2025-09-15_Fayetteville-VAMC-Bldg-4_FireScan.pdf

PDF 198 KB Posted

Attached to
J042--Fire Alarm Service
Solicitation number
36C25626Q0430
Issued by

About this file

This document is a Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate for Fayetteville VAMC Building 4, completed by Veterans Fire & Life Safety on September 15, 2025. The inspection was performed in compliance with The Joint Commission/VHA Standards and the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards. The facility is located at 1100 N College Ave, Fayetteville, AR 72703, with Travis Ryan serving as the building contact and Rod Davis as the inspector/manager from Veterans Fire & Life Safety.

The inspection tested a total of 108 devices across multiple categories, with 105 devices passing and 3 devices remaining untested. Passed devices include 6 batteries, 1 control panel, 2 heat detectors, 1 power supply, 16 programmable relays, 10 pull stations, 9 smoke detectors, 6 speaker/strobes, 17 speakers, 18 strobes, 12 tamper switches, 1 voice evacuation system, and 6 waterflow switches. Untested items include 1 duct detector and 2 fan shutdown devices, all located in the 1st Southeast Mechanical Room and noted as "In Trouble Upon Arrival." The system control unit was installed on August 6, 2024, with software version dated the same day, and is protected by a breaker located in the 1st Fire Panel Room. All tested supervisory signal devices, water flow devices, detectors, manual fire alarm boxes, visual and audible alarms, and auxiliary smoke-detection shutdown devices met applicable NFPA 72 (2022) and NFPA 90A (2024) standards.

View the file

Other files

File Type Posted
36C25626Q0430 0006.pdf PDF
36C25626Q0430 0006.docx DOCX document
P09 SOW Fire Alarm Service 41326 final.docx DOCX document
36C25626Q0430 0005.docx DOCX document
36C25626Q0430 0004.docx DOCX document
P09 SOW Fire Alarm Service Final 4426.docx DOCX document
Questions and answers for 36C25626Q0430 Post.docx DOCX document
36C25626Q0430 0003.docx DOCX document
564-18-135 Complete Dwgs Set.pdf PDF
P09_SOW Fire Alarm Service Revised.docx DOCX document
backflow information excel.xlsx XLSX spreadsheet
36C25626Q0430 0002.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-29_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-21_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-9_FireScan.pdf PDF
36C25626Q0430 EXHIBIT A.docx DOCX document
2025-09-08_Fayetteville-VAMC-Bldg-40_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-2_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-27_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-11_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Leroy-Pond_FireScan.pdf PDF
Marmic Fire Sprinkler Inspection Report 1.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-44_FireScan.pdf PDF
36C25626Q0430 EXHIBIT B.docx DOCX document
combined fire alarm report.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-1_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-3_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-37_FireScan.pdf PDF
2025-09-01_Fayetteville-VAMC-Bldg-6_FireScan.pdf PDF
2025-09-01_Fayetteville-VAMC-Bldg-7_FireScan.pdf PDF
2025-08-27 Fayetteville-VAMC-Red-Barn FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-34_FireScan.pdf PDF
2025-09-15 Fayetteville-VAMC-Bldg-8 FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Parking-Garage_FireScan.pdf PDF
36C25626Q0430 EXHIBIT C.docx DOCX document
FACTOR 2.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-10_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-5_FireScan.pdf PDF
FACTOR 1.docx DOCX document
36C25626Q0430 0001.docx DOCX document
WD 2015-5109.pdf PDF
P09_SOW Fire Alarm Service.docx DOCX document
36C25626Q0430_1.docx DOCX document
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate

For

Fayetteville VAMC Bldg 4 1100 N College Ave

Fayetteville, AR 72703 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

Annual Inspection Inspection Completion Date Sep 15, 2025

Building: Fayetteville VAMC Bldg 4 Company: Vets Fire & Life Safety Contact: Travis Ryan Contact: Rod Davis

Title: Safety Specialist Title: Manager Fire Alarm Testing Report

Page of 1 29 Executive Summary

Vets Fire & Life Safety Download Date: 11/05/2025

Executive Summary Generated by: BuildingReports.com

Building Information Building: Fayetteville VAMC Bldg 4 Contact: Travis Ryan

Address: 1100 N College Ave Phone: 479-225-6412

Address: Fax:

City/State/ZIP Code: Fayetteville, AR 72703 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Vets Fire & Life Safety Inspector: Rod Davis

Address: 7 Sherri Lane Phone: 314-696-7000

Address: Fax:

City/State/ZIP Code: St Peters, MO 63376 Mobile:

Country: United States of America Email: rod.davis@vflsc.com

System Control Unit Manufacturer: Inspection Date: 09/01/2025 IDC Style:

Model Number: Install Date: 08/06/2024 SLC Style:

Software Version: Version Date: 08/06/2024 NAC Style:

Location: 1st Fire Panel Room Current Protection: Breaker

Page of 2 29

Vets Fire & Life Safety Download Date: 11/05/2025

Inspection Completion Date: Sep 15, 2025 Building: Fayetteville VAMC Bldg 4 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Tamper Switch 12 12 0 12 0 12

EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Waterflow Switch 6 6 0 6 0 6

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Duct Detector 0 0 0 0 1 1

Heat Detector 2 2 0 2 0 2

Pull Station 10 10 0 10 0 10

Smoke Detector 9 9 0 9 0 9

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Speaker 17 17 0 17 0 17

Speaker/Strobe 6 6 0 6 0 6

Strobe 18 18 0 18 0 18

Voice Evacuation 1 1 0 1 0 1

EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment.

NFPA 90A (2024) 6.4.1

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Duct Detector 0 0 0 0 1 1

Fan Shutdown 0 0 0 0 2 2

LS 02.01.34 EP 02 Protected master fire alarm control panel

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Control Panel 1 1 0 1 0 1

Page of 3 29

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Battery 6 6 0 6 0 6

Power Supply 1 1 0 1 0 1

Programmable Relay 16 16 0 16 0 16

Total Device Count: 108

Page of 4 29

Vets Fire & Life Safety Download Date: 11/05/2025

Certification

Company: Vets Fire & Life Safety Building: Fayetteville VAMC Bldg 4

Inspector: Rod Davis Contact: Travis Ryan

Page of 5 29 Notes & Recommendations

Vets Fire & Life Safety Download Date: 11/05/2025

Notes & Recommendations Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 4 Control Panel: 1 - The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

Note Device Type Location Comment ScanID

EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;

water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

1 Tamper Switch 1st Passed 43812156 Testing Done By Others

2 Tamper Switch 1st Passed 43812157 Testing Done By Others

3 Tamper Switch 1st Inside Mechanical Room MR1-04 Attic Dry

Passed 43812159

Testing Done By Others 4 Tamper Switch 1st South Stair Passed 43812197

Testing Done By Others 5 Tamper Switch 1st West Lawn Passed 43812222

Testing Done By Others 6 Tamper Switch 2nd South Stair Passed 43812191

Testing Done By Others 7 Tamper Switch 3rd South Stair Passed 43812167

Testing Done By Others 8 Tamper Switch Basement Crawl Space BF Valve 1 Passed 43812216

Testing Done By Others 9 Tamper Switch Basement Crawl Space BF Valve 2 Passed 43812218

Testing Done By Others 10 Tamper Switch Basement South Stair Passed 43812204

Testing Done By Others 11 Tamper Switch Basement South Stair Elevator Equipment

Room Passed 43812214

Testing Done By Others 12 Tamper Switch Basement South Stair Elevator Pit Passed 43812211

Testing Done By Others

EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table

14.4.3.2 (17)(10)(a) & (17)(11) 13 Waterflow Switch 1st South Stair Passed 43812198

Testing Done By Others 14 Waterflow Switch 2nd South Stair Passed 43812192 javascript:editViewDevice('43812156');

javascript:editViewDevice('43812157');

javascript:editViewDevice('43812159');

javascript:editViewDevice('43812197');

javascript:editViewDevice('43812222');

javascript:editViewDevice('43812191');

javascript:editViewDevice('43812167');

javascript:editViewDevice('43812216');

javascript:editViewDevice('43812218');

javascript:editViewDevice('43812204');

javascript:editViewDevice('43812214');

javascript:editViewDevice('43812211');

javascript:editViewDevice('43812198');

javascript:editViewDevice('43812192');

Page of 6 29 Notes & Recommendations

Vets Fire & Life Safety Download Date: 11/05/2025

Note Device Type Location Comment ScanID Testing Done By Others 15 Waterflow Switch 3rd South Stair Passed 43812169

Testing Done By Others 16 Waterflow Switch Basement South Stair Passed 43812205

Testing Done By Others 17 Waterflow Switch Basement South Stair Elevator Equipment

Room Passed 43812212

Testing Done By Others 18 Waterflow Switch Basement South Stair Elevator Pit Passed 43812209

Testing Done By Others

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) 19 Duct Detector 1st Southeast Mechanical Room 45935547

In Trouble Upon Arrival

EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment.

NFPA 90A (2024) 6.4.1

20 Fan Shutdown 1st Southeast Mechanical Room 45935545

In Trouble Upon Arrival 21 Fan Shutdown 1st Southeast Mechanical Room 45935546

In Trouble Upon Arrival javascript:editViewDevice('43812169');

javascript:editViewDevice('43812205');

javascript:editViewDevice('43812212');

javascript:editViewDevice('43812209');

javascript:editViewDevice('45935547');

javascript:editViewDevice('45935545');

javascript:editViewDevice('45935546');

Page of 7 29 Inspection & Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Inspection & Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 4 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 01

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Tamper Switch 12 12 0 12 12

Device Type Location ScanID Address Q3/24 Q3/25 Tamper Switch 1st West Lawn 43812222 1-1-L1 M 08/20-P 09/15-P Tamper Switch Basement Crawl Space BF Valve 2 43812218 1-1-L1 M40 08/20-P 09/15-P Tamper Switch Basement Crawl Space BF Valve 1 43812216 1-1-L1 M39 08/20-P 09/15-P Tamper Switch Basement South Stair Elevator

Equipment Room 43812214 1-1-L1 M21 08/20-P 09/15-P

Tamper Switch Basement South Stair Elevator Pit 43812211 1-1-L1 M23 08/20-P 09/15-P Tamper Switch Basement South Stair 43812204 1-1-L1 M38 08/20-P 09/15-P Tamper Switch 1st South Stair 43812197 1-1-L1 M36 08/20-P 09/15-P Tamper Switch 2nd South Stair 43812191 1-1-L1 M34 08/20-P 09/15-P Tamper Switch 3rd South Stair 43812167 1-1-L1 M32 08/20-P 09/15-P Tamper Switch 1st Inside Mechanical Room MR1-04

Attic Dry 43812159 1-1-L1 M42 08/20-P 09/15-P

Tamper Switch 1st 43812157 1-1 08/20-P 09/15-P Tamper Switch 1st 43812156 1-1 08/20-P 09/15-P

Device Total: 12 Return to Executive Summary

Page of 8 29

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table

14.4.3.2 (17)(11)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Waterflow Switch 6 6 0 6 6

Device Type Location ScanID Address Q3/24 Q3/25 Waterflow Switch Basement South Stair Elevator

Equipment Room 43812212 1-1-L1 M20 08/20-P 09/15-P

Waterflow Switch Basement South Stair Elevator Pit 43812209 1-1-L1 M22 08/20-P 09/15-P Waterflow Switch Basement South Stair 43812205 1-1-L1 M37 08/20-P 09/15-P Waterflow Switch 1st South Stair 43812198 1-1-L1 M35 08/20-P 09/15-P Waterflow Switch 2nd South Stair 43812192 1-1-L1 M33 08/20-P 09/15-P Waterflow Switch 3rd South Stair 43812169 1-1-L1 M31 08/20-P 09/15-P

Device Total: 6 Return to Executive Summary

Page of 9 29

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Duct Detector 0 0 0 0 1

Device Type Location ScanID Address Q3/24 Q3/25 Duct Detector 1st Southeast Mechanical Room 45935547 1 08/06-P

Device Total: 1 Return to Executive Summary

Page of 10 29

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.

(NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Heat Detector 2 2 0 2 2

Device Type Location ScanID Address Q3/24 Q3/25 Heat Detector 1st Elevator Equipment Room 17804535 1-1-L1 D34 09/08-P Heat Detector 1st East First Floor Entrance 16444040 1-1-L1 D1 08/06-P 09/08-P

Device Total: 2 Return to Executive Summary

Page of 11 29

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Pull Station 10 10 0 10 10

Device Type Location ScanID Address Q3/24 Q3/25 Pull Station Basement East Exit 17804531 1-1-L1 M11 08/06-P 09/01-P Pull Station 1st East Exit 17315061 1-1-L1 M8 08/06-P 09/01-P Pull Station 1st West Entrance 17804543 1-1-1 07 08/06-P 09/01-P Pull Station 3rd North Hallway 17804593 1-1-L1 M1 08/06-P 09/01-P Pull Station 2nd South Hallway 17804579 1-1-L1 M4 08/06-P 09/01-P Pull Station 2nd Northeast Hallway 17804571 1-1-L1 M3 08/06-P 09/01-P Pull Station 1st Main Entrance 17804554 1-1-1 06 08/06-P 09/01-P Pull Station 1st Bottom Of Stairs 17804563 1-1-M 11 08/06-P 09/01-P Pull Station 1st East First Floor Entrance 17804561 1-1-1 05 08/06-P 09/01-P Pull Station 3rd South Hallway 17804585 1-1-L1 M2 08/06-P 09/01-P

Device Total: 10 Return to Executive Summary

Page of 12 29

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Smoke Detector 9 9 0 9 9

Device Type Location ScanID Address Q3/24 Q3/25 Smoke Detector 2nd Out Side Elevator 17804575 1-1-L1 D11 09/08-P Smoke Detector 3rd Top Of Elevator Shaft 16444042 1-1-L1 D9 09/08-P Smoke Detector 1st Elevator Equipment Room 17804534 1-1-L1 D30 09/08-P Smoke Detector 1st First Floor Elevator Lobby 17804555 1-1-L1 D19 09/08-P Smoke Detector 3rd Out Side Elevator 17804588 1-1-L1 D6 09/08-P Smoke Detector 1st East Fire Panel Room 17804520 1-1-L1 D12 08/06-P 09/01-P Smoke Detector 1st East First Floor Entrance 17804562 1-1-L1 D26 08/06-P 09/01-P Smoke Detector 1st Basement Chiller Room 17804714 1-L1-D33 08/06-P 09/01-P Smoke Detector 1st East First Floor Entrance 16444041 1-1-L1 D2 08/06-P 09/01-P

Device Total: 9 Return to Executive Summary

Page of 13 29

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker 17 17 0 17 17

Device Type Location ScanID Address Q3/24 Q3/25 Speaker 1st Bottom Of Stairs 17804529 1 08/06-P 09/01-P Speaker 3rd North Hallway By Room 315A-4 17804589 1 08/06-P 09/01-P Speaker 2nd South Office 17804581 1 08/06-P 09/01-P Speaker 3rd South Hallway 17804587 1 08/06-P 09/01-P Speaker 3rd North Hallway 17804584 1 08/06-P 09/01-P Speaker 1st Outside Room 134-04 17804544 1 08/06-P 09/01-P Speaker 2nd South Hallway 17804578 1 08/06-P 09/01-P Speaker 2nd Northeast Hallway By Room 215-

17804570 1 08/06-P 09/01-P

Speaker 2nd South Hallway By Room 213-04 17804576 1 08/06-P 09/01-P Speaker 1st Outside Room 123-04 17804568 1 08/06-P 09/01-P Speaker 1st Outside Room 126-04 17804567 1 08/06-P 09/01-P Speaker 1st South Hallway By Room 137-04 17804551 1 08/06-P 09/01-P Speaker 1st East Outside Room 127-04 17804565 1 08/06-P 09/01-P Speaker 1st Main Entrance Lobby 17804552 1 08/06-P 09/01-P Speaker 1st Outside Room 109-04 17804560 1 08/06-P 09/01-P Speaker 1st Outside Room 106-04 17804556 1 08/06-P 09/01-P Speaker 2nd South Hallway 17804573 1 08/06-P 09/01-P

Device Total: 17 Return to Executive Summary

Page of 14 29

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker/Strobe 6 6 0 6 6

Device Type Location ScanID Address Q3/24 Q3/25 Speaker/Strobe 1st East Hallway HR 63728742 1 08/06-P 09/01-P Speaker/Strobe 1st East Hallway HR 63728743 1 08/06-P 09/01-P Speaker/Strobe 2nd South Hallway Outside Elevator 63728747 1 08/06-P 09/01-P Speaker/Strobe 1st East Hallway HR 63728744 1 08/06-P 09/01-P Speaker/Strobe 2nd South Hallway 63728746 1 08/06-P 09/01-P Speaker/Strobe 2nd South Medical Center Director

Office 63728745 1 08/06-P 09/01-P

Page of 15 29

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Strobe 18 18 0 18 18

Device Type Location ScanID Address Q3/24 Q3/25 Strobe 1st Media Room 137 58237759 1 08/06-P 09/08-P Strobe 1st Main Entrance 17804553 1 08/06-P 09/08-P Strobe 1st Bottom Of Stairs 17804530 1 08/06-P 09/08-P Strobe 3rd East Men's Restroom 17804592 1 08/06-P 09/08-P Strobe 3rd North Hallway 17804594 1 08/06-P 09/08-P Strobe 1st West Entrance by 132-04 17804542 1 08/06-P 09/08-P Strobe 3rd North Women's Restroom 17804591 1 08/06-P 09/08-P Strobe 1st East Women?s Restroom 17804558 1 08/06-P 09/08-P Strobe 1st East Outside Room 109-04 17804559 1 08/06-P 09/08-P Strobe 2nd Northeast Hallway 17804572 1 08/06-P 09/08-P Strobe 2nd West Conference Room 17804577 1 08/06-P 09/08-P Strobe 3rd South Hallway 17804586 1 08/06-P 09/08-P Strobe 2nd South Hallway 17804580 1 08/06-P 09/08-P Strobe 2nd North Women's Restroom 17804574 1 08/06-P 09/08-P Strobe 1st East First Floor Entrance 17804564 1 08/06-P 09/08-P Strobe 1st East Outside Room 118-04 17804569 1 08/06-P 09/08-P Strobe 1st East Men?s Restroom 17804557 1 08/06-P 09/01-P Strobe 1st Southeast Mechanical Room 17804550 1 08/06-P 09/01-P

Device Total: 18 Return to Executive Summary

Page of 16 29

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Voice Evacuation 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Q3/25 Voice Evacuation 1st Fire Panel Room 17804515 1 08/06-P 09/08-P

Page of 17 29

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment.

NFPA 90A (2024) 6.4.1

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Duct Detector 0 0 0 0 1

Device Type Location ScanID Address Q3/24 Q3/25 Duct Detector 1st Southeast Mechanical Room 45935547 1 08/06-P

Page of 18 29

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment.

NFPA 90A (2024) 6.4.1

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Fan Shutdown 0 0 0 0 2

Device Type Location ScanID Address Q3/24 Q3/25 Fan Shutdown 1st Southeast Mechanical Room 45935545 1 08/06-P Fan Shutdown 1st Southeast Mechanical Room 45935546 1 08/07-P

Device Total: 2 Return to Executive Summary

Page of 19 29

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 02 Protected master fire alarm control panel

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Control Panel 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Q3/25 Control Panel 1st Fire Panel Room 17804508 1 08/06-P 09/01-P

Page of 20 29

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Battery 6 6 0 6 6

Device Type Location ScanID Address Q3/24 Q3/25 Battery 1st Fire Panel Room 58237896 1 08/06-F 09/01-P Battery 1st Fire Panel Room 58237895 1 08/06-F 09/01-P Battery 1st Fire Panel Room 58237892 1 08/06-F 09/01-P Battery 1st Fire Panel Room 58237891 1 08/06-F 09/01-P Battery 1st Fire Panel Room Main FACP 58237894 1 08/06-F 09/01-P Battery 1st Fire Panel Room Main Panel 58237893 1 08/06-F 09/01-P

Page of 21 29

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Power Supply 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Q3/25 Power Supply 1st Fire Panel Room 17804525 1 08/06-P 09/01-P

Page of 22 29

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Programmable Relay 16 16 0 16 16

Device Type Location ScanID Address Q3/24 Q3/25 Programmable Relay 1st Fire Panel Room 58237899 1-1-L1 M13 08/07-P 09/08-P Programmable Relay 1st Fire Panel Room 17804510 1-1-L1 M10 08/07-P 09/08-P Programmable Relay 1st Fire Panel Room 17804509 1-1-L1 M16 08/07-P 09/08-P Programmable Relay 1st Fire Panel Room 58237898 1-1-L1 M15 08/07-P 09/08-P Programmable Relay 1st Fire Panel Room 17804516 1-1-L1 M140 08/07-P 09/08-P Programmable Relay 1st Fire Panel Room 17804518 1-1-L1 M142 08/07-P 09/08-P Programmable Relay 1st Fire Panel Room 17804517 1-1-L1 M141 08/07-P 09/08-P Programmable Relay 1st 45935544 1-1-L1 M12 08/07-P 09/08-P Programmable Relay 1st Fire Panel Room 17804524 1-1-L1 M159 08/07-P 09/08-P Programmable Relay 1st Fire Panel Room 17804519 1-1-L1 M143 08/07-P 09/08-P Programmable Relay 1st Fire Panel Room 17804522 1-1-L1 M48 08/07-P 09/08-P Programmable Relay 1st Basement 17804532 1-1-L1 M 08/07-P 09/08-P Programmable Relay 1st Elevator Equipment Room 17804536 1-1-L1 M67 08/07-P 09/08-P Programmable Relay 1st 17804549 1-1-L1 M46 08/07-P 09/08-P Programmable Relay 1st Fire Panel Room 58237890 1-1-L1 M45 08/07-P 09/08-P Programmable Relay 1st Fire Panel Room 58237897 1-1-L1 M14 08/07-P 09/08-P

Device Total: 16 Return to Executive Summary

Page of 23 29 Service Summary

Vets Fire & Life Safety Download Date: 11/05/2025

Service Summary Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 4 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed Battery Tested 6 Control Panel Tested 1 Heat Detector Tested 2 Power Supply Tested 1 Programmable Relay Tested 16 Pull Station Tested 10 Smoke Detector Tested/Cleaned 9 Speaker/Strobe Tested 6 Speaker Tested 17 Strobe Tested 18 Tamper Switch Annual 12 Voice Evacuation Tested 1 Waterflow Switch Annual 6

Total 105

Untested Duct Detector 1 Fan Shutdown 2

Total 3 Grand Total 108

Page of 24 29 Auxiliary Functions Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Auxiliary Functions Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 4 Control Panel: 1 - The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Programmable Relay

1st Passed 17804549 1st Passed 45935544 1st Basement Passed 17804532 1st Elevator Equipment Room Passed 17804536 1st Fire Panel Room Passed 58237897 1st Fire Panel Room Passed 58237890 1st Fire Panel Room Passed 17804522 1st Fire Panel Room Passed 17804519 1st Fire Panel Room Passed 17804524 1st Fire Panel Room Passed 17804517 1st Fire Panel Room Passed 17804518 1st Fire Panel Room Passed 17804516 1st Fire Panel Room Passed 58237898 1st Fire Panel Room Passed 17804509 1st Fire Panel Room Passed 17804510 1st Fire Panel Room Passed 58237899

Untested Duct Detector

AHU Shutdown 1st Southeast Mechanical Room 45935547 javascript:editViewDevice('17804549');

javascript:editViewDevice('45935544');

javascript:editViewDevice('17804532');

javascript:editViewDevice('17804536');

javascript:editViewDevice('58237897');

javascript:editViewDevice('58237890');

javascript:editViewDevice('17804522');

javascript:editViewDevice('17804519');

javascript:editViewDevice('17804524');

javascript:editViewDevice('17804517');

javascript:editViewDevice('17804518');

javascript:editViewDevice('17804516');

javascript:editViewDevice('58237898');

javascript:editViewDevice('17804509');

javascript:editViewDevice('17804510');

javascript:editViewDevice('58237899');

javascript:editViewDevice('45935547');

Page of 25 29 Battery & Power Supply Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 4 Control Panel: 1 - The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Passed Sealed Lead Acid 1st Fire Panel Room 9 12 12.81 Sealed Lead Acid 1st Fire Panel Room 9 12 12.87 Sealed Lead Acid 1st Fire Panel Room 18 12 13.26 Sealed Lead Acid 1st Fire Panel Room 18 12 13.26 Sealed Lead Acid 1st Fire Panel Room Main

FACP

18 12 13.31

Sealed Lead Acid 1st Fire Panel Room Main Panel

18 12 13.35

Page of 26 29 Inventory & Warranty Report

Vets Fire & Life Safety Download Date: 11/05/2025

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 4 Control Panel: 1 - The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Battery Control 5.56% 6

Control Panel Control 0.93% 1

Duct Detector Initiating 0.93% 1

Fan Shutdown Auxiliary 1.85% 2

Heat Detector Initiating 1.85% 2

Power Supply Control 0.93% 1

Programmable Relay Auxiliary 14.81% 16

Pull Station Initiating 9.26% 10

Smoke Detector Initiating 8.33% 9

Speaker Indicating 15.74% 17

Speaker/Strobe Indicating 5.56% 6

Strobe Indicating 16.67% 18

Tamper Switch Supervisory 11.11% 12

Voice Evacuation Control 0.93% 1

Waterflow Switch Initiating 5.56% 6

Type Qty Model # Description Install Date

In Service - 1 Year to 2 Years Heat Detector 1 08/10/2024 Smoke Detector 5 08/10/2024 Programmable Relay 16 08/07/2024 Battery 6 Sealed Lead Acid 08/06/2024 Control Panel 1 08/06/2024 Duct Detector 1 08/06/2024 Fan Shutdown 1 08/06/2024 Fan Shutdown 1 AHU Shutdown 08/06/2024 Heat Detector 1 08/06/2024 Power Supply 1 08/06/2024 Pull Station 10 08/06/2024 Smoke Detector 4 08/06/2024 Speaker 17 08/06/2024 Speaker/Strobe 6 08/06/2024 Strobe 18 08/06/2024 Voice Evacuation 1 08/06/2024

Page of 27 29 Inventory & Warranty Report

Vets Fire & Life Safety Download Date: 11/05/2025

In Service - 25 Years or Older Tamper Switch 12 12/31/1969 Waterflow Switch 6 12/31/1969

Page of 28 29 Zone Address Report

Vets Fire & Life Safety Download Date: 11/05/2025

Zone Address Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 4 Control Panel: 1 - The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID 1 Tamper Switch 1st 43812156 1 Tamper Switch 1st 43812157

1-1 05 Pull Station 1st East First Floor Entrance 17804561 1-1 06 Pull Station 1st Main Entrance 17804554 1-1 07 Pull Station 1st West Entrance 17804543

1-L1 D1 Heat Detector 1st East First Floor Entrance 16444040 1-L1 D2 Smoke Detector 1st East First Floor Entrance 16444041 1-L1 D6 Smoke Detector 3rd Out Side Elevator 17804588 1-L1 D9 Smoke Detector 3rd Top Of Elevator Shaft 16444042

1-L1 D11 Smoke Detector 2nd Out Side Elevator 17804575 1-L1 D12 Smoke Detector 1st East Fire Panel Room 17804520 1-L1 D19 Smoke Detector 1st First Floor Elevator Lobby 17804555 1-L1 D26 Smoke Detector 1st East First Floor Entrance 17804562 1-L1 D30 Smoke Detector 1st Elevator Equipment Room 17804534 1-L1 D34 Heat Detector 1st Elevator Equipment Room 17804535 1-L1 M Programmable Relay 1st Basement 17804532 1-L1 M Tamper Switch 1st West Lawn 43812222 1-L1 M1 Pull Station 3rd North Hallway 17804593 1-L1 M2 Pull Station 3rd South Hallway 17804585 1-L1 M3 Pull Station 2nd Northeast Hallway 17804571 1-L1 M4 Pull Station 2nd South Hallway 17804579 1-L1 M8 Pull Station 1st East Exit 17315061

1-L1 M10 Programmable Relay 1st Fire Panel Room 17804510 1-L1 M11 Pull Station Basement East Exit 17804531 1-L1 M12 Programmable Relay 1st 45935544 1-L1 M13 Programmable Relay 1st Fire Panel Room 58237899 1-L1 M14 Programmable Relay 1st Fire Panel Room 58237897 1-L1 M15 Programmable Relay 1st Fire Panel Room 58237898 1-L1 M16 Programmable Relay 1st Fire Panel Room 17804509 1-L1 M20 Waterflow Switch Basement South Stair Elevator Equipment

Room 43812212

1-L1 M21 Tamper Switch Basement South Stair Elevator Equipment Room

43812214

1-L1 M22 Waterflow Switch Basement South Stair Elevator Pit 43812209 1-L1 M23 Tamper Switch Basement South Stair Elevator Pit 43812211 javascript:editViewDevice('43812156');

javascript:editViewDevice('43812157');

javascript:editViewDevice('17804561');

javascript:editViewDevice('17804554');

javascript:editViewDevice('17804543');

javascript:editViewDevice('16444040');

javascript:editViewDevice('16444041');

javascript:editViewDevice('17804588');

javascript:editViewDevice('16444042');

javascript:editViewDevice('17804575');

javascript:editViewDevice('17804520');

javascript:editViewDevice('17804555');

javascript:editViewDevice('17804562');

javascript:editViewDevice('17804534');

javascript:editViewDevice('17804535');

javascript:editViewDevice('17804532');

javascript:editViewDevice('43812222');

javascript:editViewDevice('17804593');

javascript:editViewDevice('17804585');

javascript:editViewDevice('17804571');

javascript:editViewDevice('17804579');

javascript:editViewDevice('17315061');

javascript:editViewDevice('17804510');

javascript:editViewDevice('17804531');

javascript:editViewDevice('45935544');

javascript:editViewDevice('58237899');

javascript:editViewDevice('58237897');

javascript:editViewDevice('58237898');

javascript:editViewDevice('17804509');

javascript:editViewDevice('43812212');

javascript:editViewDevice('43812214');

javascript:editViewDevice('43812209');

javascript:editViewDevice('43812211');

Page of 29 29 Zone Address Report

Vets Fire & Life Safety Download Date: 11/05/2025

Address Device Type Location Type ScanID 1-L1 M31 Waterflow Switch 3rd South Stair 43812169 1-L1 M32 Tamper Switch 3rd South Stair 43812167 1-L1 M33 Waterflow Switch 2nd South Stair 43812192 1-L1 M34 Tamper Switch 2nd South Stair 43812191 1-L1 M35 Waterflow Switch 1st South Stair 43812198 1-L1 M36 Tamper Switch 1st South Stair 43812197 1-L1 M37 Waterflow Switch Basement South Stair 43812205 1-L1 M38 Tamper Switch Basement South Stair 43812204 1-L1 M39 Tamper Switch Basement Crawl Space BF Valve 1 43812216 1-L1 M40 Tamper Switch Basement Crawl Space BF Valve 2 43812218 1-L1 M42 Tamper Switch 1st Inside Mechanical Room MR1-04 Attic

Dry 43812159

1-L1 M45 Programmable Relay 1st Fire Panel Room 58237890 1-L1 M46 Programmable Relay 1st 17804549 1-L1 M48 Programmable Relay 1st Fire Panel Room 17804522 1-L1 M67 Programmable Relay 1st Elevator Equipment Room 17804536

1-L1 M140 Programmable Relay 1st Fire Panel Room 17804516 1-L1 M141 Programmable Relay 1st Fire Panel Room 17804517 1-L1 M142 Programmable Relay 1st Fire Panel Room 17804518 1-L1 M143 Programmable Relay 1st Fire Panel Room 17804519 1-L1 M159 Programmable Relay 1st Fire Panel Room 17804524

1-M 11 Pull Station 1st Bottom Of Stairs 17804563 L1-D33 Smoke Detector 1st Basement Chiller Room 17804714 javascript:editViewDevice('43812169');

javascript:editViewDevice('43812167');

javascript:editViewDevice('43812192');

javascript:editViewDevice('43812191');

javascript:editViewDevice('43812198');

javascript:editViewDevice('43812197');

javascript:editViewDevice('43812205');

javascript:editViewDevice('43812204');

javascript:editViewDevice('43812216');

javascript:editViewDevice('43812218');

javascript:editViewDevice('43812159');

javascript:editViewDevice('58237890');

javascript:editViewDevice('17804549');

javascript:editViewDevice('17804522');

javascript:editViewDevice('17804536');

javascript:editViewDevice('17804516');

javascript:editViewDevice('17804517');

javascript:editViewDevice('17804518');

javascript:editViewDevice('17804519');

javascript:editViewDevice('17804524');

javascript:editViewDevice('17804563');

javascript:editViewDevice('17804714');

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
Executive Summary
Notes & Recommendations
Inspection & Testing
Service Summary
Auxiliary Functions Testing
Battery & Power Supply Testing
Inventory & Warranty Report
Zone Address Report

File details come from the government source that posted it. Updated .