Clay_Co_FS24_Elec_(2026_01-02)_Bid_Set.pdf

PDF 10 MB Posted

Attached to
Construction of Clay County Fire Station No. 24
Solicitation number
25/26-042
Issued by
Clay County, Harold CDP, Florida

About this file

This is an electrical bid set of construction documents for Clay County Fire Station No. 24, a new approximately 16,633 square-foot fire station facility located at 1075 County Road 226 in Green Cove Springs, Florida. The electrical scope encompasses a complete 1,000-ampere, 208/120-volt, three-phase service with automatic transfer switch and 275-kilowatt diesel generator backup, interior and exterior lighting systems utilizing LED fixtures with occupancy sensors, fire alarm and detection systems with addressable components, lightning protection systems, communications infrastructure including Cat-6 cabling, data outlets, wireless access points, and security systems integration. The project includes photometric site plans, electrical site plans, lighting plans, power and communication plans, fire alarm plans with riser diagrams, panel schedules for multiple distribution panels (MDP, P, P2, P3, L, and PW), grounding systems, and detailed electrical specifications. Mandatory pre-bid conference is scheduled for February 6, 2026, at 10:00 a.m. at the project site; questions must be submitted by February 13, 2026, at 4:30 p.m.; sealed bids are due electronically by March 2, 2026, at 4:00 p.m.; and bid opening occurs on March 3, 2026, at 9:00 a.m. Substantial completion is required by March 15, 2027, with final Certificate of Occupancy by March 20, 2027, to meet grant deadlines.

The bid documents establish comprehensive technical specifications for electrical work including wire sizing calculations, voltage drop analysis, equipment schedules with manufacturer specifications, arc flash labeling requirements, and specialized systems such as emergency lighting with battery backup, fire pump controls with dedicated service entrance, apparatus bay lighting controls, and integration with Purvis notification systems. Bidders must be Florida-licensed General Contractors with minimum five years experience in similar work and must comply with Davis-Bacon Act prevailing wage requirements due to Federal Emergency Management Agency (FEMA) Public Assistance Grant Program funding. Performance and Payment Bonds equal to 100 percent of contract value and Commercial General Liability insurance of $1,000,000 per occurrence and $2,000,000 aggregate are required. Liquidated damages of $1,000 per day apply for delays beyond the final completion date. No specific budget or contract value is disclosed in the available documents. The County reserves the right to approve all subcontractors and may utilize a Direct Purchase Program to procure major materials directly, with such purchases deducted from the contract price.

View the file

Other files

File Type Posted
Construction_of_Clay_County_Fire_Station_No._24_(Addendum_#2_Revision).pdf PDF
Demolition_Asbestos_Survey_Report_.pdf PDF
Tile_Image_.jpg JPG image
07410-STANDING_SEAM_MTL_ROOFING_(Per_Addendum_1).pdf PDF
01260-CONTRACT_MOD_(per_Addendum_1).pdf PDF
01100_Owner_Furnished_Items_(Per_Addendum_1).pdf PDF
@TOC_(Per_Addendum_1).pdf PDF
266612-ASCO_ATS_ELEC_(per_Addendum_1).pdf PDF
Addendum_#1_-_266301-ELEC_TANK_SPEC_(per_Addendum_1).pdf PDF
Addendum_#1_-_266120-ELEC_GENSET_.pdf PDF
Addendum_#1_-_230000-HVAC_.pdf PDF
Addendum_#1_-_12511-Window_Blinds_.pdf PDF
Addendum_#1_-_11452-Appliances_.pdf PDF
Addendum_#1_-_10500-Mobile_PPE_Lockers_.pdf PDF
Addendum_#1_-_10425-Signs.pdf PDF
Addendum_#1_-_Clay_Co_FS24_-_Arch_(2026_02-17)_.pdf PDF
Addendum_#1_-_Clay_Co_FS_24_-_Plum_(2026_02-17)_.pdf PDF
Addendum_#1_-_Clay_Co_FS_24_-_Mech_(2026_02-17).pdf PDF
Addendum_#1_-_Clay_Co_FS_24_-_FP_(2026_02-17).pdf PDF
Addendum_#1_-_Clay_Co_FS_24_-_Civil_(2026_02-17)_.pdf PDF
Addendum_#1_-_Clay_Co_FS24_-_Struct_(2026_02-17).pdf PDF
Addendum_#1_-_Clay_Co_FS24_-_Landscape_(2026_02-17).pdf PDF
Addendum_#1_-_Clay_Co_FS24_-_Elec_(2026_02-17).pdf PDF
Construction_of_Clay_County_Fire_Station_No._24.pdf PDF
Standard_Protection_Measures-Eastern_Indigo_Snake.pdf PDF
Indigo_Snake_Poster.pdf PDF
Clay_Co_Fire_Station_24_(2026_01-02)_Specifications-Bid_Set.pdf PDF
Clay_Co_FS24_AV_Documents_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Purvis_Documents_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Plumb_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Mech_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_FP_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Elec_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Struct_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Arch_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Landscape_Arch_(2026_01-02)_Bid_Set.pdf PDF
Clay_Co_FS24_Civil_(2026_01-02)_Bid_Set.pdf PDF
Owner_Direct_Purchase_Program.pdf PDF
Appendix_II_for_2_CFR_Part_200.pdf PDF
FEMA_Field_Manual.pdf PDF
Subgrant-Agreement-226-SR-DR-4283-Executed-Funding-Agreement-Clay-County-460634-53096.pdf PDF
W-9_(2024).pdf PDF
Certificate_of_final_payment.pdf PDF
Certificate_of_partial_payment.pdf PDF
Chapter_8_Section_I.pdf PDF
EFT_FORM.pdf PDF
Warranty_Letter_.pdf PDF
Performance_&_Paymt_Bond.doc DOC document
Show all 48

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Image

Symbol Label QTY Catalog Number Description Lamp Number

Lamps Filename

Lumens per

Lamp

Lumen

Multiplier LLF Wattage Manufacturer

P1

18 DSX1 LED P1 40K TFTM

MVOLT HS

DSX1 LED P1 40K TFTM MVOLT

with houseside shield

LED 1 DSX1_LED_P1_40K_TFT

M_MVOLT_HS.ies

5436 1 0.95 54 Lithonia

Lighting

Schedule

Symbol Label QTY Manufacturer Catalog Description Number

Lamps

Lamp

Output

LLF

Input

Power

P1 18 Lithonia Lighting DSX1 LED P1 40K TFTM

MVOLT HS

DSX1 LED P1 40K TFTM MVOLT with houseside shield

1 5436 0.95 54

P1

P1

P1

P1

P1

P1

P1

P1 P1 P1 P1 P1 P1

P1 P1

P1

P1

P1

Statistics

Description Symbol Max Min Avg/Min Avg Max/Min

Calc Zone #5 1.8 fc 0.0 fc N/A 0.7 fc N/A

Calc Zone #2 1.7 fc 0.0 fc N/A 0.7 fc N/A

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.1

0.2

0.2

0.2

0.2

0.2

0.1

0.1

0.1

0.2

0.3

0.3

0.3

0.3

0.3

0.2

0.1

0.3

0.4

0.5

0.5

0.4

0.4

0.3

0.1

0.5

0.6

0.6

0.5

0.5

0.4

0.1

0.6

0.7

0.7

0.7

0.7

0.6

0.2

0.6

0.8

0.8

0.9

0.9

0.8

0.3

0.6

0.8

0.8

0.9

1.0

0.9

0.2

0.6

0.8

0.8

0.8

0.9

0.7

0.3

0.6

0.8

0.8

0.7

0.7

0.5

0.2

0.6

0.7

0.7

0.6

0.6

0.4

0.1

0.5

0.7

0.7

0.6

0.5

0.3

0.1

0.5

0.7

0.6

0.6

0.5

0.3

0.1

0.6

0.7

0.7

0.6

0.6

0.4

0.1

0.6

0.8

0.7

0.7

0.6

0.5

0.2

0.7

0.8

0.8

0.8

0.8

0.7

0.2

0.6

0.8

0.8

0.9

1.0

0.9

0.3

0.6

0.9

0.8

0.9

1.0

0.9

0.3

0.7

0.9

0.8

0.8

0.8

0.7

0.3

0.7

0.8

0.8

0.7

0.6

0.5

0.2

0.7

0.8

0.8

0.6

0.6

0.4

0.1

0.7

0.8

0.7

0.6

0.6

0.4

0.1

0.3

0.4

0.5

0.4

0.6

0.5

0.4

0.4

0.5

0.6

0.8

0.9

1.0

0.9

0.8

0.7

0.6

0.4

0.1

0.5

0.7

1.0

1.3

1.2

1.1

0.9

0.9

1.0

1.2

1.5

1.5

1.4

1.3

1.2

0.9

0.8

0.5

0.2

0.6

0.8

1.1

1.4

1.4

1.2

1.2

1.2

1.2

1.4

1.5

1.6

1.5

1.4

1.2

1.0

0.9

0.7

0.3

0.7

0.9

1.1

1.4

1.5

1.6

1.6

1.6

1.5

1.5

1.5

1.5

1.6

1.6

1.4

1.2

1.2

0.9

0.3

0.8

1.0

1.2

1.4

1.6

1.7

1.6

1.6

1.6

1.6

1.4

1.3

1.3

0.6

0.4

0.7

0.9

1.1

1.3

1.5

1.7

1.7

1.7

1.7

1.6

1.5

1.5

1.6

1.5

1.3

1.2

1.2

0.9

0.4

0.5

0.7

0.8

1.0

1.2

1.4

1.6

1.6

1.4

1.3

1.2

1.2

1.3

1.3

1.1

1.0

0.9

0.7

0.3

0.4

0.5

0.6

0.7

0.8

1.2

1.4

1.4

1.2

0.9

0.8

0.9

1.0

1.0

0.9

0.7

0.6

0.5

0.2

0.2

0.2

0.3

0.4

0.5

0.8

1.0

1.0

0.8

0.6

0.6

0.6

0.7

0.7

0.7

0.6

0.5

0.3

0.1

0.5

0.5

0.5

0.4

0.4

0.2

0.1

0.4

0.5

0.5

0.4

0.4

0.2

0.1

0.4

0.5

0.5

0.4

0.4

0.2

0.1

0.5

0.6

0.6

0.5

0.5

0.3

0.1

0.6

0.7

0.7

0.6

0.5

0.4

0.2

0.6

0.8

0.8

0.8

0.8

0.6

0.2

0.6

0.8

0.8

0.9

1.0

0.8

0.3

0.6

0.8

0.8

0.9

1.0

0.8

0.3

0.1

0.1

0.2

0.4

0.6

0.8

0.8

0.8

0.8

0.6

0.2

0.1

0.1

0.2

0.4

0.6

0.7

0.7

0.6

0.6

0.4

0.2

0.1

0.1

0.2

0.4

0.5

0.6

0.6

0.5

0.5

0.3

0.1

0.1

0.1

0.2

0.3

0.5

0.5

0.5

0.4

0.4

0.3

0.1

0.1

0.1

0.1

0.2

0.3

0.4

0.5

0.5

0.4

0.4

0.2

0.1

0.1

0.1

0.1

0.2

0.3

0.5

0.5

0.5

0.4

0.4

0.3

0.1

0.1

0.1

0.2

0.2

0.4

0.5

0.6

0.6

0.5

0.5

0.3

0.1

0.2

0.2

0.2

0.3

0.5

0.6

0.7

0.7

0.7

0.6

0.4

0.2

0.1

0.1

0.2

0.3

0.4

0.3

0.4

0.4

0.6

0.7

0.9

0.8

0.8

0.8

0.7

0.3

0.3

0.4

0.5

0.7

0.9

1.0

0.9

0.7

0.8

0.9

1.1

1.0

1.0

1.1

0.9

0.3

0.4

0.6

0.8

1.0

1.2

1.3

1.2

1.0

1.1

1.2

1.3

1.2

1.2

1.2

0.9

0.3

0.6

0.8

1.0

1.2

1.4

1.5

1.4

1.3

1.4

1.4

1.4

1.2

1.1

1.1

0.8

0.3

0.7

1.0

1.2

1.5

1.5

1.6

1.6

1.5

1.6

1.6

1.5

1.3

1.1

0.9

0.6

0.2

0.7

1.0

1.3

1.5

1.6

1.7

1.7

1.6

1.7

1.6

1.6

1.4

1.1

0.9

0.6

0.2

0.6

0.9

1.1

1.3

1.4

1.5

1.5

1.5

1.5

1.5

1.5

1.3

1.1

0.9

0.6

0.2

0.5

0.7

0.9

1.1

1.3

1.3

1.3

1.2

1.3

1.4

1.4

1.2

1.1

1.0

0.8

0.3

0.4

0.5

0.6

0.9

1.2

1.2

1.1

0.9

1.0

1.2

1.3

1.1

1.1

1.2

0.9

0.3

0.1

0.1

0.3

0.4

0.5

0.6

0.5

0.5

0.6

0.9

1.0

0.9

1.0

1.1

0.9

0.3

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0 0.0 0.0 0.0

1.8

1.8

1.8

1.8

0.1

0.1

0.1

0.2

0.1

0.1

0.1

0.1

0.3

0.3

0.2

0.1

0.2

0.4

0.4

0.4

0.4

0.2

0.5

0.6

0.5

0.5

0.5

0.2

0.2

1.0

0.9

0.7

0.7

0.4

0.9

1.1

1.0

0.8

0.8

0.2

0.5

0.9

1.0

1.0

0.9

0.9

0.1

0.3

0.7

0.8

0.9

0.9

1.0

0.1

0.5

0.7

0.8

0.9

1.0

0.3

0.7

0.7

0.9

1.0

1.0

0.3

0.7

0.8

0.8

0.9

1.0

0.4

1.0

1.0

0.9

1.0

1.0

0.5

1.1

1.0

1.0

1.0

0.2

0.6

0.9

0.9

0.9

0.9

0.2

0.5

0.7

0.8

0.8

0.9

0.1

0.5

0.6

0.7

0.8

0.8

0.1

0.2

0.5

0.6

0.7

0.7

0.1

0.4

0.5

0.6

0.7

0.7

0.2

0.5

0.6

0.6

0.7

0.7

0.4

0.7

0.6

0.7

0.8

0.3

0.7

0.9

0.8

0.8

0.8

0.3

1.0

1.0

0.9

0.8

0.9

0.4

0.9

0.9

0.9

0.9

0.8

0.2

0.4

0.7

0.8

0.8

0.9

0.1

0.5

0.6

0.7

0.8

0.8

0.2

0.5

0.6

0.7

0.8

0.8

0.3

0.6

0.6

0.7

0.8

0.2

0.5

0.6

0.7

0.8

0.8

0.3

0.8

0.8

0.8

0.8

0.8

0.5

1.0

0.9

0.8

0.9

0.9

0.3

0.8

1.1

1.0

0.9

0.9

0.8

0.3

0.8

1.0

1.0

1.0

1.0

0.8

0.6

0.3

0.7

0.8

1.0

1.1

1.2

1.1

1.0

0.8

0.3

0.4

0.3

0.7

0.8

1.0

1.1

1.2

1.1

1.1

1.2

1.1

0.9

0.1

0.4

0.7

0.8

1.1

1.2

1.3

1.2

1.2

1.2

1.1

0.9

0.2

0.7

0.8

1.0

1.3

1.4

1.4

1.4

1.3

1.2

1.1

0.9

0.4

0.8

0.9

1.2

1.5

1.6

1.6

1.6

1.5

1.4

1.3

1.1

0.3

0.7

1.0

1.1

1.3

1.5

1.6

1.5

1.5

1.3

1.1

0.4

1.0

1.2

1.2

1.4

1.6

1.6

1.6

1.4

1.3

1.2

1.1

1.0

0.5

1.2

1.2

1.2

1.3

1.4

1.4

1.3

1.2

1.1

0.9

0.8

0.7

0.6

1.0

1.1

1.1

1.2

1.2

1.2

1.2

1.1

1.0

0.8

0.6

0.5

0.2

0.5

0.7

0.8

1.0

1.1

1.1

1.1

1.1

0.1

0.9

0.7

0.5

0.4

0.1

0.4

0.5

0.6

0.7

0.7

0.7

0.6

0.5

0.4

0.4

0.3

0.2

0.1

0.5

0.6

0.6

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

0.0

1.7

1.7

ENGINEERING

P H&

POWELL & HINKLE ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FLORIDA 32073

(904) 264-5570 FAX:(904) 278-2646

ROBERT L. HINKLE

GALTON C. MOK

LANE R. HINKLE

THOMAS M. ELDER

RICHARD A. MATHEWS

PE 29302

PE 33192

PE 48076

PE 56121

PE 59418

DAVID R. SPELL JR. PE 54729

JAMES L. HENNESSEY PE 83241

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4

P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5

W. W. W. D A S H E R H U R S T . C O M

PHOTOMETRIC

SITE PLAN

22003

06.23.2023

C

O U

N T Y

R O

A D

G R

E E N

C O

V E S

P R

IN

G

S F L

E001

BID DOCUMENTS

C L A

Y C

O U

N

TY

C L A

Y C

O F

IR

E S

TA

TI

O N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

NTS

PHOTOMETRIC SITE PLAN

REVISIONS

# DATE DESCRIPTION

S B

J J

J

J

J

J

J

C A M

C A M

C A M

PROPOSED

208/120/3P/4W

UTILITY XFMR

275KW

DIESEL

GENERATOR

CT CABINET,

CAMLOCK BOX

& UTILITY

METER

ATS

TBB

J L - 10

PROVIDE CONNECTION

TO MONUMENT SIGN

TYPE S1

J

P2 - 32

GATE OPERATOR

P1 P1 P1 P1 P1 P1

P1

P1

P1

P1

P1 L - 11,13

L - 12,14

(#10)

(#10)

PW - 8,10

WELL

WELL

WELL

PW - 9,11

PW - 12,14

P1

P1

P1

L - 16,18

P1

P1

P1

P1

L - 17

FP

WP

WP

P3 - 10

P3 - 9

(#10)

WP

WP

WP

P3 - 11

P3 - 13

P3 - 12

(#10)

(#10)

(#10)

P3 - 14

(#10)

REMOVED

TOWER

REMOVED

CAR CHARGER

CR

FP

FP

CARD READER

CR

CARD READER

AT GATE

ENGINEERING

P H&

POWELL & HINKLE ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FLORIDA 32073

(904) 264-5570 FAX:(904) 278-2646

ROBERT L. HINKLE

GALTON C. MOK

LANE R. HINKLE

THOMAS M. ELDER

RICHARD A. MATHEWS

PE 29302

PE 33192

PE 48076

PE 56121

PE 59418

DAVID R. SPELL JR. PE 54729

JAMES L. HENNESSEY PE 83241

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4

P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5

W. W. W. D A S H E R H U R S T . C O M

ELECTRICAL

SITE PLAN

22003

06.23.2023

C

O U

N T Y

R O

A D

G R

E E N

C O

V E S

P R

IN

G

S F L

E100

BID DOCUMENTS

C L A

Y C

O U

N

TY

C L A

Y C

O F

IR

E S

TA

TI

O N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

1" = 20'-0"

ELECTRICAL SITE PLAN

1. ELECTRICAL SITE PLAN NOTES:

1. PRIOR TO START OF ANY WORK OBTAIN WRITTEN APPROVAL FOR LOCATION OF POLE/TRANSFORMERS & CONNECTION POINT PER ELECTRIC UTILITY CO DIRECTION. CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND COMPLYING WITH MOST CURRENT UTILITY RULES AND REGULATIONS. PROVIDE SERVICE ENTRANCE CONDUITS W/36" RADIUS ELLS AT POLE & SERVICE CONNECTION POINT. PROVIDE CONDUITS WITH PULLWIRES AND MAINTAIN 42" MINIMUM DEPTH, LOCATION OF POLE/TRANSFORMERS AND SECONDARY CONDUIT/FEEDER(S) ARE CONTINGENT UPON ELECTRICAL UTILITY CO APPROVAL. PROVIDE GROUND RODS PER ELECTRICAL UTILITY CO REQUIREMENTS.SEE 'POWER RISER ' FOR

ADDITIONAL REQUIREMENTS. CLAY ELECTRIC UTILITY CONTACT IS XXX AT 904-276-6719.

2. PRIOR TO START OF ANY WORK OBTAIN WRITTEN APPROVAL FOR LOCATION OF SERVICE

CONDUITS & CONNECTION POINT PER TELEPHONE UTILITY DIRECTION. PROVIDE (2) 2"

CONDUITS WITH PULLWIRE TO PROPERTY LINE, STUB UP AND CAP AND MARK 'TELEPHONE'.

SEE ALSO 'TELEPHONE BACKBOARD RISER' FOR ADDITIONAL REQUIREMENTS.

3. SERVICE ENTRANCE FROM ELECTRICAL UTILITY CO TRANSFORMER, SEE 'POWER RISER' FOR

ADDITIONAL REQUIREMENTS.

4. FIRE PUMP SECONDARY SERVICE. PROVIDE CONNECTION TO FIRE PUMP CONTROLLER.

5. STAND-BY DIESEL GENERATOR WITH PAD .ALL CONDUITS AND WIRING SHALL BE BY ELECTRICAL CONTRACTOR.

6. NEW UTILITY POLE ON THE OTHER SIDE OF COUNTY ROAD 226.

7. PROVIDE 1" CONDUIT TO STUB UP INTO WATCH ROOM FROM GATE CONTROLLER.

8. CONFIRM LOCATION, QUANTITY AND HORSEPOWER OF EACH WELL FROM CIVIL BEFORE ROUGH-IN.

9. MOUNT FLAGPOLE LIGHTS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

10. PROVIDE GFI RECEPTACLE WITH WATERPROOF IN-USE COVER AT LIGHT POLE INDICATED.

11. PROVIDE MECLUBE 090-5070-07X DIESEL TRANSFER SYSTEM 'CAMI DISPENSER' SYSTEM AT GENERATOR DIESEL BASE

TANK. INSTALL, POWER AND GROUND PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

12. PROVIDE (2) 1" CONDUITS TO STUB UP INTO WATCH ROOM FROM GATE CONTROLLER. ONE CONDUIT SHALL BE FOR GATE CONTROLLER/COMMUNICATION, THE OTHER 1" CONDUIT SHALL EXTEND TO CARD READER PEDESTAL/CAMERAS.

COORDINATE EXACT LOCATION WITH GATE MANUFACTURER INSTALLATION INSTRUCTIONS. CARD READER AND CAMERA CABLING SHALL EXTEND FROM PEDESTAL TO ACCESS CONTROL SYSTEM AND CAMERA CONTROLLER AS REQUIRED.

REVISIONS

# DATE DESCRIPTION

1 11/03/2023 Permit Rev 1

5 07/19/2024 VE Rev 1

6 09/05/2025 90% IRC REVIEW

M

M

M

M

M M

M

D M

M

M

M

M

M

M M

M

M

DD

D

M

D

M

M

CLOSET

IT

LAUNDRY

CAPT OFF

LOCKERS

ELEC

OFFICE

OFFICE

UTIL

CORR

MEDICAL

MAINT

STOR

LOCKER

VESTIBULE

BUNK4

BUNK3

STOR

WATCH

FITNESS

CAPTAIN'S SUITE

DECON

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

CORR

APP BAY

BUNK5

BUNK6

BUNK1

BUNK2

BUNK9

BUNK10

BUNK7

BUNK8

BUNK 11

BUNK 12

LOBBY

L - 2

L - 1

B1 B1 B1 B1 B1

B1 B1 B1 B1B1 B1 B1 B1

B1 B1 B1 B1B1 B1 B1 B1

B1 B1 B1 B1B1 B1 B1 B1

B1 B1 B1 B1B1 B1 B1 B1

B1 B1 B1 B1B1 B1 B1 B1

B1 B1 B1 B1B1 B1 B1 B1

B1 B1 B1 B1B1 B1 B1 B1

B1 B1 B1 B1B1 B1

A1 A1

A1 A1

A1 A1 A1

A3A3 A3

A3

A3A3A3A3

A3A3

A3

A3

A3

A3

A3

A1

A1

A1

A1

A1

A1

A1

A1 A1

A1

A1

A1

A1

A1

A1

A1

A1 A1

A1

A1

A1

A1

A1

L - 3

A1 A1 A1 A1

L - 5

A3A3

A3

A3

A3

A3

A3 A3

A3

L - 4

F1

F1

F1

C1

C1

C1

C1 A1A1

A1

F1

F1

G2 G2 G2 G2

G2

G2G2G2G2

G2

G1

G1

L - 6

G2

EL

EL

EL

C2

EL

EL

A1

A3

G2

A1

A1

A1 A1

F3

F3

F3

F3

F3

F3

F3 F3

C5

C5

C5

C5

C5

C5

D D

L - 7

EL

EL

EL

EL

EL

EL

EL

EL

EL

EL

EL

C5

H2

H

H

H2

H

H

H

H2

H

H

H2

H

H

H

H2

H

H

H2

H

H

H

C2 C2 C2

C2

C2

C2

C2

C2C2

C2C2

C2

C2

C1

C1

C1

C1

C1

C1

C1

C2

C2

C2 C2

C2

C2

C1

C1

C1

C1 C1

C1

C1

C1

F1 F1F1

C1F3

L - 8

L - 9

G2

TIE TO

L-9

X1

X1

X1

X1

X1

X1

X1

X1

J J

PW - 6

K2

K

K

K

K

EL

EL

EL

EL

A1

EL

ELG1

EL

G1

EL

G1

EL

EL

EL

EL

REMOVED TOWER AND

RELATED LIGHTING

C2 J2

J2 J2

J2 J2

J2

MECH

F5

F5

C4

C4

EL

EL

ENGINEERING

P H&

POWELL & HINKLE ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FLORIDA 32073

(904) 264-5570 FAX:(904) 278-2646

ROBERT L. HINKLE

GALTON C. MOK

LANE R. HINKLE

THOMAS M. ELDER

RICHARD A. MATHEWS

PE 29302

PE 33192

PE 48076

PE 56121

PE 59418

DAVID R. SPELL JR. PE 54729

JAMES L. HENNESSEY PE 83241

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4

P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5

W. W. W. D A S H E R H U R S T . C O M

LIGHTING PLAN

22003

06.23.2023

C

O U

N T Y

R O

A D

G R

E E N

C O

V E S

P R

IN

G

S F L

E101

BID DOCUMENTS

C L A

Y C

O U

N

TY

C L A

Y C

O F

IR

E S

TA

TI

O N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

1/8" = 1'-0"

LIGHTING PLAN

NOTES:

1. REFER TO ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATIONS OF ALL

CEILING LIGHT FIXTURES.

2. TYPICAL CEILING MOUNTED OCCUPANCY SENSOR CONNECTIONS (VIA LOW VOLT CABLES NOT

SHOWN);

A.) WHERE NO CIRCUIT NUMBERS OR SWITCH LETTERS ARE DESIGNATED; CONNECT ALL

CEILING MOUNTED OCCUPANCY SENSORS FOR AUTOMATIC CONTROL OF AREA LIGHT FIXTURES

IN TANDEM WITH LOCAL SWITCH AS INDICATED.

B.) WHERE ONE CIRCUIT NUMBER OR SWITCH LETTER IS SHOWN; CONNECT CEILING

MOUNTED OCCUPANCY SENSORS TOGETHER IN TANDEM WITH THAT DESIGNATED

CIRCUIT/LOCAL SWITCH LETTER (MAXIMUM 2,500 SQ FT PER SWITCH). SEE "TYPICAL OFFICE

AREA OCCUPANCY SENSOR WIRING DIAGRAM".

3. ALL SENSORS LOCATED IN AREAS SUCH AS BREAK ROOMS & MECHANICAL ROOMS SHALL BE

PROGRAMMED AS VACANCY TYPE SENSORS. ALL SENSORS LOCATED IN AREAS SUCH AS OPEN

AREAS, CORRIDORS & RESTROOMS SHALL BE PROGRAMMED AS OCCUPANCY TYPE SENSORS.

4. BATHROOM LIGHT MOTION SENSORS SHALL CONTROL BATHROOM LIGHTS AND FANS AND

SHALL BE SET TO TURN OFF AFTER 5 MINUTES OF NO OCCUPANTS DETECTED.

5. NOTE NOT USED

6. TYPE C4 AT CANOPIES SHALL BE TIED TO EXTERIOR LIGHTING CIRCUIT AND CONTROLLED BY

PHOTOCELL/TIMESWITCH.

C4 C4 C4

C4 C4 C4

G1

EL

EL EL EL

EL EL

EL

REVISIONS

# DATE DESCRIPTION

1 11/03/2023 Permit Rev 1

G F

C I

J

J

J J

J

J

J

J

J

J

J

J J J

J J J

J

J

J J

J

J J

J J

J

J

J

J

J

J

J

J J

J

J

J

J

J

J

J

J

J

J J J

J

J J J J

J

J

J

J

J

CLOSET

IT

UTIL

LAUNDRY

UTIL

CAPT OFF

LOCKERS

ELEC

OFFICE

OFFICE

UTIL

CORR

CORR

MAINT

STOR

LOCKER

VESTIBULE

BUNK4

BUNK3

STOR

WATCH

CORR

MEETING

FITNESS

CAPTAIN'S SUITE

DECON

LOCKER

LOCKER

LOCKER

LOCKER

LOCKER

CORR

APP BAY

BUNK5

BUNK6

BUNK1

BUNK2

BUNK9

BUNK10

BUNK7

BUNK8

BUNK 11

BUNK 12

LOBBY

TV

72"

ATS

P2L

P

TV

72"

WP

WP

PHONE

42"

WP

WP

WAP

WAP

PHONE

WAP

WAP

AHU-4AHU-3

AHU-5

AHU-6

CU-6

AHU-1

AHU-2

P - 3

P - 4

P - 2

P - 1

P - 5

60" 60"

P - 6

P - 7P - 9

P - 10

P - 8

DINING

KITCHEN

P - 17 P - 18

P - 19

P - 20

P - 14

P - 15

P - 21

P - 11,13

P - 22

P - 12

PPE STOR

MEDICAL

P - 24

P - 23

P - 26

P - 25

P - 28

P - 27

P - 31

P - 29

P - 34

P - 30

P - 33

P - 35

P - 36

P - 38

M - 21,23

M - 20,22

M - 25,27 M - 24,26

M - 33,35

TO

CU-

FIT

48"x26.25", 120 V/208 V, Three Phase, 4 Wires, Wye - 8

AIR COMP.

P - 32 P - 40

P2 - 1

P2 - 2

WP

WP

WP

WP

P2 - 3

66" 66"

P2 - 4

P2 - 5

P2 - 6

P2 - 7 P2 - 8

P2 - 9,11,13 P2 - 10,12,14 P2 - 15,17,19

16 16 16

P2 - 16 P2 - 18 P2 - 20

16 16 16

P2 - 21,23,25

M

M - 1,3,5

UH-1

UH-2

M - 2,4,6

UH-3

M - 7,9,11

UH-4

M - 8,10,12

EF-2 EF-3

M - 13,15,17 M - 14,16,18

17 18

24 24

WP

WP

P2 - 22

P2 - 24

WP

P2 - 26

P2 - 27

P2 - 28

P2 - 29

P2 - 30

29 29

P2 - 31

EF-WELL

PW

PW - 1

44" 44"

(ON ROOF)

P2 - 33

P2 - 34,36,38

FPH-WELL

PW - 2,4

PW - 3,5,7

P2 - 35

ELECTRICAL CONTRACTOR SHALL REFER TO THE

PURVIS SYSTEM DRAWINGS AND PROVIDE THE

ELECTRICAL CONTACTOR SCOPE OF WORK INDICATED

ON THOSE DRAWINGS.

TV

72"

P2 - 37,3936

P2 - 40

34 34 3434

P - 16

72"

(TV)

P3

P3 - 1

41 41

41 41 41 41

P3 - 2 P3 - 3

P3 - 5 P3 - 6 P3 - 7 P3 - 8

P3 - 1572"

72"

P3 - 16,18

SCBA

P3 - 17,19

P3 - 20,22

P3 - 4

REMOVED TOWER AND

RELATED ELECTRICAL

P3 - 21,23

P3 - 24,26

FPH-STOR

FPH-MAINT

FPH-DECON

P3 - 25,27

34 34

34 34 3434 34 34

MDP-9

WP

(ON ROOF)

(ON ROOF)

P2 - 41

P - 39,41

5 7

BDA ANTENNA

LOCATION

(ON ROOF)

P2 - 42

76"

76"

P - 38

7 REVISED WATCHROOM

CU-FITCU-5

CU-4

CU-3

CU-IT

RTU-OA

CU-1

CU-2

M - 32,34

M - 36,38

M - 39,41

M - 29,31

M - 28,30

M - 40,42

TO

AHU-IT

EF-1

EF-HOOD

M - 19

M - 37

MDP-6

MDP-4

ENGINEERING

P H&

POWELL & HINKLE ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FLORIDA 32073

(904) 264-5570 FAX:(904) 278-2646

ROBERT L. HINKLE

GALTON C. MOK

LANE R. HINKLE

THOMAS M. ELDER

RICHARD A. MATHEWS

PE 29302

PE 33192

PE 48076

PE 56121

PE 59418

DAVID R. SPELL JR. PE 54729

JAMES L. HENNESSEY PE 83241

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4

P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5

W. W. W. D A S H E R H U R S T . C O M

POWER/COMM

PLAN

22003

06.23.2023

C

O U

N T Y

R O

A D

G R

E E N

C O

V E S

P R

IN

G

S F L

E102

BID DOCUMENTS

C L A

Y C

O U

N

TY

C L A

Y C

O F

IR

E S

TA

TI

O N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

1/8" = 1'-0"

POWER/COMM PLAN

NOTES:

1. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND REQUIREMENTS OF ALL HVAC

EQUIPMENT. IF CONDENSATE PUMP(S) ARE REQUIRED, TIE TO NEAREST 120V OUTLET.

2. PROVIDE TAMPER RESISTANT RECEPTACLES PER NEC 406.12

3. PROVIDE CONNECTION TO EWH-2.

4. STANDBY GENERATOR ANNUNCIATOR LOCATION. CONFIRM WITH OWNER BEFORE ROUGH-IN.

PROVIDE EMERGENCY STOP BUTTON ADJACENT TO GENERATOR ANNUNCIATOR. BUTTON SHALL

BE GLASS-BREAK TYPE WITH A NORMALLY OPEN CONTACT AND SHALL READ "EMERGENCY

GENERATOR STOP". PILLA #ST120FN4SL OR APPROVED EQUAL.

5. PROVIDE LOW FREQUENCY SINGLE STATION SMOKE DETECTOR AT THIS LOCATION.

6. PROVIDE CONNECTION TO PROJECTOR AT CEILING.

7. COORDINATE RECEPTACLE LOCATIONS TO USE WITH CHARGER RACKS.

8. PROVIDE CONNECTION TO EWH-1.

9. FROM J-BOX, PROVIDE 120V CONNECTION TO HOOD LIGHTS AND EXHAUST FAN, COORDINATE

EXACT REQUIREMENTS WITH HOOD SUPPLIER PRIOR TO ROUGH-IN.

10. TIE HOOD FIRE ALARM SUPPRESSION SYSTEM TO FIRE ALARM AS REQUIRED, COORDINATE

EXACT REQUIREMENTS WITH HOOD SUPPLIER PRIOR TO ROUGH-IN.

11. PROVIDE CONNECTION TO DISHWASHER.

12. PROVIDE POP-UP USB TYPE RECEPTACLE IN COUNTERTOP.

13. PROVIDE CONNECTION TO HOT WATER RECIRC PUMP. SEE PLUMBING DRAWINGS FOR EXACT

LOCATION.

14. SEE T101 FOR DATA OUTLET LOCATIONS AND PURVIS NOTIFICATION SYSTEM REQUIREMENTS.

DATA OUTLETS ARE SHOWN ON THIS DRAWING FOR REFERENCE ONLY FOR GENERAL TV AND

WORKSTATION LOCATIONS IN RELATION TO THE 120V RECEPTACLES THEY ARE NEXT TO. (DO NOT

DOUBLE COUNT LOCATIONS).

15. PROVIDE USB TYPE RECEPTACLES IN BUNK ROOMS, TYP.

16. TIE TO OPEN/CLOSE/STOP SWITCH PROVIDED WITH DOOR OPENER. PROVIDE WITH

CONTACTORS AND CONNECT AS REQUIRED TO DISCONNECT HVAC EQUIPMENT. COORDINATE

EXACT REQUIREMENTS WITH DOOR SUPPLIER AND HVAC CONTRACTOR PRIOR TO ROUGH-IN.

17. PROVIDE A 4X4X 2 1/8 J-BOX FOR ANTENNA ABOVE CEILING.

18. PROVIDE 1"C WITH RG58 COAXIAL CABLES TO ANTENNA, COORDINATE ANTENNA LOCATION

AND QUANTITY OF CABLES WITH OWNER.

19. PURVIS SYSTEM COMPUTER STATION SHALL BE INSTALLED ON TOP OF COUNTER WORK,

VERIFY EXACT LOCATION WITH OWNER AND PURVIS DRAWINGS BEFORE ROUGH-IN.

20. PROVIDE 6X6X4 J-BOX WITH 1"C. AND 4 PAIRS OF #18 AWG TWISTED PAIR, PLENUM RATED

(CMP) STRANDED CABLES, TERMINATE ON THE BACKBOARD IN COMM. ROOM.

21. TIMER FOR PURVIS FSAS. REFER TO PURVIS DRAWINGS.

22. OUTDOOR SPEAKER SHALL BE BOGEN #SPT 15A OR APPROVED EQUAL MOUNTED AT 15'-0" TO

CENTER AFG ON SMOOTH WALL. REFER TO PURVIS DRAWINGS.

23. PROVIDE VOLUME CONTROL FOR SPEAKER. COORDINATE MOUNTING HEIGHT AT 42" AFF.

REFER TO PURVIS DRAWINGS.

24. FLOOR BOX WITH (2) DUPLEX AND (2) CAT6 JACKS.

25. COMMUNICATIONS RACK PROVIDED AND INSTALLED BY E.C.

26. OUTDOOR SPEAKER SHALL BE BOGEN #SPT 15A OR APPROVED EQUAL MOUNTED AT 9'-0" TO

CENTER AFF ON SMOOTH WALL.

27. GENERATOR ANNUNCIATOR.

28. FIRE ALARM SYSTEM ANNUNCIATOR.

29. PROVIDE CONNECTION TO FLUSH VALVES (TYP.) PER MANUACTURER'S INSTALLATION

INSTRUCTIONS. REFER TO PLUMBING PLANS.

30. PROVIDE CONNECTION TO EF-WELL FAN AND LINE VOLTAGE THERMOSTAT. SEE MECHANICAL

DRAWINGS.

31. POWER/DATA FLOORBOX WITH RECEPTACLE AND (2) CAT6 CONNECTIONS.

32. POWER/DATA FOR TV'S SHALL BE AT 72" AFF. COORDINATE WITH OWNER'S TV MOUNTING

BRACKET. CONCEAL ALL DEVICES BEHIND TV.

33. POWER FOR 5HP VEHICLE EXHAUST SYSTEM. COORDINATE WITH MANUFACTURER

INSTALLATION INSTRUCTIONS AND PROVIDE BREAKER AND CIRCUIT.

34. DOOR SIGNAL LIGHT CONTROL/POWER SUPPLY J-BOX LOCATION @ 20" FROM TOP OF DOOR

AND 8" OUTSIDE OPENING (CONFIRM WITH OWNER BEFORE ROUGH-IN.) SEE ARCHITECTURAL

DRAWINGS FOR INTERIOR AND EXTERIOR WARNING LIGHT LOCATIONS. PROVIDE ALL

CONNECTIONS TO SYSTEM PER MANUFACTURER INSTALLATION INSTRUCTIONS FOR A FULL AND

COMPLETE WARNING LIGHT SYSTEM. TERMINATE CONDUIT ABOVE CEILING. TYPICAL FOR ALL OH

APP BAY DOORS, J-BOXES INSIDE AT FRONT AND OUTSIDE AT BACK.

35. SEE PURVIS DRAWINGS FOR GAS SHUTOFF CONNECTION TO PURVIS SYSTEM.

36. PROVIDE CONNECTION TO RECIRC. PUMP.

37. PROVIDE CONNECTION TO TRAP PRIMER.

38. PROVIDE CONNECTION TO MOTORIZED SCREEN AND CONTROLS PER MANUFACTURER'S

INSTALLATION INSTRUCTIONS. COORDINATE SWITCH LOCATION WITH OWNER BEFORE ROUGH-IN.

39. PROVIDE CONNECTION TO CONDENSATE PUMP.

40. PROVIDE CONNECTION TO IRRIGATION CONTROLLER.

41. PROVIDE CONNECTION TO EXTENSION CORD REEL AT CEILING. PROVIDE LEGRAND 1200

SERIES WITH BALL STOP, 35' OF CORD, SINGLE OUTLET, 20A.

42. ELECTRICAL IN APP BAY SHALL BE RECESSED. COORDINATE ANY ITEMS REQUIRED TO BE

SURFACE MOUNTED WITH ARCHITECT BEFORE ROUGH-IN.

43. PROVIDE CONNECTION TO EXTRACTOR PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

44. PROVIDE CONNECTION TO SCBA PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.

COORDINATE EXACT LOCATION WITH OWNER BEFORE ROUGH-IN.

45. THIS SPACE SHALL HAVE THE TOP OUTLET OF EACH RECEPTACLE SWITCHED AND THE

BOTTOM OUTLET UNSWITCHED. PROVIDE LABELS AT EACH OUTLET THAT READ SWITCHED AND

UNSWITCHED. RECEPTACLES SHALL BE SWITCHED BY ROOM OCCUPANCY SENSOR AND SHALL

TURN OFF AFTER 20 MINUTES WITHOUT OCCUPANT DETECTION.

REVISIONS

# DATE DESCRIPTION

1 11/03/2023 Permit Rev 1

2 12/01/2023 Permit Rev 2

5 07/19/2024 VE Rev 1

6 09/05/2025 90% IRC REVIEW

7 01/02/2026 90% V2 IRC REV

1/8" = 1'-0"

ROOF POWER PLAN

S

P

P

P

P

P

P

P

P

P

P

S

H

H

S

H

M

L

L

L

L

H

M M

M M

M M M

M M

M

L

M

H

H

L

L

S

H

H

H

H

H

H

H

L

H

H H

H

S

H

H H

H

H

H

M M

FACP

CO

CO

CO

CO

110 110

CO

CO CO

CO CO

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

S

LF

REMOVED

TOWER

MEETING

WATCH

LOBBY

CORR

CLOSET

MEN

WOMEN

UTIL

DECON

PPE STOR

CORR

OFFICE

QUIET RM

DAY ROOM

ELEC

KITCHEN

DINING

SHOWER RM

IT

MEDICAL

CORR

SHOWER RM

WOMEN

FITNESS

APP BAY

LAUNDRY

LOCKERS

UTIL

UTIL

VESTIBULE

CORR

CAPT SUITE

CAPT RR

CAPT OFF

CORR

BUNK1

BUNK2

BUNK3

BUNK4

BUNK5

BUNK6

BUNK7

LOCKER

LOCKER

134 LOCKER

LOCKER

BUNK8

BUNK9

BUNK10

BUNK11

W/C

BUNK 12

STOR

MAINT

LOCKER

LOCKER

ENGINEERING

P H&

POWELL & HINKLE ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FLORIDA 32073

(904) 264-5570 FAX:(904) 278-2646

ROBERT L. HINKLE

GALTON C. MOK

LANE R. HINKLE

THOMAS M. ELDER

RICHARD A. MATHEWS

PE 29302

PE 33192

PE 48076

PE 56121

PE 59418

DAVID R. SPELL JR. PE 54729

JAMES L. HENNESSEY PE 83241

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4

P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5

W. W. W. D A S H E R H U R S T . C O M

FIRE ALARM

PLAN

22003

06.23.2023

C

O U

N T Y

R O

A D

G R

E E N

C O

V E S

P R

IN

G

S F L

E103

BID DOCUMENTS

C L A

Y C

O U

N

TY

C L A

Y C

O F

IR

E S

TA

TI

O N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

1/8" = 1'-0"

FIRE ALARM PLAN

NOTES:

1. REFER TO MECHANICAL DRAWINGS FOR EXACT LOCATIONS AND REQUIREMENTS OF ALL HVAC

EQUIPMENT. IF CONDENSATE PUMP(S) ARE REQUIRED, TIE TO NEAREST 120V OUTLET.

2. FIELD VERIFY LOCATION/QUANTITY OF ALL FIRE ALARM DEVICES AND PROVIDE AS REQUIRED

PER FIRE PROTECTION DRAWINGS. SEE FIRE ALARM RISER FOR ADDITIONAL REQUIREMENTS.

3. DEVICE COLOR SHALL BE COORDINATED WITH ARCHITECT BEFORE ORDERING.

ADDED SINGLE STATION SMOKE

DETECTORS WITH LOW

FREQUENCY SOUNDER BASES

INSIDE AND OUTSIDE OF ALL

SLEEPING ROOMS

REVISIONS

# DATE DESCRIPTION

1 11/03/2023 Permit Rev 1

4 01/23/2024 Permit Rev 3

IN ADHESIVE

NO. AUBU12I, ALUMINUM

ALUMINUM AIR TERMINAL

NO. 1224ALAT, 1/2" X 24"

GENTLY TAPERED SOLID

UNIVERSAL BASE SET

L

H25 0

LIGHTNING CONDUCTOR (24

STRANDS OF 14 AWG WIRES -

98 LBS. PER 1000')

NO. A24, CLASS I ALUMINUM

NO. A262, ALUM. ADHESIVE

EVERY 3' MAX.

CABLE FASTENER

1" PVC PIPE BY OTHERS

10'-0" MIN.

NO. A24, CLASS I ALUMINUM

98 LBS. PER 1000')

STRANDS OF 14 AWG WIRES -

LIGHTNING CONDUCTOR (24

NO. BMTRC1, BIMETAL THRU-ROOF

CONNECTOR ASSEMBLY

WITH UWM115 WELD METAL

VU-29B ULTRAWELD MOLD

WITH UWM90 WELD METAL

VA-29B ULTRAWELD MOLD

WITH UWM115 WELD METAL

GD-5829B ULTRAWELD MOLD

WITH UWM150 WELD METAL

G0-5829B ULTRAWELD MOLD

NO. 5810, 5/8" X 10'

COPPER CLAD GROUND ROD

NO. 29, CLASS I COPPER

LIGHTNING CONDUCTOR (29

STRANDS OF 16 AWG WIRES -

215 LBS. PER 1000')

NO. 29, CLASS I COPPER

LIGHTNING CONDUCTOR (29

STRANDS OF 16 AWG WIRES -

215 LBS. PER 1000')

AIR TERMINAL DETAIL 'A'

NTS

THRU ROOF DETAIL 'T'

NTS

GROUND ROD DETAIL 'G'

NTS

A

A

A

A

AA

A

A

A

A A

A

A A

A

A A

AAA

A

TWO NO. 5810 5/8"X10'

COPPER CLAD GROUND

RODS WITH ULTRAWELD

CONNECTIONS SPACED

10' APART. SEE DETAIL 'G'

(TYPICAL)

REMOVED

TOWER

E1112 E111 3

E111

E1115

E111

E111 7

ENGINEERING

P H&

POWELL & HINKLE ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FLORIDA 32073

(904) 264-5570 FAX:(904) 278-2646

ROBERT L. HINKLE

GALTON C. MOK

LANE R. HINKLE

THOMAS M. ELDER

RICHARD A. MATHEWS

PE 29302

PE 33192

PE 48076

PE 56121

PE 59418

DAVID R. SPELL JR. PE 54729

JAMES L. HENNESSEY PE 83241

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4

P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5

W. W. W. D A S H E R H U R S T . C O M

LIGHTNING

PROTECTION

SYSTEM

22003

06.23.2023

C

O U

N T Y

R O

A D

G R

E E N

C O

V E S

P R

IN

G

S F L

E104

BID DOCUMENTS

C L A

Y C

O U

N

TY

C L A

Y C

O F

IR

E S

TA

TI

O N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

1/8" = 1'-0"

ROOF PLAN LIGHTNING PROTECTION

LIGHTNING PLAN NOTES

1. CONTRACTOR TO PROVIDE SEPARATE

PRICE FOR ALL WORK INDICATED ON THE SHEET,

TITLE "ALTERNATE LIGHTNING PROTECTION

SYSTEM" FOR OWNERS REVIEW/APPROVAL.

2. THE COMPLETED INSTALLATION SHALL

MEET THE "INSTALLATION REQUIREMENTS FOR

LIGHTNING PROTECTION SYSTEMS, UL96A" OF

UNDERWRITERS LABORATORIES - 2001 EDITION.

THE UL MASTER LABEL SHALL BE FURNISHED TO

THE OWNER UPON COMPLETION.

3. ALUMINUM LIGHTNING PROTECTION

SYSTEM COMPONENTS SHALL NOT BE MOUNTED

TO COPPER SURFACES. COPPER COMPONENTS

SHALL BE USED TO AVOID ELECTROLYTIC

CORROSION.

4. METAL BODIES WITHIN 6' - 0" OF THE

LIGHTNING PROTECTION SYSTEM SHALL BE

BONDED TO THE SYSTEM IN ACCORDANCE WITH

UL96A - 1995 REQUIREMENTS.

5. UNDERGROUND METALLIC PIPING

ENTERING THE BUILDING SHALL BE BONDED TO

THE NEAREST DOWN CONDUCTOR OR GROUND

ELECTRODE.

6. ADHESIVE USED WITH ADHESIVE AIR

TERMINAL BASES AND CONDUCTOR FASTENERS

SHALL BE COMPATIBLE WITH ROOFING

MEMBRANE - VERIFY WITH ROOFING

CONTRACTOR.

7. AIR TERMINALS HAVE BEEN LOCATED ON

THE ROOF TOP EQUIPMENT AS REQUIRED. IF THE

METAL THICKNESS OF AN OBJECT IS 3/16" OR

GREATER, AIR TERMINALS MAY BE ELIMINATED IF

THE OBJECT IS PROPERLY CONNECTED TO THE

SYSTEM.

8. ROOF TOP EQUIPMENT NOT SHOWN ON

THIS DRAWING SHALL BE PROTECTED AS

REQUIRED TO MEET THE REQUIREMENTS LISTED

ABOVE INCLUDING THE INSTALLATION OF AIR

TERMINALS AND OR BONDING. IF THE METAL

THICKNESS OF AN OBJECT IS 3/16" OR GREATER,

AIR TERMINALS MAY BE ELIMINATED IF THE

OBJECT IS PROPERLY CONNECTED TO THE

SYSTEM.

9. AIR TERMINALS ARE TO BE LOCATED AS

SHOWN. THEY ARE TO BE A MAXIMUM OF 24" FROM

THE ROOF EDGE AND PROJECT A MINIMUM OF 10"

ABOVE THE PROTECTED EDGE. THE SPACING

BETWEEN AIR TERMINALS ARE NOT TO EXCEED 20

FEET. AIR TERMINALS THAT EXTEND 24" ABOVE

THE PROTECTED EDGE ARE NOT TO EXCEED A

SPACING GREATER THAN 25', EXCEPT FOR MID-

ROOF AIR TERMINALS (50' MAX SPACING).

10. ALL LIGHTNING CONDUCTORS ARE TO

MAINTAIN A HORIZONTAL OR DOWNWARD PATH.

ALL BENDS IN THE CONDUCTOR SHALL HAVE A

RADIUS BEND OF 8 INCHES OR GREATER, AND

SHALL HAVE AN ANGLE BEND OF 90 DEGREES OR

GREATER.

11. EACH INDIVIDUAL ITEM OF THE LIGHTNING

PROTECTION SYSTEM IS NOT LABELED FOR THE

SAKE OF CLARITY. ITEMS ARE INDICATED AT

RANDOM LOCATIONS ONLY, BUT A COMPLETE

SYSTEM SHALL BE PROVIDED TO MEET MASTER

LABEL REQUIREMENTS.

12. ROOF PADS, PAVERS, FLASHINGS OR ANY

OTHER SPECIAL ROOFING MATERIALS REQUIRED

FOR THE INSTALLATION OF THE LIGHTNING

PROTECTION SYSTEM SHALL BE FURNISHED AND

INSTALLED BY THE ROOFING CONTRACTOR.

13. SUBMIT SHOP DRAWINGS, CATALOG

SHEETS, OR OTHER DESCRIPTIVE DATA WITH

SUFFICIENT INFORMATION TO ESTABLISH DESIGN,

QUALITY AND PERFORMANCE. MANUFACTURER

CATALOG SHEETS SUBMITTED WITHOUT SPECIFIC

MODEL NUMBERS INDICATED WILL BE REJECTED.

DATA SHALL DESCRIBE APPARATUS, EQUIPMENT,

PANELS.

14. LIGHTNING PROTECTION SYSTEMS SHALL

BE ROOF AIR TERMINALS AND GROUNDING

SYSTEM DESIGNED AND INSTALLED IN

ACCORDANCE WITH NFPA 780 AND CERTIFIED TO

UL 96A STANDARDS. THE ENTIRE SYSTEM SHALL

BE DESIGNED AND INSTALLED BY CERTIFIED

LIGHTNING PROTECTION CONTRACTOR. THE

SYSTEM SHALL INCLUDE PROTECTION FOR ALL

ROOF EQUIPMENT, APPURTENANCES AND

BONDING TO THE ELECTRICAL SYSTEM PER UL

REQUIREMENTS. ALL AIR TERMINALS AND ROOF

CONDUCTORS SHALL BE ALUMINUM. ALL GROUND

CONDUCTORS AND GROUND RODS SHALL BE

COPPER. ROOF TOP HVAC EQUIPMENT AND

ENCLOSURES SHALL NOT BE USED AS

CONDUCTORS. ALL AIR TERMINALS INSTALLED ON

ROOF TOP HVAC EQUIPMENT SHALL BE

CONNECTED WITH CONDUCTORS TO THE MAIN

LIGHTNING CONDUCTORS. CONTRACTOR SHALL

PROVIDE DETAILED DESIGN SHOP DRAWINGS FOR

THE COMPLETE SYSTEM TO INDICATE THE

LOCATION OF AIR TERMINALS, ROOF

CONDUCTORS, DOWN CONDUCTORS, GROUND

RODS AND COMPLETE INSTALLATION DETAILS.

COMPLETED SYSTEM SHALL BEAR UL MASTER

LABEL WITH ALL REQUIRED CERTIFICATION AND

DOCUMENTATION. PROVIDE WITH UL LIGHTNING

PROTECTION INSPECTION CERTIFICATE CERTIFIED

TO UL96A STANDARDS.

15. EXTERIOR EXPOSED DOWN CONDUCTORS

ARE NOT ALLOWED.

16. PROVIDE LIGHTNING PROTECTION FOR THE

GENERATOR (NOT SHOWN) AND RF ANTENNA(S),

CONNECT THE LIGHTNING PROTECTION SYSTEM

TO THE GROUND COUNTERPOISE USING A

COPPER BONDING JUMPER.

17. THE LIGHTNING PROTECTION SYSTEM

SHALL NOT VOID THE ROOF WARRANTY.

NTS

LIGHTNING PROTECTION DETAILS

REVISIONS

MDP

1000A

208/120V

3 PHASE

MLO

NOTES:

1. PROVIDE (1000A) 3 SETS: 4-#400 (NO GROUND) IN 4"C. TO TRANSFORMER PER UTILITY DIRECTION.

2. PRIOR TO START OF ANY WORK OBTAIN WRITTEN APPROVAL FOR LOCATION OF POLE/TRANSFORMERS & CONNECTION POINT PER ELECTRIC UTILITY CO DIRECTION. CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND COMPLYING WITH MOST CURRENT UTILITY RULES AND REGULATIONS. PROVIDE SERVICE ENTRANCE CONDUITS W/36" RADIUS ELLS AT POLE & SERVICE CONNECTION POINT. PROVIDE CONDUITS WITH PULLWIRES AND MAINTAIN 42" MINIMUM DEPTH, LOCATION OF POLE/TRANSFORMERS AND SECONDARY CONDUIT/FEEDER(S) ARE CONTINGENT UPON ELECTRICAL UTILITY CO APPROVAL. PROVIDE GROUND RODS PER ELECTRICAL UTILITY CO REQUIREMENTS. COORDINATE CONDUIT UNDER ROAD INSTALLATION WITH COUNTY AND OBTAIN ALL PERMISSIONS

AND PERMITS.

3. 1"C. TO PHOTOCELL ON ROOF.

4. METER CAN PER UTILITY REQUIREMENTS.

5. 275 KW, 343.8KVA 208/120/3P STANDBY GENERATOR WITH 4 DAY (500 GALLON) DIESEL BASE TANK. ASSEMBLY RATED FOR 160 MPH WIND ZONE. PROVIDE WITH SOUND ATTENTUATING WEATHERPROOF ENCLOSURE.

6. 1000A 208/120/3P/4W AUTOMATIC TRANSFER SWITCH WITH FULLY RATED 1000A MAIN BREAKER, 42,000 AIC, SERVICE ENTRANCE RATED.

7. PROVIDE 3 SETS 4 #400, #2/0 G, 3"C.

8. #2/0 GROUND PER NEC.

9. FIRE PUMP SERVICE: PROVIDE 4-#1/0 IN 1-1/2"C.

10. #1 FIRE PUMP CONTROLLER GROUND.

11. 25 HP FIRE PUMP - PROVIDE CONNECTION TO CONTROLLER PER MANUFACTURER'S INSTALLATION

INSTRUCTIONS.

12. 4-#1/0, #1G-2"C.

13. GENERATOR DURING FIRE EVENT MODE: WHEN BUILDING IS ON GENERATOR POWER AND THE FIRE SPRINKLER SYSTEM IS ACTIVATED, BUILDING ATS SHALL DEACTIVATE AND FIRE PUMP ATS WILL ACTIVATE PROVIDING THE

FIRE PUMP ONLY WITH GENERATOR POWER.

14. 1" PVC CONDUIT STUBBED UP IN MAIN ELECTRICAL ROOM AND FIRE PUMP HOUSE FOR CONTROL WIRING.

ATS

1000A

208/120V

3 PHASE

STANDBY

GENERATOR

208/120V/3P

M

L 100A

208/120V

3 PHASE

MLO

SPD

T/S

L/C

PHOTOCELL ON ROOF

FACING NORTH

M 400A

208/120V

3 PHASE

MLO

P 225A

208/120V

3 PHASE

MLO

UTILITY

TRANSFORMER

208/120V/3P

CT

CABINET

COUNTY ROAD 226

P2 225A

208/120V

3 PHASE

MLO

FIRE PUMP HOUSE

25 HP

FIRE PUMP

208/120V/3P

4 M

CT'S

FIRE STATION

PW

100A

208/120V

3 PHASE

MB

ATS

600A

208/120V

3 PHASE

CAMLOCK

BOX

CAMLOCK

BOX

P3 225A

208/120V

3 PHASE

MLO

FIRE PUMP OVERCURRENT PROTECTION SIZED

TO CARRY INDEFINITELY SUM OF LOCKED ROTOR

CURRENT AND ACCESSORY EQUIPMENT PER 695.6(D).

LRC (25HP)= 404A = 600A BREAKER

FIRE PUMP FEEDER SIZED FOR NOT LESS THAN 125%

OF FIRE PUMP FULL LOAD CURRENT PER 430.248 OR

430.250.

RLC (25HP) = 74.8A X 1.25 = 93.5A #1/0 AMPACITY =150A

FIRE PUMP FEEDER VOLTAGE DROP: NOT MORE THAN

15% BELOW THE CONTROLLER'S RATED VOLTAGE

Vd = [2(130)(0.122)404] / 1000 = 12.8% W/ 1/0 COPPER

NOT MORE THAN 5% BELOW THE VOLTAGE RATING OF

MOTOR WHEN MOTOR OPERATES AT 115% OF FIRE

PUMP FULL-LOAD CURRENT RATING PER 695.7.

Vd = [2(130)(0.245)131.1] / 1000 = 3.3% W/ 1/0 COPPER

130'

G

GROUNDING DETAIL NOTES :

1. EQUIPMENT GROUNDING CONDUCTOR (GND) -REFER TO POWER RISER FOR WIRE SIZE.

2. ALL SERVICE GROUNDING CONNECTIONS SHALL BE DONE WITH EXOTHERMIC WELDS.

3. AFTER GROUNDING SYSTEM IS INSTALLED, GROUND RESISTANCE SHALL BE MEASURED, TO ASSURE THAT GROUND

VALUE OF 10 OHM MAXIMUM RESISTANCE IS ACHIEVED. IF NOT, ADDITIONAL GROUNDING SHALL BE PROVIDED TO

MEET SPECIFIC VALUE.

4. GROUNDING ELECTRODE CONDUCTOR (NEUTRAL) - REFER TO POWER RISER FOR WIRE SIZE.

5. MAIN BONDING JUMPER SIZE PER NEC 250-66.

6. #3/0 AWG GROUNDING ELECTRODE CONDUCTOR.

7. GROUNDING ELECTRODE CONDUCTOR PER NEC TABLE 250.66

GROUNDING ELECTRODE

3/4" x 10FT

CU CLAD GROUND

RODS (TYPICAL)

EXOTHERMIC

WELD (TYP)

20FT MIN

1000A MB

EQUIPMENT GROUNDING BUS

(NEUTRAL) BUS

METALLIC

UNDERGROUND

WATER PIPE

MIN 20FT #1/0 BARE CU

ENCASED IN BLDG

MIN 2"THICK FOOTING

IN DIRECT

CONTACT WITH EARTH

SLAB/GRADE

B L D

G S

T E

E L

#6 AWG

GROUNDING

BUSBAR(S)

SEE DETAIL

MSB

N G

PROVIDE GROUND ROD AT

EACH CORNER OF ATS.

(4) TOTAL.

S E

E S

T R

U C

T U

R A

L D

E T

A

IL

S

ENGINEERING

P H&

POWELL & HINKLE ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FLORIDA 32073

(904) 264-5570 FAX:(904) 278-2646

ROBERT L. HINKLE

GALTON C. MOK

LANE R. HINKLE

THOMAS M. ELDER

RICHARD A. MATHEWS

PE 29302

PE 33192

PE 48076

PE 56121

PE 59418

DAVID R. SPELL JR. PE 54729

JAMES L. HENNESSEY PE 83241

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4

P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5

W. W. W. D A S H E R H U R S T . C O M

POWER RISER &

PANEL

SCHEDULES

22003

06.23.2023

C

O U

N T Y

R O

A D

G R

E E N

C O

V E S

P R

IN

G

S F L

E105

BID DOCUMENTS

C L A

Y C

O U

N

TY

C L A

Y C

O F

IR

E S

TA

TI

O N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

NTS

POWER RISER DIAGRAM

Notes:

Receptacle 39000 VA 62.82% 24500 VA

Power 204376 VA 100.00% 204376 VA

Other 58099 VA 100.00% 58099 VA

Lighting - Exterior 980 VA 125.00% 1225 VA Total Est. Demand Current: 850 A

Lighting - Dwelling Unit 192 VA 100.00% 192 VA Total Conn. Current: 895 A

Lighting 6944 VA 100.00% 6944 VA Total Est. Demand: 306402 VA

Electric Range - 3.5 kW to 8.75 kW 8000 VA 80.00% 6400 VA Total Conn. Load: 322268 VA

Electric Clothes Dryer 5000 VA 100.00% 5000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

H/N/G - Hot Wire, Neutral Wire, Ground Wire

Legend:

Total Amps: 895 A

Total Conn. Load: 322268 VA

11 PANEL P2 3 225 A 225 A 3-#300, 1-#300, 1-#4 59290 VA

10 PANEL PW 3 100 A 100 A 3-#3/0, 1-#3/0, 1-#6 27941 VA

9 AIR COMP 10HP 3 100 A 70 A 3-#4, 1-#4, 1-#8 11000 VA

8 Power DECON 160 3 100 A 40 A 3-#8, 1-#8, 1-#10 10000 VA

7 CU-6 2 100 A 50 A 2-#6, 1-#6, 1-#10 5600 VA

6 CU-3 2 100 A 60 A 2-#4, 1-#4, 1-#10 5800 VA

5 WH-1 3 225 A 125 A 3-#1/0, 1-#1/0, 1-#6 30000 VA

4 RTU-OA 3 100 A 70 A 3-#4, 1-#4, 1-#8 19599 VA

3 PANEL L 3 225 A 225 A 3-#300, 1-#300, 1-#4 9622 VA

2 PANEL P 3 225 A 225 A 3-#300, 1-#300, 1-#4 44780 VA

1 PANEL M 3 400 A 400 A 3-#750, 1-#750, 1-#3 98900 VA

CKT Circuit Description # of Poles Frame Size Trip Rating Wire Size H/N/G Load Remarks

Notes:

Enclosure: NEMA 1 MCB Rating: 1 A

Mounting: SURF Wires: 4 Mains Rating: 1000 A

Supply From: Phases: 3 Mains Type:

Location: ELEC 113 Volts: 120/208 Wye A.I.C. Rating: 42,000

MDP:

N.T.S.

SYSTEM GROUNDING DETAIL1

Notes:

Receptacle 26280 VA 69.03% 18140 VA Total Est. Demand Current: 97 A

Power 1900 VA 100.00% 1900 VA Total Conn. Current: 124 A

Other 3600 VA 100.00% 3600 VA Total Est. Demand: 35040 VA

Electric Range - 3.5 kW to 8.75 kW 8000 VA 80.00% 6400 VA Total Conn. Load: 44780 VA

Electric Clothes Dryer 5000 VA 100.00% 5000 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 116 A 154 A 106 A

Total Load: 13740 VA 18300 VA 12740 VA

41 0 VA 42

Electric Range - 3.5 kW to 8.75 kW 20 A 2

8000... 1200... 1 20 A Power MEETING 102 40

37 2280... 1 20 A Receptacle WATCH 108 38

35 Receptacle WATCH 108 20 A 1 360 VA 720 VA 1 20 A Receptacle WATCH 108 36

33 Receptacle CORR 104 20 A 1 600 VA 360 VA 1 20 A Receptacle CLOSET 103 34

31 Other 20 A 1 1080... 1080... 1 20 A Other 32

29 Receptacle 20 A 1 900 VA 900 VA 1 20 A Receptacle 30

27 Receptacle Room 101, 104, 105, 106 20 A 1 1180... 540 VA 1 20 A Receptacle Space 48 28

25 Space 48 20 A 1 1260... 720 VA 1 20 A Receptacle Room 110, 48 26

23 Receptacle Room 111, 112 20 A 1 1080... 540 VA 1 20 A Receptacle SCBA 157 24

21 Other Space 47 20 A 1 360 VA 1200... 1 20 A Receptacle CORR 119 22

19 Receptacle Space 47 20 A 1 1200... 180 VA 1 20 A Receptacle Space 47 20

17 RANGE HOOD 20 A 1 180 VA 720 VA 1 20 A Receptacle Space 47 18

15 Receptacle Space 47 20 A 1 1200... 180 VA 1 20 A Receptacle LOBBY 101 16

13 0 VA 1200... 1 20 A Receptacle Space 47 14

Electric Clothes Dryer LAUNDRY 122 40 A 2

5000... 1080... 1 20 A Space 46 12

9 Receptacle Room 126, 119 20 A 1 900 VA 1500... 1 20 A Receptacle LAUNDRY 122 10

7 Receptacle FITNESS 154 20 A 1 720 VA 1450... 1 20 A Receptacle CHIEF SUITE 128 8

5 Receptacle CORR 130 20 A 1 900 VA 360 VA 1 20 A Other FITNESS 154 6

3 Receptacle 20 A 1 180 VA 900 VA 1 20 A Receptacle CORR 130 4

1 Receptacle STOR 153 20 A 1 1260... 1310... 1 20 A Receptacle BUNK 12 150 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 1 A

Mounting: Recessed Wires: 4 Mains Rating: 225 A

Supply From: 48"x26.25", 120 V/208 V, Three... Phases: 3 Mains Type:

Location: Space 48 Volts: 120/208 Wye A.I.C. Rating: 22,000

Branch Panel: P

PANEL SCHEDULE NOTES:

1. PROVIDE ARC FLASH LABEL ON ALL PANELBOARDS. ALL BRANCH CIRCUIT CONDUCTORS SHALL

BE SIZED FOR LESS THAN 3% VOLTAGE DROP AT DESIGN LOAD. SEE ARC FLASH WARNING AND

BRANCH CIRCUIT CONDUCTOR DETAILS.

2. ATS MAIN BREAKER SHALL BE 100% RATED.

3. FROM SPD TO SPD DEVICE - KEEP CONDUCTOR LENGTHS TO A MINIMUM.

4. WIRE/BREAKER SIZES ARE FOR REFERENCE ONLY. PRIOR TO ROUGH-IN, FIELD VERIFY EXACT

EQUIPMENT SELECTION AND PROVIDE WIRE AND BREAKER SIZE & TYPE TO MATCH MECHANICAL

EQUIPMENT REQUIREMENTS.

5. CONNECT VIA LIGHTING CONTROL PANEL.

6. PROVIDE GFI TYPE BREAKER.

10. ALL CIRCUIT BREAKERS SERVING DRINKING WATER FOUNTAINS SHALL BE GFI TYPE (NEC 422.52).

11. ALL DIRECT CONNECTED APPLIANCES RATED OVER 0.3 KVA OR 1/8HP SHALL BE PROVIDED WITH

LOCK-OUT TYPE CIRCUIT BREAKER.

12. SHUNT TRIP TYPE CIRCUIT BREAKER & INTERLOCK WITH KITCHEN HOOD CONTROLS AS REQUIRED

BY APPLICABLE CODES.

13. PROVIDE ARC-FAULT TYPE (AFI) CIRCUIT BREAKERS FOR ALL BEDROOM RECEPTACLES AND

LIGHTING OUTLETS.

REVISIONS

# DATE DESCRIPTION

1 11/03/2023 Permit Rev 1

2 12/01/2023 Permit Rev 2

TYPICAL ARC FLASH LABEL DETAIL

NOT TO SCALE

WARNING

Arc Flash & Shock Hazard

Appropriate PPE Required

Flash Hazard Category

Min. Arc Rating

Flash Protection Boundary

Min. Arc Rating

Restricted Approach Boundary

Prohibited Approach Boundary

Cotton underwear

T-shirt

Long sleeve shirt

Long pants

FR Shirt

FR Pants

FR overall

Flash Suit

Flash Hood

Hard hat

Face shield

Ear Protection

Safety Glasses

Safety Goggles

Hard hat

Face shield

Ear Protection

Safety Glasses

Safety Goggles

FLASH PIPE SHOCK PPE

Class

V-rating

VAC Shock Hazard When

Equipment ID:

NOTES:

1. PROVIDE ELECTRICAL GEAR SUBMITTAL PACKAGE WITH ARCH FLASH CALCULATIONS FOR

ALL EQUIPMENT. EACH ITEM TO BEAR THE WARNING LABEL (AS SHOWN ABOVE) WITH ALL

APPROPRIATE INFORMATION INDICATED AS A RESULT OF THE ARC FLASH CALCULATION.

ENGINEERING

P H&

POWELL & HINKLE ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FLORIDA 32073

(904) 264-5570 FAX:(904) 278-2646

ROBERT L. HINKLE

GALTON C. MOK

LANE R. HINKLE

THOMAS M. ELDER

RICHARD A. MATHEWS

PE 29302

PE 33192

PE 48076

PE 56121

PE 59418

DAVID R. SPELL JR. PE 54729

JAMES L. HENNESSEY PE 83241

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4

P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5

W. W. W. D A S H E R H U R S T . C O M

PANEL

SCHEDULES

22003

06.23.2023

C

O U

N T Y

R O

A D

G R

E E N

C O

V E S

P R

IN

G

S F L

E106

BID DOCUMENTS

C L A

Y C

O U

N

TY

C L A

Y C

O F

IR

E S

TA

TI

O N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

Notes:

Power 1626 VA 100.00% 1626 VA Total Est. Demand Current: 27 A

Other 0 VA 0.00% 0 VA Total Conn. Current: 27 A

Lighting - Exterior 980 VA 125.00% 1225 VA Total Est. Demand: 9867 VA

Lighting - Dwelling Unit 128 VA 100.00% 128 VA Total Conn. Load: 9622 VA

Lighting 6944 VA 100.00% 6944 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 28 A 36 A 19 A

Total Load: 3226 VA 4151 VA 2245 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 Flagpole 20 A 1 100 VA 171 VA 18

15 171 VA

2 20 A Lights - Site Poles

13 171 VA 171 VA 14

Lights - Site Poles 20 A 2

171 VA 171 VA

2 20 A Lights - Site Poles

9 Lighting - Exterior 20 A 1 616 VA 500 VA 1 20 A Lights 10

7 Lights 20 A 1 48 VA 533 VA 1 20 A Lighting - Exterior 8

5 Lighting Space 48 20 A 1 888 VA 767 VA 1 20 A Lighting - Dwelling Unit 6

3 Lighting CORR 130 20 A 1 1500... 1388... 1 20 A Lighting ELEC 113 4

1 Lighting 20 A 1 1409... 907 VA 1 20 A Lighting 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 1 A

Mounting: Surface Wires: 4 Mains Rating: 100 A

Supply From: 48"x26.25", 120 V/208 V, Three... Phases: 3 Mains Type:

Location: Space 48 Volts: 120/208 Wye A.I.C. Rating: 22,000

Branch Panel: L

Notes:

Total Est. Demand Current: 161 A

Total Conn. Current: 165 A

Total Est. Demand: 58020 VA

Receptacle 12540 VA 89.87% 11270 VA Total Conn. Load: 59290 VA

Power 46750 VA 100.00% 46750 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 196 A 135 A 174 A

Total Load: 22860 VA 16160 VA 20270 VA

41 Receptacle 20 A 1 720 VA 1200... 1 20 A Receptacle WATCH 108 42

39 550 VA 1200... 1 20 A Power 40

Power LAUNDRY 122 20 A 2

550 VA 2000... 38

35 Receptacle APP BAY 161 20 A 1 180 VA 2000... 36

33 Receptacle DECON 160 20 A 1 180 VA 2000...

3 40 A VEHICLE EXHAUST SYS. 5HP

31 Power 20 A 1 1200... 500 VA 1 20 A Power 32

29 Power 20 A 1 460 VA 900 VA 1 20 A Receptacle Room 22, 157, 156 30

27 Disposal 20 A 1 1200... 900 VA 1 20 A Receptacle Room 110, 160 28

25 200 VA 1200... 1 20 A Receptacle - coffee 26

23 200 VA 360 VA 1 20 A Receptacle ROOF 24

ROLL UP DOOR 20 A 3

200 VA 180 VA 1 20 A Receptacle ROOF 22

19 200 VA 1200... 1 20 A Power 20

17 200 VA 1200... 1 20 A Power 18

ROLL UP DOOR 20 A 3

200 VA 1200... 1 20 A Power 16

13 200 VA 200 VA 14

11 200 VA 200 VA 12

ROLL UP DOOR 20 A 3

200 VA 200 VA

3 20 A ROLL UP DOOR

7 Power IT 114 20 A 1 500 VA 500 VA 1 20 A Power IT 114 8

5 Receptacle APP BAY 161 20 A 1 360 VA 180 VA 1 20 A Receptacle APP BAY 161 6

3 Receptacle APP BAY 161 20 A 1 900 VA 610 VA 1 20 A Receptacle SHOWER RM 123 4

1 Receptacle APP BAY 161 20 A 1 540 VA 540 VA 1 20 A Receptacle APP BAY 161 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 1 A

Mounting: Recessed Wires: 4 Mains Rating: 225 A

Supply From: 48"x26.25", 120 V/208 V, Three... Phases: 3 Mains Type:

Location: OFFICE 112 Volts: 120/208 Wye A.I.C. Rating: 22,000

Branch Panel: P2 PANEL SCHEDULE NOTES:

1. PROVIDE ARC FLASH LABEL ON ALL PANELBOARDS. ALL BRANCH CIRCUIT

CONDUCTORS SHALL

BE SIZED FOR LESS THAN 3% VOLTAGE DROP AT DESIGN LOAD. SEE ARC

FLASH WARNING AND

BRANCH CIRCUIT CONDUCTOR DETAILS.

2. MAIN BRAKER SHALL BE 100% RATED.

3. FROM SPD TO SPD DEVICE - KEEP CONDUCTOR LENGTHS TO A MINIMUM.

4. WIRE/BREAKER SIZES ARE FOR REFERENCE ONLY. PRIOR TO ROUGH-IN,

FIELD VERIFY EXACT EQUIPMENT SELECTION AND PROVIDE WIRE AND

BREAKER SIZE & TYPE TO MATCH MECHANICAL EQUIPMENT REQUIREMENTS.

5. CONNECT VIA LIGHTING CONTROL PANEL WITH PHOTOCELL/TIMESWITCH

CONTROL FOR EXTERIOR.

6. PROVIDE GFI TYPE BREAKER.

10. ALL CIRCUIT BREAKERS SERVING DRINKING WATER FOUNTAINS SHALL BE

GFI TYPE (NEC 422.52).

11. ALL DIRECT CONNECTED APPLIANCES RATED OVER 0.3 KVA OR 1/8HP

SHALL BE PROVIDED WITH LOCK-OUT TYPE CIRCUIT BREAKER.

12. SHUNT TRIP TYPE CIRCUIT BREAKER & INTERLOCK WITH KITCHEN HOOD

CONTROLS AS REQUIRED BY APPLICABLE CODES.

13. PROVIDE ARC-FAULT TYPE (AFI) CIRCUIT BREAKERS FOR ALL BEDROOM

RECEPTACLES AND LIGHTING OUTLETS PER CODE.

5 5

Notes:

Total Est. Demand Current: 78 A

Receptacle 180 VA 100.00% 180 VA Total Conn. Current: 78 A

Power 27700 VA 100.00% 27700 VA Total Est. Demand: 27941 VA

Other 0 VA 0.00% 0 VA Total Conn. Load: 27941 VA

Lighting - Dwelling Unit 64 VA 100.00% 64 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 86 A 84 A 67 A

Total Load: 10080 VA 9800 VA 8061 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 28

25 26

23 24

21 22

19 20

17 18

15 16

13 3000... 14

11 3000... 3000...

2 70 A Well, 5hp (basis of design, confirm)

Well. 5hp (basis of design, confirm) 70 A 2

3000... 3000... 10

7 2000... 3000...

2 70 A Well, 5hp (basis of design, confirm)

5 2000... 64 VA 1 20 A LIGHTS 6

JOCKEY PUMP, 5HP (basis of design, confirm) 40 A 3

2000... 1800... 4

1 recept, fan 20 A 1 280 VA 1800...

2 70 A FHP-WELL

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 100 A

Mounting: Recessed Wires: 4 Mains Rating: 100 A

Supply From: 48"x26.25", 120 V/208 V, Three... Phases: 3 Mains Type:

Location: Volts: 120/208 Wye A.I.C. Rating: 22,000

Branch Panel: PW

Notes:

Total Est. Demand Current: 275 A

Total Conn. Current: 275 A

Total Est. Demand: 98900 VA

Power 75400 VA 100.00% 75400 VA Total Conn. Load: 98900 VA

Other 23500 VA 100.00% 23500 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 241 A 308 A 287 A

Total Load: 28917 VA 36267 VA 33717 VA

41 2800... 2350... 42

CU-4 50 A 2

2800... 2350...

2 30 A CU-IT

37 EF-HOOD (1/3 HP) 15 A 1 300 VA 1200... 38

35 2600... 1200...

2 25 A CU-2

AHU-6 35 A 2

2600... 2100... 34

31 950 VA 2100...

2 40 A CU-1

CU-5/AHU-5 30 A 2

950 VA 2350... 30

27 2600... 2350...

2 30 A CU-FIT

AHU-3 35 A 2

2600... 2600... 26

23 2600... 2600...

2 35 A AHU-4

AHU-1 35 A 2

2600... 2600... 22

19 EF-1 (1/6 HP) 15 A 1 300 VA 2600...

2 35 A AHU-2

17 667 VA 667 VA 18

15 667 VA 667 VA 16

EF-2 (1.5HP) 15 A 3

667 VA 667 VA

3 15 A EF-3 (1.5HP)

11 3733... 3733... 12

9 3733... 3733... 10

UH-3 40 A 3

3733... 3733...

3 40 A UH-4

5 3733... 3733... 6

3 3733... 3733... 4

UH-1 40 A 3

3733... 3733...

3 40 A UH-2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 1 A

Mounting: Recessed Wires: 4 Mains Rating: 400 A

Supply From: 48"x26.25", 120 V/208 V, Three... Phases: 3 Mains Type:

Location: Space 48 Volts: 120/208 Wye A.I.C. Rating: 42,000

Branch Panel: M

REVISIONS

ENGINEERING

P H&

POWELL & HINKLE ENGINEERING, P.A.

1409 KINGSLEY AVENUE, BLDG 12A

ORANGE PARK, FLORIDA 32073

(904) 264-5570 FAX:(904) 278-2646

ROBERT L. HINKLE

GALTON C. MOK

LANE R. HINKLE

THOMAS M. ELDER

RICHARD A. MATHEWS

PE 29302

PE 33192

PE 48076

PE 56121

PE 59418

DAVID R. SPELL JR. PE 54729

JAMES L. HENNESSEY PE 83241

DATE:

PROJECT NO.:

THIS DRAWING IS AN INSTRUMENT OF SERVICE

AND IS THE PROPERTY OF DASHER HURST

ARCHITECTS, PA. IT SHALL NOT BE

REPRODUCED IN WHOLE OR IN PART WITHOUT

THE EXPRESS WRITTEN PERMISSION OF DASHER

HURST ARCHITECTS, PA.

DASHER HURST

1 0 2 2 P A R K S T R E E T , S U I T E 2 0 8

A R C H I T E C T S

J A C K S O N V I L L E , F L O R I D A 3 2 2 0 4

P H O N E : 9 0 4 . 4 2 5 . 1 1 9 0

F L L I C E N S E N U M B E R A A 2 6 0 0 2 1 6 5

W. W. W. D A S H E R H U R S T . C O M

PANEL

SCHEDULES

22003

06.23.2023

C

O U

N T Y

R O

A D

G R

E E N

C O

V E S

P R

IN

G

S F L

E107

BID DOCUMENTS

C L A

Y C

O U

N

TY

C L A

Y C

O F

IR

E S

TA

TI

O N

STRUCTURAL ENGINEER

G.M. HILL ENGINEERING,

INC.

9700 PHILIPS HWY, SUITE 101

JACKSONVILLE, FL 32256

Notes:

Total Est. Demand Current: 88 A

Total Conn. Current: 88 A

Total Est. Demand: 31680 VA

Receptacle 2280 VA 100.00% 2280 VA Total Conn. Load: 31680 VA

Power 29400 VA 100.00% 29400 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 118 A 54 A 106 A

Total Load: 13330 VA 6440 VA 11910 VA

41 42

39 40

37 38

35 36

33 34

31 32

29 30

27 750 VA 28

FHP DECON 160 15 A 2

750 VA 1500... 26

23 1500... 1500...

2 20 A FHP MAINT 152

FHP STOR 153 20 A 2

1500... 600 VA 22

19 5500... 600 VA

2 20 A Power

Power APP BAY 161 90 A 2

5500... 650 VA 18

15 Receptacle APP BAY 161 20 A 1 180 VA 650 VA

2 20 A EXTRACTOR

13 REC - PARKING POLE 20 A 1 180 VA 0 VA 1 20 A PUMP POWER 14

11 REC - PARKING POLE 20 A 1 180 VA 180 VA 1 20 A REC - PARKING POLE 12

9 REC - PARKING POLE 20 A 1 180 VA 180 VA 1 20 A REC - PARKING POLE 10

7 CORD REEL 20 A 1 1200... 1200... 1 20 A CORD REEL 8

5 CORD REEL 20 A 1 1200... 1200... 1 20 A CORD REEL 6

3 CORD REEL 20 A 1 1200... 1200... 1 20 A Receptacle - Decon Dryer 4

1 CORD REEL 20 A 1 1200... 1200... 1 20 A CORD REEL 2

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: Type 1 MCB Rating: 1 A

Mounting: Recessed Wires: 4 Mains Rating: 225 A

Supply From: P2 Phases: 3 Mains Type:

Location: OFFICE 112 Volts: 120/208 Wye A.I.C. Rating: 22,000

Branch Panel: P3

ADDED SHEET.

PANEL SCHEDULE NOTES:

1. PROVIDE ARC FLASH LABEL ON ALL PANELBOARDS. ALL BRANCH CIRCUIT

CONDUCTORS SHALL

BE SIZED FOR LESS THAN 3% VOLTAGE DROP AT DESIGN LOAD. SEE ARC

FLASH WARNING AND

BRANCH CIRCUIT CONDUCTOR DETAILS.

2. MAIN BRAKER SHALL BE 100% RATED.

3. FROM SPD TO SPD DEVICE - KEEP CONDUCTOR LENGTHS TO A MINIMUM.

4. WIRE/BREAKER SIZES ARE FOR REFERENCE ONLY. PRIOR TO ROUGH-IN,

FIELD VERIFY EXACT EQUIPMENT SELECTION AND PROVIDE WIRE AND

BREAKER SIZE & TYPE TO MATCH MECHANICAL EQUIPMENT REQUIREMENTS.

5. CONNECT VIA LIGHTING CONTROL PANEL WITH PHOTOCELL/TIMESWITCH

CONTROL FOR EXTERIOR.

6. PROVIDE GFI TYPE BREAKER.

10. ALL CIRCUIT BREAKERS SERVING DRINKING WATER FOUNTAINS SHALL BE

GFI TYPE (NEC 422.52).

11. ALL DIRECT CONNECTED APPLIANCES RATED OVER 0.3 KVA OR 1/8HP

SHALL BE PROVIDED WITH LOCK-OUT TYPE CIRCUIT BREAKER.

12. SHUNT TRIP TYPE CIRCUIT BREAKER & INTERLOCK WITH KITCHEN HOOD

CONTROLS AS REQUIRED BY APPLICABLE CODES.

13. PROVIDE ARC-FAULT TYPE (AFI) CIRCUIT BREAKERS FOR ALL BEDROOM

RECEPTACLES AND LIGHTING OUTLETS PER CODE.

5 5

REVISIONS

# DATE DESCRIPTION

1 11/03/2023 Permit Rev 1

SPRINKLED BUILDING

MOUNTED

ABOVE FACP

(2) TELE LINES

TO SECURITY PNL

DEDICATED 120V CKT

ANNUNCIATOR

FIRE ALARM

CONTROL

PANEL

(FACP)

FA FIRE ALARM

FA- PULL STATION WALL MTD

FA- HORN/STROBE WALL MTD

FIRE ALARM A-0 CRITERIA:

(A) THE PLANS SHALL BE CLEAR, WITH A SYMBOLS LEGEND, SYSTEM RISER DIAGRAM

SHOWING ALL INITIATION AND NOTIFICATION COMPONENTS, AND CABLING REQUIREMENTS.

INDICATE LOCATIONS WHERE FIRE RATINGS ARE REQUIRED AS DETERMINED BY THE

SYSTEM'S SURVIVABILITY REQUIREMENTS. IDENTIFY THE GENERAL OCCUPANCY OF THE

PROTECTED PROPERTY, AND FOR EACH ROOM AND AREA UNLESS IT IS CLEAR FROM

FEATURES SHOWN.

- OCCUPANCY TYPE IS MIXED OCCUPANCY/STORAGE/RESIDENTIAL ASSEMBLY- FULLY SPRINKLERED

(B) LOCATE INITIATION AND NOTIFICATION DEVICES AND CONNECTIONS TO RELATED

SYSTEMS ON THE FLOOR PLANS AND SECTIONS WHEN NEEDED FOR CLARITY. RELATED

SYSTEMS INCLUDE ELEVATOR CONTROLS SMOKE CONTROL SYSTEMS, DAMPERS, AND

DOORS.

- NO…