618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-6.pdf

PDF 20 MB Posted

Attached to
EHRM Infrastructure Upgrades Construction Design-Bid Build Project at the Minneapolis VA Medical Center (VAMC)
Solicitation number
36C77622R0045
Issued by

About this file

This document provides details for a federal contract opportunity to conduct construction and commissioning work for the Electronic Health Record Modernization infrastructure upgrades project at the Minneapolis VA Medical Center. The solicitation will be issued as a Request for Proposal to SDVOSB concerns only, with a size standard of $39.5 million, for a period of performance of approximately 450 calendar days from notice to proceed. The construction magnitude is expected to be between $20-50 million. Work includes building a new server room on the roof and upgrades throughout the hospital. Limited on-site storage will require off-site material storage planning. Phased structural and civil work will require early coordination. The majority of work will likely need to be done on off-hours and weekends to minimize hospital disruptions. All questions must be submitted in writing to the identified point of contact.

View the file

Other files

File Type Posted
Technical Question Tracking Sheet Infra Upgrades FINAL.pdf PDF
36C77622R0045 0009.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-11.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-1.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-7.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-2.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-4.pdf PDF
618-21-700.ADD-001.Summary.Log.20220707.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-9.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-5.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-10.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-3.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-8.pdf PDF
36C77622R0045 0008.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades - FINAL.pdf PDF
36C77622R0045 0007.pdf PDF
36C77622R0045 0006.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades - Minneapolis.docx DOCX document
36C77622R0045 0005.docx DOCX document
36C77622R0045 0004.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades.docx DOCX document
36C77622R0045 0003.pdf PDF
Site Visit Sign In sheet.pdf PDF
36C77622R0045 0002.pdf PDF
36C77622R0045 0001.pdf PDF
36C77622R0045 - Update 5.23.22.docx DOCX document
618-21-700.MEHRM.FINAL.B70.20220506Part-7.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-11.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-33-36.zip ZIP file
618-21-700.MEHRM.FINAL.B76.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-48-52.zip ZIP file
36C77622R0045.docx DOCX document
618-21-700.MEHRM.FINAL.B70.20220506Part-21.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-25-28.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-4.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-23.pdf PDF
618-21-700.MEHRM.FINAL.B75.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL_SPECIFICATIONS.20220506Part-2.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-45-47.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-6.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-13.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-20.pdf PDF
618-21-700.MEHRM.FINAL.B73.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B49.20220506-REDUCED.pdf PDF
01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
618-21-700.MEHRM.FINAL.SITE.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B222.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-12.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-16-17.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-29-32.zip ZIP file
Show 40 more

Latest 50 of 80 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

OSE

SCR

DCRX

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

70E-422

B6

TELECOM

ROOM

(ORANGE-STACK)

2H-1122H-112

2F-1492F-149 2F-1472F-147

2F-1462F-146

2F-1442F-144 2F-1422F-142

2F-1412F-141 2F-1532F-153

2F-141A2F-141A

2L-1012L-101

2L-1022L-102

2L-1032L-103 2L-1042L-104 2L-1052L-105

2L-1062L-106

2L-1072L-107

2L-1082L-108 2L-1092L-109

2L-1102L-110

2L-1112L-111

2L-1122L-112

2L-1132L-113

2L-1142L-114

2L-1152L-115

2L-1162L-116

2L-118A2L-118A

2L-1182L-118

2L-1192L-119

2L-1202L-120 2L-1212L-121

2L-1222L-122

2L-1232L-123

2L-1242L-124

2L-1252L-125

2L-1262L-126

2L-1272L-127

2L-1282L-1282L-1292L-129

2L-1302L-130

2L-1312L-131

2L-1322L-1322L-1332L-1332L-1342L-1342L-1352L-135

2L-1362L-136

2H-1102H-110

2H-1112H-111

2H-1132H-113

2H-1142H-114

C-6C-6

2H-1092H-109

2C-482C-48

2C-492C-49

2C-502C-50

2C-512C-51

C2-52C2-52

C2-53C2-53 C2-54C2-54

C2-55C2-55

C2-56C2-56

C2-57C2-57

2C-582C-58

C2-60C2-60

C2-54AC2-54A

C2-50AC2-50A

MECHANICAL

2F-1212F-121

ELECTRICAL

ROOM

2F-121A2F-121A

TELECOM

ROOM

2F-121B2F-121B

ELECTRICAL

ROOM

2F-121C2F-121C

TELECOM

ROOM

2F-121D2F-121D

M-5M-5

2H-111A2H-111A2H-111B2H-111B

2H-111C2H-111C

2L-135A2L-135A

2L-102A2L-102A

2L-103A2L-103A

2L-103B2L-103B

2L-104A2L-104A

2L-104B2L-104B

2L-105A2L-105A

2L-109A2L-109A

2L-115A2L-115A 2L-120A2L-120A

2L-121A2L-121A

2L-123A2L-123A

2L-124A2L-124A2L-126A2L-126A

2L-127A2L-127A

2L-128A2L-128A2L-129A2L-129A

2L-132A2L-132A

2L-133A2L-133A

2L-119A2L-119A

2K-1012K-101

2K-103A2K-103A

70E-422

B3

70E-422

D6 on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRUE NORTH

PLAN NORTH

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

A

B D

EF

G

H

J

K

L

M

C

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/7

/2

:3

:4

A

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-102G

ELECTRICAL PLAN - SECOND LEVEL AREA G

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-30R RECEPTACLE.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. REMOVE EXISTING RECEPTACLE.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR

PRIOR TO BEGINNING OF CONSTRUCTION.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1" = 10'-0"

F2

ELECTRICAL PLAN - SECOND LEVEL

AREA G

1 Revision 1 Date 1

05/06/2022

ADDENDUM #1 07/07/2022

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

2L-1352L-135

2H-111A2H-111A2H-111B2H-111B

2H-111C2H-111C

2L-135A2L-135A

2J-1532J-153

C2-73C2-73

2H-106A2H-106A

2K-1012K-101

2K-1032K-103

2K-106A2K-106A

2K-1322K-132

2K-109A2K-109A

2K-1102K-110 2K-1112K-111

2K-1122K-112

2K-1132K-113

2K-1142K-114 2K-115A2K-115A

2K-119A2K-119A

2K-1172K-117

2K-1202K-120

2K-120A2K-120A

2K-1222K-122

2K-123A2K-123A

2K-1242K-124

2K-1262K-126

2K-1252K-125

2K-1282K-128

2K-129A2K-129A

2K-1302K-130

2K-1332K-133

2K-1352K-135

C2-62C2-62

C2-68C2-68

C2-67C2-67

2K-137A2K-137A

2K-1042K-104

2K-1092K-109

2K-1152K-115

2K-1182K-118

2K-1172K-117

C2-68AC2-68A

TELE COM

ROOM

2K-122A2K-122A

2K-1222K-122

2K-1272K-127

2K-1292K-129

2K-1212K-121

2K-104A2K-104A

2K-103A2K-103A

2K-108A2K-108A

2K-1192K-119

2K-118A2K-118A

2K-125A2K-125A

2K-127A2K-127A

2K-124A2K-124A

2K-128A2K-128A

2K-133A2K-133A

2K-131A2K-131A

2K-134A2K-134A

2K-135A2K-135A

2K-1002K-100

C2-65C2-65

C2-69C2-69

2K-123B2K-123B

2K-1232K-123

2K-1072K-107 2K-1312K-131

2K-1062K-106

2K-1082K-108

2K-1342K-134 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRUE NORTH

PLAN NORTH

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

A

B D

EF

G

H

J

K

L

M

C

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/6

/2

:4 :0

P

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-102H

ELECTRICAL PLAN - SECOND LEVEL AREA H

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. NOT USED.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. NOT USED.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR

PRIOR TO BEGINNING OF CONSTRUCTION.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1" = 10'-0"

F6

ELECTRICAL PLAN - SECOND LEVEL

AREA H

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

2J-1002J-100

2J-1012J-101 2J-1022J-102

2J-1032J-103

2J-1052J-105 2J-1062J-106

2J-1072J-107

2J-1082J-108

2J-1092J-1092J-1102J-1102J-1112J-111 2J-1122J-112

2J-1142J-114

2J -1

2J

-1

2J-1162J-116

2J-1172J-117

2J-1192J-119 2J-1202J-1202J-1212J-121

2J-1222J-122

2J-1232J-123

2J-1242J-124

2J-1252J-125

2J-1262J-126

2J-1272J-127 2J-1282J-128

2J-1292J-129

2J-1302J-130

2J-1312J-131

2J-1322J-132

2J-1332J-133

2J-1342J-134

2J-1352J-135

2J-1362J-136

2J-1372J-137

2J-1382J-138

2J-1392J-139

2J-1402J-140

2J-1412J-141

2J-1422J-142

2J-1432J-143

2J-1442J-144

2J-1452J-145

2J-1462J-146

2J-1472J-147

2J-1482J-148

2J-1492J-149 2J-1502J-150

2J-1512J-151

2J-1522J-152

2J-1532J-153

2J-1542J-154

2J-1552J-155

2H-1012H-101

2H-1022H-102

2H-1032H-103

2H-1042H-104

2H-1052H-105

2H-1062H-106

2H-1082H-108

C2-72C2-72

C2-73C2-73

C2-74C2-74

C2-75C2-75

C2-77C2-77

C2-79C2-79

C2-80C2-80

C2-81C2-81C2-82C2-82C2-83C2-83

C2-84C2-84

C2-85C2-85

C2-61C2-61

2H-103A2H-103A

C2-71BC2-71B

C2-71CC2-71C

C2-75AC2-75A

C2-75BC2-75B

C2-75CC2-75C

C2-75DC2-75D

C2-77AC2-77A

C2-77BC2-77B

2J-154A2J-154A

2H-106A2H-106A

2J-152A2J-152A2J-146A2J-146A

2J-144A2J-144A

2J-144B2J-144B

2J-143A2J-143A

2J-143B2J-143B

2J-140A2J-140A

TELECOM

ROOM

2J-132A2J-132A

ELECTRICAL

ROOM

2J-132B2J-132B

ELECTRICAL

ROOM

2J-132C2J-132C

TELECOM

ROOM

2J-132D2J-132D

2J-130A2J-130A

2J-131A2J-131A 2J-131B2J-131B

C-8C-8

C2-71C2-71

2K-137A2K-137A

2K-135A2K-135A on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRUE NORTH

PLAN NORTH

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

A

B D

EF

G

H

J

K

L

M

C

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/6

/2

:4 :1

P

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-102J

ELECTRICAL PLAN - SECOND LEVEL AREA J

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. NOT USED.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. NOT USED.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR

PRIOR TO BEGINNING OF CONSTRUCTION.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1" = 10'-0"

F2

ELECTRICAL PLAN - SECOND LEVEL

AREA J

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

2S-72S-7

C-10C-10

ELECTRICAL

ROOM

2M-1152M-115

TELECOM

ROOM

2M-1162M-116

2A-1012A-101

2A-1022A-102

2A-1032A-103 2M-1012M-101

2M-1022M-102 2M-1032M-103

2M-1042M-104

2M-1052M-105

2M-1062M-106

2M-1072M-107

2M-1082M-108

2M-1092M-109

2M-1102M-110

2M-1112M-111

2M-1122M-112

2M-1132M-113 2P-1022P-102

2P-1032P-103

2P-1042P-104

2P-1052P-105

2P-1062P-106

2P-1072P-107

2P-1082P-108 2P-1092P-109

TELECOM

ROOM

(BLUE

STACK -

ALTERNATE)

2P-1102P-110

2P-1012P-101

2P-1112P-111

2P-1122P-112

2P-1132P-113

2P-1142P-114

2P-1152P-115

2P-1162P-116

2P-1172P-117

2P-1182P-118

2P-1192P-119

2P-1202P-120 2P-1212P-121

2P-1222P-122

2P-1232P-123

2P-1242P-124

C2-87C2-87

C2-88C2-88

C2-89C2-89

2P-125B2P-125B

2P-125C2P-125C

2P-125D2P-125D

2P-125E2P-125E

2P-125F2P-125F

2P-125G2P-125G

C2-96C2-96

C2-98C2-98

2P-125H2P-125H 2P-125I2P-125I 2P-125J2P-125J

C2-102C2-102

C2-103C2-103

C2-104C2-104

C2-105C2-105

C2-106C2-106

C2-107C2-107

C2-108C2-108

C2-109C2-109

C2-110C2-110

C2-111C2-111

C2-112C2-112

2M-1142M-114

2P-106A2P-106A

2P-106B2P-106B

C2-102AC2-102A

2S-82S-8FF

2P-112A2P-112A

2P-123A2P-123A

2P-123B2P-123B

2P-123C2P-123C

2P-122A2P-122A

2P-119A2P-119A 2P-120A2P-120A

C2-86C2-86

C2-76C2-76

C2-102BC2-102B

2R-1622R-162

2Q-1042Q-1042Q-1042Q-1042Q-1042Q-1042Q-1042Q-104 2R-149A2R-149A

2R-1002R-100 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRUE NORTH

PLAN NORTH

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

A

B D

EF

G

H

J

K

L

M

C

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/6

/2

:4 :3

P

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-102K

ELECTRICAL PLAN - SECOND LEVEL AREA K

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. NOT USED.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. NOT USED.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR

PRIOR TO BEGINNING OF CONSTRUCTION.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1" = 10'-0"

F3

ELECTRICAL PLAN - SECOND LEVEL

AREA K

C R

ES D

CR

X O

S

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

70E-422

F6

TELECOM

ROOM

2T-1022T-102

C2-126C2-126

C2-127C2-127

C2-153C2-153

2A-1052A-105

AATELECOM

ROOM

2M-1162M-116

C2-108C2-108

C2-109C2-109

2T-1342T-134

2R-1082R-108 2R-1092R-109

2R-1132R-113

2R-1142R-114

2R-1152R-115

2R-1162R-116

2R-1162R-116

2R-1192R-119

2R-1202R-120

2R-1202R-120

2R-1222R-122

2R-1532R-1532R-1542R-154

2R-1552R-155

2R-1562R-156

2R-1572R-157

2R-1582R-158

2R-1592R-159

2R-1602R-160

2R-1612R-161

2R-1622R-162

ELECTRICAL

ROOM

2Q-1022Q-102

TELECOM

ROOM

2Q-1032Q-103

2Q-1042Q-104

2Q-1042Q-104

2Q-1042Q-104

2Q-1072Q-107 2Q-1072Q-107

2Q-1092Q-109

2Q-1042Q-104

2Q-1112Q-111

2Q-1122Q-112 2Q-1042Q-104

2Q-1042Q-104

2Q-1152Q-115

2Q-1162Q-116

2Q-1172Q-117

2Q-1182Q-118

2Q-1042Q-1042Q-1042Q-104

2Q-1212Q-121

2Q-1222Q-122

2Q-1232Q-123

2Q-1242Q-124

2Q-1242Q-124

2Q-1262Q-126

2Q-1272Q-127

2Q-1282Q-128

2Q-1282Q-128

2Q-1282Q-128

2Q-1282Q-128

2Q-1322Q-132

2Q-1332Q-133

2Q-1342Q-134

2Q-1352Q-135

2R-1162R-116

2R-1162R-116

C2-173C2-173 C2-173C2-173

C2-173C2-173

C2-173C2-173

C2-173C2-173

C2-178C2-178

C2-178C2-178

2Q-1322Q-132

C2-191AC2-191A

C2-191AC2-191A

C2-183C2-183

2Q-1042Q-104

2Q-1042Q-104

2Q-1042Q-104

2Q-1042Q-104

2Q-1042Q-104

2Q-1042Q-104

2Q-1042Q-104

2Q-1042Q-104

2Q-1042Q-104 C2-183C2-183

C2-183C2-183

C2-183C2-183

2Q-1042Q-104

C2-180AC2-180A

2R-160B2R-160B

BB

ELECTRICAL

ROOM

2T-1032T-103

2S-22S-2

2R-1162R-116

2R-1602R-160

2R-149A2R-149A

2R-149A2R-149A

2Q-135A2Q-135A

2Q-132A2Q-132A

2Q-121a2Q-121a

2Q-1072Q-107

2T-1282T-128

2T-1292T-129 2T-1302T-130

2T-1312T-131

2T-1422T-142 2T-1412T-141 2T-1402T-140

2T-1392T-139

2T-1352T-135

2T-1362T-136

2T-1372T-137

2T-1382T-1382T-1462T-146

2T-1452T-145

2T-1542T-154 2T-1532T-153 2T-1522T-152 2T-1512T-151

2T-1482T-148

2T-1492T-149

2T-1502T-150

2T-1552T-155 2T-1562T-156 2T-1572T-157 2T-1582T-158

2T-1592T-159

2T-1612T-161

2T-1602T-160 2R-1072R-107

2R-1062R-106

2R-1052R-105

2R-104A2R-104A

2R-1032R-103

2R-103B2R-103B

2R-1002R-100

2T-1012T-101

2R-1102R-110

2T-0042T-004

2T-0052T-005

2T-0062T-006

2T-0072T-007

2T-0082T-008

2R-1162R-116

C2-151C2-151

2V-1202V-120

2V-1312V-131

2V-1472V-147

2V-1542V-154

2V-146A2V-146A

2V-146B2V-146BC2-198C2-198

2T-1332T-1332T-0032T-003

2T-1472T-1472T-1442T-144

70E-422

F3 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRUE NORTH

PLAN NORTH

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

A

B D

EF

G

H

J

K

L

M

C

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/6

/2

:4 :4

P

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-102L

ELECTRICAL PLAN - SECOND LEVEL AREA L

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. NOT USED.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. NOT USED.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS

FOR ADDITIONAL INFORMATION.

A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING

WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL

PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN

REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.

B. EXISTING CONDITIONS ARE BASED ON EXISTING PLANS AND FIELD VERIFICATION

WHERE FEASIBLE. CONSTRUCTION AREA CONDITIONS MAY DIFFER FROM

THOSE INDICATED.

C. MINIMUM BRANCH CIRCUIT SIZE SHALL BE 2#12, 1#12G., 3/4"C.

D. CONTRACTOR SHALL COORDINATE FINAL POINT OF CONNECTIONS

WITH VA COR PRIOR TO ROUGH-IN.

E. PROVIDE NEMA 3R ENCLOSURES FOR EQUIPMENT INSTALLED

OUTDOORS

F. SIZE BRANCH CIRCUITS AND FEEDERS TO EQUIPMENT PER PANEL

SCHEDULE AND FEEDER AND BRANCH CIRCUIT SIZING TABLE ON E-501.

G. COORDINATE FINAL EQUIPMENT CONNECTIONS AT EQUIPMENT WITH

EQUIPMENT SUPPLIER, PRIOR TO ROUGH-IN.

H. LABEL DEVICE PLATES WITH A PERMANENT ADHESIVE LABEL LISTING

PANEL AND CIRCUIT FEEDING THE WIRING DEVICE.

I. UPDATE PANEL SCHEDULES AFFECTED BY RENOVATION.

J. NEW CIRCUIT BREAKERS PROVIDED SHALL MATCH THE EXISTING TYPE

OF CIRCUIT BREAKERS IN PANEL BEING RENOVATED.

K. CONTRACTOR SHALL FIELD COORDINATE CABLE TRAY LAYOUT WITH

EXISTING UTILITIES ROUTED THROUGH THE RENOVATED SPACE.

L. CONTRACTOR SHALL COMPLY WITH NEC 300.22 FOR CONDUIT ROUTED IN

PLENUM SPACES.

M. REFER TO E-901 FOR CUTSHEETS.

N. COMPLY WITH NEC 220.81 FOR ALL 30-DAY LOAD MEASUREMENTS OF

PANELBOARDS. SUBMIT LOAD MEASUREMENT REPORTS TO EEOR

PRIOR TO BEGINNING OF CONSTRUCTION.

O. LOCATED DISCONNECT SWITCHES TO MAINTAIN WORKING

CLEARANCES PER NEC 110.26.

NOTE: NOT ALL KEYNOTES

ARE USED ON EACH SHEET

SCALE: 1" = 10'-0"

F3

ELECTRICAL PLAN - SECOND LEVEL

AREA L

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

70E-422

F6

2T-1282T-128

2T-1292T-129 2T-1302T-130

2T-1312T-131

C2-209C2-209

2T-1112T-111

2V-1202V-120

2V-1212V-121

2V-1222V-122

2V-1232V-123

2V-1242V-124

2V-1252V-125

2V-1262V-126

2V-1272V-127

2V-1292V-129

2V-1302V-130

2V-1312V-131

2V-1322V-132

2V-1332V-133

2V-1342V-134 2V-1352V-135

2V-1362V-136

2V-1372V-137

2V-1382V-138

2V -1

2V

-1

2V-1402V-1402V-1412V-141

2V-1432V-143

2V-1442V-144

2V-1452V-145

2V-1462V-146

2V-1472V-147

2V-1482V-148

2V-1492V-149

2V-1502V-150

2V-1512V-151

2V-1522V-152

2V-1542V-154

C2-200C2-200

C2-201C2-201

C2-202C2-202

C2-203C2-203

C2-204C2-204

C2-205C2-205

2T-1102T-110

C2-199C2-199

2T-1082T-108

2T-1092T-109

2V-127A2V-127A

2V-145A2V-145A

2V-146A2V-146A

2V-146B2V-146B

ELECTRICAL

ROOM

2V-153A2V-153A

TELECOM

ROOM

2V-153B2V-153B

ELECTRICAL

ROOM

2V-153C2V-153C

TELECOM

ROOM

2V-153D2V-153D

ELECTRICAL

ROOM

2V-153E2V-153E

TELECOM

ROOM

2V-153F2V-153F

C2-200AC2-200A

2S-12S-1

C2-198C2-198

2V-1422V-142

2T-1122T-112

M-SM-S

2T-110A2T-110A

2T-110B2T-110B

2T-1132T-113

2T-1182T-118

2T-1172T-117

2T-1162T-116

2T-1142T-114

2T-1152T-115

2T-1222T-1222T-1212T-121 2T-1202T-120

2T-0012T-001

2T-0092T-009

2T-1232T-123 2T-1072T-107

ELECTRICAL

ROOM

2T-1062T-1062T-1242T-124

2T-1322T-132

2T-1332T-133

2T-1272T-127

2T-1262T-126 2T-1252T-125

2T-0022T-002

2T-0032T-003

TELECOM

ROOM

2T-1052T-105

70E-422

F4

TELECOM

ROOM

2V-153G2V-153G on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRUE NORTH

PLAN NORTH

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

A

B D

EF

G

H

J

K

L

M

C

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/7

/2

:3

:5

A

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-102M

ELECTRICAL PLAN - SECOND LEVEL AREA M

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 30A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-30R RECEPTACLE.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. REMOVE EXISTING RECEPTACLE.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL…