2025-09-08_Fayetteville-VAMC-Parking-Garage_FireScan.pdf

PDF 137 KB Posted

Attached to
J042--Fire Alarm Service
Solicitation number
36C25626Q0430
Issued by

About this file

This is a Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate for the Fayetteville VAMC Parking Garage located at 1100 N College Ave, Fayetteville, AR 72703. The inspection was completed on September 8, 2025, by Veterans Fire & Life Safety (Inspector Mike Gill) in compliance with The Joint Commission/VHA Standards and the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards. The fire alarm system control unit was installed on August 10, 2024, and is located at the 3rd Main Pedestrian Entrance with breaker protection.

The inspection report documents comprehensive testing of 86 total devices across multiple categories with a 100% pass rate. Tested devices include 2 pull stations, 7 smoke detectors, 11 speakers, 28 speaker/strobes, 25strobes, 1 control panel, 6 batteries, 2 power supplies, and 4 programmable relays. All devices tested in Q3/2025 passed inspection, with no failures recorded. Battery testing confirmed proper voltage levels ranging from 12.21 to 12.67 volts for sealed lead acid batteries rated at 7 Ah and 12-17 volts. The control panel and all auxiliary functions, including elevator control relays, verified correct receipt of alarm and supervisory signals, proper operation of evacuation signals, circuit supervision, and power supply supervision. All equipment was installed between August 10 and October 10, 2024, and remains within the one to two-year warranty period.

View the file

Other files

File Type Posted
36C25626Q0430 0006.pdf PDF
36C25626Q0430 0006.docx DOCX document
P09 SOW Fire Alarm Service 41326 final.docx DOCX document
36C25626Q0430 0005.docx DOCX document
36C25626Q0430 0004.docx DOCX document
P09 SOW Fire Alarm Service Final 4426.docx DOCX document
Questions and answers for 36C25626Q0430 Post.docx DOCX document
36C25626Q0430 0003.docx DOCX document
564-18-135 Complete Dwgs Set.pdf PDF
P09_SOW Fire Alarm Service Revised.docx DOCX document
backflow information excel.xlsx XLSX spreadsheet
36C25626Q0430 0002.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-29_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-21_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-9_FireScan.pdf PDF
36C25626Q0430 EXHIBIT A.docx DOCX document
2025-09-08_Fayetteville-VAMC-Bldg-40_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-2_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-27_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-11_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Leroy-Pond_FireScan.pdf PDF
Marmic Fire Sprinkler Inspection Report 1.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-44_FireScan.pdf PDF
36C25626Q0430 EXHIBIT B.docx DOCX document
combined fire alarm report.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-1_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-3_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-37_FireScan.pdf PDF
2025-09-01_Fayetteville-VAMC-Bldg-6_FireScan.pdf PDF
2025-09-01_Fayetteville-VAMC-Bldg-7_FireScan.pdf PDF
2025-08-27 Fayetteville-VAMC-Red-Barn FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-34_FireScan.pdf PDF
2025-09-15 Fayetteville-VAMC-Bldg-8 FireScan.pdf PDF
36C25626Q0430 EXHIBIT C.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-4_FireScan.pdf PDF
FACTOR 2.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-10_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-5_FireScan.pdf PDF
FACTOR 1.docx DOCX document
36C25626Q0430 0001.docx DOCX document
WD 2015-5109.pdf PDF
P09_SOW Fire Alarm Service.docx DOCX document
36C25626Q0430_1.docx DOCX document
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate

For

Fayetteville VAMC Parking Garage

1100 N College Ave Fayetteville, AR 72703

Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

Inspection Completion Date Sep 8, 2025

Building: Fayetteville VAMC Parking Garage Company: Vets Fire & Life Safety Contact: Travis Ryan Contact: Mike Gill

Title: Safety Specialist Title: Inspector Fire Alarm Testing Report

Page of 1 18 Executive Summary

Vets Fire & Life Safety Download Date: 11/05/2025

Executive Summary Generated by: BuildingReports.com

Building Information Building: Fayetteville VAMC Parking Garage Contact: Travis Ryan

Address: 1100 N College Ave Phone: 479-225-6412

Address: Fax:

City/State/ZIP Code: Fayetteville, AR 72703 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Vets Fire & Life Safety Inspector: Mike Gill

Address: 7 Sherri Lane Phone: 636-543-0165

Address: Fax:

City/State/ZIP Code: St Peters, MO 63376 Mobile:

Country: United States of America Email: mike.gill@vflsc.com

System Control Unit Manufacturer: Inspection Date: 09/08/2025 IDC Style:

Model Number: Install Date: 08/10/2024 SLC Style:

Software Version: Version Date: 08/10/2024 NAC Style:

Location: 3rd Main Pedestrian Entrance Parking Garage Current Protection: Breaker

Page of 2 18

Vets Fire & Life Safety Download Date: 11/05/2025

Inspection Completion Date: Sep 8, 2025 Building: Fayetteville VAMC Parking Garage EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Pull Station 2 2 0 2 0 2

Smoke Detector 7 7 0 7 0 7

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Speaker 11 11 0 11 0 11

Speaker/Strobe 28 28 0 28 0 28

Strobe 25 25 0 25 0 25

LS 02.01.34 EP 02 Protected master fire alarm control panel

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Control Panel 1 1 0 1 0 1

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Battery 6 6 0 6 0 6

Power Supply 2 2 0 2 0 2

Programmable Relay 4 4 0 4 0 4

Total Device Count: 86

Page of 3 18

Vets Fire & Life Safety Download Date: 11/05/2025

Certification

Company: Vets Fire & Life Safety Building: Fayetteville VAMC Parking Garage

Inspector: Mike Gill Contact: Travis Ryan

Page of 4 18 Inspection & Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Inspection & Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Parking Garage The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Pull Station 2 2 0 2 2

Device Type Location ScanID Address Q3/24 Q3/25 Pull Station 3rd By South Stairwell Parking

Garage 58237702 1 08/10-P 09/08-P

Pull Station 3rd Main Entrance Parking Garage 58237718 1 08/10-P 09/08-P

Device Total: 2 Return to Executive Summary

Page of 5 18

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Smoke Detector 7 7 0 7 7

Device Type Location ScanID Address Q3/24 Q3/25 Smoke Detector 1st Elevator Lobby Parking Garage 58237780 1 09/08-P Smoke Detector 1st In E100-18 Elevator Equipment

Room Parking Garage 58237774 1 09/08-P

Smoke Detector 1st In E101-18 Parking Garage 58237779 1 08/10-P 09/08-P Smoke Detector 1st In E102-18 Elevator Equipment

Room Parking Garage 58237775 1 09/08-P

Smoke Detector 2nd Elevator Lobby Parking Garage 58237781 1 09/08-P Smoke Detector 3rd Elevator Lobby Parking Garage 58237763 1 09/08-P Smoke Detector 4th Elevator Lobby Parking Garage 58237743 1 09/08-P

Device Total: 7 Return to Executive Summary

Page of 6 18

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker 11 11 0 11 11

Device Type Location ScanID Address Q3/24 Q3/25 Speaker 2nd Outside Exit of Parking Garage 58237733 1 08/10-P 09/08-P Speaker 3rd Outside By South Stairwell

Parking Garage Parking Garage 58237815 1 08/10-P 09/08-P

Speaker 3rd Outside Main Entrance Parking Garage Parking Garage

58237814 1 08/10-P 09/08-P

Speaker 4th Outside Behind Elevators Parking Garage

58237742 1 08/10-P 09/08-P

Speaker 4th Outside Pole 103 Parking Garage 58237810 1 08/10-P 09/08-P Speaker 4th Outside Pole 104 Parking Garage 58237809 1 08/10-P 09/08-P Speaker 4th Outside Pole 105 Parking Garage 58237808 1 08/10-P 09/08-P Speaker 4th Outside Pole 106 Parking Garage 58237807 1 08/10-P 09/08-P Speaker 4th Outside Pole 86 Parking Garage 58237813 1 08/10-P 09/08-P Speaker 4th Outside Pole 87 Parking Garage 58237812 1 08/10-P 09/08-P Speaker 4th Outside Pole 88 Parking Garage 58237811 1 08/10-P 09/08-P

Device Total: 11 Return to Executive Summary

Page of 7 18

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker/Strobe 28 28 0 28 28

Device Type Location ScanID Address Q3/24 Q3/25 Speaker/Strobe 1st 4th Column From Exit Parking

Garage 58237735 1 08/10-P 09/08-P

Speaker/Strobe 1st 4th Column From Exit Parking Garage Parking Garage

58237734 1 08/10-P 09/08-P

Speaker/Strobe 1st 8th Column From Exit Parking Garage Parking Garage

58237736 1 08/10-P 09/08-P

Speaker/Strobe 1st Across From South Stairwell Parking Garage Parking Garage

58237741 1 08/10-P 09/08-P

Speaker/Strobe 1st By Equipment Storage Parking Garage Parking Garage

58237737 1 08/10-P 09/08-P

Speaker/Strobe 1st Center Column Parking Garage 58237739 1 08/10-P 09/08-P Speaker/Strobe 1st Elevator Lobby Parking Garage 58237724 1 08/10-P 09/08-P Speaker/Strobe 1st Outside Elevator Lobby Parking

Garage Parking Garage 58237725 1 08/10-P 09/08-P

Speaker/Strobe 1st South Exit Parking Garage 58237732 1 08/10-P 09/08-P Speaker/Strobe 2nd Across From South Stairwell

Parking Garage 58237716 1 08/10-P 09/08-P

Speaker/Strobe 2nd By Exit In Parking Garage 58237767 1 08/10-F 09/08-P Speaker/Strobe 2nd Elevator Lobby Parking Garage 58237721 1 08/10-P 09/08-P Speaker/Strobe 2nd North Ramp 2nd To 1st Parking

Garage Parking Garage 58237730 1 08/10-P 09/08-P

Speaker/Strobe 2nd Outside Center Column Parking Garage Parking Garage

58237769 1 08/10-P 09/08-P

Speaker/Strobe 2nd Outside Elevator Lobby Parking Garage

58237722 1 08/10-P 09/08-P

Speaker/Strobe 2nd Ramp 2nd To 1st Parking Garage 58237758 1 08/10-P 09/08-P Speaker/Strobe 3rd 5 Column in Parking Garage 58237708 1 08/10-P 09/08-P Speaker/Strobe 3rd 9th Column in Parking Garage 58237710 1 08/10-P 09/08-P Speaker/Strobe 3rd By Main Panel in Parking Garage 58237697 1 08/10-P 09/08-P Speaker/Strobe 3rd By Mini Bus Parking In Parking

Garage 58237698 1 08/10-P 09/08-P

Speaker/Strobe 3rd Center Lower End Of Ramp 3 to 2 Parking Garage

58237714 1 08/10-P 09/08-P

Speaker/Strobe 3rd Center Top Of Ramp 3 to 2 Parking Garage

58237711 1 08/10-P 09/08-P

Speaker/Strobe 3rd Floor North End Parking Garage 58237705 1 08/10-P 09/08-P Speaker/Strobe 3rd Level 5th Column in Parking 58237765 1 08/10-P 09/08-P

Page of 8 18

Vets Fire & Life Safety Download Date: 11/05/2025

Device Type Location ScanID Address Q3/24 Q3/25 Garage

Speaker/Strobe 3rd Level 9th Column in Parking Garage Parking Garage

58237764 1 08/10-P 09/08-P

Speaker/Strobe 3rd Middle Column Parking Garage 58237700 1 08/10-P 09/08-P Speaker/Strobe 3rd South End Parking Garage 58237706 1 08/10-P 09/08-P Speaker/Strobe 4th Elevator Lobby Parking Garage 58237744 1 08/10-P 09/08-P

Device Total: 28 Return to Executive Summary

Page of 9 18

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Strobe 25 25 0 25 25

Device Type Location ScanID Address Q3/24 Q3/25 Strobe 1st 1st Column From Elevator Lobby

Parking Garage 58237738 1 08/10-P 09/08-P

Strobe 1st 2nd Column From Exit Parking Garage Parking Garage

58237729 1 08/10-P 09/08-P

Strobe 1st 6th Column From Exit Parking Garage

582376 1 08/10-P 09/08-P

Strobe 1st Column by South Stairway Parking Garage Parking Garage

58237740 1 08/10-P 09/08-P

Strobe 1st Ramp 2nd to 1st Parking Garage 58237731 1 08/10-P 09/08-P Strobe 1st Stairs Across From Elevator?s

Parking Garage 58237723 1 08/10-P 09/08-P

Strobe 2nd Behind Elevator Lobby Parking Garage

58237770 1 08/10-P 09/08-P

Strobe 2nd Bottom Of Ramp 3 to 2 Parking Garage

58237715 1 08/10-P 09/08-P

Strobe 2nd By South Stairwell Parking Garage

58237768 1 08/10-P 09/08-P

Strobe 2nd Level 7th Cloumn in Parking Garage Parking Garage

17804384 1 08/10-P 09/08-P

Strobe 2nd North Ramp 2nd To 1st Parking Garage Parking Garage

58237728 1 08/10-P 09/08-P

Strobe 2nd Ramp 2nd to 1st Parking Garage 58237727 1 08/10-P 09/08-P Strobe 2nd Side 3rd Column Parking Garage 58237766 1 08/10-P 09/08-P Strobe 2nd South Stairwell Between 1&2

Floors Parking Garage 58237717 1 08/10-P 09/08-P

Strobe 2nd Stairs Across From Elevator?s Parking Garage

58237720 1 08/10-P 09/08-P

Strobe 3rd 3rd Column Parking Garage 58237707 1 08/10-P 09/08-P Strobe 3rd 7th Column Parking Garage 58237709 1 08/10-P 09/08-P Strobe 3rd By Mini Bus Parking In Parking

Garage Parking Garage 58237699 1 08/10-P 09/08-P

Strobe 3rd Column by South Stairway Parking Garage Parking Garage

58237701 1 08/10-P 09/08-P

Strobe 3rd Ramp 3 to 2 Parking Garage 58237712 1 08/10-P 09/08-P Strobe 3rd Ramp 3 to 2 Parking Garage 58237713 1 08/10-P 09/08-P Strobe 3rd Ramp To 4th Floor Parking

Garage 58237704 1 08/10-P 09/08-P

Strobe 3rd South Stairwell Between 3&4 58237703 1 08/10-P 09/08-P

Page of 10 18

Vets Fire & Life Safety Download Date: 11/05/2025

Device Type Location ScanID Address Q3/24 Q3/25 Floors Parking Garage

Strobe 3rd Stairs By Main Entrance Parking Garage

58237719 1 08/10-P 09/08-P

Strobe 4th Stairs Across From Elevator?s Parking Garage

58237745 1 08/10-P 09/08-P

Device Total: 25 Return to Executive Summary

Page of 11 18

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 02 Protected master fire alarm control panel

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Control Panel 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Q3/25 Control Panel 3rd Main Pedestrian Entrance

Parking Garage 58237690 1 08/10-P 09/08-P

Device Total: 1 Return to Executive Summary

Page of 12 18

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Battery 6 6 0 6 6

Device Type Location ScanID Address Q3/24 Q3/25 Battery 1st In Power Supply Parking Garage 42073985 1 08/10-P 09/08-P Battery 1st In Power Supply Parking Garage 42073986 1 08/10-P 09/08-P Battery 1st In Room 101-18 Parking Garage 42073987 1 08/10-P 09/08-P Battery 1st In Room 101-18 Parking Garage 42073988 1 08/10-P 09/08-P Battery 1st Main FCPS Parking Garage 42073991 1 08/10-P 09/08-P Battery 1st Main FCPS Parking Garage 42073992 1 08/10-P 09/08-P

Device Total: 6 Return to Executive Summary

Page of 13 18

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Power Supply 2 2 0 2 2

Device Type Location ScanID Address Q3/24 Q3/25 Power Supply 1st Beside Power Supply Parking

Garage 42073984 1 08/10-P 09/08-P

Power Supply 1st In Room 101-18 Parking Garage 42073983 1 08/10-P 09/08-P

Device Total: 2 Return to Executive Summary

Page of 14 18

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Programmable Relay 4 4 0 4 4

Device Type Location ScanID Address Q3/24 Q3/25 Programmable Relay 1st In E100-18 Elevator Equipment

Room Parking Garage 58237772 1 09/08-P

Programmable Relay 1st In E100-18 Elevator Equipment Room Parking Garage

58237771 1 09/08-P

Programmable Relay 1st In E100-18 Elevator Equipment Room Parking Garage

58237726 1 09/08-P

Programmable Relay 1st In E100-18 Elevator Equipment Room Parking Garage

58237773 1 09/08-P

Device Total: 4 Return to Executive Summary

Page of 15 18 Service Summary

Vets Fire & Life Safety Download Date: 11/05/2025

Service Summary Generated by: BuildingReports.com

Building: Fayetteville VAMC Parking Garage The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed Battery Tested 6 Control Panel Tested 1 Power Supply Tested 2 Programmable Relay Tested 4 Pull Station Tested 2 Smoke Detector Tested/Cleaned 7 Speaker/Strobe Tested 28 Speaker Tested 11 Strobe Tested 25

Total 86 Grand Total 86

Page of 16 18 Auxiliary Functions Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Auxiliary Functions Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Parking Garage

Control Panel: 1 -

The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Programmable Relay

1st In E100-18 Elevator Equipment Room Parking Garage

Passed 58237772

1st In E100-18 Elevator Equipment Room Parking Garage

Passed 58237771

1st In E100-18 Elevator Equipment Room Parking Garage

Passed 58237726

1st In E100-18 Elevator Equipment Room Parking Garage

Passed 58237773 javascript:editViewDevice('58237772');

javascript:editViewDevice('58237771');

javascript:editViewDevice('58237726');

javascript:editViewDevice('58237773');

Page of 17 18 Battery & Power Supply Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Parking Garage

Control Panel: 1 -

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Passed Sealed Lead Acid 1st In Power Supply Parking

Garage 7 12 12.21

Sealed Lead Acid 1st In Power Supply Parking Garage

7 17 12.28

Sealed Lead Acid 1st In Room 101-18 Parking Garage

7 12 12.43

Sealed Lead Acid 1st In Room 101-18 Parking Garage

7 12 12.56

Sealed Lead Acid 1st Main FCPS Parking Garage

7 12 12.38

Sealed Lead Acid 1st Main FCPS Parking Garage

7 12 12.67

Page of 18 18 Inventory & Warranty Report

Vets Fire & Life Safety Download Date: 11/05/2025

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Parking Garage

Control Panel: 1 -

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Battery Control 6.98% 6

Control Panel Control 1.16% 1

Power Supply Control 2.33% 2

Programmable Relay Auxiliary 4.65% 4

Pull Station Initiating 2.33% 2

Smoke Detector Initiating 8.14% 7

Speaker Indicating 12.79% 11

Speaker/Strobe Indicating 32.56% 28

Strobe Indicating 29.07% 25

Type Qty Model # Description Install Date

In Service - 1 Year to 2 Years Battery 6 Sealed Lead Acid 08/10/2024 Control Panel 1 08/10/2024 Power Supply 2 08/10/2024 Programmable Relay 4 08/10/2024 Pull Station 2 08/10/2024 Smoke Detector 7 08/10/2024 Speaker 11 08/10/2024 Speaker/Strobe 28 08/10/2024 Strobe 25 08/10/2024

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
Executive Summary
Inspection & Testing
Service Summary
Auxiliary Functions Testing
Battery & Power Supply Testing
Inventory & Warranty Report

File details come from the government source that posted it. Updated .