Base-Sheet-Fastener-7-Inch.pdf
PDF 117 KB Posted
- Attached to
- High School Roof Replacement
- Solicitation number
- RFP MASO 260000002613 2
- Issued by
- Genesee County, Edmore Village, Michigan
About this file
This is a technical drawing specification document for roof base sheet fastener placement on a built-up roofing system constructed over lightweight concrete decking. The document provides detailed installation requirements for securing Tremco-specified base sheets to roof decking using approved fasteners and plates. The fastener spacing requirements specify 7-inch on-center spacing along sidelaps and within two equally staggered rows positioned 12 inches from each edge along the longitudinal center of the sheet. Perimeter edge fastening must be increased by 70 percent and corner fastening by 160 percent in accordance with FM Global Loss Prevention Data Sheets 1-28 and 1-29. The specification establishes a minimum fastener spacing of 4 inches on center and requires fastener density determination on a unit area basis, with provisions for adding additional rows and increasing fasteners per row as needed to meet performance requirements.
The document does not contain information regarding pricing, contract terms, award dates, response deadlines, set-asides, or funding sources. This specification serves as a technical control document for construction quality assurance and installation standardization rather than as a procurement or bidding document.
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DWG NO. 15
NOTES
1. ATTACH BASE SHEET TO THE ROOF DECKING WITH APPROVED FASTENERS AND DISCS.
2. SPACE FASTENERS 7 INCHES ON CENTER ALONG SIDELAP AND 7 INCHES ON CENTER IN TWO ROWS
EQUALLY STAGGERED DOWN THE LONGITUDINAL CENTER OF THE SHEET (12 INCHES FROM EACH
EDGE).
3. INCREASE PERIMETER EDGE FASTENING BY 70% AND CORNER FASTENING BY 160% PER FM GLOBAL
LOSS PREVENTION DATA SHEETS 1-28 AND 1-29.
4. DETERMINE FASTENER DENSITY ON A UNIT AREA PER FASTENER BASIS. ADD ADDITIONAL ROWS AND INCREASE FASTENERS PER ROW. DO NOT SPACE FASTENERS CLOSER THAN 4 INCHES ON CENTER.
BUILT-UP ROOFING
HOT/COLD BASE SHEET FASTENER
PLACEMENT FOR LIGHTWEIGHT
CONCRETE
SPECIFIED TREMCO
BASE SHEET
SPECIFIED SEPARATOR
LIGHTWEIGHT CONCRETE
SPECIFIED TREMCO
FASTENER AND PLATE
SHEET TITLE:
DRAWING No.:
SCALE:
NTS
AutoCAD SHX Text
BASE SHEET WIDTH
AutoCAD SHX Text 4"
AutoCAD SHX Text 7"
AutoCAD SHX Text 7"
AutoCAD SHX Text 12"
| Sheets and Views |
| Model |
File details come from the government source that posted it. Updated .