589A6-21-700.LEHRM.ASI-001.B122.20220418.pdf

PDF 1 MB Posted

Attached to
Y1DZ--589A6-21-700 EHRM Infrastructure Upgrades Construction Leavenworth VAMC
Solicitation number
36C77622R0061
Issued by

About this file

This solicitation is for a construction contract to prepare a VA medical campus for Electronic Health Record Modernization upgrades by replacing all telecommunications cabling and equipment across multiple buildings. The scope of work includes replacing existing copper, fiber and wireless cabling one-for-one with CAT6A, OM4 and OS-2 fiber, along with associated patch panels, racks and ladder racks. An additional 15% capacity must be provided. The contractor must also install new computer room air conditioning systems, electrical panels and backup generators. A new 600 ton water cooled chiller and pump will be installed in Building 161 to serve new telecom rooms. The solicitation was issued by the VA Technology Acquisition Center in Austin, Texas. Bids are due by the date specified in the solicitation number listed.

View the file

Other files

File Type Posted
01 00 00 Appendix A - Bid Form Template.20220505.xlsx XLSX spreadsheet
36C77622R0061 0004.pdf PDF
01 00 00 Appendix A - Bid Form Template.20220505.pdf PDF
Follow Up Technical Questions Tracking Spreadsheet - 5-5-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links - Rev01.pdf PDF
36C77622R0061 0003.pdf PDF
01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
589A6-21-700.LEHRM.ASI-001.B54.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B161.20220418.pdf PDF
Site Visit Attendance Sheet - LV EHRM Infra 4-11-22.pdf PDF
TR Space Impact - Leavenworth.pdf PDF
Technical Questions Tracking Spreadsheet - 4-27-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links.pdf PDF
B7 Electrical Panel Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.SITE.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B42.20220418.pdf PDF
Attachment 14 - DBA Wage Rates - Leavenworth County - 4-15-22.pdf PDF
Unitary Disconnect Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.B41.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B39.20220418.pdf PDF
Attachment 17 - Rev Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
01 00 00 Appendix A - Bid Form Template.pdf PDF
Unitary Cooling Photos.zip ZIP file
21 22 00 - Clean Agent Fire Suppression Systems.pdf PDF
23 64 00 - Packaged Water Chillers.ASI001.pdf PDF
589A6-21-700.LEHRM.ASI-001.B71.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B153.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.Summary.Log.20220419.pdf PDF
B88.89.90.91 Photos.zip ZIP file
Panel Photos.zip ZIP file
UPS Data Photos.zip ZIP file
589A6-21-700.LEHRM.IFC_R1.B39.20220119.pdf PDF
589A6-21-700.LEHRM.ASI-001.B21.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B160.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B90.20220419.pdf PDF
36C77622R0061 Amendment 0002.pdf PDF
36C77622R0061 Amendment 0001.pdf PDF
RFP 36C77622R0061.pdf PDF
Attachment 10 - 589A6-21-700 LEHRM IFC_R1 B161 Drawing.pdf PDF
Attachment 17 - Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment 4 - 589A6-21-700 LEHRM IFC_R1 B54 Drawing.pdf PDF
Attachment 3 - 589A6-21-700 LEHRM IFC_R1 B42 Drawing.pdf PDF
Attachment 18 - VA Notice of Limitations on Subcontracting-Certificate of Compliance.docx DOCX document
Attachment 13 - Asbestos Report Part 2 of 7.zip ZIP file
Attachment 5 - 589A6-21-700 LEHRM IFC_R1 B71 Part 1 of 2 Drawing.pdf PDF
Attachment 7 - 589A6-21-700 LEHRM IFC_R1 B122 Drawing.pdf PDF
Attachment 2 - 589A6-21-700 LEHRM IFC_R1 B41 Drawing.pdf PDF
Attachment 13 - Asbestos Report Part 4 of 7.zip ZIP file
Attachment 13 - Asbestos Report Part 5 of 7.zip ZIP file
Attachment 6 - 589A6-21-700 LEHRM IFC_R1 B88-89-90-91 Part 3 of 3 Drawing.pdf PDF
Show 40 more

Latest 50 of 67 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

1/2" 1/2"

VARIES

SEE PLAN

WALL - SEE PLAN

FOR TYPE

SEALANT - EA. SIDE

& ALL AROUND,

TYP.

HOLLOW METAL

FRAME

/2

V

A R

IE

S

S E

E P

L A

N

/2

4" 2"

ADJACENT WALL

WHERE OCCURS

SEALANT - EA SIDE &

ALL AROUND, TYP.

HOLLOW METAL

FRAME

WALL - SEE PLAN

FOR TYPE

F4

TYPICAL FRAME

H E

IG

H

T

2" WIDTH 2"

F5

FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS

F

FLUSH

F2

TELECOM

ROOM

B4B4

122A-400

D7

CRAWL SPACE

B7DB7D

B7B7

B7AB7A

B7BB7B

B7CB7C

B9B9

B10B10

B2AB2A

STB2STB2

B5BB5B

B6B6

B2B2

B11B11

B11AB11A B11BB11B

B13CB13C

B12EB12E B13BB13B

B13GB13G

B13DB13D

B13AB13A

B13B13 B13HB13H

B14B14

PT CLINIC

B5B5B5AB5A

B18B18B19B19

B3B3

B15B15

STB1STB1

B17B17

B0-E2B0-E2

B0-E1B0-E1

B4AB4A

B1B1

TELECOM

ROOM

B4

ACTUAL: 55 SF

PROG: 170 SF

B B

B

B

TYP.

5' -9

/8

9'-4 7/8"

B

6' -0

/8

9 10

ACOUSTICAL OR RATED

SEALANT BOTH SIDES

FLOOR LINE

5/8" GWB BOTH SIDES

SOUND ATTENUATION

BATTS (SAB) PER

SCHEDULE.

CEILING LINE

STRUCTURAL DECK

METAL STUDS, SIZE

PER SCHEDULE

122A-512

D5

A/C GRADE, 3/4" FIRE-

TREATED PLYWOOD TO 8'-0"

ABOVE FINISHED FLOOR

122A-512

B5

AT FIRE RATED

PARTITIONS

AT SMOKE RATED

PARTITIONS

BOTTOM OF PLYWOOD TO

BE AT 12" AFF

ACOUSTICAL OR RATED

FLEXIBLE SEALANT

FLOOR LINE

ADD ONE LAYER OF 5/8" GWB,

ONE-SIDE WITH APPROVED UL

SETTING COMPOUND BETWEEN

LAYERS AND FASTENED TO

WALL AS REQUIRED, AT

EXISTING GWB WALL

ASSEMBLIES

STRUCTURAL DECK

EXISTING METAL STUDS AND

BATT INSULATION TO REMAIN

A/C GRADE, 3/4" FIRE-TREATED

PLYWOOD TO 8'-0" ABOVE FINISHED

FLOOR, ADHERED TO CONCRETE AT

EXISTING CONCRETE WALL

ASSEMBLIES

BOTTOM OF PLYWOOD

TO BE AT 12" AFF

UL DESIGN V497

1-HOUR PARTITION RATED FROM BOTH SIDES

EXISTING GWB OR

CONCRETE WALL

ASSEMBLY, WHERE OCCURS

SIDE OF

EXISTING

ROOM OR

CORRIDOR TO

REMAIN

122A-512

D5

122A-512

B5

B4B4

C

LR

M

IN

3' -0

9 10

TELECOM

ROOM

B4B4

8B4B4

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L E

H R

M .B

.A

R C

H .r v t

/1

/2

:3

:1

A

M

122A-400

ARCHITECTURAL ENLARGED VIEWS - BASEMENT

LEVEL

589A6-21-700

B122

01/19/2022 M. Perkins K. Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048

3" = 1'-0" C1

HOLLOW METAL HEAD DETAIL

3" = 1'-0" D1

HOLLOW METAL JAMB DETAIL

1/4" = 1'-0" F1

WRAPPED FRAME TYPES ELEVATIONS

1 REMOVE EXISTING DOOR AND FRAM

2 NEW SMOKE RATED DOOR

3 REMOVE FLOORING AND WALL BASE IN ROOM.

4 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL

PENETRATIONS AS NECESSARY.

5 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C

FIRE EXTINGUISHER LOCATED NO GREATER THAN 75 FEET AWAY

FROM THE NEW TR. CONTRACTOR TO COORDINATE THE NEW

LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW FEC FOR

EACH TR IN THE SCOPE OF WORK. SEE SPECIFICATION 10 44 13.

6 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE

DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.

7 REMOVE EXISTING LIGHT. MODIFY AND/OR PROVIDE ADDITIONAL

SUPPORTS AS REQUIRED FOR EXISTING CEILING ITEMS TO REMAIN.

8 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

9 TEMPORARY WALLS FOR ICRA ENCLOSURE

10 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE

Revisions: Date:

ASI 1 04/14/22

1/16" = 1'-0" F3

BASEMENT REFERENCE PLAN

1/4" = 1'-0" D7

ARCHITECTURAL ENLARGED FLOOR PLAN -

BASEMENT LEVEL - ROOM B4 - NEW

1 1/2" = 1'-0" D6

1-HOUR WALL

1 1/2" = 1'-0"

D3

1-HOUR WALL

NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL

U465

(TYPE A) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

A3 3 5/8" 4 7/8" 35

A4 4" 5 1/4" 35

NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL

V438, UL U411

(TYPE B) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

B 2 1/2" 3/4" 45

DOOR AND FRAME SCHEDULE

IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL

FIRE RATING

HARDWARE

NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL

BASEMENT B4 TELECOM ROOM B4 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-9 SEE ELEC

LEVEL 1 104A TELECOM ROOM 104A 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC

LEVEL 1 104 NURSE STATION 104 3' - 6" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD HW-SH-3D SEE ELEC

LEVEL 2 202F TELECOM ROOM 202F 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC

LEVEL 3 302F TELECOM ROOM 302F 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC

1/4" = 1'-0" D5

ARCHITECTURAL ENLARGED FLOOR PLAN -

BASEMENT LEVEL - ROOM B4 - DEMO

1/4" = 1'-0" C7

ARCHITECTURAL RCP - BASEMENT LEVEL -

ROOM B4 - NEW

1/4" = 1'-0"

C5

ARCHITECTURAL RCP - BASEMENT LEVEL -

ROOM B4 - DEMO

04/18/22

/18

/20

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

TELECOM

ROOM

104A

63 SF

122A-401

C7

101101 102102

104104

105105 106106

107107

108108

109109

110110111111

112112

113113

114114

115115

116116

117117

118118

119119

120120

121121 122122

ST11ST11

124124

125125

126126

127127

128A128A

129129

130130

131131

132132

133133

134134

135135

136136

137137

138138

139139140140

141141

142142143143

144144145145

146146

147147

148148149149 149D149D

149A149A149C149C

100A100A

100B100B

104E104E

104B104B 107B107B

107C107C 107A107A

110A110A

108A108A

ST12ST12

111A111A

112A112A 111B111B

115A115A

113A113A

122A122A

123123

149E149E 146B146B

146A146A

142A142A

140A140A

138A138A 139A139A

ST14ST14

135A135A

137A137A

133A133A

132B132B

132C132C

132A132A

131A131A

127A127A

127E127E

127B127B

128B128B

129A129A

127D127D

127C127C

ST13ST13

125F125F

125C125C

ST15ST15

125E125E

125D125D

125K125K

125J125J

125A125A

125B125B

125G125G

100100

104104

100C100C

TELECOM

ROOM

104A

ACTUAL: 63 SF

PROG: 170 SF

TYP.

NURSE

STATION

104104

A4

A

ALIGN

B

B

5' -0

9'

-8

A

A

6'-7 3/4"

M

IN

C

LR

3' -6

NURSE

STATION

104104

104A104A

TELECOM

ROOM

104A104A

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L E

H R

M .B

.A

R C

H .r v t

/1

/2

:3

:1

A

M

122A-401

ARCHITECTURAL ENLARGED VIEWS - FIRST

LEVEL

589A6-21-700

B122

01/19/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048

SCALE: 1/16" = 1'-0"

F3

FIRST LEVEL REFERENCE PLAN

1/4" = 1'-0" C7

ARCHITECTURAL ENLARGED FLOOR PLAN -

FIRST LEVEL - ROOM 104A - NEW

1 REMOVE EXISTING DOOR AND FRAME. INFILL OPENING TO MATCH

ADJACENT CONSTRUCTION AND FINISH FOR CONTINUOUS SURFACE.

2 REMOVE EXISTING WALL AND FRAMING.

3 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL

PENETRATIONS AS NECESSARY.

4 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE DOOR

AND FRAME WITH ACCESS CONTROL HARDWARE.

5 PROVIDE NEW DOOR AND FRAME IN EXISTING OPENING

6 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C

FIRE EXTINGUISHER LOCATED NO GREATER THAN 75 FEET AWAY

FROM THE NEW TR. CONTRACTOR TO COORDINATE THE NEW

LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW FEC FOR

EACH TR IN THE SCOPE OF WORK. SEE SPECIFICATION 10 44 13.

7 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

8 RELOCATE MEDICAL GAS

9 TEMPORARY WALLS FOR ICRA ENCLOSURE - SCHEDULE WORK WITH

COR WHEN STAFF DOES NOT REQUIRE ACCESS TO ROOMS 104, 104B

AND 104E

10 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE

11 SEAL ALL DOORS INTO WORK AREA WITH PLASTIC SHEET WITH

TAPED EDGES

Revisions: Date:

ASI 1 04/14/22

1/4" = 1'-0" C5

ARCHITECTURAL ENLARGED FLOOR PLAN -

FIRST LEVEL - ROOM 104A - DEMO

1/4" = 1'-0" C4

ARCHITECTURAL RCP - FIRST LEVEL

- ROOM 104A - NEW

1/4" = 1'-0"

C2

ARCHITECTURAL RCP - FIRST LEVEL

- ROOM 104A - DEMO

04/18/22

/18

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

204A204A

122A-402

C8

202202

202A202A

202B202B

202C202C202D202D202E202E

205205

206A206A

206B206B

206206

207207

209A209A

207A207A

208208

209209

ST22ST22

201B201B

210210

210A210A

211A211A

211211

212212

215215

214A214A

213213

214214

216216

214B214B

201A201A

217217

218218 219219

220220

220A220A

ST21ST21

221221

222222

223223224224

223C223C

226A226A

226B226B 227227

226226

225225

224224

228228

229229

200C200C

230230

229B229B

231231

232232

232A232A

233233

234234

235235

236236

237237

238A238A

238238

240240

240A240A

241A241A

241241

241B241B

242242

201C201C

243243

243A243A

244244

245245 247247

247A247A

245A245A

246246

ST24ST24

248248

249A249A 248A248A

249249 250250

250A250A

252A252A

251251

252252

253253

254254

256256

256A256A

255255

257257

260260

TELECOM

ROOM

202F

ACTUAL: 97 SF

204A204A

TYP.

TELECOM

ROOM

202F

ACTUAL: 97 SF

F

A4

B

B

B

6'-11 1/4"

CLEAR

4'-4 3/4"

M

IN

C

LR

3' -6

1'-6"

1'-6"

202F202F

204A204A

TELECOM

ROOM

202F

ACTUAL: 97 SF

204A204A

202F202F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L E

H R

M .B

.A

R C

H .r v t

/1

/2

:3

:1

A

M

122A-402

ARCHITECTURAL ENLARGED VIEWS - SECOND

LEVEL

589A6-21-700

B122

01/19/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048

1 REMOVE EXISTING DOOR AND FRAME. INFILL OPENING TO MATCH

ADJACENT CONSTRUCTION AND FINISH FOR CONTINUOUS

SURFACE.

2 REMOVE EXISTING WALL AND FRAMING.

3 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE

2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75

FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE

THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A

NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE

SPECIFICATION 10 44 13.

4 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL

PENETRATIONS AS NECESSARY.

5 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE

DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.

7 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

8 REMOVE PORTION OF NURSES STATION TO ALLOW CLEARANCE

FOR NEW TELECOM ROOM. CONTRACTOR TO COORDINATE WITH

COR.

9 PROVIDE NEW WALL AND DOOR TO CLOSE OFF NURSE STATION

FROM CORRIDOR. SEE DOOR SCHEDULE AND SPECIFICATIONS

FOR ADDITIONAL INFORMATION. COORDINATE WITH COR.

10 RELOCATE MEDICAL GAS LINES

11 TEMPORARY WALLS FOR ICRA ENCLOSURE - SCHEDULE WORK

WITH COR WHEN STAFF DOES NOT REQUIRE ACCESS TO ROOMS

202E

12 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE

13 SEAL ALL DOORS INTO WORK AREA WITH PLASTIC SHEET WITH

TAPED EDGES

1/16" = 1'-0" F3

SECOND LEVEL REFERENCE PLAN

1/4" = 1'-0" C8

ARCHITECTURAL ENLARGED FLOOR PLAN -

SECOND LEVEL - ROOM 202F - NEW

Revisions: Date:

ASI 1 04/14/22

1/4" = 1'-0" C6

ARCHITECTURAL ENLARGED FLOOR PLAN -

SECOND LEVEL - ROOM 202F - DEMO

1/4" = 1'-0" C5

ARCHITECTURAL RCP - SECOND

LEVEL - ROOM 202F - NEW

1/4" = 1'-0"

C3

ARCHITECTURAL RCP - SECOND

LEVEL - ROOM 202F - DEMO

04/18/22

/18

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

122A-403

C8

300300

302302

303303

304304

305305

306306307307

308308

309309

310310

311311

312312

313313

314314

315315 316316 317317

318318

319319 320320

322322

323323

324324

325325

326326

327327

328328

329329

330330

331331 332332

333333

334334

335335

336336

337337

338338

339339

340340

341341

342342

343343

344344

345345

346346

347347

349349

350350

351351352352

353353

354354

355355

356356357357

358358

302A302A

302B302B

302C302C

302D302D

302E302E

ST31ST31

323A323A 323B323B

323C323C

327A327A

327B327B

329A329A

329B329B

330A330A 330B330B

ST33ST33

334A334A

337A337A

337B337B

337C337C

340A340A

340B340B

B3-E2B3-E2

B3-E1B3-E1 342A342A

343A343A

343B343B

345A345A 349A349A

348348

347A347A

ST34ST34

351A351A 350A350A

354A354A

352A352A 306A306A

306B306B 307A307A

309A309A

ST32ST32

311A311A310A310A

312A312A

314A314A

321321

320A320A

TELECOM

ROOM

302F

100 SF

TELECOM

ROOM

302F

ACTUAL: 100 SF

F

TYP.

B

A4

A

B

1'-6" MIN.

C

LR

M

IN

3' -6

1'-6"

2'-0"

302F302F

304304

TELECOM

ROOM

302F

ACTUAL: 100 SF

302F302F

302302

304304

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L E

H R

M .B

.A

R C

H .r v t

/1

/2

:3

:1

A

M

122A-403

ARCHITECTURAL ENLARGED VIEWS - THIRD

LEVEL

589A6-21-700

B122

01/19/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048

1/16" = 1'-0" F3

THIRD LEVEL REFERENCE PLAN

1/4" = 1'-0" C8

ARCHITECTURAL ENLARGED FLOOR PLAN -

THIRD LEVEL - ROOM 302F - NEW

1 REMOVE EXISTING DOOR AND FRAME. INFILL OPENING TO MATCH

ADJACENT CONSTRUCTION AND FINISH FOR CONTINUOUS

SURFACE.

2 REMOVE EXISTING WALL AND FRAMING.

3 PROVIDENEW FIRE EXTINGUISHER CABINET WITH A TYPE

2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75

FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE

THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A

NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE

SPECIFICATION 10 44 13.

4 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL

PENETRATIONS AS NECESSARY.

5 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE

DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.

7 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

8 REMOVE EXISTING GLASS BLOCK WINDOW. INFILL OPENING TO

MATCH ADJACENT CONSTRUCTION AND FINISH FOR CONTINUOUS

SURFACE.

9 PROVIDE NEW WALL AND DOOR TO CLOSE OFF NURSE STATION

FROM CORRIDOR. SEE DOOR SCHEDULE AND SPECIFICATIONS

FOR ADDITIONAL INFORMATION. COORDINATE WITH COR.

10 RELOCATE MEDICAL GAS LINES

11 TEMPORARY WALLS FOR ICRA ENCLOSURE - SCHEDULE WORK

WITH COR WHEN STAFF DOES NOT REQUIRE ACCESS TO ROOMS

302E

12 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE

13 SEAL ALL DOORS INTO WORK AREA WITH PLASTIC SHEET WITH

TAPED EDGES

Revisions: Date:

ASI 1 04/14/22

1/4" = 1'-0" C6

ARCHITECTURAL ENLARGED FLOOR PLAN -

THIRD LEVEL - ROOM 302F - DEMO

1/4" = 1'-0" B8

ARCHITECTURAL RCP - THIRD LEVEL

- ROOM 302F - NEW

1/4" = 1'-0"

B6

ARCHITECTURAL RCP - THIRD LEVEL

- ROOM 302F - DEMO

04/18/22

/18

Sheets
122A-400 - ARCHITECTURAL ENLARGED VIEWS - BASEMENT LEVEL
122A-401 - ARCHITECTURAL ENLARGED VIEWS - FIRST LEVEL
122A-402 - ARCHITECTURAL ENLARGED VIEWS - SECOND LEVEL
122A-403 - ARCHITECTURAL ENLARGED VIEWS - THIRD LEVEL