANUAL BALANCE DAMPER MUST BE
PROVIDED ON THE OUTSIDE AIR BRANCH DUCT SERVING THAT
AIR HANDLER, AND A MANUAL BALANCE DAMPER SHALL ALSO
BE PROVIDED ON THE RETURN DUCT DUCT UPSTREAM FROM
THE OUTSIDE AIR BRANCH DUCT CONNECTION. BOTH
DAMPERS SHOULD BE ACCESSIBLE.
IN ROOMS SERVED BY AHU-IT, AHU-FITNES, AND AHU-5, THERE
SHALL BE A THERMOSTAT SERVING THE UNIT ITSELF (MARKED
BY 'T'), AND AN ADJACENT TEMPERATURE SENSOR (MARKED
BY 'TS') THAT REPORTS TO THE DDC CONTROLS SYTEM.
IN THE AREA BENEATH THE LOW-FLAT ROOF, DUCTS MUST BE
RUN BETWEEN THE STRUCTURAL MEMBERS SUPPORTING THE
ROOF (OR FOR SMALL OR SHALLOW DUCTS, UNDER THE
STRUCTURAL MEMBERS).
BD
x 1
O A x 10 OA 10 x 6 OA 8
CONDENSATE/REFRIGERANT NOTES:
RUN CONDENSATE FROM AHU-1, AHU-2, AHU-3, AHU-4, AHU-5, & AHU-6 TO HUB DRAIN IN SAME ROOM
WHERE AIR HANDLER IS INSTALLED.
PUMP CONDENSATE FROM AHU-IT TO HUB DRAIN IN MECHANICAL CLOSET CONTAINING AHU-1 & AHU-2.
PUMP CONDENSATE FROM AHU-FITNESS TO HUB DRAIN IN MECHANICAL CLOSET CONTAINING AHU-5.
FOR AHU-1 THRU AHU-5, AHU-IT, & AHU-FITNESS, RUN REFRIGERANT LINES ABOVE CEILING THEN ACROSS BUILDING TO FLAT ROOF AREA, THEN UP THROUGH FLAT ROOF (GROUPING TOGETHER TO
MINIMIZE PENETRATIONS) AND OVER TO CONDENSING UNITS.
FOR AHU-6, RUN REFRIGERANT LINES UP ABOVE CEILING, THEN RUN THROUGH EXTERIOR WALL, THROUGH STORAGE-157 & MAINT-156, DOWN EXTERIOR WALL OF MAINT-156, AND TO CONDENSING
UNIT.
G-8, 6x6
50 CFM
x 8 O
A
BD
T
TS
TS
BD
x 8 O
A x 1
O A x 10 OA 12 x 18 SA 18 x 6 OA 6 x 14 OA 14
BD
x 10 OA 12 x 12 EA 12 x 6 E
A x 6 E
A x 6 E
A x 6 EA 6 x 6 EA 8
BD
BD
BD
BD
BDx 6 E
A x 6 EA 6 x 6 E
A x 6 E
A
BD
x 10 EA 10 x 1
O A
HVAC CONTROLS SYSTEM,
DDC CONTROLLER
4"⌀ EA
DRYER VENT
DAY ROOM
x 8 R
A x 1
RA
G-2, 10X10 x 10 RA 12
G-2, 8X8 x 8 T
A
FD
BD
BD
G-7, 6X6
(TYP FOR 2)
JUST BELOW CEILING
FDFPH-DECON
FD
FD FD FD
FD
FD
FD
G-1, 6"⌀
50 CFM
x 12 RA 12
BD
x 6 EA 8
CONDENSATE OVERFLOW
VISUAL ALARM (TO AHU-IT)
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC FLOOR
PLAN - AREA
"A"
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M101A
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
3/16" = 1'-0"1 HVAC FLOOR PLAN - AREA "A"
NEW SHEET - ORIGINAL HVAC FLOOR PLAN
(SHEET M101) WAS SPLIT UP INTO THREE
FLOOR PLANS (SHEETS M101A, M101B, AND
M101C)
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 Permit Rev 1 3 07/19/2024 VE Rev 1
4 09/05/2025 90% IRC REVIEW
CAPT SUITE
CAPT OFF
MAINT
STOR
BUNK 13
BUNK 12
W/C
BUNK11
BUNK10
BUNK9
BUNK8
BUNK1
BUNK2
BUNK3
BUNK4
BUNK5
BUNK6
BUNK7
CORR
AHU-6
T
TO AHU-6
G-1, 8"⌀
100 CFM
G-1, 6"⌀
85 CFM
G-1, 6"⌀
85 CFM
G-1, 6"⌀
85 CFM
G-1, 6"⌀
85 CFM
G-1, 6"⌀
85 CFM
G-1, 8"⌀
95 CFM
G-1, 8"⌀
95 CFM
G-1, 6"⌀
85 CFM
G-1, 6"⌀
75 CFM
G-1, 6"⌀
75 CFM
G-1, 6"⌀
25 CFM
G-1, 6"⌀
85 CFM
G-1, 6"⌀
85 CFM
G-1, 8"⌀
90 CFM
(TYP. FOR 4)
G-2, 6X6
(TYP. FOR 13
x 1
SA
x 10 SA 18 x 10 SA 8 x 1
SA
x 1
SA
BD
BD
BD
x 1
SA
x 1
SA
ø
SA
8" ø
SA
8" x 10 SA 12
BD
x 10 SA 12 x 1
SA
BD
BD
x 6 R
A x 8 R
A x 8 R
A x 8
R A x 6
R A x 8 RA 16 x 8 R
A x 1
RA
x 1
SA
x 1
SA
x 1
SA
x 1
SA
x 8 RA 18 x 8 RA 12 x 8 R
A x 6
R A x 8
R A x 6
R A x 8 R
A
BD
G-2, 12X12
CU-6
x 8 O
A
BD
x 6 E
A x 8 T
A
FPH-STOR
FPH-MAINT
G-2, 8X8
FD
FD
FDFD
FD FD
FDFD
FD
FD
FD
FD
FD
FD
FD
FD
FD FD
FD
FD
FD
FD
FDFD
FD
FD
FDFD
FD
FD
FD
GENERAL NOTES:
AT EACH AIR HANDLER WITH OUTSIDE AIR CONNECTION TO
THE RETURN, A MANUAL BALANCE DAMPER MUST BE
PROVIDED ON THE OUTSIDE AIR BRANCH DUCT SERVING THAT
AIR HANDLER, AND A MANUAL BALANCE DAMPER SHALL ALSO
BE PROVIDED ON THE RETURN DUCT DUCT UPSTREAM FROM
THE OUTSIDE AIR BRANCH DUCT CONNECTION. BOTH
DAMPERS SHOULD BE ACCESSIBLE.
IN ROOMS SERVED BY AHU-IT, AHU-FITNES, AND AHU-5, THERE
SHALL BE A THERMOSTAT SERVING THE UNIT ITSELF (MARKED
BY 'T'), AND AN ADJACENT TEMPERATURE SENSOR (MARKED
BY 'TS') THAT REPORTS TO THE DDC CONTROLS SYTEM.
IN THE AREA BENEATH THE LOW-FLAT ROOF, DUCTS MUST BE
RUN BETWEEN THE STRUCTURAL MEMBERS SUPPORTING THE
ROOF (OR FOR SMALL OR SHALLOW DUCTS, UNDER THE
STRUCTURAL MEMBERS).
CONDENSATE/REFRIGERANT NOTES:
RUN CONDENSATE FROM AHU-1, AHU-2, AHU-3, AHU-4, AHU-5, & AHU-6 TO HUB DRAIN IN SAME ROOM
WHERE AIR HANDLER IS INSTALLED.
PUMP CONDENSATE FROM AHU-IT TO HUB DRAIN IN MECHANICAL CLOSET CONTAINING AHU-1 & AHU-2.
PUMP CONDENSATE FROM AHU-FITNESS TO HUB DRAIN IN MECHANICAL CLOSET CONTAINING AHU-5.
FOR AHU-1 THRU AHU-5, AHU-IT, & AHU-FITNESS, RUN REFRIGERANT LINES ABOVE CEILING THEN ACROSS BUILDING TO FLAT ROOF AREA, THEN UP THROUGH FLAT ROOF (GROUPING TOGETHER TO
MINIMIZE PENETRATIONS) AND OVER TO CONDENSING UNITS.
FOR AHU-6, RUN REFRIGERANT LINES UP ABOVE CEILING, THEN RUN THROUGH EXTERIOR WALL, THROUGH STORAGE-157 & MAINT-156, DOWN EXTERIOR WALL OF MAINT-156, AND TO CONDENSING
UNIT.
G-5, 6X6
50 CFM
FD
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC FLOOR
PLAN - AREA
"B"
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M101B
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
3/16" = 1'-0"1 HVAC FLOOR PLAN - AREA "B"
NEW SHEET - ORIGINAL HVAC FLOOR PLAN
(SHEET M101) WAS SPLIT UP INTO THREE FLOOR
PLANS (SHEETS M101A, M101B, AND M101C)
REVISIONS
# DATE DESCRIPTION
APP BAY
G-3, 22X22
1165 CFM
(TYP. FOR 3)
G-3, 22X22
1165 CFM
(TYP. FOR 3)
x 20 EA 22x 10 EA 22 x 20 EA 22 x 14 EA 22 x 10 EA 22x 20 EA 20 x 20 EA 20
L-2, 60"X60"
BOTTOM @ 21'4" A.F.F.
L-1, 60"X60"
BOTTOM @ 21'4" A.F.F.
G-4, 22X22
(TYP. FOR 6)
x 10 OA 24 x 16 OA 24 x 2
O A x 10 OA 24x 16 OA 24x 22 OA 24
UH-1
UH-2 UH-3
UH-4
NO2
CO
NO2
CO
GAS DETECTION
SYSTEM CONTROLLER
CARBON MONOXIDE SENSORS (MOUNT @ 4' A.F.F.)
NITROGEN DIOXIDE SENSORS (MOUNT @ 2' BELOW CEILING)
x 2
O A
TRUCK EXHAUST SYSTEM FAN
(PERFORMANCE SPEC, TO BE
PROVIDED & INSTALLED BY OTHERS)
TO BE LOCATED IN THIS AREA
EF-WELL
T
TO EF-WELL
ø EA8"
WELL HOUSE
FPH-WELL
DOOR TO HAVE 18"x18" LOUVER
ROUTE DUCT OVER BEAM,
RUNNING BETWEEN TRUSSES
ROUTE DUCT OVER BEAM,
RUNNING BETWEEN TRUSSES
FD
EF-3EF-2
x 20 EA 20 x 20 EA 20
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC FLOOR
PLAN - AREA
"C"
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M101C
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
3/16" = 1'-0"1 HVAC FLOOR PLAN - AREA "C"
NEW SHEET - ORIGINAL HVAC FLOOR PLAN
(SHEET M101) WAS SPLIT UP INTO THREE FLOOR
PLANS (SHEETS M101A, M101B, AND M101C)
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 Permit Rev 1
RTU-OA
CU-FITCU-5
CU-IT
CU-1
CU-2
CU-3
CU-4
EF-HOOD
EF-1
HVAC NOTES:
RUN CONDENSATE FROM RTU-OA TO NEAREST ROOF DRAIN THAT RUNS TO STORM SYSTEM.
DO NOT DUMP CONDENSATE TO THE ADJACENT OVERFLOW ROOF DRAIN THAT DRAINS TO
GRADE.
MOUNT CONDENSING UNITS ON ALUMINUM OR GALVANIZED STEEL RACKS TIED TO
STRUCTURE, WITH CLEARANCE IN ACCORDANCE WITH FLORIDA BUILDING CODE, TABLE 1510.10.
GENERAL CONTRACTOR IS TO COORDINATE THE RACK WITH THE ROOF FRAMING LAYOUT (SO
THAT LEGS OF RACK SIT ON THE FRAMING MEMBERS, NOT BETWEEN JOISTS) AND CUSTOM
SIZE THE RACK IF NECESSARY TO ENSURE PROPER SUPPORT.
CU-1, CU-2, & CU-IT SHOULD BE MOUNTED ON A COMMON RACK WITH 18" CLEARANCE.
CU-3 & CU-4 SHOULD BE MOUNTED ON A COMMON RACK WITH 18" CLEARANCE.
CU-5 & CU-FIT SHOULD BE MOUNTED ON A COMMON RACK WITH 14" CLEARANCE.
PROVIDE STACK ON FAN DISCHARGE TO MAINTAIN MINIMUM 5'-0" CLEARANCE FROM ADJACENT
BUILDING STRUCTURE PER FLORIDA MECHANICAL CODE SECTION 506.3.13.3.
DRYER VENT CAP
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC ROOF
PLAN
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M102
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1/8" = 1'-0"1 HVAC ROOF PLAN
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 Permit Rev 1 2 12/11/2023 Permit Rev 2
GENERAL DAMPER NOTE:
DAMPERS HAVE BEEN LOCATED (TO THE EXTENT POSSIBLE) ABOVE LAY-IN CEILINGS SO THAT THEY CAN BE
ACCESSED FOR ADJUSTMENT.
SUPPLY FLEX DUCT CONNECTIONS THAT ARE INACCESSIBLE (ABOVE HARD CEILINGS, OR TOO HIGH FOR ACCESS) SHALL HAVE YOUNG REGULATOR DAMPER IN BRANCH DUCT, WITH REMOTE ADJUSTMENT DEVICE
LOCATED IN CEILING ADJACENT TO GRILLE (YOUNG REGULATOR MODEL # 270-301).
MANUAL BALANCE DAMPERS LOCATED IN INACCESSIBLE AREAS (ABOVE HARD CEILINGS, OR TOO HIGH FOR ACCESS) SHALL HAVE YOUNG REGULATOR DAMPER, WITH REMOTE ADJUSTMENT DEVICE LOCATED IN
CEILING BELOW, WITH LABEL (YOUNG REGULATOR MODEL # 270-301).
HVAC LEGEND
THERMOSTAT
TEMPERATURE SENSOR FOR MONITORING
T
DUCT-MOUNTED SMOKE DETECTORS
DUCT-MOUNTED SMOKE DETECTOR
ELECTRIC UNIT HEATEREUH NEW SUPPLY DIFFUSER
NEW RETURN GRILLE
NEW DUCT
DUCT WITH DAMPER
NEW LINEAR GRILLE
EXHAUST FANEF
AIR HANDLING UNITAHU
CONDENSING UNITCU
ROOFTOP AIR CONDITIONING UNITRTU
SUPPLY AIRSA
RETURN AIRRA
EXHAUST AIREA
TRANSFER AIRTA
OUTSIDE AIROA
MANUAL BALANCE DAMPERBD
MOTORIZED BALANCE DAMPERMD
OPENING ABOVE CEILINGO.A.C.
FREEZE PROTECTION HEATERFPH
TS
CO
FIRE DAMPERFD
HVAC CONTROLS
PROVIDE DDC CONTROLS SYSTEM SERVING HVAC SYSTEMS, SIMILAR TO CARRIER IVu.
SYSTEM SHALL BE PROVIDED WITH FRONT-END ON SITE IN "IT-114", AS WELL AS BEING WEB-ACCESSIBLE.
SYSTEM SHALL PROVIDE FOR MONITORING (OF FAN STATUS, COMPRESSOR STATUS, ELECTRIC HEAT STATUS, SPACE TEMPERATURE, DISCHARGE AIR TEMPERATURE) AND CONTROL (OF TEMPERATURE SETPOINTS AND SCHEDULES) OF AHU/CU-1,2,3,4,6.
SYSTEM SHALL PROVIDE FOR TEMPERATURE MONITORING OF SPACES SERVED BY MINI-SPLIT SYSTEMS (AHU/CU-IT, AHU/CU-FITNESS, AHU/CU-5), WITH TEMPERATURE SENSOR ADJACENT TO UNIT THERMOSTAT. THE CONTROL OF THESE SYSTEMS WILL BE BY MANUFACTURER'S
CONTROLS & THERMOSTAT.
SYSTEM SHALL PROVIDE FOR MONITORING (OF FAN STATUS, DISCHARGE TEMPERATURE, AND RELATIVE HUMIDITY LEVELS) OF AIR LEAVING RTU-OA. SCHEDULING AND UNIT SETUP OF RTU-OA SHALL BE BY MANUFACTURERS CONTROLS AT UNIT, WITH REMOTE STATION ALSO LOCATED
IN "IT-114".
EF-1 - DDC SYSTEM WILL CONTROL SCHEDULING (START/STOP) OF UNIT AND WILL MONITOR FAN STATUS.
EF-HOOD - DDC SYSTEM WILL MONITOR FAN STATUS. THIS UNIT WILL BE CONTROLLED BY SWITCH AT HOOD, AS DETAILED ON HOOD DRAWINGS.
EF-2 & EF-3 - DDC SYSTEM WILL MONITOR FAN STATUS. CONTROL OF THESE UNITS WILL BE AS DETAILED IN APPARATUS BAY SEQUENCE OF
OPERATION ON SCHEDULE SHEETS.
GAS DETECTION SYSTEM - DDC SYSTEM WILL MONITOR ALARM STATUS OF THIS SYSTEM.EQUIPMENT SCHEDULE - ELECTRIC UNIT HEATER
APPROVED MANUFACTURER QMARK
EQUIPMENT NUMBER EUH-1,2,3,4 FPH-WELL FPH-MAINT FPH-STOR FPH-DECON
MOUNTING TYPE WALL WALL WALL WALL WALL
COIL CAPACITY - KW 11.2 KW (@ 208V) 3.6 KW (@ 208V) 3.0 KW (@ 208V) 3.0 KW (@ 208V) 1.5 KW (@ 208V)
ENT AIR TEMP - °F 40°F 40°F 40°F 40°F 40°F
FAN
TYPE PROPELLER PROPELLER PROPELLER PROPELLER PROPELLER
DRIVE DIRECT DIRECT DIRECT DIRECT DIRECT
RPM 1530 -- -- -- --
CFM 910 100 100 100 100
S.P. -- -- -- -- --
HP 1/20 -- -- -- --
VOLTS/PHASE 208 V/3Ø 208 V/1Ø 208 V/1Ø 208 V/1Ø 208 V/1Ø
MODEL NUMBER MUH-15-2 LFK484F LFK404F LFK404F LFK204F
MOUNTING HEIGHT - BOTTOM OF UNIT
A.F.F 10'0" 3'0" 3'0" 3'0" 3'0"
ACCESSORIES / REMARK 1,2,3,4,5 1,5,6,7 1,5,6,7 1,5,6,7 1,5,6,7
NOTE:
1 PROVIDE WITH UNIT-MOUNTED DISCONNECT.
2 BUILT-IN 24V CONTROL TRANSFORMER FOR THERMOSTAT, WITH WALL-MOUNTED THERMOSTAT
3 PROVIDE UNIT WITH BRACKET FOR WALL MOUNTING
4 UNIT TO BE CONFIGURED FOR HORIZONTAL AIR DISCHARGE.
5 UNIT TO BE USED FOR FREEZE PROTECTION ONLY, WITH THERMOSTAT SET NOT HIGHER THAN 50°F.
6 INTEGRAL THERMOSTAT
7 SURFACE MOUNT
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC
SCHEDULE
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M201
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 Permit Rev 1 2 12/11/2023 Permit Rev 2
AIR BALANCE SCHEDULE
UNIT NAME SUPPLY AIR
CFM
RETURN AIR
CFM
OUTSIDE AIR
CFM
EXHAUST AIR
CFM
DIFFERENTIAL
CFM
AHU-1 (pre-fed by RTU-OA) 1200 935 265 0 +265 AHU-2 (pre-fed by RTU-OA) 700 620 80 0 +80 AHU-3 (pre-fed by RTU-OA) 1875 1440 435 0 +435 AHU-4 (pre-fed by RTU-OA) 1400 980 420 0 +420 AHU-5 (pre-fed by RTU-OA) 340 305 35 0 +35 AHU-6 (pre-fed by RTU-OA) 1500 1285 215 0 +215
FITNESS-158 - - 50 0 +50
RTU-OA (Exhaust for ERV) 0 0 0 700 -700
EF-HOOD 0 0 0 500 -500
TOTAL 7015 5565 1500 1200 +300
GAS DETECTION SYSTEM
PROVIDE GAS DETECTION SYSTEMS AS MANUFACTURED BY HONEYWELL
ANALYTIC/VULCAIN.
SYSTEM SHALL BE CONFIGURED IN THE FOLLOWING MANNER:
CONTROLLER SHALL BE A VA301C MULTI-CHANNEL CONTROLLER, CONNECTED
TO A REMOTE STROBE LIGHT AND HORN ADJACENT TO THE CONTROLLER. THIS
SYSTEM SHALL HAVE TWO NETWORKABLE CARBON MONOXIDE SENSORS,
MODEL # E3SMSCO (MOUNTED AT 4' A.F.F.), AND TWO NETWORKABLE NITROGEN
DIOXIDE SENSORS, MODEL # E3SMSNO2 (MOUNTED AT 2' BELOW CEILING). [IF
DIFFERENT MANUFACTURER IS SUBMITTED AND ACCEPTED, USE
MANUFACTURER'S RECOMMENDED MOUNTING HEIGHTS FOR SENSORS]
FOR CONTROLS TIED TO THIS SYSTEM, SEE "APPARATUS BAY SEQUENCE OF
OPERATION" ON SHEET M205.
MECHANICAL CONTRACTOR SHALL CONTACT LOCAL HONEYWELL
ANALYTIC/VULCAIN REPRESENTATIVE (R.M. MYERS COMPANY) FOR GAS
DETECTION SYSTEM COMMISSIONING AND OWNER TRAINING.
EQUIPMENT SCHEDULE - DIFFUSERS, GRILLES & REGISTERS
NOTES:
SEE ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LOCATION OF ALL CEILING DIFFUSERS. ALL FLEXIBLE DUCT CONNECTIONS TO RECTANGULAR DUCT TO BE SPIN-INS WITH AIR SCOOP AND BALANCE DAMPER. NECK SIZE AND CFM
AS SHOWN ON THE DRAWINGS, UNLESS OTHERWISE NOTED.
APPROVED MANUFACTURER: PRICE
EQUIP. NO. MOUNTING STYLE MODEL NUMBER ACCESSORIES/REMARKS
G-1 LAY-IN CEILING (SUPPLY) SPD (24X24) (2)
G-2 LAY-IN CEILING (RETURN) 80 (24X24)
G-3 LAY-IN CEILING (EXHAUST) 530L (24X24) (1)
G-4 LAY-IN CEILING (RELIEF) 510L (24X24)
G-5 SURFACE (EXHAUST) 530L (1)
G-6 SURFACE, SLOT (SUPPLY) CF-JS (5)
G-7 SURFACE (RETURN/TRANSFER) 530L
G-8 SURFACE (SUPPLY) 520L (1)(6)
L-1 SURFACE (INTAKE) HZ700MD * (3)(4) RUSKIN LOUVER
L-2 SURFACE (EXHAUST) HZ700MD * (3) RUSKIN LOUVER
NOTE:
1 PROVIDE GRILLE WITH OPPOSED BLADE DAMPER, ADJUSTABLE FROM FACE OF GRILLE.
2 WHERE USED IN GYP BOARD CEILINGS, PROVIDE ANGLE FRAME FOR CUT OPENING AND USE LAY-IN TYPE DIFFUSER.
3 LOUVER SHALL MEET REQUIREMENTS OF AMCA-540 & AMCA-550. PROVIDE LOUVER WITH INSECT SCREEN AT INTERIOR
FACE, AND 12" DEEP PLENUM CHAMBER FOR DUCT CONNECTION.
4 PROVIDE 24V MOTORIZED DAMPER AT INTERIOR OF LOUVER (TIED TO GAS DETECTION CONTROL SYSTEM)
UNIT SHALL BE AN ARCHITECTURAL SLOT SUPPLY DIFFUSER WITH JET-SLOT CONTROLLER. PROVIDE UNIT WITH A UNIVERSAL PLENUM (UP) [SEE DRAWING FOR FLEX DUCT CONNECTION SIZE]. UNIT SHALL BE CONFIGURED DISCHARGE AIR HORIZONTALLY (DIRECTLY AWAY FROM WALL THAT UNIT IS INSTALLED IN). COORDINATE WITH ARCHITECT FOR
BORDER TYPE.
6 PROVIDE BOOT FOR FLEX DUCT CONNECTION.
EQUIPMENT SCHEDULE - FAN
APPROVED MANUFACTURER LOREN COOK CO.
EQUIPMENT NUMBER EF-1 EF-2, EF-3 EF-WELL
MOUNTING TYPE ROOF INLINE INLINE
FAN
TYPE CENTRIFUGAL CENTRIFUGAL CENTRIFUGAL
DRIVE DIRECT - EC DIRECT DIRECT - EC
RPM 1440 1024 1074
CFM 250 3500 160
S.P. 0.5" W.G. 0.35" W.G. 0.25" W.G.
MOTOR H.P. 1/6 1.5 28 WATTS
VOLTS/PHASE 120 V/1Ø 208 V/3Ø 120 V/1Ø
MODEL NUMBER 90C17DEC 180SQN17D (VF2) GNVF-180
ACCESSORIES/REMARKS 1,2,3,4,5,6 1,2,3,4,7 1,2,3,4,8,9
NOTE:
1 BACK DRAFT DAMPER
2 UNIT MOUNTED SPEED CONTROLLER
3 UNIT MOUNTED DISCONNECT
4 PROVIDE EC MOTOR.
5 14" HIGH INSULATED ROOF CURB
6 FAN TO RUN 24/7
7 SEE SEQUENCE OF OPERATION FOR CONTROL.
8 PROVIDE LINE VOLTAGE THERMOSTAT FOR CONTROL OF EXHAUST FAN.
9 PROVIDE 8"Ø WALL CAP WITH BACKDRAFT DAMPER.
ALL FANS SHALL BE PROVIDED WITH BACKDRAFT DAMPERS. IF MANUFACTURER DOES NOT PROVIDE BACKDRAFT DAMPERS AS AN INTEGRAL ACCESSORY TO THE UNIT, THIS SHALL BE EXPLICITLY LABELED IN THE MECHANICAL SUBMITTALS. DUCT-MOUNTED BACKDRAFT DAMPERS SHALL BE INSTALLED AS AN ALTERNATE IF FAN IS
APPROVED DURING SUBMITTAL.
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC
SCHEDULE
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M202
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 Permit Rev 1
8 6
1 9
: REFRIGERANT LINE TO CONDENSER, SEE PLAN FOR CONDENSER
LOCATION, DO NOT BLOCK FILTER ACCESS PANEL
FOR ADDITIONAL REQUIREMENTS, DO NOT BLOCK FILTER ACCESS PANEL
: CONNECT TO CONDENSATE TRAP, SEE CONDENSATE TRAP DETAIL
: FILTER ACCESS PANEL, "DO NOT BLOCK"
SEE SPECIFICATION FOR ADDITIONAL REQUIREMENTS
: CONNECT TO RA DUCT, SEE PLAN FOR SIZE AND LOCATION,
: CONNECT TO SA DUCT, SEE PLAN FOR SIZE AND LOCATION
: AHU, SEE SCHEDULE FOR SIZE AND PLAN FOR LOCATION
: SHEET METAL RA PLENUM WITH EXTERNAL INSULATION, SEE
SPECIFICATION FOR ADDITIONAL REQUIREMENTS
BOLTS TO PREVENT MOVEMENT.
BOLTS AT FOUR CORNERS. FASTEN AHU ONTO THE FRAME WITH
RISER SUPPORT. ANCHOR FRAME TO FLOOR WITH 1/2" ANCHOR
: 1-1/2x1-1/2x1/4 GALV. STEEL FRAME FOR AHU AND RA DUCT
: SECONDARY DRAIN PAN UNDER STEEL MOUNTING FRAME, SEE SPECIFICATION
FOR ADDITIONAL INFORMATION
DIFFUSER
METAL SHIELD
OR CEILING.
SPIN-IN FITTING WITH AIR
SCOOP AND LOCKING DAMPER
INSULATION
SUPPLY DUCT
METAL CLAMP AROUND FLEX
DUCT & COLLAR. CONNECTION
TO
BE DRAWN TIGHT & TAPED.
WRAP INSULATION
DOWN
TO CEILING FORMING
AIRTIGHT SEAL.
PRE-INSULATED FLEX.
DUCT
8'-0" MAXIMUM LENGTH.
WRAP INSULATION TO
FLEX
DUCT WITH DUCT TAPE
FORMING AIRTIGHT SEAL.
DO NOT LAY ON LIGHT FIXTURES
SUPPORT DUCT FROM STRUCTURE
REFER TO ARCH.
DWG's
FOR CEILING TYPE.
ATTACH STRAP HANGER TO
BLDG.
STRUCTURE WITH ANCHOR BOLT
AND LOCK WASHER - TYP.
STRAP HANGER FOR
HVAC
DUCTWORK PER SMACNA
STANDARDS
ATTACH STRAP HANGER TO
BLDG.
STRUCTURE WITH ANCHOR BOLT
AND LOCK WASHER - TYP.
RECT. DUCT WITH WIDTH
OF
22" AND SMALLER, SEE
PLAN
FOR SIZE AND LOCATION
STRAP HANGER FOR
HVAC
DUCTWORK PER SMACNA
STANDARDS
RECT. DUCT WITH WIDTH
OF
24" OR LARGER, SEE PLAN
FOR SIZE AND LOCATION
LOAD RATED FASTENER FOR
STRAP HANGER PER
SMACNA
STANDARDS
SIZE AND LOCATION
DUCT, SEE PLAN FOR
INSULATED HVAC
FOR SIZE AND LOCATION
SEE STRUCTURAL DWG.
STRUCTURAL JOIST
FASTENER
LOAD RATED
METAL GA. AND HANGER
LOOP FOR DUCT SUPPORT,
1" WIDE HANGER STRAP
STANDARDS
SPACING PER SMACNA
RA GRILLE, SEE PLAN
FOR SIZE AND LOCATION
INSULATION
RETURN DUCT
INSULATION
FLEX. DUCT
PRE-INSULATED
RA DUCT, SEE
PLAN FOR SIZE
LAY-IN CEILING
DIRECTION
AIR FLOW
SA DUCT
DIFFUSER FACE
WITH KEY OPERATOR THRU
ADJ. VOLUME EXTRACTOR
O.B. BAL. DAMPER
SPLINE DRIVE SLOT
THRU. FACE OF REGISTER
WALL
SIDEWALL DIFFUSER LOCATED
BELOW FINISHED CEILING
(SEE FLOOR PLANS FOR
MOUNTING HEIGHT)
SUPPORT DUCT FROM
STRUCTURE DO NOT LAY ON
LIGHT FIXTURES OR CEILING.
PRE-INSULATED FLEX DUCT
INSULATED MECH. PLENUM
PROVIDE PLENUM
EXTENSION WHEN NEEDED.
SLOT DIFFUSER.
BLOCKING (TYP.) BY OTHERS
SEE PLAN FOR LOCATION
DUCT, SEE PLAN
AND LOCKING DAMPER
FITTING WITH AIR SCOOP
INSULATED SPIN-IN
PLAN FOR SIZE
FLEX. DUCT, SEE
PRE-INSULATED
DUCT TO SA OUTLET
PRE-INSULATED FLEX.
DUCT FROM MAIN SA
FOR SIZE
WITH HANGER STRAP
FROM STRUCTURE
SUPPORT DUCT
INSULATED SA
STRUCTURE, DO NOT
SUPPORT DUCT FROM
LAY ON LIGHT
FIXTURES OR CEILING.
HVAC SUPPLY AIR
DUCT FROM AHU,
SEE PLAN FOR SIZE
AND LOCATION
HVAC BRANCH DUCT, SEE
PLAN FOR SIZE AND
LOCATION.
MAXIMUM OPENING SIZE SHALL NOT EXCEED 1/8" PER FOOT PLUS 1", NOR SHALL THE OPENING BE LESS THAN 1/4" LARGER THAN
1. OPENING IN FLOOR OR FIRE WALL SHALL BE A MINIMUM OF 1/8" PER FOOT LARGER THAN OVERALL SIZE OF DAMPER & SLEEVE ASSEMBLY.
2. DUCT AND SLEEVE SHALL NOT BE LESS THAN 16 GAGE FOR DAMPER UP TO 36" WIDE & 24" HIGH AND NOT LESS THAN 14 GAGE FOR ALL OTHERS.
DUCT CONNECTION SHALL BE PLAIN S-SLIP, HEMMED S-SLIP, STANDING S-SLIP, REINFORCED S-SLIP OR INSIDE S-SLIP.
3. MOUNTING ANGLES SHALL BE 1-1/2" X 1-1/2" X 14 GAGE MINIMUM AND FASTENED WITH NO. 10 BOLTS OR SCREWS ON 8" CENTERS.
4. APPROVED CAULK MATERIAL SHALL BE DOW-CORNING 999, DOW-CORNING SILASTIC 732, OR GE RTV 108 SEALANT. APPLY CONTINUOUS 1/8" BEAD OF SEALANT BETWEEN DAMPER AND SLEEVE ON ONE SIDE OF SMOKE DAMPER. SEALANT IS NOT REQUIRED ON FIRE DAMPER
5. PLACE OPERATOR/ACTUATOR ON ENTERING AIR SIDE OF COMBINATION SMOKE/FIRE DAMPER.
INSTALLATION INSTRUCTIONS FOR BOTH FIRE AND FIRE/SMOKE DAMPERS.
ANY SIZE DAMPER AND SLEEVE ASSEMBLY.
ONLY APPLICATIONS.
PROVIDE ACCESS DOOR OR
PANEL FOR SERVICE AND
INSPECTION. OPENING SHALL BE
LARGE ENOUGH TO CHANGE
LINK.
FIRE WALL
6" MAX
APPROVED FIRE DAMPER WITH 165F FUSIBLE
LINK. FIRE DAMPER MFG. INSTALLATION DETAILS
AND INSTRUCTIONS AS TESTED AND APPROVED
BY U.L. SHALL BE USED IN LIEU OF THIS DETAIL
WHERE APPLICABLE. PROVIDE COPY OF MFG.
INSTALLATION INSTRUCTIONS AT TIME OF
INSPECTION.
RETAINING ANGLES:
MIN. 1.5 X 1.5 X 16 GA.
SECURE RETAINING ANGLES TO SLEEVE ONLY
WITH NO. 10 SCREWS 8" ON CENTER.
RETAINING ANGLE SHALL OVER-LAP EDGE OF
OPENING BY 1" MINIMUM BEYOND ALL
MATERIALS IN OPENING.
FIRE WALL
1/8" MIN. CLEARANCE PER
LINEAR FT. BOTH
DIMENSIONS
STEEL SLEEVE: STEEL GAUGE AS
REQUIRED BY MANUFACTURER'S
INSTRUCTIONS. SECURE DAMPER TO
SLEEVE WITH NO.10 STEEL SCREWS 8"
ON CENTER.
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC DETAILS
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M203
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1/8" = 1'-0"1 DETAIL - AHU FLOOR SUPPORT LT
N.T.S.2
DETAIL - DIFFUSER INSTALLATION
(FLEX)
N.T.S.3 DETAIL - DUCT SUPPORT
N.T.S.4 DETAIL - DUCT SUPPORT (JOISTS)
N.T.S.7 DETAIL - RA GRILLE INSTALLATION
N.T.S.5 DETAIL - SIDEWALL DIFFUSER
N.T.S.6 DETAIL - SLOT DIFFUSER (BORDER 77)
N.T.S.8 DETAIL - SUPPLY AIR BRANCH
N.T.S.9
DETAIL - WALL-MOUNTED FIRE DAMPER
DETAIL
REVISIONS
INTAKE HOOD
OUTSIDE AIR
ROOF TOP A/C UNIT
SEE PLAN FOR LOCATION
SIZE AND LOCATION
RETURN AIR DUCT FROM
SPACE, SEE PLAN FOR
SUPPLY AIR DUCT TO
SIZE AND LOCATION
SPACE, SEE PLAN FOR
PROVIDE MIN. 8" CLEARANCE BETWEEN
ROOF
AND RTU PER FBC CODE CHAPTER 15. PARA.
1510.10 'MECHANICAL UNITS' REQUIREMENTS
CURB AT PERIMETER 4 SIDES
AT 10" O.C. INTO ROOF
PROVIDE TEK#10 SCREWS
ROOF CURB
VENT
GOOSENECK
WITH SCREW-IN CAP
FEMALE HOSE CONNECTION
SLOPE TOWARD DRAIN
CURB AT PERIMETER 4 SIDES
AT 10" O.C. INTO ROOF
PROVIDE TEK#10 SCREWS
PER
EQUIPMENT
MANUFACTURER'
S
REQUIREMENT
PVC CONDENSATE TRAP (MIN.
4"
DEEP OR PER EQUIP.
MANUFACTURER'S
REQUIREMENTS)
BALL VALVE
SMOKE DETECTOR, FURNISHED
BY
ELECTRICAL CONTRACTOR AND
INSTALLED BY MECHANICAL
CONTRACTOR.
SMOKE DETECTOR, FURNISHED
BY
ELECTRICAL CONTRACTOR AND
INSTALLED BY MECHANICAL
CONTRACTOR.
FINISHED
GRADE
ANCHOR RESIDENTIAL TYPE
CONDENSER TO CONC. MOUNTING
PAD IN ACCORDANCE WITH FBC
MECH SECTION 301.CONC. MOUNTING PAD,
PROVIDE AND INSTALL PAD
PER
REQUIREMENTS OF FBC-
MECH.
PARA 304.10 REQUIREMENTS
AND DETAILS.
SEE STRUCTURAL DRAWINGS FOR ANCHORING EQUIPMENT SIZES4.
FLASHING, GALV. STEEL
BASE TO METAL STRAP
BOLT THROUGH TO CONNECT FAN
HVAC EQUIPMENT
ROOF MOUNTED
TO NAILER STRIP
RUN ROOF MEMBRANE UNDER
COUNTER FLASHING AND NAIL
ROOF INSULATION
ON ROOF DECK.
SCREW CURB TO
SET ROOF CURB
ROOF DECK.
ROOF DECK
JOIST OR BEAM
ROOF MEMBRANE
3/8"x3" BOLT (MIN. 2 PER SIDE)
BOLT AT 12" O.C. ALL SIDES MIN
GASKET
16 GA. (MIN.)
1/8"x2" METAL STRAP
GALV. METAL CURB
2"x2" WOOD
3/8"∅ BOLT
SEE STRUCTURAL DWGS
FOR ANGLE SIZES
STYROFOAM INSULATION
(SEE NOTE No.1)
FOIL FACED DOW
FRAMING AROUND OPENING
1.
3.
2.
NOTES:
INSTALLATION TO WITHSTAND WIND RATING AS DEFINED IN STRUCTURAL DRAWINGS.
ADDITIONAL BRACING AND SUPPORT AS REQUIRED FOR ROOF CURB
ROOF CURB BY AIR CONDITIONER/FAN MANUFACTURER. PROVIDE
CURB HEIGHT SHALL BE AS STATED IN SCHEDULES NOTES OR IN SPECS.
OPENING SIZE WITH THE INSULATION & STEEL CONTRACTORS.
MECHANICAL CONTRACTOR SHALL COORDINATE OVERALL ROOF
SECURE ROOF CURB TO STRUCTURAL ROOF DECK1
BIRD
SCREEN
SECURE FAN TO ROOF CURB
WITH TEK#10 SCREWS AT 10" O.C.
AT PERIMETER 4 SIDES
ROOF
GRAVITY BACK-
DRAFT DAMPER
EA DUCT
ROOF CURB
SPUN ALUMINUM
ROOF EXHAUSTER
STAINLESS
STEEL SHEET
METAL GOOSE
NECK &
FLASHING
ROOF CURB
ROOF
REFRIG. PIPING
SEAL AND PROTECT
OPENING AGAINST WEATHER
AND INSECTS
ALUMINUM JACKETING
ROOF TRUSS
24"
ON CENTER
VA
R
IE
S
FI
EL
D V
ER
IF
Y
MECHANICAL EQUIPMENT/KITCHEN HOOD
THREADED ROD - SIZED
PER MANUFACTURERS
RECOMMENDATION
FOR
EQUIPMENT LOAD.
UNISTRUT - FASTEN TO TOP
OF
BOTTOM CHORD OF TRUSS.
PROVIDE UNISTRUT MODEL
RATED FOR EQUIPMENT LOAD
PER MANUFACTURERS
RECOMMENDATIONS.
WALL
WATER TIGHT SEAL.
CAULK TO PROVIDE
DUCT
WALL CAP WITH BUILT-IN DAMPER & INSECT
SCREEN.
(ALL SCREENS SHALL BE OMITTED OR REMOVED
FOR WALL CAPS SERVING DRYERS.)
INLINE FAN, SEE
PLAN
FOR LOCATION
TOTAL 4 REQUIRED
VIBRATION ISOLATOR
SPRING TYPE
SECURE 1/2" HANGER
ROF TO BLDG.
STRUCTURE - TYP. FOR 4
S/E FAN
BALL VALVE
A/C UNIT
EZ TRAP INC. MODEL EZT 200
INLINE CONDENSATE
OVERFLOW SWTCH.
CONNECT TO AHU TO SHUT
OFF UNIT WEHN WATER
FILLS TRAP ABOVE INLET.
PER EQUIPMENT
MANUFACTURER'S
REQUIREMENT
CONDENSATE TO FLOOR
DRAIN OR OTHER APPROVED
LOCATION. SLOPE TOWARD
DRAIN.
PVC CONDENSATE TRAP (MIN 4" DEEP
OR PER EQUIPMENT
MANUFACTURER'S REQUIREMENTS.)
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC DETAILS
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M204
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
N.T.S.2 DETAIL - ROOFTOP AC UNIT
N.T.S.3 DETAIL - PAD MOUNTED CONDENSER
N.T.S.4 DETAIL - ROOF CURB HOLD DOWN
N.T.S.5 DETAIL - ROOF EXHAUST FAN
N.T.S.6 DETAIL - ROOF PENETRATION
N.T.S.7 DETAIL - UNISTRUT
N.T.S.8 DETAIL - WALL CAP
N.T.S.9 DETAIL - IN-LINE MOUNTING DETAIL
N.T.S.10
DETAIL - CONDENSATE TRAP WITH
FLOAT SWITCH
REVISIONS
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
APP BAY
EXHAUST
SEQUENCE
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M205
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
REVISIONS
# DATE DESCRIPTION
NEW SHEET
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC -
KITCHEN HOOD
DRAWINGS
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M301
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
REVISIONS
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC -
KITCHEN HOOD
DRAWINGS
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M302
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
REVISIONS
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC -
KITCHEN HOOD
DRAWINGS
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M303
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC -
KITCHEN HOOD
DRAWINGS
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M304
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC -
KITCHEN HOOD
DRAWINGS
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M305
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC -
KITCHEN HOOD
DRAWINGS
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M306
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4 P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5 W. W. W. D A S H E R H U R S T . C O M
HVAC -
KITCHEN HOOD
DRAWINGS
22003
06.23.2023
C O
UN
TY
R O
A D
G
RE
EN
C
O V
E
SP
RI
N
G S, F L
M307
BID DOCUMENTS
C
LA
Y C
O
UN
TY
C
LA
Y C
O F
IR
E
ST
A
TIO
N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
| M101A - HVAC FLOOR PLAN - AREA "A" |
| M101B - HVAC FLOOR PLAN - AREA "B" |
| M101C - HVAC FLOOR PLAN - AREA "C" |
| M102 - HVAC ROOF PLAN |
| M201 - HVAC SCHEDULE |
| M202 - HVAC SCHEDULE |
| M203 - HVAC DETAILS |
| M204 - HVAC DETAILS |
| M205 - APP BAY EXHAUST SEQUENCE |
| M301 - HVAC - KITCHEN HOOD DRAWINGS |
| M302 - HVAC - KITCHEN HOOD DRAWINGS |
| M303 - HVAC - KITCHEN HOOD DRAWINGS |
| M304 - HVAC - KITCHEN HOOD DRAWINGS |
| M305 - HVAC - KITCHEN HOOD DRAWINGS |
| M306 - HVAC - KITCHEN HOOD DRAWINGS |
| M307 - HVAC - KITCHEN HOOD DRAWINGS |
File details come from the government source that posted it. Updated .