589A6-21-700.LEHRM.ASI-001.B160.20220418.pdf
PDF 1 MB Posted
- Solicitation number
- 36C77622R0061
About this file
This document package includes architectural drawings and specifications for telecommunications infrastructure upgrades at the VA Medical Center campus in Leavenworth, Kansas, as well as a related federal contract solicitation.
The architectural drawings depict telecommunications room layouts and details for upgrades on the first and second floors. Specifications require replacing all telecommunications cabling, outlets, and equipment across multiple campus buildings to support Electronic Health Record Modernization. Work includes installing smoke-rated optical fiber and CAT6A copper cabling, along with patch panels, equipment racks, cable management, and electrical upgrades in telecommunications rooms. The solicitation is seeking bids for construction services to complete this work per the drawings and specifications. The award date is not provided. The Department of Veterans Affairs Technology Acquisition Center in Austin, Texas, is the contracting agency.
View the file
Other files
Show 40 more
Latest 50 of 67 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH
THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS
STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
TELECOM
ROOM
D137AD137A
TELECOM
ROOM
G125G125
TELECOM
ROOM
F125F125
160A-400
D8
160A-400
D6
160A-400
F3
160A-400
D1
160A-400
D5
160A-400
D7
TELECOM
ROOM
G125
ACTUAL: 109 SF
PROG: 170 SF
G125
B
B
B
B
B
B
TELECOM
ROOM
F125
ACTUAL: 111 SF
PROG: 170 SF
F125
B
B
B
B
B
B
TELECOM
ROOM
D137A
ACTUAL: 168 SF
PROG: 170 SF
B
B
B
B
A4
B
A
B
14'-1 5/8"
10'-0 3/8"
D
7A
REC
THERAPY
D138
ACTUAL: 349 SF
CLR
M
IN4'-
0"
CLR MIN
3'-6"
11'-2"
1'-10"
IT ROOM
D137A
ACTUAL: 70 SF
DIETETICS
STORAGE
D138
ACTUAL: 450 SF
TELECOM
ROOM
F125
ACTUAL: 111 SF
PROG: 170 SF
SOCIAL
WORK
F125
ACTUAL: 113 SF
SOCIAL
WORK
F125
ACTUAL: 113 SF
TELECOM
ROOM
D137A
ACTUAL: 168 SF
PROG: 170 SF
IT ROOM
D137A
ACTUAL: 70 SF
DIETETICS
STORAGE
D138
ACTUAL: 450 SF
PSYCHOLOGIST
G125
ACTUAL: 111 SF
TELECOM
ROOM
G125
ACTUAL: 109 SF
PROG: 170 SF
PSYCHOLOGIST
G125
ACTUAL: 111 SF
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.A
R C
H .r v t
/1
/2
:1
:2
A
M
160A-400
ARCHITECTURAL ENLARGED VIEWS - FIRST
LEVEL
589A6-21-700
B160
01/19/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
1 NEW SMOKE-RATED DOOR.
2 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL
PENETRATIONS AS NECESSARY.
3 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE
2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE
THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A
NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE
SPECIFICATION 10 44 13.
4 REMOVE EXISTING WALL AND FRAMING.
5 REMOVE FLOORING AND WALL BASE IN ROOM.
6 TELECOM ROOM TO BE OPEN TO DECK ABOVE.
7 FURNITURE NOT IN SCOPE OF WORK, SHOWN FOR REFERENCE
ONLY.
8 TEMPORARY WALLS FOR ICRA ENCLOSURE
9 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE
10 PROVIDE TEMPORARY AIR TIGHT BARRIER AROUND WORK AREA
DURING ANY ACTIVITIES WHICH PRODUCE DUST - TYPICAL
1/32" = 1'-0" F6
FIRST LEVEL REFERENCE PLAN
1/4" = 1'-0" D8
ARCHITECTURAL ENLARGED FLOOR PLAN -
FIRST LEVEL - ROOM G125 - NEW
1/4" = 1'-0"
D6
ARCHITECTURAL ENLARGED FLOOR PLAN -
FIRST LEVEL - ROOM F125 - NEW
1/4" = 1'-0" F3
ARCHITECTURAL ENLARGED FLOOR PLAN -
FIRST LEVEL - ROOM D137A - NEW
1/4" = 1'-0" D1
ARCHITECTURAL ENLARGED FLOOR PLAN -
FIRST LEVEL - ROOM D137A - DEMO
1/4" = 1'-0" B6
ARCHITECTURAL RCP - FIRST LEVEL
- ROOM F125 - NEW
1/4" = 1'-0"
B5
ARCHITECTURAL RCP - FIRST LEVEL
- ROOM F125 - DEMO
1/4" = 1'-0" D5
ARCHITECTURAL ENLARGED FLOOR
PLAN - FIRST LEVEL - ROOM F125 - DEMO
1/4" = 1'-0" B3
ARCHITECTURAL RCP - FIRST LEVEL - ROOM
D137A - NEW
1/4" = 1'-0"
B1
ARCHITECTURAL RCP - FIRST LEVEL - ROOM
D137A - DEMO
1/4" = 1'-0" D7
ARCHITECTURAL ENLARGED FLOOR PLAN -
FIRST LEVEL - ROOM G125 - DEMO
1/4" = 1'-0" B8
ARCHITECTURAL RCP - FIRST LEVEL
- ROOM G125 - NEW
1/4" = 1'-0"
B7
ARCHITECTURAL RCP - FIRST LEVEL
- ROOM G125 - DEMO
Revisions: Date:
ASI 1 04/14/22
04/18/22
/18
/20
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH
THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS
STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
ACOUSTICAL OR RATED
FLEXIBLE SEALANT
FLOOR LINE
ADD ONE LAYER OF 5/8" GWB,
ONE-SIDE WITH APPROVED UL
SETTING COMPOUND BETWEEN
LAYERS AND FASTENED TO
WALL AS REQUIRED, AT
EXISTING GWB WALL
ASSEMBLIES
STRUCTURAL DECK
EXISTING METAL STUDS AND
BATT INSULATION TO REMAIN
A/C GRADE, 3/4" FIRE-TREATED
PLYWOOD TO 8'-0" ABOVE FINISHED
FLOOR, ADHERED TO CONCRETE AT
EXISTING CONCRETE WALL
ASSEMBLIES
BOTTOM OF PLYWOOD
TO BE AT 12" AFF
UL DESIGN V497
1-HOUR PARTITION RATED FROM BOTH SIDES
EXISTING GWB OR
CONCRETE WALL
ASSEMBLY, WHERE OCCURS
SIDE OF
EXISTING
ROOM OR
CORRIDOR TO
REMAIN
160A-512
D5
160A-512
B5
ACOUSTICAL OR RATED
SEALANT BOTH SIDES
FLOOR LINE
5/8" GWB BOTH SIDES
SOUND ATTENUATION
BATTS (SAB) PER
SCHEDULE.
CEILING LINE
STRUCTURAL DECK
METAL STUDS, SIZE
PER SCHEDULE
160A-512
D5
A/C GRADE, 3/4" FIRE-
TREATED PLYWOOD TO 8'-0"
ABOVE FINISHED FLOOR
160A-512
B5
AT FIRE RATED
PARTITIONS
AT SMOKE RATED
PARTITIONS
BOTTOM OF PLYWOOD TO
BE AT 12" AFF
TELECOM
ROOM
G225G225
160A-401
C8
TELECOM
ROOM
F225F225
160A-401
C4
160A-401
C6 160A-401
C3
TELECOM
ROOM
G225
ACTUAL: 111 SF
PROG: 170 SF
G225
B
B
B
B
B
B
TELECOM
ROOM
F225
ACTUAL: 110 SF
PROG: 170 SF
F225
B
B
B
B
B
B
VOC.
REHAB
SPECIALIST
G225
ACTUAL: 114 SF
STAFF
PSYCHOLOGIST
F225
ACTUAL: 112 SF
TELECOM
ROOM
F225F225
STAFF
PSYCHOLOGIST
F225
ACTUAL: 112 SF
VOC.
REHAB
SPECIALIST
G225
ACTUAL: 114 SF
TELECOM
ROOM
G225G225
F4
TYPICAL FRAME
H E
IG
H
T
2" WIDTH 2"
F5
FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS
F
FLUSH
F2
1/2" 1/2"
VARIES
SEE PLAN
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND,
TYP.
HOLLOW METAL
FRAME
/2
V
A R
IE
S
S E
E P
L A
N
/2
4" 2"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL
FRAME
WALL - SEE PLAN
FOR TYPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L E
H R
M .B
.A
R C
H .r v t
/1
/2
:1
:2
A
M
160A-401
ARCHITECTURAL ENLARGED VIEWS - SECOND
LEVEL
589A6-21-700
B160
01/19/2022 M. Perkins K.Hutchinson
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
1 1/2" = 1'-0" E1
1-HOUR WALL
1 1/2" = 1'-0" B1
1-HOUR WALL
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL
U465
(TYPE A) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
A4 4" 5 1/4" 35
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V438, UL U411
(TYPE B) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
B 2 1/2" 3/4" 45
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL
FIRE RATING
HARDWARE
NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL
LEVEL 1 G125 TELECOM ROOM G125 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC
LEVEL 1 F125 TELECOM ROOM F125 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC
LEVEL 1 D137A TELECOM ROOM D137A 3' - 6" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC
LEVEL 2 G225 TELECOM ROOM G225 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC
LEVEL 2 F225 TELECOM ROOM F225 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC
1/32" = 1'-0" F6
SECOND LEVEL REFERENCE PLAN
1/4" = 1'-0" C8
ARCHITECTURAL ENLARGED FLOOR PLAN -
SECOND LEVEL - ROOM G225 - NEW
1/4" = 1'-0"
C4
ARCHITECTURAL ENLARGED FLOOR PLAN -
SECOND LEVEL - ROOM F225 - NEW
1 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE
DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.
2 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL
PENETRATIONS AS NECESSARY.
3 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE
2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE
THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A
NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE
SPECIFICATION 10 44 13.
4 REMOVE FLOORING AND WALL BASE IN ROOM.
5 TELECOM ROOM TO BE OPEN TO DECK ABOVE.
6 PROVIDE TEMPORARY AIR TIGHT BARRIER AROUND WORK AREA
DURING ANY ACTIVITIES WHICH PRODUCE DUST - TYPICAL
1/4" = 1'-0" C6
ARCHITECTURAL ENLARGED FLOOR PLAN -
SECOND LEVEL - ROOM G225 - DEMO
1/4" = 1'-0"
C3
ARCHITECTURAL ENLARGED FLOOR PLAN -
SECOND LEVEL - ROOM F225 - DEMO
1/4" = 1'-0" B4
ARCHITECTURAL RCP - SECOND LEVEL -
ROOM F225 - NEW
1/4" = 1'-0"
B3
ARCHITECTURAL RCP - SECOND LEVEL -
ROOM F225 - DEMO
1/4" = 1'-0"
B8
ARCHITECTURAL RCP - SECOND LEVEL -
ROOM G225 - NEW
1/4" = 1'-0"
B6
ARCHITECTURAL RCP - SECOND LEVEL -
ROOM G225 - NEW
1/4" = 1'-0" E3
WRAPPED FRAME TYPES ELEVATIONS
3" = 1'-0" F4
HOLLOW METAL HEAD DETAIL
3" = 1'-0"
F3
HOLLOW METAL JAMB DETAIL
Revisions: Date:
ASI 1 04/14/22
1 1
1 1
04/18/22
/18
/20
| Sheets |
| 160A-400 - ARCHITECTURAL ENLARGED VIEWS - FIRST LEVEL |
| 160A-401 - ARCHITECTURAL ENLARGED VIEWS - SECOND LEVEL |