618-21-700.MEHRM.FINAL.B70.20220506Part-13.pdf

PDF 19 MB Posted

Attached to
EHRM Infrastructure Upgrades Construction Design-Bid Build Project at the Minneapolis VA Medical Center (VAMC)
Solicitation number
36C77622R0045
Issued by

About this file

This document describes a federal solicitation for construction services. The solicitation is being issued by the Department of Veterans Affairs to upgrade infrastructure in support of an Electronic Health Record Modernization project at the Minneapolis VA Medical Center. The scope of work includes construction and commissioning activities to build out a new server room and make other improvements throughout the hospital according to design plans. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and offers from other than SDVOSB concerns will not be considered. The period of performance is approximately 450 calendar days with a magnitude of construction estimated between $20-50 million. Questions regarding the solicitation must be submitted in writing by the deadline.

View the file

Other files

File Type Posted
Technical Question Tracking Sheet Infra Upgrades FINAL.pdf PDF
36C77622R0045 0009.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-11.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-1.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-7.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-2.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-6.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-4.pdf PDF
618-21-700.ADD-001.Summary.Log.20220707.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-9.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-5.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-10.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-3.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-8.pdf PDF
36C77622R0045 0008.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades - FINAL.pdf PDF
36C77622R0045 0007.pdf PDF
36C77622R0045 0006.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades - Minneapolis.docx DOCX document
36C77622R0045 0005.docx DOCX document
36C77622R0045 0004.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades.docx DOCX document
36C77622R0045 0003.pdf PDF
Site Visit Sign In sheet.pdf PDF
36C77622R0045 0002.pdf PDF
36C77622R0045 0001.pdf PDF
36C77622R0045 - Update 5.23.22.docx DOCX document
618-21-700.MEHRM.FINAL.B70.20220506Part-7.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-11.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-33-36.zip ZIP file
618-21-700.MEHRM.FINAL.B76.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-48-52.zip ZIP file
36C77622R0045.docx DOCX document
618-21-700.MEHRM.FINAL.B70.20220506Part-21.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-25-28.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-4.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-23.pdf PDF
618-21-700.MEHRM.FINAL.B75.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL_SPECIFICATIONS.20220506Part-2.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-45-47.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-6.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-20.pdf PDF
618-21-700.MEHRM.FINAL.B73.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B49.20220506-REDUCED.pdf PDF
01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
618-21-700.MEHRM.FINAL.SITE.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B222.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-12.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-16-17.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-29-32.zip ZIP file
Show 40 more

Latest 50 of 80 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

C R

R X

D C

EH

R X

C R

EH D

C

M

LM

L

E L

E L

DC

DC

M L

M L

O

SC

R

ES R

XD

C

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

4U-1014U-101

TELECOM

ROOM

4U-100A4U-100A

4D-1224D-122

4S-94S-9

4C-1074C-107

4U-1034U-103

4U-104A4U-104A 4U-1044U-104

4U-1054U-105

4U-1064U-106 4U-1074U-107

4U-1084U-108

4S-130A4S-130A

4S-130B4S-130B

4S-130C4S-130C

4S-130D4S-130D

4S-130E4S-130E

4S-130F4S-130F

4S-130G4S-130G4S-130H4S-130H

4S-1324S-132

4S-1354S-135

4S-1364S-136

4S-1374S-137

4S-1384S-138

4S-1394S-139

4S-1404S-140

4S-1414S-141

4S-1424S-142

4S-1434S-143

4S-1444S-144

4S-1454S-145

4S-1334S-133

CC

4U-1004U-100

4T-1054T-105

C4-197C4-197

C4-4C4-4

C4-23C4-23 4U-1094U-109 C4-41C4-41

C4-22C4-22

4S-1304S-130

4S-1314S-131

4S-1344S-134

C4-1C4-1

C4-2C4-2

C4-6C4-6 C4-7C4-7 C4-8C4-8

C4-9C4-9

4U-104C4U-104C

C4-11C4-11

C4-12C4-12

C4-13C4-13

C4-14C4-14

C4-15C4-15

C4-16C4-16

C4-8AC4-8A

4U-104D4U-104D4U-104B4U-104B

4E-1534E-153

4S-1294S-129

4D-1474D-147 4D-1484D-148 4D-1494D-149 4D-1504D-150 4D-1514D-151 4D-1524D-152

4D-1464D-146 4D-1454D-145 4D-1444D-144

4D-1374D-137

4D-1344D-134 4D-1354D-135 4D-1364D-136

4D-137A4D-137A

4D-1384D-138

4D-1434D-143

4D-1424D-142

4D-1394D-139

4D-1414D-141

4D-1404D-140

4D-1334D-133 4D-132A4D-132A 4D-1324D-132

4D-1214D-121 4D-1234D-123 4D-1244D-124

4D-1254D-125

4D-1314D-131

4D-1264D-126 4D-1274D-127

4D-1304D-130 4D-1294D-129

4D-1284D-128

C4D-036C4D-036

C4D-037C4D-037

C4-19C4-19

C4-20C4-20

4S-130F4S-130F 4D-1334D-133

C4-20C4-20

4D-1224D-122

4D-122A4D-122A

4D-122B4D-122B

4U-1094U-109

4U-1014U-101 4C-1074C-107

4S-130A4S-130A

4S-130B4S-130B

4S-130C4S-130C

4S-1334S-133

4U-1004U-100

4T-1054T-105

C4-197C4-197

C4-22C4-22

4S-1314S-131

C4-1C4-1

70E-446 F5

70E-446 F7 on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

A

B D

TRUE NORTH

PLAN NORTH

E F

G

H

J

K

L

M

C

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a st ru ct u re

U p g ra d e s

M P

L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r vt /6

/2

:2 :4

P

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-104A

ELECTRICAL PLAN - FOURTH LEVEL AREA A

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. NOT USED.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. NOT USED.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR

PRIOR TO BEGINNING OF CONSTRUCTION.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES ARE

USED ON EACH SHEET

SCALE: 1" = 10'-0"

F2

ELECTRICAL PLAN - FOURTH LEVEL

AREA A

05/06/2022

X

C R

EH D

C

CR

E

SRXDC

R X

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

4S-130G4S-130G4S-130H4S-130H4T-1054T-105

4S-1284S-128

4S-1294S-129

C4-20C4-20

4D-1214D-121

4S-1014S-101

4S-1024S-102

4S-1034S-103

4S-1044S-104

4S-1054S-105

4S-1184S-118

4S-1234S-123

4S-1244S-124

4S-1254S-125

4S-1264S-126

4S-1274S-127

4S-24S-2

4T-1024T-102

4T-102A4T-102A

4T-102C4T-102C

M-4M-4

4T-1014T-101

AA

BB

4A-1054A-105 4A-1064A-106

4A-1074A-107

4A-1084A-108

4A-1094A-109

4A-1104A-110

4S-54S-5

4A-110A4A-110A

4A-107A4A-107A

4S-34S-3

C4-89C4-89

4B-1014B-101

4B-1024B-102

4B-1034B-103

4B-1044B-104

4B-1054B-105 4B-1064B-106 4B-1074B-107

4B-1084B-108

4B-1094B-109 4B-1104B-110

4B-1114B-111 4B-108B4B-108B

4B-1134B-113

4B-1144B-114

4B-1154B-115

4B-1164B-116

4B-1174B-117

4B-1184B-118

4B-1194B-119 4B-1204B-120

4B-1214B-1214B-1224B-1224B-1234B-123

4B-1244B-124

4B-1254B-125

4B-1264B-126

4B-1274B-127

4B-1284B-128

4B-1294B-1294B-1304B-130

4B-1314B-131

4B-1324B-1324B-1334B-133

4B-1344B-134

4B-1354B-135

4B-1364B-136

4B-1374B-137

4B-1404B-140

4B-1414B-141

4B-1424B-1424B-1434B-143 4B-1444B-144

4B-1454B-145

4B-1464B-146

4B-1474B-147

4B-1494B-149

4B-1504B-150

4B-1514B-151 4B-1524B-1524B-1534B-1534B-1544B-154

4B-1554B-155 4B-1564B-156

4B-1574B-157

4B-101B4B-101B

4B-101C4B-101C

4B-108A4B-108A

4B-1584B-158 4B-1594B-159 4B-1604B-160

4S-44S-4

C4-181C4-181

C4-32C4-32

C4-86C4-86

4S-1214S-121

4S-1224S-122

4T-102B4T-102B

C4-76C4-76

C4-80C4-80

C4-82C4-82

C4-79C4-79

C4-84C4-84

C4-73C4-73

C4-72C4-72

C4-72AC4-72A

C4-74C4-74

C4-28C4-28 C4-29C4-29

C4-30C4-30

C4-183C4-183

C4-184C4-184

C4-185C4-185

4B-1394B-139

C4-88C4-88

C4-182C4-182

C4-31C4-31

4S-1004S-100

4B-1004B-100

4B-108C4B-108C

4D-1204D-120

4D-1084D-108

4C-1174C-117

C-10C-10 4A-1014A-101

4A-1024A-102

4A-1034A-103

M2M2

C9C9

4M-1054M-105

C4-90C4-90

C4-179C4-179

4B-1604B-160

C4-32C4-32C4-32C4-32

C4-72C4-72C4-72C4-72

4S-1014S-101

C4-181C4-181

4T-1054T-105

4S-1054S-105

4S-24S-2C4-185C4-185

C4-20C4-20 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

A

B D

TRUE NORTH

PLAN NORTH

E F

G

H

J

K

L

M

C

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a st ru ct u re

U p g ra d e s

M P

L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r vt /6

/2

:2 :0

P

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-104B

ELECTRICAL PLAN - FOURTH LEVEL AREA B

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. NOT USED.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. NOT USED.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR

PRIOR TO BEGINNING OF CONSTRUCTION.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES ARE

USED ON EACH SHEET

SCALE: 1" = 10'-0"

F3

ELECTRICAL PLAN - FIRST LEVEL

AREA B

E

LDC

D C

ES

C R

R X

O S

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

C4-41C4-414E-1534E-153

4D-1474D-147 4D-1484D-148 4D-1494D-149 4D-1504D-150 4D-1514D-151 4D-1524D-152

4D-1464D-146 4D-1454D-145 4D-1444D-144

4D-1374D-137

4D-1344D-134 4D-1354D-135 4D-1364D-136

4D-137A4D-137A

4D-1384D-138

4D-1434D-143

4D-1424D-142

4D-1394D-139

4D-1414D-141

4D-1404D-140

4D-1334D-133 4D-132A4D-132A 4D-1324D-132

4D-1214D-121 4D-1234D-123 4D-1244D-124

4D-1254D-125

4D-1314D-131

4D-1264D-126 4D-1274D-127

4D-1304D-130 4D-1294D-129

4D-1284D-128

4D-1004D-100

C4D-036C4D-036

C4D-037C4D-037

4D-1334D-133

4D-1204D-120

4D-1084D-108

4D-1074D-107

4C-1174C-117

C4D-034C4D-034

C4D-035C4D-035

C4-33C4-33

4D-1014D-101

4D-1194D-119

4D-1094D-109

4D-1184D-118

4D-1104D-110

4D-1114D-111

4D-1174D-117

4D-111C4D-111C

4D-1124D-112

4D-1164D-116

4D-1134D-113

4D-1154D-115

4D-1144D-114

4C-1184C-118

4D-1064D-106 4D-1044D-104

4C-1174C-117

4D-1024D-102

4D-1054D-105

4D-1034D-1034D-1034D-103

TELECOM

ROOM

4C-1214C-121 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

A

B D

TRUE NORTH

PLAN NORTH

E F

G

H

J

K

L

M

C

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a st ru ct u re

U p g ra d e s

M P

L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r vt /6

/2

:2 :1

P

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-104C

ELECTRICAL PLAN - FOURTH LEVEL AREA C

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. NOT USED.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. NOT USED.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR

PRIOR TO BEGINNING OF CONSTRUCTION.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES ARE

USED ON EACH SHEET

SCALE: 1" = 10'-0"

F6

ELECTRICAL PLAN - FOURTH LEVEL

AREA C

CR

H

RXDC

D

CELML

D C

ES

C R

R X

O S

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

4D-1004D-100

4B-1114B-111

4B-1184B-118

4B-1204B-120

4B-1604B-160

DD

4S-44S-4

4C-1174C-117

4C-1094C-109

4C-1144C-114

C4-33C4-33

4C-108D4C-108D

4C-108A4C-108A

4F-1074F-107

4B-1604B-160

4D-1014D-101

4C-1184C-118 4C-1174C-117

4C-108C4C-108C

4E-1074E-107

4E-116A4E-116A C4-44C4-44

4C-108A4C-108A

4E-122C4E-122C

4E-122A4E-122A

4E-122B4E-122B

M7M7

4C-1064C-1064C-1084C-108

4C-1124C-112

4C-1104C-110

4C-1104C-110

4C-1114C-111

C4-69C4-69

C4-70C4-70

C4-47C4-47

C4-46C4-46C4-58C4-58

4E-105A4E-105A 4E-1054E-105

4C-116A4C-116A

4E-1024E-102

4C-1154C-115

4E-1014E-1014C-1134C-113

4E-1604E-160

4E-1084E-108 4E-1204E-120

4E-1094E-109 4E-1194E-119

4E-1104E-110 4E-1184E-118

4E-1114E-111

4E-1124E-112 4E-111C4E-111C 4E-1174E-117

4E-1134E-113 4E-1284E-128

4E-1144E-114 4E-1154E-115

4E-1234E-123 4E-1304E-130

4E-1244E-124

4E-125A4E-125A

4E-1254E-125

4E-1264E-126

4E-1274E-127

4E-1284E-128 4E-1294E-129

4E-1314E-131

4E-1294E-129

4E-1344E-134 4E-1464E-146

4E-1354E-135 4E-1454E-145

4E-1364E-136 4E-1444E-144

4E-1374E-137

4E-1384E-138 4E-137A4E-137A 4E-1434E-143

4E-1394E-139 4E-1424E-142

4E-1404E-140 4E-1414E-141

4E-1524E-152

4E-1514E-151

4E-1504E-150

4E-1494E-149

4E-1484E-148

C4E-038C4E-038

4E-137B4E-137B

C4E-037C4E-037

4E-137C4E-137C

C4E-036C4E-036C4E-035C4E-035

4E-123A4E-123A

4E-111A4E-111A

C4E-034C4E-034

4E-1214E-121 4E-1334E-133

4E-1024E-102

4E-1004E-100

4E-1474E-147

C4-45C4-45

4F-1014F-101

4F-1004F-1004F-1054F-105

4F-1064F-106

C4-70C4-70

4E-1474E-147

4F-1004F-100

70E-445 C5

70E-445 C7

TELECOM

ROOM

4C-1214C-121 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

A

B D

TRUE NORTH

PLAN NORTH

E F

G

H

J

K

L

M

C

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a st ru ct u re

U p g ra d e s

M P

L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r vt /6

/2

:2 :3

P

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-104D

ELECTRICAL PLAN - FOURTH LEVEL AREA D

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. NOT USED.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. NOT USED.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR

PRIOR TO BEGINNING OF CONSTRUCTION.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES ARE

USED ON EACH SHEET

SCALE: 1" = 10'-0"

F3

ELECTRICAL PLAN - FOURTH LEVEL

AREA D

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

4B-1184B-118

4B-1204B-120

4C-1144C-114

4F-1074F-107

4C-1124C-112

4C-1114C-111

C4-69C4-69

4E-1014E-1014C-1134C-113

4E-1604E-160 4F-1014F-101

4F-1034F-103

4F-1004F-1004F-1054F-105

4F-1064F-106

C4F-066C4F-066

4F-1084F-108 4F-1044F-104

4F-1094F-109

4F-1204F-120

4F-1104F-110

4F-119A4F-119A

4F-1114F-111

4F-1194F-119

4F-1124F-112

4F-112C4F-112C

4F-1184F-118

4F-1144F-114

4F-1174F-117

4F-1154F-115

4F-1164F-116

4F-1224F-122

4F-1344F-134

4F-1234F-123

4F-1334F-133 4F-1324F-132

4F-1244F-124

4F-1254F-125

4F-1264F-126

4F-1314F-131

4F-1274F-127

4F-1304F-130

4F-1284F-128

4F-1294F-129

4F-1354F-135

4F-1464F-146 4F-1454F-145

4F-135A4F-135A 4F-1364F-136

4F-1444F-144

4F-1374F-137 4F-137B4F-137B

4F-1384F-138

4F-1434F-143

4F-1394F-139

4F-1424F-142

4F-1404F-140

4F-1414F-141

4F-1474F-147 4F-1484F-148 4F-1494F-149 4F-1504F-150 4F-1514F-151

4F-1024F-102

C4F-061C4F-061

C4F-060C4F-060

C4F-062C4F-062

C4F-063C4F-063

C4F-064C4F-064

4F-137A4F-137A

4F-137C4F-137C

4F-125A4F-125A

4L-117B4L-117B

4F-121A4F-121A

4F-121B4F-121B

C4F-065C4F-065

4F-1474F-147

C4F-060C4F-060

C4F-062C4F-062

C4F-063C4F-063

C4F-064C4F-064

4F-1004F-100

C4F-066C4F-066 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

A

B D

TRUE NORTH

PLAN NORTH

E F

G

H

J

K

L

M

C

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a st ru ct u re

U p g ra d e s

M P

L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r vt /6

/2

:2 :4

P

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-104E

ELECTRICAL PLAN - FOURTH LEVEL AREA E

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. NOT USED.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. NOT USED.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR

PRIOR TO BEGINNING OF CONSTRUCTION.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES ARE

USED ON EACH SHEET

SCALE: 1" = 10'-0"

F6

ELECTRICAL PLAN - FOURTH LEVEL

AREA E

SDCRX

D C

EL

ML

M L

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

4A-1104A-110

4B-1184B-118

4B-1214B-1214B-1224B-1224B-1234B-1234B-1254B-1254B-1294B-1294B-1304B-1304B-1324B-1324B-1334B-1334B-1354B-1354B-1424B-1424B-1434B-143 4B-1444B-1444B-1514B-151

4B-1524B-1524B-1534B-1534B-1544B-154

4B-1554B-155 4B-1564B-156

4B-1574B-157

C4-72C4-72

4F-1074F-107

4G-1014G-101

4G-1024G-102 4G-1034G-103

C4-100C4-100

C4-90C4-90

C4-72C4-72C4-72C4-72

4F-1084F-108

4F-1094F-109

4F-1204F-120

4F-1224F-122

4F-1344F-134

4F-1354F-135

4F-1464F-146

4L-117B4L-117B

4G-1044G-104

4G-1054G-105

4G-1064G-106

4G-109B4G-109B

4G-1074G-107

4G-109D4G-109D

4G-109E4G-109E

4G-1114G-111

4G-1124G-112

4G-1144G-114

4S-64S-6 4H-1214H-121

4H-1224H-122

4H-1234H-123

C4-116C4-116

4G-1094G-109

4G-1164G-116 4G-1154G-115 4G-111C4G-111C 4G-111B4G-111B 4G-111A4G-111A

4G-1104G-110 4G-109C4G-109C

4G-109A4G-109A

4H-1204H-120

EE

C-6C-6

4L-1014L-101

4L-1084L-108 4L-1094L-109 4L-1104L-110 4L-1124L-112

4L-1134L-113 4L-1154L-115 4L-1174L-117 4L-117A4L-117A

4L-117A4L-117A2323

4H-1014H-101

28282828

4S-64S-6

C4-100C4-100

EE

C4-100C4-100 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

A

B D

TRUE NORTH

PLAN NORTH

E F

G

H

J

K

L

M

C

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a st ru ct u re

U p g ra d e s

M P

L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r vt /6

/2

:2 :0

P

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-104F

ELECTRICAL PLAN - FOURTH LEVEL AREA F

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. NOT USED.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. NOT USED.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS…