This solicitation is for infrastructure upgrades at the Leavenworth VA Medical Center campus to prepare for Electronic Health Record Modernization. The scope of work includes replacing all telecommunications cabling in multiple buildings, including installing smoke-rated OM4 fiber for intra-building runs and OS-2 fiber for inter-building runs. Copper replacement will be CAT6A to support 1GbE connectivity to all desktops and equipment. The contractor must provide 15% additional capacity over existing circuits and terminate all cables. Additional requirements include installing new patch panels, racks, ladder racks, and labeling all components according to specifications. The project also involves adding new computer room air conditioning systems, electrical panels, backup generators, and a new 600-ton water-cooled chiller. The solicitation was issued by the Department of Veterans Affairs Technology Acquisition Center in Austin.
View the file
Other files
Show 40 more
Latest 50 of 67 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH
THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS
STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
1/2" 1/2"
VARIES
SEE PLAN
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND,
TYP.
HOLLOW METAL
FRAME
/2
V
A R
IE
S
S E
E P
L A
N
/2
4" 2"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL
FRAME
WALL - SEE PLAN
FOR TYPE
F4
TYPICAL FRAME
H E
IG
H
T
2" WIDTH 2"
F5
FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS
F
FLUSH
F2
71A-400
D8
TELECOM
ROOM
15B15B
71A-400
D7
B
B
B
STORAGE
A
A4
B
TELECOM
ROOM
15B
ACTUAL: 109 SF
PROG: 170 SF
11'-0 1/8"
9' -1
7/
8"
71A-400
D6
TELECOM
ROOM
69 SF
71A-400
D4
TELECOM
ROOM
ACTUAL: 69 SF
PROG: 170 SF
A 4 B
B
B
B
B
B
(EXT'G VIF)
11'-4 3/8"(E
X T
'G V
IF
6' -5
/8
15B15B
3' -6
1'-0"
14110110
TELECOM
ROOM
110110
110110
TELECOM
ROOM
15B15B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L
E H
R M
.B
.A
R C
H .r v t
/1
/2
:1
:5
P
M
71A-400
ARCHITECTURAL ENLARGED VIEWS - BASEMENT
& FIRST LEVELS
589A6-21-700
B71
01/19/2022 M. Perkins K. Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
3" = 1'-0" C1
HOLLOW METAL HEAD DETAIL
3" = 1'-0"
C2
HOLLOW METAL JAMB DETAIL
1/4" = 1'-0" B1
WRAPPED FRAME TYPES ELEVATIONS
1 REMOVE EXISTING WALL AND FRAMING.
2 REMOVE EXISTING DOOR AND FRAME.
3 REMOVE FLOORING AND WALL BASE IN ROOM.
4 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL
PENETRATIONS AS NECESSARY.
6 NEW SMOKE-RATED DOOR.
7 REMOVE EXISTING ACOUSTICAL CEILING AND LIGHTS. MODIFY
AND/OR PROVIDE ADDITIONAL SUPPORTS AS REQUIRED FOR
EXISTING CEILING ITEMS TO REMAIN.
8 TELECOM ROOM TO BE OPEN TO DECK ABOVE.
9 INFILL ACOUSTICAL CEILING AS REQUIRED.
10 NEW FURRING WALL AT EXTERIOR WALL TO ENCLOSE WINDOW.
MAINTAIN 1/2" GAP BETWEEN EXISTING WALL INTERIOR FACE AND
NEW STUDS. MODIFY/ REMOVE INTERIOR WINDOW TRIM AS
REQUIRED.
11 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C
FIRE EXTINGUISHER LOCATED NO GREATER THAN 75 FEET AWAY
FROM THE NEW TR. CONTRACTOR TO COORDINATE THE NEW
LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW FEC
FOR EACH TR IN THE SCOPE OF WORK. SEE SPECIFICATION 10 44
13.
12 PROVIDE TEMPORARY AIR TIGHT BARRIER AROUND WORK AREA
DURING AND ACTIVITIES WHICH PRODUCE DUST - TYPICAL
13 TEMPORARY WALLS FOR ICRA ENCLOSURE
14 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE
1/16" = 1'-0" F5
BASEMENT REFERENCE PLAN
1/4" = 1'-0" D8
ARCHITECTURAL ENLARGED FLOOR PLAN -
BASEMENT LEVEL - ROOM 15B - NEW
1/16" = 1'-0" F1
FIRST LEVEL REFERENCE PLAN
1/4" = 1'-0" D6
ARCHITECTURAL ENLARGED FLOOR PLAN -
FIRST LEVEL - ROOM 110 - NEW
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL
FIRE RATING
HARDWARE
NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL
BASEMENT 15B TELECOM ROOM 15B 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-3F SEE ELEC
LEVEL 1 110 TELECOM ROOM 110 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-3F SEE ELEC
LEVEL 2 212B TELECOM ROOM 212B 2' - 10" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-3F SEE ELEC
LEVEL 3 312B TELECOM ROOM 312B 2' - 10" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-3F SEE ELEC
1/4" = 1'-0" D7
ARCHITECTURAL ENLARGED FLOOR PLAN -
BASEMENT LEVEL - ROOM 15B - DEMO
1/4" = 1'-0" D4
ARCHITECTURAL ENLARGED FLOOR PLAN -
FIRST LEVEL - ROOM 110 - DEMO
1/4" = 1'-0" C6
ARCHITECTURAL RCP - FIRST LEVEL
- ROOM 110 - NEW
1/4" = 1'-0"
C4
ARCHITECTURAL RCP - FIRST LEVEL
- ROOM 110 - DEMO
1/4" = 1'-0"
C7
ARCHITECTURAL RCP - BASEMENT
LEVEL - ROOM 15B - DEMO
1/4" = 1'-0"
ARCHITECTURAL RCP - BASEMENT
LEVEL - ROOM 15B - NEW
Revisions: Date:
ASI 1 04/14/21
04/18/22
/18
/20
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH
THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS
STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
B
TELECOM
ROOM
212B
ACTUAL: 73 SF
PROG: 170 SF
A
4BB
B
B
B
(E X
T 'G
V
IF
6'
-5
/8
(EXT'G VIF)
12'-2 5/8"
71A-401
D8
200200
204A204A
239239 238238
237237 236236
205205 203203
202202
201201
233C233C 233233
232232
208208 207207
206206
231231 230230
209209
2-E12-E1
229229 228228
227227
213213 214214
226226 225225 224224
217217216216
211211
223223
221221222222
219219
218218 200C200C
212212
239A239A 239B239B
235235
237A237A
203A203A 201B201B
201A201A
240240
204C204C
233A233A
208A208A
231A231A
209A209A
213A213A 215215 217A217A
221A221A 221B221B
215A215A
219C219C 219A219A
200B200B
210210
71A-401
D4
300300 301301
302302
337337
338338
339339
336336 335335
303303 305305 306306
304304
307307 308308
309309
331331332332333333334334
310C310C 3-E13-E1
329329 330330
327327
310310 316316
326326
314314313313
325325 324324
315315 317317
319319
318318 320320
321321
322322
323323
312312
TELECOM
ROOM
312B312B
71A-401
D2
304A304A
339A339A
300B300B 302A302A
310A310A
337A337A 336A336A
303A303A 310B310B 307A307A 308A308A
309A309A
333A333A
313A313A312A312A
325A325A
314A314A 317A317A 318A318A
319A319A 320A320A
316A316A
321A321A
323A323A
TELECOM
ROOM
312B
ACTUAL: 70 SF
PROG: 170 SF
B
BB
B
B
(E X
T 'G
V
IF
6'
-6
/2
(EXT'G VIF)
12'-1"
312B312B
1 2
212B212B
1 2
TELECOM
ROOM
212B212B
212B212B
TELECOM
ROOM
312B312B
312B312B
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L
E H
R M
.B
.A
R C
H .r v t
/1
/2
:1
:5
P
M
71A-401
ARCHITECTURAL ENLARGED VIEWS - SECOND &
THIRD LEVELS
589A6-21-700
B71
01/19/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
1/4" = 1'-0" D8
ARCHITECTURAL ENLARGED FLOOR PLAN -
SECOND LEVEL - ROOM 212B - NEW
1/16" = 1'-0" F6
SECOND LEVEL REFERENCE PLAN
1/16" = 1'-0"
F2
THIRD LEVEL REFERENCE PLAN
1/4" = 1'-0" D4
ARCHITECTURAL ENLARGED FLOOR PLAN -
THIRD LEVEL - ROOM 312B - NEW
1 REMOVE EXISTING DOOR AND FRAME.
2 REMOVE PORTION OF EXISTING WALL AS REQUIRED FOR NEW
DOOR.
3 REMOVE FLOORING AND WALL BASE IN ROOM.
4 REMOVE EXISTING ACOUSTICAL CEILING AND LIGHTS. MODIFY
AND/OR PROVIDE ADDITIONAL SUPPORTS AS REQUIRED FOR
EXISTING CEILING ITEMS TO REMAIN.
5 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL
PENETRATIONS AS NECESSARY.
6 NEW SMOKE-RATED DOOR.
7 TELECOM ROOM TO BE OPEN TO DECK ABOVE.
8 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE
2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE
THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A
NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE
SPECIFICATION 10 44 13.
9 PROVIDE TEMPORARY AIR TIGHT BARRIER AROUND WORK AREA
DURING AND ACTIVITIES WHICH PRODUCE DUST - TYPICAL
1/4" = 1'-0" D2
ARCHITECTURAL ENLARGED FLOOR PLAN -
THIRD LEVEL - ROOM 312B - DEMO
1/4" = 1'-0"
D6
ARCHITECTURAL ENLARGED FLOOR PLAN -
SECOND LEVEL - ROOM 212B - DEMO
1/4" = 1'-0" C8
ARCHITECTURAL RCP - SECOND LEVEL -
ROOM 212B - NEW
1/4" = 1'-0"
C6
ARCHITECTURAL RCP - SECOND LEVEL -
ROOM 212B - DEMO
1/4" = 1'-0"
C4
ARCHITECTURAL RCP - THIRD LEVEL
- ROOM 312B - NEW
1/4" = 1'-0"
C2
ARCHITECTURAL RCP - THIRD LEVEL
- ROOM 312B - DEMO
Revisions: Date:
ASI 1 04/14/2104/18/22
/18
/20
| Sheets |
| 71A-400 - ARCHITECTURAL ENLARGED VIEWS - BASEMENT & FIRST LEVELS |
| 71A-401 - ARCHITECTURAL ENLARGED VIEWS - SECOND & THIRD LEVELS |