This is a Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate for Fayetteville VAMC Building 44 located at 1100 N College Ave, Fayetteville, AR 72703. The inspection was completed on September 15, 2025, by Veterans Fire and Life Safety, with inspector Rod Davis and facility contact Travis Ryan. The inspection was performed in compliance with The Joint Commission/VHA Standards and the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
The comprehensive inspection tested 108 total devices across multiple fire and life safety systems, with all devices passing inspection. Key testing included: 4 duct detectors, 11 pull stations, and 7 smoke detectors (all per EC 02.03.05 EP 03); 25 speakers, 3 speaker/strobes, and 35 strobes for visual and audible alarms (per EC 02.03.05 EP 04); 1 fire pump running supervisory signal tested annually (per EC 02.03.05 EP 11); 4 duct detectors and 2 fan shutdowns for HVAC smoke detection shutdown (per EC 02.03.05 EP 19); and additional life safety systems including 1 annunciator, 4 batteries, 2 power supplies, 11 programmable relays, and 2 remote test switches (per LS 02.01.34 EP 10). All 108 devices tested year-to-date in 2025 passed inspection with zero failures. Battery testing showed sealed lead acid batteries ranging from 8-12 Ah rated capacity with post-test voltages between 12.36 and 13.28 volts, all within acceptable ranges.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Fayetteville VAMC Bldg 44 1100 N College Ave
Fayetteville, AR 72703 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
Annual Inspection Inspection Completion Date Sep 15, 2025
Building: Fayetteville VAMC Bldg 44 Company: Vets Fire & Life Safety Contact: Travis Ryan Contact: Rod Davis
Title: Safety Specialist Title: Manager Fire Alarm Testing Report
Page of 1 25 Executive Summary
Vets Fire & Life Safety Download Date: 11/05/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fayetteville VAMC Bldg 44 Contact: Travis Ryan
Address: 1100 N College Ave Phone: 479-225-6412
Address: Fax:
City/State/ZIP Code: Fayetteville, AR 72703 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Vets Fire & Life Safety Inspector: Rod Davis
Address: 7 Sherri Lane Phone: 314-696-7000
Address: Fax:
City/State/ZIP Code: St Peters, MO 63376 Mobile:
Country: United States of America Email: rod.davis@vflsc.com
Page of 2 25
Vets Fire & Life Safety Download Date: 11/05/2025
Inspection Completion Date: Sep 15, 2025 Building: Fayetteville VAMC Bldg 44 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Duct Detector 4 4 0 4 0 4
Pull Station 11 11 0 11 0 11
Smoke Detector 7 7 0 7 0 7
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Speaker 25 25 0 25 0 25
Speaker/Strobe 3 3 0 3 0 3
Strobe 35 35 0 35 0 35
EC 02.03.05 EP 11 For automatic sprinkler systems: Every 12 months, the hospital tests fire pumps under flow. Fire pump supervisory signals for pump running and pump power loss are tested annually. NFPA 25 (2023) 8.3.3
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Fire Pump Running 1 1 0 1 0 1
EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2024) 6.4.1
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Duct Detector 4 4 0 4 0 4
Fan Shutdown 2 2 0 2 0 2
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Annunciator 1 1 0 1 0 1
Battery 4 4 0 4 0 4
Power Supply 2 2 0 2 0 2
Programmable Relay 11 11 0 11 0 11
Remote Test Switch 2 2 0 2 0 2
Total Device Count: 108
Page of 3 25
Vets Fire & Life Safety Download Date: 11/05/2025
Certification
Company: Vets Fire & Life Safety Building: Fayetteville VAMC Bldg 44
Inspector: Rod Davis Contact: Travis Ryan
Page of 4 25 Notes & Recommendations
Vets Fire & Life Safety Download Date: 11/05/2025
Notes & Recommendations Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 44 Control Panel: 1 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
1 Duct Detector Ground Room 124 Passed 12365438 Shuts Down Unit
2 Duct Detector Ground Room 124 Passed 12873649 Shuts Down Unit
3 Duct Detector 2nd 2nd Between Mens & Womens Restrm Passed 34543457 Shuts Down Unit
4 Duct Detector 2nd 2nd Between Mens & Womens Restrm Passed 46738293 Shuts Down Unit
EC 02.03.05 EP 11 For automatic sprinkler systems: Every 12 months, the hospital tests fire pumps under flow.
Fire pump supervisory signals for pump running and pump power loss are tested annually. NFPA 25 (2023) 8.3.3
5 Fire Pump Running 1st 1st Outdoor Pump Room Passed 8537352 Testing Done By Others javascript:editViewDevice('12365438');
javascript:editViewDevice('12873649');
javascript:editViewDevice('34543457');
javascript:editViewDevice('46738293');
javascript:editViewDevice('8537352');
Page of 5 25 Inspection & Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Inspection & Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 44 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Duct Detector 4 4 0 4 4
Device Type Location ScanID Address Q3/24 Q3/25 Duct Detector Ground Room 124 12873649 1 09/02-P Duct Detector Ground Room 124 12365438 1 09/02-P Duct Detector 2nd 2nd Between Mens & Womens
Restrm 46738293 1-1-5 52 09/02-P
Duct Detector 2nd 2nd Between Mens & Womens Restrm
34543457 1-1-5 51 09/02-P
Device Total: 4 Return to Executive Summary
Page of 6 25
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Pull Station 11 11 0 11 11
Device Type Location ScanID Address Q3/24 Q3/25 Pull Station 1st 1st Northwest Pump Room 8537270 1-1-5 4 08/10-P 08/27-P Pull Station 1st 1st North Exit By 124A 8537269 1-1-5 35 08/10-P 08/27-P Pull Station 1st 1st South Exit In Stairwell 8537271 1-1-5 38 08/10-P 08/27-P Pull Station 1st 1st Southeast Exit 8537272 1-1-5 38 08/10-P 08/27-P Pull Station 1st 1st East Exit In 124B 8537268 1-1-5 03 08/10-P 08/27-P Pull Station 1st 1st East Exit In 124A 8537267 1-1-5 03 08/10-P 08/27-P Pull Station 1st 1st Next to Nurses Office 144-44 8537266 1-1-5 01 08/10-P 08/27-P Pull Station 1st 1st Front Entrance 8537265 1-1-5 35 08/10-P 08/27-P Pull Station 1st 1st Front Entrance 8537264 1-1-5 01 08/10-P 08/27-P Pull Station 2nd 2nd East Stair Exit 8537273 1-1-5 33 08/10-P 08/27-P Pull Station 2nd 2nd West Stair Exit 8537274 1-1-5 33 08/10-P 08/27-P
Device Total: 11 Return to Executive Summary
Page of 7 25
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Smoke Detector 7 7 0 7 7
Device Type Location ScanID Address Q3/24 Q3/25 Smoke Detector 1st 1st Elevator Equipment Room 143 8537276 1-1-5 01 09/02-P Smoke Detector 1st 1st Northwest Pump Room 8537280 1-1-5 08/10-P 08/27-P Smoke Detector 1st 1st Front Entrance Behind
Vestibule 8537275 1-1-5 01 08/10-P 08/27-P
Smoke Detector 1st 1st HVAC Room 124B 8537279 1-1-5 01 08/10-P 08/27-P Smoke Detector 1st 1st HVAC Room 124B 8537278 1-1-5 01 08/10-P 08/27-P Smoke Detector 1st 1st HVAC Room 124A 8537277 1-1-5 01 08/10-P 08/27-P Smoke Detector 2nd 2nd Elevator Lobby 8537281 1-1-5 01 09/02-P
Device Total: 7 Return to Executive Summary
Page of 8 25
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker 25 25 0 25 25
Device Type Location ScanID Address Q3/24 Q3/25 Speaker 1st 1st Front Entrance 8537282 1 08/07-P 09/02-P Speaker 1st 1st Outside Room 132 8537288 1 08/07-P 09/02-P Speaker 1st 1st Outside Room 116 8537287 1 08/07-P 09/02-P Speaker 1st 1st Outside Room 104 8537286 1 08/07-P 09/02-P Speaker 1st 1st Front Entrance 8537283 1 08/07-P 09/02-P Speaker 1st 1st Front Lobby 8537285 1 08/07-P 09/02-P Speaker 1st 1st Front Entrance Behind
Vestibule 8537284 1 08/07-P 09/02-P
Speaker 1st 1st Outside Breakroom Room 130 8537291 1 08/07-P 09/02-P Speaker 1st 1st Outside Room 142 8537290 1 08/07-P 09/02-P Speaker 1st 1st Outside Room 142 8537289 1 08/07-P 09/02-P Speaker 1st 1st Resource Room In Room 117 8537296 1 08/07-P 09/02-P Speaker 1st 1st Southeast Hallway 8537298 1 08/07-P 09/02-P Speaker 1st 1st Rear Exit by 1A Outside
Room 132 8537297 1 08/07-P 09/02-P
Speaker 1st 1st Resource Room By 121 8537294 1 08/07-P 09/02-P Speaker 1st 1st Resource Room By 124C 8537295 1 08/07-P 09/02-P Speaker 1st 1st Outside Elevator Equipment
Room 8537292 1 08/07-P 09/02-P
Speaker 1st 1st Resource Room By 119 8537293 1 08/07-P 09/02-P Speaker 2nd 2nd Front Lobby 8537306 1 08/07-P 09/02-P Speaker 2nd 2nd By Room 216 8537301 1 08/07-P 09/02-P Speaker 2nd 2nd Front Lobby 8537305 1 08/07-P 09/02-P Speaker 2nd 2nd By Room 236 8537304 1 08/07-P 09/02-P Speaker 2nd 2nd By Room 222 8537302 1 08/07-P 09/02-P Speaker 2nd 2nd By Room 226-44 8537303 1 08/07-P 09/02-P Speaker 2nd 2nd By Room 205 8537300 1 08/07-P 09/02-P Speaker 2nd 2nd By Breakroom 230 8537299 1 08/07-P 09/02-P
Device Total: 25 Return to Executive Summary
Page of 9 25
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker/Strobe 3 3 0 3 3
Device Type Location ScanID Address Q3/24 Q3/25 Speaker/Strobe 1st 1st Main Lobby 8537309 1 08/07-P 09/02-P Speaker/Strobe 1st 1st Hallway by Room 140 8537307 1 08/07-P 09/02-P Speaker/Strobe 1st 1st Outside Women's Restroom 8537308 1 08/07-P 09/02-P
Device Total: 3 Return to Executive Summary
Page of 10 25
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Strobe 35 35 0 35 35
Device Type Location ScanID Address Q3/24 Q3/25 Strobe 1st 1st Front Entrance 8537315 1 08/06-P 09/08-P Strobe 1st 1st Men?s Restroom 8537318 1 08/06-P 09/08-P Strobe 1st 1st Front Entrance 8537316 1 08/06-P 09/08-P Strobe 1st 1st By Breakroom 8537310 1 08/06-P 09/08-P Strobe 1st 1st By Room 104-A 8537311 1 08/06-P 09/02-P Strobe 1st 1st By Room 104-A 8537312 1 08/06-P 09/02-P Strobe 1st 1st By Room 124C 8537313 1 08/06-P 09/02-P Strobe 1st 1st By Room 142 8537314 1 08/06-P 09/02-P Strobe 1st 1st Women?s Restroom 8537319 1 08/06-P 09/02-P Strobe 1st 1st Front Entrance 8537317 1 08/06-P 09/02-P Strobe 1st 1st Northwest Mechanical Room 8537325 1 08/06-P 09/02-P Strobe 1st 1st Southwest Hallway By 122 8537328 1 08/06-P 09/02-P Strobe 1st 1st Southeast Hallway 8537327 1 08/06-P 09/02-P Strobe 1st 1st Northwest Pump Room 8537326 1 08/06-P 09/02-P Strobe 1st 1st Electric Room 124A 8537320 1 08/06-P 09/02-P Strobe 1st 1st Women?s Restroom 128 8537324 1 08/06-P 09/02-P Strobe 1st 1st Men?s Restroom 129 8537323 1 08/06-P 09/02-P Strobe 1st 1st Group RM 3 Room117 8537322 1 08/06-P 09/02-P Strobe 1st 1st Group RM 1 Room117 8537321 1 08/06-P 09/02-P Strobe 2nd 2nd West Stair Exit 8537344 1 08/06-P 09/08-P Strobe 2nd 2nd West By Room 210 8537343 1 08/06-P 09/02-P Strobe 2nd 2nd By Room 215 8537332 1 08/06-P 09/02-P Strobe 2nd 2nd Front Lobby 8537337 1 08/06-P 09/02-P Strobe 2nd 2nd Women?s Restroom 8537342 1 08/06-P 09/02-P Strobe 2nd 2nd Men?s Restroom 8537340 1 08/06-P 09/02-P Strobe 2nd 2nd Women's Restroom 8537341 1 08/06-P 09/02-P Strobe 2nd 2nd By Room 203 8537331 1 08/06-P 09/02-P Strobe 2nd 2nd Men?s Restroom 8537339 1 08/06-P 09/02-P Strobe 2nd 2nd Group Room217A 8537338 1 08/06-P 09/02-P Strobe 2nd 2nd Conference Room 8537336 1 08/06-P 09/02-P Strobe 2nd 2nd By Room 239 8537335 1 08/06-P 09/02-P Strobe 2nd 2nd By Room 218B 8537333 1 08/06-P 09/02-P Strobe 2nd 2nd By Room 222 8537334 1 08/06-P 09/02-P Strobe 2nd 2nd By East Stairwell 8537330 1 08/06-P 09/02-P Strobe 2nd 2nd By Breakroom 230 8537329 1 08/06-P 09/02-P
Page of 11 25
Vets Fire & Life Safety Download Date: 11/05/2025
Device Type Location ScanID Address Q3/24 Q3/25
Device Total: 35 Return to Executive Summary
Page of 12 25
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 11
For automatic sprinkler systems: Every 12 months, the hospital tests fire pumps under flow. Fire pump supervisory signals for pump running and pump power loss are tested annually. NFPA 25 (2023) 8.3.3
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table
14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Fire Pump Running 1 1 0 1 1
Device Type Location ScanID Address Q3/24 Q3/25 Fire Pump Running 1st 1st Outdoor Pump Room 8537352 1-1-L5 M21 08/20-P 09/15-P
Device Total: 1 Return to Executive Summary
Page of 13 25
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2024) 6.4.1
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Duct Detector 4 4 0 4 4
Device Type Location ScanID Address Q3/24 Q3/25 Duct Detector Ground Room 124 12873649 1 09/02-P Duct Detector Ground Room 124 12365438 1 09/02-P Duct Detector 2nd 2nd Between Mens & Womens
Restrm 46738293 1-1-5 52 09/02-P
Duct Detector 2nd 2nd Between Mens & Womens Restrm
34543457 1-1-5 51 09/02-P
Page of 14 25
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment.
NFPA 90A (2024) 6.4.1
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Fan Shutdown 2 2 0 2 2
Device Type Location ScanID Address Q3/24 Q3/25 Fan Shutdown 1st 1st HVAC Room 124 8537346 1-1-5 01 08/10-P 09/02-P Fan Shutdown 1st 1st HVAC Room 124 8537345 1-1-5 01 08/10-P 09/02-P
Device Total: 2 Return to Executive Summary
Page of 15 25
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-22 Table 14.4.3.2 (11)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Annunciator 1 1 0 1 1
Device Type Location ScanID Address Q3/24 Q3/25 Annunciator 1st 1st Behind Front Desk 8537347 1-1-5 01 08/10-P 08/27-P
Device Total: 1 Return to Executive Summary
Page of 16 25
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Battery 4 4 0 4 4
Device Type Location ScanID Address Q3/24 Q3/25 Battery 1st 1st 8537351 1 08/10-P 09/02-P Battery 1st 1st 8537350 1 08/10-P 09/02-P Battery 1st 1st 8537349 1 08/10-P 09/02-P Battery 1st 1st 8537348 1 08/10-P 09/02-P
Page of 17 25
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table
14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Power Supply 2 2 0 2 2
Device Type Location ScanID Address Q3/24 Q3/25 Power Supply 1st 1st Comm Room 8537354 1 08/10-P 09/02-P Power Supply 1st 1st Comm Room 8537353 1 08/10-P 09/02-P
Page of 18 25
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Programmable Relay 11 11 0 11 11
Device Type Location ScanID Address Q3/24 Q3/25 Programmable Relay 1st 1st Comm Room 8537364 1-1-3 128 08/10-P 09/02-P Programmable Relay 1st 1st Elevator Equipment Room 143 8537355 1-1-5 04 09/02-P Programmable Relay 1st 1st Elevator Equipment Room 143 8537358 1-1-5 04 09/02-P Programmable Relay 1st 1st Comm Room 8537361 1-1-5 34 08/10-P 09/02-P Programmable Relay 1st 1st Elevator Equipment Room 143 8537357 1-1-5 04 09/02-P Programmable Relay 1st 1st Comm Room 8537363 1-1-3 129 08/10-P 09/02-P Programmable Relay 1st 1st Comm Room 8537362 1-1-5 97 08/10-P 09/02-P Programmable Relay 1st 1st Elevator Equipment Room 143 8537356 1-1-5 41 09/02-P Programmable Relay 1st 1st Comm Room 8537365 1-1-3 134 08/10-P 09/02-P Programmable Relay 1st 1st HVAC Room 124B 8537360 1-1-5 38 08/10-P 09/02-P Programmable Relay 1st 1st HVAC Room 124B 8537359 1-1-5 38 08/10-P 09/02-P
Device Total: 11 Return to Executive Summary
Page of 19 25
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Remote Test Switch 2 2 0 2 2
Device Type Location ScanID Address Q3/24 Q3/25 Remote Test Switch 2nd 2nd Between Mens & Women?s
Restrm 8537367 1-1-5 01 08/10-P 09/02-P
Remote Test Switch 2nd 2nd Between Mens & Women?s Restrm
8537366 1-1-5 01 08/10-P 09/02-P
Page of 20 25 Service Summary
Vets Fire & Life Safety Download Date: 11/05/2025
Service Summary Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 44 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed Annunciator Tested 1 Battery Tested 4 Duct Detector Battery Replaced 4 Fan Shutdown Tested 2 Fire Pump Running Tested 1 Power Supply Tested 2 Programmable Relay Tested 11 Pull Station Tested 11 Remote Test Switch Tested 2 Smoke Detector Tested/Cleaned 7 Speaker/Strobe Tested 3 Speaker Tested 25 Strobe Tested 35
Total 108 Grand Total 108
Page of 21 25 Auxiliary Functions Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Auxiliary Functions Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 44 Control Panel: 1 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed Fan Shutdown
AHU Shutdown 1st 1st HVAC Room 124 Passed 8537345 AHU Shutdown 1st 1st HVAC Room 124 Passed 8537346
Programmable Relay 1st 1st Comm Room Passed 8537365 1st 1st Comm Room Passed 8537362 1st 1st Comm Room Passed 8537363 1st 1st Comm Room Passed 8537361 1st 1st Comm Room Passed 8537364 1st 1st Elevator Equipment Room 143 Passed 8537356 1st 1st Elevator Equipment Room 143 Passed 8537357 1st 1st Elevator Equipment Room 143 Passed 8537358 1st 1st Elevator Equipment Room 143 Passed 8537355 1st 1st HVAC Room 124B Passed 8537359 1st 1st HVAC Room 124B Passed 8537360 javascript:editViewDevice('8537345');
javascript:editViewDevice('8537346');
javascript:editViewDevice('8537365');
javascript:editViewDevice('8537362');
javascript:editViewDevice('8537363');
javascript:editViewDevice('8537361');
javascript:editViewDevice('8537364');
javascript:editViewDevice('8537356');
javascript:editViewDevice('8537357');
javascript:editViewDevice('8537358');
javascript:editViewDevice('8537355');
javascript:editViewDevice('8537359');
javascript:editViewDevice('8537360');
Page of 22 25 Battery & Power Supply Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Battery & Power Supply Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 44 Control Panel: 1 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Passed Sealed Lead Acid 1st 1st 8 12 12.38 Sealed Lead Acid 1st 1st 8 12 12.36 Sealed Lead Acid 1st 1st 12 12 13.28 1st 1st 12 12 13.20
Page of 23 25 Inventory & Warranty Report
Vets Fire & Life Safety Download Date: 11/05/2025
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 44 Control Panel: 1 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Annunciator Control 0.93% 1
Battery Control 3.70% 4
Duct Detector Initiating 3.70% 4
Fan Shutdown Auxiliary 1.85% 2
Fire Pump Running Supervisory 0.93% 1
Power Supply Control 1.85% 2
Programmable Relay Auxiliary 10.19% 11
Pull Station Initiating 10.19% 11
Remote Test Switch Initiating 1.85% 2
Smoke Detector Initiating 6.48% 7
Speaker Indicating 23.15% 25
Speaker/Strobe Indicating 2.78% 3
Strobe Indicating 32.41% 35
Type Qty Model # Description Install Date
In Service - 1 Year to 2 Years Annunciator 1 LCD Display 08/10/2024 Battery 1 08/10/2024 Battery 3 Sealed Lead Acid 08/10/2024 Duct Detector 4 08/10/2024 Fan Shutdown 2 AHU Shutdown 08/10/2024 Power Supply 2 08/10/2024 Programmable Relay 11 08/10/2024 Pull Station 11 08/10/2024 Remote Test Switch 2 08/10/2024 Smoke Detector 7 08/10/2024 Speaker 25 08/06/2024 Speaker/Strobe 3 08/06/2024 Strobe 35 08/06/2024
In Service - 25 Years or Older Fire Pump Running 1 12/31/1969
Page of 24 25 Zone Address Report
Vets Fire & Life Safety Download Date: 11/05/2025
Zone Address Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 44 Control Panel: 1 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID 1-3 128 Programmable Relay 1st 1st Comm Room 8537364 1-3 129 Programmable Relay 1st 1st Comm Room 8537363 1-3 134 Programmable Relay 1st 1st Comm Room 8537365
1-5 Smoke Detector 1st 1st Northwest Pump Room 8537280 1-5 01 Annunciator 1st 1st Behind Front Desk LCD Display 8537347 1-5 01 Smoke Detector 1st 1st Elevator Equipment Room 143 8537276 1-5 01 Pull Station 1st 1st Front Entrance 8537264 1-5 01 Smoke Detector 1st 1st Front Entrance Behind Vestibule 8537275 1-5 01 Fan Shutdown 1st 1st HVAC Room 124 AHU Shutdown 8537345 1-5 01 Fan Shutdown 1st 1st HVAC Room 124 AHU Shutdown 8537346 1-5 01 Smoke Detector 1st 1st HVAC Room 124A 8537277 1-5 01 Smoke Detector 1st 1st HVAC Room 124B 8537278 1-5 01 Smoke Detector 1st 1st HVAC Room 124B 8537279 1-5 01 Pull Station 1st 1st Next to Nurses Office 144-44 8537266 1-5 01 Remote Test Switch 2nd 2nd Between Mens & Women?s
Restrm 8537366
1-5 01 Remote Test Switch 2nd 2nd Between Mens & Women?s Restrm
8537367
1-5 01 Smoke Detector 2nd 2nd Elevator Lobby 8537281 1-5 03 Pull Station 1st 1st East Exit In 124A 8537267 1-5 03 Pull Station 1st 1st East Exit In 124B 8537268 1-5 04 Programmable Relay 1st 1st Elevator Equipment Room 143 8537355 1-5 04 Programmable Relay 1st 1st Elevator Equipment Room 143 8537357 1-5 04 Programmable Relay 1st 1st Elevator Equipment Room 143 8537358 1-5 4 Pull Station 1st 1st Northwest Pump Room 8537270 1-5 33 Pull Station 2nd 2nd East Stair Exit 8537273 1-5 33 Pull Station 2nd 2nd West Stair Exit 8537274 1-5 34 Programmable Relay 1st 1st Comm Room 8537361 1-5 35 Pull Station 1st 1st Front Entrance 8537265 1-5 35 Pull Station 1st 1st North Exit By 124A 8537269 1-5 38 Programmable Relay 1st 1st HVAC Room 124B 8537359 1-5 38 Programmable Relay 1st 1st HVAC Room 124B 8537360 1-5 38 Pull Station 1st 1st South Exit In Stairwell 8537271 1-5 38 Pull Station 1st 1st Southeast Exit 8537272 1-5 41 Programmable Relay 1st 1st Elevator Equipment Room 143 8537356 javascript:editViewDevice('8537364');
javascript:editViewDevice('8537363');
javascript:editViewDevice('8537365');
javascript:editViewDevice('8537280');
javascript:editViewDevice('8537347');
javascript:editViewDevice('8537276');
javascript:editViewDevice('8537264');
javascript:editViewDevice('8537275');
javascript:editViewDevice('8537345');
javascript:editViewDevice('8537346');
javascript:editViewDevice('8537277');
javascript:editViewDevice('8537278');
javascript:editViewDevice('8537279');
javascript:editViewDevice('8537266');
javascript:editViewDevice('8537366');
javascript:editViewDevice('8537367');
javascript:editViewDevice('8537281');
javascript:editViewDevice('8537267');
javascript:editViewDevice('8537268');
javascript:editViewDevice('8537355');
javascript:editViewDevice('8537357');
javascript:editViewDevice('8537358');
javascript:editViewDevice('8537270');
javascript:editViewDevice('8537273');
javascript:editViewDevice('8537274');
javascript:editViewDevice('8537361');
javascript:editViewDevice('8537265');
javascript:editViewDevice('8537269');
javascript:editViewDevice('8537359');
javascript:editViewDevice('8537360');
javascript:editViewDevice('8537271');
javascript:editViewDevice('8537272');
javascript:editViewDevice('8537356');
Page of 25 25 Zone Address Report
Vets Fire & Life Safety Download Date: 11/05/2025
Address Device Type Location Type ScanID 1-5 51 Duct Detector 2nd 2nd Between Mens & Womens
Restrm 34543457
1-5 52 Duct Detector 2nd 2nd Between Mens & Womens Restrm
46738293
1-5 97 Programmable Relay 1st 1st Comm Room 8537362 1-L5 M21 Fire Pump Running 1st 1st Outdoor Pump Room 8537352 javascript:editViewDevice('34543457');
javascript:editViewDevice('46738293');
javascript:editViewDevice('8537362');
javascript:editViewDevice('8537352');
| Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate |
| Executive Summary |
| Notes & Recommendations |
| Inspection & Testing |
| Service Summary |
| Auxiliary Functions Testing |
| Battery & Power Supply Testing |
| Inventory & Warranty Report |
| Zone Address Report |