589A6-21-700.LEHRM.ASI-001.B21.20220418.pdf

PDF 2 MB Posted

Attached to
Y1DZ--589A6-21-700 EHRM Infrastructure Upgrades Construction Leavenworth VAMC
Solicitation number
36C77622R0061
Issued by

About this file

This solicitation is for a construction project to upgrade telecommunications infrastructure at the Leavenworth VA Medical Center campus in preparation for an Electronic Health Record modernization. The scope of work includes replacing all telecommunications cabling in multiple buildings on campus with CAT6A copper and single-mode fiber optic cable. Additional requirements are to provide 15% spare capacity, terminate and label cables per specifications, install patch panels and patch cables in new telecommunications rooms, add computer room air conditioning systems and backup generators, and replace one chiller. The selected contractor will be responsible for project management, material procurement and installation, testing, and documentation. The issuing agency is the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The response due date is not provided.

View the file

Other files

File Type Posted
01 00 00 Appendix A - Bid Form Template.20220505.xlsx XLSX spreadsheet
36C77622R0061 0004.pdf PDF
01 00 00 Appendix A - Bid Form Template.20220505.pdf PDF
Follow Up Technical Questions Tracking Spreadsheet - 5-5-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links - Rev01.pdf PDF
36C77622R0061 0003.pdf PDF
01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
589A6-21-700.LEHRM.ASI-001.B54.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B161.20220418.pdf PDF
Site Visit Attendance Sheet - LV EHRM Infra 4-11-22.pdf PDF
TR Space Impact - Leavenworth.pdf PDF
Technical Questions Tracking Spreadsheet - 4-27-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links.pdf PDF
B7 Electrical Panel Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.SITE.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B42.20220418.pdf PDF
Attachment 14 - DBA Wage Rates - Leavenworth County - 4-15-22.pdf PDF
Unitary Disconnect Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.B41.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B39.20220418.pdf PDF
Attachment 17 - Rev Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
01 00 00 Appendix A - Bid Form Template.pdf PDF
Unitary Cooling Photos.zip ZIP file
21 22 00 - Clean Agent Fire Suppression Systems.pdf PDF
23 64 00 - Packaged Water Chillers.ASI001.pdf PDF
589A6-21-700.LEHRM.ASI-001.B71.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B153.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.Summary.Log.20220419.pdf PDF
B88.89.90.91 Photos.zip ZIP file
Panel Photos.zip ZIP file
UPS Data Photos.zip ZIP file
589A6-21-700.LEHRM.IFC_R1.B39.20220119.pdf PDF
589A6-21-700.LEHRM.ASI-001.B160.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B122.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B90.20220419.pdf PDF
36C77622R0061 Amendment 0002.pdf PDF
36C77622R0061 Amendment 0001.pdf PDF
RFP 36C77622R0061.pdf PDF
Attachment 10 - 589A6-21-700 LEHRM IFC_R1 B161 Drawing.pdf PDF
Attachment 17 - Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment 4 - 589A6-21-700 LEHRM IFC_R1 B54 Drawing.pdf PDF
Attachment 3 - 589A6-21-700 LEHRM IFC_R1 B42 Drawing.pdf PDF
Attachment 18 - VA Notice of Limitations on Subcontracting-Certificate of Compliance.docx DOCX document
Attachment 13 - Asbestos Report Part 2 of 7.zip ZIP file
Attachment 5 - 589A6-21-700 LEHRM IFC_R1 B71 Part 1 of 2 Drawing.pdf PDF
Attachment 7 - 589A6-21-700 LEHRM IFC_R1 B122 Drawing.pdf PDF
Attachment 2 - 589A6-21-700 LEHRM IFC_R1 B41 Drawing.pdf PDF
Attachment 13 - Asbestos Report Part 4 of 7.zip ZIP file
Attachment 13 - Asbestos Report Part 5 of 7.zip ZIP file
Attachment 6 - 589A6-21-700 LEHRM IFC_R1 B88-89-90-91 Part 3 of 3 Drawing.pdf PDF
Show 40 more

Latest 50 of 67 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOM SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

21A-400

D7

TELECOM

ROOM

003003

1/2" 1/2"

VARIES

SEE PLAN

WALL - SEE PLAN

FOR TYPE

SEALANT - EA. SIDE

& ALL AROUND,

TYP.

HOLLOW METAL

FRAME

/2

V

A R

IE

S

S E

E P

L A

N

/2

4" 2"

ADJACENT WALL

WHERE OCCURS

SEALANT - EA SIDE &

ALL AROUND, TYP.

HOLLOW METAL

FRAME

WALL - SEE PLAN

FOR TYPE

F4

TYPICAL FRAME

H E

IG

H

T

2" WIDTH 2"

F5

FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS

F

FLUSH

F2

TELECOM

ROOM

ACTUAL: 142 SF

PROG: 170 SF

B

B

B

B

ACOUSTICAL OR RATED

SEALANT BOTH SIDES

FLOOR LINE

5/8" GWB BOTH SIDES

SOUND ATTENUATION

BATTS (SAB) PER

SCHEDULE.

CEILING LINE

STRUCTURAL DECK

METAL STUDS, SIZE

PER SCHEDULE

21A-512

D5

A/C GRADE, 3/4" FIRE-

TREATED PLYWOOD TO 8'-0"

ABOVE FINISHED FLOOR

21A-512

B5

AT FIRE RATED

PARTITIONS

AT SMOKE RATED

PARTITIONS

BOTTOM OF PLYWOOD TO

BE AT 12" AFF

ACOUSTICAL OR RATED

FLEXIBLE SEALANT

FLOOR LINE

ADD ONE LAYER OF 5/8" GWB,

ONE-SIDE WITH APPROVED UL

SETTING COMPOUND BETWEEN

LAYERS AND FASTENED TO

WALL AS REQUIRED, AT

EXISTING GWB WALL

ASSEMBLIES

STRUCTURAL DECK

EXISTING METAL STUDS AND

BATT INSULATION TO REMAIN

A/C GRADE, 3/4" FIRE-TREATED

PLYWOOD TO 8'-0" ABOVE FINISHED

FLOOR, ADHERED TO CONCRETE AT

EXISTING CONCRETE WALL

ASSEMBLIES

BOTTOM OF PLYWOOD

TO BE AT 12" AFF

UL DESIGN V497

1-HOUR PARTITION RATED FROM BOTH SIDES

EXISTING GWB OR

CONCRETE WALL

ASSEMBLY, WHERE OCCURS

SIDE OF

EXISTING

ROOM OR

CORRIDOR TO

REMAIN

21A-512

D5

21A-512

B5

STORAGE

003003

TELECOM

ROOM

ACTUAL: 142 SF

PROG: 170 SF

STORAGE

003003

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L

E H

R M

.B

.A

R C

H .r v t

/1

/2

:2

:4

A

M

21A-400

ARCHITECTURAL ENLARGED VIEWS - BASEMENT 589A6-21-700

B21

01/19/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048

1/16" = 1'-0" F7

BASEMENT REFERENCE PLAN

3" = 1'-0" C1

HOLLOW METAL HEAD DETAIL

3" = 1'-0" D1

HOLLOW METAL JAMB DETAIL

1/4" = 1'-0" E1

WRAPPED FRAME TYPES ELEVATIONS

1 EXISTING TO REMAIN CLOSET

2 EXISTING DOOR TO BECOME SMOKE-RATED.

3 EXISTING WALLS TO BECOME SMOKE-RATED. PATCH AND SEAL

ALL PENETRATIONS AS NECESSARY.

4 EXISTING ROOM OPEN TO STRUCTURE ABOVE TO REMAIN.

5 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE

2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75

FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE

THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A

NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE

SPECIFICATION 10 44 13.

1/4" = 1'-0" D7

ARCHITECTURAL FLOOR PLAN - BASEMENT

LEVEL - ROOM 003 - NEW

NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL

U465

(TYPE A) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

A4 4" 5 1/4" 35

NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL

V438, UL U411

(TYPE B) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

B 2 1/2" 3/4" 45

DOOR AND FRAME SCHEDULE

IDENTIFICATION DIMENSIONS PANEL FRAME FIRE

RATING

HARDWARE

NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH GROUP ELECTRICAL

BASEMENT 003 TELECOM ROOM 003 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE SPEC 1,2,3

1/4" = 1'-0" D5

ARCHITECTURAL FLOOR PLAN - BASEMENT

LEVEL - ROOM 003 - DEMO

1/4" = 1'-0" B7

ARCHITECTURAL REFLECTED CEILING PLAN -

BASEMENT LEVEL - ROOM 003 - NEW

1/4" = 1'-0"

B5

ARCHITECTURAL REFLECTED CEILING PLAN -

BASEMENT LEVEL - ROOM 003 - DEMO

Revisions: Date:

ASI 1 04/14/22

DOOR SCHEDULE NOTES:

1. TELECOM ROOM DOOR PANEL AND FRAME TO BE SMOKE RATED FOR TRANSITION,

INCLUDING CLOSER, SEALS, THRESHOLD, AND SWEEP.

2. PAINT DOOR TRIM TO MATCH EXISTING TRIM PAINT IN SPACE.

3. COORDINATE DOOR PANEL, FRAME, AND HARDWARE WITH ELECTRICAL HARDWARE

(ACCESS CONTROL, ELECTRICAL STRIKE, DOOR CONTACT SWITCH, ETC.) SEE ELECTRICAL

PLANS FOR ADDITIONAL INFORMATION.

MECHANICAL

SPACE

04/18/22

/18

/20

B 208/120V

125A

MCB

A 208/120V

125A

MCB

SECOND LEVEL

BASEMENT LEVEL

FIRST LEVEL

100A 3P

ROOM TR 003

(NEW) NORMAL POWER PANELBOARD

LOCATED IN B21

NP-TR-01, 225A, 120/208V, 3PH, 4W

ROOM TR 003

3 2

100A 3P

225A 3P

MCB

(EXISTING) NORMAL POWER SWITCHBOARD

LOCATED IN B07

7-MDP, 1200A, 120/208V, 3PH, 4W

225A 3P

1 5

NTS

F3

ELECTRICAL ONE LINE/RISER DIAGRAM

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

CONSULTANT

321 4 5 6 7 8 9 10

GENERAL NOTES

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

STAMP

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L

E H

R M

.B

.M E

P .r v t

/1

/2

:0

:1

P

M

21E-601

ELECTRICAL ONE-LINE DIAGRAMS 589A6-21-700

B21

01/19/2022 M. Perkins G. Weaver

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048

1. CONTRACTOR SHALL PROVIDE A 30 DAY LOAD MEASUREMENT

OF EQUPMENT INDICATED AND PROVIDE THE RESULTS TO THE

ELECTICAL ENGINEER OF RECORD (EEOR) TO VERFIY THE

EQUIPMENT HAS CAPACITY TO SUPPORT ADDITIONAL LOAD.

2. PROVIDE SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY.

CIRCUITS SHALL BE EQUIPPED WITH NEW MONITORED POWER

METER. BASIS OF DESIGN: E-MON D-M0N.

3. PROVIDE SUB-METERING OF NEW DEDICATED ROOM HVAC

SYSTEM. CIRCUITS SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-M0N.

4. PANELBOARD SHALL HAVE MANUFACTURER INSTALLED SPD.

5. PROVIDE CIRCUIT BREAKER INDICATED IN AVAILABLE SPACE.

6. REFER TO SHEET E-701 FOR FEEDER SIZES.

7. SITE ROUTING, SEE SITE SHEET ES100 FOR ADDITIONAL

INFORMATION.

8. PROVIDE 4" CONDUIT, COORDINATE WITH SITE ROUTING.

KEYNOTES

Revisions: Date:

ASI-001 04/18/22

ALL NEW FEEDER CONDUCTORS SHALL BE CONTINUOUS WITH NO

SPLICES.

ALL FEEDERS SHALL BE COPPER WITH 90° C. (THHN/THWN)

INSULATION.

NEW CIRCUIT BREAKERS SHALL BE TYPE TO MATCH EXISTING, U.N.O.

PROVIDE ALL REQUIRED MOUNTING HARDWARE, LUGS AND

COVERPLATES FOR A COMPLETE INSTALLATION.

FEEDER VOLTAGE DROP CALCULATIONS ARE INDICATED FOR

FEEDERS EXCEEDING 100'-0".

CONTRACTOR TO PROVIDE SHORT CIRCUIT, OVERCURRENT

PROTECTIVE DEVICE COORDINATION AND ARC FLASH ANALYSIS FOR

ALL NEW PANELS, SWITCHBOARDS AND SWITCHGEAR. STUDY SHALL

INCLUDE EXISTING SYSTEM TO THE EXTENT THAT THE FAULT

CURRENT, COORDINATION AND ARC FLASH PREPARED IN

COMPLIANCE WITH 2018 NFPA 70E FOR THE NEW PANELS CAN BE

CALCULATED. CONTRACTOR IS RESPONSIBLE FOR ALL DATA

COLLECTION REQUIRED TO COMPLETE THE ANALYSIS. REPORT OF

THE ANALYSIS SHALL BE PREPARED SUMMARIZING THE INPUT DATA,

SINGLE-LINE USED IN CALCULATION, AND RESULTS INCLUDING ARC

FLASH LABELS. REPORT SHALL BE STAMPED AND SIGNED BY

PROFESSIONAL ENGINEER UNDER WHOSE DIRECTION THE STUDY

WAS PERFORMED. CONTRACTOR TO INSTALL ARC FLASH LABELS ON

PANELS IN COMPLIANCE WITH 2018 NFPA 70E. ELECTRICAL

EQUIPMENT SUBMITTALS SHALL REFLECT RESULTS OF SHORT

CIRCUIT ANALYSIS. CONTRACTOR SHALL SET ALL ADJUSTABLE

CIRCUIT BREAKERS PER OVERCURRENT PROTECTIVE DEVICE

STUDY. MINIMAL INFORMATION INCLUDED ON ARC FLASH LABELS

INCLUDE:

• NOMINAL SYSTEM VOLTAGE

• ARC FLASH BOUNDRY

• AT LEAST ONE OF THE FOLLOWING:

A. EITHER THE AVAILABLE INCIDENT ENERGY AND THE

CORRESPONDING WORKING DISTANCE, OR THE ARC

FLASH PPE CATEGORY FOR THE EQUIPMENT, BUT

NOT BOTH.

B. MINIMUM ARC RATING OF CLOTHING.

C. SITE-SPECIFIC LEVEL OF PPE.

ANALYSIS SHALL BE PREPARED PRIOR TO OR CONCURRENT WITH

ELECTRICAL SWITCHGEAR, SWITCHBOARDS AND PANEL

SUBMITTALS. EQUIPMENT SUBMITTALS WITHOUT ANALYSIS SHALL BE

REJECTED AND NOT REVIEWED.

EEOR CAN NOT BE RESPONSIBLE FOR ANALYSIS UNLESS

SEPARATELY AND SPECIFICALLY CONTRACTED TO DO SO.

CONTRACTOR SHALL PROVIDE A 30 DAY LOAD MEASUREMENT OF

EQUPMENT INDICATED AND PROVIDE THE RESULTS TO THE

ELECTICAL ENGINEER OF RECORD (EEOR) TO VERFIY THE

EQUIPMENT HAS CAPACITY TO SUPPORT ADDITIONAL LOAD.

/18

/20

04/18/2022

Sheets
21A-400 - ARCHITECTURAL ENLARGED VIEWS - BASEMENT

File details come from the government source that posted it. Updated .