589A6-21-700.LEHRM.ASI-001.B153.20220418.pdf

PDF 877 KB Posted

Attached to
Y1DZ--589A6-21-700 EHRM Infrastructure Upgrades Construction Leavenworth VAMC
Solicitation number
36C77622R0061
Issued by

About this file

This solicitation is for a federal construction contract to prepare a VA medical campus for an electronic health record modernization by replacing all telecommunications cabling, outlets, and associated equipment across multiple buildings. The scope of work includes replacing all copper cabling with CAT6a, installing new fiber optic cabling, adding 15% spare capacity, and ensuring no conduit exceeds 40% capacity. New patch panels, equipment racks with 40% spare capacity, cable support structures, and patch cables will be provided for each telecommunications room. Wall outlets will be upgraded to CAT6a, and color coding standards will be followed. Wireless access point cabling will be labeled purple. The contract also requires adding new computer room air conditioning systems, electrical panels, backup generators, and a new 600-ton water-cooled chiller to serve the new telecommunications rooms.

View the file

Other files

File Type Posted
01 00 00 Appendix A - Bid Form Template.20220505.xlsx XLSX spreadsheet
36C77622R0061 0004.pdf PDF
01 00 00 Appendix A - Bid Form Template.20220505.pdf PDF
Follow Up Technical Questions Tracking Spreadsheet - 5-5-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links - Rev01.pdf PDF
36C77622R0061 0003.pdf PDF
01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
589A6-21-700.LEHRM.ASI-001.B54.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B161.20220418.pdf PDF
Site Visit Attendance Sheet - LV EHRM Infra 4-11-22.pdf PDF
TR Space Impact - Leavenworth.pdf PDF
Technical Questions Tracking Spreadsheet - 4-27-22.pdf PDF
Leavenworth VA EHRM Project Lidar Links.pdf PDF
B7 Electrical Panel Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.SITE.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B42.20220418.pdf PDF
Attachment 14 - DBA Wage Rates - Leavenworth County - 4-15-22.pdf PDF
Unitary Disconnect Photos.zip ZIP file
589A6-21-700.LEHRM.ASI-001.B41.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B39.20220418.pdf PDF
Attachment 17 - Rev Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
01 00 00 Appendix A - Bid Form Template.pdf PDF
Unitary Cooling Photos.zip ZIP file
21 22 00 - Clean Agent Fire Suppression Systems.pdf PDF
23 64 00 - Packaged Water Chillers.ASI001.pdf PDF
589A6-21-700.LEHRM.ASI-001.B71.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.Summary.Log.20220419.pdf PDF
B88.89.90.91 Photos.zip ZIP file
Panel Photos.zip ZIP file
UPS Data Photos.zip ZIP file
589A6-21-700.LEHRM.IFC_R1.B39.20220119.pdf PDF
589A6-21-700.LEHRM.ASI-001.B21.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B160.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B122.20220418.pdf PDF
589A6-21-700.LEHRM.ASI-001.B90.20220419.pdf PDF
36C77622R0061 Amendment 0002.pdf PDF
36C77622R0061 Amendment 0001.pdf PDF
RFP 36C77622R0061.pdf PDF
Attachment 10 - 589A6-21-700 LEHRM IFC_R1 B161 Drawing.pdf PDF
Attachment 17 - Contractor Safety and Environmental Record Evaluation Form.docx DOCX document
Attachment 4 - 589A6-21-700 LEHRM IFC_R1 B54 Drawing.pdf PDF
Attachment 3 - 589A6-21-700 LEHRM IFC_R1 B42 Drawing.pdf PDF
Attachment 18 - VA Notice of Limitations on Subcontracting-Certificate of Compliance.docx DOCX document
Attachment 13 - Asbestos Report Part 2 of 7.zip ZIP file
Attachment 5 - 589A6-21-700 LEHRM IFC_R1 B71 Part 1 of 2 Drawing.pdf PDF
Attachment 7 - 589A6-21-700 LEHRM IFC_R1 B122 Drawing.pdf PDF
Attachment 2 - 589A6-21-700 LEHRM IFC_R1 B41 Drawing.pdf PDF
Attachment 13 - Asbestos Report Part 4 of 7.zip ZIP file
Attachment 13 - Asbestos Report Part 5 of 7.zip ZIP file
Attachment 6 - 589A6-21-700 LEHRM IFC_R1 B88-89-90-91 Part 3 of 3 Drawing.pdf PDF
Show 40 more

Latest 50 of 67 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SHEET SYMBOL LEGEND

KEYNOTES

GENERAL NOTES

EXISTING CONSTRUCTION TO REMAIN

EXISTING CONSTRUCTION TO BE DEMOLISHED

NEW CONSTRUCTION, WITH PARTITION TYPE

A

A. SEE GENERAL NOTES AND PLANS FOR TYPICAL GENERAL PROJECT

REQUIREMENTS AND PROJECT LOCATION DRAWINGS.

B. SEE INTERIOR FINISH DRAWINGS FOR ADDITIONAL FINISHES

INFORMATION.

C. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR ADDITIONAL

SYSTEMS INFORMATION.

D. NEW TELECOM ROOMS SHALL BE SMOKE RATED AND COMPLY WITH

THE LATEST VA PHYSICAL SECURITY STANDARDS, AND CAMPUS

STANDARDS.

E. SEE TYPICAL WALL FRAMING DETAILS ON SHEET A-511.

F. SEE TYPICAL HEAD OF WALL DETAIL ON SHEET A-512.

G. SEE TYPICAL CEILING DETAILS ON SHEET A-531

PARTITION RATING GRAPHICS:

4 HR FIRE BARRIER

3 HR FIRE BARRIER

2 HR FIRE & SMOKE BARRIER

2 HR FIRE BARRIER

2 HR FIRE BARRIER/SHAFT

1 HR FIRE & SMOKE BARRIER

1 HR FIRE BARRIER

1 HR FIRE BARRIER/SHAFT

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION: PRIORITY

1 HIGHEST

5 LOWEST

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE

RESISTANT, OR BOTH FIRE AND SMOKE RESISTANT ARE SHOWN

GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

153A-402

D8

TELECOM

ROOM

201A201A

ACOUSTICAL OR RATED

FLEXIBLE SEALANT

FLOOR LINE

ADD ONE LAYER OF 5/8" GWB,

ONE-SIDE WITH APPROVED UL

SETTING COMPOUND BETWEEN

LAYERS AND FASTENED TO

WALL AS REQUIRED, AT

EXISTING GWB WALL

ASSEMBLIES

STRUCTURAL DECK

EXISTING METAL STUDS AND

BATT INSULATION TO REMAIN

A/C GRADE, 3/4" FIRE-TREATED

PLYWOOD TO 8'-0" ABOVE FINISHED

FLOOR, ADHERED TO CONCRETE AT

EXISTING CONCRETE WALL

ASSEMBLIES

BOTTOM OF PLYWOOD

TO BE AT 12" AFF

UL DESIGN V497

1-HOUR PARTITION RATED FROM BOTH SIDES

EXISTING GWB OR

CONCRETE WALL

ASSEMBLY, WHERE OCCURS

SIDE OF

EXISTING

ROOM OR

CORRIDOR TO

REMAIN

153A-512

D5

153A-512

B5

ACOUSTICAL OR RATED

SEALANT BOTH SIDES

FLOOR LINE

5/8" GWB BOTH SIDES

SOUND ATTENUATION

BATTS (SAB) PER

SCHEDULE.

CEILING LINE

STRUCTURAL DECK

METAL STUDS, SIZE

PER SCHEDULE

153A-512

D5

A/C GRADE, 3/4" FIRE-

TREATED PLYWOOD TO 8'-0"

ABOVE FINISHED FLOOR

153A-512

B5

AT FIRE RATED

PARTITIONS

AT SMOKE RATED

PARTITIONS

BOTTOM OF PLYWOOD TO

BE AT 12" AFF

TELECOM

ROOM

201A

101 SF

B

A4

B

A

B

A4

A

B

TELECOM

ROOM

201A

ACTUAL: 101 SF

IT CLOSET

201A201A

MECHANICAL

ROOM

201201

IT CLOSET

201A201A

MECHANICAL

ROOM

2012012

1/2" 1/2"

VARIES

SEE PLAN

WALL - SEE PLAN

FOR TYPE

SEALANT - EA. SIDE

& ALL AROUND,

TYP.

HOLLOW METAL

FRAME

/2

V

A R

IE

S

S E

E P

L A

N

/2

4" 2"

ADJACENT WALL

WHERE OCCURS

SEALANT - EA SIDE &

ALL AROUND, TYP.

HOLLOW METAL

FRAME

WALL - SEE PLAN

FOR TYPE

F4

TYPICAL FRAME

H E

IG

H

T

2" WIDTH 2"

F5

FRAME TYPE ELEVATIONS DOOR TYPE ELEVATIONS

F

FLUSH

F2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

TRIPLE C - The A/E Group

4625 Lindell Blvd., 2nd Floor, 2064

St. Louis, MO 63108

MAT PERKINS

314-372-0067

B

IM

/5

A -2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e a t L e a v e n w o rt h K

S V

A M

C /5

A

-2

-7

.L E

H R

M .B

.A

R C

H .r v t

/1

/2

:0

:1

A

M

153A-402

ARCHITECTURAL ENLARGED VIEWS - SECOND

LEVEL

589A6-21-700

B153

01/19/2022 M. Perkins K. McDermott

ISSUED FOR

CONSTRUCTION

EHRM INFRASTRUCTURE

UPGRADES

4101 4th St Trafficway, Leavenworth, KS 66048

1/32" = 1'-0" F1

SECOND LEVEL REFERENCE PLAN

NOTE: FIRE RESISTANCE TEST FOR ONE HOUR RATED WALLS: UL

U465

(TYPE A) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

A4 4" 5 1/4" 35

NOTE: FIRE RESISTANCE TEST FOR TWO HOUR RATED WALLS: UL

V438, UL U411

(TYPE B) TYPICAL PARTITION

MARK STUD WIDTH PRTN WIDTH DESIGN STC

B 2 1/2" 3/4" 45

1/4" = 1'-0" D8

ARCHITECTURE FLOOR PLAN - SECOND

LEVEL - ROOM 201A - NEW

1/4" = 1'-0"

D6

ARCHITECTURE FLOOR PLAN - SECOND

LEVEL - ROOM 201A - DEMO

DOOR AND FRAME SCHEDULE

IDENTIFICATION DIMENSIONS PANEL FRAME DETAIL

FIRE RATING

HARDWARE

NOTESLEVEL ROOM NO. ROOM NAME DOOR NO. W1 H T TYPE MATERIAL FINISH GLAZING UNDERCUT TYPE MATERIAL FINISH HEAD JAMB SILL GROUP ELECTRICAL

LEVEL 2 201A TELECOM ROOM 201A 3' - 0" 7' - 0" 1 3/4" F WD WD NONE 3/8" 1 HM PTD 45 MIN HW-SH-3F SEE ELEC

1/4" = 1'-0" B6

ARCHITECTURE REFLECTED CEILING PLAN -

SECOND LEVEL - ROOM 201A - DEMO

1/4" = 1'-0"

B8

ARCHITECTURE REFLECTED CEILING PLAN -

SECOND LEVEL - ROOM 201A - NEW

3" = 1'-0"

B1

HOLLOW METAL HEAD DETAIL

3" = 1'-0" B3

HOLLOW METAL JAMB DETAIL

1/4" = 1'-0" D3

WRAPPED FRAME TYPES ELEVATIONS

1 REMOVE EXISTING WALL AND FRAMING.

2 REMOVE EXISTING DOOR AND FRAME.

3 NEW SMOKE RATED DOOR. SEE DOOR SCHEDULE AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION. COORDINATE

DOOR AND FRAME WITH ACCESS CONTROL HARDWARE.

4 EXISTING WALLS TO BECOME SMOKE-RATED. PATCH AND SEAL ALL

PENETRATIONS AS NECESSARY.

5 PROVIDE NEW FIRE EXTINGUISHER CABINET WITH A TYPE 2A:10B:C

FIRE EXTINGUISHER LOCATED NO GREATER THAN 75 FEET AWAY

FROM THE NEW TR. CONTRACTOR TO COORDINATE THE NEW

LOCATION WITH THE COR. CONTRACTOR SHALL BID A NEW FEC

FOR EACH TR IN THE SCOPE OF WORK. SEE SPECIFICATION 10 44

13.

6 TELECOM ROOM TO BE OPEN TO DECK ABOVE.

Revisions: Date:

ASI 1 04/14/22

MECHANICAL

ROOM

04/18/22

/18

/20

Sheets
153A-402 - ARCHITECTURAL ENLARGED VIEWS - SECOND LEVEL

File details come from the government source that posted it. Updated .