This document provides details for a federal solicitation seeking construction design and build services. The solicitation will be issued as a Request for Proposal to upgrade infrastructure needed for an Electronic Health Record Modernization project at the Minneapolis VA Medical Center. The construction and commissioning must be completed in accordance with drawings and specifications provided by the architect-engineer. Services include building a new server room on the hospital roof and upgrades throughout multiple departments. The period of performance is approximately 450 calendar days from notice to proceed. The magnitude of construction is estimated between $20-50 million. The solicitation is set aside as a total small business preference and only offers from Service-Disabled Veteran-Owned Small Businesses will be considered. The NAICS code is 236220 and all questions must be submitted in writing to the agency contact.
View the file
Other files
Show 40 more
Latest 50 of 80 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PARTITION RATING GRAPHICS:
2 HR FIRE SHAFT
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
70M-441
F5
70M-442
F7
4F-1474F-147 4F-1484F-148 4F-1494F-149 4F-1504F-150 4F-1514F-151
C4F-064C4F-064
4L-117B4L-117B
4F-121A4F-121A
4F-121B4F-121B
C4F-065C4F-065
C4-120C4-120
C4-122C4-122
4F-1474F-147
C4F-064C4F-064 4S-64S-6 4H-1214H-121
C4-116C4-116
4H-1204H-120
EE
C-6C-6
4L-1014L-101
4L-1084L-108 4L-1094L-109 4L-1104L-110 4L-1124L-112
4L-1134L-113 4L-1154L-115 4L-1174L-117 4L-117A4L-117A
4L-117A4L-117A2323
4F-121E4F-121E
4H-1144H-114
4H-1154H-115 4H-1164H-116
M-8M-8
4L-1034L-103 4L-1044L-104 4L-1054L-105
4L-1064L-106
4L-1074L-107 4L-1114L-111
4L-1144L-114 4L-118C4L-118C
4L-1214L-121
4L-1224L-122
4L-1234L-123
4L-1244L-124
4L-1254L-125
4L-1264L-1264L-1274L-127 4L-1284L-128
4L-1294L-129
4L-1304L-130
4L-1314L-131
4L-1324L-132
4L-1334L-133
4L-1344L-134
4L-1354L-135
4L-1364L-136
4L-1374L-137
4L-1384L-138
4L-1394L-139
4L-1404L-140
C5C5
4L-125A4L-125A
4F-121C4F-121C
4F-121D4F-121D
C4-117C4-117
C4-118C4-118
C4-119C4-119
C4-123C4-123
C4-126C4-126
C4-115C4-115
4L-1024L-102
4L-102A4L-102A
C4-124C4-124
4L-114A4L-114A 4L-1164L-116
4L-118A4L-118A 4L-118B4L-118B
4L-118D4L-118D4L-1184L-118
4K-1014K-101
4K-1024K-102
4K-1434K-143
4H-1084H-108
C4-114C4-114
4L-1394L-139
C4-125C4-125
4S-64S-6
4H-1144H-114
EE
C4-115C4-115
C4-137C4-137
70M-441
F2
70M-442
F5
1" CD
1" CD
1 1/2" CHWS
1 1/2" CHWR
TELECOM
ROOM
(ORANGE-STACK)
4H-1184H-118
TELECOM
ROOM
(PINK-STACK)
4F-121F4F-121F
3/4" CD
1 1/2" CHWR1 1/2" CHWS
1 1/4" CHWS
1 1/4" CHWR
3/4" CD
3/4" CD
1 1/4" CHWR
1 1/4" CHWS
on e-ei gh th in ch o ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in es ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e s M
P L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r v t
/7
/2
:4
:5
P
M
05/06/2022 M. Perkins G. Weaver
618-21-700
1383 - 70M-104G
MECHANICAL PLAN - FOURTH LEVEL AREA G
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. PROVIDE PACKAGED NEW FAN COIL UNIT, CHILLED WATER PIPING,
CONDENSATE PIPING, THERMOSTAT AND BACNET CONTROLS MODULE
CONNECTED TO EXISTING CHILLED WATER SUPPLY/RETURN RISER. SEE RISER
DIAGRAMS FOR CONNECTIONS. LOCATE FAN COIL UNITS ABOVE DOOR.
PROVIDE DRAIN PAN WITH LEAK DETECTION CONNECTED TO BAS.
2. PROVIDE CONDENSATE PUMP, TO BE MOUNTED HIDDEN WITHIN THE INDOOR
UNIT, CAPABLE OF LIFTING UP 50 FEET WITH 8 FEET SUCTION AND 10 GPH
PUMPING CAPACITY. PROVIDE ELECTRICAL SERVICE FOR CONDENSATE PUMP
IF NOT FED FROM INDOOR UNIT. PROVIDE NEW CONDENSATE LINE FOR NEW
MECHANICAL EQUIPMENT, COORDINATE WITH VA. PROVIDE COORDINATION
DRAWINGS FOR EACH DRAIN LINE INSTALLATION PER 01 33 23 PRIOR TO
BEGINNING WORK.
3. PROVIDE NEW DEDICATED THERMOSTAT, COORDINATE FINAL LOCATION WITH
EXISTING AND NEW EQUIPMENT. THERMOSTATS SHALL BE DISPLAY ONLY WITH
CONTROLLABILITY THROUGH THE BMS.
4. PROVIDE BACNET CONTROLLER MOUNTED ADJACENT TO UNIT IN TR. CONNECT
WITH UTP CABLE TO EXISTING ETHERNET SWITCH IN LOCAL TR TO BE
ADDRESSABLE ON VA NETWORK/HVAC FMS.
5. PROVIDE NEW PUMPED CONDENSATE LINE, DROP DOWN ON WALL TO
DISCHARGE OVER EXISTING SINK BELOW, SECURE PIPING TO WALL. PIPE TO BE
CUT AT 45 DEGREE ANGLE AT OUTLET.
6. SEE ARCHITECTURAL DRAWINGS FOR CONTEXT.
7. PROVIDE ELECTRICAL CIRCUIT FOR EACH NEW CHILLED WATER FAN COIL UNIT.
SEE ELECTRICAL SHEETS.
8. EXISTING FACILITY HOUSE AIR THERMOSTAT TO REMAIN, PROTECT IN PLACE.
9. EXISTING CEILING MOUNTED SUPPLY AND RETURN AIR DEVICES TO REMAIN.
COORDINATE WITH REMOVAL OF EXISTING GYPSUM CEILING AND ALL OTHER
TRADES, RESUPPORT AIR DEVICE AS REQUIRED ABOVE CABLE TRAY AND
LIGHTING. SEE SHEET E-501 AND ARCHITECTURAL PLANS FOR ADDITIONAL
INFORMATION.
10. CONTRACTOR SHALL PROVIDE RATED PENETRATION TO MATCH WALL RATING
AT THIS LOCATION. SEE DETAILS ON M-500 SERIES SHEETS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
11. EXISTING PENETRATION TO REMAIN.
12. REBALANCE AIRFLOW AFTER CONSTRUCTION IS COMPLETE.
13. REMOVE RADIATORS AND CAP SERVICE LINES IN THE INTERSTITIAL SPACE.
14. CONNECT TO EXISTING CONDENSATE STACK.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. COORDINATE ALL DUCTWORK AND PIPE ROUTING AND ELEVATIONS WITH
OTHER TRADES IN ADVANCE OF INSTALLATION.
C. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-
CONSTRUCTION TAB REPORT FOR THE EQUIPMENT AND ASSOCIATED
SYSTEMS SHOWN ON THE CONSTRUCTION DOCUMENTS AND UTILIZE
ALL AVAILABLE AS-BUILT DRAWINGS FROM THE OWNER. TEST AND
BALANCE CONTRACTOR SHALL VISIT SITE PRIOR TO CONSTRUCTION
AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND DEVELOP
THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING
EQUIPMENT LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND
TAG NUMBERS. IF THERE ARE LOCATIONS WHERE THE DRAWINGS DO
NOT REFLECT FIELD CONDITIONS, THE TEST AND BALANCE
CONTRACTOR SHALL INCLUDE THE AIRFLOW READINGS ON THE FORMS
AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE ON THE DRAWINGS.
REFER TO SPECIFICATION SECTION 23 05 93 FOR MORE INFORMATION.
D. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED
TO ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND BALANCE DATA
FOR THE RENOVATION. DATA SHALL BE FORWARDED TO THE PROJECT
ENGINEER FOR REVIEW AND COMMENT PRIOR TO COMMENCING THE
DEMOLITION AND/OR NEW WORK ASSOCIATED WITH THE FACILITY
RENOVATION.
E. THE CONTRACTOR SHALL PATCH, PAINT AND RETURN TO MATCH EXISTING
CONDITIONS FOR ANY FLOOR, WALL, OR CEILING THAT WAS DISTURBED TO
COMPLETE THIS PROJECT.
F. ALL NEW THERMOSTATS ARE TO BE MOUNTED AT A HEIGHT OF 54” ABOVE
FINISHED FLOOR. VERIFY FINAL THERMOSTAT LOCATIONS WITH VA.
G. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHTS AND
ELEVATIONS.
H. ALL PIPING PLACED WITHIN INTERSTITIAL AREA.
NOTE: NOT ALL KEYNOTES ARE
USED ON EACH SHEET
SCALE: 1" = 10'-0"
F2
MECHANICAL PLAN - FIRST LEVEL
AREA G
1 Revision 1 Date 1
05/06/2022
ADDENDUM #1 07/07/2022
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
4K-1014K-101
4K-1024K-102
4K-1034K-103
4K-1434K-143
4H-1084H-108
C4-127C4-127
4K-1244K-124
4K-1204K-120 4K-1214K-121
4K-1044K-104
4K-1054K-105
4K-1064K-106
4K-1074K-107
4K-1084K-108
4K-1094K-109 4K-1104K-110
4K-1114K-111
4K-1124K-112 4K-1134K-113
4K-1144K-114
4K-1154K-115
4K-1164K-116
4K-1174K-117
4K-1194K-119
4K-1224K-1224K-1234K-1234K-1254K-125
4K-1264K-126
4K-1274K-127 4K-1284K-128
4K-1294K-129
4K-1314K-131
4K-1324K-132
4K-1334K-133
4K-1344K-134
4K-1354K-135
4K-1364K-136
4K-1374K-137
4K-1384K-138 4K-1394K-139
4K-1404K-140
4K-1414K-141
4K-1424K-142
4K-102A4K-102A
4K-134A4K-134A
4K-136A4K-136A
4K-133A4K-133A
C-7C-7
4K-131A4K-131A
4K-140A4K-140A
4K-138A4K-138A
4K-1184K-118
4K-1304K-130
4K-121A4K-121A
C4-132C4-132
C4-133C4-133
C4-134C4-134
C4-131C4-131
4K-142A4K-142A
C4-135C4-135
4K-130A4K-130A
4K-124A4K-124A
4K-124B4K-124B
4H-108A4H-108A
4H-101A4H-101A
C4-138C4-138
C4-137C4-137
C4-135C4-135 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a st ru ct u re
U p g ra d e s
M P
L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r vt /6
/2
:2 :3
P
M
05/06/2022 M. Perkins G. Weaver
618-21-700
1383 - 70M-104H
MECHANICAL PLAN - FOURTH LEVEL AREA H
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. PROVIDE PACKAGED NEW FAN COIL UNIT, CHILLED WATER PIPING,
CONDENSATE PIPING, THERMOSTAT AND BACNET CONTROLS MODULE
CONNECTED TO EXISTING CHILLED WATER SUPPLY/RETURN RISER. SEE RISER
DIAGRAMS FOR CONNECTIONS. LOCATE FAN COIL UNITS ABOVE DOOR.
PROVIDE DRAIN PAN WITH LEAK DETECTION CONNECTED TO BAS.
2. PROVIDE CONDENSATE PUMP, TO BE MOUNTED HIDDEN WITHIN THE INDOOR
UNIT, CAPABLE OF LIFTING UP 50 FEET WITH 8 FEET SUCTION AND 10 GPH
PUMPING CAPACITY. PROVIDE ELECTRICAL SERVICE FOR CONDENSATE PUMP
IF NOT FED FROM INDOOR UNIT. PROVIDE NEW CONDENSATE LINE FOR NEW
MECHANICAL EQUIPMENT, COORDINATE WITH VA. PROVIDE COORDINATION
DRAWINGS FOR EACH DRAIN LINE INSTALLATION PER 01 33 23 PRIOR TO
BEGINNING WORK.
3. PROVIDE NEW DEDICATED THERMOSTAT, COORDINATE FINAL LOCATION WITH
EXISTING AND NEW EQUIPMENT. THERMOSTATS SHALL BE DISPLAY ONLY WITH
CONTROLLABILITY THROUGH THE BMS.
4. PROVIDE BACNET CONTROLLER MOUNTED ADJACENT TO UNIT IN TR. CONNECT
WITH UTP CABLE TO EXISTING ETHERNET SWITCH IN LOCAL TR TO BE
ADDRESSABLE ON VA NETWORK/HVAC FMS.
5. PROVIDE NEW PUMPED CONDENSATE LINE, DROP DOWN ON WALL TO
DISCHARGE OVER EXISTING SINK BELOW, SECURE PIPING TO WALL. PIPE TO BE
CUT AT 45 DEGREE ANGLE AT OUTLET.
6. SEE ARCHITECTURAL DRAWINGS FOR CONTEXT.
7. PROVIDE ELECTRICAL CIRCUIT FOR EACH NEW CHILLED WATER FAN COIL UNIT.
SEE ELECTRICAL SHEETS.
8. EXISTING FACILITY HOUSE AIR THERMOSTAT TO REMAIN, PROTECT IN PLACE.
9. EXISTING CEILING MOUNTED SUPPLY AND RETURN AIR DEVICES TO REMAIN.
COORDINATE WITH REMOVAL OF EXISTING GYPSUM CEILING AND ALL OTHER
TRADES, RESUPPORT AIR DEVICE AS REQUIRED ABOVE CABLE TRAY AND
LIGHTING. SEE SHEET E-501 AND ARCHITECTURAL PLANS FOR ADDITIONAL
INFORMATION.
10. CONTRACTOR SHALL PROVIDE RATED PENETRATION TO MATCH WALL RATING
AT THIS LOCATION. SEE DETAILS ON M-500 SERIES SHEETS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
11. EXISTING PENETRATION TO REMAIN.
12. REBALANCE AIRFLOW AFTER CONSTRUCTION IS COMPLETE.
13. REMOVE RADIATORS AND CAP SERVICE LINES IN THE INTERSTITIAL SPACE.
14. CONNECT TO EXISTING CONDENSATE STACK.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. COORDINATE ALL DUCTWORK AND PIPE ROUTING AND ELEVATIONS WITH
OTHER TRADES IN ADVANCE OF INSTALLATION.
C. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-
CONSTRUCTION TAB REPORT FOR THE EQUIPMENT AND ASSOCIATED
SYSTEMS SHOWN ON THE CONSTRUCTION DOCUMENTS AND UTILIZE
ALL AVAILABLE AS-BUILT DRAWINGS FROM THE OWNER. TEST AND
BALANCE CONTRACTOR SHALL VISIT SITE PRIOR TO CONSTRUCTION
AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND DEVELOP
THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING
EQUIPMENT LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND
TAG NUMBERS. IF THERE ARE LOCATIONS WHERE THE DRAWINGS DO
NOT REFLECT FIELD CONDITIONS, THE TEST AND BALANCE
CONTRACTOR SHALL INCLUDE THE AIRFLOW READINGS ON THE FORMS
AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE ON THE DRAWINGS.
REFER TO SPECIFICATION SECTION 23 05 93 FOR MORE INFORMATION.
D. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED
TO ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND BALANCE DATA
FOR THE RENOVATION. DATA SHALL BE FORWARDED TO THE PROJECT
ENGINEER FOR REVIEW AND COMMENT PRIOR TO COMMENCING THE
DEMOLITION AND/OR NEW WORK ASSOCIATED WITH THE FACILITY
RENOVATION.
E. THE CONTRACTOR SHALL PATCH, PAINT AND RETURN TO MATCH EXISTING
CONDITIONS FOR ANY FLOOR, WALL, OR CEILING THAT WAS DISTURBED TO
COMPLETE THIS PROJECT.
F. ALL NEW THERMOSTATS ARE TO BE MOUNTED AT A HEIGHT OF 54” ABOVE
FINISHED FLOOR. VERIFY FINAL THERMOSTAT LOCATIONS WITH VA.
G. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHTS AND
ELEVATIONS.
H. ALL PIPING PLACED WITHIN INTERSTITIAL AREA.
NOTE: NOT ALL KEYNOTES ARE
USED ON EACH SHEET
1" = 10'-0" F6
MECHANICAL PLAN - FIRST LEVEL AREA H
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
4G-1124G-112
4G-1164G-116 4G-1154G-115
4H-1014H-101
C4-110C4-110
4H-1154H-115
4K-1024K-102
4K-1434K-143
4H-1084H-108
C4-114C4-114
4K-1424K-142 4K-142A4K-142A
4J-1014J-101
4H-108A4H-108A
4H-101A4H-101A
C4-139C4-139
C4-138C4-138
4J-1024J-1024J-1034J-1034J-1044J-104
4J-1054J-105
4J-1064J-106
4J-1074J-107
4J-1084J-108 4J-1094J-109
4J-1104J-110
4J-1114J-111
4J-1124J-1124J-1134J-113
4J-1144J-114
4J-1154J-115
4J-1164J-116
4J-1174J-117
4J-1184J-118
4J-1194J-119
4J-1204J-120
4J-1214J-121
4J-1224J-122
4J-1234J-123
4J-1244J-124
4J-1254J-125
4J-1264J-126
4J-1274J-127 4J-1284J-128
4J-1294J-129 4J-1304J-130
4J-1314J-131
4J-1324J-132
4J-102B4J-102B4J-103B4J-103B
4J-102A4J-102A4J-103A4J-103A
4J-104A4J-104A
4J-109A4J-109A4J-115A4J-115A4J-119A4J-119A
4J-120A4J-120A
4J-121A4J-121A
4J-121B4J-121B
4J-121C4J-121C
4J-121D4J-121D
4J-123A4J-123A
4J-125A4J-125A 4J-116A4J-116A
C-8C-8
4J-124A4J-124A 4J-126A4J-126A 4J-129A4J-129A 4J-130A4J-130A
4J-132A4J-132A
4H-1024H-102
4H-1034H-103
4H-1044H-104
4H-1054H-105
4H-1064H-106
4H-1074H-107
4H-1094H-109 4H-1104H-110
4H-1114H-111
4H-1134H-113
4H-101D4H-101D
4H-101C4H-101C
4H-101B4H-101B4H-101E4H-101E
C4-142C4-142
C4-141C4-141
C4-143C4-143
C4-144C4-144
C4-145C4-145
C4-146C4-146
C4-147C4-147
C4-148C4-148
C4-149C4-149
4J-122A4J-122A
4H-1124H-112
4P-1194P-119
4P-1204P-120
4P-1214P-121
4P-1224P-122
4P-1234P-123 4P-1244P-124
4J-1214J-121
4J-121C4J-121C on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a st ru ct u re
U p g ra d e s
M P
L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r vt /6
/2
:2 :4
P
M
05/06/2022 M. Perkins G. Weaver
618-21-700
1383 - 70M-104J
MECHANICAL PLAN - FOURTH LEVEL AREA J
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. PROVIDE PACKAGED NEW FAN COIL UNIT, CHILLED WATER PIPING,
CONDENSATE PIPING, THERMOSTAT AND BACNET CONTROLS MODULE
CONNECTED TO EXISTING CHILLED WATER SUPPLY/RETURN RISER. SEE RISER
DIAGRAMS FOR CONNECTIONS. LOCATE FAN COIL UNITS ABOVE DOOR.
PROVIDE DRAIN PAN WITH LEAK DETECTION CONNECTED TO BAS.
2. PROVIDE CONDENSATE PUMP, TO BE MOUNTED HIDDEN WITHIN THE INDOOR
UNIT, CAPABLE OF LIFTING UP 50 FEET WITH 8 FEET SUCTION AND 10 GPH
PUMPING CAPACITY. PROVIDE ELECTRICAL SERVICE FOR CONDENSATE PUMP
IF NOT FED FROM INDOOR UNIT. PROVIDE NEW CONDENSATE LINE FOR NEW
MECHANICAL EQUIPMENT, COORDINATE WITH VA. PROVIDE COORDINATION
DRAWINGS FOR EACH DRAIN LINE INSTALLATION PER 01 33 23 PRIOR TO
BEGINNING WORK.
3. PROVIDE NEW DEDICATED THERMOSTAT, COORDINATE FINAL LOCATION WITH
EXISTING AND NEW EQUIPMENT. THERMOSTATS SHALL BE DISPLAY ONLY WITH
CONTROLLABILITY THROUGH THE BMS.
4. PROVIDE BACNET CONTROLLER MOUNTED ADJACENT TO UNIT IN TR. CONNECT
WITH UTP CABLE TO EXISTING ETHERNET SWITCH IN LOCAL TR TO BE
ADDRESSABLE ON VA NETWORK/HVAC FMS.
5. PROVIDE NEW PUMPED CONDENSATE LINE, DROP DOWN ON WALL TO
DISCHARGE OVER EXISTING SINK BELOW, SECURE PIPING TO WALL. PIPE TO BE
CUT AT 45 DEGREE ANGLE AT OUTLET.
6. SEE ARCHITECTURAL DRAWINGS FOR CONTEXT.
7. PROVIDE ELECTRICAL CIRCUIT FOR EACH NEW CHILLED WATER FAN COIL UNIT.
SEE ELECTRICAL SHEETS.
8. EXISTING FACILITY HOUSE AIR THERMOSTAT TO REMAIN, PROTECT IN PLACE.
9. EXISTING CEILING MOUNTED SUPPLY AND RETURN AIR DEVICES TO REMAIN.
COORDINATE WITH REMOVAL OF EXISTING GYPSUM CEILING AND ALL OTHER
TRADES, RESUPPORT AIR DEVICE AS REQUIRED ABOVE CABLE TRAY AND
LIGHTING. SEE SHEET E-501 AND ARCHITECTURAL PLANS FOR ADDITIONAL
INFORMATION.
10. CONTRACTOR SHALL PROVIDE RATED PENETRATION TO MATCH WALL RATING
AT THIS LOCATION. SEE DETAILS ON M-500 SERIES SHEETS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
11. EXISTING PENETRATION TO REMAIN.
12. REBALANCE AIRFLOW AFTER CONSTRUCTION IS COMPLETE.
13. REMOVE RADIATORS AND CAP SERVICE LINES IN THE INTERSTITIAL SPACE.
14. CONNECT TO EXISTING CONDENSATE STACK.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. COORDINATE ALL DUCTWORK AND PIPE ROUTING AND ELEVATIONS WITH
OTHER TRADES IN ADVANCE OF INSTALLATION.
C. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-
CONSTRUCTION TAB REPORT FOR THE EQUIPMENT AND ASSOCIATED
SYSTEMS SHOWN ON THE CONSTRUCTION DOCUMENTS AND UTILIZE
ALL AVAILABLE AS-BUILT DRAWINGS FROM THE OWNER. TEST AND
BALANCE CONTRACTOR SHALL VISIT SITE PRIOR TO CONSTRUCTION
AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND DEVELOP
THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING
EQUIPMENT LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND
TAG NUMBERS. IF THERE ARE LOCATIONS WHERE THE DRAWINGS DO
NOT REFLECT FIELD CONDITIONS, THE TEST AND BALANCE
CONTRACTOR SHALL INCLUDE THE AIRFLOW READINGS ON THE FORMS
AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE ON THE DRAWINGS.
REFER TO SPECIFICATION SECTION 23 05 93 FOR MORE INFORMATION.
D. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED
TO ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND BALANCE DATA
FOR THE RENOVATION. DATA SHALL BE FORWARDED TO THE PROJECT
ENGINEER FOR REVIEW AND COMMENT PRIOR TO COMMENCING THE
DEMOLITION AND/OR NEW WORK ASSOCIATED WITH THE FACILITY
RENOVATION.
E. THE CONTRACTOR SHALL PATCH, PAINT AND RETURN TO MATCH EXISTING
CONDITIONS FOR ANY FLOOR, WALL, OR CEILING THAT WAS DISTURBED TO
COMPLETE THIS PROJECT.
F. ALL NEW THERMOSTATS ARE TO BE MOUNTED AT A HEIGHT OF 54” ABOVE
FINISHED FLOOR. VERIFY FINAL THERMOSTAT LOCATIONS WITH VA.
G. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHTS AND
ELEVATIONS.
H. ALL PIPING PLACED WITHIN INTERSTITIAL AREA.
NOTE: NOT ALL KEYNOTES ARE
USED ON EACH SHEET
SCALE: 1" = 10'-0"
F2
MECHANICAL PLAN - FIRST LEVEL
AREA J
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
C4-100C4-100
4H-1014H-101
C4-100C4-100
4J-1234J-123
4J-1244J-124 4J-1264J-126 4J-1294J-129 4J-1304J-130
4J-1324J-132
4J-121D4J-121D
4H-101D4H-101D
C4-149C4-149
4J-122A4J-122A
4P-1194P-119
4P-1204P-120
4P-1214P-121
4P-1224P-122
4P-1234P-123 4P-1244P-124
C4-152C4-152
C4-150C4-150
4P-1084P-108
4P-1094P-109
4P-1104P-110
4P-1114P-111
4P-1124P-112 4P-1134P-113
4P-1144P-1144P-1154P-115
4P-1164P-116
4P-1174P-117
4P-1184P-118
4P-1254P-125
4P-1264P-1264P-1274P-127
4P-1284P-128
4P-1294P-129
4P-1304P-130
4P-1314P-131
4P-1324P-132
4P-1074P-107
C4-151C4-151
C4-100C4-100
4P-1324P-132
C4-152C4-152
C4-150C4-150
1" CD
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a st ru ct u re
U p g ra d e s
M P
L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r vt /6
/2
:2 :5
P
M
05/06/2022 M. Perkins G. Weaver
618-21-700
1383 - 70M-104K
MECHANICAL PLAN - FOURTH LEVEL AREA K
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. PROVIDE PACKAGED NEW FAN COIL UNIT, CHILLED WATER PIPING,
CONDENSATE PIPING, THERMOSTAT AND BACNET CONTROLS MODULE
CONNECTED TO EXISTING CHILLED WATER SUPPLY/RETURN RISER. SEE RISER
DIAGRAMS FOR CONNECTIONS. LOCATE FAN COIL UNITS ABOVE DOOR.
PROVIDE DRAIN PAN WITH LEAK DETECTION CONNECTED TO BAS.
2. PROVIDE CONDENSATE PUMP, TO BE MOUNTED HIDDEN WITHIN THE INDOOR
UNIT, CAPABLE OF LIFTING UP 50 FEET WITH 8 FEET SUCTION AND 10 GPH
PUMPING CAPACITY. PROVIDE ELECTRICAL SERVICE FOR CONDENSATE PUMP
IF NOT FED FROM INDOOR UNIT. PROVIDE NEW CONDENSATE LINE FOR NEW
MECHANICAL EQUIPMENT, COORDINATE WITH VA. PROVIDE COORDINATION
DRAWINGS FOR EACH DRAIN LINE INSTALLATION PER 01 33 23 PRIOR TO
BEGINNING WORK.
3. PROVIDE NEW DEDICATED THERMOSTAT, COORDINATE FINAL LOCATION WITH
EXISTING AND NEW EQUIPMENT. THERMOSTATS SHALL BE DISPLAY ONLY WITH
CONTROLLABILITY THROUGH THE BMS.
4. PROVIDE BACNET CONTROLLER MOUNTED ADJACENT TO UNIT IN TR. CONNECT
WITH UTP CABLE TO EXISTING ETHERNET SWITCH IN LOCAL TR TO BE
ADDRESSABLE ON VA NETWORK/HVAC FMS.
5. PROVIDE NEW PUMPED CONDENSATE LINE, DROP DOWN ON WALL TO
DISCHARGE OVER EXISTING SINK BELOW, SECURE PIPING TO WALL. PIPE TO BE
CUT AT 45 DEGREE ANGLE AT OUTLET.
6. SEE ARCHITECTURAL DRAWINGS FOR CONTEXT.
7. PROVIDE ELECTRICAL CIRCUIT FOR EACH NEW CHILLED WATER FAN COIL UNIT.
SEE ELECTRICAL SHEETS.
8. EXISTING FACILITY HOUSE AIR THERMOSTAT TO REMAIN, PROTECT IN PLACE.
9. EXISTING CEILING MOUNTED SUPPLY AND RETURN AIR DEVICES TO REMAIN.
COORDINATE WITH REMOVAL OF EXISTING GYPSUM CEILING AND ALL OTHER
TRADES, RESUPPORT AIR DEVICE AS REQUIRED ABOVE CABLE TRAY AND
LIGHTING. SEE SHEET E-501 AND ARCHITECTURAL PLANS FOR ADDITIONAL
INFORMATION.
10. CONTRACTOR SHALL PROVIDE RATED PENETRATION TO MATCH WALL RATING
AT THIS LOCATION. SEE DETAILS ON M-500 SERIES SHEETS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
11. EXISTING PENETRATION TO REMAIN.
12. REBALANCE AIRFLOW AFTER CONSTRUCTION IS COMPLETE.
13. REMOVE RADIATORS AND CAP SERVICE LINES IN THE INTERSTITIAL SPACE.
14. CONNECT TO EXISTING CONDENSATE STACK.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. COORDINATE ALL DUCTWORK AND PIPE ROUTING AND ELEVATIONS WITH
OTHER TRADES IN ADVANCE OF INSTALLATION.
C. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-
CONSTRUCTION TAB REPORT FOR THE EQUIPMENT AND ASSOCIATED
SYSTEMS SHOWN ON THE CONSTRUCTION DOCUMENTS AND UTILIZE
ALL AVAILABLE AS-BUILT DRAWINGS FROM THE OWNER. TEST AND
BALANCE CONTRACTOR SHALL VISIT SITE PRIOR TO CONSTRUCTION
AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND DEVELOP
THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING
EQUIPMENT LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND
TAG NUMBERS. IF THERE ARE LOCATIONS WHERE THE DRAWINGS DO
NOT REFLECT FIELD CONDITIONS, THE TEST AND BALANCE
CONTRACTOR SHALL INCLUDE THE AIRFLOW READINGS ON THE FORMS
AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE ON THE DRAWINGS.
REFER TO SPECIFICATION SECTION 23 05 93 FOR MORE INFORMATION.
D. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED
TO ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND BALANCE DATA
FOR THE RENOVATION. DATA SHALL BE FORWARDED TO THE PROJECT
ENGINEER FOR REVIEW AND COMMENT PRIOR TO COMMENCING THE
DEMOLITION AND/OR NEW WORK ASSOCIATED WITH THE FACILITY
RENOVATION.
E. THE CONTRACTOR SHALL PATCH, PAINT AND RETURN TO MATCH EXISTING
CONDITIONS FOR ANY FLOOR, WALL, OR CEILING THAT WAS DISTURBED TO
COMPLETE THIS PROJECT.
F. ALL NEW THERMOSTATS ARE TO BE MOUNTED AT A HEIGHT OF 54” ABOVE
FINISHED FLOOR. VERIFY FINAL THERMOSTAT LOCATIONS WITH VA.
G. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHTS AND
ELEVATIONS.
H. ALL PIPING PLACED WITHIN INTERSTITIAL AREA.
NOTE: NOT ALL KEYNOTES ARE
USED ON EACH SHEET
SCALE: 1" = 10'-0"
F3
MECHANICAL PLAN - FIRST LEVEL
AREA K
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
4M-101
4M-104
TELECOM ROOM
4M-106
ELECTRICAL ROOM
4M-107
C4-177
4P-133
C4-154
4P-101
4P-102
TELECOM ROOM
4P-103
4P-101A
4N-101
4N-1024N-1034N-104
4N-1054N-106
TELECOM ROOM
4N-107
ELECTRICAL ROOM
4N-108
F
G
4S-8
4S-10
4M-102
4M-103
4M-108
4M-1104M-1114M-1124M-1134M-1144M-115 4M-1164M-117
4M-119
4M-120
4M-121
4M-122
4M-125
4M-126
4M-131
4M-132
4M-133
4M-134
4M-135
4M-122A
4M-109B
4M-109C
4M-115A
4S-7
4Q-101
4Q-102
4Q-103
4Q-104
4Q-105
4Q-106
4Q-107
4Q-108
4Q-109
4Q-111 4Q-112 4Q-123
4Q-124
4Q-125
4Q-126
4Q-127
C4-173
C4-174A
C4-156
C4-165
C4-157
C4-158
C4-166
4M-118
4M-109
4M-109A
C4-164
C4-159 C4-163C4-159 C4-163
70M-441 C5
70M-441 C2
1 1/2" CHWR
1 1/2" CHWS
3/4" CD
1" CDPIPE RISER
PIPE RISER
1 1/2" CHWS
1 1/2" CHWR
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a st ru ct u re
U p g ra d e s
M P
L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r vt /6
/2
:2 :1
P
M
05/06/2022 M. Perkins G. Weaver
618-21-700
1383 - 70M-104L
MECHANICAL PLAN - FOURTH LEVEL AREA L
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. PROVIDE PACKAGED NEW FAN COIL UNIT, CHILLED WATER PIPING,
CONDENSATE PIPING, THERMOSTAT AND BACNET CONTROLS MODULE
CONNECTED TO EXISTING CHILLED WATER SUPPLY/RETURN RISER. SEE RISER
DIAGRAMS FOR CONNECTIONS. LOCATE FAN COIL UNITS ABOVE DOOR.
PROVIDE DRAIN PAN WITH LEAK DETECTION CONNECTED TO BAS.
2. PROVIDE CONDENSATE PUMP, TO BE MOUNTED HIDDEN WITHIN THE INDOOR
UNIT, CAPABLE OF LIFTING UP 50 FEET WITH 8 FEET SUCTION AND 10 GPH
PUMPING CAPACITY. PROVIDE ELECTRICAL SERVICE FOR CONDENSATE PUMP
IF NOT FED FROM INDOOR UNIT. PROVIDE NEW CONDENSATE LINE FOR NEW
MECHANICAL EQUIPMENT, COORDINATE WITH VA. PROVIDE COORDINATION
DRAWINGS FOR EACH DRAIN LINE INSTALLATION PER 01 33 23 PRIOR TO
BEGINNING WORK.
3. PROVIDE NEW DEDICATED THERMOSTAT, COORDINATE FINAL LOCATION WITH
EXISTING AND NEW EQUIPMENT. THERMOSTATS SHALL BE DISPLAY ONLY WITH
CONTROLLABILITY THROUGH THE BMS.
4. PROVIDE BACNET CONTROLLER MOUNTED ADJACENT TO UNIT IN TR. CONNECT
WITH UTP CABLE TO EXISTING ETHERNET SWITCH IN LOCAL TR TO BE
ADDRESSABLE ON VA NETWORK/HVAC FMS.
5. PROVIDE NEW PUMPED CONDENSATE LINE, DROP DOWN ON WALL TO
DISCHARGE OVER EXISTING SINK BELOW, SECURE PIPING TO WALL. PIPE TO BE
CUT AT 45 DEGREE ANGLE AT OUTLET.
6. SEE ARCHITECTURAL DRAWINGS FOR CONTEXT.
7. PROVIDE ELECTRICAL CIRCUIT FOR EACH NEW CHILLED WATER FAN COIL UNIT.
SEE ELECTRICAL SHEETS.
8. EXISTING FACILITY HOUSE AIR THERMOSTAT TO REMAIN, PROTECT IN PLACE.
9. EXISTING CEILING MOUNTED SUPPLY AND RETURN AIR DEVICES TO REMAIN.
COORDINATE WITH REMOVAL OF EXISTING GYPSUM CEILING AND ALL OTHER
TRADES, RESUPPORT AIR DEVICE AS REQUIRED ABOVE CABLE TRAY AND
LIGHTING. SEE SHEET E-501 AND ARCHITECTURAL PLANS FOR ADDITIONAL
INFORMATION.
10. CONTRACTOR SHALL PROVIDE RATED PENETRATION TO MATCH WALL RATING
AT THIS LOCATION. SEE DETAILS ON M-500 SERIES SHEETS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
11. EXISTING PENETRATION TO REMAIN.
12. REBALANCE AIRFLOW AFTER CONSTRUCTION IS COMPLETE.
13. REMOVE RADIATORS AND CAP SERVICE LINES IN THE INTERSTITIAL SPACE.
14. CONNECT TO EXISTING CONDENSATE STACK.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. COORDINATE ALL DUCTWORK AND PIPE ROUTING AND ELEVATIONS WITH
OTHER TRADES IN ADVANCE OF INSTALLATION.
C. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-
CONSTRUCTION TAB REPORT FOR THE EQUIPMENT AND ASSOCIATED
SYSTEMS SHOWN ON THE CONSTRUCTION DOCUMENTS AND UTILIZE
ALL AVAILABLE AS-BUILT DRAWINGS FROM THE OWNER. TEST AND
BALANCE CONTRACTOR SHALL VISIT SITE PRIOR TO CONSTRUCTION
AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND DEVELOP
THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING
EQUIPMENT LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND
TAG NUMBERS. IF THERE ARE LOCATIONS WHERE THE DRAWINGS DO
NOT REFLECT FIELD CONDITIONS, THE TEST AND BALANCE
CONTRACTOR SHALL INCLUDE THE AIRFLOW READINGS ON THE FORMS
AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE ON THE DRAWINGS.
REFER TO SPECIFICATION SECTION 23 05 93 FOR MORE INFORMATION.
D. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED
TO ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND BALANCE DATA
FOR THE RENOVATION. DATA SHALL BE FORWARDED TO THE PROJECT
ENGINEER FOR REVIEW AND COMMENT PRIOR TO COMMENCING THE
DEMOLITION AND/OR NEW WORK ASSOCIATED WITH THE FACILITY
RENOVATION.
E. THE CONTRACTOR SHALL PATCH, PAINT AND RETURN TO MATCH EXISTING
CONDITIONS FOR ANY FLOOR, WALL, OR CEILING THAT WAS DISTURBED TO
COMPLETE THIS PROJECT.
F. ALL NEW THERMOSTATS ARE TO BE MOUNTED AT A HEIGHT OF 54” ABOVE
FINISHED FLOOR. VERIFY FINAL THERMOSTAT LOCATIONS WITH VA.
G. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHTS AND
ELEVATIONS.
H. ALL PIPING PLACED WITHIN INTERSTITIAL AREA.
NOTE: NOT ALL KEYNOTES ARE
USED ON EACH SHEET
1" = 10'-0" F3
MECHANICAL PLAN - FIRST LEVEL AREA L
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
70M-443 C6
C4-19C4-19
C4-20C4-20
4T-1034T-103
C4-20C4-20
4S-1174S-117
C4-163C4-163
4Q-118E4Q-118E
4S-1084S-108
4S-1094S-109
4S-1104S-110
4S-1114S-111
4S-1124S-112
4S-1134S-113
4S-1144S-114
4S-1154S-115
4S-1164S-116
4Q-1174Q-117
4Q-1184Q-118
4Q-1194Q-1194Q-1204Q-120
4Q-118A4Q-118A 4Q-118B4Q-118B
4Q-118C4Q-118C
4Q-118D4Q-118D
4V-1014V-101
4V-1024V-102
4V-1034V-1034V-1044V-104
4V-1054V-105
4V-1064V-106
4V-1084V-108
4V-1094V-109
4V-1104V-110
4V-1114V-111
4V-1124V-112
4V-1134V-113
4V-1144V-114 4V-107B4V-107B
4V-100A4V-100A
4T-1064T-106
4T-1074T-107
4T-1084T-108
4T-1094T-109
4T-1104T-110
4T-1114T-111
4T-1124T-112
4T-1134T-113 4T-1144T-114
4T-114A4T-114A
4S-14S-1
4T-1044T-104
4V-1074V-107
4V-107A4V-107A
C4-186C4-186
C4-161C4-161
C4-194C4-194
C4-193C4-193
C4-190C4-190
C4-191C4-191
C4-192C4-192C4-195C4-195
4V-1004V-100
C4-187C4-187
4T-113A4T-113A
C4-136C4-136
70M-443 C3
1 1/2" CHWR
1 1/2" CHWS
1 1/2" CHWR
1 1/2" CHWS
1" CD
on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A
B D
TRUE NORTH
PLAN NORTH
E F
G
H
J
K
L
M
C
KEYPLANA/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a st ru ct u re
U p g ra d e s
M P
L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r vt /6
/2
:2 :2
P
M
05/06/2022 M. Perkins G. Weaver
618-21-700
1383 - 70M-104M
MECHANICAL PLAN - FOURTH LEVEL AREA M
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. PROVIDE PACKAGED NEW FAN COIL UNIT, CHILLED WATER PIPING,
CONDENSATE PIPING, THERMOSTAT AND BACNET CONTROLS MODULE
CONNECTED TO EXISTING CHILLED WATER SUPPLY/RETURN RISER. SEE RISER
DIAGRAMS FOR CONNECTIONS. LOCATE FAN COIL UNITS ABOVE DOOR.
PROVIDE DRAIN PAN WITH LEAK DETECTION CONNECTED TO BAS.
2. PROVIDE CONDENSATE PUMP, TO BE MOUNTED HIDDEN WITHIN THE INDOOR
UNIT, CAPABLE OF LIFTING UP 50 FEET WITH 8 FEET SUCTION AND 10 GPH
PUMPING CAPACITY. PROVIDE ELECTRICAL SERVICE FOR CONDENSATE PUMP
IF NOT FED FROM INDOOR UNIT. PROVIDE NEW CONDENSATE LINE FOR NEW
MECHANICAL EQUIPMENT, COORDINATE WITH VA. PROVIDE COORDINATION
DRAWINGS FOR EACH DRAIN LINE INSTALLATION PER 01 33 23 PRIOR TO
BEGINNING WORK.
3. PROVIDE NEW DEDICATED THERMOSTAT, COORDINATE FINAL LOCATION WITH
EXISTING AND NEW EQUIPMENT. THERMOSTATS SHALL BE DISPLAY ONLY WITH
CONTROLLABILITY THROUGH THE BMS.
4. PROVIDE BACNET CONTROLLER MOUNTED ADJACENT TO UNIT IN TR. CONNECT
WITH UTP CABLE TO EXISTING ETHERNET SWITCH IN LOCAL TR TO BE
ADDRESSABLE ON VA NETWORK/HVAC FMS.
5. PROVIDE NEW PUMPED CONDENSATE LINE, DROP DOWN ON WALL TO
DISCHARGE OVER EXISTING SINK BELOW, SECURE PIPING TO WALL. PIPE TO BE
CUT AT 45 DEGREE ANGLE AT OUTLET.
6. SEE ARCHITECTURAL DRAWINGS FOR CONTEXT.
7. PROVIDE ELECTRICAL CIRCUIT FOR EACH NEW CHILLED WATER FAN COIL UNIT.
SEE ELECTRICAL SHEETS.
8. EXISTING FACILITY HOUSE AIR THERMOSTAT TO REMAIN, PROTECT IN PLACE.
9. EXISTING CEILING MOUNTED SUPPLY AND RETURN AIR DEVICES TO REMAIN.
COORDINATE WITH REMOVAL OF EXISTING GYPSUM CEILING AND ALL OTHER
TRADES, RESUPPORT AIR DEVICE AS REQUIRED ABOVE CABLE TRAY AND
LIGHTING. SEE SHEET E-501 AND ARCHITECTURAL PLANS FOR ADDITIONAL
INFORMATION.
10. CONTRACTOR SHALL PROVIDE RATED PENETRATION TO MATCH WALL RATING
AT THIS LOCATION. SEE DETAILS ON M-500 SERIES SHEETS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
11. EXISTING PENETRATION TO REMAIN.
12. REBALANCE AIRFLOW AFTER CONSTRUCTION IS COMPLETE.
13. REMOVE RADIATORS AND CAP SERVICE LINES IN THE INTERSTITIAL SPACE.
14. CONNECT TO EXISTING CONDENSATE STACK.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. COORDINATE ALL DUCTWORK AND PIPE ROUTING AND ELEVATIONS WITH
OTHER TRADES IN ADVANCE OF INSTALLATION.
C. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-
CONSTRUCTION TAB REPORT FOR THE EQUIPMENT AND ASSOCIATED
SYSTEMS SHOWN ON THE CONSTRUCTION DOCUMENTS AND UTILIZE
ALL AVAILABLE AS-BUILT DRAWINGS FROM THE OWNER. TEST AND
BALANCE CONTRACTOR SHALL VISIT SITE PRIOR TO CONSTRUCTION
AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND DEVELOP
THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING
EQUIPMENT LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND
TAG NUMBERS. IF THERE ARE LOCATIONS WHERE THE DRAWINGS DO
NOT REFLECT FIELD CONDITIONS, THE TEST AND BALANCE
CONTRACTOR SHALL INCLUDE THE AIRFLOW READINGS ON THE FORMS
AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE ON THE DRAWINGS.
REFER TO SPECIFICATION SECTION 23 05 93 FOR MORE INFORMATION.
D. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED
TO ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND BALANCE DATA
FOR THE RENOVATION. DATA SHALL BE FORWARDED TO THE PROJECT
ENGINEER FOR REVIEW AND COMMENT PRIOR TO COMMENCING THE
DEMOLITION AND/OR NEW WORK ASSOCIATED WITH THE FACILITY
RENOVATION.
E. THE CONTRACTOR SHALL PATCH, PAINT AND RETURN TO MATCH EXISTING
CONDITIONS FOR ANY FLOOR, WALL, OR CEILING THAT WAS DISTURBED TO
COMPLETE THIS PROJECT.
F. ALL NEW THERMOSTATS ARE TO BE MOUNTED AT A HEIGHT OF 54” ABOVE
FINISHED FLOOR. VERIFY FINAL THERMOSTAT LOCATIONS WITH VA.
G. REFER TO ARCHITECTURAL DRAWINGS FOR MOUNTING HEIGHTS AND
ELEVATIONS.
H. ALL PIPING PLACED WITHIN INTERSTITIAL AREA.
NOTE: NOT ALL KEYNOTES ARE
USED ON EACH SHEET
1" = 10'-0" F3
MECHANICAL PLAN - FIRST LEVEL AREA M
1 HR SMOKE BARRIER
SMOKE PARTITION (NON RATED)
NON RATED
PARTITION RATING GRAPHIC DESIGNATION:
PARTITIONS REQUIRED TO BE SMOKE RESISTANT, FIRE RESISTANT, OR BOTH FIRE AND
SMOKE RESISTANT ARE SHOWN GRAPHICALLY ON PLANS WITH HATCH PATTERNS.
CONTRACTOR SHALL CONFIRM ALL FIRE RATED WALL ASSEMBLIES.
1 HR INCIDENTAL USE
70M-105
F1
PIPE DROP
PIPE DROP
1" CD
Elec. Equip. Room
5K-107A 200.00
SF
FCU-5K-13
FCU-5K-14
TYP.
3/4" CD
1" CD
3/4" CD
6 9 12 on e-ei gh th ne fo ot on e-qu ar te r ne fo ot th re e-ei gh th s ne fo ot on e-ha lf ne fo ot th re e-qu ar te r ne fo ot in ch on e ne fo ot on e an d on e-ha lf ne fo ot th re e in ne fo ot
REVISIONS DATE
General Notes:
GENERAL CONTRACTOR AND/OR ALL SUBCONTRACTORS SHALL FIELD VERIFY ALL DIMENSIONS SHOWN ON THESE PLANS AND SHALL BE RESPONSIBLE FOR VARIATIONS BETWEEN PLAN DIMENSIONS AND ACTUAL FIELD DIMENSIONS. WHERE VARIATIONS ARE FOUND TO OCCUR, THE CONTRACTOR SHALL NOTIFY THE PROJECT ENGINEER IN WRITING PRIOR TO PROCEEDING WITH CONSTRUCTION; NO ADJUSTMENT TO
THE WORK WILL BE MADE WITHOUT THE PRIOR APPROVAL OF THE PROJECT ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR GENERAL DEMOLITION INCLUDING REMOVAL OF WALLS, PARTITIONS, DOORS & CEILING & FLOORS. ANY AND ALL CUTTING OF CONCRETE FLOORS, WALLS OR STRUCTURE SHALL BE THE GENERAL CONTRACTOR'S RESPONSIBILITY. CORE DRILLING THROUGH CONCRETE WALLS, FLOORS OR STRUCTURE FOR PIPING OR CONDUIT SHALL BE THE RESPONSIBILITY OF THE SUBCONTRACTOR BY TRADE; FIRESTOPPING OF THESE OPENINGS SHALL BE DONE BY THE RESPECTIVE SUBCONTRACTOR. REMOVAL OF DEBRIS RESULTING FROM DEMOLITION, CUTTING, AND/OR DRILLING IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. PATCHING AND REPAIR OF CONCRETE WALLS, FLOOR, OR STRUCTURE SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR; THIS WILL BE ACCOMPLISHED UPON COMPLETION OF THE INSTALLATION OF ANY AND ALL UTILITIES INSTALLED
BY THE VARIOUS SUBCONTRACTORS.
Approved: Division Chief
Issue Date Checked Drawn
DrawingNumber
Building Number
Project NumberDrawing Title Project Title
Location Drawing Scale
Approved: Service DirectorPlot Scale U.S. Department of Veterans Affairs
Office of Construction and Facilities Management
FULLY SPRINKLERED
Phase
A
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
321 4 5 6 7 8 9 10
GENERAL NOTES
KEYNOTES
A/E:
TRIPLE C - The A/E Group
2508 29th Avenue NE
Minneapolis, MN 55418
(612) 355-1251
Mat Perkins
As indicated
B
IM
/6
-2
-7
E
H R
M I n fr a s tr u c tu re U p g ra d e s M
P L S
V A
M C
/6 -2
-7
.M
E H
R M
.M E
P .B
.L
.r v t
/6
/2
:2 :0
P
M
05/06/2022 M. Perkins G. Weaver
618-21-700
1383 - 70M-105
MECHANICAL PLAN - FIFTH LEVEL
1 Veterans Drive, Minneapolis, MN 55417
B70
EHRM INFRASTRUCTURE
UPGRADESFINAL BID DOCUMENTS
1. PROVIDE PACKAGED NEW FAN COIL UNIT, CHILLED WATER PIPING,
CONDENSATE PIPING, THERMOSTAT AND BACNET CONTROLS MODULE
CONNECTED TO EXISTING CHILLED WATER SUPPLY/RETURN RISER. SEE RISER
DIAGRAMS FOR CONNECTIONS. LOCATE FAN COIL UNITS ABOVE DOOR.
PROVIDE DRAIN PAN WITH LEAK DETECTION CONNECTED TO BAS.
2. PROVIDE CONDENSATE PUMP, TO BE MOUNTED HIDDEN WITHIN THE INDOOR
UNIT, CAPABLE OF LIFTING UP 50 FEET WITH 8 FEET SUCTION AND 10 GPH
PUMPING CAPACITY. PROVIDE ELECTRICAL SERVICE FOR CONDENSATE PUMP
IF NOT FED FROM INDOOR UNIT. PROVIDE NEW CONDENSATE LINE FOR NEW
MECHANICAL EQUIPMENT, COORDINATE WITH VA. PROVIDE COORDINATION
DRAWINGS FOR EACH DRAIN LINE INSTALLATION PER 01 33 23 PRIOR TO
BEGINNING WORK.
3. PROVIDE NEW DEDICATED THERMOSTAT, COORDINATE FINAL LOCATION WITH
EXISTING AND NEW EQUIPMENT. THERMOSTATS SHALL BE DISPLAY ONLY WITH
CONTROLLABILITY THROUGH THE BMS.
4. PROVIDE BACNET CONTROLLER MOUNTED ADJACENT TO UNIT IN TR. CONNECT
WITH UTP CABLE TO EXISTING ETHERNET SWITCH IN LOCAL TR TO BE
ADDRESSABLE ON VA NETWORK/HVAC FMS.
5. PROVIDE NEW PUMPED CONDENSATE LINE, DROP DOWN ON WALL TO
DISCHARGE OVER EXISTING SINK BELOW, SECURE PIPING TO WALL. PIPE TO BE
CUT AT 45 DEGREE ANGLE AT OUTLET.
6. SEE ARCHITECTURAL DRAWINGS FOR CONTEXT.
7. PROVIDE ELECTRICAL CIRCUIT FOR EACH NEW CHILLED WATER FAN COIL UNIT.
SEE ELECTRICAL SHEETS.
8. EXISTING FACILITY HOUSE AIR THERMOSTAT TO REMAIN, PROTECT IN PLACE.
9. EXISTING CEILING MOUNTED SUPPLY AND RETURN AIR DEVICES TO REMAIN.
COORDINATE WITH REMOVAL OF EXISTING GYPSUM CEILING AND ALL OTHER
TRADES, RESUPPORT AIR DEVICE AS REQUIRED ABOVE CABLE TRAY AND
LIGHTING. SEE SHEET E-501 AND ARCHITECTURAL PLANS FOR ADDITIONAL
INFORMATION.
10. CONTRACTOR SHALL PROVIDE RATED PENETRATION TO MATCH WALL RATING
AT THIS LOCATION. SEE DETAILS ON M-500 SERIES SHEETS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
11. EXISTING PENETRATION TO REMAIN.
12. REBALANCE AIRFLOW AFTER CONSTRUCTION IS COMPLETE.
13. REMOVE RADIATORS AND CAP SERVICE LINES IN THE INTERSTITIAL SPACE.
14. CONNECT TO EXISTING CONDENSATE STACK.
A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT, DUCTWORK AND PIPING
WITH STRUCTURAL, MECHANICAL, AND ELECTRICAL SYSTEMS AND SHALL
PROVIDE NECESSARY OFFSETS TO AVOID CONFLICTS AND TO MAINTAIN
REQUIRED EQUIPMENT ACCESS AND SERVICEABILITY.
B. COORDINATE ALL DUCTWORK AND PIPE ROUTING AND ELEVATIONS WITH
OTHER TRADES IN ADVANCE OF INSTALLATION.
C. TEST AND BALANCE CONTRACTOR SHALL PROVIDE A PRE-
CONSTRUCTION TAB REPORT FOR THE EQUIPMENT AND ASSOCIATED
SYSTEMS SHOWN ON THE CONSTRUCTION DOCUMENTS AND UTILIZE
ALL AVAILABLE AS-BUILT DRAWINGS FROM THE OWNER. TEST AND
BALANCE CONTRACTOR SHALL VISIT SITE PRIOR TO CONSTRUCTION
AND VERIFY ALL EXISTING EQUIPMENT AND DEVICES, AND DEVELOP
THEIR TEST AND BALANCE FORMS INCLUDING DRAWINGS SHOWING
EQUIPMENT LOCATIONS, AIR DISTRIBUTION DEVICE LOCATIONS AND
TAG NUMBERS. IF THERE ARE LOCATIONS WHERE THE DRAWINGS DO
NOT REFLECT FIELD CONDITIONS, THE TEST AND BALANCE
CONTRACTOR SHALL INCLUDE THE AIRFLOW READINGS ON THE FORMS
AND LOCATE THE EQUIPMENT AND/OR AIR DEVICE ON THE DRAWINGS.
REFER TO SPECIFICATION SECTION 23 05 93 FOR MORE INFORMATION.
D. ALL DATA OBTAINED VIA TESTING AND MEASURING SHALL BE UTILIZED
TO ESTABLISH NEW HVAC SYSTEM PERFORMANCE AND…