This is a fire alarm inspection and service report for the Fayetteville VAMC Building 1, generated by Vets Fire & Life Safety on November 5, 2025. The comprehensive report documents the testing and maintenance of fire alarm and life safety systems across the facility, covering 777 total devices organized by type and location. The service summary indicates that 45 devices failed or required other attention during inspection, while 732 devices passed testing. Failed items included 10 batteries requiring testing, 11 duct detectors, 6 fan shutdown units, 1 heat detector, 1 pull station, 7 releasing devices, 2 smoke detectors, and 7 speakers.
The inventory and warranty report provides detailed tracking of 777 devices across multiple categories, including 188 speakers, 118 strobes, 88 smoke detectors, 52 programmable relays, 50 pull stations, 50 releasing devices, 44 speaker/strobes, 31 waterflow switches, 29 duct detectors, and various control and supervisory devices. Battery and power supply testing documented 20 sealed lead acid batteries with rated capacities ranging from 8 to 18 amp-hours and 12 volts, all functioning within acceptable parameters. Notably, 19 batteries, 3 fan shutdown units, 3 heat detectors, 2 monitor devices, 5 monitoring units, and 8 power supplies were installed on August 10, 2024, placing them within the one to two-year service window. The zone address report lists all addressable devices by location throughout Building 1, with ScanIDs provided for tracking purposes. Multiple other buildings at the Fayetteville VAMC facility were scheduled for inspection between August 27 and September 15, 2025.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Page of 58 89 Service Summary
Vets Fire & Life Safety Download Date: 11/05/2025
Service Summary Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 1 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Failed/Other Battery Tested 10 Duct Detector Tested 11 Fan Shutdown Tested 6 Heat Detector Tested 1 Pull Station Tested 1 Releasing Device Tested 7 Smoke Detector Tested/Cleaned 2 Speaker Tested 7
Total 45
Passed Annunciator Tested 2 Battery Tested 20 Communication Line Tested 2 Communicator Tested 1 Control Panel Tested 2 Duct Detector Battery Replaced 1 Duct Detector Tested 9 Fan Shutdown Tested 4 Fire Pump Running Annual 1 Fire Pump Trouble Annual 1 Heat Detector Tested 5 Monitor Device Tested 2 Monitoring Annual 6 Monitoring Tested 1 Power Supply Tested 5 Programmable Relay Tested 50 Pull Station Tested 40 Releasing Device Tested 41 Remote Test Switch Tested 3 Smoke Detector Tested/Cleaned 80 Speaker/Strobe Tested 44 Speaker Tested 173
Page of 65 89 Battery & Power Supply Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Battery & Power Supply Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 1 Control Panel: 1 - Notifier The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Passed Sealed Lead Acid 1st E-102 Electrical Room
Near Customer Service 8 12 12.76
Sealed Lead Acid 1st E-102 Electrical Room Near Customer Service
18 12 13.26
Sealed Lead Acid 1st E-102 Electrical Room Near Customer Service
8 12 13 12.47
Sealed Lead Acid 1st E-102-01 ElectricalRoom Near Cust Service
18 12 13.24
Sealed Lead Acid 4th 407-01 Engineering 8 12 12.71 Sealed Lead Acid 4th 407-01 Engineering 8 12 12.74 Sealed Lead Acid Basement Panel Rm Red pwr sup FACP Rm 8 12 12.64
Sealed Lead Acid Basement panel rm Elect Rm FACP Rm BLDG 21 Amp Panel
18 12 13.32
Sealed Lead Acid Panel Rm-Elect Rm-FACP Room
8 12 12.82
Sealed Lead Acid Panel Rm-Elect Rm-FACP Room
8 12 12.68
Sealed Lead Acid Panel Rm-Elect Rm-FACP Room
8 12 12.68
Sealed Lead Acid Panel Rm-Elect Rm-FACP Room
8 12 12.57
Sealed Lead Acid Panel Rm-Elect Rm-FACP Room
8 12 12.66
Sealed Lead Acid Panel Rm-Elect Rm-FACP Room
8 12 12.68
Sealed Lead Acid Panel Rm-Elect Rm-FACP Room
9 12 12.78
Sealed Lead Acid Panel Rm-Elect Rm-FACP Room
9 12 12.87
Sealed Lead Acid Panel Rm-Elect Rm-FACP Room Bldg 21 Amp Panel
18 12 13.28
Sealed Lead Acid Panel Rm-Elect Rm-FACP 8 12 12.71 6.4
Page of 67 89 Inventory & Warranty Report
Vets Fire & Life Safety Download Date: 11/05/2025
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 1 Control Panel: 1 - Notifier The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Annunciator Control 0.26% 2
Battery Control 4.13% 32
Communication Line Control 0.26% 2
Communicator Control 0.13% 1
Control Panel Control 0.26% 2
Duct Detector Initiating 3.75% 29
Fan Shutdown Auxiliary 1.68% 13
Fire Pump Running Supervisory 0.13% 1
Fire Pump Trouble Supervisory 0.13% 1
Heat Detector Initiating 0.78% 6
Monitor Device Monitor 0.26% 2
Monitoring Monitor 0.90% 7
Power Supply Control 1.03% 8
Programmable Relay Auxiliary 6.72% 52
Pull Station Initiating 6.46% 50
Releasing Device Auxiliary 6.46% 50
Remote Test Switch Initiating 0.39% 3
Smoke Detector Initiating 11.37% 88
Speaker Indicating 24.29% 188
Speaker/Strobe Indicating 5.68% 44
Strobe Indicating 15.25% 118
Tamper Switch Supervisory 5.43% 42
Voice Evacuation Control 0.26% 2
Waterflow Switch Initiating 4.01% 31
Type Qty Model # Description Install Date
In Service - 1 Year to 2 Years Notifier
Battery 19 Sealed Lead Acid 08/10/2024 Fan Shutdown 3 08/10/2024 Heat Detector 3 Rate of Rise 08/10/2024 Monitor Device 2 08/10/2024 Monitoring 5 08/10/2024 Power Supply 8 08/10/2024 Programmable Relay 52 08/10/2024
Page of 69 89 Zone Address Report
Vets Fire & Life Safety Download Date: 11/05/2025
Zone Address Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 1 Control Panel: 1 - Notifier The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID 1 Strobe 1st 1-1247 Pharmacy Counseling Booth 58237540 1 Strobe 1st 1259-1 Service Elevator Lobby 1260-1 43811910 1 Strobe 1st 163 Womens RR Near Front Entry 17803852 1 Strobe 1st 166 Mens RR Near Front Entry 17803851 1 Tamper Switch 1st Above Ceiling Hall Outside Rm PC127-
43812282
1 Speaker/Strobe 1st C-1201 C-1201 Hallway Pharmacy 76325331 1 Strobe 1st C-1201 C-1201 Hallway Pharmacy 43811891 1 Waterflow Switch 1st Ceiling Hall Outside Rm PC127-01 43812283 1 Speaker 1st Dock Dock Service Elevator 45935540 1 Strobe 1st Dock Service Elevator 45935538 1 Battery 1st E-102-01 ElectricalRoom Near Cust
Service Sealed Lead Acid 58237571
1 Speaker 1st Emergency Public Entrance Patriots Cafe
17803869
1 Speaker 1st Entrance to Mental Health Hallway 17803834 1 Strobe 1st Hall Pharmacy Corridor Outside 1249-
43811878
1 Strobe 1st Hall PCC110 Near Nurses Station 17803895 1 Speaker/Strobe 1st Hall PCC112 Near Staff Elev 76325318 1 Strobe 1st Hallway 1244-1 Storage/ Pharmacy 43811898 1 Speaker/Strobe 1st Hallway 1250-01 Outside 1244-01 63734435 1 Strobe 1st Hallway 1A Near Nurses Station 17804043 1 Strobe 1st Hallway C101 1242-1 pharmacy 43811900 1 Strobe 1st Hallway C101 1242-1 Pharm 76325323 1 Programmable Relay 1st Hallway C101 Near 1A 43811866 1 Releasing Device 1st Hallway C101 Near 1A Door Holder 17803839 1 Releasing Device 1st Hallway C101 Near 1A Door Holder 17803840 1 Strobe 1st Hallway C101 Near 1A 17803836 1 Strobe 1st Hallway C106 Near Utilization management 17803994
1 Strobe 1st Hallway C107 Near 141-01 Customer Service
17803999
1 Programmable Relay 1st Hallway C110 Near Elevator 58237548 1 Programmable Relay 1st Hallway C111 Near 194-01 17803861 1 Strobe 1st Hallway C111 Near 194-01 17803855
| 2025-08-27 Bldg-9 |
| 2025-08-27 Bldg-11 |
| 2025-08-27 -Bldg-37 |
| 2025-08-27 Red-Barn |
| 2025-09-01 Bldg 6 |
| 2025-09-01 Bldg 7 |
| 2025-09-08 Bldg 3 |
| 2025-09-08 Bldg 5 |
| 2025-09-15 Bldg 29 |
| 2025-09-15 Bldg 34 |
| 2025-09-15 bldg 44 |
| 2025-09-15 LRP |
| 2025-09-15 Bldg 1 |
| 2025-09-15 Bldg 8 |
| 2025-09-15 Bldg 10 |
| 2025-09-15_=Bldg 4 |
| 2025-09-15_Bldg 2 |
| 2025-09-08 Bldg 40 |
| 2025-09-08_Parking garage |
| 2025-09-15 BLDG 21 |
| 2025-09-15 bLDG 27 |