This solicitation is for a construction contract to prepare a VA medical campus for Electronic Health Record Modernization upgrades by replacing all telecommunications cabling and equipment across multiple buildings. The scope of work includes replacing existing copper, fiber and wireless cabling one-for-one with CAT6A, OM4 and OS-2 fiber, along with associated patch panels, racks and ladder racks. An additional 15% capacity must be provided. The contractor must also install new computer room air conditioning systems, electrical panels and backup generators. A new 600 ton water cooled chiller and pump will be installed in Building 161 to serve new telecom rooms. The solicitation was issued by the VA Technology Acquisition Center in Austin, Texas. Bids are due by the date specified in the solicitation number listed.
View the file
Other files
Show 40 more
Latest 50 of 67 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH
THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS
STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
1/2" 1/2"
VARIES
SEE PLAN
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND,
TYP.
HOLLOW METAL
FRAME
/2
V
A R
IE
S
S E
E P
L A
N
/2
4" 2"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL
FRAME
WALL - SEE PLAN
FOR TYPE
F4
TYPICAL FRAME
H E
IG
H
T
2" WIDTH 2"
F5
FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS
F
FLUSH
F2
TELECOM
ROOM
B4B4
122A-400
D7
CRAWL SPACE
B7DB7D
B7B7
B7AB7A
B7BB7B
B7CB7C
B9B9
B10B10
B2AB2A
STB2STB2
B5BB5B
B6B6
B2B2
B11B11
B11AB11A B11BB11B
B13CB13C
B12EB12E B13BB13B
B13GB13G
B13DB13D
B13AB13A
B13B13 B13HB13H
B14B14
PT CLINIC
B5B5B5AB5A
B18B18B19B19
B3B3
B15B15
STB1STB1
B17B17
B0-E2B0-E2
B0-E1B0-E1
B4AB4A
B1B1
TELECOM
ROOM
B4
ACTUAL: 55 SF
PROG: 170 SF
B B
B
B
TYP.
5' -9
/8
9'-4 7/8"
B
6' -0
/8
9 10
ACOUSTICAL OR RATED
SEALANT BOTH SIDES
FLOOR LINE
5/8" GWB BOTH SIDES
SOUND ATTENUATION
BATTS (SAB) PER
SCHEDULE.
CEILING LINE
STRUCTURAL DECK
METAL STUDS, SIZE
PER SCHEDULE
122A-512
D5
A/C GRADE, 3/4" FIRE-
TREATED PLYWOOD TO 8'-0"
ABOVE FINISHED FLOOR
122A-512
B5
AT FIRE RATED
PARTITIONS
AT SMOKE RATED
PARTITIONS
BOTTOM OF PLYWOOD TO
BE AT 12" AFF
ACOUSTICAL OR RATED
FLEXIBLE SEALANT
FLOOR LINE
ADD ONE LAYER OF 5/8" GWB,
ONE-SIDE WITH APPROVED UL
SETTING COMPOUND BETWEEN
LAYERS AND FASTENED TO
WALL AS REQUIRED, AT
EXISTING GWB WALL
ASSEMBLIES
STRUCTURAL DECK
EXISTING METAL STUDS AND
BATT INSULATION TO REMAIN
A/C GRADE, 3/4" FIRE-TREATED
PLYWOOD TO 8'-0" ABOVE FINISHED
FLOOR, ADHERED TO CONCRETE AT
EXISTING CONCRETE WALL
ASSEMBLIES
BOTTOM OF PLYWOOD
TO BE AT 12" AFF
UL DESIGN V497
1-HOUR PARTITION RATED FROM BOTH SIDES
EXISTING GWB OR
CONCRETE WALL
ASSEMBLY, WHERE OCCURS
SIDE OF
EXISTING
ROOM OR
CORRIDOR TO
REMAIN
122A-512
D5
122A-512
B5
B4B4
C
LR
M
IN
3' -0
9 10
TELECOM
ROOM
B4B4
8B4B4
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.A
R C
H .r v t
/1
/2
:3
:1
A
M
122A-400
ARCHITECTURAL ENLARGED VIEWS - BASEMENT
LEVEL
589A6-21-700
B122
01/19/2022 M. Perkins K. Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
3" = 1'-0" C1
HOLLOW METAL HEAD DETAIL
3" = 1'-0" D1
HOLLOW METAL JAMB DETAIL
1/4" = 1'-0" F1
WRAPPED FRAME TYPES ELEVATIONS
1 REMOVE EXISTING DOOR AND FRAM
2 NEW SMOKE RATED DOOR
3 REMOVE FLOORING AND WALL BASE IN ROOM.
4 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL
PENETRATIONS AS NECESSARY.
5 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C
FIRE EXTINGUISHER LOCATED NO GREATER THAN 75 FEET AWAY
FROM THE NEW TR. CONTRACTOR TO COORDINATE THE NEW
LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW FEC FOR
EACH TR IN THE SCOPE OF WORK. SEE SPECIFICATION 10 44 13.
6 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE
DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.
7 REMOVE EXISTING LIGHT. MODIFY AND/OR PROVIDE ADDITIONAL
SUPPORTS AS REQUIRED FOR EXISTING CEILING ITEMS TO REMAIN.
8 TELECOM ROOM TO BE OPEN TO DECK ABOVE.
9 TEMPORARY WALLS FOR ICRA ENCLOSURE
10 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE
Revisions: Date:
ASI 1 04/14/22
1/16" = 1'-0" F3
BASEMENT REFERENCE PLAN
1/4" = 1'-0" D7
ARCHITECTURAL ENLARGED FLOOR PLAN -
BASEMENT LEVEL - ROOM B4 - NEW
1 1/2" = 1'-0" D6
1-HOUR WALL
1 1/2" = 1'-0"
D3
1-HOUR WALL
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL
U465
(TYPE A) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
A3 3 5/8" 4 7/8" 35
A4 4" 5 1/4" 35
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V438, UL U411
(TYPE B) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
B 2 1/2" 3/4" 45
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL
FIRE RATING
HARDWARE
NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL
BASEMENT B4 TELECOM ROOM B4 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-9 SEE ELEC
LEVEL 1 104A TELECOM ROOM 104A 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC
LEVEL 1 104 NURSE STATION 104 3' - 6" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD HW-SH-3D SEE ELEC
LEVEL 2 202F TELECOM ROOM 202F 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC
LEVEL 3 302F TELECOM ROOM 302F 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC
1/4" = 1'-0" D5
ARCHITECTURAL ENLARGED FLOOR PLAN -
BASEMENT LEVEL - ROOM B4 - DEMO
1/4" = 1'-0" C7
ARCHITECTURAL RCP - BASEMENT LEVEL -
ROOM B4 - NEW
1/4" = 1'-0"
C5
ARCHITECTURAL RCP - BASEMENT LEVEL -
ROOM B4 - DEMO
04/18/22
/18
/20
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH
THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS
STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
TELECOM
ROOM
104A
63 SF
122A-401
C7
101101 102102
104104
105105 106106
107107
108108
109109
110110111111
112112
113113
114114
115115
116116
117117
118118
119119
120120
121121 122122
ST11ST11
124124
125125
126126
127127
128A128A
129129
130130
131131
132132
133133
134134
135135
136136
137137
138138
139139140140
141141
142142143143
144144145145
146146
147147
148148149149 149D149D
149A149A149C149C
100A100A
100B100B
104E104E
104B104B 107B107B
107C107C 107A107A
110A110A
108A108A
ST12ST12
111A111A
112A112A 111B111B
115A115A
113A113A
122A122A
123123
149E149E 146B146B
146A146A
142A142A
140A140A
138A138A 139A139A
ST14ST14
135A135A
137A137A
133A133A
132B132B
132C132C
132A132A
131A131A
127A127A
127E127E
127B127B
128B128B
129A129A
127D127D
127C127C
ST13ST13
125F125F
125C125C
ST15ST15
125E125E
125D125D
125K125K
125J125J
125A125A
125B125B
125G125G
100100
104104
100C100C
TELECOM
ROOM
104A
ACTUAL: 63 SF
PROG: 170 SF
TYP.
NURSE
STATION
104104
A4
A
ALIGN
B
B
5' -0
9'
-8
A
A
6'-7 3/4"
M
IN
C
LR
3' -6
NURSE
STATION
104104
104A104A
TELECOM
ROOM
104A104A
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.A
R C
H .r v t
/1
/2
:3
:1
A
M
122A-401
ARCHITECTURAL ENLARGED VIEWS - FIRST
LEVEL
589A6-21-700
B122
01/19/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
SCALE: 1/16" = 1'-0"
F3
FIRST LEVEL REFERENCE PLAN
1/4" = 1'-0" C7
ARCHITECTURAL ENLARGED FLOOR PLAN -
FIRST LEVEL - ROOM 104A - NEW
1 REMOVE EXISTING DOOR AND FRAME. INFILL OPENING TO MATCH
ADJACENT CONSTRUCTION AND FINISH FOR CONTINUOUS SURFACE.
2 REMOVE EXISTING WALL AND FRAMING.
3 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL
PENETRATIONS AS NECESSARY.
4 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE DOOR
AND FRAME WITH ACCESS CONTROL HARDWARE.
5 PROVIDE NEW DOOR AND FRAME IN EXISTING OPENING
6 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C
FIRE EXTINGUISHER LOCATED NO GREATER THAN 75 FEET AWAY
FROM THE NEW TR. CONTRACTOR TO COORDINATE THE NEW
LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW FEC FOR
EACH TR IN THE SCOPE OF WORK. SEE SPECIFICATION 10 44 13.
7 TELECOM ROOM TO BE OPEN TO DECK ABOVE.
8 RELOCATE MEDICAL GAS
9 TEMPORARY WALLS FOR ICRA ENCLOSURE - SCHEDULE WORK WITH
COR WHEN STAFF DOES NOT REQUIRE ACCESS TO ROOMS 104, 104B
AND 104E
10 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE
11 SEAL ALL DOORS INTO WORK AREA WITH PLASTIC SHEET WITH
TAPED EDGES
Revisions: Date:
ASI 1 04/14/22
1/4" = 1'-0" C5
ARCHITECTURAL ENLARGED FLOOR PLAN -
FIRST LEVEL - ROOM 104A - DEMO
1/4" = 1'-0" C4
ARCHITECTURAL RCP - FIRST LEVEL
- ROOM 104A - NEW
1/4" = 1'-0"
C2
ARCHITECTURAL RCP - FIRST LEVEL
- ROOM 104A - DEMO
04/18/22
/18
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH
THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS
STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
204A204A
122A-402
C8
202202
202A202A
202B202B
202C202C202D202D202E202E
205205
206A206A
206B206B
206206
207207
209A209A
207A207A
208208
209209
ST22ST22
201B201B
210210
210A210A
211A211A
211211
212212
215215
214A214A
213213
214214
216216
214B214B
201A201A
217217
218218 219219
220220
220A220A
ST21ST21
221221
222222
223223224224
223C223C
226A226A
226B226B 227227
226226
225225
224224
228228
229229
200C200C
230230
229B229B
231231
232232
232A232A
233233
234234
235235
236236
237237
238A238A
238238
240240
240A240A
241A241A
241241
241B241B
242242
201C201C
243243
243A243A
244244
245245 247247
247A247A
245A245A
246246
ST24ST24
248248
249A249A 248A248A
249249 250250
250A250A
252A252A
251251
252252
253253
254254
256256
256A256A
255255
257257
260260
TELECOM
ROOM
202F
ACTUAL: 97 SF
204A204A
TYP.
TELECOM
ROOM
202F
ACTUAL: 97 SF
F
A4
B
B
B
6'-11 1/4"
CLEAR
4'-4 3/4"
M
IN
C
LR
3' -6
1'-6"
1'-6"
202F202F
204A204A
TELECOM
ROOM
202F
ACTUAL: 97 SF
204A204A
202F202F
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.A
R C
H .r v t
/1
/2
:3
:1
A
M
122A-402
ARCHITECTURAL ENLARGED VIEWS - SECOND
LEVEL
589A6-21-700
B122
01/19/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
1 REMOVE EXISTING DOOR AND FRAME. INFILL OPENING TO MATCH
ADJACENT CONSTRUCTION AND FINISH FOR CONTINUOUS
SURFACE.
2 REMOVE EXISTING WALL AND FRAMING.
3 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE
2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE
THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A
NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE
SPECIFICATION 10 44 13.
4 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL
PENETRATIONS AS NECESSARY.
5 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE
DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.
7 TELECOM ROOM TO BE OPEN TO DECK ABOVE.
8 REMOVE PORTION OF NURSES STATION TO ALLOW CLEARANCE
FOR NEW TELECOM ROOM. CONTRACTOR TO COORDINATE WITH
COR.
9 PROVIDE NEW WALL AND DOOR TO CLOSE OFF NURSE STATION
FROM CORRIDOR. SEE DOOR SCHEDULE AND SPECIFICATIONS
FOR ADDITIONAL INFORMATION. COORDINATE WITH COR.
10 RELOCATE MEDICAL GAS LINES
11 TEMPORARY WALLS FOR ICRA ENCLOSURE - SCHEDULE WORK
WITH COR WHEN STAFF DOES NOT REQUIRE ACCESS TO ROOMS
202E
12 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE
13 SEAL ALL DOORS INTO WORK AREA WITH PLASTIC SHEET WITH
TAPED EDGES
1/16" = 1'-0" F3
SECOND LEVEL REFERENCE PLAN
1/4" = 1'-0" C8
ARCHITECTURAL ENLARGED FLOOR PLAN -
SECOND LEVEL - ROOM 202F - NEW
Revisions: Date:
ASI 1 04/14/22
1/4" = 1'-0" C6
ARCHITECTURAL ENLARGED FLOOR PLAN -
SECOND LEVEL - ROOM 202F - DEMO
1/4" = 1'-0" C5
ARCHITECTURAL RCP - SECOND
LEVEL - ROOM 202F - NEW
1/4" = 1'-0"
C3
ARCHITECTURAL RCP - SECOND
LEVEL - ROOM 202F - DEMO
04/18/22
/18
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH
THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS
STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
122A-403
C8
300300
302302
303303
304304
305305
306306307307
308308
309309
310310
311311
312312
313313
314314
315315 316316 317317
318318
319319 320320
322322
323323
324324
325325
326326
327327
328328
329329
330330
331331 332332
333333
334334
335335
336336
337337
338338
339339
340340
341341
342342
343343
344344
345345
346346
347347
349349
350350
351351352352
353353
354354
355355
356356357357
358358
302A302A
302B302B
302C302C
302D302D
302E302E
ST31ST31
323A323A 323B323B
323C323C
327A327A
327B327B
329A329A
329B329B
330A330A 330B330B
ST33ST33
334A334A
337A337A
337B337B
337C337C
340A340A
340B340B
B3-E2B3-E2
B3-E1B3-E1 342A342A
343A343A
343B343B
345A345A 349A349A
348348
347A347A
ST34ST34
351A351A 350A350A
354A354A
352A352A 306A306A
306B306B 307A307A
309A309A
ST32ST32
311A311A310A310A
312A312A
314A314A
321321
320A320A
TELECOM
ROOM
302F
100 SF
TELECOM
ROOM
302F
ACTUAL: 100 SF
F
TYP.
B
A4
A
B
1'-6" MIN.
C
LR
M
IN
3' -6
1'-6"
2'-0"
302F302F
304304
TELECOM
ROOM
302F
ACTUAL: 100 SF
302F302F
302302
304304
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.A
R C
H .r v t
/1
/2
:3
:1
A
M
122A-403
ARCHITECTURAL ENLARGED VIEWS - THIRD
LEVEL
589A6-21-700
B122
01/19/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
1/16" = 1'-0" F3
THIRD LEVEL REFERENCE PLAN
1/4" = 1'-0" C8
ARCHITECTURAL ENLARGED FLOOR PLAN -
THIRD LEVEL - ROOM 302F - NEW
1 REMOVE EXISTING DOOR AND FRAME. INFILL OPENING TO MATCH
ADJACENT CONSTRUCTION AND FINISH FOR CONTINUOUS
SURFACE.
2 REMOVE EXISTING WALL AND FRAMING.
3 PROVIDENEW FIRE EXTINGUISHER CABINET WITH A TYPE
2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE
THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A
NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE
SPECIFICATION 10 44 13.
4 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL
PENETRATIONS AS NECESSARY.
5 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE
DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.
7 TELECOM ROOM TO BE OPEN TO DECK ABOVE.
8 REMOVE EXISTING GLASS BLOCK WINDOW. INFILL OPENING TO
MATCH ADJACENT CONSTRUCTION AND FINISH FOR CONTINUOUS
SURFACE.
9 PROVIDE NEW WALL AND DOOR TO CLOSE OFF NURSE STATION
FROM CORRIDOR. SEE DOOR SCHEDULE AND SPECIFICATIONS
FOR ADDITIONAL INFORMATION. COORDINATE WITH COR.
10 RELOCATE MEDICAL GAS LINES
11 TEMPORARY WALLS FOR ICRA ENCLOSURE - SCHEDULE WORK
WITH COR WHEN STAFF DOES NOT REQUIRE ACCESS TO ROOMS
302E
12 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE
13 SEAL ALL DOORS INTO WORK AREA WITH PLASTIC SHEET WITH
TAPED EDGES
Revisions: Date:
ASI 1 04/14/22
1/4" = 1'-0" C6
ARCHITECTURAL ENLARGED FLOOR PLAN -
THIRD LEVEL - ROOM 302F - DEMO
1/4" = 1'-0" B8
ARCHITECTURAL RCP - THIRD LEVEL
- ROOM 302F - NEW
1/4" = 1'-0"
B6
ARCHITECTURAL RCP - THIRD LEVEL
- ROOM 302F - DEMO
04/18/22
/18
| Sheets |
| 122A-400 - ARCHITECTURAL ENLARGED VIEWS - BASEMENT LEVEL |
| 122A-401 - ARCHITECTURAL ENLARGED VIEWS - FIRST LEVEL |
| 122A-402 - ARCHITECTURAL ENLARGED VIEWS - SECOND LEVEL |
| 122A-403 - ARCHITECTURAL ENLARGED VIEWS - THIRD LEVEL |
File details come from the government source that posted it. Updated .