589A6-21-700.LEHRM.ASI-001.B71.20220418.pdf

PDF 1 MB Posted

Attached to
Y1DZ--589A6-21-700 EHRM Infrastructure Upgrades Construction Leavenworth VAMC
Solicitation number
36C77622R0061
Issued by

About this file

This solicitation is for infrastructure upgrades at the Leavenworth VA Medical Center campus to prepare for Electronic Health Record Modernization. The scope of work includes replacing all telecommunications cabling in multiple buildings, including installing smoke-rated OM4 fiber for intra-building runs and OS-2 fiber for inter-building runs. Copper replacement will be CAT6A to support 1GbE connectivity to all desktops and equipment. The contractor must provide 15% additional capacity over existing circuits and terminate all cables. Additional requirements include installing new patch panels, racks, ladder racks, and labeling all components according to specifications. The project also involves adding new computer room air conditioning systems, electrical panels, backup generators, and a new 600-ton water-cooled chiller. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center in Austin.

View the file

Other files

File Type Posted
01 00 00 Appendix A - Bid Form Template.20220505.xlsx XLSX spreadsheet
36C77622R0061 0004.pdf PDF
01 00 00 Appendix A - Bid Form Template.20220505.pdf PDF
Follow Up Technical Questions Tracking Spreadsheet - 5-5-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links - Rev01.pdf PDF
36C77622R0061 0003.pdf PDF
01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
589A6-21-700.LEHRM.ASI-001.B54.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B161.20220418.pdf PDF
Site Visit Attendance Sheet - LV EHRM Infra 4-11-22.pdf PDF
TR Space Impact - Leavenworth.pdf PDF
Technical Questions Tracking Spreadsheet - 4-27-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links.pdf PDF
B7 Electrical Panel Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.SITE.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B42.20220418.pdf PDF
Attachment 14 - DBA Wage Rates - Leavenworth County - 4-15-22.pdf PDF
Unitary Disconnect Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.B41.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B39.20220418.pdf PDF
Attachment 17 - Rev Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
01 00 00 Appendix A - Bid Form Template.pdf PDF
Unitary Cooling Photos.zip ZIP file
21 22 00 - Clean Agent Fire Suppression Systems.pdf PDF
23 64 00 - Packaged Water Chillers.ASI001.pdf PDF
589A6-21-700.LEHRM.ASI-001.B153.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.Summary.Log.20220419.pdf PDF
B88.89.90.91 Photos.zip ZIP file
Panel Photos.zip ZIP file
UPS Data Photos.zip ZIP file
589A6-21-700.LEHRM.IFC_R1.B39.20220119.pdf PDF
589A6-21-700.LEHRM.ASI-001.B21.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B160.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B122.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B90.20220419.pdf PDF
36C77622R0061 Amendment 0002.pdf PDF
36C77622R0061 Amendment 0001.pdf PDF
RFP 36C77622R0061.pdf PDF
Attachment 10 - 589A6-21-700 LEHRM IFC_R1 B161 Drawing.pdf PDF
Attachment 17 - Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment 4 - 589A6-21-700 LEHRM IFC_R1 B54 Drawing.pdf PDF
Attachment 3 - 589A6-21-700 LEHRM IFC_R1 B42 Drawing.pdf PDF
Attachment 18 - VA Notice of Limitations on Subcontracting-Certificate of Compliance.docx DOCX document
Attachment 13 - Asbestos Report Part 2 of 7.zip ZIP file
Attachment 5 - 589A6-21-700 LEHRM IFC_R1 B71 Part 1 of 2 Drawing.pdf PDF
Attachment 7 - 589A6-21-700 LEHRM IFC_R1 B122 Drawing.pdf PDF
Attachment 2 - 589A6-21-700 LEHRM IFC_R1 B41 Drawing.pdf PDF
Attachment 13 - Asbestos Report Part 4 of 7.zip ZIP file
Attachment 13 - Asbestos Report Part 5 of 7.zip ZIP file
Attachment 6 - 589A6-21-700 LEHRM IFC_R1 B88-89-90-91 Part 3 of 3 Drawing.pdf PDF
Show 40 more

Latest 50 of 67 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

1/2" 1/2"

VARIES

SEE PLAN

WALL - SEE PLAN

FOR TYPE

SEALANT - EA. SIDE

& ALL AROUND,

TYP.

HOLLOW METAL

FRAME

/2

V

A R

IE

S

S E

E P

L A

N

/2

4" 2"

ADJACENT WALL

WHERE OCCURS

SEALANT - EA SIDE &

ALL AROUND, TYP.

HOLLOW METAL

FRAME

WALL - SEE PLAN

FOR TYPE

F4

TYPICAL FRAME

H E

IG

H

T

2" WIDTH 2"

F5

FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS

F

FLUSH

F2

71A-400

D8

TELECOM

ROOM

15B15B

71A-400

D7

B

B

B

STORAGE

A

A4

B

TELECOM

ROOM

15B

ACTUAL: 109 SF

PROG: 170 SF

11'-0 1/8"

9' -1

7/

8"

71A-400

D6

TELECOM

ROOM

69 SF

71A-400

D4

TELECOM

ROOM

ACTUAL: 69 SF

PROG: 170 SF

A 4 B

B

B

B

B

B

(EXT'G VIF)

11'-4 3/8"(E

X T

'G V

IF

6' -5

/8

15B15B

3' -6

1'-0"

14110110

TELECOM

ROOM

110110

110110

TELECOM

ROOM

15B15B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L

E H

R M

.B

.A

R C

H .r v t

/1

/2

:1

:5

P

M

71A-400

ARCHITECTURAL ENLARGED VIEWS - BASEMENT

& FIRST LEVELS

589A6-21-700

B71

01/19/2022 M. Perkins K. Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048

3" = 1'-0" C1

HOLLOW METAL HEAD DETAIL

3" = 1'-0"

C2

HOLLOW METAL JAMB DETAIL

1/4" = 1'-0" B1

WRAPPED FRAME TYPES ELEVATIONS

1 REMOVE EXISTING WALL AND FRAMING.

2 REMOVE EXISTING DOOR AND FRAME.

3 REMOVE FLOORING AND WALL BASE IN ROOM.

4 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL

PENETRATIONS AS NECESSARY.

6 NEW SMOKE-RATED DOOR.

7 REMOVE EXISTING ACOUSTICAL CEILING AND LIGHTS. MODIFY

AND/OR PROVIDE ADDITIONAL SUPPORTS AS REQUIRED FOR

EXISTING CEILING ITEMS TO REMAIN.

8 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

9 INFILL ACOUSTICAL CEILING AS REQUIRED.

10 NEW FURRING WALL AT EXTERIOR WALL TO ENCLOSE WINDOW.

MAINTAIN 1/2" GAP BETWEEN EXISTING WALL INTERIOR FACE AND

NEW STUDS. MODIFY/ REMOVE INTERIOR WINDOW TRIM AS

REQUIRED.

11 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C

FIRE EXTINGUISHER LOCATED NO GREATER THAN 75 FEET AWAY

FROM THE NEW TR. CONTRACTOR TO COORDINATE THE NEW

LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW FEC

FOR EACH TR IN THE SCOPE OF WORK. SEE SPECIFICATION 10 44

13.

12 PROVIDE TEMPORARY AIR TIGHT BARRIER AROUND WORK AREA

DURING AND ACTIVITIES WHICH PRODUCE DUST - TYPICAL

13 TEMPORARY WALLS FOR ICRA ENCLOSURE

14 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE

1/16" = 1'-0" F5

BASEMENT REFERENCE PLAN

1/4" = 1'-0" D8

ARCHITECTURAL ENLARGED FLOOR PLAN -

BASEMENT LEVEL - ROOM 15B - NEW

1/16" = 1'-0" F1

FIRST LEVEL REFERENCE PLAN

1/4" = 1'-0" D6

ARCHITECTURAL ENLARGED FLOOR PLAN -

FIRST LEVEL - ROOM 110 - NEW

DOOR AND FRAME SCHEDULE

IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL

FIRE RATING

HARDWARE

NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL

BASEMENT 15B TELECOM ROOM 15B 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-3F SEE ELEC

LEVEL 1 110 TELECOM ROOM 110 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-3F SEE ELEC

LEVEL 2 212B TELECOM ROOM 212B 2' - 10" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-3F SEE ELEC

LEVEL 3 312B TELECOM ROOM 312B 2' - 10" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-3F SEE ELEC

1/4" = 1'-0" D7

ARCHITECTURAL ENLARGED FLOOR PLAN -

BASEMENT LEVEL - ROOM 15B - DEMO

1/4" = 1'-0" D4

ARCHITECTURAL ENLARGED FLOOR PLAN -

FIRST LEVEL - ROOM 110 - DEMO

1/4" = 1'-0" C6

ARCHITECTURAL RCP - FIRST LEVEL

- ROOM 110 - NEW

1/4" = 1'-0"

C4

ARCHITECTURAL RCP - FIRST LEVEL

- ROOM 110 - DEMO

1/4" = 1'-0"

C7

ARCHITECTURAL RCP - BASEMENT

LEVEL - ROOM 15B - DEMO

1/4" = 1'-0"

ARCHITECTURAL RCP - BASEMENT

LEVEL - ROOM 15B - NEW

Revisions: Date:

ASI 1 04/14/21

04/18/22

/18

/20

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

B

TELECOM

ROOM

212B

ACTUAL: 73 SF

PROG: 170 SF

A

4BB

B

B

B

(E X

T 'G

V

IF

6'

-5

/8

(EXT'G VIF)

12'-2 5/8"

71A-401

D8

200200

204A204A

239239 238238

237237 236236

205205 203203

202202

201201

233C233C 233233

232232

208208 207207

206206

231231 230230

209209

2-E12-E1

229229 228228

227227

213213 214214

226226 225225 224224

217217216216

211211

223223

221221222222

219219

218218 200C200C

212212

239A239A 239B239B

235235

237A237A

203A203A 201B201B

201A201A

240240

204C204C

233A233A

208A208A

231A231A

209A209A

213A213A 215215 217A217A

221A221A 221B221B

215A215A

219C219C 219A219A

200B200B

210210

71A-401

D4

300300 301301

302302

337337

338338

339339

336336 335335

303303 305305 306306

304304

307307 308308

309309

331331332332333333334334

310C310C 3-E13-E1

329329 330330

327327

310310 316316

326326

314314313313

325325 324324

315315 317317

319319

318318 320320

321321

322322

323323

312312

TELECOM

ROOM

312B312B

71A-401

D2

304A304A

339A339A

300B300B 302A302A

310A310A

337A337A 336A336A

303A303A 310B310B 307A307A 308A308A

309A309A

333A333A

313A313A312A312A

325A325A

314A314A 317A317A 318A318A

319A319A 320A320A

316A316A

321A321A

323A323A

TELECOM

ROOM

312B

ACTUAL: 70 SF

PROG: 170 SF

B

BB

B

B

(E X

T 'G

V

IF

6'

-6

/2

(EXT'G VIF)

12'-1"

312B312B

1 2

212B212B

1 2

TELECOM

ROOM

212B212B

212B212B

TELECOM

ROOM

312B312B

312B312B

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L

E H

R M

.B

.A

R C

H .r v t

/1

/2

:1

:5

P

M

71A-401

ARCHITECTURAL ENLARGED VIEWS - SECOND &

THIRD LEVELS

589A6-21-700

B71

01/19/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048

1/4" = 1'-0" D8

ARCHITECTURAL ENLARGED FLOOR PLAN -

SECOND LEVEL - ROOM 212B - NEW

1/16" = 1'-0" F6

SECOND LEVEL REFERENCE PLAN

1/16" = 1'-0"

F2

THIRD LEVEL REFERENCE PLAN

1/4" = 1'-0" D4

ARCHITECTURAL ENLARGED FLOOR PLAN -

THIRD LEVEL - ROOM 312B - NEW

1 REMOVE EXISTING DOOR AND FRAME.

2 REMOVE PORTION OF EXISTING WALL AS REQUIRED FOR NEW

DOOR.

3 REMOVE FLOORING AND WALL BASE IN ROOM.

4 REMOVE EXISTING ACOUSTICAL CEILING AND LIGHTS. MODIFY

AND/OR PROVIDE ADDITIONAL SUPPORTS AS REQUIRED FOR

EXISTING CEILING ITEMS TO REMAIN.

5 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL

PENETRATIONS AS NECESSARY.

6 NEW SMOKE-RATED DOOR.

7 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

8 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE

2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75

FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE

THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A

NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE

SPECIFICATION 10 44 13.

9 PROVIDE TEMPORARY AIR TIGHT BARRIER AROUND WORK AREA

DURING AND ACTIVITIES WHICH PRODUCE DUST - TYPICAL

1/4" = 1'-0" D2

ARCHITECTURAL ENLARGED FLOOR PLAN -

THIRD LEVEL - ROOM 312B - DEMO

1/4" = 1'-0"

D6

ARCHITECTURAL ENLARGED FLOOR PLAN -

SECOND LEVEL - ROOM 212B - DEMO

1/4" = 1'-0" C8

ARCHITECTURAL RCP - SECOND LEVEL -

ROOM 212B - NEW

1/4" = 1'-0"

C6

ARCHITECTURAL RCP - SECOND LEVEL -

ROOM 212B - DEMO

1/4" = 1'-0"

C4

ARCHITECTURAL RCP - THIRD LEVEL

- ROOM 312B - NEW

1/4" = 1'-0"

C2

ARCHITECTURAL RCP - THIRD LEVEL

- ROOM 312B - DEMO

Revisions: Date:

ASI 1 04/14/2104/18/22

/18

/20

Sheets
71A-400 - ARCHITECTURAL ENLARGED VIEWS - BASEMENT & FIRST LEVELS
71A-401 - ARCHITECTURAL ENLARGED VIEWS - SECOND & THIRD LEVELS

File details come from the government source that posted it. Updated .