This solicitation is for construction services to upgrade telecommunications infrastructure at the Leavenworth VA Medical Center campus in preparation for Electronic Health Record Modernization. The scope of work includes replacing all telecommunications cabling, outlets, and associated equipment across multiple buildings on campus. The contractor will replace existing copper cabling with CAT6A and existing fiber with OM4 and OS2 fiber, providing an additional 15% capacity above current needs. In addition to cabling replacement, the contractor will install new computer room air conditioning systems, electrical panels and circuits, backup generators, and a new 600-ton water-cooled chiller and pump. The contractor must follow standards for cable labeling, termination, and organization. The solicitation is issued by the Department of Veterans Affairs Technology Acquisition Center in Austin, Texas.
View the file
Other files
Show 40 more
Latest 50 of 67 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SHEET SYMBOL LEGEND
KEYNOTES
GENERAL NOTES
EXISTING CONSTRUCTION TO REMAIN
EXISTING CONSTRUCTION TO BE DEMOLISHED
NEW CONSTRUCTION, WITH PARTITION TYPE
A
A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT
REQUIREMENTS AND PROJECT LOCATION DRAWINGS.
B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES
INFORMATION.
C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL
SYSTEMS INFORMATION.
D. NEW TELECOM ROOM SHALL BE SMOKE RATED AND COMPLY WITH
THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS
STANDARDS.
E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.
F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.
G. SEE TYPICAL CEILING DETAILS ON SHEET A-531
PARTITION RATING GRAPHICS:
4 HR FIRE BARRIER
3 HR FIRE BARRIER
2 HR FIRE & SMOKE BARRIER
2 HR FIRE BARRIER
2 HR FIRE BARRIER/SHAFT
1 HR FIRE & SMOKE BARRIER
1 HR FIRE BARRIER
1 HR FIRE BARRIER/SHAFT
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION: PRIORITY
1 HIGHEST
5 LOWEST
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE
RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN
GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
41A-400
D5
41A-400
D7TELECOM
ROOM
B1CB1C
TELECOM
ROOM
B1CB1C
STORAGE
LOG
B1B1
TELECOM
ROOM
B1C
ACTUAL: 100 SF
PROG: 100 SF
B
B
A3
B
B A
11'-1 7/8"
ALIGN
B C
1/2" 1/2"
VARIES
SEE PLAN
WALL - SEE PLAN
FOR TYPE
SEALANT - EA. SIDE
& ALL AROUND,
TYP.
HOLLOW METAL
FRAME
/2
V
A R
IE
S
S E
E P
L A
N
/2
4" 2"
ADJACENT WALL
WHERE OCCURS
SEALANT - EA SIDE &
ALL AROUND, TYP.
HOLLOW METAL
FRAME
WALL - SEE PLAN
FOR TYPE
F4
TYPICAL FRAME
H E
IG
H
T
2" WIDTH 2"
F5
FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS
F
FLUSH
F2
ACOUSTICAL OR RATED
SEALANT BOTH SIDES
FLOOR LINE
5/8" GWB BOTH SIDES
SOUND ATTENUATION
BATTS (SAB) PER
SCHEDULE.
CEILING LINE
STRUCTURAL DECK
METAL STUDS, SIZE
PER SCHEDULE
41A-512
D5
A/C GRADE, 3/4" FIRE-
TREATED PLYWOOD TO 8'-0"
ABOVE FINISHED FLOOR
41A-512
B5
AT FIRE RATED
PARTITIONS
AT SMOKE RATED
PARTITIONS
BOTTOM OF PLYWOOD TO
BE AT 12" AFF
ACOUSTICAL OR RATED
FLEXIBLE SEALANT
FLOOR LINE
ADD ONE LAYER OF 5/8" GWB,
ONE-SIDE WITH APPROVED UL
SETTING COMPOUND BETWEEN
LAYERS AND FASTENED TO
WALL AS REQUIRED, AT
EXISTING GWB WALL
ASSEMBLIES
STRUCTURAL DECK
EXISTING METAL STUDS AND
BATT INSULATION TO REMAIN
A/C GRADE, 3/4" FIRE-TREATED
PLYWOOD TO 8'-0" ABOVE FINISHED
FLOOR, ADHERED TO CONCRETE AT
EXISTING CONCRETE WALL
ASSEMBLIES
BOTTOM OF PLYWOOD
TO BE AT 12" AFF
UL DESIGN V497
1-HOUR PARTITION RATED FROM BOTH SIDES
EXISTING GWB OR
CONCRETE WALL
ASSEMBLY, WHERE OCCURS
SIDE OF
EXISTING
ROOM OR
CORRIDOR TO
REMAIN
41A-512
D5
41A-512
B5
TELECOM
ROOM
B1C
ACTUAL: 100 SF
PROG: 100 SF
TELECOM
ROOM
B1CB1C
STORAGE
LOG
B1B1
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
CONSULTANT
321 4 5 6 7 8 9 10
TRIPLE C - The A/E Group
4625 Lindell Blvd., 2nd Floor, 2064
St. Louis, MO 63108
MAT PERKINS
314-372-0067
STAMP
B
IM
/5
A -2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K
S V
A M
C /5
A
-2
-7
.L
E H
R M
.B
.A
R C
H .r v t
/1
/2
:1
:1
A
M
41A-400
ARCHITECTURAL ENLARGED VIEWS - BASEMENT
LEVEL
589A6-21-700
B41
01/19/2022 M. Perkins K. McDermott
ISSUED FOR
CONSTRUCTION
EHRM INFRASTRUCTURE
UPGRADES
4101 4TH ST TRAFFICWAY, LEAVENWORTH, KS 66048
1/16" = 1'-0" F5
BASEMENT REFERENCE PLAN
1/4" = 1'-0" D5
ARCHITECTURAL DEMOLITION FLOOR PLAN -
BASEMENT LEVEL - ROOM B1C - DEMO
1/4" = 1'-0"
D7
ARCHITECTURAL FLOOR PLAN - BASEMENT
LEVEL - ROOM B1C - NEW
3" = 1'-0" B3
HOLLOW METAL HEAD DETAIL
3" = 1'-0" D1
HOLLOW METAL JAMB DETAIL
1/4" = 1'-0"
D3
WRAPPED FRAME TYPES ELEVATIONS
1 REMOVE EXISTING WALL AND FRAMING.
2 REMOVE EXISTING DOOR AND FRAME.
3 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE
DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.
4 EXISTING WALLS TO BECOME SMOKE-RATED. PATCH AND SEAL
ALL PENETRATIONS AS NECESSARY.
5 REMOVE EXISTING LIGHT FIXTURE.
6 TELECOM ROOM TO BE OPEN TO DECK ABOVE.
7 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE
2A:10B:C FIRE EXTINGUISHER LOCATED NO GREATER THAN 75
FEET AWAY FROM THE NEW TR. CONTRACTOR TO COORDINATE
THE NEW LOCATION WITH THE COR. CONTRACTOR SHALL BID A
NEW FEC FOR EACH TR IN THE SCOPE OF WORK. SEE
SPECIFICATION 10 44 13.
NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL
U465
(TYPE A) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
A3 3 5/8" 4 7/8" 35
NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL
V438, UL U411
(TYPE B) TYPICAL PARTITION
MARK STUD WIDTH PRTN WIDTH DESIGN STC
B 2 1/2" 3/4" 45
DOOR AND FRAME SCHEDULE
IDENTIFICATION DIMENSIONS PANEL FRAME
FIRE RATING
HARDWARE
NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH GROUP ELECTRICAL
BASEMENT B1C TELECOM ROOM B1C 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC 1,2,3
1/4" = 1'-0" B7
ARCHITECTURAL REFLECTED CEILING PLAN -
ROOM B1C - NEW
1/4" = 1'-0"
B5
ARCHITECTURAL REFLECTED CEILING PLAN -
ROOM B1C - DEMO
DOOR SCHEDULE NOTES:
1. TELECOM ROOM DOOR PANEL AND FRAME TO BE SMOKE RATED FOR TRANSITION,
INCLUDING CLOSER, SEALS, THRESHOLD, AND SWEEP.
2. PAINT DOOR TRIM TO MATCH EXISTING TRIM PAINT IN SPACE.
3. COORDINATE DOOR PANEL, FRAME, AND HARDWARE WITH ELECTRICAL HARDWARE
(ACCESS CONTROL, ELECTRICAL STRIKE, DOOR CONTACT SWITCH, ETC.) SEE ELECTRICAL
PLANS FOR ADDITIONAL INFORMATION.
Revisions: Date:
ASI 1 04/14/22
STORAGE SPACE
04/18/22
/18
/20
04/18/2022
| Sheets |
| 41A-400 - ARCHITECTURAL ENLARGED VIEWS - BASEMENT LEVEL |