589A6-21-700.LEHRM.ASI-001.B54.20220418.pdf
PDF 741 KB Posted
- Solicitation number
- 36C77622R0061
About this file
This solicitation is for a construction project to upgrade telecommunications infrastructure at the Leavenworth VA Medical Center campus in preparation for an Electronic Health Record modernization. The scope of work includes replacing all telecommunications cabling for multiple buildings on campus with CAT6A copper cabling and OS2 single-jacketed fiber optic cabling. An additional 15% capacity over existing needs must be provided. The project also requires installing new computer room air conditioning systems, electrical panels, backup generators, and a new 600-ton water-cooled chiller to serve new telecom rooms. The awarded contractor will be responsible for all materials, labor, documentation, and equipment to complete the cabling replacement and infrastructure upgrades according to the specifications, including providing new patch panels, equipment racks, ladder racks, and patch cables in each telecom room.
View the file
Other files
Show 40 more
Latest 50 of 67 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH
THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS
STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
ACOUSTICAL OR RATED
FLEXIBLE SEALANT
FLOOR LINE
ADD ONE LAYER OF 5/8" GWB,
ONE-SIDE WITH APPROVED UL
SETTING COMPOUND BETWEEN
LAYERS AND FASTENED TO
WALL AS REQUIRED, AT
EXISTING GWB WALL
ASSEMBLIES
STRUCTURAL DECK
EXISTING METAL STUDS AND
BATT INSULATION TO REMAIN
A/C GRADE, 3/4" FIRE-TREATED
PLYWOOD TO 8'-0" ABOVE FINISHED
FLOOR, ADHERED TO CONCRETE AT
EXISTING CONCRETE WALL
ASSEMBLIES
BOTTOM OF PLYWOOD
TO BE AT 12" AFF
UL DESIGN V497
1-HOUR PARTITION RATED FROM BOTH SIDES
EXISTING GWB OR
CONCRETE WALL
ASSEMBLY, WHERE OCCURS
SIDE OF
EXISTING
ROOM OR
CORRIDOR TO
REMAIN
54A-512
D5
54A-512
B5
ACOUSTICAL OR RATED
SEALANT BOTH SIDES
FLOOR LINE
5/8" GWB BOTH SIDES
SOUND ATTENUATION
BATTS (SAB) PER
SCHEDULE.
CEILING LINE
STRUCTURAL DECK
METAL STUDS, SIZE
PER SCHEDULE
54A-512
D5
A/C GRADE, 3/4" FIRE-
TREATED PLYWOOD TO 8'-0"
ABOVE FINISHED FLOOR
54A-512
B5
AT FIRE RATED
PARTITIONS
AT SMOKE RATED
PARTITIONS
BOTTOM OF PLYWOOD TO
BE AT 12" AFF
TELECOM
ROOM
104A104A
FIRE
HOUSE
104104
54A-402
D8
TELECOM
ROOM
104A104A
TELECOM
ROOM
104A
80 SF
B
B A
B
A4
B
104A
A4
7' -7
/4
ALIGN
14'-8"
'-2
8' -5
/4
11'-8"
FIRE
HOUSE
104104
1/2" 1/2"
VARIES
SEE PLAN
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND,
TYP.
HOLLOW METAL
FRAME
/2
V
A R
IE
S
S E
E P
L A
N
/2
4" 2"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL
FRAME
WALL - SEE PLAN
FOR TYPE
F4
TYPICAL FRAME
H E
IG
H
T
2" WIDTH 2"
F5
FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS
F
FLUSH
F2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L
E H
R M
.B
.A
R C
H .r v t
/1
/2
:0
:3
P
M
54A-402
ARCHITECTURAL ENLARGED VIEWS - SECOND
LEVEL
589A6-21-700
B54
01/19/2022 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4th St Trafficway, Leavenworth, KS 66048
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL
U465
(TYPE A) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
A4 4" 5 1/4" 35
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V438, UL U411
(TYPE B) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
B 2 1/2" 3/4" 45
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL
FIRE RATING
HARDWARE
NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL
LEVEL 2 104A TELECOM ROOM 104A 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" HM PTD 45 MIN HW-SH-3F SEE ELEC
1/4" = 1'-0" B6
ARCHITECTURE REFLECTED CEILING PLAN -
SECOND FLOOR - ROOM 104A - DEMO
1/4" = 1'-0"
B8
ARCHITECTURE REFLECTED CEILING PLAN -
SECOND FLOOR - ROOM 104A - NEW
1/32" = 1'-0" F5
SECOND LEVEL REFERENCE PLAN
1/4" = 1'-0" D8
ARCHITECTURE FLOOR PLAN - SECOND
LEVEL - ROOM 104A - NEW
1/4" = 1'-0"
D6
ARCHITECTURE FLOOR PLAN - SECOND
LEVEL - ROOM 104A - DEMO
3" = 1'-0" B1
HOLLOW METAL HEAD DETAIL
3" = 1'-0"
B3
HOLLOW METAL JAMB DETAIL
1/4" = 1'-0" F1
WRAPPED FRAME TYPES ELEVATIONS
1 REMOVE EXISTING FLOORING AND WALL BASE.
2 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE
DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.
3 ALL WALLS TO BE SMOKE-RATED. PATCH AND SEAL ALL
PENETRATIONS AS NECESSARY.
4 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C
FIRE EXTINGUISHER LOCATED NO GREATER THAN 75 FEET AWAY
FROM THE NEW TR. CONTRACTOR TO COORDINATE THE NEW
LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW FEC
FOR EACH TR IN THE SCOPE OF WORK. SEE SPECIFICATION 10 44
13.
5 TELECOM ROOM TO BE OPEN TO DECK ABOVE.
6 TEMPORARY WALLS FOR ICRA ENCLOSURE
7 TEMPORARY DOOR AND STICKY MATS FOR ICRA ENCLOSURE
Revisions: Date:
ASI 1 04/14/22
04/18/22
/18
/20
04/18/2022
| Sheets |
| 54A-402 - ARCHITECTURAL ENLARGED VIEWS - SECOND LEVEL |
File details come from the government source that posted it. Updated .