This document describes a federal solicitation for construction services. The solicitation is being issued by the Department of Veterans Affairs to upgrade infrastructure in support of an Electronic Health Record Modernization project at the Minneapolis VA Medical Center. The scope of work includes construction and commissioning activities to build out a new server room and make other improvements throughout the hospital according to design plans. The solicitation will be set aside for Service-Disabled Veteran-Owned Small Businesses and offers from other than SDVOSB concerns will not be considered. The period of performance is approximately 450 calendar days with a magnitude of construction estimated between $20-50 million. Questions regarding the solicitation must be submitted in writing by the deadline.
View the file
Other files
Show 40 more
Latest 50 of 80 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
C R
R X
D C
EH
R X
C R
EH D
C
M
LM
L
E L
E L
DC
DC
M L
M L
O
SC
R
ES R
XD
C
PARTITION RATING GRAPHICS:
2 HR FIRE SHAFT
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
4U-1014U-101
TELECOM
ROOM
4U-100A4U-100A
4D-1224D-122
4S-94S-9
4C-1074C-107
4U-1034U-103
4U-104A4U-104A 4U-1044U-104
4U-1054U-105
4U-1064U-106 4U-1074U-107
4U-1084U-108
4S-130A4S-130A
4S-130B4S-130B
4S-130C4S-130C
4S-130D4S-130D
4S-130E4S-130E
4S-130F4S-130F
4S-130G4S-130G4S-130H4S-130H
4S-1324S-132
4S-1354S-135
4S-1364S-136
4S-1374S-137
4S-1384S-138
4S-1394S-139
4S-1404S-140
4S-1414S-141
4S-1424S-142
4S-1434S-143
4S-1444S-144
4S-1454S-145
4S-1334S-133
CC
4U-1004U-100
4T-1054T-105
C4-197C4-197
C4-4C4-4
C4-23C4-23 4U-1094U-109 C4-41C4-41
C4-22C4-22
4S-1304S-130
4S-1314S-131
4S-1344S-134
C4-1C4-1
C4-2C4-2
C4-6C4-6 C4-7C4-7 C4-8C4-8
C4-9C4-9
4U-104C4U-104C
C4-11C4-11
C4-12C4-12
C4-13C4-13
C4-14C4-14
C4-15C4-15
C4-16C4-16
C4-8AC4-8A
4U-104D4U-104D4U-104B4U-104B
4E-1534E-153
4S-1294S-129
4D-1474D-147 4D-1484D-148 4D-1494D-149 4D-1504D-150 4D-1514D-151 4D-1524D-152
4D-1464D-146 4D-1454D-145 4D-1444D-144
4D-1374D-137
4D-1344D-134 4D-1354D-135 4D-1364D-136
4D-137A4D-137A
4D-1384D-138
4D-1434D-143
4D-1424D-142
4D-1394D-139
4D-1414D-141
4D-1404D-140
4D-1334D-133 4D-132A4D-132A 4D-1324D-132
4D-1214D-121 4D-1234D-123 4D-1244D-124
4D-1254D-125
4D-1314D-131
4D-1264D-126 4D-1274D-127
4D-1304D-130 4D-1294D-129
4D-1284D-128
C4D-036C4D-036
C4D-037C4D-037
C4-19C4-19
C4-20C4-20
4S-130F4S-130F 4D-1334D-133
C4-20C4-20
4D-1224D-122
4D-122A4D-122A
4D-122B4D-122B
4U-1094U-109
4U-1014U-101 4C-1074C-107
4S-130A4S-130A
4S-130B4S-130B
4S-130C4S-130C
4S-1334S-133
4U-1004U-100
4T-1054T-105
C4-197C4-197
C4-22C4-22
4S-1314S-131
C4-1C4-1
70E-446 F5
70E-446 F7 on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a st ru ct u re
U p g ra d e s
M P
L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r vt /6
/2
:2 :4
P
M
05/06/2022 M. Perkins K.Hutchinson
618-21-700
1383 - 70E-104A
ELECTRICAL PLAN - FOURTH LEVEL AREA A
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO
ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL
DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE
PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER
CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE
COORDINATED WITH THE VA COR.
2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE
SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.
PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL
DETAIL ON T-500 SERIES SHEETS.
3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS.
4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.
5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE
LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET
ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.
COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE
CUTSHEETS ON 70E-901.
6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,
CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON
70E-901.
7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES
SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD
ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED
POWER METER. BASIS OF DESIGN: E-MON D-MON.
9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR
SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:
E-MON D-MON.
10. NOT USED.
11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.
12. REMOVE EXISTING ACCESS CONTROLS.
13. NOT USED.
14. REMOVE EXISTING LIGHT FIXTURES.
15. NOT USED.
16. NOT USED.
17. NOT USED.
18. NOT USED.
19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE
INFORMATION.
21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A
120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW
CONDUIT, CONDUCTORS AND DEVICES.
22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.
24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR
PRIOR TO BEGINNING OF CONSTRUCTION.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
NOTE: NOT ALL KEYNOTES ARE
USED ON EACH SHEET
SCALE: 1" = 10'-0"
F2
ELECTRICAL PLAN - FOURTH LEVEL
AREA A
05/06/2022
X
C R
EH D
C
CR
E
SRXDC
R X
PARTITION RATING GRAPHICS:
2 HR FIRE SHAFT
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
4S-130G4S-130G4S-130H4S-130H4T-1054T-105
4S-1284S-128
4S-1294S-129
C4-20C4-20
4D-1214D-121
4S-1014S-101
4S-1024S-102
4S-1034S-103
4S-1044S-104
4S-1054S-105
4S-1184S-118
4S-1234S-123
4S-1244S-124
4S-1254S-125
4S-1264S-126
4S-1274S-127
4S-24S-2
4T-1024T-102
4T-102A4T-102A
4T-102C4T-102C
M-4M-4
4T-1014T-101
AA
BB
4A-1054A-105 4A-1064A-106
4A-1074A-107
4A-1084A-108
4A-1094A-109
4A-1104A-110
4S-54S-5
4A-110A4A-110A
4A-107A4A-107A
4S-34S-3
C4-89C4-89
4B-1014B-101
4B-1024B-102
4B-1034B-103
4B-1044B-104
4B-1054B-105 4B-1064B-106 4B-1074B-107
4B-1084B-108
4B-1094B-109 4B-1104B-110
4B-1114B-111 4B-108B4B-108B
4B-1134B-113
4B-1144B-114
4B-1154B-115
4B-1164B-116
4B-1174B-117
4B-1184B-118
4B-1194B-119 4B-1204B-120
4B-1214B-1214B-1224B-1224B-1234B-123
4B-1244B-124
4B-1254B-125
4B-1264B-126
4B-1274B-127
4B-1284B-128
4B-1294B-1294B-1304B-130
4B-1314B-131
4B-1324B-1324B-1334B-133
4B-1344B-134
4B-1354B-135
4B-1364B-136
4B-1374B-137
4B-1404B-140
4B-1414B-141
4B-1424B-1424B-1434B-143 4B-1444B-144
4B-1454B-145
4B-1464B-146
4B-1474B-147
4B-1494B-149
4B-1504B-150
4B-1514B-151 4B-1524B-1524B-1534B-1534B-1544B-154
4B-1554B-155 4B-1564B-156
4B-1574B-157
4B-101B4B-101B
4B-101C4B-101C
4B-108A4B-108A
4B-1584B-158 4B-1594B-159 4B-1604B-160
4S-44S-4
C4-181C4-181
C4-32C4-32
C4-86C4-86
4S-1214S-121
4S-1224S-122
4T-102B4T-102B
C4-76C4-76
C4-80C4-80
C4-82C4-82
C4-79C4-79
C4-84C4-84
C4-73C4-73
C4-72C4-72
C4-72AC4-72A
C4-74C4-74
C4-28C4-28 C4-29C4-29
C4-30C4-30
C4-183C4-183
C4-184C4-184
C4-185C4-185
4B-1394B-139
C4-88C4-88
C4-182C4-182
C4-31C4-31
4S-1004S-100
4B-1004B-100
4B-108C4B-108C
4D-1204D-120
4D-1084D-108
4C-1174C-117
C-10C-10 4A-1014A-101
4A-1024A-102
4A-1034A-103
M2M2
C9C9
4M-1054M-105
C4-90C4-90
C4-179C4-179
4B-1604B-160
C4-32C4-32C4-32C4-32
C4-72C4-72C4-72C4-72
4S-1014S-101
C4-181C4-181
4T-1054T-105
4S-1054S-105
4S-24S-2C4-185C4-185
C4-20C4-20 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a st ru ct u re
U p g ra d e s
M P
L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r vt /6
/2
:2 :0
P
M
05/06/2022 M. Perkins K.Hutchinson
618-21-700
1383 - 70E-104B
ELECTRICAL PLAN - FOURTH LEVEL AREA B
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO
ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL
DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE
PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER
CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE
COORDINATED WITH THE VA COR.
2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE
SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.
PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL
DETAIL ON T-500 SERIES SHEETS.
3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS.
4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.
5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE
LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET
ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.
COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE
CUTSHEETS ON 70E-901.
6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,
CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON
70E-901.
7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES
SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD
ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED
POWER METER. BASIS OF DESIGN: E-MON D-MON.
9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR
SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:
E-MON D-MON.
10. NOT USED.
11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.
12. REMOVE EXISTING ACCESS CONTROLS.
13. NOT USED.
14. REMOVE EXISTING LIGHT FIXTURES.
15. NOT USED.
16. NOT USED.
17. NOT USED.
18. NOT USED.
19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE
INFORMATION.
21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A
120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW
CONDUIT, CONDUCTORS AND DEVICES.
22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.
24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR
PRIOR TO BEGINNING OF CONSTRUCTION.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
NOTE: NOT ALL KEYNOTES ARE
USED ON EACH SHEET
SCALE: 1" = 10'-0"
F3
ELECTRICAL PLAN - FIRST LEVEL
AREA B
E
LDC
D C
ES
C R
R X
O S
PARTITION RATING GRAPHICS:
2 HR FIRE SHAFT
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
C4-41C4-414E-1534E-153
4D-1474D-147 4D-1484D-148 4D-1494D-149 4D-1504D-150 4D-1514D-151 4D-1524D-152
4D-1464D-146 4D-1454D-145 4D-1444D-144
4D-1374D-137
4D-1344D-134 4D-1354D-135 4D-1364D-136
4D-137A4D-137A
4D-1384D-138
4D-1434D-143
4D-1424D-142
4D-1394D-139
4D-1414D-141
4D-1404D-140
4D-1334D-133 4D-132A4D-132A 4D-1324D-132
4D-1214D-121 4D-1234D-123 4D-1244D-124
4D-1254D-125
4D-1314D-131
4D-1264D-126 4D-1274D-127
4D-1304D-130 4D-1294D-129
4D-1284D-128
4D-1004D-100
C4D-036C4D-036
C4D-037C4D-037
4D-1334D-133
4D-1204D-120
4D-1084D-108
4D-1074D-107
4C-1174C-117
C4D-034C4D-034
C4D-035C4D-035
C4-33C4-33
4D-1014D-101
4D-1194D-119
4D-1094D-109
4D-1184D-118
4D-1104D-110
4D-1114D-111
4D-1174D-117
4D-111C4D-111C
4D-1124D-112
4D-1164D-116
4D-1134D-113
4D-1154D-115
4D-1144D-114
4C-1184C-118
4D-1064D-106 4D-1044D-104
4C-1174C-117
4D-1024D-102
4D-1054D-105
4D-1034D-1034D-1034D-103
TELECOM
ROOM
4C-1214C-121 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a st ru ct u re
U p g ra d e s
M P
L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r vt /6
/2
:2 :1
P
M
05/06/2022 M. Perkins K.Hutchinson
618-21-700
1383 - 70E-104C
ELECTRICAL PLAN - FOURTH LEVEL AREA C
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO
ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL
DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE
PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER
CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE
COORDINATED WITH THE VA COR.
2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE
SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.
PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL
DETAIL ON T-500 SERIES SHEETS.
3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS.
4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.
5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE
LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET
ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.
COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE
CUTSHEETS ON 70E-901.
6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,
CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON
70E-901.
7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES
SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD
ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED
POWER METER. BASIS OF DESIGN: E-MON D-MON.
9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR
SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:
E-MON D-MON.
10. NOT USED.
11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.
12. REMOVE EXISTING ACCESS CONTROLS.
13. NOT USED.
14. REMOVE EXISTING LIGHT FIXTURES.
15. NOT USED.
16. NOT USED.
17. NOT USED.
18. NOT USED.
19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE
INFORMATION.
21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A
120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW
CONDUIT, CONDUCTORS AND DEVICES.
22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.
24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR
PRIOR TO BEGINNING OF CONSTRUCTION.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
NOTE: NOT ALL KEYNOTES ARE
USED ON EACH SHEET
SCALE: 1" = 10'-0"
F6
ELECTRICAL PLAN - FOURTH LEVEL
AREA C
CR
H
RXDC
D
CELML
D C
ES
C R
R X
O S
PARTITION RATING GRAPHICS:
2 HR FIRE SHAFT
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
4D-1004D-100
4B-1114B-111
4B-1184B-118
4B-1204B-120
4B-1604B-160
DD
4S-44S-4
4C-1174C-117
4C-1094C-109
4C-1144C-114
C4-33C4-33
4C-108D4C-108D
4C-108A4C-108A
4F-1074F-107
4B-1604B-160
4D-1014D-101
4C-1184C-118 4C-1174C-117
4C-108C4C-108C
4E-1074E-107
4E-116A4E-116A C4-44C4-44
4C-108A4C-108A
4E-122C4E-122C
4E-122A4E-122A
4E-122B4E-122B
M7M7
4C-1064C-1064C-1084C-108
4C-1124C-112
4C-1104C-110
4C-1104C-110
4C-1114C-111
C4-69C4-69
C4-70C4-70
C4-47C4-47
C4-46C4-46C4-58C4-58
4E-105A4E-105A 4E-1054E-105
4C-116A4C-116A
4E-1024E-102
4C-1154C-115
4E-1014E-1014C-1134C-113
4E-1604E-160
4E-1084E-108 4E-1204E-120
4E-1094E-109 4E-1194E-119
4E-1104E-110 4E-1184E-118
4E-1114E-111
4E-1124E-112 4E-111C4E-111C 4E-1174E-117
4E-1134E-113 4E-1284E-128
4E-1144E-114 4E-1154E-115
4E-1234E-123 4E-1304E-130
4E-1244E-124
4E-125A4E-125A
4E-1254E-125
4E-1264E-126
4E-1274E-127
4E-1284E-128 4E-1294E-129
4E-1314E-131
4E-1294E-129
4E-1344E-134 4E-1464E-146
4E-1354E-135 4E-1454E-145
4E-1364E-136 4E-1444E-144
4E-1374E-137
4E-1384E-138 4E-137A4E-137A 4E-1434E-143
4E-1394E-139 4E-1424E-142
4E-1404E-140 4E-1414E-141
4E-1524E-152
4E-1514E-151
4E-1504E-150
4E-1494E-149
4E-1484E-148
C4E-038C4E-038
4E-137B4E-137B
C4E-037C4E-037
4E-137C4E-137C
C4E-036C4E-036C4E-035C4E-035
4E-123A4E-123A
4E-111A4E-111A
C4E-034C4E-034
4E-1214E-121 4E-1334E-133
4E-1024E-102
4E-1004E-100
4E-1474E-147
C4-45C4-45
4F-1014F-101
4F-1004F-1004F-1054F-105
4F-1064F-106
C4-70C4-70
4E-1474E-147
4F-1004F-100
70E-445 C5
70E-445 C7
TELECOM
ROOM
4C-1214C-121 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a st ru ct u re
U p g ra d e s
M P
L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r vt /6
/2
:2 :3
P
M
05/06/2022 M. Perkins K.Hutchinson
618-21-700
1383 - 70E-104D
ELECTRICAL PLAN - FOURTH LEVEL AREA D
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO
ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL
DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE
PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER
CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE
COORDINATED WITH THE VA COR.
2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE
SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.
PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL
DETAIL ON T-500 SERIES SHEETS.
3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS.
4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.
5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE
LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET
ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.
COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE
CUTSHEETS ON 70E-901.
6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,
CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON
70E-901.
7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES
SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD
ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED
POWER METER. BASIS OF DESIGN: E-MON D-MON.
9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR
SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:
E-MON D-MON.
10. NOT USED.
11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.
12. REMOVE EXISTING ACCESS CONTROLS.
13. NOT USED.
14. REMOVE EXISTING LIGHT FIXTURES.
15. NOT USED.
16. NOT USED.
17. NOT USED.
18. NOT USED.
19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE
INFORMATION.
21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A
120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW
CONDUIT, CONDUCTORS AND DEVICES.
22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.
24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR
PRIOR TO BEGINNING OF CONSTRUCTION.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
NOTE: NOT ALL KEYNOTES ARE
USED ON EACH SHEET
SCALE: 1" = 10'-0"
F3
ELECTRICAL PLAN - FOURTH LEVEL
AREA D
PARTITION RATING GRAPHICS:
2 HR FIRE SHAFT
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
4B-1184B-118
4B-1204B-120
4C-1144C-114
4F-1074F-107
4C-1124C-112
4C-1114C-111
C4-69C4-69
4E-1014E-1014C-1134C-113
4E-1604E-160 4F-1014F-101
4F-1034F-103
4F-1004F-1004F-1054F-105
4F-1064F-106
C4F-066C4F-066
4F-1084F-108 4F-1044F-104
4F-1094F-109
4F-1204F-120
4F-1104F-110
4F-119A4F-119A
4F-1114F-111
4F-1194F-119
4F-1124F-112
4F-112C4F-112C
4F-1184F-118
4F-1144F-114
4F-1174F-117
4F-1154F-115
4F-1164F-116
4F-1224F-122
4F-1344F-134
4F-1234F-123
4F-1334F-133 4F-1324F-132
4F-1244F-124
4F-1254F-125
4F-1264F-126
4F-1314F-131
4F-1274F-127
4F-1304F-130
4F-1284F-128
4F-1294F-129
4F-1354F-135
4F-1464F-146 4F-1454F-145
4F-135A4F-135A 4F-1364F-136
4F-1444F-144
4F-1374F-137 4F-137B4F-137B
4F-1384F-138
4F-1434F-143
4F-1394F-139
4F-1424F-142
4F-1404F-140
4F-1414F-141
4F-1474F-147 4F-1484F-148 4F-1494F-149 4F-1504F-150 4F-1514F-151
4F-1024F-102
C4F-061C4F-061
C4F-060C4F-060
C4F-062C4F-062
C4F-063C4F-063
C4F-064C4F-064
4F-137A4F-137A
4F-137C4F-137C
4F-125A4F-125A
4L-117B4L-117B
4F-121A4F-121A
4F-121B4F-121B
C4F-065C4F-065
4F-1474F-147
C4F-060C4F-060
C4F-062C4F-062
C4F-063C4F-063
C4F-064C4F-064
4F-1004F-100
C4F-066C4F-066 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a st ru ct u re
U p g ra d e s
M P
L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r vt /6
/2
:2 :4
P
M
05/06/2022 M. Perkins K.Hutchinson
618-21-700
1383 - 70E-104E
ELECTRICAL PLAN - FOURTH LEVEL AREA E
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO
ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL
DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE
PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER
CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE
COORDINATED WITH THE VA COR.
2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE
SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.
PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL
DETAIL ON T-500 SERIES SHEETS.
3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS.
4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.
5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE
LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET
ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.
COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE
CUTSHEETS ON 70E-901.
6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,
CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON
70E-901.
7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES
SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD
ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED
POWER METER. BASIS OF DESIGN: E-MON D-MON.
9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR
SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:
E-MON D-MON.
10. NOT USED.
11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.
12. REMOVE EXISTING ACCESS CONTROLS.
13. NOT USED.
14. REMOVE EXISTING LIGHT FIXTURES.
15. NOT USED.
16. NOT USED.
17. NOT USED.
18. NOT USED.
19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE
INFORMATION.
21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A
120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW
CONDUIT, CONDUCTORS AND DEVICES.
22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.
24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION
WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM
THOSE INDICATED.
C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.
D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS
WITH VA COR PRIOR TO ROUGH-IN.
E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED
OUTDOORS
F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL
SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.
G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH
EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.
H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING
PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.
I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.
J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE
OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.
K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH
EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.
L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN
PLENUM SPACES.
M. REFER TO E-901 FOR CUTSHEETS.
N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF
PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR
PRIOR TO BEGINNING OF CONSTRUCTION.
O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING
CLEARANCES PER NEC 110.26.
NOTE: NOT ALL KEYNOTES ARE
USED ON EACH SHEET
SCALE: 1" = 10'-0"
F6
ELECTRICAL PLAN - FOURTH LEVEL
AREA E
SDCRX
D C
EL
ML
M L
PARTITION RATING GRAPHICS:
2 HR FIRE SHAFT
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
4A-1104A-110
4B-1184B-118
4B-1214B-1214B-1224B-1224B-1234B-1234B-1254B-1254B-1294B-1294B-1304B-1304B-1324B-1324B-1334B-1334B-1354B-1354B-1424B-1424B-1434B-143 4B-1444B-1444B-1514B-151
4B-1524B-1524B-1534B-1534B-1544B-154
4B-1554B-155 4B-1564B-156
4B-1574B-157
C4-72C4-72
4F-1074F-107
4G-1014G-101
4G-1024G-102 4G-1034G-103
C4-100C4-100
C4-90C4-90
C4-72C4-72C4-72C4-72
4F-1084F-108
4F-1094F-109
4F-1204F-120
4F-1224F-122
4F-1344F-134
4F-1354F-135
4F-1464F-146
4L-117B4L-117B
4G-1044G-104
4G-1054G-105
4G-1064G-106
4G-109B4G-109B
4G-1074G-107
4G-109D4G-109D
4G-109E4G-109E
4G-1114G-111
4G-1124G-112
4G-1144G-114
4S-64S-6 4H-1214H-121
4H-1224H-122
4H-1234H-123
C4-116C4-116
4G-1094G-109
4G-1164G-116 4G-1154G-115 4G-111C4G-111C 4G-111B4G-111B 4G-111A4G-111A
4G-1104G-110 4G-109C4G-109C
4G-109A4G-109A
4H-1204H-120
EE
C-6C-6
4L-1014L-101
4L-1084L-108 4L-1094L-109 4L-1104L-110 4L-1124L-112
4L-1134L-113 4L-1154L-115 4L-1174L-117 4L-117A4L-117A
4L-117A4L-117A2323
4H-1014H-101
28282828
4S-64S-6
C4-100C4-100
EE
C4-100C4-100 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a st ru ct u re
U p g ra d e s
M P
L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r vt /6
/2
:2 :0
P
M
05/06/2022 M. Perkins K.Hutchinson
618-21-700
1383 - 70E-104F
ELECTRICAL PLAN - FOURTH LEVEL AREA F
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES
ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO
ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL
DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE
PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER
CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE
COORDINATED WITH THE VA COR.
2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE
SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.
PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL
DETAIL ON T-500 SERIES SHEETS.
3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH
NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND
RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR
ADDITIONAL REQUIREMENTS.
4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT
BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,
CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.
5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE
LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET
ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.
COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE
CUTSHEETS ON 70E-901.
6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,
CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON
70E-901.
7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES
SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR
ADDITIONAL INFORMATION.
8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD
ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED
POWER METER. BASIS OF DESIGN: E-MON D-MON.
9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR
SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:
E-MON D-MON.
10. NOT USED.
11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.
12. REMOVE EXISTING ACCESS CONTROLS.
13. NOT USED.
14. REMOVE EXISTING LIGHT FIXTURES.
15. NOT USED.
16. NOT USED.
17. NOT USED.
18. NOT USED.
19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE
THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD
RENOVATION.
20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE
INFORMATION.
21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A
120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW
CONDUIT, CONDUCTORS AND DEVICES.
22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR
CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS
RECOMMENDATIONS.
23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.
24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH
EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR
ADDITIONAL INFORMATION.
25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION
WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS
FOR ADDITIONAL INFORMATION
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS…