Attachment 6 - 589A6-21-700 LEHRM IFC_R1 B88-89-90-91 Part 3 of 3 Drawing.pdf
PDF 8 MB Posted
- Solicitation number
- 36C77622R0061
About this file
This is a solicitation for a telecommunications infrastructure upgrade project at the Leavenworth VA Medical Center campus. The scope of work includes replacing all telecommunications cabling, outlets, and equipment across multiple buildings to support an Electronic Health Record Modernization initiative. Key requirements include installing CAT6a cabling and fiber optic cabling with at least 15% additional capacity. The contractor must also provide new patch panels, cable trays, racks, and related infrastructure in telecommunications rooms to terminate and support all new cabling. Wireless access points will be reused and recabled. Existing conduit and pathways must be protected where possible. The project also involves adding new HVAC systems and electrical infrastructure to support the telecommunications upgrades. The solicitation is issued by the Department of Veterans Affairs Technology Acquisition Center in Austin.
View the file
Other files
Show 40 more
Latest 50 of 67 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
DN
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
STAIR 3
C1-S3
RESTROOM
C127B
SECURITY
C127A
EMPLOYEE GYM
C127D
BIO-MED
C127E
BIO-MED
C127F
BIO-MED
C127G
CLOSET
C141
HOUSEKEEPING
C157
OFFICE
C137
STAFF ONLY RESTROOM
C143
SUPPLY ROOM
C138
RELEASE OF INFORMATION
C136
CONFERENCE ROOM
C148
STORAGE
C154
SOCIAL WORKER
C152
SOCIAL WORK SERVICE
C155
STORAGE
C153
COMP & PEN EXAM ROOM
C146
COMP & PEN EXAM ROOM
C144
SOCIAL WORKER
C147MSA SUPERVISOR
C156
PATIENT ELIGIBILITY
C134
PATIENT REPRESENTATIVE
C132
OEF/OIF/OND CASE MGR.
C145
SOCIAL WORKER
C149
COMP & PEN EXAM ROOM
C151
COMP & PEN EXAM ROOM
C139
ELIGIBILITY
C516
STAFF ONLY RESTROOM
C133A
RHIT CHIEF HEALTH ADMIN
C140
SOCIAL WORKER
C142
MECHANICAL STORAGE
C-A
GENERATOR ROOM
C-B
CORRIDOR
C1-C3
IT CLOSET
C127C
CHASE
C139A
CHASE
C533
CHASE
C534
DIRECTOR'S OFFICE
C127H
Room
C127J
C152-A
152-AP-A
C
-AC150-B
C150-A
C1-C3-AP-A
C142-AP-A
C146-A
C146-B
C146-C
C144-A
C144-B
C144-C
C142-A
C1-C3-AP-B
C132-AP-A
C140-A
C140-B
C140-C
C136-A
C136-B
C134-A
C134-B
C132-A
C156-A
C145-AP-A
C155-A
C155-B
C153-B
C153-A C151-A
C149-C
C149-B C149-A
C147-C
C147-B
C147-A C145-B
C145-A
C -S
-A
P -A
C137-AP-A
C141-A
C137-A
C127G-AP-A
C127D-AP-A
C127G-A
C D
-A
C D
-B
C127D-C
C A
-A
C A
-B
C A
-C
C H
-A
C127H-B
C H
-C
C H
-D
C H
-E
C127H-AP-A
TYP.
91E-414
F1
UPS ROOM
C-C
91E-414
C1
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
AREA
91-A
B
IM
/5
A
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.8 .9
.9
.M
E P
.r v t
/1
/2
:3
:3
A
M
91T-101A
TELECOMMUNICATION PLANS - FIRST LEVEL -
B91A
589A6-21-700
B88/89/90/91
01/19/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
1/8" = 1'-0" F3
TELECOMMUNICATION PLAN - FIRST LEVEL - B91A
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,
FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL
OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL
NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &
NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END
WARRANTEED SOLUTION FOR THE CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.
E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR
EXCEED CATEGORY 6A STANDARDS.
F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN
WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.
UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR
PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A
MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR
TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE
TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF
EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE
TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL
PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE
EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE
REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH
EXISTING CONDUIT CAPACITY.
H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO
PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE
OR JUNCTION BOX.
I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.
J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW
EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE
TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.
K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING
BACK TO THE RACK.
L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL
STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL
INFORMATION
M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL
TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE
DOCUMENTS. HANG ON THE WALL WITHIN THE TELECOM ROOM.
N. REFER TO T-600 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING
CONDITIONS.
1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH
EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS
ON SHEET T-501 FOR ADDITIONAL INFORMATION.
2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE NEW
CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON SHEET
T-501 FOR ADDITIONAL INFORMATION.
3. PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS
AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE
SPECIFICATIONS. PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION AND
TRANSFER DATA CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK.
PROVIDE TEMPORARY EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES
AND OTHER DEVICES TO ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING
DATA CIRCUITS ARE RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND
ALL EXISTING DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK,
REMOVE THE EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL
PERMANENT POSITION.
4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY
PROTECTED IN PLACE. ALL EXISTING DEVICES ON THE EXISTING RACK SHALL BE
TRANSFERRED TO THE NEW SECOND LEVEL LOCATION ON THE NEW RACK.
CONTRACTOR SHALL PROVIDE SHOP DRAWINGS SHOWING THE PROPOSED NEW
RACK ELEVATION AND PROVIDE A PHASING PLAN FOR TRANSFERRING ALL
EXISTING DEVICES TO REMAIN TO THE NEW RACKS.
6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY
SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT
COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK.
COORDINATE FIXTURES WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD
CABLE TRAY.
7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION SENSOR,
AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET XNP-6320.
MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE CAMERA INTO
EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT NETWORK.
8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.
9. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR
HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH
ENDS TO PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.
10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS
INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE
AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN
FOR TRANSFERRING FIBER.
11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.
12. EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH
EXISTING FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE
OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR
TRANSFERRING FIBER.
13. PROVIDE NEW iSTAR EDGE (ESTAR002) ACCESS CONTROL SYSTEM. INSTALL PER
MANUFACTURERS RECOMMENDATIONS.
14. ALL EXISTING ANALOG PHONE CABLE DEVICES AND TERMINATIONS ETC. SHALL
REMAIN OPERATIONAL AT ALL TIMES AND SHALL BE RETAINED AND REUSED.
PROTECT IN PLACE.
15. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.
16. EXISTING EQUIPMENT TO BE DEMOLISHED.
17. VERTICAL ROUTE FOR TELECOM RISER. ALL FLOOR PENETRATIONS TO MAINTAIN
FIRE RATING.
18. PROVIDE NEW SERVER RACK AS SHOWN ON T-500/ T-600 SERIES SHEETS AND THE
SPECIFICATIONS. CONSOLIDATE EXISTING DEVICES AND REINSTALL IN NEW
CABINET.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
Revisions: Date:
/19
/20
1/19/2022
UP
DN
WAP
WAP
WAP
WAP
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
HOUSEKEEPING
C121
MECHANICAL
C135
TELECOM ROOM
C128
COMPENSATION & PENSION
C130
OFFICE
C137
PATIENT REPRESENTATIVE
C132
TRAVEL UNIT
C125A
AGENT CASHIER
C125
STORAGE
B104C
MVP RESEARCH ASSIST.
B104B
OFFICE
B104E
RESEARCH
B104D
STAFF ONLY RESTROOM
C133A
TELEPHONE SWITCHBOARD
C133
WOMEN'S RESTROOM
C129A
VESTIBULE
C129
EAST ENTRY VESTIBULE
C100A
CORRIDOR
C1-C5
MEN'S RESTROOM
C129B
MECHANICAL
C107B
EMERGENCY GENERATOR
C107A
STAIR 1
C1-S1
CORRIDOR
C127
TELECOM ROOM
B106A
CHASE
C529
CHASE
C530
CHASE
C531
CHASE
C532
CORRIDOR
C1-C6
ELEV 3
C1-E3
ELEV 4
C1-E4
ELEV 2
C1-E2
C132-AP-A
C132-A
C137-AP-A
C137-A
C130-A
C1-C5-A
C1-C5-AP-A
C133-AP-A
C133-A
C -B
C -C
C133-D
C133-E
C -F
C127-AP-A
C A
-A
B106A-AP-B
B104B-AP-A
B104B-A B104C-A
B B
-C
B104E-AP-A
B D
-A
B E
-C
B E
-B
B104E-A
C120A-A
C123-AP-A
M104-A
M104-B
M130-E M130-A
M130-B
M130-C M130-D
M -A
C122-B
C122-A
C123B-B
C123B-A
C123C-B
C123C-A
C123D-B
C123D-A
C -B
C -A
C -B
C124-A
C119A-A
C113-A
C1-C1-AP-A
C1-S2-AP-A
C -A
C -B
C118-C C116-B
C -A
C -A
C -B
C114-C
C112-A
C112-B
C -A
C106A-A
C106A-B
C1-C2-AP-A
C A
-A
C A
-B
C B
-A
C100B-AP-A
C102A-A C102A-B
C102A-C
C102B-A
C102B-B
C B
-C
C102B-AP-A
C103-AP-A
C -F
C -G
C -H
C -J
C -K
C -B
C103-C
C103-D
C103-E
C -A
C -A
CLOSET
C115
VEST
C100B
TRTMT #5 (FEMALE)
C106A
TLT/SHWR
C120B
TLT
C106B
ANTE
C104C
TRTMT #6 (ISO)
C104A
CORR.
C1-C2
TLT
C108
CLEAN STERILE
C110
NURSE MANAGER
C112
TRTMT #3
C114
TRTMT #2
C116
TRTMT #1
C118
ON-CALL ROOM
C120A
NOURISH
C109
DECON
C104B
CORR.
C1-C1
HAC
C101
TRAUMA #1
C102A
TRAUMA #2
C102B
NURSE
C103
MECHANICAL RM
C107C
TRTMT #4 (SECLUSION)
C105
SOILED UTILITY
C107STAIR 2
C1-S2
TLT
C111
EQUIP RM
C113
STAFF LOUNGE & LOCKERS
C119A
STAFF TLT
C119B
CONSULT/ BEREAVEMENT
C124
TRIAGE
C117
BUSINESS OFFICE
C122
AOD
C123B
AOD
C123C
AOD
C123D
CORR.
C1-C0
WAITING
C123
CLERK
M101
MRI LOBBY
M100
TLT/ DRESS
M102
CONTROL
M103
EQUIP
M104
MRI
M105
91T-101B
F1 91T-101B
C1
TYP.
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
TELECOM ROOM
C128
118 SF
TYP.
TYP.
TYP.
TYP.
C128-CAM-1
TYP.
TELECOM ROOM
C128
118 SF
TYP.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
AREA
91-B
B
IM
/5
A
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.8 .9
.9
.M
E P
.r v t
/1
/2
:3
:3
A
M
91T-101B
TELECOMMUNICATION PLANS - FIRST LEVEL -
B91B
589A6-21-700
B88/89/90/91
01/19/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
1/8" = 1'-0" F2
TELECOMMUNICATION PLAN - FIRST LEVEL - B91B
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,
FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL
OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL
NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &
NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END
WARRANTEED SOLUTION FOR THE CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.
E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR
EXCEED CATEGORY 6A STANDARDS.
F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN
WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.
UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR
PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A
MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR
TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE
TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF
EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE
TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL
PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE
EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE
REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH
EXISTING CONDUIT CAPACITY.
H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO
PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE
OR JUNCTION BOX.
I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.
J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW
EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE
TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.
K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING
BACK TO THE RACK.
L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL
STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL
INFORMATION
M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL
TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE
DOCUMENTS. HANG ON THE WALL WITHIN THE TELECOM ROOM.
N. REFER TO T-600 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING
CONDITIONS.
1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH
EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS
ON SHEET T-501 FOR ADDITIONAL INFORMATION.
2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE NEW
CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON SHEET
T-501 FOR ADDITIONAL INFORMATION.
3. PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS
AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE
SPECIFICATIONS. PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION AND
TRANSFER DATA CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK.
PROVIDE TEMPORARY EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES
AND OTHER DEVICES TO ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING
DATA CIRCUITS ARE RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND
ALL EXISTING DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK,
REMOVE THE EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL
PERMANENT POSITION.
4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY
PROTECTED IN PLACE. ALL EXISTING DEVICES ON THE EXISTING RACK SHALL BE
TRANSFERRED TO THE NEW SECOND LEVEL LOCATION ON THE NEW RACK.
CONTRACTOR SHALL PROVIDE SHOP DRAWINGS SHOWING THE PROPOSED NEW
RACK ELEVATION AND PROVIDE A PHASING PLAN FOR TRANSFERRING ALL
EXISTING DEVICES TO REMAIN TO THE NEW RACKS.
6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY
SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT
COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK.
COORDINATE FIXTURES WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD
CABLE TRAY.
7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION SENSOR,
AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET XNP-6320.
MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE CAMERA INTO
EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT NETWORK.
8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.
9. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR
HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH
ENDS TO PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.
10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS
INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE
AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN
FOR TRANSFERRING FIBER.
11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.
12. EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH
EXISTING FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE
OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR
TRANSFERRING FIBER.
13. PROVIDE NEW iSTAR EDGE (ESTAR002) ACCESS CONTROL SYSTEM. INSTALL PER
MANUFACTURERS RECOMMENDATIONS.
14. ALL EXISTING ANALOG PHONE CABLE DEVICES AND TERMINATIONS ETC. SHALL
REMAIN OPERATIONAL AT ALL TIMES AND SHALL BE RETAINED AND REUSED.
PROTECT IN PLACE.
15. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.
16. EXISTING EQUIPMENT TO BE DEMOLISHED.
17. VERTICAL ROUTE FOR TELECOM RISER. ALL FLOOR PENETRATIONS TO MAINTAIN
FIRE RATING.
18. PROVIDE NEW SERVER RACK AS SHOWN ON T-500/ T-600 SERIES SHEETS AND THE
SPECIFICATIONS. CONSOLIDATE EXISTING DEVICES AND REINSTALL IN NEW
CABINET.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
SCALE: 1/2" = 1'-0"
F1
TELECOMMUNICATION ENLARGED
PLAN - FIRST LEVEL - ROOM C128 -
NEW
SCALE: 1/2" = 1'-0"
C1
TELECOMMUNICATION ENLARGED
PLAN - FIRST LEVEL - ROOM C128 -
DEMO
Revisions: Date:
/19
/20
UP
WAP
WAP
WAP
WAP
WAP
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
C -A
C -B
C -C
C -D
C -E
C -F
C -G
C241-AP-A
C241-B
C241-C
C241-D
C241-E
C -F
C -A
C -A
C239-B
C239-C
C239-D
C239-E
C239-F
C239-G
C237-AP-A
C237-A
C237-B
C -C
C2-C3-AP-A
C -C
-A
C -C
-B
C242A-AP-A
C242A-A
C -M
C -L
C -K
C -J
C -H
C -G C
-F
C -E
C -D
C -C
C -B
C -A
C -N
C -O
C242-P
C242-Q
C242-R
C242-S
C -T
C -U
C -V
C242B-A
C B
-B
C240-AP-A
NO DATA
NO DATA
C -A
C -B
C -C
C236-AP-A
NO DATA NO DATA
C -A
C230-B
NO DATA
NO DATA
NO
DATA
C229-A
C229-B
PATIENT ROOM 1
C244
PATIENT ROOM 4
C237
PATIENT ROOM 5
C235
ANTE
C233
PATIENT ROOM 2
C241
NURSES' STATION
C242
STORAGE
C238
STAFF WOMEN'S
C234
STAFF LOUNGE
C236
STAFF MEN'S
C232
EMERGENCY SHOWER
C240A
SOILED UTILITY
C240
LINEN/ CLEAN SUPPLY
C230
MECHANICAL
C229
MECHANICAL
C227
MECHANICAL
C225
PATIENT ROOM 3
C239
PATIENT ROOM 6
C231
STAIR 3
C2-S3
CORRIDOR
C2-C3
MEDICATION
C242A
MEDICATION
C242B
TYP.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
AREA
91-A
B
IM
/5
A
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.8 .9
.9
.M
E P
.r v t
/1
/2
:3
:4
A
M
91T-102A
TELECOMMUNICATION PLANS - SECOND LEVEL -
B91A
589A6-21-700
B88/89/90/91
01/19/2022 M. Perkins K. Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,
FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL
OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL
NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &
NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END
WARRANTEED SOLUTION FOR THE CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.
E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR
EXCEED CATEGORY 6A STANDARDS.
F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN
WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.
UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR
PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A
MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR
TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE
TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF
EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE
TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL
PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE
EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE
REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH
EXISTING CONDUIT CAPACITY.
H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO
PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE
OR JUNCTION BOX.
I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.
J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW
EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE
TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.
K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING
BACK TO THE RACK.
L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL
STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL
INFORMATION
M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL
TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE
DOCUMENTS. HANG ON THE WALL WITHIN THE TELECOM ROOM.
N. REFER TO T-600 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING
CONDITIONS.
1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH
EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS
ON SHEET T-501 FOR ADDITIONAL INFORMATION.
2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE NEW
CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON SHEET
T-501 FOR ADDITIONAL INFORMATION.
3. PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS
AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE
SPECIFICATIONS. PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION AND
TRANSFER DATA CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK.
PROVIDE TEMPORARY EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES
AND OTHER DEVICES TO ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING
DATA CIRCUITS ARE RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND
ALL EXISTING DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK,
REMOVE THE EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL
PERMANENT POSITION.
4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY
PROTECTED IN PLACE. ALL EXISTING DEVICES ON THE EXISTING RACK SHALL BE
TRANSFERRED TO THE NEW SECOND LEVEL LOCATION ON THE NEW RACK.
CONTRACTOR SHALL PROVIDE SHOP DRAWINGS SHOWING THE PROPOSED NEW
RACK ELEVATION AND PROVIDE A PHASING PLAN FOR TRANSFERRING ALL
EXISTING DEVICES TO REMAIN TO THE NEW RACKS.
6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY
SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT
COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK.
COORDINATE FIXTURES WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD
CABLE TRAY.
7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION SENSOR,
AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET XNP-6320.
MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE CAMERA INTO
EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT NETWORK.
8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.
9. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR
HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH
ENDS TO PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.
10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS
INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE
AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN
FOR TRANSFERRING FIBER.
11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.
12. EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH
EXISTING FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE
OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR
TRANSFERRING FIBER.
13. PROVIDE NEW iSTAR EDGE (ESTAR002) ACCESS CONTROL SYSTEM. INSTALL PER
MANUFACTURERS RECOMMENDATIONS.
14. ALL EXISTING ANALOG PHONE CABLE DEVICES AND TERMINATIONS ETC. SHALL
REMAIN OPERATIONAL AT ALL TIMES AND SHALL BE RETAINED AND REUSED.
PROTECT IN PLACE.
15. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.
16. EXISTING EQUIPMENT TO BE DEMOLISHED.
17. VERTICAL ROUTE FOR TELECOM RISER. ALL FLOOR PENETRATIONS TO MAINTAIN
FIRE RATING.
18. PROVIDE NEW SERVER RACK AS SHOWN ON T-500/ T-600 SERIES SHEETS AND THE
SPECIFICATIONS. CONSOLIDATE EXISTING DEVICES AND REINSTALL IN NEW
CABINET.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
SCALE: 1/8" = 1'-0"
F3
TELECOMMUNICATION PLAN -
SECOND LEVEL - B91A
Revisions: Date:
/19
/20
WAP
WAP
WAP WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
C228-AP-A
C -A
C230-B
NO DATA NO DATA
C2-C2-AP-A
NO DATA
NO DATA
C2-C2-AP-B C2-C2-AP-C
C217-AP-A
C217-B
C -A
NO DATA
NO DATA
NO DATA
N O
D A
T A
NO DATA
NO DATA
C222-AP-A
C222-A
C222-B
C220-A
C220-B
C -A
C216-B
C -C
C216-D
C216-AP-A
C214-A
C213-A
C213-B
C211-AP-A
C211-A
C211-B
C209-B
C209-C
C209-A
C209-D C207-A
C207-B NO DATA
NO DATA
C205-B
C205-A
C205-AP-A
C206-AP-A
C -A
C212-B
C212-C
C212-D
C208-B
C208-A
C206-B
C206-A
C200-AP-A
C -B C
-A
C202-B
C202-C
C200-A
C200-B
C -C
C201-A
C202-A
B2-C4-AP-A
TELECOM ROOM
C228
91T-102B
F1
MEN'S RESTROOM
C223
PHYSICIANS ASSISTANT
C213
MECHANICAL
C218
CHAPLAIN'S OFFICE
C220
MANAGER'S OFFICE
C222
HOUSEKEEPING
C224
MECHANICAL
C226
WAITING
C217
CONF. REPORT ROOM
C216
G.I. OFFICE
C211
PRE-OP
C207
RESTROOM
C209A
SLEEP ROOM
C209
PRE-OP
C205
STORAGE
C203
G.I. ROOM
C200
CLEAN UTILITY
C202
DIRTY UTILITY
C204
G.I. STAFF LOUNGE
C201
POST-OP
C206
POST-OP
C208
RESTROOM
C210
NURSE STATION
C212
STORAGE
C214
CONFERENCE
B204
DEPUTY CHIEF OF STAFF
B206A
RESPIRATORY STORAGE
C215
IT CLOSET
C225A
CORRIDOR
C2-C4
STAIR 1
C2-S1
STAIR 2
C2-S2
CORRIDOR
C2-C1
CORRIDOR
C2-C2
WOMEN'S RESTROOM
C219
ELEV 2
C2-E2
ELEV 3
C2-E3
ELEV 4
C2-E4
CHASE
C223P
91T-102B
C1
TYP.
TELECOM ROOM
C228
136 SF
C228-CAM-01
TYP.
TYP.
TYP.
TYP.
TYP.
C228-AP-A
EQUIPMENT
STORAGE
C228
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
AREA
91-B
B
IM
/5
A
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.8 .9
.9
.M
E P
.r v t
/1
/2
:3
:5
A
M
91T-102B
TELECOMMUNICATION PLANS - SECOND LEVEL -
B91B
589A6-21-700
B88/89/90/91
01/19/2022 M. Perkins K. Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,
FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL
OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL
NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &
NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END
WARRANTEED SOLUTION FOR THE CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.
E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR
EXCEED CATEGORY 6A STANDARDS.
F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN
WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.
UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR
PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A
MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR
TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE
TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF
EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE
TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL
PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE
EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE
REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH
EXISTING CONDUIT CAPACITY.
H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO
PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE
OR JUNCTION BOX.
I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.
J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW
EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE
TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.
K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING
BACK TO THE RACK.
L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL
STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL
INFORMATION
M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL
TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE
DOCUMENTS. HANG ON THE WALL WITHIN THE TELECOM ROOM.
N. REFER TO T-600 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING
CONDITIONS.
1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH
EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS
ON SHEET T-501 FOR ADDITIONAL INFORMATION.
2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE NEW
CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON SHEET
T-501 FOR ADDITIONAL INFORMATION.
3. PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS
AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE
SPECIFICATIONS. PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION AND
TRANSFER DATA CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK.
PROVIDE TEMPORARY EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES
AND OTHER DEVICES TO ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING
DATA CIRCUITS ARE RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND
ALL EXISTING DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK,
REMOVE THE EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL
PERMANENT POSITION.
4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY
PROTECTED IN PLACE. ALL EXISTING DEVICES ON THE EXISTING RACK SHALL BE
TRANSFERRED TO THE NEW SECOND LEVEL LOCATION ON THE NEW RACK.
CONTRACTOR SHALL PROVIDE SHOP DRAWINGS SHOWING THE PROPOSED NEW
RACK ELEVATION AND PROVIDE A PHASING PLAN FOR TRANSFERRING ALL
EXISTING DEVICES TO REMAIN TO THE NEW RACKS.
6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY
SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT
COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK.
COORDINATE FIXTURES WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD
CABLE TRAY.
7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION SENSOR,
AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET XNP-6320.
MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE CAMERA INTO
EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT NETWORK.
8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.
9. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR
HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH
ENDS TO PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.
10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS
INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE
AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN
FOR TRANSFERRING FIBER.
11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.
12. EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH
EXISTING FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE
OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR
TRANSFERRING FIBER.
13. PROVIDE NEW iSTAR EDGE (ESTAR002) ACCESS CONTROL SYSTEM. INSTALL PER
MANUFACTURERS RECOMMENDATIONS.
14. ALL EXISTING ANALOG PHONE CABLE DEVICES AND TERMINATIONS ETC. SHALL
REMAIN OPERATIONAL AT ALL TIMES AND SHALL BE RETAINED AND REUSED.
PROTECT IN PLACE.
15. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.
16. EXISTING EQUIPMENT TO BE DEMOLISHED.
17. VERTICAL ROUTE FOR TELECOM RISER. ALL FLOOR PENETRATIONS TO MAINTAIN
FIRE RATING.
18. PROVIDE NEW SERVER RACK AS SHOWN ON T-500/ T-600 SERIES SHEETS AND THE
SPECIFICATIONS. CONSOLIDATE EXISTING DEVICES AND REINSTALL IN NEW
CABINET.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
SCALE: 1/8" = 1'-0"
F2
TELECOMMUNICATION PLAN -
SECOND LEVEL - B91B
SCALE: 1/2" = 1'-0"
F1
TELECOMMUNICATION ENLARGED
PLAN - SECOND LEVEL - ROOM C228 -
NEW
SCALE: 1/2" = 1'-0"
C1
TELECOMMUNICATION ENLARGED
PLAN - SECOND LEVEL - ROOM C228 -
DEMO
Revisions: Date:
/19
/20
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
C301-AP-A
C304-AP-A
C304-A
C304-B
C3-C3-AP-A
C301A-A
C309-A
C -B
C307-B
C307-AC305-A
NO DATA
NO DATA
C310A-A
C -A
C -B
C -A
P
-A C316A-AC316A-B
C -D
C -C
C -A
C -B
NO DATA
C3-S3-AP-A
NO DATA
NO DATAC322-AP-A
C318-A
C318-B
C -C
C -A
C315-AP-A
C -E
C315-A
C315-B
C315-C
C315-D
NO DATA
NO DATA
C -A
TYP.
STORAGE
C319
RADIOLOGY
C304
CLOSET
C304A
X-RAY
C301
RESTROOM
C324
CT ROOM
C322X-RAY
C310
ULTRASOUND
C309
RESTROOM
C313
SUPERVISORY DRT
C307
EQUIPMENT
C305
RESTROOM
C303
RADIOLOGY
C301A
IMAGING
C315
PT DOSING
C317
UPTAKE TOOM
C321
X-RAY
C316
RESTROOM
C314
STORAGE
C332
STAIR 3
C3-S3
CONTROL
C316A
CLEAN STORAGE
C326
PLUMBING
C322B
HALLWAY
C332A
PLUMBING
C321A
CONTROL
C310A
ALCOVE
C307A
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
AREA
91-A
B
IM
/5
A
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.8 .9
.9
.M
E P
.r v t
/1
/2
:3
:5
A
M
91T-103A
TELECOMMUNICATION PLAN - THIRD LEVEL -
B91A
589A6-21-700
B88/89/90/91
01/19/2022 M. Perkins K. Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,
FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL
OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL
NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &
NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END
WARRANTEED SOLUTION FOR THE CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.
E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR
EXCEED CATEGORY 6A STANDARDS.
F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN
WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.
UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR
PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A
MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR
TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE
TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF
EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE
TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL
PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE
EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE
REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH
EXISTING CONDUIT CAPACITY.
H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO
PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE
OR JUNCTION BOX.
I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.
J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW
EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE
TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.
K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING
BACK TO THE RACK.
L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL
STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL
INFORMATION
M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL
TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE
DOCUMENTS. HANG ON THE WALL WITHIN THE TELECOM ROOM.
N. REFER TO T-600 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING
CONDITIONS.
1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH
EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS
ON SHEET T-501 FOR ADDITIONAL INFORMATION.
2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE NEW
CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON SHEET
T-501 FOR ADDITIONAL INFORMATION.
3. PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS
AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE
SPECIFICATIONS. PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION AND
TRANSFER DATA CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK.
PROVIDE TEMPORARY EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES
AND OTHER DEVICES TO ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING
DATA CIRCUITS ARE RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND
ALL EXISTING DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK,
REMOVE THE EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL
PERMANENT POSITION.
4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY
PROTECTED IN PLACE. ALL EXISTING DEVICES ON THE EXISTING RACK SHALL BE
TRANSFERRED TO THE NEW SECOND LEVEL LOCATION ON THE NEW RACK.
CONTRACTOR SHALL PROVIDE SHOP DRAWINGS SHOWING THE PROPOSED NEW
RACK ELEVATION AND PROVIDE A PHASING PLAN FOR TRANSFERRING ALL
EXISTING DEVICES TO REMAIN TO THE NEW RACKS.
6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY
SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT
COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK.
COORDINATE FIXTURES WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD
CABLE TRAY.
7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION SENSOR,
AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET XNP-6320.
MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE CAMERA INTO
EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT NETWORK.
8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.
9. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR
HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH
ENDS TO PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.
10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS
INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE
AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN
FOR TRANSFERRING FIBER.
11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.
12. EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH
EXISTING FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE
OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR
TRANSFERRING FIBER.
13. PROVIDE NEW iSTAR EDGE (ESTAR002) ACCESS CONTROL SYSTEM. INSTALL PER
MANUFACTURERS RECOMMENDATIONS.
14. ALL EXISTING ANALOG PHONE CABLE DEVICES AND TERMINATIONS ETC. SHALL
REMAIN OPERATIONAL AT ALL TIMES AND SHALL BE RETAINED AND REUSED.
PROTECT IN PLACE.
15. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.
16. EXISTING EQUIPMENT TO BE DEMOLISHED.
17. VERTICAL ROUTE FOR TELECOM RISER. ALL FLOOR PENETRATIONS TO MAINTAIN
FIRE RATING.
18. PROVIDE NEW SERVER RACK AS SHOWN ON T-500/ T-600 SERIES SHEETS AND THE
SPECIFICATIONS. CONSOLIDATE EXISTING DEVICES AND REINSTALL IN NEW
CABINET.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
SCALE: 1/8" = 1'-0"
F3
TELECOMMUNICATION PLAN - THIRD
LEVEL - B91A
Revisions: Date:
/19
/20
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WAP
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
NO DATA
NO DATA
C330-A
C -A
NO DATA
NO DATA
NO DATA
C -A
C320-A
C320-B
C320-AP-A
NO DATA
C -B
C -C
C331-A C331-D
NO DATA C335-AP-A
C3-C2-AP-A
C353-AP-A
C3-C2-AP-B
C341-A
C341-B
C345-B C345B-A
C345B-B
C -A
C345-A
C348-AP-A
C348-A
C350-B
C350-C
C -A
C3-S2-AP-A
C A
-A
C -A
NO DATA
NO DATA
NO DATA
NO DATA
NO DATA
C364-AP-A
C3-S1-AP-A
C364-A
C -B C368-A C370-A
NO DATA
C386-A
C386-AP-A
NO DATA
C366-C
C -A
C -B
C374-A
C374-AP-A
C355-AP-A
C355-A C -A
C -A
C -A
C363-AP-A
C -A
C3-C4-AP-A
NO DATA
B3-C4-AP-A
TELECOM ROOM
C346
91T-103B
F1
91T-103B
C1
TYP.
RESTROOM
C347
LOCKERS
C340
WAITING ROOM
C335
WAITING ROOM
C333
BONE DENSITY
C345B
ULTRASOUND
C345
LAB
B328
OFFICE
B329
STORAGE
C319
HOT LAB
C320
ADMIN. ASSIST.
C370
SL. MGR. DIAG. CARE
C386
CONFERENCE
C384
COPY ROOM
C374
ADMIN. OFFICE
C382
QUALITY ASSURANCE
C368
MRI SUPERVISOR
C361
STORAGE
C360
CONFRENCE ROOM
C366
VIEWING ROOM C
C365
VIEWING ROOM B
C365A
VIEWING ROOM A
C364
OFFICE
C355
OFFICE
C357
CHIEF RADIOLOGY
C363
RESTROOM
C378
STAIR 1
C3-S1
MECHANICAL ROOM
C352
STAIR 2
C3-S2
HOUSEKEEPING
C334
CLOSET
C358
RESTROOM
C324 READING ROOM D
C350
READING ROOM E
C348
STORAGE
C341
ELECTRICAL
C330
UPTAKE TOOM
C321
RECEPTION
C331
STORAGE
C332
RESTROOM
C338
RESTROOM
C344
CORRIDOR
C3-C4
HALLWAY
C332A
CORRIDOR
C3-C5
CORRIDOR
C3-C1
PLUMBING
C321A
CHASE
C338P
ELEV 3
C3-E3
ELEV 4
C3-E4
CHASE
C366P
TELECOM ROOM
C346
C346-CAM-01
TYP.
TYP.
TYP.
TYP.
TYP.
TELECOM ROOM
C346
TYP.
N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
KEY PLAN
KEYNOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
AREA
91-B
B
IM
/5
A
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.8 .9
.9
.M
E P
.r v t
/1
/2
:3
:0
A
M
91T-103B
TELECOMMUNICATION PLANS - THIRD LEVEL -
B91B
589A6-21-700
B88/89/90/91
01/19/2022 M. Perkins K. Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
A. PROPERLY FIRE STOP AND SEAL ALL PENETRATIONS THROUGH WALLS,
FLOORS, CEILINGS, AND ROOF AS PER OWNER, CODE, AND AHJ.
B. PRIOR TO INSTALLATION OF CABLE TRAY COORDINATE LOCATIONS WITH ALL
OTHER TRADES AND PROVIDE COORDINATION DRAWINGS FOR REVIEW. ALL
NEW CABLE, CABLE TRAY, J HOOKS SHALL BE INDEPENDENTLY SUPPORTED &
NOT CAUSE ADDITIONAL LOAD ON OTHER SYSTEMS.
C. NOT ALL PARTS AND PIECES ARE SHOWN FOR A COMPLETE SYSTEM.
CONTRACTOR IS RESPONSIBLE FOR PROVIDING A COMPLETE END-TO-END
WARRANTEED SOLUTION FOR THE CABLING.
D. ALL CABLING TO BE PLENUM RATED THROUGHOUT THE BUILDING.
E. ALL COMMUNICATIONS AND WIRELESS ACCESS POINT CABLING TO MEET OR
EXCEED CATEGORY 6A STANDARDS.
F. SEE E-501 FOR DEVICE STANDARD MOUNTING HEIGHTS.
G. ALL CONDUITS FOR TELECOMMUNICATIONS OUTLETS SHALL BE STEEL THIN
WALL ELECTRICAL METALLIC TUBING (TYPE EMT) UNLESS OTHERWISE NOTED.
UNDER NO CIRCUMSTANCES SHALL FLEXIBLE CONDUIT BE USED FOR
PATHWAYS INDICATED ON THIS DRAWING. ALL CONDUITS ARE TO BE, AT A
MINIMUM, 1-1/4" TRADE SIZE, UNLESS OTHERWISE NOTED. ALL CONDUITS FOR
TELECOMMUNICATIONS OUTLETS ARE TO BE STUBBED TO NEAREST CABLE
TRAY. CONTRACTOR IS TO ENSURE THAT NO CONDUIT EXCEEDS 40% FILL. IF
EXISTING CONDUIT IS NOT LARGE ENOUGH TO SUPPORT NEW CAT 6A CABLE
TO REPLACE ALL EXISTING CIRCUITS ONE-FOR-ONE, CONTRACTOR SHALL
PROVIDE THE MAXIMUM ALLOWABLE NEW CAT 6A CIRCUITS TO REPLACE
EXISTING. THE ADDITIONAL NEW CIRCUITS TO COMPLETE THE ONE-FOR-ONE
REPLACEMENT SHALL BE PROVIDED AT THE NEAREST AVAILABLE DROP WITH
EXISTING CONDUIT CAPACITY.
H. ALL CONDUIT PATHWAYS SHALL BE PROVIDED WITH NYLON BUSHINGS TO
PROTECT CABLES, REGARDLESS OF WHETHER THEY TERMINATE IN A DEVICE
OR JUNCTION BOX.
I. TERMINATE, TEST, LABEL AND DOCUMENT ALL TELECOMMUNICATION CABLES.
J. CONTRACTOR SHALL AVOID ALL SYSTEMS SHUTDOWNS, INSTALL NEW
EQUIPMENT PRIOR TO THE RENOVATION OF EXISTING EQUIPMENT; PROVIDE
TEMPORARY UTILITIES AS REQUIRED TO MEET THIS REQUIREMENT.
K. THE DEMOLITION OF DEVICES SHALL INCLUDE ALL ASSOCIATED CABLING
BACK TO THE RACK.
L. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL FOLLOWING ALL
STANDARDS AND REQUIREMENTS, SEE DETAIL SHEETS FOR ADDITIONAL
INFORMATION
M. CONTRACTOR SHALL PROVIDE TWO SETS OF LAMINATED FINAL
TELECOMMUNICATION ONE-LINE, RACK ELEVATION, AND CABLE SCHEDULE
DOCUMENTS. HANG ON THE WALL WITHIN THE TELECOM ROOM.
N. REFER TO T-600 SERIES SHEETS FOR PHOTO DOCUMENTATION OF EXISTING
CONDITIONS.
1. PROVIDE NEW TELECOMMUNICATIONS OUTLET IN EXISTING LOCATION WITH
EXISTING EMT STUB UP TO NEAREST ACCESSIBLE CEILING SPACE. SEE DETAILS
ON SHEET T-501 FOR ADDITIONAL INFORMATION.
2. EXISTING WIRELESS ACCESS POINT TO BE RETAINED AND REUSED. PROVIDE NEW
CABLING AND TELECOMMUNICATIONS OUTLET. REFER TO DETAILS ON SHEET
T-501 FOR ADDITIONAL INFORMATION.
3. PROVIDE NEW 4-POST RACK, PDU, UPS AND WIRE MANAGEMENT COMPONENTS
AS SHOWN ON T-500 SERIES AND T-600 SERIES SHEETS AND IN THE
SPECIFICATIONS. PHASE TO PROVIDE NEW RACK IN A TEMPORARY LOCATION AND
TRANSFER DATA CIRCUITS FROM THE EXISTING RACK TO THE NEW RACK.
PROVIDE TEMPORARY EXTRA LENGTH JUMPER CABLES TO EXISTING SWITCHES
AND OTHER DEVICES TO ENSURE UNINTERRUPTED SERVICE. ONCE ALL EXISTING
DATA CIRCUITS ARE RELOCATED TO NEW PATCH PANELS ON THE NEW RACK AND
ALL EXISTING DEVICES TO REMAIN ARE TRANSFERRED TO THE NEW RACK,
REMOVE THE EXISTING RACK AND INSTALL THE NEW RACKS IN THE FINAL
PERMANENT POSITION.
4. PROVIDE NEW VERTICAL WIRE MANAGEMENT SYSTEM, SEE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
5. EXISTING CABLING CONDUIT AND WIREWAYS ARE TO REMAIN AND BE CAREFULLY
PROTECTED IN PLACE. ALL EXISTING DEVICES ON THE EXISTING RACK SHALL BE
TRANSFERRED TO THE NEW SECOND LEVEL LOCATION ON THE NEW RACK.
CONTRACTOR SHALL PROVIDE SHOP DRAWINGS SHOWING THE PROPOSED NEW
RACK ELEVATION AND PROVIDE A PHASING PLAN FOR TRANSFERRING ALL
EXISTING DEVICES TO REMAIN TO THE NEW RACKS.
6. PROVIDE NEW CABLE TRAY PER REQUIREMENTS LISTED IN CABLE TRAY
SCHEDULE. COORDINATE WITH EXISTING CONDITIONS AND SUBMIT
COORDINATION DRAWINGS FOR REVIEW PRIOR TO COMMENCING WORK.
COORDINATE FIXTURES WITH OVERHEAD TRAY. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS. COORDINATE LIGHT FIXTURES WITH OVERHEAD
CABLE TRAY.
7. PROVIDE NEW IP ADDRESSABLE NETWORK CAMERA, POE+, PTZ, MOTION SENSOR,
AUTO-TRACKING, DOME WITH WALL MOUNT. BASIS OF DESIGN WISENET XNP-6320.
MOUNT AT 8’ – 6” A.F.F. TO TOP OF WALL BRACKET. INTEGRATE CAMERA INTO
EXISTING VMS. PROVIDE CONTROLLABILITY THROUGH EXISTING IT NETWORK.
8. PROVIDE NEW DATA OUTLET, STUB-UP, AND BACK-BOX IN NEW LOCATION IN TR.
9. NEW 4” SPEED CONDUIT SLEEVE THROUGH WALL ABOVE CEILING GRID FOR
HORIZONTAL VOICE/DATA CABLING OR FIBER WITH PLASTIC BUSHINGS ON BOTH
ENDS TO PROTECT CABLES. FIRE CAULK PENETRATION PER SPECIFICATIONS.
10. EXISTING CONDUIT THROUGH WALL OR FLOOR WITH OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED CONDUIT SLEEVE AND FIBER IS
INSTALLED. DEMOLISH EXISTING CONDUIT ONCE NEW SPEED CONDUIT SLEEVE
AND FIBER ARE OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN
FOR TRANSFERRING FIBER.
11. EXISTING EQUIPMENT TO REMAIN, PROTECT-IN-PLACE.
12. EXISTING WALL MOUNTED FIBER SPLICE WITH MULTI-MODE OPTICAL CABLE TO BE
PROTECTED IN PLACE UNTIL NEW SPEED FIBER IS INSTALLED. DEMOLISH
EXISTING FIBER SPLICE ONCE NEW SPEED CONDUIT SLEEVE AND FIBER ARE
OPERATIONAL. CONTRACTOR SHALL PROVIDE A PHASING PLAN FOR
TRANSFERRING FIBER.
13. PROVIDE NEW iSTAR EDGE (ESTAR002) ACCESS CONTROL SYSTEM. INSTALL PER
MANUFACTURERS RECOMMENDATIONS.
14. ALL EXISTING ANALOG PHONE CABLE DEVICES AND TERMINATIONS ETC. SHALL
REMAIN OPERATIONAL AT ALL TIMES AND SHALL BE RETAINED AND REUSED.
PROTECT IN PLACE.
15. HORIZONTAL CABLE LENGTH LIMITATIONS PER STANDARD 3.1.
16. EXISTING EQUIPMENT TO BE DEMOLISHED.
17. VERTICAL ROUTE FOR TELECOM RISER. ALL FLOOR PENETRATIONS TO MAINTAIN
FIRE RATING.
18. PROVIDE NEW SERVER RACK AS SHOWN ON T-500/ T-600 SERIES SHEETS AND THE
SPECIFICATIONS. CONSOLIDATE EXISTING DEVICES AND REINSTALL IN NEW
CABINET.
NOTE: NOT ALL KEYNOTES
ARE USED ON EACH SHEET
SCALE: 1/8" = 1'-0"
F3
TELECOMMUNICATION PLAN - THIRD
LEVEL - B91B
SCALE: 1/2" = 1'-0"
F1
TELECOMMUNICATION ENLARGED
PLAN - THIRD LEVEL - ROOM C3496 -
NEW
SCALE: 1/2" = 1'-0"
C1
TELECOMMUNICATION ENLARGED
PLAN - THIRD LEVEL - ROOM C3496 -
DEMO
Revisions: Date:
/19
/20
UPDN
WAP
WAP
WAP
WAP
WAP WAP
WAP
WALL SYMBOL LEGEND
EXISTING CONSTRUCTION TO REMAIN
SMOKE AND 1-HR RATED FIRE
BARRIER AND OPENINGS
SMOKE AND 2-HR RATED FIRE BARRIER
AND OPENINGS
SMOKE BARRIER AND OPENINGS
1 HR RATED FIRE BARRIER AND
OPENINGS
2 HR RATED FIRE BARRIER AND OPENINGS
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES
C401-A
C401-B C403-A C405-A C407-A C409-A C411-A
C404-A
C406-A
C401-A…