This is a Fire/Life Safety System Inspection, Testing, and Maintenance Certificate for Fayetteville VAMC Building 2 located at 1100 N College Ave, Fayetteville, AR 72703. The inspection was completed on September 15, 2025, by Veterans Fire & Life Safety, with Rod Davis serving as the inspector and Rod Davis as manager. The work was performed in compliance with The Joint Commission/VHA Standards and the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
The inspection tested 212 total devices across multiple categories including tamper switches (9 units), waterflow switches (9 units), duct detectors (14 units), heat detectors (10 units), smoke detectors (32 units), pull stations (14 units), speakers (40 units), strobes (45 units), releasing devices (5 units), voice evacuation systems (1 unit), monitor devices (6 units), fan shutdown systems (3 units), programmable relays (16 units), remote test switches (3 units), batteries (4 units), and power supplies (1 unit). Of the 212 devices tested, 203 passed and 9 failed or required other action. Failures included 2 duct detectors, 2 heat detectors, 3 smoke detectors, and 2 batteries that require investigation or replacement. The Proposed Solutions Report identifies all discrepancies and recommends repairs on a time and materials basis, with no specific cost estimates provided in the report. The inspection includes detailed testing and maintenance records organized by NFPA and Joint Commission standards, along with inventory and warranty information noting that most equipment was installed between August and October 2024, with tamper and waterflow switches dating to 1969.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Fayetteville VAMC Bldg 2 1100 N College Ave
Fayetteville, AR 72703 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
Annual Inspection Inspection Completion Date Sep 15, 2025
Building: Fayetteville VAMC Bldg 2 Company: Vets Fire & Life Safety Contact: Travis Ryan Contact: Rod Davis
Title: Safety Specialist Title: Manager Fire Alarm Testing Report
Page of 1 42 Executive Summary
Vets Fire & Life Safety Download Date: 11/05/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fayetteville VAMC Bldg 2 Contact: Travis Ryan
Address: 1100 N College Ave Phone: 479-225-6412
Address: Fax:
City/State/ZIP Code: Fayetteville, AR 72703 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Vets Fire & Life Safety Inspector: Rod Davis
Address: 7 Sherri Lane Phone: 314-696-7000
Address: Fax:
City/State/ZIP Code: St Peters, MO 63376 Mobile:
Country: United States of America Email: rod.davis@vflsc.com
Page of 2 42
Vets Fire & Life Safety Download Date: 11/05/2025
Inspection Completion Date: Sep 15, 2025 Building: Fayetteville VAMC Bldg 2 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Tamper Switch 9 9 0 9 0 9
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Waterflow Switch 9 9 0 9 0 9
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Duct Detector 14 12 2 14 0 14
Heat Detector 10 8 2 10 0 10
Pull Station 14 14 0 14 0 14
Smoke Detector 32 29 3 32 0 32
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Releasing Device 5 5 0 5 0 5
Speaker 40 40 0 40 0 40
Strobe 45 45 0 45 0 45
Voice Evacuation 1 1 0 1 0 1
EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Monitor Device 6 6 0 6 0 6
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2024) 6.4.1
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Duct Detector 14 12 2 14 0 14
Fan Shutdown 3 3 0 3 0 3
Page of 3 42
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Battery 4 2 2 4 0 4
Power Supply 1 1 0 1 0 1
Programmable Relay 16 16 0 16 0 16
Remote Test Switch 3 3 0 3 0 3
Total Device Count: 212
Page of 4 42
Vets Fire & Life Safety Download Date: 11/05/2025
Certification
Company: Vets Fire & Life Safety Building: Fayetteville VAMC Bldg 2
Inspector: Rod Davis Contact: Travis Ryan
Page of 5 42 Discrepancy Report
Vets Fire & Life Safety Download Date: 11/05/2025
Discrepancy Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 2 Control Panel: 1 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) Duct Detector
89471363 3rd Stair 5 Above Kitchen Failed Operation 1-3-D48 NFPA72 14.2.2.3.1
89471364 3rd Stair 5 Above Kitchen Failed Operation 1-3-D75 NFPA72 14.2.2.3.1
Heat Detector
17804333 1st 1214-02 Elevator Equipment Room Failed Operation 1-1-L3 40 NFPA72 14.2.2.3.1
16444060 1st 1214-02 Elevator Equipment Room Failed Operation 1-1-L3 41 NFPA72 14.2.2.3.1
Smoke Detector
17804334 1st 1214-02 Elevator Equipment Room Failed Operation 1-1-3 62 NFPA72 14.2.2.3.1
17804191 1st Hallway C1213-02 Building 2 Elevator Lobby
Failed Operation 1-1-3 63 NFPA72 14.2.2.3.1
17804379 3rd Elevator Lobby Failed Operation 1-1-3 49 NFPA72 14.2.2.3.1
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Battery
58237560 1st 1127-02 Mech Room Near MRI lobbybathrooms
Date Expired 1-1 NFPA72 Table
14.4.3.2 (9)(5)
58237561 1st 1127-02 Mech Room Near MRI lobbybathrooms
Date Expired 1-1 NFPA72 Table
14.4.3.2 (9)(5)
Code References NFPA72 14.2.2.3.1 System deficiencies shall be corrected.
NFPA72 Table 14.4.3.2 (9) (5)
Replace the battery or conduct a load test of the battery capacity every 3 years.
javascript:editViewDevice('89471363');
javascript:editViewDevice('89471364');
javascript:editViewDevice('17804333');
javascript:editViewDevice('16444060');
javascript:editViewDevice('17804334');
javascript:editViewDevice('17804191');
javascript:editViewDevice('17804379');
javascript:editViewDevice('58237560');
javascript:editViewDevice('58237561');
Page of 6 42 Proposed Solutions Report
Vets Fire & Life Safety Download Date: 11/05/2025
Proposed Solutions Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 2 Control Panel: 1 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Duct Detector 89471363 3rd Stair 5 Above Kitchen Investigate T/M 89471364 3rd Stair 5 Above Kitchen Investigate T/M
Heat Detector 17804333 1st 1214-02 Elevator Equipment Room Investigate T/M 16444060 1st 1214-02 Elevator Equipment Room Investigate T/M
Smoke Detector 17804334 1st 1214-02 Elevator Equipment Room Investigate T/M 17804191 1st Hallway C1213-02 Building 2 Elevator
Lobby Investigate T/M
17804379 3rd Elevator Lobby Investigate T/M
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Battery 58237560 1st 1127-02 Mech Room Near MRI lobbybathrooms Replace Battery T/M
58237561 1st 1127-02 Mech Room Near MRI lobbybathrooms
Replace Battery T/M
Internal WO/PO #: (none) T/M
Page of 7 42 Notes & Recommendations
Vets Fire & Life Safety Download Date: 11/05/2025
Notes & Recommendations Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 2 Control Panel: 1 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;
water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
1 Tamper Switch 1st Above Ceiling Elevator Lobby Equipment Room
Passed 17804960
Testing Done By Others 2 Tamper Switch 1st Above Ceiling in Hall Outside Elevator
Lobby Passed 46717001
Testing Done By Others 3 Tamper Switch 1st Housek Rm1193-02 Freight Elevator Pit Passed 16444087
Testing Done By Others 4 Tamper Switch 1st MRI Waiting Mech Rm 1127-02 Attic Dry Passed 46717268
Testing Done By Others 5 Tamper Switch 1st MRI Waiting Mechanical Room 1127-02
Dock Dry Passed 46717280
Testing Done By Others 6 Tamper Switch 1st MRI Waiting MechlRoom 1127-02 Passed 46717291
Testing Done By Others 7 Tamper Switch 2nd Stair 6 Passed 46717303
Testing Done By Others 8 Tamper Switch 3rd Stair 5 Room 3303-02Freight Elevr Equi
Rm Passed 17804234
Testing Done By Others 9 Tamper Switch 3rd Stair 6 Passed 46717298
Testing Done By Others
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table
14.4.3.2 (17)(10)(a) & (17)(11) 10 Waterflow Switch 1st Above Ceiling Elevator Lobby Equipment
Room Passed 16444086
Testing Done By Others
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17) 11 Duct Detector 1st 1118-02 HVAC Passed 17804326
Shuts Down Unit 12 Duct Detector 3rd Attic HVAC Passed 43812057 javascript:editViewDevice('17804960');
javascript:editViewDevice('46717001');
javascript:editViewDevice('16444087');
javascript:editViewDevice('46717268');
javascript:editViewDevice('46717280');
javascript:editViewDevice('46717291');
javascript:editViewDevice('46717303');
javascript:editViewDevice('17804234');
javascript:editViewDevice('46717298');
javascript:editViewDevice('16444086');
javascript:editViewDevice('17804326');
javascript:editViewDevice('43812057');
Page of 8 42 Notes & Recommendations
Vets Fire & Life Safety Download Date: 11/05/2025
Note Device Type Location Comment ScanID Shuts Down Unit 13 Duct Detector 3rd Attic HVAC Passed 43812058
Shuts Down Unit 14 Heat Detector 1st 1214-02 Elevator Equipment Room Failed Operation 16444060
Did Not Shunt 15 Heat Detector 1st 1214-02 Elevator Equipment Room Failed Operation 17804333
Do Not Shunt 16 Heat Detector 1st Freight Elevator Passed 16444055
Disabled Upon Arrival 17 Smoke Detector 1st 1214-02 Elevator Equipment Room Failed Operation 17804334
The Elevators Called To Two Different Floors.
RIGHT ELEV. WENT To Wrong Floor.
18 Smoke Detector 1st Hallway C1213-02 Building 2 Elevator Lobby
Failed Operation 17804191
Recalls To Incorrect Floor. Right Elevator Recalls To Incorrect Floor 19 Smoke Detector 3rd Elevator Lobby Failed Operation 17804379
RECALLS to Alternate Floor. Should Go To Primary Floor 20 Duct Detector 1st Mech Room 1188 Passed 89471369
Shuts Down Unit 21 Duct Detector 1st Mech Room 1188 Passed 89471370
Shuts Down Unit 22 Duct Detector 3rd Stair 5 Above Kitchen Failed Operation 89471363
Did Not Shut Down Unit 23 Duct Detector 3rd Stair 5 Above Kitchen Failed Operation 89471364
Did Not Shut Down Unit javascript:editViewDevice('43812058');
javascript:editViewDevice('16444060');
javascript:editViewDevice('17804333');
javascript:editViewDevice('16444055');
javascript:editViewDevice('17804334');
javascript:editViewDevice('17804191');
javascript:editViewDevice('17804379');
javascript:editViewDevice('89471369');
javascript:editViewDevice('89471370');
javascript:editViewDevice('89471363');
javascript:editViewDevice('89471364');
Page of 9 42 Inspection & Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Inspection & Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 2 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Tamper Switch 9 9 0 9 9
Device Type Location ScanID Address Q3/24 Q3/25 Tamper Switch 2nd Stair 6 46717303 1-1-L3 M97 08/20-P 09/15-P Tamper Switch 3rd Stair 6 46717298 1-1-L3 M93 08/20-P 09/15-P Tamper Switch 1st MRI Waiting MechlRoom 1127-02 46717291 1-1-L3 M9 08/20-P 09/15-P Tamper Switch 1st MRI Waiting Mechanical Room
1127-02 Dock Dry 46717280 1-1-L3 M148 08/20-P 09/15-P
Tamper Switch 1st MRI Waiting Mech Rm 1127-02 Attic Dry
46717268 1-1-L3 M8 08/20-P 09/15-P
Tamper Switch 1st Above Ceiling in Hall Outside Elevator Lobby
46717001 1-1-L3 M159 08/20-P 09/15-P
Tamper Switch 1st Above Ceiling Elevator Lobby Equipment Room
17804960 1-1-L3 M158 08/20-P 09/15-P
Tamper Switch 3rd Stair 5 Room 3303-02Freight Elevr Equi Rm
17804234 1-1-L3 M113 08/20-P 09/15-P
Tamper Switch 1st Housek Rm1193-02 Freight Elevator Pit
16444087 1-1-L3 M111 08/20-P 09/15-P
Device Total: 9 Return to Executive Summary
Page of 10 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table
14.4.3.2 (17)(11)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Waterflow Switch 9 9 0 9 9
Device Type Location ScanID Address Q3/24 Q3/25 Waterflow Switch 3rd Stair 5 Room 3303-02 Freight
Eleva Equip Rm 46717407 1-1-L3 M112 08/20-P 09/15-P
Waterflow Switch 2nd Stair 6 46717305 1-1-L3 M98 08/20-P 09/15-P Waterflow Switch 3rd Stair 6 46717300 1-1-L3 M32 08/20-P 09/15-P Waterflow Switch 1st MRI Waiting Mech Rm 1127-02
1st Floor 46717293 1-1-L3 M45 08/20-P 09/15-P
Waterflow Switch 1st MRI Waiting Mechanical Room 1127-02 Dock Dry
46717287 1-1-L3 M149 08/20-P 09/15-P
Waterflow Switch 1st MRI Waiting Mech Rm 1127-02 Attic Dry
46717275 1-1 08/20-P 09/15-P
Waterflow Switch 1st Housek Rm1193-02 Freight Elev Pit
16444088 1-1-L3 M110 08/20-P 09/15-P
Waterflow Switch 1st Above Ceiling in Hall Outside Elevator Lobby
46717006 1-1-L3 M109 08/20-P 09/15-P
Waterflow Switch 1st Above Ceiling Elevator Lobby Equipment Room
16444086 1-1-L3 M108 08/20-P 09/15-P
Device Total: 9 Return to Executive Summary
Page of 11 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Duct Detector 14 12 2 14 14
Device Type Location ScanID Address Q3/24 Q3/25 Duct Detector 3rd AHU Room HVAC Room Behind
Engineering 45935282 1-1 08/07-P 09/08-P
Duct Detector 3rd AHU Room HVAC Room Behind Engineering
45935275 1-1 08/07-P 09/08-P
Duct Detector 3rd AHU Room HVAC Room Behind Engineering
45935281 1-1 08/07-P 09/02-P
Duct Detector 1st 1118-02 HVAC 17804326 1-1 08/07-P 09/02-P Duct Detector 3rd Attic HVAC 43812058 1-1 08/07-P 09/02-P Duct Detector 3rd Attic HVAC 43812057 1-1 08/07-P 09/02-P Duct Detector 1st AC Equipment Room 2-12 89471371 1-3-D65 08/10-P 09/08-P Duct Detector 1st Mech Room 1188 89471370 1-3-D24 08/10-P 09/02-P Duct Detector 1st Mech Room 1188 89471369 1-3-D7 08/10-P 09/02-P Duct Detector 1st MRI Mrch Room 89471366 1-3-D24 08/10-P 09/08
Removed Duct Detector 1st MRI Room MB-3 89471365 1-3-M46 08/10-P 09/08
Removed Duct Detector 3rd Elevator Lobby 89471372 1-3-D49 08/10-P 09/08-P Duct Detector 3rd LAB Attic 89471367 1-3-D116 08/10-P 09/08-P Duct Detector 3rd LAB Attic 89471368 1-3-D115 08/10-P 09/08-P Duct Detector 3rd Stair 5 Above Kitchen 89471363 1-3-D48 08/10-P 09/02-F Duct Detector 3rd Stair 5 Above Kitchen 89471364 1-3-D75 08/10-P 09/02-F
Device Total: 14 Return to Executive Summary
Page of 12 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.
(NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Heat Detector 10 8 2 10 10
Device Type Location ScanID Address Q3/24 Q3/25 Heat Detector 1st Mechanical Room Near MRI
Lobby Bathrooms 43811998 1-1-3 150 08/05-P 09/08-P
Heat Detector 3rd 17804678 1-1-3 61 08/05-P 09/08-P Heat Detector 1st 1127-02 Mech Room Near MRI
Lobby RR 17804954 1-1-L3 23 08/05-P 09/08-P
Heat Detector 3rd Attic Attic 16444032 1-1-3 50 08/05-P 09/08-P Heat Detector 3rd Attic Attic 16444033 1-1-3 50 08/05-P 09/08-P Heat Detector 1st Freight Elevator 16444055 1-1-3 79 09/08-P Heat Detector 3rd Elev Equip Rm in 2133-02 Eng
Rm 3303-02 45935271 1-1-3 79 08/28-P
Heat Detector 1st Bottom of Staff Elevator Shaft 16444051 1-1-3 81 08/28-P Heat Detector 1st 1214-02 Elevator Equipment
Room 16444060 1-1-L3 41 08/28-F
Heat Detector 1st 1214-02 Elevator Equipment Room
17804333 1-1-L3 40 08/28-F
Device Total: 10 Return to Executive Summary
Page of 13 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Pull Station 14 14 0 14 14
Device Type Location ScanID Address Q3/24 Q3/25 Pull Station 2nd kitchen By Door 2133-02 45935266 1-1-3 35 08/05-P 09/08-P Pull Station 2nd Dock Exit Kitchen 45935285 1-1-3 35 08/05-P 09/08-P Pull Station 1st Hallway C1001-02 Near 1101-02
& 1102-02 17804188 1-1-3 46 08/05-P 09/08-P
Pull Station 2nd kitchen By Freezer 45935263 1-1-3 35 08/05-P 09/08-P Pull Station 1st Hallway C1001-02 Near 1101-02
& 1102-02 17804202 1-1-3 71 08/05-P 09/08-P
Pull Station 2nd In Dish Room 45935247 1-1-3 46 08/05-P 09/08-P Pull Station 2nd In serving Room Door 45935252 1-1-3 46 08/05-P 09/08-P Pull Station 2nd In Dish Room by Stair 6 45935249 1-1-3 140 08/05-P 09/08-P Pull Station 2nd Dinning Room Exit Door 45935258 1-1-3 35 08/05-P 09/08-P Pull Station 3rd Corridor Corridor 3004-2 43812072 1-1-L3 27 08/05-P 08/25-P Pull Station 3rd Attic Attic Off 3rd floor bldg2 43812052 1-1-3 65 08/05-P 08/25-P Pull Station 3rd Corridor Corridor 3003-2 at stair
6 door 43812051 1-1-L3 28 08/05-P 08/25-P
Pull Station 3rd Corridor Corridor 3003 43812074 1-1-3 71 08/05-P 08/25-P Pull Station 3rd Corridor Corridor 3003 by Door for Stair 4 43812078 1-1-3 78 08/05-P 08/25-P
Page of 14 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Smoke Detector 32 29 3 32 32
Device Type Location ScanID Address Q3/24 Q3/25 Smoke Detector 1st Computer 1186-02 Computer
1186-02 43811996 1-1-3 74 08/05-P 09/08-P
Smoke Detector 2nd Rm 2114-02 Dinning Rm on Ramp
45935284 1-1-3 47 08/05-P 09/08-P
Smoke Detector 2nd In 2133-02 Engineering Rm 3302-02
45935277 1-1-3 52 08/05-P 09/08-P
Smoke Detector 2nd In Serving Room Door 45935254 1-1-3 47 08/10-P 09/08-P Smoke Detector 2nd Kitchen Supervisor arm 2119-02 45935251 1-1-3 76 08/05-P 09/08-P Smoke Detector 2nd Rm 2114-02 By Door Dinning Rm 45935257 1-1-3 47 08/05-P 09/08-P Smoke Detector 2nd In 2133-02 Engineering Rm
3302-02 45935278 1-1-3 52 08/05-P 09/08-P
Smoke Detector 2nd kitchen By 2133-02 Engineering 45935268 1-1-3 52 08/05-P 09/08-P Smoke Detector 2nd Kitchen Outside Elevator 45935269 1-1-3 52 08/10-P 09/08-P Smoke Detector 2nd In 2133-02 Engineering Rm
3303-02 45935272 1-1-3 52 08/05-P 09/08-P
Smoke Detector 1st In 1197-02 17804973 1-1-3 84 08/05-P 09/08-P Smoke Detector 2nd Freight Elevator 17804232 1-1-3 47 08/28-P Smoke Detector 1st Freight Elevator Lobby 17804223 1-1-3 84 08/28-P Smoke Detector 1st Freight Elevator Pit 16444054 1-1-3 74 08/28-P Smoke Detector 2nd Elevator Lobby 17804264 1-1-3 52 08/28-P Smoke Detector 2nd Top of Freight Elevator Shaft 16444053 1-1-3 59 08/28-P Smoke Detector 1st Bottom of Staff Elevator Shaft 16444050 1-1-3 80 08/28-P Smoke Detector 3rd Top of Staff Elevator 16444034 1-1-3 50 08/28-P Smoke Detector 1st Computer room 021185-02
MRIComp Rm under Flr 43811997 1-1-3 73 08/10-P 08/25-P
Smoke Detector 2nd Outside Rm 2102-02 45935246 1-1-3 47 08/05-P 08/25-P Smoke Detector 1st Computer 1185-02 Computer
1185-02 17804662 1-1-3 74 08/05-P 08/25-P
Smoke Detector 1st Hallway C1001-02 Near 1101-02 & 1102-02
17804189 1-1-3 64 08/05-P 08/25-P
Smoke Detector 1st Hallway C1001-02 Near 1101-02 & 1102-02
17804187 1-L1-51 08/05-P 08/25-P
Smoke Detector 2nd Stairwell # 6 lobby 45935289 1-1-3 47 08/05-P 08/25-P Smoke Detector 2nd Rm 2114-02 In ServingRoom
Door 45935400 1-1-3 47 08/10-P 08/25-P
Smoke Detector 3rd Corridor Corridor 3003 43812073 1-1-3 49 08/05-P 08/25-P
Page of 15 42
Vets Fire & Life Safety Download Date: 11/05/2025
Device Type Location ScanID Address Q3/24 Q3/25 Smoke Detector 3rd Corridor Corridor 3004-2 43812071 1-1-3 49 08/05-P 08/25-P Smoke Detector 3rd 17804677 1-1-3 36 08/05-P 08/25-P Smoke Detector 3rd Corridor Corridor 3005-02 17804283 1-1-3 50 08/05-P 08/25-P Smoke Detector 3rd Elevator Lobby 17804379 1-1-3 49 08/05-P 08/28-F Smoke Detector 1st Hallway C1213-02 Building 2
Elevator Lobby 17804191 1-1-3 63 08/28-F
Smoke Detector 1st 1214-02 Elevator Equipment Room
17804334 1-1-3 62 08/28-F
Device Total: 32 Return to Executive Summary
Page of 16 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Releasing Device 5 5 0 5 5
Device Type Location ScanID Address Q3/24 Q3/25 Releasing Device 3rd Corridor Corridor 3003 43812079 1-1 08/07-P 09/08-P Releasing Device 3rd Corridor Corridor 3003 43812080 1-1 08/07-P 09/08-P Releasing Device 1st Hallway C1010-02 Near Biomed
& Electronics 17804185 1-1 08/07-P 09/08-P
Releasing Device 3rd Corridor Corridor 3005-2 17804285 1-1 08/07-P 09/08-P Releasing Device 1st Hallway C1010-02 Near Biomed
& Electronics 17804184 1-1 08/07-P 09/08-P
Device Total: 5 Return to Executive Summary
Page of 17 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker 40 40 0 40 40
Device Type Location ScanID Address Q3/24 Q3/25 Speaker 2nd Server Line 45935291 1-1 08/06-P 09/08-P Speaker 1st Hallway C1001-02 Near 1104-02
& 1102-02 17804186 1-1 08/06-P 09/08-P
Speaker 1st MRI MRI waiting room 17804201 1-1 08/06-P 09/08-P Speaker 1st Hallway C1010-02 Near Biomed
& Electronics 17804196 1-1 08/06-P 09/08-P
Speaker 1st Hallway C1001-02 Near Biomed
& MRI
17804192 1-1 08/06-P 09/08-P
Speaker 1st Hallway By 1151-02 17804208 1-1 08/06-P 09/08-P Speaker 1st MRI MRI waiting room 17804200 1-1 08/06-P 09/08-P Speaker 2nd Server Line 45935290 1-1 08/06-P 09/08-P Speaker 1st Hallway By 1171-02 17804216 1-1 08/06-P 09/08-P Speaker 1st 1111-02 Biomed 17804324 1-1 08/06-P 09/08-P Speaker 2nd Kitchen By Freezer 45935265 1-1 08/06-P 09/08-P Speaker 2nd 2114-02 Dinning Room 45935262 1-1 08/06-P 09/08-P Speaker 2nd 2114-02 Dinning Room 45935261 1-1 08/06-P 09/08-P Speaker 3rd Corridor Corridor 3001-2 43812042 1-1 08/06-P 09/08-P Speaker 2nd 2114-02 Dinning Room 45935260 1-1 08/06-P 09/08-P Speaker 2nd Hallway Building 2 Outside Rm
2102-02 45935245 1-1 08/06-P 09/08-P
Speaker 3rd Corridor Corridor 3003 43812076 1-1 08/06-P 09/08-P Speaker 3rd Corridor Corridor 3003 43812077 1-1 08/06-P 09/08-P Speaker 3rd Corridor Corridor 3004-2 43812070 1-1 08/06-P 09/08-P Speaker 3rd Corridor Corridor 3004-2 43812066 1-1 08/06-P 09/08-P Speaker 3rd Corridor Corridor 3003-2 43812050 1-1 08/06-P 09/08-P Speaker 3rd Corridor Corridor 3002-2 43812060 1-1 08/06-P 09/08-P Speaker 3rd Corridor Corridor 3003-2 43812048 1-1 08/06-P 09/08-P Speaker 3rd Corridor Corridor 3001-2 43812044 1-1 08/06-P 09/08-P Speaker 2nd Hallway Outside Building 2
Elevator 43812041 1-1 08/06-P 09/08-P
Speaker 1st 1120-02 Biomed 17804325 1-1 08/06-P 09/08-P Speaker 1st MRI MRI 17804664 1-1 08/06-P 09/08-P Speaker 1st MRI MRI control room 17804663 1-1 08/06-P 09/08-P Speaker 1st MRI MRI 1141-02 Inpatient
Holding 17804332 1-1 08/06-P 09/08-P
Speaker 1st MRI MRI 1143-02 Outpatient 17804328 1-1 08/06-P 09/08-P
Page of 18 42
Vets Fire & Life Safety Download Date: 11/05/2025
Device Type Location ScanID Address Q3/24 Q3/25 Holding
Speaker 1st Hallway C1010-02 Near Biomed & Electronics
17804195 1-1 08/06-P 09/08-P
Speaker 1st Hallway C1001-02 Near Biomed
& MRI
17804194 1-1 08/06-P 09/08-P
Speaker 3rd In Front of bldg2 Elevators Corridor
17804286 1-1 08/06-P 09/08-P
Speaker 2nd Kitchen Dishwasher 17804249 1-1 08/06-P 09/08-P Speaker 2nd Kitchen Prep line 17804237 1-1 08/06-P 09/08-P Speaker 1st Hallway By Room 1195-92 17804225 1-1 08/06-P 09/08-P Speaker 1st Hallway By 1162-02 17804218 1-1 08/06-P 09/08-P Speaker 1st Hallway By 1164-02 17804220 1-1 08/06-P 09/08-P Speaker 1st Hallway C1213-02 Building 2
Elevator Lobby 17804190 1-1 08/06-P 09/08-P
Speaker 1st 1151-02 1151-02 Break Room 17804210 1-1 08/06-P 09/08-P
Device Total: 40 Return to Executive Summary
Page of 19 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Strobe 45 45 0 45 45
Device Type Location ScanID Address Q3/24 Q3/25 Strobe 2nd In Rm 2108-02 16444062 1-1-47 08/07-P 09/08-P Strobe 1st Hallway By MRI Reception 45935412 1-1-3 47 08/07-P 09/08-P Strobe 1st MRI women?s restroom MRI women?s restroom 17804199 1-1 08/06-P 09/08-P
Strobe 2nd Kitchen Dock Exit 45935286 1-1-47 08/07-P 09/08-P Strobe 1st MRI waiting room MRI waiting room 17804197 1-1 08/06-P 09/08-P
Strobe 3rd Corridor Corridor 3005-2 17804282 1-1 08/06-P 09/08-P Strobe 1st MRI MRI 17804654 1-1 08/07-P 09/08-P Strobe 1st Stairwell Women?s Restroom 17804226 1-1-47 08/06-P 09/08-P Strobe 1st Stairwell Restroom 17804224 1-1-47 08/06-P 09/08-P Strobe 1st In Restroom In Women?s Locker
Room 1152-02 17804212 1-1-47 08/06-P 09/08-P
Strobe 3rd Blood Bank Blood Bank 3215-02 43812067 1-1 08/07-P 09/08-P Strobe 3rd Office Office 3212-02 43812061 1-1 08/07-P 09/08-P Strobe 2nd In Dining Area On Ramp 45935283 1-1-47 08/07-P 09/08-P Strobe 2nd In 2133-02 Engineering 3303-02 45935279 1-1-47 08/07-P 09/08-P Strobe 3rd Blood Bank Blood Bank 3215-02 43812069 1-1 08/07-P 09/08-P Strobe 2nd In Kitchen By Freezer 45935264 1-1-47 08/07-P 09/08-P Strobe 2nd In 2133-02 Engineering 3303-02 45935267 1-1-47 08/07-P 09/08-P Strobe 3rd Corridor Corridor 3003 43812075 1-1 08/07-P 09/08-P Strobe 2nd In Dining Area 45935259 1-1-47 08/07-P 09/08-P Strobe 2nd In Side Serving Area Door 45935253 1-1-47 08/07-P 09/08-P Strobe 2nd In Dish Area By Stair 6 45935250 1-1-47 08/07-P 09/08-P Strobe 2nd In Dish Area 45935248 1-1-47 08/07-P 09/08-P Strobe 3rd Office Office 3217-02 43812065 1-1 08/07-P 09/08-P Strobe 3rd Office Office 3218-02 43812063 1-1 08/07-P 09/08-P Strobe 3rd Corridor Corridor 3002-2 43812062 1-1 08/07-P 09/08-P Strobe 3rd Attic Attic Above Pull Station 43812053 1-1 08/07-P 09/08-P Strobe 3rd Corridor Corridor 3003-2 43812049 1-1 08/07-P 09/08-P Strobe 3rd Conference Conference 3202-2 43812047 1-1 08/07-P 09/08-P Strobe 3rd Bathroom Corridor 3001-2 bathroom 43812046 1-1 08/06-P 09/08-P
Strobe 3rd Bathroom Corridor 3001-2 bathroom
43812045 1-1 08/07-P 09/08-P
Strobe 3rd Corridor Corridor 3001-2 43812043 1-1 08/07-P 09/08-P
Page of 20 42
Vets Fire & Life Safety Download Date: 11/05/2025
Device Type Location ScanID Address Q3/24 Q3/25 Strobe 1st MRI MRI 1141-02 inpatient holding 17804331 1-1 08/07-P 09/08-P
Strobe 1st MRI MRI 1143-02 outpatient holding
17804329 1-1 08/06-P 09/08-P
Strobe 1st MRI MRI 1145-02 outpatient holding
17804330 1-1 08/06-P 09/08-P
Strobe 1st Hallway by Storage 1164-02 17804219 1-1-47 08/06-P 09/08-P Strobe 1st 1151-02 1151-02 Break Room 17804213 1-1 08/06-P 09/08-P Strobe 1st Hallway By Room 1151-02 17804207 1-1-47 08/06-P 09/08-P Strobe 1st 1153-02 1153-02 Locker Room
Men?s 17804214 1-1 08/06-P 09/08-P
Strobe 1st Hallway By Room 1171-02 17804217 1-1-47 08/06-P 09/08-P Strobe 1st 1153-02 1153-02 Rest Room
Men?s 17804215 1-1 08/06-P 09/08-P
Strobe 1st 1151-02 1151-02 Break Room 17804209 1-1 08/06-P 09/08-P Strobe 1st 1153-02 1153-02 Locker Room
Women?s 17804211 1-1 08/06-P 09/08-P
Strobe 1st MRI waiting room MRI waiting room
17804203 1-1 08/06-P 09/08-P
Strobe 1st Hallway By MRI Reception 17804193 1-1-47 08/06-P 09/08-P Strobe 1st MRI men?s restroom MRI men?s restroom 17804198 1-1 08/06-P 09/08-P
Device Total: 45 Return to Executive Summary
Page of 21 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Voice Evacuation 1 1 0 1 1
Device Type Location ScanID Address Q3/24 Q3/25 Voice Evacuation 1st 1127-02 Mech Room Near MRI
LobbyBathrooms 17804949 1-1 08/07-P 09/08-P
Device Total: 1 Return to Executive Summary
Page of 22 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 05
Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)
Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-22 Table 14.4.3.2 (4)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Monitor Device 6 6 0 6 6
Device Type Location ScanID Address Q3/24 Q3/25 Monitor Device 1st 1197-02 17804974 1-1-3 55 08/07-P 09/08-P Monitor Device 1st 1127-02 Mech Room Near MRI lobbybathrooms 58237556 1-1-3 148 08/07-P 09/08-P
Monitor Device 1st 1127-02 Mech Room Near MRI lobbybathrooms
58237555 1-1-L3 9 08/07-P 09/08-P
Monitor Device 2nd 1127-02 Above Kitchen Hood 45935288 1-1-3 144 08/07-P 09/08-P Monitor Device 1st 1197-02 17804975 1-1-3 114 08/07-P 09/08-P Monitor Device 1st 1127-02 Mech Room Near MRI
LobbyBathrooms 17804953 1-1-3 45 08/07-P 09/08-P
Device Total: 6 Return to Executive Summary
Page of 23 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2024) 6.4.1
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Duct Detector 14 12 2 14 14
Device Type Location ScanID Address Q3/24 Q3/25 Duct Detector 3rd AHU Room HVAC Room Behind
Engineering 45935282 1-1 08/07-P 09/08-P
Duct Detector 3rd AHU Room HVAC Room Behind Engineering
45935275 1-1 08/07-P 09/08-P
Duct Detector 3rd AHU Room HVAC Room Behind Engineering
45935281 1-1 08/07-P 09/02-P
Duct Detector 1st 1118-02 HVAC 17804326 1-1 08/07-P 09/02-P Duct Detector 3rd Attic HVAC 43812058 1-1 08/07-P 09/02-P Duct Detector 3rd Attic HVAC 43812057 1-1 08/07-P 09/02-P Duct Detector 1st AC Equipment Room 2-12 89471371 1-3-D65 08/10-P 09/08-P Duct Detector 1st Mech Room 1188 89471370 1-3-D24 08/10-P 09/02-P Duct Detector 1st Mech Room 1188 89471369 1-3-D7 08/10-P 09/02-P Duct Detector 1st MRI Mrch Room 89471366 1-3-D24 08/10-P 09/08
Removed Duct Detector 1st MRI Room MB-3 89471365 1-3-M46 08/10-P 09/08
Removed Duct Detector 3rd Elevator Lobby 89471372 1-3-D49 08/10-P 09/08-P Duct Detector 3rd LAB Attic 89471367 1-3-D116 08/10-P 09/08-P Duct Detector 3rd LAB Attic 89471368 1-3-D115 08/10-P 09/08-P Duct Detector 3rd Stair 5 Above Kitchen 89471363 1-3-D48 08/10-P 09/02-F Duct Detector 3rd Stair 5 Above Kitchen 89471364 1-3-D75 08/10-P 09/02-F
Page of 24 42
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2024) 6.4.1
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Fan Shutdown 3 3 0 3 3
Device Type Location ScanID Address Q3/24 Q3/25 Fan Shutdown 3rd Attic HVAC 43812055 1-1 08/07-P 09/08-P Fan Shutdown 3rd Attic HVAC 43812059 1-1 08/07-P 09/08-P Fan Shutdown 1st 1118-02 HVAC 58237564 1-1 08/07-P 09/02-P
Device Total: 3 Return to Executive Summary
Page of 25 42
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Battery 4 2 2 4 4
Device Type Location ScanID Address Q3/24 Q3/25 Battery 1st 1127-02 Mech Room Near MRI lobbybathrooms 58237559 1-1 08/10-P 08/26-P
Battery 1st 1127-02 Mech Room Near MRI lobby bathrooms Top Set
58237557 1-1 08/10-P 08/26-P
Battery 1st 1127-02 Mech Room Near MRI lobbybathrooms
58237561 1-1 08/10-P 08/26-F
Battery 1st 1127-02 Mech Room Near MRI lobbybathrooms
58237560 1-1 08/10-P 08/26-F
Device Total: 4 Return to Executive Summary
Page of 26 42
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table
14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Power Supply 1 1 0 1 1
Device Type Location ScanID Address Q3/24 Q3/25 Power Supply 1st 1127-02 Mech Room Near MRI lobbybathrooms 58237558 1-1 08/10-P 08/26-P
Device Total: 1 Return to Executive Summary
Page of 27 42
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Programmable Relay 16 16 0 16 16
Device Type Location ScanID Address Q3/24 Q3/25 Programmable Relay 1st Hallway C1215-02 Near Building
2 elevators 58237562 1-1-81 08/07-P 09/08-P
Programmable Relay 3rd Corridor Corridor 3005-2 17804284 1-1-3 115 08/07-P 09/08-P Programmable Relay 1st 1127-02 Mech Room Near MRI
LobbyBathrooms 17804943 1-1-3 61 08/07-P 09/08-P
Programmable Relay 1st 1127-02 Mech Room Near MRI LobbyBathrooms
17804942 1-1-3 62 08/07-P 09/08-P
Programmable Relay 1st 1214-02 Elevator Equipment Room
17804335 1-1-3 115 08/07-P 09/08-P
Programmable Relay 1st 1214-02 Elevator Equipment Room
17804336 1-1-3 51 08/07-P 09/08-P
Programmable Relay 1st 1127-02 Mech Room Near MRI Lobby Bathrooms
17804941 1-1-3 63 08/07-P 09/08-P
Programmable Relay 3rd AHU Room Mechanical Room Above Kitchen
17804673 1-1-3 59 08/07-P 09/08-P
Programmable Relay 1st 1214-02 Elevator Equipment Room
17804338 1-1-3 48 08/07-P 09/08-P
Programmable Relay 1st 1214-02 Elevator Equipment Room
17804337 1-1-3 50 08/07-P 09/08-P
Programmable Relay 3rd Corridor Corridor 3003 43812081 1-1-3 115 08/07-P 09/08-P Programmable Relay 1st 1127-02 Mech Room Near MRI
LobbyBathrooms 17804951 1-1-3 76 08/07-P 09/08-P
Programmable Relay 3rd AHU Room Mechanical Room Above Kitchen
45935280 1-1-3 59 08/07-P 09/08-P
Programmable Relay 3rd Attic HVAC 43812056 1-1-L3 82 08/07-P 09/08-P Programmable Relay 1st 1127-02 Mecha Room Near MRI
LobbyBathrooms 17804944 1-1-3 60 08/07-P 09/08-P
Programmable Relay 1st 1118-02 HVAC 17804327 1-1-81 08/07-P 09/08-P
Device Total: 16 Return to Executive Summary
Page of 28 42
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Remote Test Switch 3 3 0 3 3
Device Type Location ScanID Address Q3/24 Q3/25 Remote Test Switch 3rd AHU Room In 2133-02
Engineering Rm 3302-02 45935274 1-1-3 52 08/07-P 09/08-P
Remote Test Switch 3rd AHU Room In 2133-02 Engineering Rm 3302-02
45935273 1-1-3 52 08/07-P 09/08-P
Remote Test Switch 3rd Attic HVAC 43812054 1-1 08/07-P 09/02-P
Device Total: 3 Return to Executive Summary
Page of 29 42 Service Summary
Vets Fire & Life Safety Download Date: 11/05/2025
Service Summary Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 2 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Failed/Other Battery Tested 2 Duct Detector Battery Replaced 2 Heat Detector Tested 2 Smoke Detector Tested/Cleaned 3
Total 9
Passed Battery Tested 2 Duct Detector Battery Replaced 9 Duct Detector Tested 3 Fan Shutdown Tested 3 Heat Detector Tested 8 Monitor Device Tested 6 Power Supply Tested 1 Programmable Relay Tested 16 Pull Station Tested 14 Releasing Device Tested 5 Remote Test Switch Tested 3 Smoke Detector Tested/Cleaned 29 Speaker Tested 40 Strobe Tested 45 Tamper Switch Annual 9 Voice Evacuation Tested 1 Waterflow Switch Annual 9
Total 203 Grand Total 212
Page of 30 42 Auxiliary Functions Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Auxiliary Functions Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 2 Control Panel: 1 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed Fan Shutdown
1st 1118-02 HVAC Passed 58237564 3rd Attic HVAC Passed 43812059 3rd Attic HVAC Passed 43812055
Programmable Relay 1st 1118-02 HVAC Passed 17804327 1st 1127-02 Mech Room Near MRI Lobby
Bathrooms Passed 17804941
1st 1127-02 Mech Room Near MRI LobbyBathrooms
Passed 17804951
1st 1127-02 Mech Room Near MRI LobbyBathrooms
Passed 17804942
1st 1127-02 Mech Room Near MRI LobbyBathrooms
Passed 17804943
1st 1127-02 Mecha Room Near MRI LobbyBathrooms
Passed 17804944
1st 1214-02 Elevator Equipment Room Passed 17804337 1st 1214-02 Elevator Equipment Room Passed 17804338 1st 1214-02 Elevator Equipment Room Passed 17804336 1st 1214-02 Elevator Equipment Room Passed 17804335 1st Hallway C1215-02 Near Building 2 elevators Passed 58237562
3rd AHU Room Mechanical Room Above Kitchen
Passed 45935280
3rd AHU Room Mechanical Room Above Kitchen
Passed 17804673
3rd Attic HVAC Passed 43812056 3rd Corridor Corridor 3005-2 Passed 17804284 3rd Corridor Corridor 3003 Passed 43812081
Releasing Device 1st Hallway C1010-02 Near Biomed &
Electronics Passed 17804184 javascript:editViewDevice('58237564');
javascript:editViewDevice('43812059');
javascript:editViewDevice('43812055');
javascript:editViewDevice('17804327');
javascript:editViewDevice('17804941');
javascript:editViewDevice('17804951');
javascript:editViewDevice('17804942');
javascript:editViewDevice('17804943');
javascript:editViewDevice('17804944');
javascript:editViewDevice('17804337');
javascript:editViewDevice('17804338');
javascript:editViewDevice('17804336');
javascript:editViewDevice('17804335');
javascript:editViewDevice('58237562');
javascript:editViewDevice('45935280');
javascript:editViewDevice('17804673');
javascript:editViewDevice('43812056');
javascript:editViewDevice('17804284');
javascript:editViewDevice('43812081');
javascript:editViewDevice('17804184');
Page of 31 42
Vets Fire & Life Safety Download Date: 11/05/2025
Building: Fayetteville VAMC Bldg 2 Control Panel: 1 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed Releasing Device
1st Hallway C1010-02 Near Biomed & Electronics
Passed 17804185
3rd Corridor Corridor 3005-2 Passed 17804285 3rd Corridor Corridor 3003 Passed 43812080 3rd Corridor Corridor 3003 Passed 43812079
Duct Detector AHU Shutdown 1st 1118-02 HVAC Passed 17804326 AHU Shutdown 3rd Attic HVAC Passed 43812057 AHU Shutdown 3rd Attic HVAC Passed 43812058 AHU Shutdown 1st Mech Room 1188 Passed 89471369 AHU Shutdown 1st Mech Room 1188 Passed 89471370 AHU Shutdown 3rd AHU Room HVAC Room Behind
Engineering Passed 45935281
AHU Shutdown 3rd AHU Room HVAC Room Behind Engineering
Passed 45935282
AHU Shutdown 3rd AHU Room HVAC Room Behind Engineering
Passed 45935275
AHU Shutdown 1st AC Equipment Room 2-12 Passed 89471371 AHU Shutdown 3rd Elevator Lobby Passed 89471372 AHU Shutdown 3rd LAB Attic Passed 89471368 AHU Shutdown 3rd LAB Attic Passed 89471367
Heat Detector Shunt Trip 1st Bottom of Staff Elevator Shaft Passed 16444051 Shunt Trip 3rd Elev Equip Rm in 2133-02 Eng Rm 3303-
Passed 45935271
Smoke Detector Elevator Recall 1st Bottom of Staff Elevator Shaft Passed 16444050 Elevator Recall 1st Freight Elevator Lobby Passed 17804223 Elevator Recall 1st Freight Elevator Pit Passed 16444054 Elevator Recall 2nd Elevator Lobby Passed 17804264 Elevator Recall 2nd Freight Elevator Passed 17804232 Elevator Recall 2nd Top of Freight Elevator Shaft Passed 16444053 Elevator Recall 3rd Top of Staff Elevator Passed 16444034 javascript:editViewDevice('17804185');
javascript:editViewDevice('17804285');
javascript:editViewDevice('43812080');
javascript:editViewDevice('43812079');
javascript:editViewDevice('17804326');
javascript:editViewDevice('43812057');
javascript:editViewDevice('43812058');
javascript:editViewDevice('89471369');
javascript:editViewDevice('89471370');
javascript:editViewDevice('45935281');
javascript:editViewDevice('45935282');
javascript:editViewDevice('45935275');
javascript:editViewDevice('89471371');
javascript:editViewDevice('89471372');
javascript:editViewDevice('89471368');
javascript:editViewDevice('89471367');
javascript:editViewDevice('16444051');
javascript:editViewDevice('45935271');
javascript:editViewDevice('16444050');
javascript:editViewDevice('17804223');
javascript:editViewDevice('16444054');
javascript:editViewDevice('17804264');
javascript:editViewDevice('17804232');
javascript:editViewDevice('16444053');
javascript:editViewDevice('16444034');
Page of 32 42
Vets Fire & Life Safety Download Date: 11/05/2025
Building: Fayetteville VAMC Bldg 2 Control Panel: 1 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Failed/Other Duct Detector
AHU Shutdown 3rd Stair 5 Above Kitchen Failed Operation 89471364 AHU Shutdown 3rd Stair 5 Above Kitchen Failed Operation 89471363
Heat Detector Shunt Trip 1st 1214-02 Elevator Equipment Room Failed Operation 17804333 Shunt Trip 1st 1214-02 Elevator Equipment Room Failed Operation 16444060
Smoke Detector Elevator Recall 1st 1214-02 Elevator Equipment Room Failed Operation 17804334 Elevator Recall 3rd Elevator Lobby Failed Operation 17804379 javascript:editViewDevice('89471364');
javascript:editViewDevice('89471363');
javascript:editViewDevice('17804333');
javascript:editViewDevice('16444060');
javascript:editViewDevice('17804334');
javascript:editViewDevice('17804379');
Page of 33 42 Battery & Power Supply Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Battery & Power Supply Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 2 Control Panel: 1 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Passed 1st 1127-02 Mech Room Near
MRI lobby bathrooms Top Set 12 12 13.00
Sealed Lead Acid 1st 1127-02 Mech Room Near MRI lobbybathrooms
12 12 12.97
Failed/Other Sealed Lead Acid 1st 1127-02 Mech Room Near
MRI lobbybathrooms 18 12
Sealed Lead Acid 1st 1127-02 Mech Room Near MRI lobbybathrooms
18 12
Page of 34 42 Inventory & Warranty Report
Vets Fire & Life Safety Download Date: 11/05/2025
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 2 Control Panel: 1 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Battery Control 1.89% 4
Duct Detector Initiating 6.60% 14
Fan Shutdown Auxiliary 1.42% 3
Heat Detector Initiating 4.72% 10
Monitor Device Monitor 2.83% 6
Power Supply Control 0.47% 1
Programmable Relay Auxiliary 7.55% 16
Pull Station Initiating 6.60% 14
Releasing Device Auxiliary 2.36% 5
Remote Test Switch Initiating 1.42% 3
Smoke Detector Initiating 15.09% 32
Speaker Indicating 18.87% 40
Strobe Indicating 21.23% 45
Tamper Switch Supervisory 4.25% 9
Voice Evacuation Control 0.47% 1
Waterflow Switch Initiating 4.25% 9
Type Qty Model # Description Install Date
In Service - 1 Year to 2 Years Notifier
Battery 1 08/10/2024 Battery 3 Sealed Lead Acid 08/10/2024 Heat Detector 5 08/10/2024 Power Supply 1 08/10/2024 Smoke Detector 12 08/10/2024 Duct Detector 13 08/07/2024 Fan Shutdown 3 08/07/2024 Monitor Device 6 08/07/2024 Programmable Relay 16 08/07/2024 Releasing Device 5 08/07/2024 Remote Test Switch 3…