589A6-21-700.LEHRM.ASI-001.B160.20220418.pdf

PDF 1 MB Posted

Attached to
Y1DZ--589A6-21-700 EHRM Infrastructure Upgrades Construction Leavenworth VAMC
Solicitation number
36C77622R0061
Issued by

About this file

This document package includes architectural drawings and specifications for telecommunications infrastructure upgrades at the VA Medical Center campus in Leavenworth, Kansas, as well as a related federal contract solicitation.

The architectural drawings depict telecommunications room layouts and details for upgrades on the first and second floors. Specifications require replacing all telecommunications cabling, outlets, and equipment across multiple campus buildings to support Electronic Health Record Modernization. Work includes installing smoke-rated optical fiber and CAT6A copper cabling, along with patch panels, equipment racks, cable management, and electrical upgrades in telecommunications rooms. The solicitation is seeking bids for construction services to complete this work per the drawings and specifications. The award date is not provided. The Department of Veterans Affairs Technology Acquisition Center in Austin, Texas, is the contracting agency.

View the file

Other files

File Type Posted
01 00 00 Appendix A - Bid Form Template.20220505.xlsx XLSX spreadsheet
36C77622R0061 0004.pdf PDF
01 00 00 Appendix A - Bid Form Template.20220505.pdf PDF
Follow Up Technical Questions Tracking Spreadsheet - 5-5-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links - Rev01.pdf PDF
36C77622R0061 0003.pdf PDF
01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
589A6-21-700.LEHRM.ASI-001.B54.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B161.20220418.pdf PDF
Site Visit Attendance Sheet - LV EHRM Infra 4-11-22.pdf PDF
TR Space Impact - Leavenworth.pdf PDF
Technical Questions Tracking Spreadsheet - 4-27-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links.pdf PDF
B7 Electrical Panel Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.SITE.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B42.20220418.pdf PDF
Attachment 14 - DBA Wage Rates - Leavenworth County - 4-15-22.pdf PDF
Unitary Disconnect Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.B41.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B39.20220418.pdf PDF
Attachment 17 - Rev Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
01 00 00 Appendix A - Bid Form Template.pdf PDF
Unitary Cooling Photos.zip ZIP file
21 22 00 - Clean Agent Fire Suppression Systems.pdf PDF
23 64 00 - Packaged Water Chillers.ASI001.pdf PDF
589A6-21-700.LEHRM.ASI-001.B71.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B153.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.Summary.Log.20220419.pdf PDF
B88.89.90.91 Photos.zip ZIP file
Panel Photos.zip ZIP file
UPS Data Photos.zip ZIP file
589A6-21-700.LEHRM.IFC_R1.B39.20220119.pdf PDF
589A6-21-700.LEHRM.ASI-001.B21.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B122.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B90.20220419.pdf PDF
36C77622R0061 Amendment 0002.pdf PDF
36C77622R0061 Amendment 0001.pdf PDF
RFP 36C77622R0061.pdf PDF
Attachment 10 - 589A6-21-700 LEHRM IFC_R1 B161 Drawing.pdf PDF
Attachment 17 - Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment 4 - 589A6-21-700 LEHRM IFC_R1 B54 Drawing.pdf PDF
Attachment 3 - 589A6-21-700 LEHRM IFC_R1 B42 Drawing.pdf PDF
Attachment 18 - VA Notice of Limitations on Subcontracting-Certificate of Compliance.docx DOCX document
Attachment 13 - Asbestos Report Part 2 of 7.zip ZIP file
Attachment 5 - 589A6-21-700 LEHRM IFC_R1 B71 Part 1 of 2 Drawing.pdf PDF
Attachment 7 - 589A6-21-700 LEHRM IFC_R1 B122 Drawing.pdf PDF
Attachment 2 - 589A6-21-700 LEHRM IFC_R1 B41 Drawing.pdf PDF
Attachment 13 - Asbestos Report Part 4 of 7.zip ZIP file
Attachment 13 - Asbestos Report Part 5 of 7.zip ZIP file
Attachment 6 - 589A6-21-700 LEHRM IFC_R1 B88-89-90-91 Part 3 of 3 Drawing.pdf PDF
Show 40 more

Latest 50 of 67 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

TELECOM

ROOM

D137AD137A

TELECOM

ROOM

G125G125

TELECOM

ROOM

F125F125

160A-400

D8

160A-400

D6

160A-400

F3

160A-400

D1

160A-400

D5

160A-400

D7

TELECOM

ROOM

G125

ACTUAL: 109 SF

PROG: 170 SF

G125

B

B

B

B

B

B

TELECOM

ROOM

F125

ACTUAL: 111 SF

PROG: 170 SF

F125

B

B

B

B

B

B

TELECOM

ROOM

D137A

ACTUAL: 168 SF

PROG: 170 SF

B

B

B

B

A4

B

A

B

14'-1 5/8"

10'-0 3/8"

D

7A

REC

THERAPY

D138

ACTUAL: 349 SF

CLR

M

IN4'-

0"

CLR MIN

3'-6"

11'-2"

1'-10"

IT ROOM

D137A

ACTUAL: 70 SF

DIETETICS

STORAGE

D138

ACTUAL: 450 SF

TELECOM

ROOM

F125

ACTUAL: 111 SF

PROG: 170 SF

SOCIAL

WORK

F125

ACTUAL: 113 SF

SOCIAL

WORK

F125

ACTUAL: 113 SF

TELECOM

ROOM

D137A

ACTUAL: 168 SF

PROG: 170 SF

IT ROOM

D137A

ACTUAL: 70 SF

DIETETICS

STORAGE

D138

ACTUAL: 450 SF

PSYCHOLOGIST

G125

ACTUAL: 111 SF

TELECOM

ROOM

G125

ACTUAL: 109 SF

PROG: 170 SF

PSYCHOLOGIST

G125

ACTUAL: 111 SF

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L E

H R

M .B

.A

R C

H .r v t

/1

/2

:1

:2

A

M

160A-400

ARCHITECTURAL ENLARGED VIEWS - FIRST

LEVEL

589A6-21-700

B160

01/19/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048

1 NEW SMOKE-RATED DOOR.

2 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL

PENETRATIONS AS NECESSARY.

3 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE

2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75

FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE

THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A

NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE

SPECIFICATION 10 44 13.

4 REMOVE EXISTING WALL AND FRAMING.

5 REMOVE FLOORING AND WALL BASE IN ROOM.

6 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

7 FURNITURE NOT IN SCOPE OF WORK, SHOWN FOR REFERENCE

ONLY.

8 TEMPORARY WALLS FOR ICRA ENCLOSURE

9 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE

10 PROVIDE TEMPORARY AIR TIGHT BARRIER AROUND WORK AREA

DURING ANY ACTIVITIES WHICH PRODUCE DUST - TYPICAL

1/32" = 1'-0" F6

FIRST LEVEL REFERENCE PLAN

1/4" = 1'-0" D8

ARCHITECTURAL ENLARGED FLOOR PLAN -

FIRST LEVEL - ROOM G125 - NEW

1/4" = 1'-0"

D6

ARCHITECTURAL ENLARGED FLOOR PLAN -

FIRST LEVEL - ROOM F125 - NEW

1/4" = 1'-0" F3

ARCHITECTURAL ENLARGED FLOOR PLAN -

FIRST LEVEL - ROOM D137A - NEW

1/4" = 1'-0" D1

ARCHITECTURAL ENLARGED FLOOR PLAN -

FIRST LEVEL - ROOM D137A - DEMO

1/4" = 1'-0" B6

ARCHITECTURAL RCP - FIRST LEVEL

- ROOM F125 - NEW

1/4" = 1'-0"

B5

ARCHITECTURAL RCP - FIRST LEVEL

- ROOM F125 - DEMO

1/4" = 1'-0" D5

ARCHITECTURAL ENLARGED FLOOR

PLAN - FIRST LEVEL - ROOM F125 - DEMO

1/4" = 1'-0" B3

ARCHITECTURAL RCP - FIRST LEVEL - ROOM

D137A - NEW

1/4" = 1'-0"

B1

ARCHITECTURAL RCP - FIRST LEVEL - ROOM

D137A - DEMO

1/4" = 1'-0" D7

ARCHITECTURAL ENLARGED FLOOR PLAN -

FIRST LEVEL - ROOM G125 - DEMO

1/4" = 1'-0" B8

ARCHITECTURAL RCP - FIRST LEVEL

- ROOM G125 - NEW

1/4" = 1'-0"

B7

ARCHITECTURAL RCP - FIRST LEVEL

- ROOM G125 - DEMO

Revisions: Date:

ASI 1 04/14/22

04/18/22

/18

/20

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

ACOUSTICAL OR RATED

FLEXIBLE SEALANT

FLOOR LINE

ADD ONE LAYER OF 5/8" GWB,

ONE-SIDE WITH APPROVED UL

SETTING COMPOUND BETWEEN

LAYERS AND FASTENED TO

WALL AS REQUIRED, AT

EXISTING GWB WALL

ASSEMBLIES

STRUCTURAL DECK

EXISTING METAL STUDS AND

BATT INSULATION TO REMAIN

A/C GRADE, 3/4" FIRE-TREATED

PLYWOOD TO 8'-0" ABOVE FINISHED

FLOOR, ADHERED TO CONCRETE AT

EXISTING CONCRETE WALL

ASSEMBLIES

BOTTOM OF PLYWOOD

TO BE AT 12" AFF

UL DESIGN V497

1-HOUR PARTITION RATED FROM BOTH SIDES

EXISTING GWB OR

CONCRETE WALL

ASSEMBLY, WHERE OCCURS

SIDE OF

EXISTING

ROOM OR

CORRIDOR TO

REMAIN

160A-512

D5

160A-512

B5

ACOUSTICAL OR RATED

SEALANT BOTH SIDES

FLOOR LINE

5/8" GWB BOTH SIDES

SOUND ATTENUATION

BATTS (SAB) PER

SCHEDULE.

CEILING LINE

STRUCTURAL DECK

METAL STUDS, SIZE

PER SCHEDULE

160A-512

D5

A/C GRADE, 3/4" FIRE-

TREATED PLYWOOD TO 8'-0"

ABOVE FINISHED FLOOR

160A-512

B5

AT FIRE RATED

PARTITIONS

AT SMOKE RATED

PARTITIONS

BOTTOM OF PLYWOOD TO

BE AT 12" AFF

TELECOM

ROOM

G225G225

160A-401

C8

TELECOM

ROOM

F225F225

160A-401

C4

160A-401

C6 160A-401

C3

TELECOM

ROOM

G225

ACTUAL: 111 SF

PROG: 170 SF

G225

B

B

B

B

B

B

TELECOM

ROOM

F225

ACTUAL: 110 SF

PROG: 170 SF

F225

B

B

B

B

B

B

VOC.

REHAB

SPECIALIST

G225

ACTUAL: 114 SF

STAFF

PSYCHOLOGIST

F225

ACTUAL: 112 SF

TELECOM

ROOM

F225F225

STAFF

PSYCHOLOGIST

F225

ACTUAL: 112 SF

VOC.

REHAB

SPECIALIST

G225

ACTUAL: 114 SF

TELECOM

ROOM

G225G225

F4

TYPICAL FRAME

H E

IG

H

T

2" WIDTH 2"

F5

FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS

F

FLUSH

F2

1/2" 1/2"

VARIES

SEE PLAN

WALL - SEE PLAN

FOR TYPE

SEALANT - EA. SIDE

& ALL AROUND,

TYP.

HOLLOW METAL

FRAME

/2

V

A R

IE

S

S E

E P

L A

N

/2

4" 2"

ADJACENT WALL

WHERE OCCURS

SEALANT - EA SIDE &

ALL AROUND, TYP.

HOLLOW METAL

FRAME

WALL - SEE PLAN

FOR TYPE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L E

H R

M .B

.A

R C

H .r v t

/1

/2

:1

:2

A

M

160A-401

ARCHITECTURAL ENLARGED VIEWS - SECOND

LEVEL

589A6-21-700

B160

01/19/2022 M. Perkins K.Hutchinson

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048

1 1/2" = 1'-0" E1

1-HOUR WALL

1 1/2" = 1'-0" B1

1-HOUR WALL

NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL

U465

(TYPE A) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

A4 4" 5 1/4" 35

NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL

V438, UL U411

(TYPE B) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

B 2 1/2" 3/4" 45

DOOR AND FRAME SCHEDULE

IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL

FIRE RATING

HARDWARE

NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL

LEVEL 1 G125 TELECOM ROOM G125 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC

LEVEL 1 F125 TELECOM ROOM F125 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC

LEVEL 1 D137A TELECOM ROOM D137A 3' - 6" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC

LEVEL 2 G225 TELECOM ROOM G225 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC

LEVEL 2 F225 TELECOM ROOM F225 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC

1/32" = 1'-0" F6

SECOND LEVEL REFERENCE PLAN

1/4" = 1'-0" C8

ARCHITECTURAL ENLARGED FLOOR PLAN -

SECOND LEVEL - ROOM G225 - NEW

1/4" = 1'-0"

C4

ARCHITECTURAL ENLARGED FLOOR PLAN -

SECOND LEVEL - ROOM F225 - NEW

1 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE

DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.

2 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL

PENETRATIONS AS NECESSARY.

3 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE

2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75

FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE

THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A

NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE

SPECIFICATION 10 44 13.

4 REMOVE FLOORING AND WALL BASE IN ROOM.

5 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

6 PROVIDE TEMPORARY AIR TIGHT BARRIER AROUND WORK AREA

DURING ANY ACTIVITIES WHICH PRODUCE DUST - TYPICAL

1/4" = 1'-0" C6

ARCHITECTURAL ENLARGED FLOOR PLAN -

SECOND LEVEL - ROOM G225 - DEMO

1/4" = 1'-0"

C3

ARCHITECTURAL ENLARGED FLOOR PLAN -

SECOND LEVEL - ROOM F225 - DEMO

1/4" = 1'-0" B4

ARCHITECTURAL RCP - SECOND LEVEL -

ROOM F225 - NEW

1/4" = 1'-0"

B3

ARCHITECTURAL RCP - SECOND LEVEL -

ROOM F225 - DEMO

1/4" = 1'-0"

B8

ARCHITECTURAL RCP - SECOND LEVEL -

ROOM G225 - NEW

1/4" = 1'-0"

B6

ARCHITECTURAL RCP - SECOND LEVEL -

ROOM G225 - NEW

1/4" = 1'-0" E3

WRAPPED FRAME TYPES ELEVATIONS

3" = 1'-0" F4

HOLLOW METAL HEAD DETAIL

3" = 1'-0"

F3

HOLLOW METAL JAMB DETAIL

Revisions: Date:

ASI 1 04/14/22

1 1

1 1

04/18/22

/18

/20

Sheets
160A-400 - ARCHITECTURAL ENLARGED VIEWS - FIRST LEVEL
160A-401 - ARCHITECTURAL ENLARGED VIEWS - SECOND LEVEL

File details come from the government source that posted it. Updated .