9-Exhibit H_NFPA 110 EPSS Suggested Maintenance Schedule_04012026_BA.pdf

NFPA Standard PDF 186 KB Posted

Attached to
Generator IDIQ
Solicitation number
1232SA26Q1346
Issued by

About this file

This document is Exhibit H of the BARC EPSS (Generator/ATS/MTS) Maintenance and Repair IDIQ contract for the Beltsville Agricultural Research Center (BARC), USDA-ARS in Beltsville, Maryland. It presents the NFPA 110-2022 suggested maintenance schedule for Emergency Power Supply Systems (EPSS).

The schedule establishes maintenance frequencies across two compliance levels (Level 1 and Level 2) for multiple EPSS component categories: Fuel System, Lubrication System, Cooling System, Exhaust System, Battery System, Electrical System, Prime Mover (Engine), Generator End, General Condition, and Automatic Transfer Switch. Maintenance actions are identified through visual inspection, checking, changing, cleaning, and testing, with frequencies designated as Weekly (W), Monthly (M), Quarterly (Q), Semi-Annual (S), or Annually (A). Specific components require attention at defined intervals; for example, oil changes occur at 50 hours or annually, while certain inspections such as wire insulation breakdown testing occur every 5 years or 500 hours, and valve clearance checks occur every 3 years or 500 hours. The schedule distinguishes between action items (marked X) and replacement requirements (marked R, if needed), providing contractors with comprehensive guidance for maintaining EPSS equipment at the facility to ensure operational readiness and compliance with NFPA 110 standards.

View the file

Other versions and copies of NFPA 110

File Revision Posted Attached to
ATTACHMENT A-NFPA 110-19(STANDARD FOR EMERGENCY POWER).pdf 2019 edition J059--SOURCES SOUGHT NOTICE- ANNUAL ATS AND PARALLEL SWITCH GEAR INSPECTION SERVICES
NFPA 110 2010 Edition Chapter 8.pdf 2010 Service of Emergency generator, automatic transfer switches, and relay panels FY24-26
Quarterly_Inspection_Checklist_2005_NFPA_110_Annex_A _Figure_A_8.3.1(a).docx 2005 Generator and Transfer Switch Service & Repairs
Quarterly_Inspection_Checklist_2005_NFPA_110_Annex_A _Figure_A_8.3.1(a).docx 2005 Emergency Generator Service and Repair Contract
11-Exhibit J_NFPA 110 EPSS Operational Test Report_04012026_BA.pdf Revision not stated Generator IDIQ
7-Exhibit F_NFPA 110 EPSS Maintenance History Form_04012026_BA.pdf Revision not stated Generator IDIQ
10-Exhibit I_NFPA 110 EPSS Maintenance and Operation Testing Log_04012026_BA.pdf Revision not stated Generator IDIQ
8-Exhibit G_NFPA 110 EPSS Maintenance Log_04012026_BA.pdf Revision not stated Generator IDIQ
10-Exhibit I_NFPA 110 EPSS Maintenance and Operation Testing Log_04012026_BA.pdf Revision not stated Generator IDIQ Contract
9-Exhibit H_NFPA 110 EPSS Suggested Maintenance Schedule_04012026_BA.pdf Same revision and size as this file Revision not stated Generator IDIQ Contract
8-Exhibit G_NFPA 110 EPSS Maintenance Log_04012026_BA.pdf Revision not stated Generator IDIQ Contract
11-Exhibit J_NFPA 110 EPSS Operational Test Report_04012026_BA.pdf Revision not stated Generator IDIQ Contract
7-Exhibit F_NFPA 110 EPSS Maintenance History Form_04012026_BA.pdf Revision not stated Generator IDIQ Contract
11-Exhibit J_NFPA 110 EPSS Operational Test Report_04012026_BA.pdf Revision not stated Generator Maintenance
8-Exhibit G_NFPA 110 EPSS Maintenance Log_04012026_BA.pdf Revision not stated Generator Maintenance
9-Exhibit H_NFPA 110 EPSS Suggested Maintenance Schedule_04012026_BA.pdf Same revision and size as this file Revision not stated Generator Maintenance
7-Exhibit F_NFPA 110 EPSS Maintenance History Form_04012026_BA.pdf Revision not stated Generator Maintenance
10-Exhibit I_NFPA 110 EPSS Maintenance and Operation Testing Log_04012026_BA.pdf Revision not stated Generator Maintenance
S.O.W. NFPA-110.pdf Revision not stated NFPA 110 Course Power Generating Equipment Training
RFQ_NFPA_110.pdf Revision not stated NFPA 110 and Power Gerating Equipment Training
Show all 20

Who attaches NFPA 110

State Files
Massachusetts 1

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

BARC EPSS (Generator/ATS/MTS) Maintenance and Repair IDIQ Beltsville Agricultural Research Center (BARC) USDA-ARS, Beltsville, MD

Exhibit H NFPA 110 EPSS Suggested Maintenance Schedule

EPSS Maintenance Schedule Suggested Maintenance Schedule for Emergency Power Supply Systems (EPSSs) Source: NFPA 110-2022 Figure A.8.3.1(a)

W=Weekly S=Semi-Annual M=Monthly A=Annually

Visual Q=Quarterly #'s=hours Component (as applicable) Inspection Check Change Clean Test Level 1 Level 2

Fuel System Main supply tank level X W M Day tank level X X W M Day tank float switch X X W Q Supply or transfer pump operation X X W Q Solenoid valve operation X X W Q Strainer, filter and/or dirt leg X Q Q Water in system X X W Q Flexible hose and connectors X R W M Tank vents/overflow pipe blocked X X A A Piping X A A Wiring in fuel system X A A Fuel in main tank R A A

Lubrication System Oil level X X W M Oil change R 50 or A 50 or A Oil filter R 50 or A 50 or A Lube oil heater X W M Crankcase breather X R X Q S

Cooling System Coolant level X X W M Antifreeze protection level X S A Antifreeze R A A Adequate cooling water to heat exchanger X W M Rod out heat exchanger X A A Adequate fresh air through radiator X W M Clean exterior of radiator X A A Fan and alternator belts X X M Q Water pump X W Q Flexible water hoses and connections X X W M Jacket water heater X W M Inspect ductwork, clean louvers X X X A A Louver motor and controls X X X A A

Exhaust System Leakage X X W M Drain condensate trap X W M Insulation and fire hazards X Q Q Excessive back pressure X X A A Exhaust system hanger and supports X A A Flexible exhaust section X S S

Battery System Electrolyte level X W M Terminals clean and tight X X Q Q Remove corrosion from case X X M M Specific gravity or state of charge X M M Charger and charge rate X M M Equalize charge X M M

(X=Action; R=Replace, if needed)

Source: NFPA 110-2022 Figure A.8.3.1(a)

W=Weekly S=Semi-Annual M=Monthly A=Annually

Visual Q=Quarterly #'s=hours Component (as applicable) Inspection Check Change Clean Test Level 1 Level 2

Electrical System General inspection X W M Tighten control and power wiring connections X A A Wire chafing if subject to movement X X Q S Operation of safeties and alarms X S S Boxes, panels and cabinets X S S Circuit breakers, fuses X X R X X M A Transfer switch main contacts X X A A Calibration of voltage-sensing relays/devices X X A A Wire insulation breakdown X 5/500a 3/500b

Prime Mover (Engine) General inspection X W M Service air cleaner R X S S Governor oil level and linkage X X M M Governor oil R A A Ignition system - plugs, cap, rotor, secondary wire insulation X X R X X A A Choke setting and carburetor adjustment X S S Injector pump and injectors for flow rate, pressure, and/or spray pattern X A A Load test at minimum of 30% nameplate rating X 3/4c 3/4c

Valve clearance X 3/500b 3/500b

Torque bolts X 3/500b 3/500b

Generator End Brush length, appearance free to move in holder X X X S S Commutator and slip rings X X A A Rotor and stator X X A A Bearings X R A A Bearing grease X R A A Exciter X X X A A Voltage regulator X X X A A Measure and record resistance readings of windings with insulation tester (Megger) X A A

General Condition Unusual noises, vibrations, leakage, temperatures or deterioration X X W M Service room/surrounding area X X W M Restore system to automatic operation condition X W M a Every 5 years or 500 hours b Every 3 years or 500 hours c Every 3 years for 4 hours

Source: NFPA 110-2022 Figure A.8.3.1(a)

W=Weekly S=Semi-Annual M=Monthly A=Annually

Visual Q=Quarterly #'s=hours Component (as applicable) Inspection Check Change Clean Test Level 1 Level 2

Automatic Transfer Switch General inspection X W M Exercise the system under load X W M Automatic control system X M Q Cabinet exterior X X M Q Tighten external components X X M Q External operating mechanism X X Q A Inspect interior of transfer switch X Q A Tighten internal components X X A A LED indicators and remote control systems operation X A A Transfer switch main contacts X R X A A Tighten wiring connections X A A Thermographic temperature scan X A A Wire insulation deterioration X A A

File details come from the government source that posted it. Updated .