Clay_Co_FS24_Elec_(2026_01-02)_Bid_Set.pdf
PDF 10 MB Posted
- Attached to
- Construction of Clay County Fire Station No. 24
- Solicitation number
- 25/26-042
- Issued by
- Clay County, Harold CDP, Florida
About this file
This is an electrical bid set of construction documents for Clay County Fire Station No. 24, a new approximately 16,633 square-foot fire station facility located at 1075 County Road 226 in Green Cove Springs, Florida. The electrical scope encompasses a complete 1,000-ampere, 208/120-volt, three-phase service with automatic transfer switch and 275-kilowatt diesel generator backup, interior and exterior lighting systems utilizing LED fixtures with occupancy sensors, fire alarm and detection systems with addressable components, lightning protection systems, communications infrastructure including Cat-6 cabling, data outlets, wireless access points, and security systems integration. The project includes photometric site plans, electrical site plans, lighting plans, power and communication plans, fire alarm plans with riser diagrams, panel schedules for multiple distribution panels (MDP, P, P2, P3, L, and PW), grounding systems, and detailed electrical specifications. Mandatory pre-bid conference is scheduled for February 6, 2026, at 10:00 a.m. at the project site; questions must be submitted by February 13, 2026, at 4:30 p.m.; sealed bids are due electronically by March 2, 2026, at 4:00 p.m.; and bid opening occurs on March 3, 2026, at 9:00 a.m. Substantial completion is required by March 15, 2027, with final Certificate of Occupancy by March 20, 2027, to meet grant deadlines.
The bid documents establish comprehensive technical specifications for electrical work including wire sizing calculations, voltage drop analysis, equipment schedules with manufacturer specifications, arc flash labeling requirements, and specialized systems such as emergency lighting with battery backup, fire pump controls with dedicated service entrance, apparatus bay lighting controls, and integration with Purvis notification systems. Bidders must be Florida-licensed General Contractors with minimum five years experience in similar work and must comply with Davis-Bacon Act prevailing wage requirements due to Federal Emergency Management Agency (FEMA) Public Assistance Grant Program funding. Performance and Payment Bonds equal to 100 percent of contract value and Commercial General Liability insurance of $1,000,000 per occurrence and $2,000,000 aggregate are required. Liquidated damages of $1,000 per day apply for delays beyond the final completion date. No specific budget or contract value is disclosed in the available documents. The County reserves the right to approve all subcontractors and may utilize a Direct Purchase Program to procure major materials directly, with such purchases deducted from the contract price.
View the file
Other files
Show all 48
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Image
Symbol Label QTY Catalog Number Description Lamp Number
Lamps Filename
Lumens per
Lamp
Lumen
Multiplier LLF Wattage Manufacturer
P1
18 DSX1 LED P1 40K TFTM
MVOLT HS
DSX1 LED P1 40K TFTM MVOLT
with houseside shield
LED 1 DSX1_LED_P1_40K_TFT
M_MVOLT_HS.ies
5436 1 0.95 54 Lithonia
Lighting
Schedule
Symbol Label QTY Manufacturer Catalog Description Number
Lamps
Lamp
Output
LLF
Input
Power
P1 18 Lithonia Lighting DSX1 LED P1 40K TFTM
MVOLT HS
DSX1 LED P1 40K TFTM MVOLT with houseside shield
1 5436 0.95 54
P1
P1
P1
P1
P1
P1
P1
P1 P1 P1 P1 P1 P1
P1 P1
P1
P1
P1
Statistics
Description Symbol Max Min Avg/Min Avg Max/Min
Calc Zone #5 1.8 fc 0.0 fc N/A 0.7 fc N/A
Calc Zone #2 1.7 fc 0.0 fc N/A 0.7 fc N/A
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
0.2
0.2
0.2
0.1
0.1
0.1
0.2
0.3
0.3
0.3
0.3
0.3
0.2
0.1
0.3
0.4
0.5
0.5
0.4
0.4
0.3
0.1
0.5
0.6
0.6
0.5
0.5
0.4
0.1
0.6
0.7
0.7
0.7
0.7
0.6
0.2
0.6
0.8
0.8
0.9
0.9
0.8
0.3
0.6
0.8
0.8
0.9
1.0
0.9
0.2
0.6
0.8
0.8
0.8
0.9
0.7
0.3
0.6
0.8
0.8
0.7
0.7
0.5
0.2
0.6
0.7
0.7
0.6
0.6
0.4
0.1
0.5
0.7
0.7
0.6
0.5
0.3
0.1
0.5
0.7
0.6
0.6
0.5
0.3
0.1
0.6
0.7
0.7
0.6
0.6
0.4
0.1
0.6
0.8
0.7
0.7
0.6
0.5
0.2
0.7
0.8
0.8
0.8
0.8
0.7
0.2
0.6
0.8
0.8
0.9
1.0
0.9
0.3
0.6
0.9
0.8
0.9
1.0
0.9
0.3
0.7
0.9
0.8
0.8
0.8
0.7
0.3
0.7
0.8
0.8
0.7
0.6
0.5
0.2
0.7
0.8
0.8
0.6
0.6
0.4
0.1
0.7
0.8
0.7
0.6
0.6
0.4
0.1
0.3
0.4
0.5
0.4
0.6
0.5
0.4
0.4
0.5
0.6
0.8
0.9
1.0
0.9
0.8
0.7
0.6
0.4
0.1
0.5
0.7
1.0
1.3
1.2
1.1
0.9
0.9
1.0
1.2
1.5
1.5
1.4
1.3
1.2
0.9
0.8
0.5
0.2
0.6
0.8
1.1
1.4
1.4
1.2
1.2
1.2
1.2
1.4
1.5
1.6
1.5
1.4
1.2
1.0
0.9
0.7
0.3
0.7
0.9
1.1
1.4
1.5
1.6
1.6
1.6
1.5
1.5
1.5
1.5
1.6
1.6
1.4
1.2
1.2
0.9
0.3
0.8
1.0
1.2
1.4
1.6
1.7
1.6
1.6
1.6
1.6
1.4
1.3
1.3
0.6
0.4
0.7
0.9
1.1
1.3
1.5
1.7
1.7
1.7
1.7
1.6
1.5
1.5
1.6
1.5
1.3
1.2
1.2
0.9
0.4
0.5
0.7
0.8
1.0
1.2
1.4
1.6
1.6
1.4
1.3
1.2
1.2
1.3
1.3
1.1
1.0
0.9
0.7
0.3
0.4
0.5
0.6
0.7
0.8
1.2
1.4
1.4
1.2
0.9
0.8
0.9
1.0
1.0
0.9
0.7
0.6
0.5
0.2
0.2
0.2
0.3
0.4
0.5
0.8
1.0
1.0
0.8
0.6
0.6
0.6
0.7
0.7
0.7
0.6
0.5
0.3
0.1
0.5
0.5
0.5
0.4
0.4
0.2
0.1
0.4
0.5
0.5
0.4
0.4
0.2
0.1
0.4
0.5
0.5
0.4
0.4
0.2
0.1
0.5
0.6
0.6
0.5
0.5
0.3
0.1
0.6
0.7
0.7
0.6
0.5
0.4
0.2
0.6
0.8
0.8
0.8
0.8
0.6
0.2
0.6
0.8
0.8
0.9
1.0
0.8
0.3
0.6
0.8
0.8
0.9
1.0
0.8
0.3
0.1
0.1
0.2
0.4
0.6
0.8
0.8
0.8
0.8
0.6
0.2
0.1
0.1
0.2
0.4
0.6
0.7
0.7
0.6
0.6
0.4
0.2
0.1
0.1
0.2
0.4
0.5
0.6
0.6
0.5
0.5
0.3
0.1
0.1
0.1
0.2
0.3
0.5
0.5
0.5
0.4
0.4
0.3
0.1
0.1
0.1
0.1
0.2
0.3
0.4
0.5
0.5
0.4
0.4
0.2
0.1
0.1
0.1
0.1
0.2
0.3
0.5
0.5
0.5
0.4
0.4
0.3
0.1
0.1
0.1
0.2
0.2
0.4
0.5
0.6
0.6
0.5
0.5
0.3
0.1
0.2
0.2
0.2
0.3
0.5
0.6
0.7
0.7
0.7
0.6
0.4
0.2
0.1
0.1
0.2
0.3
0.4
0.3
0.4
0.4
0.6
0.7
0.9
0.8
0.8
0.8
0.7
0.3
0.3
0.4
0.5
0.7
0.9
1.0
0.9
0.7
0.8
0.9
1.1
1.0
1.0
1.1
0.9
0.3
0.4
0.6
0.8
1.0
1.2
1.3
1.2
1.0
1.1
1.2
1.3
1.2
1.2
1.2
0.9
0.3
0.6
0.8
1.0
1.2
1.4
1.5
1.4
1.3
1.4
1.4
1.4
1.2
1.1
1.1
0.8
0.3
0.7
1.0
1.2
1.5
1.5
1.6
1.6
1.5
1.6
1.6
1.5
1.3
1.1
0.9
0.6
0.2
0.7
1.0
1.3
1.5
1.6
1.7
1.7
1.6
1.7
1.6
1.6
1.4
1.1
0.9
0.6
0.2
0.6
0.9
1.1
1.3
1.4
1.5
1.5
1.5
1.5
1.5
1.5
1.3
1.1
0.9
0.6
0.2
0.5
0.7
0.9
1.1
1.3
1.3
1.3
1.2
1.3
1.4
1.4
1.2
1.1
1.0
0.8
0.3
0.4
0.5
0.6
0.9
1.2
1.2
1.1
0.9
1.0
1.2
1.3
1.1
1.1
1.2
0.9
0.3
0.1
0.1
0.3
0.4
0.5
0.6
0.5
0.5
0.6
0.9
1.0
0.9
1.0
1.1
0.9
0.3
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0 0.0 0.0 0.0
1.8
1.8
1.8
1.8
0.1
0.1
0.1
0.2
0.1
0.1
0.1
0.1
0.3
0.3
0.2
0.1
0.2
0.4
0.4
0.4
0.4
0.2
0.5
0.6
0.5
0.5
0.5
0.2
0.2
1.0
0.9
0.7
0.7
0.4
0.9
1.1
1.0
0.8
0.8
0.2
0.5
0.9
1.0
1.0
0.9
0.9
0.1
0.3
0.7
0.8
0.9
0.9
1.0
0.1
0.5
0.7
0.8
0.9
1.0
0.3
0.7
0.7
0.9
1.0
1.0
0.3
0.7
0.8
0.8
0.9
1.0
0.4
1.0
1.0
0.9
1.0
1.0
0.5
1.1
1.0
1.0
1.0
0.2
0.6
0.9
0.9
0.9
0.9
0.2
0.5
0.7
0.8
0.8
0.9
0.1
0.5
0.6
0.7
0.8
0.8
0.1
0.2
0.5
0.6
0.7
0.7
0.1
0.4
0.5
0.6
0.7
0.7
0.2
0.5
0.6
0.6
0.7
0.7
0.4
0.7
0.6
0.7
0.8
0.3
0.7
0.9
0.8
0.8
0.8
0.3
1.0
1.0
0.9
0.8
0.9
0.4
0.9
0.9
0.9
0.9
0.8
0.2
0.4
0.7
0.8
0.8
0.9
0.1
0.5
0.6
0.7
0.8
0.8
0.2
0.5
0.6
0.7
0.8
0.8
0.3
0.6
0.6
0.7
0.8
0.2
0.5
0.6
0.7
0.8
0.8
0.3
0.8
0.8
0.8
0.8
0.8
0.5
1.0
0.9
0.8
0.9
0.9
0.3
0.8
1.1
1.0
0.9
0.9
0.8
0.3
0.8
1.0
1.0
1.0
1.0
0.8
0.6
0.3
0.7
0.8
1.0
1.1
1.2
1.1
1.0
0.8
0.3
0.4
0.3
0.7
0.8
1.0
1.1
1.2
1.1
1.1
1.2
1.1
0.9
0.1
0.4
0.7
0.8
1.1
1.2
1.3
1.2
1.2
1.2
1.1
0.9
0.2
0.7
0.8
1.0
1.3
1.4
1.4
1.4
1.3
1.2
1.1
0.9
0.4
0.8
0.9
1.2
1.5
1.6
1.6
1.6
1.5
1.4
1.3
1.1
0.3
0.7
1.0
1.1
1.3
1.5
1.6
1.5
1.5
1.3
1.1
0.4
1.0
1.2
1.2
1.4
1.6
1.6
1.6
1.4
1.3
1.2
1.1
1.0
0.5
1.2
1.2
1.2
1.3
1.4
1.4
1.3
1.2
1.1
0.9
0.8
0.7
0.6
1.0
1.1
1.1
1.2
1.2
1.2
1.2
1.1
1.0
0.8
0.6
0.5
0.2
0.5
0.7
0.8
1.0
1.1
1.1
1.1
1.1
0.1
0.9
0.7
0.5
0.4
0.1
0.4
0.5
0.6
0.7
0.7
0.7
0.6
0.5
0.4
0.4
0.3
0.2
0.1
0.5
0.6
0.6
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
0.0
1.7
1.7
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
PHOTOMETRIC
SITE PLAN
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
E001
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
NTS
PHOTOMETRIC SITE PLAN
REVISIONS
# DATE DESCRIPTION
S B
J J
J
J
J
J
J
C A M
C A M
C A M
PROPOSED
208/120/3P/4W
UTILITY XFMR
275KW
DIESEL
GENERATOR
CT CABINET,
CAMLOCK BOX
& UTILITY
METER
ATS
TBB
J L - 10
PROVIDE CONNECTION
TO MONUMENT SIGN
TYPE S1
J
P2 - 32
GATE OPERATOR
P1 P1 P1 P1 P1 P1
P1
P1
P1
P1
P1 L - 11,13
L - 12,14
(#10)
(#10)
PW - 8,10
WELL
WELL
WELL
PW - 9,11
PW - 12,14
P1
P1
P1
L - 16,18
P1
P1
P1
P1
L - 17
FP
WP
WP
P3 - 10
P3 - 9
(#10)
WP
WP
WP
P3 - 11
P3 - 13
P3 - 12
(#10)
(#10)
(#10)
P3 - 14
(#10)
REMOVED
TOWER
REMOVED
CAR CHARGER
CR
FP
FP
CARD READER
CR
CARD READER
AT GATE
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
ELECTRICAL
SITE PLAN
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
E100
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1" = 20'-0"
ELECTRICAL SITE PLAN
1. ELECTRICAL SITE PLAN NOTES:
1. PRIOR TO START OF ANY WORK OBTAIN WRITTEN APPROVAL FOR LOCATION OF POLE/TRANSFORMERS & CONNECTION POINT PER ELECTRIC UTILITY CO DIRECTION. CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND COMPLYING WITH MOST CURRENT UTILITY RULES AND REGULATIONS. PROVIDE SERVICE ENTRANCE CONDUITS W/36" RADIUS ELLS AT POLE & SERVICE CONNECTION POINT. PROVIDE CONDUITS WITH PULLWIRES AND MAINTAIN 42" MINIMUM DEPTH, LOCATION OF POLE/TRANSFORMERS AND SECONDARY CONDUIT/FEEDER(S) ARE CONTINGENT UPON ELECTRICAL UTILITY CO APPROVAL. PROVIDE GROUND RODS PER ELECTRICAL UTILITY CO REQUIREMENTS.SEE 'POWER RISER ' FOR
ADDITIONAL REQUIREMENTS. CLAY ELECTRIC UTILITY CONTACT IS XXX AT 904-276-6719.
2. PRIOR TO START OF ANY WORK OBTAIN WRITTEN APPROVAL FOR LOCATION OF SERVICE
CONDUITS & CONNECTION POINT PER TELEPHONE UTILITY DIRECTION. PROVIDE (2) 2"
CONDUITS WITH PULLWIRE TO PROPERTY LINE, STUB UP AND CAP AND MARK 'TELEPHONE'.
SEE ALSO 'TELEPHONE BACKBOARD RISER' FOR ADDITIONAL REQUIREMENTS.
3. SERVICE ENTRANCE FROM ELECTRICAL UTILITY CO TRANSFORMER, SEE 'POWER RISER' FOR
ADDITIONAL REQUIREMENTS.
4. FIRE PUMP SECONDARY SERVICE. PROVIDE CONNECTION TO FIRE PUMP CONTROLLER.
5. STAND-BY DIESEL GENERATOR WITH PAD .ALL CONDUITS AND WIRING SHALL BE BY ELECTRICAL CONTRACTOR.
6. NEW UTILITY POLE ON THE OTHER SIDE OF COUNTY ROAD 226.
7. PROVIDE 1" CONDUIT TO STUB UP INTO WATCH ROOM FROM GATE CONTROLLER.
8. CONFIRM LOCATION, QUANTITY AND HORSEPOWER OF EACH WELL FROM CIVIL BEFORE ROUGH-IN.
9. MOUNT FLAGPOLE LIGHTS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
10. PROVIDE GFI RECEPTACLE WITH WATERPROOF IN-USE COVER AT LIGHT POLE INDICATED.
11. PROVIDE MECLUBE 090-5070-07X DIESEL TRANSFER SYSTEM 'CAMI DISPENSER' SYSTEM AT GENERATOR DIESEL BASE
TANK. INSTALL, POWER AND GROUND PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
12. PROVIDE (2) 1" CONDUITS TO STUB UP INTO WATCH ROOM FROM GATE CONTROLLER. ONE CONDUIT SHALL BE FOR GATE CONTROLLER/COMMUNICATION, THE OTHER 1" CONDUIT SHALL EXTEND TO CARD READER PEDESTAL/CAMERAS.
COORDINATE EXACT LOCATION WITH GATE MANUFACTURER INSTALLATION INSTRUCTIONS. CARD READER AND CAMERA CABLING SHALL EXTEND FROM PEDESTAL TO ACCESS CONTROL SYSTEM AND CAMERA CONTROLLER AS REQUIRED.
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 Permit Rev 1
5 07/19/2024 VE Rev 1
6 09/05/2025 90% IRC REVIEW
M
M
M
M
M M
M
D M
M
M
M
M
M
M M
M
M
DD
D
M
D
M
M
CLOSET
IT
LAUNDRY
CAPT OFF
LOCKERS
ELEC
OFFICE
OFFICE
UTIL
CORR
MEDICAL
MAINT
STOR
LOCKER
VESTIBULE
BUNK4
BUNK3
STOR
WATCH
FITNESS
CAPTAIN'S SUITE
DECON
LOCKER
LOCKER
LOCKER
LOCKER
LOCKER
CORR
APP BAY
BUNK5
BUNK6
BUNK1
BUNK2
BUNK9
BUNK10
BUNK7
BUNK8
BUNK 11
BUNK 12
LOBBY
L - 2
L - 1
B1 B1 B1 B1 B1
B1 B1 B1 B1B1 B1 B1 B1
B1 B1 B1 B1B1 B1 B1 B1
B1 B1 B1 B1B1 B1 B1 B1
B1 B1 B1 B1B1 B1 B1 B1
B1 B1 B1 B1B1 B1 B1 B1
B1 B1 B1 B1B1 B1 B1 B1
B1 B1 B1 B1B1 B1 B1 B1
B1 B1 B1 B1B1 B1
A1 A1
A1 A1
A1 A1 A1
A3A3 A3
A3
A3A3A3A3
A3A3
A3
A3
A3
A3
A3
A1
A1
A1
A1
A1
A1
A1
A1 A1
A1
A1
A1
A1
A1
A1
A1
A1 A1
A1
A1
A1
A1
A1
L - 3
A1 A1 A1 A1
L - 5
A3A3
A3
A3
A3
A3
A3 A3
A3
L - 4
F1
F1
F1
C1
C1
C1
C1 A1A1
A1
F1
F1
G2 G2 G2 G2
G2
G2G2G2G2
G2
G1
G1
L - 6
G2
EL
EL
EL
C2
EL
EL
A1
A3
G2
A1
A1
A1 A1
F3
F3
F3
F3
F3
F3
F3 F3
C5
C5
C5
C5
C5
C5
D D
L - 7
EL
EL
EL
EL
EL
EL
EL
EL
EL
EL
EL
C5
H2
H
H
H2
H
H
H
H2
H
H
H2
H
H
H
H2
H
H
H2
H
H
H
C2 C2 C2
C2
C2
C2
C2
C2C2
C2C2
C2
C2
C1
C1
C1
C1
C1
C1
C1
C2
C2
C2 C2
C2
C2
C1
C1
C1
C1 C1
C1
C1
C1
F1 F1F1
C1F3
L - 8
L - 9
G2
TIE TO
L-9
X1
X1
X1
X1
X1
X1
X1
X1
J J
PW - 6
K2
K
K
K
K
EL
EL
EL
EL
A1
EL
ELG1
EL
G1
EL
G1
EL
EL
EL
EL
REMOVED TOWER AND
RELATED LIGHTING
C2 J2
J2 J2
J2 J2
J2
MECH
F5
F5
C4
C4
EL
EL
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
LIGHTING PLAN
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
E101
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1/8" = 1'-0"
LIGHTING PLAN
NOTES:
1. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF ALL
CEILING LIGHT FIXTURES.
2. TYPICAL CEILING MOUNTED OCCUPANCY SENSOR CONNECTIONS (VIA LOW VOLT CABLES NOT
SHOWN);
A.) WHERE NO CIRCUIT NUMBERS OR SWITCH LETTERS ARE DESIGNATED; CONNECT ALL
CEILING MOUNTED OCCUPANCY SENSORS FOR AUTOMATIC CONTROL OF AREA LIGHT FIXTURES
IN TANDEM WITH LOCAL SWITCH AS INDICATED.
B.) WHERE ONE CIRCUIT NUMBER OR SWITCH LETTER IS SHOWN; CONNECT CEILING
MOUNTED OCCUPANCY SENSORS TOGETHER IN TANDEM WITH THAT DESIGNATED
CIRCUIT/LOCAL SWITCH LETTER (MAXIMUM 2,500 SQ FT PER SWITCH). SEE "TYPICAL OFFICE
AREA OCCUPANCY SENSOR WIRING DIAGRAM".
3. ALL SENSORS LOCATED IN AREAS SUCH AS BREAK ROOMS & MECHANICAL ROOMS SHALL BE
PROGRAMMED AS VACANCY TYPE SENSORS. ALL SENSORS LOCATED IN AREAS SUCH AS OPEN
AREAS, CORRIDORS & RESTROOMS SHALL BE PROGRAMMED AS OCCUPANCY TYPE SENSORS.
4. BATHROOM LIGHT MOTION SENSORS SHALL CONTROL BATHROOM LIGHTS AND FANS AND
SHALL BE SET TO TURN OFF AFTER 5 MINUTES OF NO OCCUPANTS DETECTED.
5. NOTE NOT USED
6. TYPE C4 AT CANOPIES SHALL BE TIED TO EXTERIOR LIGHTING CIRCUIT AND CONTROLLED BY
PHOTOCELL/TIMESWITCH.
C4 C4 C4
C4 C4 C4
G1
EL
EL EL EL
EL EL
EL
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 Permit Rev 1
G F
C I
J
J
J J
J
J
J
J
J
J
J
J J J
J J J
J
J
J J
J
J J
J J
J
J
J
J
J
J
J
J J
J
J
J
J
J
J
J
J
J
J J J
J
J J J J
J
J
J
J
J
CLOSET
IT
UTIL
LAUNDRY
UTIL
CAPT OFF
LOCKERS
ELEC
OFFICE
OFFICE
UTIL
CORR
CORR
MAINT
STOR
LOCKER
VESTIBULE
BUNK4
BUNK3
STOR
WATCH
CORR
MEETING
FITNESS
CAPTAIN'S SUITE
DECON
LOCKER
LOCKER
LOCKER
LOCKER
LOCKER
CORR
APP BAY
BUNK5
BUNK6
BUNK1
BUNK2
BUNK9
BUNK10
BUNK7
BUNK8
BUNK 11
BUNK 12
LOBBY
TV
72"
ATS
P2L
P
TV
72"
WP
WP
PHONE
42"
WP
WP
WAP
WAP
PHONE
WAP
WAP
AHU-4AHU-3
AHU-5
AHU-6
CU-6
AHU-1
AHU-2
P - 3
P - 4
P - 2
P - 1
P - 5
60" 60"
P - 6
P - 7P - 9
P - 10
P - 8
DINING
KITCHEN
P - 17 P - 18
P - 19
P - 20
P - 14
P - 15
P - 21
P - 11,13
P - 22
P - 12
PPE STOR
MEDICAL
P - 24
P - 23
P - 26
P - 25
P - 28
P - 27
P - 31
P - 29
P - 34
P - 30
P - 33
P - 35
P - 36
P - 38
M - 21,23
M - 20,22
M - 25,27 M - 24,26
M - 33,35
TO
CU-
FIT
48"x26.25", 120 V/208 V, Three Phase, 4 Wires, Wye - 8
AIR COMP.
P - 32 P - 40
P2 - 1
P2 - 2
WP
WP
WP
WP
P2 - 3
66" 66"
P2 - 4
P2 - 5
P2 - 6
P2 - 7 P2 - 8
P2 - 9,11,13 P2 - 10,12,14 P2 - 15,17,19
16 16 16
P2 - 16 P2 - 18 P2 - 20
16 16 16
P2 - 21,23,25
M
M - 1,3,5
UH-1
UH-2
M - 2,4,6
UH-3
M - 7,9,11
UH-4
M - 8,10,12
EF-2 EF-3
M - 13,15,17 M - 14,16,18
17 18
24 24
WP
WP
P2 - 22
P2 - 24
WP
P2 - 26
P2 - 27
P2 - 28
P2 - 29
P2 - 30
29 29
P2 - 31
EF-WELL
PW
PW - 1
44" 44"
(ON ROOF)
P2 - 33
P2 - 34,36,38
FPH-WELL
PW - 2,4
PW - 3,5,7
P2 - 35
ELECTRICAL CONTRACTOR SHALL REFER TO THE
PURVIS SYSTEM DRAWINGS AND PROVIDE THE
ELECTRICAL CONTACTOR SCOPE OF WORK INDICATED
ON THOSE DRAWINGS.
TV
72"
P2 - 37,3936
P2 - 40
34 34 3434
P - 16
72"
(TV)
P3
P3 - 1
41 41
41 41 41 41
P3 - 2 P3 - 3
P3 - 5 P3 - 6 P3 - 7 P3 - 8
P3 - 1572"
72"
P3 - 16,18
SCBA
P3 - 17,19
P3 - 20,22
P3 - 4
REMOVED TOWER AND
RELATED ELECTRICAL
P3 - 21,23
P3 - 24,26
FPH-STOR
FPH-MAINT
FPH-DECON
P3 - 25,27
34 34
34 34 3434 34 34
MDP-9
WP
(ON ROOF)
(ON ROOF)
P2 - 41
P - 39,41
5 7
BDA ANTENNA
LOCATION
(ON ROOF)
P2 - 42
76"
76"
P - 38
7 REVISED WATCHROOM
CU-FITCU-5
CU-4
CU-3
CU-IT
RTU-OA
CU-1
CU-2
M - 32,34
M - 36,38
M - 39,41
M - 29,31
M - 28,30
M - 40,42
TO
AHU-IT
EF-1
EF-HOOD
M - 19
M - 37
MDP-6
MDP-4
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
POWER/COMM
PLAN
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
E102
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1/8" = 1'-0"
POWER/COMM PLAN
NOTES:
1. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND REQUIREMENTS OF ALL HVAC
EQUIPMENT. IF CONDENSATE PUMP(S) ARE REQUIRED, TIE TO NEAREST 120V OUTLET.
2. PROVIDE TAMPER RESISTANT RECEPTACLES PER NEC 406.12
3. PROVIDE CONNECTION TO EWH-2.
4. STANDBY GENERATOR ANNUNCIATOR LOCATION. CONFIRM WITH OWNER BEFORE ROUGH-IN.
PROVIDE EMERGENCY STOP BUTTON ADJACENT TO GENERATOR ANNUNCIATOR. BUTTON SHALL
BE GLASS-BREAK TYPE WITH A NORMALLY OPEN CONTACT AND SHALL READ "EMERGENCY
GENERATOR STOP". PILLA #ST120FN4SL OR APPROVED EQUAL.
5. PROVIDE LOW FREQUENCY SINGLE STATION SMOKE DETECTOR AT THIS LOCATION.
6. PROVIDE CONNECTION TO PROJECTOR AT CEILING.
7. COORDINATE RECEPTACLE LOCATIONS TO USE WITH CHARGER RACKS.
8. PROVIDE CONNECTION TO EWH-1.
9. FROM J-BOX, PROVIDE 120V CONNECTION TO HOOD LIGHTS AND EXHAUST FAN, COORDINATE
EXACT REQUIREMENTS WITH HOOD SUPPLIER PRIOR TO ROUGH-IN.
10. TIE HOOD FIRE ALARM SUPPRESSION SYSTEM TO FIRE ALARM AS REQUIRED, COORDINATE
EXACT REQUIREMENTS WITH HOOD SUPPLIER PRIOR TO ROUGH-IN.
11. PROVIDE CONNECTION TO DISHWASHER.
12. PROVIDE POP-UP USB TYPE RECEPTACLE IN COUNTERTOP.
13. PROVIDE CONNECTION TO HOT WATER RECIRC PUMP. SEE PLUMBING DRAWINGS FOR EXACT
LOCATION.
14. SEE T101 FOR DATA OUTLET LOCATIONS AND PURVIS NOTIFICATION SYSTEM REQUIREMENTS.
DATA OUTLETS ARE SHOWN ON THIS DRAWING FOR REFERENCE ONLY FOR GENERAL TV AND
WORKSTATION LOCATIONS IN RELATION TO THE 120V RECEPTACLES THEY ARE NEXT TO. (DO NOT
DOUBLE COUNT LOCATIONS).
15. PROVIDE USB TYPE RECEPTACLES IN BUNK ROOMS, TYP.
16. TIE TO OPEN/CLOSE/STOP SWITCH PROVIDED WITH DOOR OPENER. PROVIDE WITH
CONTACTORS AND CONNECT AS REQUIRED TO DISCONNECT HVAC EQUIPMENT. COORDINATE
EXACT REQUIREMENTS WITH DOOR SUPPLIER AND HVAC CONTRACTOR PRIOR TO ROUGH-IN.
17. PROVIDE A 4X4X 2 1/8 J-BOX FOR ANTENNA ABOVE CEILING.
18. PROVIDE 1"C WITH RG58 COAXIAL CABLES TO ANTENNA, COORDINATE ANTENNA LOCATION
AND QUANTITY OF CABLES WITH OWNER.
19. PURVIS SYSTEM COMPUTER STATION SHALL BE INSTALLED ON TOP OF COUNTER WORK,
VERIFY EXACT LOCATION WITH OWNER AND PURVIS DRAWINGS BEFORE ROUGH-IN.
20. PROVIDE 6X6X4 J-BOX WITH 1"C. AND 4 PAIRS OF #18 AWG TWISTED PAIR, PLENUM RATED
(CMP) STRANDED CABLES, TERMINATE ON THE BACKBOARD IN COMM. ROOM.
21. TIMER FOR PURVIS FSAS. REFER TO PURVIS DRAWINGS.
22. OUTDOOR SPEAKER SHALL BE BOGEN #SPT 15A OR APPROVED EQUAL MOUNTED AT 15'-0" TO
CENTER AFG ON SMOOTH WALL. REFER TO PURVIS DRAWINGS.
23. PROVIDE VOLUME CONTROL FOR SPEAKER. COORDINATE MOUNTING HEIGHT AT 42" AFF.
REFER TO PURVIS DRAWINGS.
24. FLOOR BOX WITH (2) DUPLEX AND (2) CAT6 JACKS.
25. COMMUNICATIONS RACK PROVIDED AND INSTALLED BY E.C.
26. OUTDOOR SPEAKER SHALL BE BOGEN #SPT 15A OR APPROVED EQUAL MOUNTED AT 9'-0" TO
CENTER AFF ON SMOOTH WALL.
27. GENERATOR ANNUNCIATOR.
28. FIRE ALARM SYSTEM ANNUNCIATOR.
29. PROVIDE CONNECTION TO FLUSH VALVES (TYP.) PER MANUACTURER'S INSTALLATION
INSTRUCTIONS. REFER TO PLUMBING PLANS.
30. PROVIDE CONNECTION TO EF-WELL FAN AND LINE VOLTAGE THERMOSTAT. SEE MECHANICAL
DRAWINGS.
31. POWER/DATA FLOORBOX WITH RECEPTACLE AND (2) CAT6 CONNECTIONS.
32. POWER/DATA FOR TV'S SHALL BE AT 72" AFF. COORDINATE WITH OWNER'S TV MOUNTING
BRACKET. CONCEAL ALL DEVICES BEHIND TV.
33. POWER FOR 5HP VEHICLE EXHAUST SYSTEM. COORDINATE WITH MANUFACTURER
INSTALLATION INSTRUCTIONS AND PROVIDE BREAKER AND CIRCUIT.
34. DOOR SIGNAL LIGHT CONTROL/POWER SUPPLY J-BOX LOCATION @ 20" FROM TOP OF DOOR
AND 8" OUTSIDE OPENING (CONFIRM WITH OWNER BEFORE ROUGH-IN.) SEE ARCHITECTURAL
DRAWINGS FOR INTERIOR AND EXTERIOR WARNING LIGHT LOCATIONS. PROVIDE ALL
CONNECTIONS TO SYSTEM PER MANUFACTURER INSTALLATION INSTRUCTIONS FOR A FULL AND
COMPLETE WARNING LIGHT SYSTEM. TERMINATE CONDUIT ABOVE CEILING. TYPICAL FOR ALL OH
APP BAY DOORS, J-BOXES INSIDE AT FRONT AND OUTSIDE AT BACK.
35. SEE PURVIS DRAWINGS FOR GAS SHUTOFF CONNECTION TO PURVIS SYSTEM.
36. PROVIDE CONNECTION TO RECIRC. PUMP.
37. PROVIDE CONNECTION TO TRAP PRIMER.
38. PROVIDE CONNECTION TO MOTORIZED SCREEN AND CONTROLS PER MANUFACTURER'S
INSTALLATION INSTRUCTIONS. COORDINATE SWITCH LOCATION WITH OWNER BEFORE ROUGH-IN.
39. PROVIDE CONNECTION TO CONDENSATE PUMP.
40. PROVIDE CONNECTION TO IRRIGATION CONTROLLER.
41. PROVIDE CONNECTION TO EXTENSION CORD REEL AT CEILING. PROVIDE LEGRAND 1200
SERIES WITH BALL STOP, 35' OF CORD, SINGLE OUTLET, 20A.
42. ELECTRICAL IN APP BAY SHALL BE RECESSED. COORDINATE ANY ITEMS REQUIRED TO BE
SURFACE MOUNTED WITH ARCHITECT BEFORE ROUGH-IN.
43. PROVIDE CONNECTION TO EXTRACTOR PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
44. PROVIDE CONNECTION TO SCBA PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
COORDINATE EXACT LOCATION WITH OWNER BEFORE ROUGH-IN.
45. THIS SPACE SHALL HAVE THE TOP OUTLET OF EACH RECEPTACLE SWITCHED AND THE
BOTTOM OUTLET UNSWITCHED. PROVIDE LABELS AT EACH OUTLET THAT READ SWITCHED AND
UNSWITCHED. RECEPTACLES SHALL BE SWITCHED BY ROOM OCCUPANCY SENSOR AND SHALL
TURN OFF AFTER 20 MINUTES WITHOUT OCCUPANT DETECTION.
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 Permit Rev 1
2 12/01/2023 Permit Rev 2
5 07/19/2024 VE Rev 1
6 09/05/2025 90% IRC REVIEW
7 01/02/2026 90% V2 IRC REV
1/8" = 1'-0"
ROOF POWER PLAN
S
P
P
P
P
P
P
P
P
P
P
S
H
H
S
H
M
L
L
L
L
H
M M
M M
M M M
M M
M
L
M
H
H
L
L
S
H
H
H
H
H
H
H
L
H
H H
H
S
H
H H
H
H
H
M M
FACP
CO
CO
CO
CO
110 110
CO
CO CO
CO CO
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
S
LF
REMOVED
TOWER
MEETING
WATCH
LOBBY
CORR
CLOSET
MEN
WOMEN
UTIL
DECON
PPE STOR
CORR
OFFICE
QUIET RM
DAY ROOM
ELEC
KITCHEN
DINING
SHOWER RM
IT
MEDICAL
CORR
SHOWER RM
WOMEN
FITNESS
APP BAY
LAUNDRY
LOCKERS
UTIL
UTIL
VESTIBULE
CORR
CAPT SUITE
CAPT RR
CAPT OFF
CORR
BUNK1
BUNK2
BUNK3
BUNK4
BUNK5
BUNK6
BUNK7
LOCKER
LOCKER
134 LOCKER
LOCKER
BUNK8
BUNK9
BUNK10
BUNK11
W/C
BUNK 12
STOR
MAINT
LOCKER
LOCKER
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
FIRE ALARM
PLAN
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
E103
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1/8" = 1'-0"
FIRE ALARM PLAN
NOTES:
1. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND REQUIREMENTS OF ALL HVAC
EQUIPMENT. IF CONDENSATE PUMP(S) ARE REQUIRED, TIE TO NEAREST 120V OUTLET.
2. FIELD VERIFY LOCATION/QUANTITY OF ALL FIRE ALARM DEVICES AND PROVIDE AS REQUIRED
PER FIRE PROTECTION DRAWINGS. SEE FIRE ALARM RISER FOR ADDITIONAL REQUIREMENTS.
3. DEVICE COLOR SHALL BE COORDINATED WITH ARCHITECT BEFORE ORDERING.
ADDED SINGLE STATION SMOKE
DETECTORS WITH LOW
FREQUENCY SOUNDER BASES
INSIDE AND OUTSIDE OF ALL
SLEEPING ROOMS
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 Permit Rev 1
4 01/23/2024 Permit Rev 3
IN ADHESIVE
NO. AUBU12I, ALUMINUM
ALUMINUM AIR TERMINAL
NO. 1224ALAT, 1/2" X 24"
GENTLY TAPERED SOLID
UNIVERSAL BASE SET
L
H25 0
LIGHTNING CONDUCTOR (24
STRANDS OF 14 AWG WIRES -
98 LBS. PER 1000')
NO. A24, CLASS I ALUMINUM
NO. A262, ALUM. ADHESIVE
EVERY 3' MAX.
CABLE FASTENER
1" PVC PIPE BY OTHERS
10'-0" MIN.
NO. A24, CLASS I ALUMINUM
98 LBS. PER 1000')
STRANDS OF 14 AWG WIRES -
LIGHTNING CONDUCTOR (24
NO. BMTRC1, BIMETAL THRU-ROOF
CONNECTOR ASSEMBLY
WITH UWM115 WELD METAL
VU-29B ULTRAWELD MOLD
WITH UWM90 WELD METAL
VA-29B ULTRAWELD MOLD
WITH UWM115 WELD METAL
GD-5829B ULTRAWELD MOLD
WITH UWM150 WELD METAL
G0-5829B ULTRAWELD MOLD
NO. 5810, 5/8" X 10'
COPPER CLAD GROUND ROD
NO. 29, CLASS I COPPER
LIGHTNING CONDUCTOR (29
STRANDS OF 16 AWG WIRES -
215 LBS. PER 1000')
NO. 29, CLASS I COPPER
LIGHTNING CONDUCTOR (29
STRANDS OF 16 AWG WIRES -
215 LBS. PER 1000')
AIR TERMINAL DETAIL 'A'
NTS
THRU ROOF DETAIL 'T'
NTS
GROUND ROD DETAIL 'G'
NTS
A
A
A
A
AA
A
A
A
A A
A
A A
A
A A
AAA
A
TWO NO. 5810 5/8"X10'
COPPER CLAD GROUND
RODS WITH ULTRAWELD
CONNECTIONS SPACED
10' APART. SEE DETAIL 'G'
(TYPICAL)
REMOVED
TOWER
E1112 E111 3
E111
E1115
E111
E111 7
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
LIGHTNING
PROTECTION
SYSTEM
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
E104
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
1/8" = 1'-0"
ROOF PLAN LIGHTNING PROTECTION
LIGHTNING PLAN NOTES
1. CONTRACTOR TO PROVIDE SEPARATE
PRICE FOR ALL WORK INDICATED ON THE SHEET,
TITLE "ALTERNATE LIGHTNING PROTECTION
SYSTEM" FOR OWNERS REVIEW/APPROVAL.
2. THE COMPLETED INSTALLATION SHALL
MEET THE "INSTALLATION REQUIREMENTS FOR
LIGHTNING PROTECTION SYSTEMS, UL96A" OF
UNDERWRITERS LABORATORIES - 2001 EDITION.
THE UL MASTER LABEL SHALL BE FURNISHED TO
THE OWNER UPON COMPLETION.
3. ALUMINUM LIGHTNING PROTECTION
SYSTEM COMPONENTS SHALL NOT BE MOUNTED
TO COPPER SURFACES. COPPER COMPONENTS
SHALL BE USED TO AVOID ELECTROLYTIC
CORROSION.
4. METAL BODIES WITHIN 6' - 0" OF THE
LIGHTNING PROTECTION SYSTEM SHALL BE
BONDED TO THE SYSTEM IN ACCORDANCE WITH
UL96A - 1995 REQUIREMENTS.
5. UNDERGROUND METALLIC PIPING
ENTERING THE BUILDING SHALL BE BONDED TO
THE NEAREST DOWN CONDUCTOR OR GROUND
ELECTRODE.
6. ADHESIVE USED WITH ADHESIVE AIR
TERMINAL BASES AND CONDUCTOR FASTENERS
SHALL BE COMPATIBLE WITH ROOFING
MEMBRANE - VERIFY WITH ROOFING
CONTRACTOR.
7. AIR TERMINALS HAVE BEEN LOCATED ON
THE ROOF TOP EQUIPMENT AS REQUIRED. IF THE
METAL THICKNESS OF AN OBJECT IS 3/16" OR
GREATER, AIR TERMINALS MAY BE ELIMINATED IF
THE OBJECT IS PROPERLY CONNECTED TO THE
SYSTEM.
8. ROOF TOP EQUIPMENT NOT SHOWN ON
THIS DRAWING SHALL BE PROTECTED AS
REQUIRED TO MEET THE REQUIREMENTS LISTED
ABOVE INCLUDING THE INSTALLATION OF AIR
TERMINALS AND OR BONDING. IF THE METAL
THICKNESS OF AN OBJECT IS 3/16" OR GREATER,
AIR TERMINALS MAY BE ELIMINATED IF THE
OBJECT IS PROPERLY CONNECTED TO THE
SYSTEM.
9. AIR TERMINALS ARE TO BE LOCATED AS
SHOWN. THEY ARE TO BE A MAXIMUM OF 24" FROM
THE ROOF EDGE AND PROJECT A MINIMUM OF 10"
ABOVE THE PROTECTED EDGE. THE SPACING
BETWEEN AIR TERMINALS ARE NOT TO EXCEED 20
FEET. AIR TERMINALS THAT EXTEND 24" ABOVE
THE PROTECTED EDGE ARE NOT TO EXCEED A
SPACING GREATER THAN 25', EXCEPT FOR MID-
ROOF AIR TERMINALS (50' MAX SPACING).
10. ALL LIGHTNING CONDUCTORS ARE TO
MAINTAIN A HORIZONTAL OR DOWNWARD PATH.
ALL BENDS IN THE CONDUCTOR SHALL HAVE A
RADIUS BEND OF 8 INCHES OR GREATER, AND
SHALL HAVE AN ANGLE BEND OF 90 DEGREES OR
GREATER.
11. EACH INDIVIDUAL ITEM OF THE LIGHTNING
PROTECTION SYSTEM IS NOT LABELED FOR THE
SAKE OF CLARITY. ITEMS ARE INDICATED AT
RANDOM LOCATIONS ONLY, BUT A COMPLETE
SYSTEM SHALL BE PROVIDED TO MEET MASTER
LABEL REQUIREMENTS.
12. ROOF PADS, PAVERS, FLASHINGS OR ANY
OTHER SPECIAL ROOFING MATERIALS REQUIRED
FOR THE INSTALLATION OF THE LIGHTNING
PROTECTION SYSTEM SHALL BE FURNISHED AND
INSTALLED BY THE ROOFING CONTRACTOR.
13. SUBMIT SHOP DRAWINGS, CATALOG
SHEETS, OR OTHER DESCRIPTIVE DATA WITH
SUFFICIENT INFORMATION TO ESTABLISH DESIGN,
QUALITY AND PERFORMANCE. MANUFACTURER
CATALOG SHEETS SUBMITTED WITHOUT SPECIFIC
MODEL NUMBERS INDICATED WILL BE REJECTED.
DATA SHALL DESCRIBE APPARATUS, EQUIPMENT,
PANELS.
14. LIGHTNING PROTECTION SYSTEMS SHALL
BE ROOF AIR TERMINALS AND GROUNDING
SYSTEM DESIGNED AND INSTALLED IN
ACCORDANCE WITH NFPA 780 AND CERTIFIED TO
UL 96A STANDARDS. THE ENTIRE SYSTEM SHALL
BE DESIGNED AND INSTALLED BY CERTIFIED
LIGHTNING PROTECTION CONTRACTOR. THE
SYSTEM SHALL INCLUDE PROTECTION FOR ALL
ROOF EQUIPMENT, APPURTENANCES AND
BONDING TO THE ELECTRICAL SYSTEM PER UL
REQUIREMENTS. ALL AIR TERMINALS AND ROOF
CONDUCTORS SHALL BE ALUMINUM. ALL GROUND
CONDUCTORS AND GROUND RODS SHALL BE
COPPER. ROOF TOP HVAC EQUIPMENT AND
ENCLOSURES SHALL NOT BE USED AS
CONDUCTORS. ALL AIR TERMINALS INSTALLED ON
ROOF TOP HVAC EQUIPMENT SHALL BE
CONNECTED WITH CONDUCTORS TO THE MAIN
LIGHTNING CONDUCTORS. CONTRACTOR SHALL
PROVIDE DETAILED DESIGN SHOP DRAWINGS FOR
THE COMPLETE SYSTEM TO INDICATE THE
LOCATION OF AIR TERMINALS, ROOF
CONDUCTORS, DOWN CONDUCTORS, GROUND
RODS AND COMPLETE INSTALLATION DETAILS.
COMPLETED SYSTEM SHALL BEAR UL MASTER
LABEL WITH ALL REQUIRED CERTIFICATION AND
DOCUMENTATION. PROVIDE WITH UL LIGHTNING
PROTECTION INSPECTION CERTIFICATE CERTIFIED
TO UL96A STANDARDS.
15. EXTERIOR EXPOSED DOWN CONDUCTORS
ARE NOT ALLOWED.
16. PROVIDE LIGHTNING PROTECTION FOR THE
GENERATOR (NOT SHOWN) AND RF ANTENNA(S),
CONNECT THE LIGHTNING PROTECTION SYSTEM
TO THE GROUND COUNTERPOISE USING A
COPPER BONDING JUMPER.
17. THE LIGHTNING PROTECTION SYSTEM
SHALL NOT VOID THE ROOF WARRANTY.
NTS
LIGHTNING PROTECTION DETAILS
REVISIONS
MDP
1000A
208/120V
3 PHASE
MLO
NOTES:
1. PROVIDE (1000A) 3 SETS: 4-#400 (NO GROUND) IN 4"C. TO TRANSFORMER PER UTILITY DIRECTION.
2. PRIOR TO START OF ANY WORK OBTAIN WRITTEN APPROVAL FOR LOCATION OF POLE/TRANSFORMERS & CONNECTION POINT PER ELECTRIC UTILITY CO DIRECTION. CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND COMPLYING WITH MOST CURRENT UTILITY RULES AND REGULATIONS. PROVIDE SERVICE ENTRANCE CONDUITS W/36" RADIUS ELLS AT POLE & SERVICE CONNECTION POINT. PROVIDE CONDUITS WITH PULLWIRES AND MAINTAIN 42" MINIMUM DEPTH, LOCATION OF POLE/TRANSFORMERS AND SECONDARY CONDUIT/FEEDER(S) ARE CONTINGENT UPON ELECTRICAL UTILITY CO APPROVAL. PROVIDE GROUND RODS PER ELECTRICAL UTILITY CO REQUIREMENTS. COORDINATE CONDUIT UNDER ROAD INSTALLATION WITH COUNTY AND OBTAIN ALL PERMISSIONS
AND PERMITS.
3. 1"C. TO PHOTOCELL ON ROOF.
4. METER CAN PER UTILITY REQUIREMENTS.
5. 275 KW, 343.8KVA 208/120/3P STANDBY GENERATOR WITH 4 DAY (500 GALLON) DIESEL BASE TANK. ASSEMBLY RATED FOR 160 MPH WIND ZONE. PROVIDE WITH SOUND ATTENTUATING WEATHERPROOF ENCLOSURE.
6. 1000A 208/120/3P/4W AUTOMATIC TRANSFER SWITCH WITH FULLY RATED 1000A MAIN BREAKER, 42,000 AIC, SERVICE ENTRANCE RATED.
7. PROVIDE 3 SETS 4 #400, #2/0 G, 3"C.
8. #2/0 GROUND PER NEC.
9. FIRE PUMP SERVICE: PROVIDE 4-#1/0 IN 1-1/2"C.
10. #1 FIRE PUMP CONTROLLER GROUND.
11. 25 HP FIRE PUMP - PROVIDE CONNECTION TO CONTROLLER PER MANUFACTURER'S INSTALLATION
INSTRUCTIONS.
12. 4-#1/0, #1G-2"C.
13. GENERATOR DURING FIRE EVENT MODE: WHEN BUILDING IS ON GENERATOR POWER AND THE FIRE SPRINKLER SYSTEM IS ACTIVATED, BUILDING ATS SHALL DEACTIVATE AND FIRE PUMP ATS WILL ACTIVATE PROVIDING THE
FIRE PUMP ONLY WITH GENERATOR POWER.
14. 1" PVC CONDUIT STUBBED UP IN MAIN ELECTRICAL ROOM AND FIRE PUMP HOUSE FOR CONTROL WIRING.
ATS
1000A
208/120V
3 PHASE
STANDBY
GENERATOR
208/120V/3P
M
L 100A
208/120V
3 PHASE
MLO
SPD
T/S
L/C
PHOTOCELL ON ROOF
FACING NORTH
M 400A
208/120V
3 PHASE
MLO
P 225A
208/120V
3 PHASE
MLO
UTILITY
TRANSFORMER
208/120V/3P
CT
CABINET
COUNTY ROAD 226
P2 225A
208/120V
3 PHASE
MLO
FIRE PUMP HOUSE
25 HP
FIRE PUMP
208/120V/3P
4 M
CT'S
FIRE STATION
PW
100A
208/120V
3 PHASE
MB
ATS
600A
208/120V
3 PHASE
CAMLOCK
BOX
CAMLOCK
BOX
P3 225A
208/120V
3 PHASE
MLO
FIRE PUMP OVERCURRENT PROTECTION SIZED
TO CARRY INDEFINITELY SUM OF LOCKED ROTOR
CURRENT AND ACCESSORY EQUIPMENT PER 695.6(D).
LRC (25HP)= 404A = 600A BREAKER
FIRE PUMP FEEDER SIZED FOR NOT LESS THAN 125%
OF FIRE PUMP FULL LOAD CURRENT PER 430.248 OR
430.250.
RLC (25HP) = 74.8A X 1.25 = 93.5A #1/0 AMPACITY =150A
FIRE PUMP FEEDER VOLTAGE DROP: NOT MORE THAN
15% BELOW THE CONTROLLER'S RATED VOLTAGE
Vd = [2(130)(0.122)404] / 1000 = 12.8% W/ 1/0 COPPER
NOT MORE THAN 5% BELOW THE VOLTAGE RATING OF
MOTOR WHEN MOTOR OPERATES AT 115% OF FIRE
PUMP FULL-LOAD CURRENT RATING PER 695.7.
Vd = [2(130)(0.245)131.1] / 1000 = 3.3% W/ 1/0 COPPER
130'
G
GROUNDING DETAIL NOTES :
1. EQUIPMENT GROUNDING CONDUCTOR (GND) -REFER TO POWER RISER FOR WIRE SIZE.
2. ALL SERVICE GROUNDING CONNECTIONS SHALL BE DONE WITH EXOTHERMIC WELDS.
3. AFTER GROUNDING SYSTEM IS INSTALLED, GROUND RESISTANCE SHALL BE MEASURED, TO ASSURE THAT GROUND
VALUE OF 10 OHM MAXIMUM RESISTANCE IS ACHIEVED. IF NOT, ADDITIONAL GROUNDING SHALL BE PROVIDED TO
MEET SPECIFIC VALUE.
4. GROUNDING ELECTRODE CONDUCTOR (NEUTRAL) - REFER TO POWER RISER FOR WIRE SIZE.
5. MAIN BONDING JUMPER SIZE PER NEC 250-66.
6. #3/0 AWG GROUNDING ELECTRODE CONDUCTOR.
7. GROUNDING ELECTRODE CONDUCTOR PER NEC TABLE 250.66
GROUNDING ELECTRODE
3/4" x 10FT
CU CLAD GROUND
RODS (TYPICAL)
EXOTHERMIC
WELD (TYP)
20FT MIN
1000A MB
EQUIPMENT GROUNDING BUS
(NEUTRAL) BUS
METALLIC
UNDERGROUND
WATER PIPE
MIN 20FT #1/0 BARE CU
ENCASED IN BLDG
MIN 2"THICK FOOTING
IN DIRECT
CONTACT WITH EARTH
SLAB/GRADE
B L D
G S
T E
E L
#6 AWG
GROUNDING
BUSBAR(S)
SEE DETAIL
MSB
N G
PROVIDE GROUND ROD AT
EACH CORNER OF ATS.
(4) TOTAL.
S E
E S
T R
U C
T U
R A
L D
E T
A
IL
S
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
POWER RISER &
PANEL
SCHEDULES
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
E105
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
NTS
POWER RISER DIAGRAM
Notes:
Receptacle 39000 VA 62.82% 24500 VA
Power 204376 VA 100.00% 204376 VA
Other 58099 VA 100.00% 58099 VA
Lighting - Exterior 980 VA 125.00% 1225 VA Total Est. Demand Current: 850 A
Lighting - Dwelling Unit 192 VA 100.00% 192 VA Total Conn. Current: 895 A
Lighting 6944 VA 100.00% 6944 VA Total Est. Demand: 306402 VA
Electric Range - 3.5 kW to 8.75 kW 8000 VA 80.00% 6400 VA Total Conn. Load: 322268 VA
Electric Clothes Dryer 5000 VA 100.00% 5000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
H/N/G - Hot Wire, Neutral Wire, Ground Wire
Legend:
Total Amps: 895 A
Total Conn. Load: 322268 VA
11 PANEL P2 3 225 A 225 A 3-#300, 1-#300, 1-#4 59290 VA
10 PANEL PW 3 100 A 100 A 3-#3/0, 1-#3/0, 1-#6 27941 VA
9 AIR COMP 10HP 3 100 A 70 A 3-#4, 1-#4, 1-#8 11000 VA
8 Power DECON 160 3 100 A 40 A 3-#8, 1-#8, 1-#10 10000 VA
7 CU-6 2 100 A 50 A 2-#6, 1-#6, 1-#10 5600 VA
6 CU-3 2 100 A 60 A 2-#4, 1-#4, 1-#10 5800 VA
5 WH-1 3 225 A 125 A 3-#1/0, 1-#1/0, 1-#6 30000 VA
4 RTU-OA 3 100 A 70 A 3-#4, 1-#4, 1-#8 19599 VA
3 PANEL L 3 225 A 225 A 3-#300, 1-#300, 1-#4 9622 VA
2 PANEL P 3 225 A 225 A 3-#300, 1-#300, 1-#4 44780 VA
1 PANEL M 3 400 A 400 A 3-#750, 1-#750, 1-#3 98900 VA
CKT Circuit Description # of Poles Frame Size Trip Rating Wire Size H/N/G Load Remarks
Notes:
Enclosure: NEMA 1 MCB Rating: 1 A
Mounting: SURF Wires: 4 Mains Rating: 1000 A
Supply From: Phases: 3 Mains Type:
Location: ELEC 113 Volts: 120/208 Wye A.I.C. Rating: 42,000
MDP:
N.T.S.
SYSTEM GROUNDING DETAIL1
Notes:
Receptacle 26280 VA 69.03% 18140 VA Total Est. Demand Current: 97 A
Power 1900 VA 100.00% 1900 VA Total Conn. Current: 124 A
Other 3600 VA 100.00% 3600 VA Total Est. Demand: 35040 VA
Electric Range - 3.5 kW to 8.75 kW 8000 VA 80.00% 6400 VA Total Conn. Load: 44780 VA
Electric Clothes Dryer 5000 VA 100.00% 5000 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 116 A 154 A 106 A
Total Load: 13740 VA 18300 VA 12740 VA
41 0 VA 42
Electric Range - 3.5 kW to 8.75 kW 20 A 2
8000... 1200... 1 20 A Power MEETING 102 40
37 2280... 1 20 A Receptacle WATCH 108 38
35 Receptacle WATCH 108 20 A 1 360 VA 720 VA 1 20 A Receptacle WATCH 108 36
33 Receptacle CORR 104 20 A 1 600 VA 360 VA 1 20 A Receptacle CLOSET 103 34
31 Other 20 A 1 1080... 1080... 1 20 A Other 32
29 Receptacle 20 A 1 900 VA 900 VA 1 20 A Receptacle 30
27 Receptacle Room 101, 104, 105, 106 20 A 1 1180... 540 VA 1 20 A Receptacle Space 48 28
25 Space 48 20 A 1 1260... 720 VA 1 20 A Receptacle Room 110, 48 26
23 Receptacle Room 111, 112 20 A 1 1080... 540 VA 1 20 A Receptacle SCBA 157 24
21 Other Space 47 20 A 1 360 VA 1200... 1 20 A Receptacle CORR 119 22
19 Receptacle Space 47 20 A 1 1200... 180 VA 1 20 A Receptacle Space 47 20
17 RANGE HOOD 20 A 1 180 VA 720 VA 1 20 A Receptacle Space 47 18
15 Receptacle Space 47 20 A 1 1200... 180 VA 1 20 A Receptacle LOBBY 101 16
13 0 VA 1200... 1 20 A Receptacle Space 47 14
Electric Clothes Dryer LAUNDRY 122 40 A 2
5000... 1080... 1 20 A Space 46 12
9 Receptacle Room 126, 119 20 A 1 900 VA 1500... 1 20 A Receptacle LAUNDRY 122 10
7 Receptacle FITNESS 154 20 A 1 720 VA 1450... 1 20 A Receptacle CHIEF SUITE 128 8
5 Receptacle CORR 130 20 A 1 900 VA 360 VA 1 20 A Other FITNESS 154 6
3 Receptacle 20 A 1 180 VA 900 VA 1 20 A Receptacle CORR 130 4
1 Receptacle STOR 153 20 A 1 1260... 1310... 1 20 A Receptacle BUNK 12 150 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 1 A
Mounting: Recessed Wires: 4 Mains Rating: 225 A
Supply From: 48"x26.25", 120 V/208 V, Three... Phases: 3 Mains Type:
Location: Space 48 Volts: 120/208 Wye A.I.C. Rating: 22,000
Branch Panel: P
PANEL SCHEDULE NOTES:
1. PROVIDE ARC FLASH LABEL ON ALL PANELBOARDS. ALL BRANCH CIRCUIT CONDUCTORS SHALL
BE SIZED FOR LESS THAN 3% VOLTAGE DROP AT DESIGN LOAD. SEE ARC FLASH WARNING AND
BRANCH CIRCUIT CONDUCTOR DETAILS.
2. ATS MAIN BREAKER SHALL BE 100% RATED.
3. FROM SPD TO SPD DEVICE - KEEP CONDUCTOR LENGTHS TO A MINIMUM.
4. WIRE/BREAKER SIZES ARE FOR REFERENCE ONLY. PRIOR TO ROUGH-IN, FIELD VERIFY EXACT
EQUIPMENT SELECTION AND PROVIDE WIRE AND BREAKER SIZE & TYPE TO MATCH MECHANICAL
EQUIPMENT REQUIREMENTS.
5. CONNECT VIA LIGHTING CONTROL PANEL.
6. PROVIDE GFI TYPE BREAKER.
10. ALL CIRCUIT BREAKERS SERVING DRINKING WATER FOUNTAINS SHALL BE GFI TYPE (NEC 422.52).
11. ALL DIRECT CONNECTED APPLIANCES RATED OVER 0.3 KVA OR 1/8HP SHALL BE PROVIDED WITH
LOCK-OUT TYPE CIRCUIT BREAKER.
12. SHUNT TRIP TYPE CIRCUIT BREAKER & INTERLOCK WITH KITCHEN HOOD CONTROLS AS REQUIRED
BY APPLICABLE CODES.
13. PROVIDE ARC-FAULT TYPE (AFI) CIRCUIT BREAKERS FOR ALL BEDROOM RECEPTACLES AND
LIGHTING OUTLETS.
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 Permit Rev 1
2 12/01/2023 Permit Rev 2
TYPICAL ARC FLASH LABEL DETAIL
NOT TO SCALE
WARNING
Arc Flash & Shock Hazard
Appropriate PPE Required
Flash Hazard Category
Min. Arc Rating
Flash Protection Boundary
Min. Arc Rating
Restricted Approach Boundary
Prohibited Approach Boundary
Cotton underwear
T-shirt
Long sleeve shirt
Long pants
FR Shirt
FR Pants
FR overall
Flash Suit
Flash Hood
Hard hat
Face shield
Ear Protection
Safety Glasses
Safety Goggles
Hard hat
Face shield
Ear Protection
Safety Glasses
Safety Goggles
FLASH PIPE SHOCK PPE
Class
V-rating
VAC Shock Hazard When
Equipment ID:
NOTES:
1. PROVIDE ELECTRICAL GEAR SUBMITTAL PACKAGE WITH ARCH FLASH CALCULATIONS FOR
ALL EQUIPMENT. EACH ITEM TO BEAR THE WARNING LABEL (AS SHOWN ABOVE) WITH ALL
APPROPRIATE INFORMATION INDICATED AS A RESULT OF THE ARC FLASH CALCULATION.
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
PANEL
SCHEDULES
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
E106
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
Notes:
Power 1626 VA 100.00% 1626 VA Total Est. Demand Current: 27 A
Other 0 VA 0.00% 0 VA Total Conn. Current: 27 A
Lighting - Exterior 980 VA 125.00% 1225 VA Total Est. Demand: 9867 VA
Lighting - Dwelling Unit 128 VA 100.00% 128 VA Total Conn. Load: 9622 VA
Lighting 6944 VA 100.00% 6944 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 28 A 36 A 19 A
Total Load: 3226 VA 4151 VA 2245 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 Flagpole 20 A 1 100 VA 171 VA 18
15 171 VA
2 20 A Lights - Site Poles
13 171 VA 171 VA 14
Lights - Site Poles 20 A 2
171 VA 171 VA
2 20 A Lights - Site Poles
9 Lighting - Exterior 20 A 1 616 VA 500 VA 1 20 A Lights 10
7 Lights 20 A 1 48 VA 533 VA 1 20 A Lighting - Exterior 8
5 Lighting Space 48 20 A 1 888 VA 767 VA 1 20 A Lighting - Dwelling Unit 6
3 Lighting CORR 130 20 A 1 1500... 1388... 1 20 A Lighting ELEC 113 4
1 Lighting 20 A 1 1409... 907 VA 1 20 A Lighting 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 1 A
Mounting: Surface Wires: 4 Mains Rating: 100 A
Supply From: 48"x26.25", 120 V/208 V, Three... Phases: 3 Mains Type:
Location: Space 48 Volts: 120/208 Wye A.I.C. Rating: 22,000
Branch Panel: L
Notes:
Total Est. Demand Current: 161 A
Total Conn. Current: 165 A
Total Est. Demand: 58020 VA
Receptacle 12540 VA 89.87% 11270 VA Total Conn. Load: 59290 VA
Power 46750 VA 100.00% 46750 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 196 A 135 A 174 A
Total Load: 22860 VA 16160 VA 20270 VA
41 Receptacle 20 A 1 720 VA 1200... 1 20 A Receptacle WATCH 108 42
39 550 VA 1200... 1 20 A Power 40
Power LAUNDRY 122 20 A 2
550 VA 2000... 38
35 Receptacle APP BAY 161 20 A 1 180 VA 2000... 36
33 Receptacle DECON 160 20 A 1 180 VA 2000...
3 40 A VEHICLE EXHAUST SYS. 5HP
31 Power 20 A 1 1200... 500 VA 1 20 A Power 32
29 Power 20 A 1 460 VA 900 VA 1 20 A Receptacle Room 22, 157, 156 30
27 Disposal 20 A 1 1200... 900 VA 1 20 A Receptacle Room 110, 160 28
25 200 VA 1200... 1 20 A Receptacle - coffee 26
23 200 VA 360 VA 1 20 A Receptacle ROOF 24
ROLL UP DOOR 20 A 3
200 VA 180 VA 1 20 A Receptacle ROOF 22
19 200 VA 1200... 1 20 A Power 20
17 200 VA 1200... 1 20 A Power 18
ROLL UP DOOR 20 A 3
200 VA 1200... 1 20 A Power 16
13 200 VA 200 VA 14
11 200 VA 200 VA 12
ROLL UP DOOR 20 A 3
200 VA 200 VA
3 20 A ROLL UP DOOR
7 Power IT 114 20 A 1 500 VA 500 VA 1 20 A Power IT 114 8
5 Receptacle APP BAY 161 20 A 1 360 VA 180 VA 1 20 A Receptacle APP BAY 161 6
3 Receptacle APP BAY 161 20 A 1 900 VA 610 VA 1 20 A Receptacle SHOWER RM 123 4
1 Receptacle APP BAY 161 20 A 1 540 VA 540 VA 1 20 A Receptacle APP BAY 161 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 1 A
Mounting: Recessed Wires: 4 Mains Rating: 225 A
Supply From: 48"x26.25", 120 V/208 V, Three... Phases: 3 Mains Type:
Location: OFFICE 112 Volts: 120/208 Wye A.I.C. Rating: 22,000
Branch Panel: P2 PANEL SCHEDULE NOTES:
1. PROVIDE ARC FLASH LABEL ON ALL PANELBOARDS. ALL BRANCH CIRCUIT
CONDUCTORS SHALL
BE SIZED FOR LESS THAN 3% VOLTAGE DROP AT DESIGN LOAD. SEE ARC
FLASH WARNING AND
BRANCH CIRCUIT CONDUCTOR DETAILS.
2. MAIN BRAKER SHALL BE 100% RATED.
3. FROM SPD TO SPD DEVICE - KEEP CONDUCTOR LENGTHS TO A MINIMUM.
4. WIRE/BREAKER SIZES ARE FOR REFERENCE ONLY. PRIOR TO ROUGH-IN,
FIELD VERIFY EXACT EQUIPMENT SELECTION AND PROVIDE WIRE AND
BREAKER SIZE & TYPE TO MATCH MECHANICAL EQUIPMENT REQUIREMENTS.
5. CONNECT VIA LIGHTING CONTROL PANEL WITH PHOTOCELL/TIMESWITCH
CONTROL FOR EXTERIOR.
6. PROVIDE GFI TYPE BREAKER.
10. ALL CIRCUIT BREAKERS SERVING DRINKING WATER FOUNTAINS SHALL BE
GFI TYPE (NEC 422.52).
11. ALL DIRECT CONNECTED APPLIANCES RATED OVER 0.3 KVA OR 1/8HP
SHALL BE PROVIDED WITH LOCK-OUT TYPE CIRCUIT BREAKER.
12. SHUNT TRIP TYPE CIRCUIT BREAKER & INTERLOCK WITH KITCHEN HOOD
CONTROLS AS REQUIRED BY APPLICABLE CODES.
13. PROVIDE ARC-FAULT TYPE (AFI) CIRCUIT BREAKERS FOR ALL BEDROOM
RECEPTACLES AND LIGHTING OUTLETS PER CODE.
5 5
Notes:
Total Est. Demand Current: 78 A
Receptacle 180 VA 100.00% 180 VA Total Conn. Current: 78 A
Power 27700 VA 100.00% 27700 VA Total Est. Demand: 27941 VA
Other 0 VA 0.00% 0 VA Total Conn. Load: 27941 VA
Lighting - Dwelling Unit 64 VA 100.00% 64 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 86 A 84 A 67 A
Total Load: 10080 VA 9800 VA 8061 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 28
25 26
23 24
21 22
19 20
17 18
15 16
13 3000... 14
11 3000... 3000...
2 70 A Well, 5hp (basis of design, confirm)
Well. 5hp (basis of design, confirm) 70 A 2
3000... 3000... 10
7 2000... 3000...
2 70 A Well, 5hp (basis of design, confirm)
5 2000... 64 VA 1 20 A LIGHTS 6
JOCKEY PUMP, 5HP (basis of design, confirm) 40 A 3
2000... 1800... 4
1 recept, fan 20 A 1 280 VA 1800...
2 70 A FHP-WELL
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 100 A
Mounting: Recessed Wires: 4 Mains Rating: 100 A
Supply From: 48"x26.25", 120 V/208 V, Three... Phases: 3 Mains Type:
Location: Volts: 120/208 Wye A.I.C. Rating: 22,000
Branch Panel: PW
Notes:
Total Est. Demand Current: 275 A
Total Conn. Current: 275 A
Total Est. Demand: 98900 VA
Power 75400 VA 100.00% 75400 VA Total Conn. Load: 98900 VA
Other 23500 VA 100.00% 23500 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 241 A 308 A 287 A
Total Load: 28917 VA 36267 VA 33717 VA
41 2800... 2350... 42
CU-4 50 A 2
2800... 2350...
2 30 A CU-IT
37 EF-HOOD (1/3 HP) 15 A 1 300 VA 1200... 38
35 2600... 1200...
2 25 A CU-2
AHU-6 35 A 2
2600... 2100... 34
31 950 VA 2100...
2 40 A CU-1
CU-5/AHU-5 30 A 2
950 VA 2350... 30
27 2600... 2350...
2 30 A CU-FIT
AHU-3 35 A 2
2600... 2600... 26
23 2600... 2600...
2 35 A AHU-4
AHU-1 35 A 2
2600... 2600... 22
19 EF-1 (1/6 HP) 15 A 1 300 VA 2600...
2 35 A AHU-2
17 667 VA 667 VA 18
15 667 VA 667 VA 16
EF-2 (1.5HP) 15 A 3
667 VA 667 VA
3 15 A EF-3 (1.5HP)
11 3733... 3733... 12
9 3733... 3733... 10
UH-3 40 A 3
3733... 3733...
3 40 A UH-4
5 3733... 3733... 6
3 3733... 3733... 4
UH-1 40 A 3
3733... 3733...
3 40 A UH-2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 1 A
Mounting: Recessed Wires: 4 Mains Rating: 400 A
Supply From: 48"x26.25", 120 V/208 V, Three... Phases: 3 Mains Type:
Location: Space 48 Volts: 120/208 Wye A.I.C. Rating: 42,000
Branch Panel: M
REVISIONS
ENGINEERING
P H&
POWELL & HINKLE ENGINEERING, P.A.
1409 KINGSLEY AVENUE, BLDG 12A
ORANGE PARK, FLORIDA 32073
(904) 264-5570 FAX:(904) 278-2646
ROBERT L. HINKLE
GALTON C. MOK
LANE R. HINKLE
THOMAS M. ELDER
RICHARD A. MATHEWS
PE 29302
PE 33192
PE 48076
PE 56121
PE 59418
DAVID R. SPELL JR. PE 54729
JAMES L. HENNESSEY PE 83241
DATE:
PROJECT NO.:
THIS DRAWING IS AN INSTRUMENT OF SERVICE
AND IS THE PROPERTY OF DASHER HURST
ARCHITECTS, PA. IT SHALL NOT BE
REPRODUCED IN WHOLE OR IN PART WITHOUT
THE EXPRESS WRITTEN PERMISSION OF DASHER
HURST ARCHITECTS, PA.
DASHER HURST
1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8
A R C H I T E C T S
J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4
P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0
F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5
W. W. W. D A S H E R H U R S T . C O M
PANEL
SCHEDULES
22003
06.23.2023
C
O U
N T Y
R O
A D
G R
E E N
C O
V E S
P R
IN
G
S F L
E107
BID DOCUMENTS
C L A
Y C
O U
N
TY
C L A
Y C
O F
IR
E S
TA
TI
O N
STRUCTURAL ENGINEER
G.M. HILL ENGINEERING,
INC.
9700 PHILIPS HWY, SUITE 101
JACKSONVILLE, FL 32256
Notes:
Total Est. Demand Current: 88 A
Total Conn. Current: 88 A
Total Est. Demand: 31680 VA
Receptacle 2280 VA 100.00% 2280 VA Total Conn. Load: 31680 VA
Power 29400 VA 100.00% 29400 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 118 A 54 A 106 A
Total Load: 13330 VA 6440 VA 11910 VA
41 42
39 40
37 38
35 36
33 34
31 32
29 30
27 750 VA 28
FHP DECON 160 15 A 2
750 VA 1500... 26
23 1500... 1500...
2 20 A FHP MAINT 152
FHP STOR 153 20 A 2
1500... 600 VA 22
19 5500... 600 VA
2 20 A Power
Power APP BAY 161 90 A 2
5500... 650 VA 18
15 Receptacle APP BAY 161 20 A 1 180 VA 650 VA
2 20 A EXTRACTOR
13 REC - PARKING POLE 20 A 1 180 VA 0 VA 1 20 A PUMP POWER 14
11 REC - PARKING POLE 20 A 1 180 VA 180 VA 1 20 A REC - PARKING POLE 12
9 REC - PARKING POLE 20 A 1 180 VA 180 VA 1 20 A REC - PARKING POLE 10
7 CORD REEL 20 A 1 1200... 1200... 1 20 A CORD REEL 8
5 CORD REEL 20 A 1 1200... 1200... 1 20 A CORD REEL 6
3 CORD REEL 20 A 1 1200... 1200... 1 20 A Receptacle - Decon Dryer 4
1 CORD REEL 20 A 1 1200... 1200... 1 20 A CORD REEL 2
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: Type 1 MCB Rating: 1 A
Mounting: Recessed Wires: 4 Mains Rating: 225 A
Supply From: P2 Phases: 3 Mains Type:
Location: OFFICE 112 Volts: 120/208 Wye A.I.C. Rating: 22,000
Branch Panel: P3
ADDED SHEET.
PANEL SCHEDULE NOTES:
1. PROVIDE ARC FLASH LABEL ON ALL PANELBOARDS. ALL BRANCH CIRCUIT
CONDUCTORS SHALL
BE SIZED FOR LESS THAN 3% VOLTAGE DROP AT DESIGN LOAD. SEE ARC
FLASH WARNING AND
BRANCH CIRCUIT CONDUCTOR DETAILS.
2. MAIN BRAKER SHALL BE 100% RATED.
3. FROM SPD TO SPD DEVICE - KEEP CONDUCTOR LENGTHS TO A MINIMUM.
4. WIRE/BREAKER SIZES ARE FOR REFERENCE ONLY. PRIOR TO ROUGH-IN,
FIELD VERIFY EXACT EQUIPMENT SELECTION AND PROVIDE WIRE AND
BREAKER SIZE & TYPE TO MATCH MECHANICAL EQUIPMENT REQUIREMENTS.
5. CONNECT VIA LIGHTING CONTROL PANEL WITH PHOTOCELL/TIMESWITCH
CONTROL FOR EXTERIOR.
6. PROVIDE GFI TYPE BREAKER.
10. ALL CIRCUIT BREAKERS SERVING DRINKING WATER FOUNTAINS SHALL BE
GFI TYPE (NEC 422.52).
11. ALL DIRECT CONNECTED APPLIANCES RATED OVER 0.3 KVA OR 1/8HP
SHALL BE PROVIDED WITH LOCK-OUT TYPE CIRCUIT BREAKER.
12. SHUNT TRIP TYPE CIRCUIT BREAKER & INTERLOCK WITH KITCHEN HOOD
CONTROLS AS REQUIRED BY APPLICABLE CODES.
13. PROVIDE ARC-FAULT TYPE (AFI) CIRCUIT BREAKERS FOR ALL BEDROOM
RECEPTACLES AND LIGHTING OUTLETS PER CODE.
5 5
REVISIONS
# DATE DESCRIPTION
1 11/03/2023 Permit Rev 1
SPRINKLED BUILDING
MOUNTED
ABOVE FACP
(2) TELE LINES
TO SECURITY PNL
DEDICATED 120V CKT
ANNUNCIATOR
FIRE ALARM
CONTROL
PANEL
(FACP)
FA FIRE ALARM
FA- PULL STATION WALL MTD
FA- HORN/STROBE WALL MTD
FIRE ALARM A-0 CRITERIA:
(A) THE PLANS SHALL BE CLEAR, WITH A SYMBOLS LEGEND, SYSTEM RISER DIAGRAM
SHOWING ALL INITIATION AND NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS.
INDICATE LOCATIONS WHERE FIRE RATINGS ARE REQUIRED AS DETERMINED BY THE
SYSTEM'S SURVIVABILITY REQUIREMENTS. IDENTIFY THE GENERAL OCCUPANCY OF THE
PROTECTED PROPERTY, AND FOR EACH ROOM AND AREA UNLESS IT IS CLEAR FROM
FEATURES SHOWN.
- OCCUPANCY TYPE IS MIXED OCCUPANCY/STORAGE/RESIDENTIAL ASSEMBLY- FULLY SPRINKLERED
(B) LOCATE INITIATION AND NOTIFICATION DEVICES AND CONNECTIONS TO RELATED
SYSTEMS ON THE FLOOR PLANS AND SECTIONS WHEN NEEDED FOR CLARITY. RELATED
SYSTEMS INCLUDE ELEVATOR CONTROLS SMOKE CONTROL SYSTEMS, DAMPERS, AND
DOORS.
- NO…
This is the start of the file's text. The full file is on GovTribe.
File details come from the government source that posted it. Updated .