2025-09-15_Fayetteville-VAMC-Bldg-10_FireScan.pdf
PDF 151 KB Posted
- Attached to
- J042--Fire Alarm Service
- Solicitation number
- 36C25626Q0430
About this file
This is a Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate for Fayetteville VAMC Building 10 located at 1100 N College Ave, Fayetteville, AR 72703. The annual inspection was completed on September 15, 2025, by Veterans Fire & Life Safety (inspector Rod Davis) in compliance with The Joint Commission/VHA Standards and the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
The inspection encompassed testing of 38 total devices across multiple categories, all of which passed inspection. Key devices tested include: 3 tamper switches (supervisory signal devices), 1 waterflow switch, 5 pull stations, 1 smoke detector, 10 speakers, 3 speaker/strobe combinations, 7strobes, 2 batteries (sealed lead acid, 9 Ah rated), 1 power supply, and 5 programmable relays. Battery testing showed post-test voltages of 12.84V and 12.85V for the two units tested. All testing was performed in accordance with NFPA 72 (2022) and NFPA 101-2024 standards. The inventory report notes that most fire alarm and notification devices were installed between August 7-10, 2024, while tamper switches and waterflow switches have been in service for 25+ years. No deficiencies or failed items were identified in this inspection cycle.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Fayetteville VAMC Bldg 10 1100 N College Ave
Fayetteville, AR 72703 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
Annual Inspection Inspection Completion Date Sep 15, 2025
Building: Fayetteville VAMC Bldg 10 Company: Vets Fire & Life Safety Contact: Travis Ryan Contact: Rod Davis
Title: Safety Specialist Title: Manager Fire Alarm Testing Report
Page of 1 21 Executive Summary
Vets Fire & Life Safety Download Date: 11/05/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fayetteville VAMC Bldg 10 Contact: Travis Ryan
Address: 1100 N College Ave Phone: 479-225-6412
Address: Fax:
City/State/ZIP Code: Fayetteville, AR 72703 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Vets Fire & Life Safety Inspector: Rod Davis
Address: 7 Sherri Lane Phone: 314-696-7000
Address: Fax:
City/State/ZIP Code: St Peters, MO 63376 Mobile:
Country: United States of America Email: rod.davis@vflsc.com
Page of 2 21
Vets Fire & Life Safety Download Date: 11/05/2025
Inspection Completion Date: Sep 15, 2025 Building: Fayetteville VAMC Bldg 10 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Tamper Switch 3 3 0 3 0 3
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Waterflow Switch 1 1 0 1 0 1
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Pull Station 5 5 0 5 0 5
Smoke Detector 1 1 0 1 0 1
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Speaker 10 10 0 10 0 10
Speaker/Strobe 3 3 0 3 0 3
Strobe 7 7 0 7 0 7
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Battery 2 2 0 2 0 2
Power Supply 1 1 0 1 0 1
Programmable Relay 5 5 0 5 0 5
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Elevator 0 0 0 0 0 0
Total Device Count: 38
Page of 3 21
Vets Fire & Life Safety Download Date: 11/05/2025
Certification
Company: Vets Fire & Life Safety Building: Fayetteville VAMC Bldg 10
Inspector: Rod Davis Contact: Travis Ryan
Page of 4 21 Notes & Recommendations
Vets Fire & Life Safety Download Date: 11/05/2025
Notes & Recommendations Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 10 Control Panel: 1 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;
water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
1 Tamper Switch Ground Ground Garage Restroom BF Valve
Passed 9187409
Testing Done By Others 2 Tamper Switch Ground Ground Garage Restroom BF Valve
Passed 9187410
Testing Done By Others 3 Tamper Switch Ground Ground South Lawn Passed 9187411
Testing Done By Others
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table
14.4.3.2 (17)(10)(a) & (17)(11)
4 Waterflow Switch Ground Ground Garage Restroom Passed 9187412 Testing Done By Others javascript:editViewDevice('9187409');
javascript:editViewDevice('9187410');
javascript:editViewDevice('9187411');
javascript:editViewDevice('9187412');
Page of 5 21 Inspection & Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Inspection & Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 10 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Tamper Switch 3 3 0 3 3
Device Type Location ScanID Address Q3/24 Q3/25 Tamper Switch Ground Ground Garage Restroom
BF Valve 1 9187409 1-1-L1 M17 08/20-P 09/15-P
Tamper Switch Ground Ground Garage Restroom BF Valve 2
9187410 1-1-L1 M17 08/20-P 09/15-P
Tamper Switch Ground Ground South Lawn 9187411 1-1-L1 M18 08/20-P 09/15-P
Device Total: 3 Return to Executive Summary
Page of 6 21
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table
14.4.3.2 (17)(11)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Waterflow Switch 1 1 0 1 1
Device Type Location ScanID Address Q3/24 Q3/25 Waterflow Switch Ground Ground Garage Restroom 9187412 1-1-L1 M16 08/20-P 09/15-P
Device Total: 1 Return to Executive Summary
Page of 7 21
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Pull Station 5 5 0 5 5
Device Type Location ScanID Address Q3/24 Q3/25 Pull Station Upper Level 9187416 1-9-LM30 08/07-P 08/27-P Pull Station Upper Level Front Door 9187417 1-1-L9 M3 08/07-P 08/27-P Pull Station 1st Bldg 26 Transformer Room 9187413 1-3-M100 08/10-P 08/27-P Pull Station 1st Boiler Plant Office 9187418 1-9-M1 08/07-P 08/27-P Pull Station 1st South Door 9187419 1-1-L9 M2 08/07-P 08/27-P
Device Total: 5 Return to Executive Summary
Page of 8 21
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Smoke Detector 1 1 0 1 1
Device Type Location ScanID Address Q3/24 Q3/25 Smoke Detector Ground Bldg 26 Transformer Room 9187420 1-3-D101 08/10-P 08/27-P
Page of 9 21
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker 10 10 0 10 10
Device Type Location ScanID Address Q3/24 Q3/25 Speaker Ground Ground 9187426 1-1 08/10-P 08/27-P Speaker Ground Ground 9187427 1-1 08/10-P 08/27-P Speaker Ground Ground 9187428 1-1 08/10-P 08/27-P Speaker Ground Ground Plumbing Office 9187429 1-1 08/10-P 08/27-P Speaker 1st 1st 9187424 1-1 08/10-P 08/27-P Speaker 1st 1st 9187425 1-1 08/10-P 08/27-P Speaker 1st 1st 9187423 1-1 08/10-P 08/27-P Speaker 1st 1st 9187422 1-1 08/10-P 08/27-P Speaker 1st 1st 9187421 1-1 08/10-P 08/27-P Speaker 1st BLDG 26 9187414 1 08/10-P 08/27-P
Device Total: 10 Return to Executive Summary
Page of 10 21
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker/Strobe 3 3 0 3 3
Device Type Location ScanID Address Q3/24 Q3/25 Speaker/Strobe 2nd By Room Room 217 9187446 1 08/10-P 08/27-P Speaker/Strobe 2nd Nurses Station 9187447 1 08/10-P 08/27-P Speaker/Strobe 2nd Reception 9187448 1 08/10-P 08/27-P
Device Total: 3 Return to Executive Summary
Page of 11 21
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Strobe 7 7 0 7 7
Device Type Location ScanID Address Q3/24 Q3/25 Strobe Ground Ground 9187434 1-1 08/10-P 08/27-P Strobe Ground Ground 9187433 1-1 08/10-P 08/27-P Strobe Ground Ground Plumbing Office 9187435 1-1 08/10-P 08/27-P Strobe 1st 1st 9187431 1-1 08/10-P 08/27-P Strobe 1st 1st 9187430 1-1 08/10-P 08/27-P Strobe 1st 1st 9187432 1-1 08/10-P 08/27-P Strobe 1st BLDG 26 West Exit 9187415 1 08/10-P 08/27-P
Device Total: 7 Return to Executive Summary
Page of 12 21
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Battery 2 2 0 2 2
Device Type Location ScanID Address Q3/24 Q3/25 Battery Ground Ground 9187437 1-1 08/10
Removed
Battery Ground Ground Operators Room 9187438 1-1 08/10-F 08/27-P Battery Ground Ground Operators Room 9187439 1-1 08/10-F 08/27-P Battery 2nd 2nd North Ceiling Ceiling 9187436 1-1 08/10
Device Total: 2 Return to Executive Summary
Page of 13 21
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table
14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Power Supply 1 1 0 1 1
Device Type Location ScanID Address Q3/24 Q3/25 Power Supply Ground Operators Room 9187440 1-1 08/10-P 08/27-P
Page of 14 21
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Programmable Relay 5 5 0 5 5
Device Type Location ScanID Address Q3/24 Q3/25 Programmable Relay Ground Ground Plumbing Office 9187442 1-1-1 -59 08/10-P 08/27-P Programmable Relay Ground Ground Plumbing Office 9187443 1-1--43 08/10-P 08/27-P Programmable Relay Ground Ground Plumbing Office 9187444 1-1--41 08/10-P 08/27-P Programmable Relay Ground Ground Plumbing Office 9187445 1-1-1 -42 08/10-P 08/27-P Programmable Relay Ground Ground Plumbing Office 9187441 1-1-1 -40 08/10-P 08/27-P
Device Total: 5 Return to Executive Summary
Page of 15 21
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.50 EP 07 Annual - Elevators are fully equipped and protected
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Elevator 0 0 0 0 0
Device Type Location ScanID Address Q3/24 Q3/25 Elevator 1st Elevator 25 Recall 9187449 1 08/10
Page of 16 21 Service Summary
Vets Fire & Life Safety Download Date: 11/05/2025
Service Summary Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 10 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed Battery Tested 2 Power Supply Tested 1 Programmable Relay Tested 5 Pull Station Tested 5 Smoke Detector Tested/Cleaned 1 Speaker/Strobe Tested 3 Speaker Tested 10 Strobe Tested 7 Tamper Switch Annual 3 Waterflow Switch Annual 1
Total 38 Grand Total 38
Page of 17 21 Auxiliary Functions Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Auxiliary Functions Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 10 Control Panel: 1 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed Programmable Relay
Ground Ground Plumbing Office Passed 9187442 Ground Ground Plumbing Office Passed 9187443 Ground Ground Plumbing Office Passed 9187444 Ground Ground Plumbing Office Passed 9187445 Ground Ground Plumbing Office Passed 9187441 javascript:editViewDevice('9187442');
javascript:editViewDevice('9187443');
javascript:editViewDevice('9187444');
javascript:editViewDevice('9187445');
javascript:editViewDevice('9187441');
Page of 18 21 Battery & Power Supply Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Battery & Power Supply Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 10 Control Panel: 1 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Passed Sealed Lead Acid Ground Ground Operators
Room 9 12 12.84
Sealed Lead Acid Ground Ground Operators Room
9 12 12.85
Page of 19 21 Inventory & Warranty Report
Vets Fire & Life Safety Download Date: 11/05/2025
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 10 Control Panel: 1 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Battery Control 5.26% 2
Power Supply Control 2.63% 1
Programmable Relay Auxiliary 13.16% 5
Pull Station Initiating 13.16% 5
Smoke Detector Initiating 2.63% 1
Speaker Indicating 26.32% 10
Speaker/Strobe Indicating 7.89% 3
Strobe Indicating 18.42% 7
Tamper Switch Supervisory 7.89% 3
Waterflow Switch Initiating 2.63% 1
Type Qty Model # Description Install Date
In Service - 1 Year to 2 Years Battery 2 Sealed Lead Acid 08/10/2024 Power Supply 1 08/10/2024 Programmable Relay 5 08/10/2024 Smoke Detector 1 08/10/2024 Speaker 9 08/10/2024 Strobe 6 08/10/2024
Simplex Speaker/Strobe 3 08/10/2024
Pull Station 5 08/07/2024 Speaker 1 08/07/2024 Strobe 1 08/07/2024
In Service - 25 Years or Older Tamper Switch 3 12/31/1969 Waterflow Switch 1 12/31/1969
Page of 20 21 Zone Address Report
Vets Fire & Life Safety Download Date: 11/05/2025
Zone Address Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 10 Control Panel: 1 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID 1 Speaker Ground Ground 9187426 1 Speaker Ground Ground 9187427 1 Speaker Ground Ground 9187428 1 Strobe Ground Ground 9187433 1 Strobe Ground Ground 9187434 1 Battery Ground Ground Operators Room Sealed Lead Acid 9187438 1 Battery Ground Ground Operators Room Sealed Lead Acid 9187439 1 Speaker Ground Ground Plumbing Office 9187429 1 Strobe Ground Ground Plumbing Office 9187435 1 Power Supply Ground Operators Room 9187440 1 Speaker 1st 1st 9187421 1 Speaker 1st 1st 9187422 1 Speaker 1st 1st 9187423 1 Speaker 1st 1st 9187424 1 Speaker 1st 1st 9187425 1 Strobe 1st 1st 9187430 1 Strobe 1st 1st 9187431 1 Strobe 1st 1st 9187432
1-1 -40 Programmable Relay Ground Ground Plumbing Office 9187441 1-1 -42 Programmable Relay Ground Ground Plumbing Office 9187445 1-1 -59 Programmable Relay Ground Ground Plumbing Office 9187442 1--41 Programmable Relay Ground Ground Plumbing Office 9187444 1--43 Programmable Relay Ground Ground Plumbing Office 9187443
1-L1 M16 Waterflow Switch Ground Ground Garage Restroom 9187412 1-L1 M17 Tamper Switch Ground Ground Garage Restroom BF
Valve 1 9187409
1-L1 M17 Tamper Switch Ground Ground Garage Restroom BF Valve 2
9187410
1-L1 M18 Tamper Switch Ground Ground South Lawn 9187411 1-L9 M2 Pull Station 1st South Door 9187419 1-L9 M3 Pull Station Upper Level Front Door 9187417 3-D101 Smoke Detector Ground Bldg 26 Transformer Room 9187420 3-M100 Pull Station 1st Bldg 26 Transformer Room 9187413 9-LM30 Pull Station Upper Level 9187416
9-M1 Pull Station 1st Boiler Plant Office 9187418 javascript:editViewDevice('9187426');
javascript:editViewDevice('9187427');
javascript:editViewDevice('9187428');
javascript:editViewDevice('9187433');
javascript:editViewDevice('9187434');
javascript:editViewDevice('9187438');
javascript:editViewDevice('9187439');
javascript:editViewDevice('9187429');
javascript:editViewDevice('9187435');
javascript:editViewDevice('9187440');
javascript:editViewDevice('9187421');
javascript:editViewDevice('9187422');
javascript:editViewDevice('9187423');
javascript:editViewDevice('9187424');
javascript:editViewDevice('9187425');
javascript:editViewDevice('9187430');
javascript:editViewDevice('9187431');
javascript:editViewDevice('9187432');
javascript:editViewDevice('9187441');
javascript:editViewDevice('9187445');
javascript:editViewDevice('9187442');
javascript:editViewDevice('9187444');
javascript:editViewDevice('9187443');
javascript:editViewDevice('9187412');
javascript:editViewDevice('9187409');
javascript:editViewDevice('9187410');
javascript:editViewDevice('9187411');
javascript:editViewDevice('9187419');
javascript:editViewDevice('9187417');
javascript:editViewDevice('9187420');
javascript:editViewDevice('9187413');
javascript:editViewDevice('9187416');
javascript:editViewDevice('9187418');
Page of 21 21 Zone Address Report
Vets Fire & Life Safety Download Date: 11/05/2025
| Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate |
| Executive Summary |
| Notes & Recommendations |
| Inspection & Testing |
| Service Summary |
| Auxiliary Functions Testing |
| Battery & Power Supply Testing |
| Inventory & Warranty Report |
| Zone Address Report |