This solicitation package includes architectural drawings and specifications for a federal construction project. The project involves replacing all telecommunications cabling across multiple buildings on the Leavenworth VA Medical Campus to prepare for an Electronic Health Record Modernization upgrade. Work includes replacing existing Category 3, 5e, and 6 cabling with new Category 6A cabling for voice and data circuits, installing additional conduit and cable trays as needed, upgrading telecommunications rooms with new racks and patch panels, replacing wall plates and cables at end user devices, and adding air conditioning systems and backup generators to computer rooms. The Department of Veterans Affairs Technology Acquisition Center is the contracting agency. The response due date and award information are not provided.

View the file

Other files

File Type Posted
01 00 00 Appendix A - Bid Form Template.20220505.xlsx XLSX spreadsheet
36C77622R0061 0004.pdf PDF
01 00 00 Appendix A - Bid Form Template.20220505.pdf PDF
Follow Up Technical Questions Tracking Spreadsheet - 5-5-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links - Rev01.pdf PDF
36C77622R0061 0003.pdf PDF
01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
589A6-21-700.LEHRM.ASI-001.B54.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B161.20220418.pdf PDF
Site Visit Attendance Sheet - LV EHRM Infra 4-11-22.pdf PDF
TR Space Impact - Leavenworth.pdf PDF
Technical Questions Tracking Spreadsheet - 4-27-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links.pdf PDF
B7 Electrical Panel Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.SITE.20220418.pdf PDF
Attachment 14 - DBA Wage Rates - Leavenworth County - 4-15-22.pdf PDF
Unitary Disconnect Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.B41.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B39.20220418.pdf PDF
Attachment 17 - Rev Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
01 00 00 Appendix A - Bid Form Template.pdf PDF
Unitary Cooling Photos.zip ZIP file
21 22 00 - Clean Agent Fire Suppression Systems.pdf PDF
23 64 00 - Packaged Water Chillers.ASI001.pdf PDF
589A6-21-700.LEHRM.ASI-001.B71.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B153.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.Summary.Log.20220419.pdf PDF
B88.89.90.91 Photos.zip ZIP file
Panel Photos.zip ZIP file
UPS Data Photos.zip ZIP file
589A6-21-700.LEHRM.IFC_R1.B39.20220119.pdf PDF
589A6-21-700.LEHRM.ASI-001.B21.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B160.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B122.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B90.20220419.pdf PDF
36C77622R0061 Amendment 0002.pdf PDF
36C77622R0061 Amendment 0001.pdf PDF
RFP 36C77622R0061.pdf PDF
Attachment 10 - 589A6-21-700 LEHRM IFC_R1 B161 Drawing.pdf PDF
Attachment 17 - Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment 4 - 589A6-21-700 LEHRM IFC_R1 B54 Drawing.pdf PDF
Attachment 3 - 589A6-21-700 LEHRM IFC_R1 B42 Drawing.pdf PDF
Attachment 18 - VA Notice of Limitations on Subcontracting-Certificate of Compliance.docx DOCX document
Attachment 13 - Asbestos Report Part 2 of 7.zip ZIP file
Attachment 5 - 589A6-21-700 LEHRM IFC_R1 B71 Part 1 of 2 Drawing.pdf PDF
Attachment 7 - 589A6-21-700 LEHRM IFC_R1 B122 Drawing.pdf PDF
Attachment 2 - 589A6-21-700 LEHRM IFC_R1 B41 Drawing.pdf PDF
Attachment 13 - Asbestos Report Part 4 of 7.zip ZIP file
Attachment 13 - Asbestos Report Part 5 of 7.zip ZIP file
Attachment 6 - 589A6-21-700 LEHRM IFC_R1 B88-89-90-91 Part 3 of 3 Drawing.pdf PDF
Show 40 more

Latest 50 of 67 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOM SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

42A-400

E8

TELECOM

ROOM

01A01A

6 TELECOM

ROOM

01A01A

B

B

B

B

B

B

B

B

B

01A

1/2" 1/2"

VARIES

SEE PLAN

WALL - SEE PLAN

FOR TYPE

SEALANT - EA. SIDE

& ALL AROUND,

TYP.

HOLLOW METAL

FRAME

/2

V

A R

IE

S

S E

E P

L A

N

/2

4" 2"

ADJACENT WALL

WHERE OCCURS

SEALANT - EA SIDE &

ALL AROUND, TYP.

HOLLOW METAL

FRAME

WALL - SEE PLAN

FOR TYPE

F4

TYPICAL FRAME

H E

IG

H

T

2" WIDTH 2"

F5

FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS

F

FLUSH

F2

ACOUSTICAL OR RATED

SEALANT BOTH SIDES

FLOOR LINE

5/8" GWB BOTH SIDES

SOUND ATTENUATION

BATTS (SAB) PER

SCHEDULE.

CEILING LINE

STRUCTURAL DECK

METAL STUDS, SIZE

PER SCHEDULE

42A-512

D5

A/C GRADE, 3/4" FIRE-

TREATED PLYWOOD TO 8'-0"

ABOVE FINISHED FLOOR

42A-512

B5

AT FIRE RATED

PARTITIONS

AT SMOKE RATED

PARTITIONS

BOTTOM OF PLYWOOD TO

BE AT 12" AFF

ACOUSTICAL OR RATED

FLEXIBLE SEALANT

FLOOR LINE

ADD ONE LAYER OF 5/8" GWB,

ONE-SIDE WITH APPROVED UL

SETTING COMPOUND BETWEEN

LAYERS AND FASTENED TO

WALL AS REQUIRED, AT

EXISTING GWB WALL

ASSEMBLIES

STRUCTURAL DECK

EXISTING METAL STUDS AND

BATT INSULATION TO REMAIN

A/C GRADE, 3/4" FIRE-TREATED

PLYWOOD TO 8'-0" ABOVE FINISHED

FLOOR, ADHERED TO CONCRETE AT

EXISTING CONCRETE WALL

ASSEMBLIES

BOTTOM OF PLYWOOD

TO BE AT 12" AFF

UL DESIGN V497

1-HOUR PARTITION RATED FROM BOTH SIDES

EXISTING GWB OR

CONCRETE WALL

ASSEMBLY, WHERE OCCURS

SIDE OF

EXISTING

ROOM OR

CORRIDOR TO

REMAIN

42A-512

D5

42A-512

B5

TELECOM

ROOM

01A01A

TELECOM

ROOM

01A01A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L

E H

R M

.B

.A

R C

H .r v t

/1

/2

:4

:5

A

M

42A-400

ARCHITECTURAL ENLARGED VIEWS - BASEMENT

LEVEL

589A6-21-700

B42

01/19/2022 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4th St Trafficway, Leavenworth, KS 66048

1/32" = 1'-0" F7

BASEMENT REFERENCE PLAN

1/4" = 1'-0" E5

ARCHITECTURAL FLOOR PLAN - BASEMENT

LEVEL - ROOM 01A - DEMO

1/4" = 1'-0"

E8

ARCHITECTURAL FLOOR PLAN - BASEMENT

LEVEL - ROOM 01A - NEW

3" = 1'-0" B1

HOLLOW METAL HEAD DETAIL

3" = 1'-0" C3

HOLLOW METAL JAMB DETAIL

1/4" = 1'-0" D1

WRAPPED FRAME TYPES ELEVATIONS

1 NOT USED

2 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL

PENETRATIONS AS NECESSARY.

3 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C

FIRE EXTINGUISHER LOCATED NO GREATER THAN 75 FEET AWAY

FROM THE NEW TR. CONTRACTOR TO COORDINATE THE NEW

LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW FEC

FOR EACH TR IN THE SCOPE OF WORK. SEE SPECIFICATION 10 44

13.

4 REMOVE EXISTING LIGHTS. MODIFY AND/OR PROVIDE ADDITIONAL

SUPPORTS AS REQUIRED FOR EXISTING CEILING ITEMS TO REMAIN.

5 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

6 PROVIDE TEMPORARY AIR TIGHT BARRIER AROUND WORK AREA

DURING ANY ACTIVIITES WHICH PRODUCE DUST - TYPICAL

NOT TO SCALE

F4

BASEMENT LEVEL ROOM 01A

NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL

U465

(TYPE A) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL

V438, UL U411

(TYPE B) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

B 2 1/2" 3/4" 45

DOOR AND FRAME SCHEDULE

IDENTIFICATION DIMENSIONS PANEL FRAME

FIRE RATING

HARDWARE

NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH GROUP ELECTRICAL

BASEMENT 01A TELECOM ROOM 01A 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-3F SEE ELEC 1,2,3

1/4" = 1'-0" C8

ARCHITECTURAL RCP - BASEMENT LEVEL -

ROOM 01A - NEW

1/4" = 1'-0"

C5

ARCHITECTURAL RCP - BASEMENT LEVEL -

ROOM 01A - DEMO

DOOR SCHEDULE NOTES:

1. TELECOM ROOM DOOR PANEL AND FRAME TO BE SMOKE RATED FOR TRANSITION,

INCLUDING CLOSER, SEALS, THRESHOLD, AND SWEEP.

2. PAINT DOOR TRIM TO MATCH EXISTING TRIM PAINT IN SPACE.

3. COORDINATE DOOR PANEL, FRAME, AND HARDWARE WITH ELECTRICAL HARDWARE

(ACCESS CONTROL, ELECTRICAL STRIKE, DOOR CONTACT SWITCH, ETC.) SEE ELECTRICAL

PLANS FOR ADDITIONAL INFORMATION.

Revisions: Date:

ASI 1 04/14/22

04/18/22

/18

/20

04/18/2022

Sheets
42A-400 - ARCHITECTURAL ENLARGED VIEWS - BASEMENT LEVEL