618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-3.pdf

PDF 19 MB Posted

Attached to
EHRM Infrastructure Upgrades Construction Design-Bid Build Project at the Minneapolis VA Medical Center (VAMC)
Solicitation number
36C77622R0045
Issued by

About this file

This document summarizes a federal solicitation for construction services. The solicitation is being issued by the Department of Veterans Affairs Office of Information Service Center to upgrade infrastructure needed for an Electronic Health Record Modernization project at the Minneapolis VA Medical Center. The construction and commissioning work will be performed in accordance with drawings and specifications provided by the architect-engineer. The project involves building a new server room on the hospital roof and infrastructure work throughout multiple departments. The solicitation is set aside for Service-Disabled Veteran-Owned Small Businesses and offers from other contractor types will not be considered. The period of performance is approximately 450 calendar days from notice to proceed. The estimated value of construction is between $20-50 million. Questions must be submitted in writing by email to the point of contact listed by the specified due date.

View the file

Other files

File Type Posted
Technical Question Tracking Sheet Infra Upgrades FINAL.pdf PDF
36C77622R0045 0009.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-11.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-1.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-7.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-2.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-6.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-4.pdf PDF
618-21-700.ADD-001.Summary.Log.20220707.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-9.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-5.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-10.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-8.pdf PDF
36C77622R0045 0008.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades - FINAL.pdf PDF
36C77622R0045 0007.pdf PDF
36C77622R0045 0006.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades - Minneapolis.docx DOCX document
36C77622R0045 0005.docx DOCX document
36C77622R0045 0004.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades.docx DOCX document
36C77622R0045 0003.pdf PDF
Site Visit Sign In sheet.pdf PDF
36C77622R0045 0002.pdf PDF
36C77622R0045 0001.pdf PDF
36C77622R0045 - Update 5.23.22.docx DOCX document
618-21-700.MEHRM.FINAL.B70.20220506Part-7.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-11.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-33-36.zip ZIP file
618-21-700.MEHRM.FINAL.B76.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-48-52.zip ZIP file
36C77622R0045.docx DOCX document
618-21-700.MEHRM.FINAL.B70.20220506Part-21.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-25-28.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-4.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-23.pdf PDF
618-21-700.MEHRM.FINAL.B75.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL_SPECIFICATIONS.20220506Part-2.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-45-47.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-6.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-13.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-20.pdf PDF
618-21-700.MEHRM.FINAL.B73.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B49.20220506-REDUCED.pdf PDF
01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
618-21-700.MEHRM.FINAL.SITE.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B222.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-12.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-16-17.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-29-32.zip ZIP file
Show 40 more

Latest 50 of 80 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

H

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

BA-109BA-109

CB32BCB32B

CB51CB51

CB49CB49

BG-101BG-101

BM-131BM-131

BM-123ABM-123A

BM-123BBM-123B

BM-123CBM-123C

BM-123EBM-123E

BM-123GBM-123G BM-123HBM-123H

BM-123BM-123

BH-111CBH-111C

BM-101BM-101

BM-102BM-102

BM-103BM-103

BM-104BM-104

BM-105BM-105

BM-107BM-107

BM-108BM-108

BM-108ABM-108A

BM-109BM-109

BM-110BM-110

BM-111BM-111

BM-112BM-112BM-113BM-113

BM-114BM-114

BM-115BM-115

BM-116BM-116

BM-117BM-117

BM-118BM-118

BM-119BM-119

BM-120BM-120

BM-121BM-121

STAFF

BREAKROOM

BM-122BM-122

TELECOM

ROOM

(BLUE-STACK)

BM-122ABM-122A

BA-101BA-101

BA-102BA-102

ELECTRICAL

ROOM

BA-104BA-104

BA-105BA-105

BA-106BA-106

BA-107BA-107

BM-116ABM-116ABM-116BBM-116B

BM-116CBM-116CBM-116DBM-116D

BM-124BM-124

BM-125BM-125

BM-126BM-126

BM-127BM-127

FF

CB-86CB-86

BM-111ABM-111A

BM-111BBM-111B

BM-111CBM-111C

BM-111DBM-111D

BM-111EBM-111E

BM-119ABM-119A

BM-119BBM-119B BM-119CBM-119C

BM-119DBM-119D

BM-119EBM-119E

BS-7BS-7

M3M3

M2M2

BM-107ABM-107A

BM-107BBM-107B

BM-107CBM-107C

BM-107DBM-107D

C10C10

M9M9

TELECOM

ROOM

BA-103BA-103

CB-87CB-87

CB-88CB-88

CB-89CB-89CB-90CB-90

CB-92ACB-92A

BW-130BW-130

CB32ACB32A

BH-111DBH-111D

CB31CB31GG

BH-111EBH-111E

CB-79CB-79

BN-101BN-101

BN-104BN-104

BN-105BN-105

BN-106BN-106 BN-107BN-107

CB-86ACB-86A

BS-10BS-10

CB-81CB-81

AA

BH-111FBH-111F

CB-79CB-79CB-86ACB-86A CB-81CB-81

CB-101CB-101

BP-105BP-105

ELECTRICAL

ROOM

BP-107BP-107

BP-113BP-113

BP-115BP-115

BP-116BP-116

BP-105ABP-105A

BP-118BP-118

TELECOM

ROOM

BP-107ABP-107A

TYP.

7' - 0" 4' - 0" 4' - 8 1/2"

TYP.

on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRUE NORTH

PLAN NORTH

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

A

B

D

F

G

H

J

K

L

M

N

P

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/7

/2

:0

:0

A

M

05/06/2022 M. Perkins G. Weaver

618-21-700

1383 -

70FX100K

FIRE PROTECTION PLAN - BASEMENT LEVEL

AREA K

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO

COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:

A. SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,

LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS

AND DETAILS

B. CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,

SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS

A. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION

OF THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED.

CONTRACTOR TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER

SIGNIFICANTLY FROM THE CONSTRUCTION DOCUMENTS.

B. A DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES

WITH DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR

PRIOR TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE

COR PRIOR TO THE START OF WORK.

C. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING

HEIGHTS, AND SQUARE FOOTAGE.

D. CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND

OTHER TRADES PRIOR TO CONSTRUCTION.

E. ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED

CHASES UNLESS NOTED OTHERWISE.

F. ALL AREAS ARE DESIGNED AS ORDINARY HAZARD GROUP 1 OCCUPANCY UNLESS

NOTED OTHERWISE ON PLAN.

G. ALL SPRINKLERS SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022

NFPA 13.

H. ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL

LISTED FOR USE IN FIRE PROTECTION SYSTEMS.

I. ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH

EXISTING BUILDING STANDARDS.

J. INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE

SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.

K. PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.

L. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

M. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT

CONNECTIONS BETWEEN ALL DISSIMILAR METALS.

N. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL

PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE

CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED

FIRE PROOF CAULKING MATERIAL.

O. ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.

P. THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE

PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT

CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.

THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION

SYSTEM SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO

PERFORMING WORK.

Q. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACES DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD

LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO

COMMENCING WORK

1. EXISTING SPRINKLER HEAD IN THIS LOCATION TO REMAIN, PROTECT IN PLACE.

2. EXISTING PENDENT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND

REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD

CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE

2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.

3. NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD CAGE. CONNECT

PIPING TO NEAREST BRANCH LINE. INSTALL SPRINKLER HEAD AND HANGERS IN

ACCORDANCE WITH THE 2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL

INFORMATION.

4. NEW HEAT/SMOKE DETECTOR AND FIRE ALARM STROBE/HORN, MOUNT AND

SUPPORT FROM DECK ABOVE. COORDINATE LOCATION WITH ALL OTHER

TRADES AND EXISTING CONDITIONS. SEE ARCHITECTURAL PLANS FOR

ADDITIONAL INFORMATION.

5. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACING DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD

LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO

COMMENCING WORK.

6. PROVIDE NEW PENDENT SPRINKLER HEAD. CONNECT TO NEAREST PIPE LINE.

INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH TEH 2022 NFPA

13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1" = 10'-0"

F2

FIRE PROTECTION PLAN - BASEMENT

LEVEL AREA K

1 Revision 1 Date 1

SPRINKLER HEAD LEGEND

SYM.

DEMO

TYPE

QUICK

RESPONSE

TEMP "K"

DEMO

QUANTITY

PENDENT

YES 170F 5.6UPRIGHT

YES 155F 5.6

NOTE: LEGEND INFORMATION IS SPECIFIC TO THIS SHEET ONLY

NEW

QUANTITY

SYM.

NEW

-2

ADDENDUM #1 07/07/2022

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

BU-102BU-102

CB-2CB-2

BB-128BB-128

BB-129BB-129

BB-130BB-130

BB-131BB-131

BB-132BB-132

BQ-105BQ-105

BQ-106BQ-106

BQ-107BQ-107

BQ-108BQ-108

BQ-109BQ-109

BQ-111BQ-111

BQ-112BQ-112

BQ-113BQ-113

BQ-114BQ-114

BQ-111ABQ-111A

BR-105BR-105

BR-106BR-106

BR-107BR-107

BR-108BR-108

BR-109BR-109

BR-110BR-110

BR-111BR-111

BR-114BR-114BR-115BR-115 BR-116BR-116

BR-126BR-126 BR-130BR-130

BR-131BR-131

BR-132BR-132BR-133BR-133

BR-134BR-134

BR-135BR-135

BR-136BR-136

BR-137BR-137

BR-147BR-147

BR-135ABR-135A

BR-135BBR-135B

BR-136ABR-136A

ELECTRICAL

ROOM

BT-103BT-103

TELECOM

ROOM

BT-104BT-104

CB-71CB-71

BR-108BR-108

BQ-110BQ-110

BQ-110ABQ-110A

TELECOM

ROOM

BQ-110BBQ-110B

ELECTRICAL

ROOM

BQ-110CBQ-110C

ELECTRICAL

ROOM

BQ-110EBQ-110ETELECOM

ROOM

BQ-110FBQ-110F

ELECTRICAL

ROOM

BQ-110GBQ-110G

BV-101BV-101

BV-103BV-103

BV-104BV-104

BV-105BV-105

BV-106BV-106

BV-107BV-107

BV-108ABV-108A

BV-109BV-109

BV-112BV-112

BV-113BV-113

BV-114BV-114

BV-115BV-115

BV-116BV-116

BV-117BV-117BV-118BV-118

BV-119BV-119

BV-120BV-120BV-121BV-121BV-122BV-122

BV-123BV-123

BV-124BV-124

BV-125BV-125

BV-126BV-126

BV-127BV-127

BV-128BV-128

BV-129BV-129

BV-130BV-130

BV-131BV-131

BV-132BV-132

M-5M-5

TELECOM

ROOM

BT-105BT-105

ELECTRICAL

ROOM

BT-106BT-106

BT-107BT-107

BT-108BT-108

BV-101ABV-101A

BV-101BBV-101BBV-101CBV-101C

BV-101DBV-101DBV-101EBV-101E

BV-101FBV-101F

BV-101GBV-101G

BV-101HBV-101H

BV-101IBV-101I

BV-101JBV-101J

BW-100BW-100

BV-111BV-111

BV-106ABV-106A

BV-106BBV-106B

BV-106CBV-106C

BV-106DBV-106D

BV-104ABV-104A

BV-104BBV-104B

BV-104CBV-104C

BV-104DBV-104D

BV-105ABV-105A BV-105BBV-105B

BV-105CBV-105C

BV-107ABV-107A

BV-107BBV-107B

BV-108BBV-108B

BV-124ABV-124A

BV-114ABV-114A

CB-57CB-57

CB-58CB-58

CB-60CB-60

CB-61CB-61

CB-62CB-62

CB-64CB-64

CB-65CB-65

CB-66CB-66

CB-67CB-67

CB-68CB-68

CB-69CB-69

CB-70CB-70

BW-124BW-124

TELECOM

ROOM

(YELLOW-STACK)

BQ-110HBQ-110H

TYP.

7'-2" 4'-4"

7' -6

3' - 8" on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRUE NORTH

PLAN NORTH

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

A

B

D

F

G

H

J

K

L

M

N

P

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/7

/2

:0

:1

A

M

05/06/2022 M. Perkins G. Weaver

618-21-700

1383 -

70FX100M

FIRE PROTECTION PLAN - BASEMENT LEVEL

AREA M

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO

COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:

A. SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,

LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS

AND DETAILS

B. CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,

SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS

A. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION

OF THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED.

CONTRACTOR TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER

SIGNIFICANTLY FROM THE CONSTRUCTION DOCUMENTS.

B. A DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES

WITH DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR

PRIOR TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE

COR PRIOR TO THE START OF WORK.

C. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING

HEIGHTS, AND SQUARE FOOTAGE.

D. CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND

OTHER TRADES PRIOR TO CONSTRUCTION.

E. ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED

CHASES UNLESS NOTED OTHERWISE.

F. ALL AREAS ARE DESIGNED AS ORDINARY HAZARD GROUP 1 OCCUPANCY UNLESS

NOTED OTHERWISE ON PLAN.

G. ALL SPRINKLERS SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022

NFPA 13.

H. ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL

LISTED FOR USE IN FIRE PROTECTION SYSTEMS.

I. ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH

EXISTING BUILDING STANDARDS.

J. INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE

SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.

K. PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.

L. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

M. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT

CONNECTIONS BETWEEN ALL DISSIMILAR METALS.

N. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL

PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE

CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED

FIRE PROOF CAULKING MATERIAL.

O. ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.

P. THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE

PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT

CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.

THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION

SYSTEM SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO

PERFORMING WORK.

Q. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACES DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD

LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO

COMMENCING WORK

1. EXISTING SPRINKLER HEAD IN THIS LOCATION TO REMAIN, PROTECT IN PLACE.

2. EXISTING PENDENT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND

REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD

CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE

2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.

3. NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD CAGE. CONNECT

PIPING TO NEAREST BRANCH LINE. INSTALL SPRINKLER HEAD AND HANGERS IN

ACCORDANCE WITH THE 2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL

INFORMATION.

4. NEW HEAT/SMOKE DETECTOR AND FIRE ALARM STROBE/HORN, MOUNT AND

SUPPORT FROM DECK ABOVE. COORDINATE LOCATION WITH ALL OTHER

TRADES AND EXISTING CONDITIONS. SEE ARCHITECTURAL PLANS FOR

ADDITIONAL INFORMATION.

5. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACING DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD

LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO

COMMENCING WORK.

6. PROVIDE NEW PENDENT SPRINKLER HEAD. CONNECT TO NEAREST PIPE LINE.

INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH TEH 2022 NFPA

13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1" = 10'-0"

F2

FIRE PROTECTION PLAN - BASEMENT

LEVEL AREA M

1 Revision 1 Date 1

SPRINKLER HEAD LEGEND

SYM.

DEMO

TYPE

QUICK

RESPONSE

TEMP "K"

DEMO

QUANTITY

PENDENT

YES 170F 5.6UPRIGHT

YES 155F 5.6

NOTE: LEGEND INFORMATION IS SPECIFIC TO THIS SHEET ONLY

NEW

QUANTITY

SYM.

NEW

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

C1-3C1-3

C1-2C1-2

C1-1C1-1

CC

C1-4C1-4

1U-1001U-100

1U-100A1U-100A

C1-6C1-6

1S-1341S-134

C1-186C1-186

C1-2AC1-2A

1U-1051U-105 1U-1061U-106 1U-1071U-107 1U-1081U-108 1U-1101U-110

C1-12C1-12

1U-1011U-101

1U-100B1U-100B 1U-101A1U-101A

1C-71C-7

1U-1331U-133

C1-14C1-14

1U-1321U-132

1U-1311U-131 1U-1291U-129 1U-1281U-128 1U-1271U-127 1U-1261U-126

1U-1221U-122 1U-1301U-130

1U-1201U-120

1U-130A1U-130A

1U-109A1U-109A

1U-1091U-109 1U-1131U-1131U-1121U-112

1U-1191U-119

C1-13C1-13

1U-1111U-111

1U-1141U-114

1U-1151U-115

1U-1161U-116

C1-12AC1-12A

1U-1171U-117 1U-1441U-144

1U-1421U-142

1U-1181U-118

1U-1211U-121 1U-1381U-138

1U-1371U-137

1U-1231U-123

1U-1241U-124 1U-1361U-136

1U-1251U-125 ?? 1U-1351U-135

C1-15C1-15

1S-1361S-136

C1-5aC1-5a 1S-1381S-138 1S-1291S-129

1S-1301S-130 1S-1311S-131 1616 1S-1331S-133

1S-126A1S-126A

1S-1321S-132

1S-1261S-126

1S-1251S-125

1S-1271S-127

1S-127A1S-127A

1S-127B1S-127B

1S-121A1S-121A

C1-187C1-187

1S-1211S-121

1S-114A1S-114A

1S-125A1S-125A

1S-1201S-120

1S-1191S-1191S-1181S-1181S-1171S-1171S-1161S-1161S-1151S-115

1S-1351S-135 1S-1371S-137

C1-5C1-5 M-6M-6

1U-1461U-146

1U-1471U-147 1U-1491U-149

1U-1511U-151

1S-127H1S-127H 1S-91S-9

C1-20AC1-20A

C1-20C1-20

1U-1431U-143 1U-1481U-148 1U-1501U-150

C1-21C1-21

1U-1551U-1551U-1401U-140

C1-19C1-19

1U -1

1U

-1

1U-1591U-159 1U-1581U-158

1U-1571U-157

1U-1561U-156

ELECTRIC

ROOM

1U-1531U-153

TELECOM

ROOM

1U-1521U-152

C1-23C1-23C1-17C1-17

C1-16C1-16

C1-24C1-24

1D-1201D-120

C1-22C1-22

1D-120A1D-120A

ELECTRIC

ROOM

1D-120B1D-120B

TELECOM

ROOM

1D-120C1D-120C

C1-35C1-35

C1-167C1-167

1R-2501R-250

1S-1121S-112

1S-1001S-100

1S -1

1S

-1

1S-1071S-107

1S-1091S-109 C1-191C1-191

1S-1231S-123

1S-1101S-110

1S-1061S-106

1U-1621U-162

1U-162A1U-162A

1U-162B1U-162B C1-34AC1-34A

1D-121A1D-121A

1D-1211D-121

1D-1221D-122C1-34C1-34

1D-1171D-117

1D-1151D-115

1D-1141D-114

1D-1161D-116

1D-1181D-118

1D-1231D-123

1D-122A1D-122A 1D-115A1D-115A

C1-36C1-36

C1-32C1-32

1D-116A1D-116A

1D-1251D-125

1D-1241D-124

1D-124A1D-124A

1D-125A1D-125A

1D-112A1D-112A

1D-1131D-113

1D-113A1D-113A

1D-1111D-111

1D-1121D-112

1D-1091D-109

C1-38C1-38

1D -1

1D

-1

1D-1261D-126

1D-1271D-127

1D-1301D-130

1D-1321D-132

1D-127A1D-127A

1D-1281D-128

1D-1081D-108

1D-1291D-129

1D-1061D-106 1D-1311D-131

1D-1071D-107

1D-107A1D-107A

1T-1051T-105

ELECTRIC

ROOM

1T-1031T-103

TELECOM

ROOM

1T-1041T-104

1S-1441S-144

1S-21S-2

C1-181C1-181

1S-11S-1

ELECTRIC

ROOM

1T-1081T-108

TELECOM

ROOM

1T-1071T-107

M-5M-5

C1-185AC1-185A

C1-3AC1-3A

C1-183AC1-183A

1V-152A1V-152A

1V-151A1V-151A

1V-1471V-147

TELECOM

ROOM

(GREEN-STACK)

1U-1041U-104

6' -3

6'

-1

7' -6

"6'-6"7'-6" on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

A

B D

TRUE NORTH

PLAN NORTH

E F

G

H

J

K

L

M

N

C

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/6

/2

:3 :2

P

M

11/05/2021 M. Perkins G. Weaver

618-21-700

1383 -

70FX101A

FIRE PROTECTION PLAN - FIRST LEVEL

AREA A

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO

COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:

A. SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,

LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS

AND DETAILS

B. CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,

SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS

A. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION

OF THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED.

CONTRACTOR TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER

SIGNIFICANTLY FROM THE CONSTRUCTION DOCUMENTS.

B. A DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES

WITH DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR

PRIOR TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE

COR PRIOR TO THE START OF WORK.

C. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING

HEIGHTS, AND SQUARE FOOTAGE.

D. CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND

OTHER TRADES PRIOR TO CONSTRUCTION.

E. ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED

CHASES UNLESS NOTED OTHERWISE.

F. ALL AREAS ARE DESIGNED AS ORDINARY HAZARD GROUP 1 OCCUPANCY UNLESS

NOTED OTHERWISE ON PLAN.

G. ALL SPRINKLERS SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022

NFPA 13.

H. ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL

LISTED FOR USE IN FIRE PROTECTION SYSTEMS.

I. ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH

EXISTING BUILDING STANDARDS.

J. INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE

SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.

K. PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.

L. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

M. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT

CONNECTIONS BETWEEN ALL DISSIMILAR METALS.

N. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL

PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE

CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED

FIRE PROOF CAULKING MATERIAL.

O. ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.

P. THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE

PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT

CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.

THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION

SYSTEM SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO

PERFORMING WORK.

Q. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACES DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD

LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO

COMMENCING WORK

1. EXISTING SPRINKLER HEAD IN THIS LOCATION TO REMAIN, PROTECT IN PLACE.

2. EXISTING PENDENT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND

REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD

CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE

2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.

3. NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD CAGE. CONNECT

PIPING TO NEAREST BRANCH LINE. INSTALL SPRINKLER HEAD AND HANGERS IN

ACCORDANCE WITH THE 2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL

INFORMATION.

4. NEW HEAT/SMOKE DETECTOR AND FIRE ALARM STROBE/HORN, MOUNT AND

SUPPORT FROM DECK ABOVE. COORDINATE LOCATION WITH ALL OTHER

TRADES AND EXISTING CONDITIONS. SEE ARCHITECTURAL PLANS FOR

ADDITIONAL INFORMATION.

5. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACING DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD

LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO

COMMENCING WORK.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1" = 10'-0"

F2

FIRE PROTECTION PLAN - FIRST

LEVEL AREA A

SPRINKLER HEAD LEGEND

SYM.

DEMO

TYPE

QUICK

RESPONSE

TEMP "K"

DEMO

QUANTITY

PENDENT

YES 170F 5.6UPRIGHT

YES 155F 5.6

NOTE: LEGEND INFORMATION IS SPECIFIC TO THIS SHEET ONLY

NEW

QUANTITY

SYM.

NEW

05/06/2022

05/06/2022

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

TELECOM

ROOM

(CYAN-STACK)

1C-1061C-106

SHARED

OFFICE

1C-1071C-107

1D -1

A

1D -1

A

1D-1011D-101

1D-136A1D-136A

1C-1051C-105

1C-1041C-104

C1-50C1-50

1C-1201C-120

C1-49C1-49

DD

1C-1121C-112

M7M7

1C-1151C-115

C1-28C1-28 C1-29C1-29

1C-1011C-101

1C-1211C-121

TOILET

1C-1031C-103

1C-1111C-111

C1-48AC1-48A

C1-37C1-37

1C-1081C-108

C1-48C1-48

1C-1161C-116

1C-1171C-117

1C-1181C-118

1C-1191C-119

1C-114B1C-114B

1C-114D1C-114D

1C-114C1C-114C

1C-114A1C-114A

C1-40C1-40

1E-101A1E-101A

1E-1011E-101 1E-1031E-103 1E-1051E-105

1E-103A1E-103A 1E-105A1E-105A

1E-1071E-107 1E-1101E-110

1E-110A1E-110A

1E-1121E-112 1E-1131E-113 1E-1141E-114

1E-1151E-115

1E-113A1E-113A

1E-115A1E-115A

1E-1161E-116

C1-45C1-45

C1-44C1-44

??1E-1111E-111

1E-111A1E-111A

1E-1091E-109

1E-1231E-123 1E-120A1E-120A

1E-123A1E-123A

C1-43C1-43

C1-42C1-42

C1-46C1-46

TELECOM

ROOM

1E-117C1E-117C

1E-1171E-117

1E-117A1E-117A

ELECTRICAL

ROOM

1E-117B1E-117B

1E-1181E-118

1E-118A1E-118A

1E-1191E-1191E-1211E-121

1E-119A1E-119A

1E-1221E-122

1E-122A1E-122A

1E-1241E-1241E-1251E-125

1E-125A1E-125A

1E-1281E-128

C1-47C1-47

1E-1261E-126

1E-1081E-108

1E-1271E-127

1E-1061E-106

1E-1041E-1041E-1021E-102

1E-1311E-131

C1-41C1-41

1E-1301E-130

1E-130A1E-130A

1E-1321E-132

1E-132A1E-132A

1E-1331E-133

1E-1291E-129

1E-1341E-134

C1-39C1-39

1C-1351C-135

1E-134A1E-134A

1C-1221C-122

1F-1361F-136

1F-136A1F-136A

C1-52C1-52

1S-41S-4

ELECTRIC

ROOM

1D-1741D-174

C1-202C1-202

3' -7

3'

-7

6' -1

5'-9" 7'-6"

OFFICE

1C-1021C-102 5 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

A

B D

TRUE NORTH

PLAN NORTH

E F

G

H

J

K

L

M

N

C

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/6

/2

:3 :2

P

M

11/05/2021 M. Perkins G. Weaver

618-21-700

1383 -

70FX101D

FIRE PROTECTION PLAN - FIRST LEVEL

AREA D

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO

COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:

A. SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,

LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS

AND DETAILS

B. CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,

SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS

A. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION

OF THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED.

CONTRACTOR TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER

SIGNIFICANTLY FROM THE CONSTRUCTION DOCUMENTS.

B. A DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES

WITH DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR

PRIOR TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE

COR PRIOR TO THE START OF WORK.

C. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING

HEIGHTS, AND SQUARE FOOTAGE.

D. CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND

OTHER TRADES PRIOR TO CONSTRUCTION.

E. ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED

CHASES UNLESS NOTED OTHERWISE.

F. ALL AREAS ARE DESIGNED AS ORDINARY HAZARD GROUP 1 OCCUPANCY UNLESS

NOTED OTHERWISE ON PLAN.

G. ALL SPRINKLERS SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022

NFPA 13.

H. ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL

LISTED FOR USE IN FIRE PROTECTION SYSTEMS.

I. ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH

EXISTING BUILDING STANDARDS.

J. INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE

SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.

K. PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.

L. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

M. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT

CONNECTIONS BETWEEN ALL DISSIMILAR METALS.

N. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL

PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE

CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED

FIRE PROOF CAULKING MATERIAL.

O. ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.

P. THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE

PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT

CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.

THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION

SYSTEM SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO

PERFORMING WORK.

Q. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACES DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD

LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO

COMMENCING WORK

1. EXISTING SPRINKLER HEAD IN THIS LOCATION TO REMAIN, PROTECT IN PLACE.

2. EXISTING PENDENT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND

REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD

CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE

2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.

3. NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD CAGE. CONNECT

PIPING TO NEAREST BRANCH LINE. INSTALL SPRINKLER HEAD AND HANGERS IN

ACCORDANCE WITH THE 2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL

INFORMATION.

4. NEW HEAT/SMOKE DETECTOR AND FIRE ALARM STROBE/HORN, MOUNT AND

SUPPORT FROM DECK ABOVE. COORDINATE LOCATION WITH ALL OTHER

TRADES AND EXISTING CONDITIONS. SEE ARCHITECTURAL PLANS FOR

ADDITIONAL INFORMATION.

5. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACING DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD

LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO

COMMENCING WORK.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1" = 10'-0"

F2

FIRE PROTECTION PLAN - FIRST

LEVEL AREA D

SPRINKLER HEAD LEGEND

SYM.

DEMO

TYPE

QUICK

RESPONSE

TEMP "K"

DEMO

QUANTITY

PENDENT

YES 170F 5.6UPRIGHT

YES 155F 5.6

NOTE: LEGEND INFORMATION IS SPECIFIC TO THIS SHEET ONLY

NEW

QUANTITY

SYM.

NEW

05/06/2022

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

1F-1171F-1171F-117A1F-117A

1F-1181F-118 C1-56C1-561F-120A1F-120A

EE

C1-65C1-65

1H-1211H-121

C-6C-6

1L-1021L-102

C1-64AC1-64A

M-8M-8

C1-66C1-66

1H-1161H-116 1H-1171H-117

1L-1401L-140

1L-1391L-139

1L-1411L-141

1L-1381L-1381H-114A1H-114A

1H-114C1H-114C

1H-1141H-114

1H-114B1H-114B

1H-1181H-118 C1-313C1-313

1L-1161L-116

C1-56AC1-56A

ELECTRIC

ROOM

1F-119A1F-119A

TELECOM

ROOM

1F-119B1F-119B

1L-1171L-117

1L-1181L-118

1L-1191L-119

1L-1221L-122

C1-58C1-58

C1-57AC1-57A

C1-57C1-57

ELECTRIC

ROOM

1F-119E1F-119E

TELECOM

ROOM

(PINK-STACK)

1F-119D1F-119D

C1-57BC1-57B

1L-1261L-126

1L-1251L-125

1L-1241L-124

ELECTRIC

ROOM

1F-119C1F-119C

1L-1031L-103

1L-1041L-104

1L-1051L-105

1L-108A1L-108A 1L-108B1L-108B

1L-1091L-109

1L-1121L-112

1L-1131L-113

1L-1151L-115

1L-1141L-1141L-116A1L-116A1L-108C1L-108C 1L-105A1L-105A

1L-104A1L-104A

C1-61C1-61

1L-1071L-107

1L-131B1L-131B

1L-131A1L-131A

1L-1101L-110

1L-1111L-111

1L-1211L-121

1L-121A1L-121A 1L-1231L-123

1L-1291L-129

1L-129A1L-129A1L-1311L-131

C1-60C1-60

1L-131C1L-131C

1L-131D1L-131D

1L-1321L-132 1L-1431L-143

1L-1331L-133

C1-63C1-63

1L-138A1L-138A 1L-136A1L-136A

1L-1371L-137 1L-1361L-136 1L-1351L-135

1L-135A1L-135A 1L-134A1L-134A

1L-128A1L-128A 1L-127A1L-127A

1L-1271L-1271L-128C1L-128C1L-128B1L-128B1L-1301L-1301L-134B1L-134B1L-134C1L-134C

C1-61AC1-61A C1-61BC1-61B

C1-61CC1-61C

1L-1281L-1281L-1341L-134

C-5C-5

C1-59C1-59

STAIRSTAIR

C1-310C1-310

MECHANICAL

ROOM

1F-1191F-119 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

A

B D

TRUE NORTH

PLAN NORTH

E F

G

H

J

K

L

M

N

C

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/7

/2

:2

:2

A

M

05/06/2022 M. Perkins G. Weaver

618-21-700

1383 -

70FX101G

FIRE PROTECTION PLAN - FIRST LEVEL

AREA G

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO

COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:

A. SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,

LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS

AND DETAILS

B. CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,

SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS

A. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION

OF THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED.

CONTRACTOR TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER

SIGNIFICANTLY FROM THE CONSTRUCTION DOCUMENTS.

B. A DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES

WITH DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR

PRIOR TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE

COR PRIOR TO THE START OF WORK.

C. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING

HEIGHTS, AND SQUARE FOOTAGE.

D. CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND

OTHER TRADES PRIOR TO CONSTRUCTION.

E. ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED

CHASES UNLESS NOTED OTHERWISE.

F. ALL AREAS ARE DESIGNED AS ORDINARY HAZARD GROUP 1 OCCUPANCY UNLESS

NOTED OTHERWISE ON PLAN.

G. ALL SPRINKLERS SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022

NFPA 13.

H. ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL

LISTED FOR USE IN FIRE PROTECTION SYSTEMS.

I. ALL NEW SPRINKLERS SHALL BE PROVIDED WITH NEW ESCUTCHEONS TO MATCH

EXISTING BUILDING STANDARDS.

J. INSTALL QUICK RESPONSE SPRINKLERS (QRS) IN ALL AREAS, EXCEPT WHERE

SPECIFICALLY PROHIBITED AS DEFINED BY 2022 NFPA 13.

K. PIPING TO BE SCHEDULE 40 BLACK STEEL WITH CAST IRON FITTINGS.

L. ANY FLOOR, WALL, OR CEILING CUTTING OR FILLING THAT IS REQUIRED TO

COMPLETE THIS PROJECT, THE CONTRACTOR SHALL PATCH AND PAINT AND

RETURN TO MATCH EXISTING CONDITIONS AND FINISHES.

M. CONTRACTOR TO PROVIDE GALVANIC PROTECTION AS REQUIRED AT

CONNECTIONS BETWEEN ALL DISSIMILAR METALS.

N. CONTRACTOR TO VALIDATE AND VERIFY ALL FIRE RATED AND/OR SMOKE RATED

WALLS AND ASSEMBLIES INDICATED ON PLANS IN WORK AREA. PROVIDE ALL

PIPING PENETRATIONS OF FIRE, SMOKE AND FULL HEIGHT WALLS SHALL BE

CAULKED AIRTIGHT TO THE ADJACENT STRUCTURE BY MEANS OF U.L. APPROVED

FIRE PROOF CAULKING MATERIAL.

O. ALL NEW PIPES TO BE CLEANED AND TESTED PRIOR TO COMMISSIONING.

P. THE SPRINKLER CONTRACTOR SHALL COORDINATE AND PERFORM ALL FIRE

PROTECTION WORK IN ACCORDANCE WITH VA REQUIREMENTS TO ENSURE THAT

CONTINUOUS SPRINKLER COVERAGE IS PROVIDED THROUGHOUT THE PROJECT.

THE SPRINKLER CONTRACTOR SHALL COORDINATE ALL FIRE PROTECTION

SYSTEM SHUTDOWNS, INCLUDING POINTS OF TIE IN, ETC. WITH THE VA PRIOR TO

PERFORMING WORK.

Q. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACES DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD

LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO

COMMENCING WORK

1. EXISTING SPRINKLER HEAD IN THIS LOCATION TO REMAIN, PROTECT IN PLACE.

2. EXISTING PENDENT SPRINKLER HEAD IN THIS LOCATION TO BE REMOVED AND

REPLACED WITH NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD

CAGE. INSTALL SPRINKLER HEAD AND HANGERS IN ACCORDANCE WITH THE

2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL INFORMATION.

3. NEW UPRIGHT SPRINKLER HEAD WITH PROTECTIVE HEAD CAGE. CONNECT

PIPING TO NEAREST BRANCH LINE. INSTALL SPRINKLER HEAD AND HANGERS IN

ACCORDANCE WITH THE 2022 NFPA 13. SEE SHEET FX001 FOR ADDITIONAL

INFORMATION.

4. NEW HEAT/SMOKE DETECTOR AND FIRE ALARM STROBE/HORN, MOUNT AND

SUPPORT FROM DECK ABOVE. COORDINATE LOCATION WITH ALL OTHER

TRADES AND EXISTING CONDITIONS. SEE ARCHITECTURAL PLANS FOR

ADDITIONAL INFORMATION.

5. CONTRACTOR IS RESPONSIBLE FOR MAINTAINING COMPLIANCE WITH THE 2022

NFPA 13 FOR SURROUNDING SPACING DURING AND AFTER RENOVATION.

CONTRACTOR IS RESPONSIBLE FOR FIELD VERIFYING SPRINKLER HEAD

LOCATIONS AND PIPING TO BE MODIFIED BY THE RENOVATION PRIOR TO

COMMENCING WORK.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1" = 10'-0"

F2

FIRE PROTECTION PLAN - FIRST

LEVEL AREA G

1 Revision 1 Date 1

SPRINKLER HEAD LEGEND

SYM.

DEMO

TYPE

QUICK

RESPONSE

TEMP "K"

DEMO

QUANTITY

PENDENT

YES 170F 5.6UPRIGHT

YES 155F 5.6

NOTE: LEGEND INFORMATION IS SPECIFIC TO THIS SHEET ONLY

NEW

QUANTITY

SYM.

NEW

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

C1-196C1-196

C1-199C1-199

C1-200C1-200

1A-1051A-105

1A-1041A-104

AA

1G-1131G-113

1G-1121G-112

C1-136C1-136 C1-138C1-138

1R-1131R-113

1R-1111R-111

1T-1051T-105

ELECTRIC

ROOM

1T-1031T-103

1R-1091R-109

1R-1081R-108

1S-1431S-143

1S-1421S-142

1S-1441S-144

1S-1411S-141

1S-1401S-140

1S-141A1S-141A

1R-105C1R-105C1R-1061R-106

1R-1031R-103 1R-1041R-104

M-4M-4

1R-105B1R-105B

1R-105A1R-105A

1R-1051R-105

CAGE

1R-1091R-109

1R-1071R-107

C1-147C1-147

1R-1021R-102

1S-21S-2

C1-139C1-139

C1-143C1-143C1-142C1-142C1-141C1-141CA-140CA-140

1R-1251R-125

1R-125A1R-125A

1R-1261R-126

1R-1321R-1321R-1341R-134

1R-1361R-136 1R-1391R-139

1R-141A1R-141A1R-1411R-141

1R-1421R-142

1R-1581R-158

1R-1401R-140

1Q-1121Q-112

1Q-1111Q-111

1Q-1101Q-110

1Q-1091Q-109

1Q-1071Q-107

1Q-1051Q-105

1Q-1061Q-106

C1-129AC1-129A

C1-129BC1-129B

1Q-1031Q-103

1Q-1041Q-104

1Q-108A1Q-108A

1Q-1081Q-108

1Q-1021Q-102

1Q-1011Q-101

1R-143A1R-143A

1R-146A1R-146A

TOILET

1R-1431R-143

1R-1451R-145

1R-1461R-146

C1-133C1-133

1R-1381R-138

C1-129C1-129

C1-132C1-132 1R-1331R-133

1R-1311R-131

C1-131C1-131

1R-1271R-127

C1-130C1-1301R-1351R-135

1R-128A1R-128A

1R-1281R-128

C1-146AC1-146A

C1-144C1-144

1R-1171R-117

1R-1181R-118

1R-1191R-119

1R-1201R-120

1R-1211R-121

1R-1221R-122

1R-1231R-123

1R-1241R-124

C1-145C1-145

C1-117C1-117

ELECTRIC

ROOM

1N-1031N-103

TELECOM

ROOM

1N-1021N-102

2727 1S-101S-10

1N-1011N-101

C1-115C1-115

1S-81S-8FF

TELECOM

ROOM

(BLUE-STACK)

C1-111C1-111

C1-116C1-116

C1-118C1-118

1M-1251M-125

1M-1221M-122

1M-1211M-121

1M-120A1M-120A

TOILET

1M-1201M-120 C1-124C1-124

1M-1191M-119

1M-1231M-123

C1-120C1-120

1M-124A1M-124A 1M-124B1M-124B 1M-124C1M-124C 1M-124D1M-124D 1M-1261M-126 1M-1271M-127 1M-1061M-106

C1-127C1-127

1M-1051M-105

1M-1071M-107

C1-125AC1-125A1M-112A1M-112A

1M-1121M-112

1M-1141M-114

1M-114A1M-114A

1M-1031M-103

1M-1041M-104

1M-1081M-108

1M-1091M-109

1M-1101M-110

1M-1111M-111

C1-148C1-148

C1-149C1-149

1M-1131M-113

1M-1151M-1151M-1161M-116

1M-1171M-117

1M-116A1M-116A 1M-115A1M-115A

1M-1181M-118

1M-123A1M-123A

C1-126C1-126

C1-126AC1-126A

1M-118B1M-118B

1M-118A1M-118A

1M-124E1M-124E

1M-124F1M-124F 1M-124G1M-124G

1M-1241M-124 1M-106A1M-106A

M-9M-9

1M-119A1M-119A

C1-123C1-123

C1-125C1-125

1M-111A1M-111A

1S-71S-7

ELECTRIC

ROOM

1M-1021M-102 1A-1021A-102

1A-1031A-103

M-3M-3

M-2M-2

TELECOM

ROOM

1M-1011M-101

C-10C-10 1A-1011A-101

C-9C-9

C1-112C1-112

C1-194C1-194

C1-194AC1-194A

M-10M-10

GG

1Q-100F1Q-100F

1Q-100G1Q-100G

1Q-100E1Q-100E

1Q-100D1Q-100D

1Q-100H1Q-100H

1Q-100A1Q-100A

1Q-100B1Q-100B

1Q-1001Q-100

1Q-100C1Q-100C

1R-1301R-130

1R-137B1R-137B

C1-134C1-134

1R-137C1R-137C

1R-1371R-137

1J-1561J-156

1R-1291R-129

1R-1121R-112

1R-1101R-110

1Q-1151Q-115

1Q-1141Q-114

1Q-1131Q-113

C1-135C1-135

1Q-1191Q-119

1Q-1201Q-120

1Q-1221Q-122

1V-1071V-107

1V-1121V-112

1V-1281V-128 1V-1271V-127

1V-1111V-111 1V-1101V-110

1V-1091V-109 1V-1081V-108

1V-1301V-130

C1-184C1-184

1V-1291V-129

1Q-1211Q-121

1V-1261V-126

1V-1251V-125

1V-112A1V-112A

C1-155C1-155

1V-1131V-113

1V-112B1V-112B

C1-174C1-174

1Q-122A1Q-122A

1Q-122B1Q-122B

C1-117AC1-117A

TYP.

3 4

7'-6" 10'-5" 7'-6"

7' -6 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

A

B D

TRUE NORTH

PLAN NORTH

E F

G

H

J

K

L

M

N

C

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/6

/2

:3 :5

P

M

11/05/2021 M. Perkins G. Weaver

618-21-700

1383 -

70FX101L

FIRE PROTECTION PLAN - FIRST LEVEL

AREA L

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

CONTRACTOR SHALL PROVIDE THE FOLLOWING PRIOR TO

COMMENCEMENT OF WORK FOR REVIEW AND APPROVAL:

A. SHOP DRAWING IDENTIFYING MAIN PIPE SIZES AND LOCATIONS,

LOCATION OF PIPE BRACING, HANGERS AND SPRINKLER HEADS

AND DETAILS

B. CUT SHEETS AND SUBMITTAL FOR ALL PIPING, FITTINGS,

SPRINKLER HEADS, HANGERS AND SUPPORT ATTACHMENTS

A. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. ACTUAL CONDITIONS MAY DIFFER FROM THOSE INDICATED.

CONTRACTOR SHALL FIELD VERIFY IN ADVANCE THE LOCATION AND CONDITION

OF THE EXISTING SYSTEMS SHOWN TO BE MODIFIED OR REMOVED.

CONTRACTOR TO NOTIFY ARCHITECT SHOULD CONDITIONS BE FOUND TO DIFFER

SIGNIFICANTLY FROM THE CONSTRUCTION DOCUMENTS.

B. A DETAILED SCHEDULE, INCLUDING PROJECTED SERVICE INTERRUPTION DATES

WITH DURATIONS, AND DETAILED PHASING PLAN IS TO BE PROVIDED TO THE COR

PRIOR TO THE START OF WORK. THIS SUBMITTAL MUST BE ACCEPTED BY THE

COR PRIOR TO THE START OF WORK.

C. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT DIMENSIONAL DATA, CEILING

HEIGHTS, AND SQUARE FOOTAGE.

D. CONTRACTOR SHALL COORDINATE ALL WORK WITH BUILDING OWNER AND

OTHER TRADES PRIOR TO CONSTRUCTION.

E. ALL PIPING TO BE ROUTED WITHIN CEILING SPACE OR CONCEALED IN FURRED

CHASES UNLESS NOTED OTHERWISE.

F. ALL AREAS ARE DESIGNED AS ORDINARY HAZARD GROUP 1 OCCUPANCY UNLESS

NOTED OTHERWISE ON PLAN.

G. ALL SPRINKLERS SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE 2022

NFPA 13.

H. ALL MATERIALS, DEVICES, HANGERS AND SUPPORTS SHALL BE NEW AND UL

LISTE…