618-21-700.MEHRM.FINAL.B70.20220506Part-11.pdf

PDF 19 MB Posted

Attached to
EHRM Infrastructure Upgrades Construction Design-Bid Build Project at the Minneapolis VA Medical Center (VAMC)
Solicitation number
36C77622R0045
Issued by

About this file

This document summarizes a federal solicitation for construction services. The solicitation is being issued by the Department of Veterans Affairs to upgrade infrastructure in support of an Electronic Health Record Modernization project at the Minneapolis VA Medical Center. The project scope includes building a new server room on the hospital roof and other construction work throughout multiple departments. The solicitation will be a Request for Proposal evaluated according to FAR criteria and is set aside for Service-Disabled Veteran-Owned Small Businesses. The period of performance is approximately 450 calendar days with a magnitude of construction estimated between $20-50 million. Questions regarding the solicitation must be submitted in writing to the point of contact by the specified deadline.

View the file

Other files

File Type Posted
Technical Question Tracking Sheet Infra Upgrades FINAL.pdf PDF
36C77622R0045 0009.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-11.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-1.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-7.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-2.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-6.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-4.pdf PDF
618-21-700.ADD-001.Summary.Log.20220707.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-9.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-5.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-10.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-3.pdf PDF
618-21-700.MEHRM.FINAL.B70.Addendum1.20220707.ReducedPart-8.pdf PDF
36C77622R0045 0008.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades - FINAL.pdf PDF
36C77622R0045 0007.pdf PDF
36C77622R0045 0006.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades - Minneapolis.docx DOCX document
36C77622R0045 0005.docx DOCX document
36C77622R0045 0004.docx DOCX document
Technical Question Tracking Sheet - Infra Upgrades.docx DOCX document
36C77622R0045 0003.pdf PDF
Site Visit Sign In sheet.pdf PDF
36C77622R0045 0002.pdf PDF
36C77622R0045 0001.pdf PDF
36C77622R0045 - Update 5.23.22.docx DOCX document
618-21-700.MEHRM.FINAL.B70.20220506Part-7.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-33-36.zip ZIP file
618-21-700.MEHRM.FINAL.B76.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-48-52.zip ZIP file
36C77622R0045.docx DOCX document
618-21-700.MEHRM.FINAL.B70.20220506Part-21.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-25-28.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-4.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-23.pdf PDF
618-21-700.MEHRM.FINAL.B75.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL_SPECIFICATIONS.20220506Part-2.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-45-47.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-6.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-13.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-20.pdf PDF
618-21-700.MEHRM.FINAL.B73.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B49.20220506-REDUCED.pdf PDF
01 00 00 Appendix A - Bid Form Template.xlsx XLSX spreadsheet
618-21-700.MEHRM.FINAL.SITE.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B222.20220506-REDUCED.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-12.pdf PDF
618-21-700.MEHRM.FINAL.B70.20220506Part-16-17.zip ZIP file
618-21-700.MEHRM.FINAL.B70.20220506Part-29-32.zip ZIP file
Show 40 more

Latest 50 of 80 listed here. See the rest on GovTribe.

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

A/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

B

IM

/6

-2

-7

E

H R

M I n fr a st ru ct u re

U p g ra d e s

M P

L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r vt /6

/2

:3 :3

P

M

05/06/2022 M. Perkins G. Weaver

618-21-700

1383 - 70M-741

MECHANICAL SCHEDULES

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

FAN COIL UNIT SCHEDULE

SYMBOL

NO.

MANUFACTURER/MODEL

NO. TYPE

SENSIBLE

COOLING

CAPACITY

(BTU/H)

SUPPLY

AIRFLOW

(CFM)

SOUND

(dBA)

ELECTRICAL DATA

WIDTH (IN)

HEIGHT

(IN)

WEIGHT

(LBS)VOLTS PHASE HZ MCA

FCU-4A-01 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-4A-02 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-4D-03 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-4D-04 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-4G-05 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-4G-06 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-4G-07 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-4G-08 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-4L-09 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-4L-10 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-4M-11 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-4M-12 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-5K-13 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

FCU-5K-14 MULTIAQUA

MHQWW-36-H-3

WALL MOUNTED 23,304 850 43 120 1 60 .92 56.5 14.25 50.5

NOTES:

1. PROVIDE WITH FACTORY INSTALLED AND TESTED DELUXE PIPING PACKAGE WITH MODULATING CONTROL

VALVES

2. PROVIDE WITH STAINLESS STEEL DRAIN PANS. SLOPE CONDENSATE LINE AT 1/8" PER FOOT MINIMUM TO

NEAREST FLOOR DRAIN. COORDINATE FINAL LOCATION WITH VA.

3. PROVIDE SECONDARY DRAIN PAN AND CONDENSATE OVERFLOW SWITCH

4. PROVIDE FLEXIBLE CHILLED WATER COIL CONNECTIONS FOR VIBRATION ISOLATION

5. COORDINATE POWER REQUIREMENTS WITH ELECTRICAL.

05/06/2022

LA LEVEL ALARM

AT ANALYTICAL TRANSMITTER

AY ANALYTICAL SIGNAL CONVERTER

ACV ANALYTICAL CONTROL VALVE

AIT ANALYTICAL INDICATING CONTROLLER

EY VOLTAGE SIGNAL CONVERTER

IY CURRENT SIGNAL CONVERTER

HS HAND SWITCH

FIT FLOW INDICATING TRANSMITTER

FET FLOW ELEMENT\TRANSMITTER

ESL VOLTAGE SWITCH LOW (24 VAC OR LESS)

II CURRENT INDICATOR

IT CURRENT TRANSMITTER

IS CURRENT SWITCH

IA CURRENT ALARM

FA FLOW ALARM

HSI HAND SWITCH INDICATOR

HK MANUAL VARIABLE CONTROL

FY FLOW SIGNAL CONVERTER

FT FLOW TRANSMITTER

FS FLOW SWITCH

FI FLOW INDICATOR

FE FLOW ELEMENT

FCV FLOW CONTROL VALVE

ET VOLTAGE TRANSMITTER

ES VOLTAGE SWITCH (CONTROL RELAY)

EA VOLTAGE ALARM

EI VOLTAGE INDICATOR

PY PRESSURE SIGNAL CONVERTER

PDT PRESSURE DIFFERENTIAL TRANSMITTER

PS PRESSURE SWITCH

PA PRESSURE ALARM

PT PRESSURE TRANSMITTER

PIT PRESSURE INDICATING TRANSMITTER

PIS PRESSURE INDICATING SWITCH

PI PRESSURE INDICATOR

PDS PRESSURE DIFFERENTIAL SWITCH

PDI PRESSURE DIFFERENTIAL INDICATOR

PCV PRESSURE CONTROL VALVE

MV MANUAL HAND VALVE

LT LEVEL TRANSMITTER

LS LEVEL SWITCH

LE LEVEL ELEMENT

LY LEVEL SIGNAL CONVERTER

LIT LEVEL INDICATING TRANSMITTER

LIC LEVEL INDICATING CONTROLLER

LCV LEVEL CONTROL VALVE

LC LEVEL CONTROLLER (STAND ALONE)

VA VIBRATION ALARM

VS VIBRATION SWITCH

XV SOLENOID VALVE

YS SMOKE DETECTOR

VA VIBRATION ALARM

VS VIBRATION SWITCH

YCD SMOKE DAMPER

TT TEMPERATURE TRANSMITTER

TS TEMPERATURE SWITCH

TIC TEMPERATURE INDICATING CONTROLLER

TIT TEMPERATURE INDICATING TRANSMITTER

TI TEMPERATURE INDICATOR

TET TEMPERATURE ELEMENT TRANSMITTER

TE TEMPERATURE ELEMENT

TCV TEMPERATURE CONTROL VALVE

TC TEMPERATURE CONTROLLER

TA TEMPERATURE ALARM

SCM SPEED CONTROL MANUAL

TSL FREEZE STAT

SC SPEED CONTROL

INSTRUMENTATION SOCIETY OF AMERICA TABLE

INSTRUMENTATION TYPE ABBREVIATION LIST

AIC ANALYTICAL INDICATING CONTROLLER

AET ANALYTICAL ELEMENT TRANSMITTER

A

AC ANALYTICAL CONTROLLER

AI ANALYTICAL INDICATOR

AE ANALYTICAL ELEMENT

AA ANALYTICAL ALARM

CODE DESCRIPTION

VARIABLE

FINAL CONTROL ELEMENT

CODE DESCRIPTION

KC TIME CLOCK

JY POWER SIGNAL CONVERTER

JIT POWER INDICATING TRANSMITTER

TOTALIZE

CHANGE

CONNECTION

CODE DESCRIPTION

VIEWING DEVICE

PRIMARY ELEMENT

NORMALLY CLOSED OVERLOAD CONTACTS

ABBREVIATIONS

IA INSTRUMENTATION AIR

DDC DIRECT DIGITAL CONTROL

C COMMON VALVE PORT

F.O FAIL OPEN

F.C FAIL CLOSED

SR SPRING RANGE

TR THROTTLING RANGE

PH PREHEAT

HR HEAT RECOVERY

CPA CONTROL POINT ADJUSTMENT

SPDT SINGLE POLE DOUBLE THROW

DPDT DOUBLE THROW DOUBLE POLE

DA DIRECT ACTING

RA REVERSE ACTING

EP COIL IN MOTOR STARTER

TRANSFORMER

R

C

OL

HOA

CONTACT NORMALLY OPEN

PILOT LIGHT (COLOR INDICATION)

COIL IN MOTOR STARTER

CONTACT NORMALLY CLOSED

SWITCH

FUSE

HAND-OFF-AUTO SWITCH

I UNDEFINED INTERLOCK LOGIC

GENERAL INSTRUMENT OR FUNCTION SYMBOLS

FIELD

MOUNTED MOUNTED

PANEL AUXILIARY

LOCATION

ACCESSIBLE INACCESSIBLE

LOCATION

AUXILIARY

DISCRETE INSTRUMENTS

SHARED DISPLAY, SHARED CONTROL

PROGRAMMABLE LOGIC CONTROL

OR DIRECT DIGITAL CONTROL

COMPUTER FUNCTION

DUAL (MULTI)

FUNCTION INSTRUMENT

INDICATING LIGHTS, ALARMS OR HORNS

CONTROL VALVE BODY/ DAMPER SYMBOLS

GENERAL SYMBOL

ANGLE

BUTTERFLY

ROTARY VALVE

THREE - WAY

FOUR - WAY

GLOBE

PARALLEL BLADE

OPPOSED BLADE

TEMPERATURE

DUCT MOUNTED AVERAGING

WELL MOUNTED

ELEMENT/SENSOR ELEMENT/SENSOR

ELEMENT/SENSOR ELEMENT/SENSOR

SURFACE MOUNTED

PRESSURE

DIRECT MOUNTED

ELEMENT/SENSOR

DIFFERENTIAL PRESSURE

ELEMENT/SENSOR

LEVEL

FLOAT TYPE PADDLE TYPE

LEVEL TRANSMITTER

TANK MOUNTED

SONIC OR

RADIOACTIVE

FLOW

ORIFICE PLATE

TURBINE OR

PROPELLER

TYPE

SENSOR

VORTEX

TYPE

TARGET

SENSOR TRANSMITTER

MAGNETIC

TYPE

M

TRANSIT TIME

SONIC FLOWMETER

"DOPPLER" OR

FLOW ARROW

XXX INDICATES

AIR TYPE

INSTRUMENT NAMING CONVENTION

XXX - FUNCTION ID

NNN - DEVICE NUMBER

ZZZ - USER CHOICE

CURRENT

CURRENT SENSOR/TRANSMITTER

LINE LEGEND

INTERNAL SYSTEM LINK

ELECTRICAL SIGNAL

PNEUMATIC SIGNAL

YI EQUIPMENT STATUS

YA EQUIPMENT ALARM

ZI POSITION INDICATOR

ZS POSITION SWITCH

ZC POSITION CONTROL

AAA - UNIT ASSOCIATION OR

PROCESS CODE

PROCESS CODES

TW COOLING TOWER OR CONDENSER WATER

CHW CHILLED WATER

SCHW SECONDARY CHILLED WATER

HW HOT WATER

SHW SECONDARY HOT WATER

STM STEAM

AAA-NNN

XXX

ZZZ

NT HUMIDITY TRANSMITTER

FMS SYSTEM OPERATING CONSTRAINTS

THE FMS CONTROL SYSTEM SHALL OPERATE WITHIN THE FOLLOWING SYSTEM CONSTRAINTS FOR CONTROL:

SUPPLY AIR DRYBULB TEMPERATURE

MIXED AIR DRYBULB TEMPERATURE

WATER TEMPERATURE

DUCT STATIC PRESSURE

SUPPLY/ RETURN AIR VOLUME

OUTSIDE AIR/ RELIEF AIR VOLUME

BUILDING PRESSURE

ROOM TEMPERATURE

ROOM AIR VOLUME

HUMIDITY LEVEL

WATER TEMPERATURE

WATER DIFFERENTIAL PRESSURE

+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

FT

FT

FE

FE

FEFE

L

L

L

TE

L

PD

TETE

TE

+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 1.0 PSI OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 0.5°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 0.1" W.C. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 0.01" W.C. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 1.0°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 2.5% OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 2.5% R.H. OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

+/- 1.0°F OF SETPOINT WITH HUNTING OF < 5% OF THE CONTROL SIGNAL

FIRST LETTER SUCCEEDING LETTERS (3)

MEASURING OR MODIFIER READOUT OR OUTPUT MODIFIER

INITIATING PASSIVE FUNCTION FUNCTION

ANALYSIS ALARM

B BURNER FLAME USER CHOICE USER CHOICE USER CHOICE

C CONDUCTIVITY CONTROL (13)

D DENSITY DIFFERENTIAL

E VOLTAGE SENSOR

F FLOW RATE RATIO FRACTION

G GAUGE GLASS,

H HAND HIGH

I CURRENT INDICATE

J POWER SCAN

K TIME TIME RATE OF CONTROL STATION

L LEVEL LIGHT LOW

M MOTION MOMENTARY MIDDLE

INTERMEDIATE

N HUMIDITY USER DEFINED USER DEFINED USER DEFINED

O USER CHOICE ORIFICE RESTRICTION

P PRESSURE, VACUUM POINT (TEST)

Q QUANTITY INTEGRATE,

R RADIATION RECORD

S SPEED, FREQUENCY SAFETY SWITCH

T TEMPERATURE TRANSMIT

U MULTI-VARIABLE MULTI-FUNCTION MULTI-FUNCTION MULTI-FUNCTION

V VIBRATION, MECHANICAL VALVE, DAMPER

ANALYSIS LOUVER

W WEIGHT, FORCE WELL

X UNCLASSIFIED X-AXIS UNCLASSIFIED UNCLASSIFIED UNCLASSIFIED

Y EVENT, STATE OR Y-AXIS RELAY, COMPUTE

PRESENCE CONVERT

Z POSITION Z-AXIS DRIVER, ACTUATOR

DIMENSION UNCLASSIFIED

on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

B70

A/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

1/4" = 1'-0"

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .G e n e ra l.

S h e e ts

.r v t

/5

/2

:2

:1

P

M

05/06/2022 M. Perkins G. Weaver

618-21-700

1383 - 70M-801

MECHANICAL CONTROL SYMBOL LEGEND

AND ABBREVIATIONS

1 Veterans Drive, Minneapolis, MN 55417

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

GENERAL SHEET NOTES

MECHANICAL CONTROLS GENERAL NOTES

A. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-CONSTRUCTION TAB REPORT FOR

THE EQUIPMENT AND ASSOCIATED SYSTEMS SHOWN ON THE CONSTRUCTION DOCUMENTS

AND UTILIZE ALL AVAILABLE AS-BUILT DRAWINGS FROM THE OWNER. TEST AND BALANCE

CONTRACTOR SHALL VISIT SITE PRIOR TO CONSTRUCTION AND VERIFY ALL EXISTING

EQUIPMENT AND DEVICES, AND DEVELOP THEIR TEST AND BALANCE FORMS INCLUDING

DRAWINGS SHOWING EQUIPMENT LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND TAG

NUMBERS. IF THERE ARE LOCATIONS WHERE THE DRAWINGS DO NOT REFLECT FIELD

CONDITIONS, THE TEST AND BALANCE CONTRACTOR SHALL INCLUDE THE AIRFLOW AND

WATER FLOW READINGS ON THE FORMS AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE

ON THE DRAWINGS. REFER TO SPECIFICATION SECTION 23 50 93 FOR MORE INFORMATION.

B. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED TO ESTABLISH NEW

HVAC SYSTEM PERFORMANCE AND BALANCE DATA FOR THE RENOVATION. DATA SHALL BE

FORWARDED TO THE PROJECT ENGINEER FOR REVIEW AND COMMENT PRIOR TO

COMMENCING THE DEMOLITION AND/OR NEW WORK ASSOCIATED WITH THE FACILITY

RENOVATION.

C. THE CONTRACTOR SHALL REMOVE ALL EXISTING EQUIPMENT, DUCTWORK, PIPING, CONTROL

PANELS, CONTROL DEVICES INCLUDING PNEUMATIC TUBING, AND ASSOCIATED ITEMS WHICH

ARE BEING REPLACED, IN THEIR ENTIRETY. THE CONTRACTOR IS RESPONSIBLE FOR

REMOVING ALL DEMOLISHED ITEMS FROM THE SITE. REFER TO SPECIFICATIONS FOR MORE

INFORMATION.

D. PROVIDE AIR BALANCE REPORT PRIOR TO FINAL INSPECTION.

E. ALL NEW TO EXISTING DUCT CONNECTIONS SHALL BE FIELD VERIFIED PRIOR TO ORDERING

AND FABRICATING NEW DUCTWORK OR DAMPERS.

F. ALL CONTROL WIRING SHALL BE ROUTED IN CONDUIT TO EACH CONTROL DEVICE.

G. AS-BUILT NOTE: THE BUILDING'S VERTICAL STRUCTURE AND GRID LAYOUT IS SHOWN BASED

ON RECORD DOCUMENTS AND / OR LASER SCANS OF THE AREA. COLUMNS MAY BE OFFSET

FROM GRID LINES WITHOUT AN IDENTIFYING GRID LINE AND ALL GRID LINES MAY NOT HOST

COLUMNS ON ALL LEVELS.

H. CONTRACTOR TO PERFORM MECHANICAL EQUIPMENT REPLACEMENT DURING NIGHTS AND

WEEKENDS TO MITIGATE FACILITY DOWNTIME. ALL OUTAGES MUST BE SCHEDULED WITH AND

APPROVED BY THE VA. FACILITY HOURS OF OPERATION ARE 7:00 AM TO 4:00 PM.

1. EQUIPMENT CONTROLLERS SHALL CONTAIN COMPLETE CONTROL LOGIC, INCLUDING ALL I/O

POINTS TO PROVIDE STAND-ALONE CONTROL IN THE EVENT OF COMMUNICATION FAILURE.

2. ALL EQUIPMENT CONTROL HARDWARE SHALL USE BACNET PROTOCOL BETWEEN THE OPERATOR

WORKSTATION, WEBSERVER AND FOR COMMUNICATIONS BETWEEN CONTROLLERS.

3. ALL EQUIPMENT CONTROL HARDWARE SHALL CONFORM TO APPLICABLE BACNET DEVICE

PROFILES AND SHALL BE LISTED BY THE BACNET TESTING LABORATORIES.

4. THE MECHANICAL CONTROL SYSTEM SOFTWARE SHALL INCLUDE A GRAPHICAL USER INTERFACE WITH POINT AND CLICK NAVIGATION THAT ALLOWS THE OPERATOR TO ADJUST PROPERTIES, SET

POINTS AND ALARMS.

5. GRAPHICAL USER INTERFACE SHALL PROVIDE AT LEAST ONE GRAPHIC FOR EACH PIECE OF

EQUIPMENT AND ZONE. GRAPHICAL USER INTERFACE SHALL USE DYNAMIC COLORS TO

REPRESENT EACH ZONE'S TEMPERATURE RELATIVE TO ITS SETPOINT.

6. CONTROL SYSTEM SHALL INCLUDE AN ENERGY REPORTING TOOL AND SCHEDULING

FUNCTIONALITY.

7. CONTRACTOR SHALL PROVIDE ALL THE TOOLS AND FUNCTIONALITY NECESSARY FOR THE

OPERATOR TO MAINTAIN AND ADJUST THE SYSTEM, INCLUDING: CONFIGURING THE DATABASE;

DOWNLOADING MEMORY TO THE CONTROLLERS; ADD, DELETE AND CONTROL PRIVILEGES FOR

EACH OPERATOR; CONFIGURE ALARMS, ALARM MESSAGES, AND ALARM REACTIONS; CONFIGURE

TRENDS INCLUDING SETTING THE INTERVAL RANGE OR CHANGE VALUE INCREMENT THAT

CAUSES A TREND SAMPLE TO BE RECORDED; CONFIGURE AND RUN STANDARD REPORTS TO

SHOW POINT STATUS, ALARM STATUS, LOCKED POINTS, AND OPERATOR ACTIVITY; CREATE AND

EDIT SYSTEM GRAPHICS AND TO DISPLAY DYNAMIC SYSTEM DATA ON THE GRAPHICS; AND

CREATE AND EDIT CUSTOM CONTROL PROGRAMS AND DOWNLOAD THESE PROGRAMS TO EACH

CONTROLLER.

8. SYSTEM SECURITY SHALL ALLOW AN AUTHORIZED USER TO CONTROL PRIVILEGES ASSOCIATED WITH EACH OPERATOR INCLUDING THE ABILITY TO VARY AND REGULATE ACCESS TO INDIVIDUAL

PIECES OF EQUIPMENT.

Run Conditions - Continuous:

The unit shall run continuously.

Continuous Mode: The unit shall maintain

• A 75°F (adj.) cooling setpoint

• A 70°F (adj.) heating setpoint.

Alarms shall be provided as follows:

• High Zone Temp: If the zone temperature is greater than the cooling setpoint by a user definable amount (adj.).

• Low Zone Temp: If the zone temperature is less than the heating setpoint by a user definable amount (adj.).

Zone Setpoint Adjust:

The occupant shall be able to adjust the zone temperature heating and cooling setpoints at the zone sensor.

Fan:

The fan shall run anytime the unit is commanded to run, unless shutdown on safeties. The fan speeds shall automatically be indexed as follows:

• Low speed shall run anytime the zone temperature is within setpoints.

• Medium speed shall run anytime the zone temperature is outside of setpoints.

• High speed shall run anytime the zone temperature is outside of setpoints by a definable amount

(adj.).

Cooling Coil Valve:

The controller shall measure the zone temperature and modulate the cooling coil valve to maintain its cooling setpoint.

The cooling shall be enabled whenever:

• The zone temperature is above cooling setpoint.

• AND the fan is on.

Fan Status:

The controller shall monitor the fan status.

Alarms shall be provided as follows:

• Fan Failure: Commanded on, but the status is off.

• Fan in Hand: Commanded off, but the status is on.

• Fan Runtime Exceeded: Fan status runtime exceeds a user definable limit (adj.).

Primary cooling shall be house air and dedicated fan coil unit shall provide cooling on call for additional cooling with an increase in room temperature.

FCU-01

TCV

TCV

FCU-01

CHWS

CHWR

(AO)V

A

L V

E

C O

O L

IN

G C

O

IL

POWER

CONTROL

N.O.

FCU-01

HS

(DO)

FCU-01

HS

(DO)

FCU-01

HS

(DO) F

A

N

L O

W S

P E

E D

F A

N

M E

D

IU

M S

P E

E D

F A

N

H

IG

H S

P E

E D

FCU-01

TIT

(AI)

FCU-01

TIT

(AI)

FCU-01

TS

(DI)

ZONE - OVERRIDE

ZONE - TEMPERATURE

ZONE - SETPOINT

R.A.

S.A.

FCU - SEQUENCES OF OPERATION

M

PDS

PDT

CHW-01

CHW-01

PDI

PDT

CHW-02

PDT

CHW-03

PDT

CHW-04

PDT

CHW-05

CHW-02

PDI

CHW-03

PDI

CHW-04

PDI

CHW-05

PDI

DIFFERENTIAL PRESSURE

SENSOR/TRANSMITTER LOCATED AT NEW

RISER. SEE SHEET M-600 FOR LOCATION.

(AI)D

IF

F E

R E

N T

IA

L P

R E

S S

U R

E

DIFFERENTIAL PRESSURE

SENSOR/TRANSMITTER LOCATED AT NEW

RISER. SEE SHEET M-600 FOR LOCATION.

DIFFERENTIAL PRESSURE

SENSOR/TRANSMITTER LOCATED AT NEW

RISER. SEE SHEET M-600 FOR LOCATION.

DIFFERENTIAL PRESSURE

SENSOR/TRANSMITTER LOCATED AT NEW

RISER. SEE SHEET M-600 FOR LOCATION.

DIFFERENTIAL PRESSURE

SENSOR/TRANSMITTER LOCATED AT

NEW RISER. SEE SHEET M-600 FOR

LOCATION.

(AI)D

IF

F E

R E

N T

IA

L P

R E

S S

U R

E

(AI)D

IF

F E

R E

N T

IA

L P

R E

S S

U R

E

(AI)D

IF

F E

R E

N T

IA

L P

R E

S S

U R

E

(AI)D

IF

F E

R E

N T

IA

L P

R E

S S

U R

E

CHS

CHR

CHS

CHR

CHS

CHR

CHS

CHR

CHS

CHR

PDT

CHW-06

CHS

CHR

CHW-06

PDI

(AI)D

IF

F E

R E

N T

IA

L P

R E

S S

U R

E

DIFFERENTIAL PRESSURE

SENSOR/TRANSMITTER

LOCATED AT NEW RISER. SEE

SHEET M-600 FOR LOCATION.

on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

B70

A/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

1/4" = 1'-0"

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .G e n e ra l.

S h e e ts

.r v t

/5

/2

:2

:2

P

M

05/06/2022 M. Perkins K. Luke

618-21-700

1383 - 70M-802

MECHANICAL CONTROL DIAGRAMS

1 Veterans Drive, Minneapolis, MN 55417

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

SCALE: 1/4" = 1'-0"

D1

FAN COIL UNIT CONTROL B70

CHILLED WATER SYSTEM DIFFERENTIAL PRESSURE SETPOINT

THE ECC SHALL RESET THE SYSTEM DIFFERENTIAL PRESSURE SETPOINT FOR

EACH OF THE SIX DIFFERENTAIL PRESSURE SENSORS USING A TRIM AND

RESPOND LOGIC WITHIN THE RANGE OF 5 PSIG TO 20 PSIG ONCE THE MAXIMUM

CHILLED WATER TEMPERATURE SETPOINT IS REACHED. ONCE THE TEMPERATURE

SETPOINT IS REACHED, THE DIFFERENTIAL PRESSURE SETPOINT FOR EACH OF

THE FIVE ZONES SHALL BE RESET BASED ON THE VALVE POSITIONS IN EACH

ZONE. EACH DIFFERENTAIL PRESSURE SETPOINT SHALL BE TRIMMED BY 0.1 PSIG

EVERY TWO MINUTES UNTIL A VALVE IN EACH DIFFERENTIAL PRESSURE ZONE IS

50% OPEN. WHEN A VALVE IN THE ZONE RISES TO 80% OPEN, THE DIFFERENTIAL

PRESSURE SETPOINT SHALL BE INCREASED BY 0.1 PSIG EVERY TWO MINUTES.

ALL SETPOINTS SHALL BE ADJUSTABLE THROUGH THE OPERATOR WORKSTATION

FOR EACH DIFFERENTIAL PRESSURE SENSOR. THE PUMPS SHALL BE

CONTROLLED TO THE DIFFERENTIAL PRESSURE SENSOR WHICH IS FURTHEST

BELOW SETPOINT.

SCALE: 1/4" = 1'-0"

D6

Control Diagram DPT ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

B70

A/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .G e n e ra l.

S h e e ts

.r v t

/5

/2

:2

:2

P

M

05/06/2022 M. Perkins G. Weaver

618-21-700

1383 - 70M-901

MECHANICAL CUTSHEETS & BASIS OF

DESIGN

1 Veterans Drive, Minneapolis, MN 55417

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

B70

A/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .G e n e ra l.

S h e e ts

.r v t

/5

/2

:2

:3

P

M

05/06/2022 M. Perkins G. Weaver

618-21-700

1383 - 70M-902

MECHANICAL CUTSHEETS & BASIS OF

DESIGN

1 Veterans Drive, Minneapolis, MN 55417

EHRM INFRASTRUCTURE

ELECTRICAL ABBREVIATIONS

J J

J

M

V

SP

R

GB

VFD

LCP

LRP

AFB

NCC

MS

1P

2P

E

DS

SS

B

MO

FBX

ET

M

M

C

DTDT

A-1

PH

D

P

K a

L

OS

R

B

CB

MD

MD

SP

VP

TV

XX

DC

C

DM

R/D

DGP

RX

ELM

DO

AC

K

AC

E

K

ATS

TBB

T

TMH

EMH

EHH

X

PSD

EMU

FB

UG

GB

G

PB

SR-X

6-30R

UPS

CT

DOOR CONTACT SWITCH

ACCESS FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)

FLOOR BOX ("X" DENOTES TYPE AS SPECIFIED)

CONTACTOR

VARIABLE FREQUENCY DRIVE/VARIABLE FREQUENCY MOTOR CONTROLLER

MANUAL MOTOR STARTER WITH PILOT LIGHT AS INDICATED.

PUSHBUTTON STATION

CCTV SURVEILLANCE CAMERA OUTLET - WALL MTD, UON

DOOR MONITOR SWITCH

RECEIVER/DRIVER UNIT

NURSE CALL CONTROL EQUIPMENT PANEL (RECESSED/SURFACE)

NURSE CALL EMERGENCY STATION - PULL CORD TYPE IN

TOILETS & SHOWERS, PUSH-BUTTON TYPE IN ALL OTHER

PLACES

NURSE CALL BEDSIDE STATION, DOUBLE PATIENT

NURSE CALL BEDSIDE STATION, SINGLE PATIENT

NURSE CALL MASTER STATION

GLASS BREAK DETECTOR

NURSE CALL DOME LIGHT

PATIENT MONITORING OUTLET

CODE BLUE CALL STATION

NURSE CALL STAFF STATION

NURSE CALL DUTY STATION

LIGHTING FIXTURE TYPE DESIGNATION - "XX" INDICATES SPECIFIC TYPE

EXIT LIGHT - WALL/CEILING MOUNTED - DIRECTIONAL

ARROWS AS INDICATED SHADING INDICATES ILLUMINATED

FACE

LIGHTING TRACK - "X" DENOTES TYPE

UTILITY LIGHTING FIXTURE - TYPE AS INDICATED

WALL MOUNTED LIGHTING FIXTURE- TYPE AS INDICATED

SITE LIGHTING FIXTURE TYPE AS INDICATED

LIGHTING FIXTURE - TYPE AS INDICATED (SUBSCRIPT INDICATES SWITCH CONTROL)

JUNCTION BOX - CEILING OR WALL MOUNTED - INDICATED IN POWER, LIGHTING & FIRE

ALARM SYSTEMS PLANS.

DIRECT CONNECTION TO EQUIPMENT

SINGLE POLE SWITCH (SUBSCRIPT INDICATES FIXTURES CONTROLLED)

DIMMER SWITCH

SINGLE OR DOUBLE, REMOTE EMERGENCY LIGHTING FIXTURE

THREE-WAY SWITCH (S3P-THREE-WAY SWITCH WITH PILOT LIGHT)

KEY OPERATED SWITCH

SINGLE POLE SWITCH WITH PILOT LIGHT

FOUR - WAY SWITCH

FUSED SWITCH

DELTA CONNECTION

CPT

PASSIVE INFRARED/ULTRASONIC OCCUPANCY SENSOR (WALL/CEILING)

ELECTRIC INTERLOCK SYSTEM

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

POTENTIAL TRANSFORMER

PHOTO CELL

KEY INTERLOCKING SYSTEM

WYE CONNECTION - SOLID GROUND

SWITCH - SINGLE THROW

TELECOMMUNICATIONS BACKBOARD

MOTOR CONTROL CENTER

TELEPHONE MANHOLE

ELECTRIC MANHOLE

FUSE

BUS DUCT PLUG-IN UNIT

GROUND

AUTOMATIC TRANSFER SWITCH

DRAWOUT TYPE, CIRCUIT BREAKER

STATIONARY CIRCUIT BREAKER

DISCONNECT SWITCH, FUSED.

PROVIDE SWITCH AND FUSE AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY,

UON

GROUND ROD

DISCONNECT SWITCH, NON-FUSED

PROVIDE SWITCH AMPACITY EQUAL TO OR GREATER THAN FEEDER AMPACITY, UON

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, FLOOR MTD SERVICE FITTING,

SURFACE TYPE ("F" DENOTES FLUSH TYPE, "P" DENOTES POKE THRU TYPE)

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, WALL MTD.

(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

TRANSFORMER - TYPE AND RATING AS INDICATED

COMBINATION MOTOR STARTER WITH DISCONNECT SWITCH.

PROVIDE SWITCH AND FUSE AMPACITY EQUAL TO OR GREATER THAN FEEDER

AMPACITY, UON

PANELBOARD - (FLUSH/SURFACE)

DISTRIBUTION PANELBOARD

ELECTRIC HANDHOLE

LIGHTING CONTROL PANEL, SURFACE MTD. UON.

LOW VOLTAGE LIGHTING RELAY PANEL, SURFACE MTD. UON

UNINTERRUPTIBLE POWER SUPPLY

SHADING INDICATES FIXTURE [CONNECTED TO CRITICAL BRANCH]

[CONNECTED TO GENERATOR CIRCUIT (SWITCHED)]

[W/FLUORESCENT BATTERY/INVERTER UNIT (SWITCHED)]

SHADING INDICATES FIXTURE [CONNECTED TO LIFE SAFETY BRANCH

(UNSWITCHED)] [W/FLUORESCENT BATTERY/INVERTER UNIT (UNSWITCHED)]

a

LOW VOLTAGE SWITCH

JUNCTION BOX - FLOOR MOUNTED

TELECOMMUNICATIONS COMBINATION VOICE/DATA OUTLET, CEILING MTD SERVICE

FITTING,

SURFACE TYPE ("F" DENOTES FLUSH TYPE)

MOTOR AND CONNECTION

EMERGENCY POWER OFF

REQUEST-FOR-EXIT SENSOR

ELECTRIC LOCKING/LATCHING AND MONITORING HARDWARE

ACCESS CONTROL STATION - KEYPAD TYPE

ACCESS CONTROL STATION - CARD TYPE

DOOR OPERATING EQUIPMENT

DATA GATHERING PANEL

NURSE CALL DOME LIGHT CEILING MTD

("Z" SUBSCRIPT DENOTES ZONE DOME LIGHT)

CODE BLUE WITH RED PHONE, WALL MTD, MOUNTED 48" AFF

CODE BLUE WITH BLUE LIGHT, WALL MTD, MOUNTED 48" AFF

MOTION DETECTOR - CEILING MTD

MOTION DETECTOR - WALL MTD

POWER SUPPLY FOR DOOR(S) WITH ELECTRICAL HARDWARE

CEILING MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.

SPECIAL PURPOSE RECEPTACLE. TYPE AS INDICATED ON DRAWINGS.

COORDINATE RECEPTACLE TYPE WITH ACTUAL EQUIPMENT PRIOR TO INSTALLATION.

SWITCHED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.

EMERGENCY DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W.

FLOOR MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,

2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON

FACEPLATE.

FLOOR MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX

RECEPTACLES WITH A COMMON FACEPLATE.

FLOOR MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

FLOOR MOUNTED DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. PROVIDE CORE

DRILL PACKAGE TO MAINTAIN FIRE RATING OF FLOOR. EXTEND CONDUIT

AND WIRING IN CEILING SPACE OF FLOOR BELOW TO ELECTRICAL CLOSET

OR PANELBOARD.

FLOOR MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V,

2P, 3W, DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON FACEPLATE.

FLOOR MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

CEILING MOUNTED SINGLE RECEPTACLE, 20A, 125V, 2P, 3W.

SINGLE ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P,

3W. (SLASH INDICATES MOUNTING ABOVE FINISH

COUNTER)

QUADRUPLEX ISOLATED GROUND RECEPTACLE, (2)20A, 125V, 2P, 3W,

DUPLEX ISOLATED GROUND RECEPTACLES WITH A COMMON

FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

DUPLEX ISOLATED GROUND RECEPTACLE, 20A, 125V, 2P, 3W.

(SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

SINGLE RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

RECEPTACLES MOUNTED ABOVE THE CEILING.

QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX RECEPTACLES

WITH A COMMON FACEPLATE. (SLASH INDICATES MOUNTING ABOVE FINISH

COUNTER)

CEILING MOUNTED QUADRUPLEX RECEPTACLE, (2)20A, 125V, 2P, 3W, DUPLEX

RECEPTACLES WITH A COMMON FACEPLATE.

GFI, DUPLEX RECEPTACLE, 20A, 125V, 2P, 3W. (SLASH INDICATES MOUNTING ABOVE FINISH COUNTER)

ELECTRONIC METERING UNIT

GROUND BUS

GROUND CABLE, SIZE AS INDICATED

PLUG-IN BUSWAY

FEEDER BUSWAY

UNDERGROUND CONDUIT/DUCTBANK

CABLE TRAY

CONDUIT TURNED DOWN

CONDUIT TURNED UP

CONDUIT CAST IN CONCRETE OR BELOW SLAB

CONDUIT RUN CONCEALED IN FINISHED AREAS, EXPOSED IN UNFINISHED

AREAS OR BELOW ACCESS FLOORS

HOMERUN TO PANEL WITH CIRCUIT NUMBER(S) AS INDICATED

TELECOMMUNICATIONS DATA OUTLET ABOVE CEILING

COMBINATION TV OUTLET AND DUPLEX RECEPTACLE ON SINGLE

FACEPLATE

SPEAKER - WALL MTD

PA VOLUME CONTROL

MICROPHONE OUTLET - CEILING MTD

MICROPHONE OUTLET - WALL MTD

MICROPHONE OUTLET - FLOOR MTD

SPEAKER - CEILING MTD

RECORDING OUTLET

COMBINATION VIDEO PROJECTOR OUTLET AND DUPLEX RECEPTACLE

CLOCK OUTLET, W/RECPT AND HANGER

CLOCK OUTLET, MASTER CLOCK

CLOCK OUTLET, ELAPSED TIME

GENERATORG

SURFACE RACEWAY ("X" DENOTES TYPE AS SPECIFIED)

WALLWASH LIGHT FIXTURE,

DEMOLITION WORK

OCCUPANCY SENSOR WALL SWITCH

M

HC ADA PUSH BUTTON.

ELECTRICAL LIGHTING SYMBOLS ELECTRICAL POWER SYMBOLS GENERAL NOTES

A INTERCOMMUNICATION SYSTEM ( AI PHONE)

A B C A B C

P P

PD PD

D D

POWER SERVICE FITTING (FLOOR/WALL) MOUNTED FOR CONNECTION TO FURNITURE

SYSTEM AS SPECIFIED.

COMBINATION POWER AND TELECOMMUNICATIONS FLOOR OR WALL MOUNTED BOX FOR

POWER AND DATA CONNECTION - INDICATED IN POWER & SPECIAL SYSTEMS PLANS.

JUNCTION BOX FLOOR OR WALL MOUNTED FOR CONNECTION TO FURNITURE SYSTEM

MOUNTING HEIGHT NOTES:

1. ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE, UNLESS OTHERWISE NOTED.

2. REFER TO EQUIPMENT ELEVATION DRAWINGS FOR COORDINATION WITH

CASEWORK.

3. MOUNT MANUAL MOTOR STARTER ADJACENT TO OR ON UNIT.

4. REFER TO ARCHITECTURAL A0 SERIES FOR ADDITIONAL ELECTRICAL DEVICE

MOUNTING HEIGHTS AND DEVICE ALIGNMENT RULES.

WALL SWITCHES

RECEPTACLES

TELECOMMUNICATIONS OUTLETS

TELECOMMUNICATIONS OUTLETS - WALL PHONE

CLOCK OUTLETS

TV OUTLETS

PUSHBUTTONS

VOLUME CONTROLS

NURSE CALL STATIONS

NURSE CALL DOME LIGHTS

DIMMERS

ACCESS CONTROL DEVICES

VANITY LIGHT IN TOILET

INTERCOM

FIREMAN'S PHONE

FIRE ALARM - PULL STATIONS

FIRE ALARM DEVICES HORN/SPEAKERS/STROBES

(MOUNTING HEIGHT AT THE TOP OF THE FIRE ALARM DEVICE OR

6" BELOW CEILING WHICH IS LOWER)

4'-0" AFF

1'-6" AFF

1'-6" AFF

4'-0" AFF

7'-0" AFF

1'-6" AFF

4'-0" AFF

4'-0" AFF

4'-0" AFF

7'-6" AFF

4'-0" AFF

4'-0" AFF

6" ABOVE THE MIRROR, UON

4'-0" AFF

4'-0" AFF

4'-0" AFF

7'-2" AFF TO TOP

PROVIDE 1#12 + 1#12N + 1#12G FOR 20A BRANCH CIRCUITING, UON; MAXIMUM OF

THREE CIRCUITS PER CONDUIT; MINIMUM CONDUIT SIZE OF 3/4" C, UON.

PROVIDE A DEDICATED NEUTRAL WIRE FOR EACH BRANCH CIRCUIT.

COORDINATE DEVICE LOCATIONS AND MOUNTING HEIGHTS WITH ARCHITECTURAL

DRAWINGS PRIOR TO ROUGH-IN.

PROVIDE FIRE STOPPING FOR CONDUITS AND ELECTRICAL EQUIPMENT FOR FLOOR

SLABS, WALLS AND CEILINGS TO MAINTAIN FIRE RATING.

INSTALL ELECTRICAL WORK IN ACCORDANCE WITH THE NATIONAL ELECTRICAL

CODE AND LOCAL BUILDING AND FIRE CODES, IN A NEAT AND WORKMANLIKE

MANNER.

LIMIT VOLTAGE DROP TO 2% FOR FEEDERS AND 3% FOR BRANCH CIRCUITS. INCLUDE

DERATING FACTOR FOR ROOF-MOUNTED CONDUITS.

REFER TO ARCH. REFLECTED CEILING PLANS FOR EXACT LOCATION OF CEILING

MOUNTED DEVICES AND LIGHT FIXTURES, UNLESS OTHERWISE INDICATED.

WHERE MULTIPLE SWITCHES, RECEPTACLES, AND OTHER OUTLETS (EXCEPT WALL

PHONES) ARE INDICATED PROVIDE MULTI-GANG BACK BOXES WITH GANG BARRIERS

AND A COMMON FACEPLATE.

WHERE DIFFERENT RECESSED ELECTRICAL DEVICES WITH THE SAME MOUNTING

HEIGHTS ARE INDICATED SIDE-BY-SIDE, MOUNT THE DEVICES SO THAT THERE IS

FOUR INCHES BETWEEN ADJACENT VERTICAL EDGES OF THE FACEPLATES, UON.

WHERE UPDATE TO TECHNOLOGY (LOW VOLTAGE/SIGNAL) ARE LOCATED IN THE

SAME AREA ALIGN DEVICES VERTICALLY THROUGH THEIR CENTERLINES, UON.

WHERE EXIT SIGNS ARE INDICATED ABOVE DOOR MOUNT AS FOLLOWS, CENTER THE

EXIT SIGN BETWEEN TOP OF DOOR FRAME AND CEILING IF DISTANCE BETWEEN TOP

OF DOOR FRAME AND CEILING IS 24 INCHES OR LESS; OTHERWISE MOUNT BOTTOM

OF EXIT SIGN 6 INCHES FROM TOP OF DOOR FRAME, MOUNT OTHER WALL MOUNTED

EXIT SIGNS IN THE SAME AREA AT THE SAME HEIGHT. COORDINATE WITH

ARCHITECTURAL DETAILS.

EXIT SIGNS ARE TO BE TYPE "X1", UON.

PROVIDE SEPARATE NEUTRALS FOR DIMMING CIRCUITS.

PROVIDE FEEDERS AND BRANCH CIRCUITS WHICH HAVE AN AMPACITY EQUAL TO OR

GREATER THAN THE CIRCUIT OVERCURRENT PROTECTIVE DEVICE RATING, U.O.N.

FURNITURE LAYOUTS ARE FOR REFERENCE ONLY. COORDINATE THE FINAL

LOCATION OF ELECTRICAL DEVICES AND OUTLETS WITH ARCHITECT, COR AND FINAL

FURNITURE PLANS PRIOR TO INSTALLATION.

MOUNT DEVICES FLUSH WITH CONCEALED CONDUIT, EXCEPT AS NOTED ON THE

DRAWINGS AND IN MECHANICAL AND ELECTRICAL EQUIPMENT ROOMS.

THE DRAWINGS REPRESENT ELECTRICAL DESIGN INTENT. THEY ARE DIAGRAMMATIC.

PROVIDE ALL COMPONENTS NECESSARY FOR COMPLETE OPERATING ELECTRICAL

SYSTEMS.

WHEN MORE THAN ONE 20A., 1P., 120 VOLT CIRCUIT FEEDS A SURFACE RACEWAY

CONNECT RECEPTACLES TO ALTERNATE CIRCUITS AS FOLLOWS - U.O.N.

A.

B.

C.

D.

E.

F.

G.

H.

J.

K.

L.

M.

N.

O.

P.

Q.

R.

ELTD EMERGENCY LIGHTING TRANSFER DEVICE

SECURITY SYSTEM SYMBOLS

TELECOMMUNICATION SYMBOLS

NURSE CALL SYSTEM SYMBOLS

MOUNTING HEIGHTS

ELECTRICAL EQUIPMENT SYMBOLS

ELECTRICAL WIRING SYMBOLS

DISTRIBUTION AND DIAGRAM SYMBOLS

REFERENCE SYMBOLS

SECTION NUMBER

DETAIL NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING NUMBER WHERE DRAWN

E1-1.0

KEY NOTE

1 DEMO KEY NOTE

SPECIAL SYSTEM OUTLET SYMBOLS

CB

E1-1.0

DISCONNECT SWITCHES

MOTOR STARTERS

PANELBOARDS & CABINETS

INDIVIDUAL CIRCUIT BREAKERS

5'-6" AFF

5'-6" AFF

6'-0" AFF TO TOP

5'-6" AFF

x

WAP WIRELESS ACCESS POINT, CEILING MOUNTED

NOTE: NOT ALL ABBREVIATIONS AND

SYMBOLS APPLY TO THIS PROJECT.

SPST

SWBD

SYM

STD

SW

SPEC(S)

SPDT

SPKR

SF

SEC

SINGLE POLE SINGLE THROW

SINGLE POLE DOUBLE THROW

SYMMETRICAL

SWITCHBOARD

STANDARD

SWITCH

SECONDARY

SQUARE FOOT

SPECIFICATION(S)

SPEAKER

PRI

RCLP

RM

SCH, SCHED

RP

REF

RCPT

RSC

RLA

RF

R, RE

QTY

PWR

PT

PVC

PA

PH, ∅

PF

PNL

PE

PB

P

OPP

OHE/T

OH

OFOI

OFCI

NO., NUM, #

OC

NTS

AMERICAN WIRE GAUGE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTOMATIC TRANSFER SWITCH

AMPERE INTERRUPTING CAPACITY

ALTERNATING CURRENT

ABOVE FINISHED COUNTER

AWG

BLDG

BRKR, BKR

BUILDING

BREAKER

AUTO

AUX

ARCH

AT

ATS

ALT

AFG

AIC

AFC

AFF

AC

AF

AUXILIARY

ALTERNATE

ARCHITECT

AUTOMATIC

AMPERES TRIP

AMPERE FRAME (BREAKER RATING)

MTG

NC

NEMA

NO

NIC

NEC

N

MV

MH

MOCP

MTD

MLO

MIN

MISC

MECH

MCC

MFR

MCA

MCB

RIGID STEEL CONDUIT

RATED (RUNNING) LOAD AMPS

RECEPTACLE PANELBOARD

ROOM

SCHEDULE

RADIO FREQUENCY

RECEPTACLE

REFRIGERATOR

RELOCATE AS SHOWN

POTENTIAL TRANSFORMER

POLYVINYL CHLORIDE

REMOTE CONTROL LIGHTING PANEL

QUANTITY

POWER

PUBLIC ADDRESS

PANEL

PRIMARY

PULL BOX

POWER FACTOR

PHOTO ELECTRIC

PHASE

POLE

OPPOSITE

OWNER FURNISHED, CONTRACTOR INSTALLED

OWNER FURNISHED, OWNER INSTALLED

OVERHEAD ELECTRIC/TELEPHONE

OVERHEAD

ON CENTER

NOT TO SCALE

NUMBER

MOUNTING

NATIONAL ELECTRICAL CODE

MEDIUM VOLTAGE (OVER 600V LESS THAN 35KV)

NORMALLY CLOSED

NORMALLY OPEN

NOT IN CONTRACT

NEUTRAL

MINIMUM CIRCUIT AMPACITY

MAIN CIRCUIT BREAKER

MOTOR CONTROL CENTER

MAXIMUM OVERCURRENT PROTECTION

MOUNTED

MISCELLANEOUS

MAIN LUGS ONLY

MINIMUM

MANHOLE

MANUFACTURER

MECHANICAL

SWGR SWITCHGEAR

AIR HANDLING UNITAHU

MTS MANUAL TRANSFER SWITCH

PDP POWER DISTRIBUTION PANEL

AMPERESAMP

OCPD OVERCURRENT PROTECTION DEVICE

A M

B N

O

P

Q

R

S

T

SPD SURGE PROTECTIVE DEVICE

OD OUTLET DESIGNATOR

LOW VOLTAGE (BELOW 50 VOLTS)

L-L

L-N

LTG

LV

LIGHTING

LINE TO LINE

LINE TO NEUTRAL

1000 CIRCULAR mils

KILOVOLTS (THOUSAND VOLTS)

KILOWATTS (THOUSAND WATTS)

LIGHTNING ARRESTOR

LOCAL AREA NETWORK

KILOVOLTS-AMPERES (THOUSAND VOLT-AMPS)

ISOLATED GROUND

KWH

LAN

LA

KW

KVA

Kcmil

KV

KILOWATT-HOURS

INCAND

KEY INTERLOCK

JUNCTION BOX

INCH/INCHES (")

INCANDESCENT

GROUND FAULT INTERRUPTER

HAND-OFF-AUTOMATIC

HIGH PRESSURE SODIUM

HEATING VENTILATION AND AIR CONDITIONING

HERTZ

HVAC

HZ

HTR

HR

HT

HPS

HOA

HP

HEATER

HEIGHT

HORSEPOWER

HOUR

GFI

G, GND, GRD

GEN

FLUOR

FL, FLR

GROUND

GENERATOR

FOOT/FEET (')

FLUORESCENT

FLOOR

CATV

ELECTRIC WATER COOLER

ELECTRIC WATER HEATER

FIRE ALARM ANNUNCIATOR PANEL

ELECTRIC, ELECTRICAL

ELECTRIC METALLIC CONDUIT

EQUIPMENT GROUND

EWC

FAAP

FLA

FDR

EWH

FA

FULL LOAD AMPS

FEEDER

FIRE ALARM

FUSE

ELEC

EQ, EQUIP

EM, EMERG

EMT

ELEV

ENCL

EG

EQUIPMENT

ELEVATOR

EMERGENCY

ENCLOSURE

DISTRIBUTION PANEL

DOUBLE POLE SINGLE THROW

DOUBLE POLE DOUBLE THROW

CONTROL POWER TRANSFORMER

CURRENT TRANSFORMER

DPDT

DWG

DPST

DIST

DISC

DC

DP

DN

DRAWING

DISTRIBUTION

DIRECT CURRENT

DISCONNECT

DOWN

CPT

CU

CT

COM, COMM

CKT

CLG

COPPER

COMMUNICATIONS

CIRCUIT

CEILING

CABLE TELEVISION

CB CIRCUIT BREAKER

CONDUIT

FIRE ALARM CONTROL PANELFACP

FIRE ALARM EXTENDER PANELFAEP

CCTV CLOSED CIRCUIT TELEVISION

CP CONTROL PANEL

FLEX FLEXIBLE

HAND HOLEHH

LIGHTING CONTROL PANELLC, LCP

LIGHTING PANEL

L-G LINE TO GROUND

C

F

EXISTINGE, EX, EXIST

FT

IN

IG

JB, JBOX

K

LP

FOOT CANDLEFC

DIV DIVISION

C

D

E

F

G

H

I

J

K

L

HORIZONTAL MOUNTINGH

COR CONTRACTING OFFICER'S REPRESENTATIVE

X

XFMR

WP

WHM

W/

W/O

W

VFD

VA

V

UPS

UL

UON

UG

UGS

UGT

UGP

TYP

TV

TP

TEL,TELE

TELECOM

TC

TRANSFORMER

REMOVE DEVICE

WATT HOUR METER

WEATHERPROOF

VOLTS

VARIABLE FREQUENCY DRIVE/

VARIABLE FREQUENCY MOTOR

CONTROLLER

WITHOUT

WITH

WIRE

VOLT-AMPERES

UNDERGROUND PRIMARY

UNDERGROUND SECONDARY

UNDERGROUND TELEPHONE

UNDERWRITER'S LABORATORY

UNLESS OTHERWISE NOTED

UNINTERRUPTIBLE POWER SUPPLY

UNDERGROUND

TELECOMMUNICATIONS

TYPICAL

TELEVISION

TAMPERPROOF

TIME CLOCK

TELEPHONE

TB TERMINAL BLOCK

TBB TELEPHONE BACKBOARD

U

V

W

X

Z

TPST TRIPLE POLE SINGLE THROW

FDS FORWARD DEPLOYED SERVICES

JOINT SECURITY ARCHITECTUREJSA

PIV PERSONAL IDENTITY VERIFICATION

CEILING MOUNTED DUPLEX RECEPTACLE, 208V.

on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

B70

A/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

1 : 1

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .G e n e ra l.

S h e e ts

.r v t

/5

/2

:1

:0

P

M

05/06/2022 K. Kaiser R. Andres

618-21-700

1383 - 70E-001

ELECTRICAL ABBREVIATIONS AND SYMBOLS

1 Veterans Drive, Minneapolis, MN 55417

EHRM INFRASTRUCTURE

OS

CR

E

SRXDC

PARTITION RATING GRAPHICS:

2 HR FIRE SHAFT

1 HR SMOKE BARRIER

SMOKE PARTITION (NON RATED)

NON RATED

PARTITION RATING GRAPHIC DESIGNATION:

PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND

SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.

CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.

1 HR INCIDENTAL USE

BT-109BT-109

CB-3CB-3

BU-101BU-101BU-102BU-102

BU-103BU-103

TELECOM

ROOM

(GREEN-STACK)

BU-107ABU-107A

BU-105BU-105

BU-106BU-106

BU-107BU-107

BU-108BU-108

BU-109BU-109

BU-110BU-110

BU-111BU-111 BU-112BU-112 BU-113BU-113 BU-114BU-114

CB-4ACB-4A

CB-1CB-1

CB-2CB-2

CB-4CB-4

CB-6CB-6

BU-116BU-116

BU-117BU-117

BU-118BU-118

BU-119BU-119BU-120BU-120

BU-121BU-121

BU-122BU-122 BU-123BU-123

CC

BU-110BBU-110B

BU-110CBU-110C BU-110DBU-110D

BU-110EBU-110E

BU-118ABU-118A

BU-118BBU-118B

BU-118CBU-118C

BU-118DBU-118D

BU-122ABU-122A

CB-10CB-10

CB-11CB-11

CB-13CB-13

CB-14CB-14

CB-15CB-15

BD-101BD-101

TELECOM

ROOM

BD-101ABD-101A

ELECTRICAL

ROOM

BD-101BBD-101B

ELECTRICAL

ROOM

BD-101CBD-101C

TELECOM

ROOM

BD-101DBD-101D

TELECOM

ROOM

BD-101EBD-101E

ELECTRICAL

ROOM

BD-101FBD-101F

BD-101GBD-101G

BD-135BD-135BD-102BD-102

BD-103BD-103

BB-128BB-128

BB-129BB-129

BB-144BB-144

BB-145BB-145

BB-146BB-146

M-5M-5

TELECOM

ROOM

BT-105BT-105

ELECTRICAL

ROOM

BT-106BT-106

BT-107BT-107

BT-108BT-108

70E-401

D6

70E-401

D2 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot

REVISIONS DATE

General Notes:

GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO

THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.

GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED

BY THE VARIOUS SUBCONTRACTORS.

Approved: Division Chief

Issue Date Checked Drawn

DrawingNumber

Building Number

Project NumberDrawing Title Project Title

Location Drawing Scale

Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs

Office of Construction and Facilities Management

FULLY SPRINKLERED

Phase

A

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

321 4 5 6 7 8 9 10

GENERAL NOTES

KEYNOTES

TRUE NORTH

PLAN NORTH

KEYPLANA/E:

TRIPLE C - The A/E Group

2508 29th Avenue NE

Minneapolis, MN 55418

(612) 355-1251

Mat Perkins

A

B

D

F

G

H

J

K

L

M

N

P

As indicated

B

IM

/6

-2

-7

E

H R

M I n fr a s tr u c tu re U p g ra d e s M

P L S

V A

M C

/6 -2

-7

.M

E H

R M

.M E

P .B

.L

.r v t

/6

/2

:3 :4

P

M

05/06/2022 M. Perkins K.Hutchinson

618-21-700

1383 - 70E-100A

ELECTRICAL PLAN - BASEMENT LEVEL AREA

A

1 Veterans Drive, Minneapolis, MN 55417

B70

EHRM INFRASTRUCTURE

UPGRADESFINAL BID DOCUMENTS

1. UNLESS OTHERWISE NOTED, REMOVE ALL EXISTING ELECTRICAL DEVICES

ASSOCIATED WITH THE AREA OF WORK FROM ENDPOINT DEVICE TO

ASSOCIATED SOURCE PANEL TO PREPARE THE SPACE FOR RENOVATION. ALL

DEVICES / CIRCUITS NOT ASSOCIATED WITH THE LOCAL DEMOLITION SHALL BE

PROTECTED AND ENSURE THAT CIRCUITS REMAIN IN SERVICE AS PER

CONDITIONS PRIOR TO DEMOLITION. ALL DEMOLITION / PHASING SHALL BE

COORDINATED WITH THE VA COR.

2. PROVIDE NEW 20"x4" PRIMARY BONDING BUSBAR (PBB) ON GROUND LEVEL AND 12"x4" SECONDARY BONDING BUSBAR (SBB) FOR ALL OTHER LEVELS. PROVIDE

SET OF INSULATORS STAND-OFF BRACKETS AND STAINLESS STEEL SCREWS.

PROVIDE ALL GROUNDING CABLE AND CONNECTORS AND INSTALL PER TYPICAL

DETAIL ON T-500 SERIES SHEETS.

3. NEW 5KW RACK-MOUNTED 208 V UNINTERRUPTIBLE POWER SUPPLY (UPS) WITH

NEMA 20A L21-20P INPUT AND L21-20R OUTPUT. PROVIDE NEW 208V CIRCUIT AND

RECEPTACLE ON EMERGENCY POWER CIRCUIT. SEE T-500 SERIES SHEETS FOR

ADDITIONAL REQUIREMENTS.

4. PROVIDE NEW EMERGENCY AND NORMAL BRANCH 20A 120/208 TPST CIRCUIT

BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW CONDUIT,

CONDUCTORS AND DEVICES TO SUPPLY EACH NEW L21-20R RECEPTACLE.

5. WIRE NEW LUMINAIRES TYPE L1 TO THE EXISTING LIGHTING CIRCUIT. WIRE

LIGHTS TO THE NEW WALL MOUNTED OCCUPANCY SENSOR AT THE CLOSET

ENTRANCE. PROVIDE AUTO ON/ AUTO OFF LIGHTING CONTROL SCHEME.

COORDINATE FIXTURES WITH OVERHEAD CABLE TRAY. REFERENCE

CUTSHEETS ON 70E-901.

6. PROVIDE NEW ACCESS CONTROL PER SPECIFICATIONS. HDP12 COMPLIANT,

CARD READER WITH PINPAD CARD, PIV READY. REFERENCE CUTSHEETS ON

70E-901.

7. PROVIDE NEW MECHANICAL INDOOR UNIT WITH NEW DISCONNECT SWITCHES

SIZED PER MANUFACTURERS REQUIREMENTS. SEE MECHANICAL SHEETS FOR

ADDITIONAL INFORMATION.

8. SUB-METERING OF NEW DEDICATED ROOM AIR CONDITIONING, NON-IT LOAD

ONLY. PANEL SERVING UNIT SHALL BE EQUIPPED WITH NEW MONITORED

POWER METER. BASIS OF DESIGN: E-MON D-MON.

9. SUB-METERING OF NEW DEDICATED TR, IT LOAD ONLY. PANEL SERVING TR

SHALL BE EQUIPPED WITH NEW MONITORED POWER METER. BASIS OF DESIGN:

E-MON D-MON.

10. NOT USED.

11. NEW EMERGENCY POWER RECEPTACLE, SEE PANEL SCHEDULE.

12. REMOVE EXISTING ACCESS CONTROLS.

13. NOT USED.

14. REMOVE EXISTING LIGHT FIXTURES.

15. NOT USED.

16. NOT USED.

17. NOT USED.

18. NOT USED.

19. PROVIDE A 30 DAY LOAD MEASUREMENT OF PANELBOARD INDICATED. PROVIDE

THE REPORT TO THE COR AND AE PRIOR TO COMMENCEMENT OF PANELBOARD

RENOVATION.

20. ELECTRICAL GUTTER. REFER TO SINGLE LINE DIAGRAM FOR MORE

INFORMATION.

21. PROVIDE NEW EMERGENCY AND NORMAL POWER JUNCTION BOX FOR 60A

120/208 TPST CIRCUIT BREAKER FOR EACH RACK UPS CIRCUIT. PROVIDE NEW

CONDUIT, CONDUCTORS AND DEVICES.

22. NEW PSX-75-E1 POWER SOLUTIONS BACKUP POWER SUPPLY FOR iSTAR DOOR

CONTROLLERS. PROVIDE A 20 AMP CIRCUIT PER NEC AND MANUFACTURERS

RECOMMENDATIONS.

23. NEW NORMAL POWER RECEPTACLE, SEE PANEL SCHEDULE.

24. NEW NORMAL POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION WITH

EXISTING AND NEW CONDITIONS. SEE E-600 AND E-700 SERIES SHEETS FOR

ADDITIONAL INFORMATION.

25. NEW EMERGENCY POWER ELECTRICAL PANEL, FIELD COORDINATE LOCATION

WITH EXISTING AND…

This is the start of the file's text. The full file is on GovTribe.