This is a Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate for Fayetteville VAMC Building 11 located at 1100 N College Ave, Fayetteville, AR 72703. The inspection was completed on August 27, 2025, by Veterans Fire and Life Safety (Vets Fire & Life Safety), with Inspector Mike Gill performing the work in compliance with The Joint Commission/VHA Standards and the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

The inspection covered six fire alarm system devices across two compliance standards. Under EC 02.03.05 EP 03, three heat detectors located in the 1st Seamstress Shop and 1st Sewing Area, one pull station in the 1st Sewing Area, and one smoke detector in the 1st Transformer Room were tested annually per NFPA 72 (2022) Table 14.4.3.2 (17), with all five devices passing inspection. Under EC 02.03.05 EP 04, one speaker/strobe device in the 1st Transformer Room was tested and passed inspection per NFPA 72 (2022) Table 14.4.3.2 (22). All six devices achieved a 100 percent pass rate with zero failures. All equipment was installed on 08/07/2024 and remains in service within the 1-2 year warranty period. The building contact is Travis Ryan (Safety Specialist), and all inspection results have been documented with individual ScanID numbers and zone addresses for tracking and compliance purposes.

View the file

Other files

File Type Posted
36C25626Q0430 0006.pdf PDF
36C25626Q0430 0006.docx DOCX document
P09 SOW Fire Alarm Service 41326 final.docx DOCX document
36C25626Q0430 0005.docx DOCX document
36C25626Q0430 0004.docx DOCX document
P09 SOW Fire Alarm Service Final 4426.docx DOCX document
Questions and answers for 36C25626Q0430 Post.docx DOCX document
36C25626Q0430 0003.docx DOCX document
564-18-135 Complete Dwgs Set.pdf PDF
P09_SOW Fire Alarm Service Revised.docx DOCX document
backflow information excel.xlsx XLSX spreadsheet
36C25626Q0430 0002.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-29_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-21_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-9_FireScan.pdf PDF
36C25626Q0430 EXHIBIT A.docx DOCX document
2025-09-08_Fayetteville-VAMC-Bldg-40_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-2_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-27_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Leroy-Pond_FireScan.pdf PDF
Marmic Fire Sprinkler Inspection Report 1.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-44_FireScan.pdf PDF
36C25626Q0430 EXHIBIT B.docx DOCX document
combined fire alarm report.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-1_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-3_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-37_FireScan.pdf PDF
2025-09-01_Fayetteville-VAMC-Bldg-6_FireScan.pdf PDF
2025-09-01_Fayetteville-VAMC-Bldg-7_FireScan.pdf PDF
2025-08-27 Fayetteville-VAMC-Red-Barn FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-34_FireScan.pdf PDF
2025-09-15 Fayetteville-VAMC-Bldg-8 FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Parking-Garage_FireScan.pdf PDF
36C25626Q0430 EXHIBIT C.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-4_FireScan.pdf PDF
FACTOR 2.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-10_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-5_FireScan.pdf PDF
FACTOR 1.docx DOCX document
36C25626Q0430 0001.docx DOCX document
WD 2015-5109.pdf PDF
P09_SOW Fire Alarm Service.docx DOCX document
36C25626Q0430_1.docx DOCX document
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate

For

Fayetteville VAMC Bldg 11 1100 N College Ave

Fayetteville, AR 72703 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

Inspection Completion Date Aug 27, 2025

Building: Fayetteville VAMC Bldg 11 Company: Vets Fire & Life Safety Contact: Travis Ryan Contact: Mike Gill

Title: Safety Specialist Title: Inspector Fire Alarm Testing Report

Page of 1 10 Executive Summary

Vets Fire & Life Safety Download Date: 11/05/2025

Executive Summary Generated by: BuildingReports.com

Building Information Building: Fayetteville VAMC Bldg 11 Contact: Travis Ryan

Address: 1100 N College Ave Phone: 479-225-6412

Address: Fax:

City/State/ZIP Code: Fayetteville, AR 72703 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Vets Fire & Life Safety Inspector: Mike Gill

Address: 7 Sherri Lane Phone: 636-543-0165

Address: Fax:

City/State/ZIP Code: St Peters, MO 63376 Mobile:

Country: United States of America Email: mike.gill@vflsc.com

Page of 2 10

Vets Fire & Life Safety Download Date: 11/05/2025

Inspection Completion Date: Aug 27, 2025 Building: Fayetteville VAMC Bldg 11 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Heat Detector 3 3 0 3 0 3

Pull Station 1 1 0 1 0 1

Smoke Detector 1 1 0 1 0 1

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Speaker/Strobe 1 1 0 1 0 1

Total Device Count: 6

Page of 3 10

Vets Fire & Life Safety Download Date: 11/05/2025

Certification

Company: Vets Fire & Life Safety Building: Fayetteville VAMC Bldg 11

Inspector: Mike Gill Contact: Travis Ryan

Page of 4 10 Inspection & Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Inspection & Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 11 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.

(NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Heat Detector 3 3 0 3 3

Device Type Location ScanID Address Q3/24 Q3/25 Heat Detector 1st Seamstress Shop 89471345 1-1-D28 08/10-P 08/27-P Heat Detector 1st Seamstress Shop 89471346 1-1-D29 08/10-P 08/27-P Heat Detector 1st Sewing Area 89471344 1-1-D12 08/10-P 08/27-P

Device Total: 3 Return to Executive Summary

Page of 5 10

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Pull Station 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Q3/25 Pull Station 1st Sewing Area 89471343 1-1-M12 08/10-P 08/27-P

Device Total: 1 Return to Executive Summary

Page of 6 10

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Smoke Detector 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Q3/25 Smoke Detector 1st Transformer Room 89471347 1-1-D11 08/10-P 08/27-P

Page of 7 10

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker/Strobe 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Q3/25 Speaker/Strobe 1st Transformer Room 89471378 1 08/10-P 08/27-P

Page of 8 10 Service Summary

Vets Fire & Life Safety Download Date: 11/05/2025

Service Summary Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 11 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed Heat Detector Tested 3 Pull Station Tested 1 Smoke Detector Tested/Cleaned 1 Speaker/Strobe Tested 1

Total 6 Grand Total 6

Page of 9 10 Inventory & Warranty Report

Vets Fire & Life Safety Download Date: 11/05/2025

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 11 Control Panel: 1 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Heat Detector Initiating 50.00% 3

Pull Station Initiating 16.67% 1

Smoke Detector Initiating 16.67% 1

Speaker/Strobe Indicating 16.67% 1

Type Qty Model # Description Install Date

In Service - 1 Year to 2 Years Heat Detector 3 08/07/2024 Pull Station 1 08/07/2024 Smoke Detector 1 08/07/2024 Speaker/Strobe 1 08/07/2024

Page of 10 10 Zone Address Report

Vets Fire & Life Safety Download Date: 11/05/2025

Zone Address Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 11 Control Panel: 1 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID 1-D11 Smoke Detector 1st Transformer Room 89471347 1-D12 Heat Detector 1st Sewing Area 89471344 1-D28 Heat Detector 1st Seamstress Shop 89471345 1-D29 Heat Detector 1st Seamstress Shop 89471346 1-M12 Pull Station 1st Sewing Area 89471343 javascript:editViewDevice('89471347');

javascript:editViewDevice('89471344');

javascript:editViewDevice('89471345');

javascript:editViewDevice('89471346');

javascript:editViewDevice('89471343');

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
Executive Summary
Inspection & Testing
Service Summary
Inventory & Warranty Report
Zone Address Report

File details come from the government source that posted it. Updated .