8-Exhibit G_NFPA 110 EPSS Maintenance Log_04012026_BA.pdf

PDF 187 KB Posted

Attached to
Generator IDIQ Contract
Solicitation number
1164311
Issued by

About this file

This is Exhibit G: NFPA 110 EPSS Maintenance Log, a template document for the BARC EPSS (Generator/ATS/MTS) Maintenance and Repair IDIQ contract at the Beltsville Agricultural Research Center (BARC), USDA-ARS in Beltsville, Maryland. The document provides a standardized maintenance logging format based on NFPA 110-2022 Figure A.8.3.1(b) for recording emergency power supply system inspections and maintenance activities.

The maintenance log is organized by system component categories including Fuel System, Lubrication System, Cooling System, Exhaust System, Battery System, Electrical System, Prime Mover (Engine), Generator End, Automatic Transfer Switch, and General Condition. Each component lists specific inspection and maintenance tasks with two maintenance levels (Level 1 and Level 2) indicating required frequency using standardized abbreviations: W (Weekly), M (Monthly), Q (Quarterly), S (Semi-Annual), and A (Annually). Select tasks reference time-based intervals such as every 3 years or 500 hours, every 5 years or 500 hours, or every 3 years for 4 hours. The log includes fields for recording generator model, engine model, installation date, standby kW nameplate rating, 30 percent of standby rating, fuel type, normal operating temperature, performer initials, and dates with columns for recording readings and observations across multiple maintenance visits. This template serves as a record-keeping tool to ensure compliance with NFPA 110 standards for emergency power system maintenance at the facility.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BARC EPSS (Generator/ATS/MTS) Maintenance and Repair IDIQ Beltsville Agricultural Research Center (BARC) USDA-ARS, Beltsville, MD

Exhibit G NFPA 110 EPSS Maintenance Log

EPSS Maintenance Log Source: NFPA 110-2022 Figure A.8.3.1(b)

Generator Model: Engine Model: Date Installed:

Standby kW nameplate rating: kW 30% of Standby Rating: kW Fuel: Normal Operating Temp: F Performed by: (Initials)

W=Weekly S=Semi-Annual M=Monthly A=Annually

Q=Quarterly #'s=hours Component (as applicable) Level 1 Level 2

Fuel System Main supply tank level W M Day tank level W M Day tank float switch W Q Supply or transfer pump operation W Q Solenoid valve operation W Q Strainer, filter and/or dirt leg Q Q Water in system W Q Flexible hose and connectors W M Tank vents/overflow pipe blocked A A Piping A A Wiring in fuel system A A Fuel in main tank A A

Lubrication System Oil level W M Oil change 50 or A 50 or A Oil filter 50 or A 50 or A Lube oil heater W M Crankcase breather Q S

Cooling System Coolant level W M Antifreeze protection level S A Antifreeze A A Adequate cooling water to heat exchanger W M Rod out heat exchanger A A Adequate fresh air through radiator W M Clean exterior of radiator A A Fan and alternator belts M Q Water pump W Q Flexible water hoses and connections W M Jacket water heater W M Inspect ductwork, clean louvers A A Louver motor and controls A A

Exhaust System Leakage W M Drain condensate trap W M Insulation and fire hazards Q Q Excessive back pressure A A Exhaust system hanger and supports A A Flexible exhaust section S S

Battery System Electrolyte level W M Terminals clean and tight Q Q Remove corrosion from case M M Specific gravity or state of charge M M Charger and charge rate M M Equalize charge M M

Fill In Appropriate Readings

Date

Generator Model: Engine Model: Date Installed:

Standby kW nameplate rating: kW 30% of Standby Rating: kW Fuel: Normal Operating Temp: F Performed by: (Initials)

W=Weekly S=Semi-Annual M=Monthly A=Annually

Q=Quarterly #'s=hours Component (as applicable) Level 1 Level 2

Electrical System General inspection W M Tighten control and power wiring connections A A Wire chafing if subject to movement Q S Operation of safeties and alarms S S Boxes, panels and cabinets S S Circuit breakers, fuses M A Transfer switch main contacts A A Calibration of voltage-sensing relays/devices A A Wire insulation breakdown 5/500a 3/500b

Prime Mover (Engine) General inspection W M Service air cleaner S S Governor oil level and linkage M M Governor oil A A Ignition system - plugs, cap, rotor, secondary wire insulation A A Choke setting and carburetor adjustment S S Injector pump and injectors for flow rate, pressure, and/or spray pattern A A Load test at minimum of 30% nameplate rating 3/4c 3/4c

Valve clearance 3/500b 3/500b

Torque bolts 3/500b 3/500b

Generator End Brush length, appearance free to move in holder S S Commutator and slip rings A A Rotor and stator A A Bearings A A Bearing grease A A Exciter A A Voltage regulator A A Measure and record resistance readings of windings with insulation tester (Megger) A A

General Condition Unusual noises, vibrations, leakage, temperatures or deterioration W M Service room/surrounding area W M Restore system to automatic operation condition W M a Every 5 years or 500 hours b Every 3 years or 500 hours c Every 3 years for 4 hours

Generator Model: Engine Model: Date Installed:

Standby kW nameplate rating: kW 30% of Standby Rating: kW Fuel: Normal Operating Temp: F Performed by: (Initials)

W=Weekly S=Semi-Annual M=Monthly A=Annually

Q=Quarterly #'s=hours Component (as applicable) Level 1 Level 2

Automatic Transfer Switch General inspection W M Exercise the system under load W M Automatic control system M Q Cabinet exterior M Q Tighten external components M Q External operating mechanism Q A Inspect interior of transfer switch Q A Tighten internal components A A LED indicators and remote control systems operation A A Transfer switch main contacts A A Tighten wiring connections A A Thermographic temperature scan A A Wire insulation deterioration A A