This is a fire alarm inspection and service report for the Fayetteville VAMC Building 1, generated by Vets Fire & Life Safety on November 5, 2025. The comprehensive report documents the testing and maintenance of fire alarm and life safety systems across the facility, covering 777 total devices organized by type and location. The service summary indicates that 45 devices failed or required other attention during inspection, while 732 devices passed testing. Failed items included 10 batteries requiring testing, 11 duct detectors, 6 fan shutdown units, 1 heat detector, 1 pull station, 7 releasing devices, 2 smoke detectors, and 7 speakers.

The inventory and warranty report provides detailed tracking of 777 devices across multiple categories, including 188 speakers, 118 strobes, 88 smoke detectors, 52 programmable relays, 50 pull stations, 50 releasing devices, 44 speaker/strobes, 31 waterflow switches, 29 duct detectors, and various control and supervisory devices. Battery and power supply testing documented 20 sealed lead acid batteries with rated capacities ranging from 8 to 18 amp-hours and 12 volts, all functioning within acceptable parameters. Notably, 19 batteries, 3 fan shutdown units, 3 heat detectors, 2 monitor devices, 5 monitoring units, and 8 power supplies were installed on August 10, 2024, placing them within the one to two-year service window. The zone address report lists all addressable devices by location throughout Building 1, with ScanIDs provided for tracking purposes. Multiple other buildings at the Fayetteville VAMC facility were scheduled for inspection between August 27 and September 15, 2025.

View the file

Other files

File Type Posted
36C25626Q0430 0006.pdf PDF
P09 SOW Fire Alarm Service 41326 final.docx DOCX document
36C25626Q0430 0006.docx DOCX document
36C25626Q0430 0005.docx DOCX document
36C25626Q0430 0004.docx DOCX document
P09 SOW Fire Alarm Service Final 4426.docx DOCX document
36C25626Q0430 0003.docx DOCX document
564-18-135 Complete Dwgs Set.pdf PDF
Questions and answers for 36C25626Q0430 Post.docx DOCX document
P09_SOW Fire Alarm Service Revised.docx DOCX document
backflow information excel.xlsx XLSX spreadsheet
36C25626Q0430 0002.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-1_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-27_FireScan.pdf PDF
2025-08-27 Fayetteville-VAMC-Red-Barn FireScan.pdf PDF
36C25626Q0430 EXHIBIT B.docx DOCX document
36C25626Q0430 EXHIBIT A.docx DOCX document
2025-09-15_Fayetteville-VAMC-Leroy-Pond_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-3_FireScan.pdf PDF
2025-09-15 Fayetteville-VAMC-Bldg-8 FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Parking-Garage_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-37_FireScan.pdf PDF
2025-09-01_Fayetteville-VAMC-Bldg-7_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-11_FireScan.pdf PDF
36C25626Q0430 EXHIBIT C.docx DOCX document
Marmic Fire Sprinkler Inspection Report 1.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-2_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-44_FireScan.pdf PDF
2025-09-01_Fayetteville-VAMC-Bldg-6_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-34_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-40_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-9_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-21_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-4_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-29_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-10_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-5_FireScan.pdf PDF
FACTOR 2.docx DOCX document
FACTOR 1.docx DOCX document
36C25626Q0430 0001.docx DOCX document
P09_SOW Fire Alarm Service.docx DOCX document
36C25626Q0430_1.docx DOCX document
WD 2015-5109.pdf PDF
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Page of 58 89 Service Summary

Vets Fire & Life Safety Download Date: 11/05/2025

Service Summary Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 1 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Failed/Other Battery Tested 10 Duct Detector Tested 11 Fan Shutdown Tested 6 Heat Detector Tested 1 Pull Station Tested 1 Releasing Device Tested 7 Smoke Detector Tested/Cleaned 2 Speaker Tested 7

Total 45

Passed Annunciator Tested 2 Battery Tested 20 Communication Line Tested 2 Communicator Tested 1 Control Panel Tested 2 Duct Detector Battery Replaced 1 Duct Detector Tested 9 Fan Shutdown Tested 4 Fire Pump Running Annual 1 Fire Pump Trouble Annual 1 Heat Detector Tested 5 Monitor Device Tested 2 Monitoring Annual 6 Monitoring Tested 1 Power Supply Tested 5 Programmable Relay Tested 50 Pull Station Tested 40 Releasing Device Tested 41 Remote Test Switch Tested 3 Smoke Detector Tested/Cleaned 80 Speaker/Strobe Tested 44 Speaker Tested 173

Page of 65 89 Battery & Power Supply Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 1 Control Panel: 1 - Notifier The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Passed Sealed Lead Acid 1st E-102 Electrical Room

Near Customer Service 8 12 12.76

Sealed Lead Acid 1st E-102 Electrical Room Near Customer Service

18 12 13.26

Sealed Lead Acid 1st E-102 Electrical Room Near Customer Service

8 12 13 12.47

Sealed Lead Acid 1st E-102-01 ElectricalRoom Near Cust Service

18 12 13.24

Sealed Lead Acid 4th 407-01 Engineering 8 12 12.71 Sealed Lead Acid 4th 407-01 Engineering 8 12 12.74 Sealed Lead Acid Basement Panel Rm Red pwr sup FACP Rm 8 12 12.64

Sealed Lead Acid Basement panel rm Elect Rm FACP Rm BLDG 21 Amp Panel

18 12 13.32

Sealed Lead Acid Panel Rm-Elect Rm-FACP Room

8 12 12.82

Sealed Lead Acid Panel Rm-Elect Rm-FACP Room

8 12 12.68

Sealed Lead Acid Panel Rm-Elect Rm-FACP Room

8 12 12.68

Sealed Lead Acid Panel Rm-Elect Rm-FACP Room

8 12 12.57

Sealed Lead Acid Panel Rm-Elect Rm-FACP Room

8 12 12.66

Sealed Lead Acid Panel Rm-Elect Rm-FACP Room

8 12 12.68

Sealed Lead Acid Panel Rm-Elect Rm-FACP Room

9 12 12.78

Sealed Lead Acid Panel Rm-Elect Rm-FACP Room

9 12 12.87

Sealed Lead Acid Panel Rm-Elect Rm-FACP Room Bldg 21 Amp Panel

18 12 13.28

Sealed Lead Acid Panel Rm-Elect Rm-FACP 8 12 12.71 6.4

Page of 67 89 Inventory & Warranty Report

Vets Fire & Life Safety Download Date: 11/05/2025

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 1 Control Panel: 1 - Notifier The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Annunciator Control 0.26% 2

Battery Control 4.13% 32

Communication Line Control 0.26% 2

Communicator Control 0.13% 1

Control Panel Control 0.26% 2

Duct Detector Initiating 3.75% 29

Fan Shutdown Auxiliary 1.68% 13

Fire Pump Running Supervisory 0.13% 1

Fire Pump Trouble Supervisory 0.13% 1

Heat Detector Initiating 0.78% 6

Monitor Device Monitor 0.26% 2

Monitoring Monitor 0.90% 7

Power Supply Control 1.03% 8

Programmable Relay Auxiliary 6.72% 52

Pull Station Initiating 6.46% 50

Releasing Device Auxiliary 6.46% 50

Remote Test Switch Initiating 0.39% 3

Smoke Detector Initiating 11.37% 88

Speaker Indicating 24.29% 188

Speaker/Strobe Indicating 5.68% 44

Strobe Indicating 15.25% 118

Tamper Switch Supervisory 5.43% 42

Voice Evacuation Control 0.26% 2

Waterflow Switch Initiating 4.01% 31

Type Qty Model # Description Install Date

In Service - 1 Year to 2 Years Notifier

Battery 19 Sealed Lead Acid 08/10/2024 Fan Shutdown 3 08/10/2024 Heat Detector 3 Rate of Rise 08/10/2024 Monitor Device 2 08/10/2024 Monitoring 5 08/10/2024 Power Supply 8 08/10/2024 Programmable Relay 52 08/10/2024

Page of 69 89 Zone Address Report

Vets Fire & Life Safety Download Date: 11/05/2025

Zone Address Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 1 Control Panel: 1 - Notifier The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID 1 Strobe 1st 1-1247 Pharmacy Counseling Booth 58237540 1 Strobe 1st 1259-1 Service Elevator Lobby 1260-1 43811910 1 Strobe 1st 163 Womens RR Near Front Entry 17803852 1 Strobe 1st 166 Mens RR Near Front Entry 17803851 1 Tamper Switch 1st Above Ceiling Hall Outside Rm PC127-

43812282

1 Speaker/Strobe 1st C-1201 C-1201 Hallway Pharmacy 76325331 1 Strobe 1st C-1201 C-1201 Hallway Pharmacy 43811891 1 Waterflow Switch 1st Ceiling Hall Outside Rm PC127-01 43812283 1 Speaker 1st Dock Dock Service Elevator 45935540 1 Strobe 1st Dock Service Elevator 45935538 1 Battery 1st E-102-01 ElectricalRoom Near Cust

Service Sealed Lead Acid 58237571

1 Speaker 1st Emergency Public Entrance Patriots Cafe

17803869

1 Speaker 1st Entrance to Mental Health Hallway 17803834 1 Strobe 1st Hall Pharmacy Corridor Outside 1249-

43811878

1 Strobe 1st Hall PCC110 Near Nurses Station 17803895 1 Speaker/Strobe 1st Hall PCC112 Near Staff Elev 76325318 1 Strobe 1st Hallway 1244-1 Storage/ Pharmacy 43811898 1 Speaker/Strobe 1st Hallway 1250-01 Outside 1244-01 63734435 1 Strobe 1st Hallway 1A Near Nurses Station 17804043 1 Strobe 1st Hallway C101 1242-1 pharmacy 43811900 1 Strobe 1st Hallway C101 1242-1 Pharm 76325323 1 Programmable Relay 1st Hallway C101 Near 1A 43811866 1 Releasing Device 1st Hallway C101 Near 1A Door Holder 17803839 1 Releasing Device 1st Hallway C101 Near 1A Door Holder 17803840 1 Strobe 1st Hallway C101 Near 1A 17803836 1 Strobe 1st Hallway C106 Near Utilization management 17803994

1 Strobe 1st Hallway C107 Near 141-01 Customer Service

17803999

1 Programmable Relay 1st Hallway C110 Near Elevator 58237548 1 Programmable Relay 1st Hallway C111 Near 194-01 17803861 1 Strobe 1st Hallway C111 Near 194-01 17803855

2025-08-27 Bldg-9
2025-08-27 Bldg-11
2025-08-27 -Bldg-37
2025-08-27 Red-Barn
2025-09-01 Bldg 6
2025-09-01 Bldg 7
2025-09-08 Bldg 3
2025-09-08 Bldg 5
2025-09-15 Bldg 29
2025-09-15 Bldg 34
2025-09-15 bldg 44
2025-09-15 LRP
2025-09-15 Bldg 1
2025-09-15 Bldg 8
2025-09-15 Bldg 10
2025-09-15_=Bldg 4
2025-09-15_Bldg 2
2025-09-08 Bldg 40
2025-09-08_Parking garage
2025-09-15 BLDG 21
2025-09-15 bLDG 27

File details come from the government source that posted it. Updated .