This solicitation is for a construction project to upgrade telecommunications infrastructure at the Leavenworth VA Medical Center campus in preparation for an Electronic Health Record modernization. The scope of work includes replacing all telecommunications cabling in multiple buildings on campus with CAT6A copper and single-mode fiber optic cable. Additional requirements are to provide 15% spare capacity, terminate and label cables per specifications, install patch panels and patch cables in new telecommunications rooms, add computer room air conditioning systems and backup generators, and replace one chiller. The selected contractor will be responsible for project management, material procurement and installation, testing, and documentation. The issuing agency is the Department of Veterans Affairs Technology Acquisition Center located in Austin, Texas. The response due date is not provided.
View the file
Other files
Show 40 more
Latest 50 of 67 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOM SHALL BE SMOKE RATED AND COMPLY WITH
THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS
STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
21A-400
D7
TELECOM
ROOM
003003
1/2" 1/2"
VARIES
SEE PLAN
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND,
TYP.
HOLLOW METAL
FRAME
/2
V
A R
IE
S
S E
E P
L A
N
/2
4" 2"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL
FRAME
WALL - SEE PLAN
FOR TYPE
F4
TYPICAL FRAME
H E
IG
H
T
2" WIDTH 2"
F5
FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS
F
FLUSH
F2
TELECOM
ROOM
ACTUAL: 142 SF
PROG: 170 SF
B
B
B
B
ACOUSTICAL OR RATED
SEALANT BOTH SIDES
FLOOR LINE
5/8" GWB BOTH SIDES
SOUND ATTENUATION
BATTS (SAB) PER
SCHEDULE.
CEILING LINE
STRUCTURAL DECK
METAL STUDS, SIZE
PER SCHEDULE
21A-512
D5
A/C GRADE, 3/4" FIRE-
TREATED PLYWOOD TO 8'-0"
ABOVE FINISHED FLOOR
21A-512
B5
AT FIRE RATED
PARTITIONS
AT SMOKE RATED
PARTITIONS
BOTTOM OF PLYWOOD TO
BE AT 12" AFF
ACOUSTICAL OR RATED
FLEXIBLE SEALANT
FLOOR LINE
ADD ONE LAYER OF 5/8" GWB,
ONE-SIDE WITH APPROVED UL
SETTING COMPOUND BETWEEN
LAYERS AND FASTENED TO
WALL AS REQUIRED, AT
EXISTING GWB WALL
ASSEMBLIES
STRUCTURAL DECK
EXISTING METAL STUDS AND
BATT INSULATION TO REMAIN
A/C GRADE, 3/4" FIRE-TREATED
PLYWOOD TO 8'-0" ABOVE FINISHED
FLOOR, ADHERED TO CONCRETE AT
EXISTING CONCRETE WALL
ASSEMBLIES
BOTTOM OF PLYWOOD
TO BE AT 12" AFF
UL DESIGN V497
1-HOUR PARTITION RATED FROM BOTH SIDES
EXISTING GWB OR
CONCRETE WALL
ASSEMBLY, WHERE OCCURS
SIDE OF
EXISTING
ROOM OR
CORRIDOR TO
REMAIN
21A-512
D5
21A-512
B5
STORAGE
003003
TELECOM
ROOM
ACTUAL: 142 SF
PROG: 170 SF
STORAGE
003003
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L
E H
R M
.B
.A
R C
H .r v t
/1
/2
:2
:4
A
M
21A-400
ARCHITECTURAL ENLARGED VIEWS - BASEMENT 589A6-21-700
B21
01/19/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
1/16" = 1'-0" F7
BASEMENT REFERENCE PLAN
3" = 1'-0" C1
HOLLOW METAL HEAD DETAIL
3" = 1'-0" D1
HOLLOW METAL JAMB DETAIL
1/4" = 1'-0" E1
WRAPPED FRAME TYPES ELEVATIONS
1 EXISTING TO REMAIN CLOSET
2 EXISTING DOOR TO BECOME SMOKE-RATED.
3 EXISTING WALLS TO BECOME SMOKE-RATED. PATCH AND SEAL
ALL PENETRATIONS AS NECESSARY.
4 EXISTING ROOM OPEN TO STRUCTURE ABOVE TO REMAIN.
5 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE
2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE
THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A
NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE
SPECIFICATION 10 44 13.
1/4" = 1'-0" D7
ARCHITECTURAL FLOOR PLAN - BASEMENT
LEVEL - ROOM 003 - NEW
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL
U465
(TYPE A) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
A4 4" 5 1/4" 35
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V438, UL U411
(TYPE B) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
B 2 1/2" 3/4" 45
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME FIRE
RATING
HARDWARE
NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH GROUP ELECTRICAL
BASEMENT 003 TELECOM ROOM 003 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE SPEC 1,2,3
1/4" = 1'-0" D5
ARCHITECTURAL FLOOR PLAN - BASEMENT
LEVEL - ROOM 003 - DEMO
1/4" = 1'-0" B7
ARCHITECTURAL REFLECTED CEILING PLAN -
BASEMENT LEVEL - ROOM 003 - NEW
1/4" = 1'-0"
B5
ARCHITECTURAL REFLECTED CEILING PLAN -
BASEMENT LEVEL - ROOM 003 - DEMO
Revisions: Date:
ASI 1 04/14/22
DOOR SCHEDULE NOTES:
1. TELECOM ROOM DOOR PANEL AND FRAME TO BE SMOKE RATED FOR TRANSITION,
INCLUDING CLOSER, SEALS, THRESHOLD, AND SWEEP.
2. PAINT DOOR TRIM TO MATCH EXISTING TRIM PAINT IN SPACE.
3. COORDINATE DOOR PANEL, FRAME, AND HARDWARE WITH ELECTRICAL HARDWARE
(ACCESS CONTROL, ELECTRICAL STRIKE, DOOR CONTACT SWITCH, ETC.) SEE ELECTRICAL
PLANS FOR ADDITIONAL INFORMATION.
MECHANICAL
SPACE
04/18/22
/18
/20
B 208/120V
125A
MCB
A 208/120V
125A
MCB
SECOND LEVEL
BASEMENT LEVEL
FIRST LEVEL
100A 3P
ROOM TR 003
(NEW) NORMAL POWER PANELBOARD
LOCATED IN B21
NP-TR-01, 225A, 120/208V, 3PH, 4W
ROOM TR 003
3 2
100A 3P
225A 3P
MCB
(EXISTING) NORMAL POWER SWITCHBOARD
LOCATED IN B07
7-MDP, 1200A, 120/208V, 3PH, 4W
225A 3P
1 5
NTS
F3
ELECTRICAL ONE LINE/RISER DIAGRAM
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
GENERAL NOTES
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L
E H
R M
.B
.M E
P .r v t
/1
/2
:0
:1
P
M
21E-601
ELECTRICAL ONE-LINE DIAGRAMS 589A6-21-700
B21
01/19/2022 M. Perkins G. Weaver
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
1. CONTRACTOR SHALL PROVIDE A 30 DAY LOAD MEASUREMENT
OF EQUPMENT INDICATED AND PROVIDE THE RESULTS TO THE
ELECTICAL ENGINEER OF RECORD (EEOR) TO VERFIY THE
EQUIPMENT HAS CAPACITY TO SUPPORT ADDITIONAL LOAD.
2. PROVIDE SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY.
CIRCUITS SHALL BE EQUIPPED WITH NEW MONITORED POWER
METER. BASIS OF DESIGN: E-MON D-M0N.
3. PROVIDE SUB-METERING OF NEW DEDICATED ROOM HVAC
SYSTEM. CIRCUITS SHALL BE EQUIPPED WITH NEW MONITORED
POWER METER. BASIS OF DESIGN: E-MON D-M0N.
4. PANELBOARD SHALL HAVE MANUFACTURER INSTALLED SPD.
5. PROVIDE CIRCUIT BREAKER INDICATED IN AVAILABLE SPACE.
6. REFER TO SHEET E-701 FOR FEEDER SIZES.
7. SITE ROUTING, SEE SITE SHEET ES100 FOR ADDITIONAL
INFORMATION.
8. PROVIDE 4" CONDUIT, COORDINATE WITH SITE ROUTING.
KEYNOTES
Revisions: Date:
ASI-001 04/18/22
ALL NEW FEEDER CONDUCTORS SHALL BE CONTINUOUS WITH NO
SPLICES.
ALL FEEDERS SHALL BE COPPER WITH 90° C. (THHN/THWN)
INSULATION.
NEW CIRCUIT BREAKERS SHALL BE TYPE TO MATCH EXISTING, U.N.O.
PROVIDE ALL REQUIRED MOUNTING HARDWARE, LUGS AND
COVERPLATES FOR A COMPLETE INSTALLATION.
FEEDER VOLTAGE DROP CALCULATIONS ARE INDICATED FOR
FEEDERS EXCEEDING 100'-0".
CONTRACTOR TO PROVIDE SHORT CIRCUIT, OVERCURRENT
PROTECTIVE DEVICE COORDINATION AND ARC FLASH ANALYSIS FOR
ALL NEW PANELS, SWITCHBOARDS AND SWITCHGEAR. STUDY SHALL
INCLUDE EXISTING SYSTEM TO THE EXTENT THAT THE FAULT
CURRENT, COORDINATION AND ARC FLASH PREPARED IN
COMPLIANCE WITH 2018 NFPA 70E FOR THE NEW PANELS CAN BE
CALCULATED. CONTRACTOR IS RESPONSIBLE FOR ALL DATA
COLLECTION REQUIRED TO COMPLETE THE ANALYSIS. REPORT OF
THE ANALYSIS SHALL BE PREPARED SUMMARIZING THE INPUT DATA,
SINGLE-LINE USED IN CALCULATION, AND RESULTS INCLUDING ARC
FLASH LABELS. REPORT SHALL BE STAMPED AND SIGNED BY
PROFESSIONAL ENGINEER UNDER WHOSE DIRECTION THE STUDY
WAS PERFORMED. CONTRACTOR TO INSTALL ARC FLASH LABELS ON
PANELS IN COMPLIANCE WITH 2018 NFPA 70E. ELECTRICAL
EQUIPMENT SUBMITTALS SHALL REFLECT RESULTS OF SHORT
CIRCUIT ANALYSIS. CONTRACTOR SHALL SET ALL ADJUSTABLE
CIRCUIT BREAKERS PER OVERCURRENT PROTECTIVE DEVICE
STUDY. MINIMAL INFORMATION INCLUDED ON ARC FLASH LABELS
INCLUDE:
• NOMINAL SYSTEM VOLTAGE
• ARC FLASH BOUNDRY
• AT LEAST ONE OF THE FOLLOWING:
A. EITHER THE AVAILABLE INCIDENT ENERGY AND THE
CORRESPONDING WORKING DISTANCE, OR THE ARC
FLASH PPE CATEGORY FOR THE EQUIPMENT, BUT
NOT BOTH.
B. MINIMUM ARC RATING OF CLOTHING.
C. SITE-SPECIFIC LEVEL OF PPE.
ANALYSIS SHALL BE PREPARED PRIOR TO OR CONCURRENT WITH
ELECTRICAL SWITCHGEAR, SWITCHBOARDS AND PANEL
SUBMITTALS. EQUIPMENT SUBMITTALS WITHOUT ANALYSIS SHALL BE
REJECTED AND NOT REVIEWED.
EEOR CAN NOT BE RESPONSIBLE FOR ANALYSIS UNLESS
SEPARATELY AND SPECIFICALLY CONTRACTED TO DO SO.
CONTRACTOR SHALL PROVIDE A 30 DAY LOAD MEASUREMENT OF
EQUPMENT INDICATED AND PROVIDE THE RESULTS TO THE
ELECTICAL ENGINEER OF RECORD (EEOR) TO VERFIY THE
EQUIPMENT HAS CAPACITY TO SUPPORT ADDITIONAL LOAD.
/18
/20
04/18/2022