2025-09-15_Fayetteville-VAMC-Leroy-Pond_FireScan.pdf

PDF 211 KB Posted

Attached to
J042--Fire Alarm Service
Solicitation number
36C25626Q0430
Issued by

About this file

This is a Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate documenting an annual inspection performed on September 15, 2025, at Fayetteville VAMC Leroy Pond (1100 N College Ave, Fayetteville, AR 72703). Veterans Fire and Life Safety conducted the inspection in compliance with The Joint Commission/VHA Standards and latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards. The inspection was performed by Rod Davis (Manager, Veterans Fire & Life Safety, St Peters, MO 63376) with building contact Travis Ryan (Safety Specialist, 479-225-6412). The system control unit is a Notifier manufacturer unit installed on August 6, 2024, located in the 1st North Electrical Room with breaker current protection.

The inspection tested a total of 190 devices across multiple categories, all of which passed testing. Testing included 2 tamper switches (semi-annual), 1 waterflow switch (semi-annual), 6 duct detectors, 1 heat detector, 20 pull stations, 34 smoke detectors, 82 horn/strobes, 10strobes, 5 monitor devices, 2 monitoring devices, 6 initiating devices, 3 annunciators, 10 batteries, 1 control panel, 3 power supplies, and 4 programmable relays. All devices were tested in accordance with NFPA 72 (2022) and NFPA 90A (2024) standards. Duct detector batteries were replaced during the inspection. All batteries tested maintained adequate voltage levels (ranging from 12.30 to 13.38 volts for sealed lead acid units). No failed devices were identified, and auxiliary functions including AHU shutdowns and programmable relays all passed testing.

View the file

Other files

File Type Posted
36C25626Q0430 0006.pdf PDF
36C25626Q0430 0006.docx DOCX document
P09 SOW Fire Alarm Service 41326 final.docx DOCX document
36C25626Q0430 0005.docx DOCX document
36C25626Q0430 0004.docx DOCX document
P09 SOW Fire Alarm Service Final 4426.docx DOCX document
Questions and answers for 36C25626Q0430 Post.docx DOCX document
36C25626Q0430 0003.docx DOCX document
564-18-135 Complete Dwgs Set.pdf PDF
P09_SOW Fire Alarm Service Revised.docx DOCX document
backflow information excel.xlsx XLSX spreadsheet
36C25626Q0430 0002.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-29_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-21_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-9_FireScan.pdf PDF
36C25626Q0430 EXHIBIT A.docx DOCX document
2025-09-08_Fayetteville-VAMC-Bldg-40_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-2_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-27_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-11_FireScan.pdf PDF
Marmic Fire Sprinkler Inspection Report 1.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-44_FireScan.pdf PDF
36C25626Q0430 EXHIBIT B.docx DOCX document
combined fire alarm report.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-1_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-3_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-37_FireScan.pdf PDF
2025-09-01_Fayetteville-VAMC-Bldg-6_FireScan.pdf PDF
2025-09-01_Fayetteville-VAMC-Bldg-7_FireScan.pdf PDF
2025-08-27 Fayetteville-VAMC-Red-Barn FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-34_FireScan.pdf PDF
2025-09-15 Fayetteville-VAMC-Bldg-8 FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Parking-Garage_FireScan.pdf PDF
36C25626Q0430 EXHIBIT C.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-4_FireScan.pdf PDF
FACTOR 2.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-10_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-5_FireScan.pdf PDF
FACTOR 1.docx DOCX document
36C25626Q0430 0001.docx DOCX document
WD 2015-5109.pdf PDF
P09_SOW Fire Alarm Service.docx DOCX document
36C25626Q0430_1.docx DOCX document
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate

For

Fayetteville VAMC Leroy Pond 1100 N College Ave

Fayetteville, AR 72703 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

Annual Inspection Inspection Completion Date Sep 15, 2025

Building: Fayetteville VAMC Leroy Pond Company: Vets Fire & Life Safety Contact: Travis Ryan Contact: Rod Davis

Title: Safety Specialist Title: Manager Fire Alarm Testing Report

Page of 1 32 Executive Summary

Vets Fire & Life Safety Download Date: 11/05/2025

Executive Summary Generated by: BuildingReports.com

Building Information Building: Fayetteville VAMC Leroy Pond Contact: Travis Ryan

Address: 1100 N College Ave Phone: 479-225-6412

Address: Fax:

City/State/ZIP Code: Fayetteville, AR 72703 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Vets Fire & Life Safety Inspector: Rod Davis

Address: 7 Sherri Lane Phone: 314-696-7000

Address: Fax:

City/State/ZIP Code: St Peters, MO 63376 Mobile:

Country: United States of America Email: rod.davis@vflsc.com

System Control Unit Manufacturer: Notifier Inspection Date: 09/08/2025 IDC Style:

Model Number: Install Date: 08/06/2024 SLC Style:

Software Version: Version Date: 08/06/2024 NAC Style:

Location: 1st 1st North Electrical Room Current Protection: Breaker

Central Station Signal Verification Type: Mfg: Model #:

Test Time/Date: Restore Time: Note:

Type of Signal Signal Confirmation Notes Confirmed Time:

Confirmed Time:

Page of 2 32

Vets Fire & Life Safety Download Date: 11/05/2025

Inspection Completion Date: Sep 15, 2025 Building: Fayetteville VAMC Leroy Pond EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Tamper Switch 2 2 0 2 0 2

EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Waterflow Switch 1 1 0 1 0 1

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Duct Detector 6 6 0 6 0 6

Heat Detector 1 1 0 1 0 1

Pull Station 20 20 0 20 0 20

Smoke Detector 34 34 0 34 0 34

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Horn/Strobe 82 82 0 82 0 82

Strobe 10 10 0 10 0 10

EC 02.03.05 EP 05 Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Monitor Device 5 5 0 5 0 5

Monitoring 2 2 0 2 0 2

EC 02.03.05 EP 19 Annual test of automatic smoke-detection shutdown devices for air-handling equipment.

NFPA 90A (2024) 6.4.1

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Duct Detector 6 6 0 6 0 6

Page of 3 32

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 02 Protected master fire alarm control panel

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Control Panel 1 1 0 1 0 1

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Annunciator 3 3 0 3 0 3

Battery 10 10 0 10 0 10

Initiating Device 6 6 0 6 0 6

Power Supply 3 3 0 3 0 3

Programmable Relay 4 4 0 4 0 4

Total Device Count: 190

Page of 4 32

Vets Fire & Life Safety Download Date: 11/05/2025

Certification

Company: Vets Fire & Life Safety Building: Fayetteville VAMC Leroy Pond

Inspector: Rod Davis Contact: Travis Ryan

Page of 5 32 Notes & Recommendations

Vets Fire & Life Safety Download Date: 11/05/2025

Notes & Recommendations Generated by: BuildingReports.com

Building: Fayetteville VAMC Leroy Pond Control Panel: 1 - Notifier The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

Note Device Type Location Comment ScanID

EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;

water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

1 Tamper Switch 1st 1st Northwest Riser in Outside Room

Passed 43810245

Testing Done By Others 2 Tamper Switch 1st 1st Northwest Riser in Outside Room

Passed 43810246

Testing Done By Others

EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table

14.4.3.2 (17)(10)(a) & (17)(11)

3 Waterflow Switch 1st 1st Northwest Riser in Outside Room

Passed 43810243

Testing Done By Others javascript:editViewDevice('43810245');

javascript:editViewDevice('43810246');

javascript:editViewDevice('43810243');

Page of 6 32 Inspection & Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Inspection & Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Leroy Pond The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 01

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Tamper Switch 2 2 0 2 2

Device Type Location ScanID Address Q3/24 Q3/25 Tamper Switch 1st 1st Northwest Riser in Outside

Room 178 43810246 1-M1-12 08/20-P 09/15-P

Tamper Switch 1st 1st Northwest Riser in Outside Room 178

43810245 1-M1-12 08/20-P 09/15-P

Device Total: 2 Return to Executive Summary

Page of 7 32

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table

14.4.3.2 (17)(11)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Waterflow Switch 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Q3/25 Waterflow Switch 1st 1st Northwest Riser in Outside

Room 178 43810243 1-M1-13 08/20-P 09/15-P

Device Total: 1 Return to Executive Summary

Page of 8 32

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Duct Detector 6 6 0 6 6

Device Type Location ScanID Address Q3/24 Q3/25 Duct Detector 1st 1st North Mech Room 146 45935576 1-1--2 08/06-P 09/08-P Duct Detector 1st 1st North Mech Room 146 43810269 1-1--2 08/06-P 09/08-P Duct Detector 1st 1st North Mech Room 149 43810262 1-1--3 08/06-P 09/08-P Duct Detector 1st 1st North Mech Room 149 43810261 1-1--5 08/06-P 09/08-P Duct Detector 1st 1st Northwest Mech Room 178 43810256 1-1--9 08/06-P 09/08-P Duct Detector 1st 1st Northwest Mech Room 178 43810255 1-1--10 08/06-P 09/08-P

Device Total: 6 Return to Executive Summary

Page of 9 32

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.

(NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Heat Detector 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Q3/25 Heat Detector 1st 1st Garage Breakroom Heat 45935557 1-D1-60 08/06-P 09/08-P

Page of 10 32

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Pull Station 20 20 0 20 20

Device Type Location ScanID Address Q3/24 Q3/25 Pull Station 1st 1st North Mech Room 146 43810267 1-1--7 08/10-P 09/08-P Pull Station 1st 1st Northwest Mech Room 178 43810247 1-1--14 08/10-P 09/08-P Pull Station 1st 1st North Storage Room 43810129 1-1--16 08/10-P 09/08-P Pull Station 1st 1st North Resident Day Room 153 43810158 1-1--10 08/10-P 09/08-P Pull Station 1st 1st Southeast Entrance 43810139 1-1--4 08/10-P 09/08-P Pull Station 1st 1st North Storage Room 43810130 1-1--6 08/10-P 09/08-P Pull Station 1st 1st North Exit By Room 112 43810133 1-1--5 08/10-P 09/08-P Pull Station 1st 1st Garage Office Room 5 Pull

Station 45935571 1-1-L1 M56 08/10-P 09/08-P

Pull Station 1st 1st South Hall By Staff Restroom

43810166 1-1--2 08/10-P 09/08-P

Pull Station 1st 1st Northwest Hall Exit By Room

43810229 1-1--7 08/10-P 09/08-P

Pull Station 1st 1st Northwest Hall Exit By Room

43810240 1-1--5 08/10-P 09/08-P

Pull Station 1st 1st North Mech Room 149 43810260 1-1--9 08/10-P 09/08-P Pull Station 1st 1st Garage North East Garage

Bay Pull Station 45935568 1-1-L1 M52 08/10-P 09/08-P

Pull Station 1st 1st Garage Office Room 8 Pull Station

45935567 1-1-L1 M51 08/10-P 09/08-P

Pull Station 1st 1st Garage Breakroom Pull Station

45935558 1-1-L1 M54 08/10-P 09/08-P

Pull Station 1st 1st Garage South East Garage Bay Pull Station

45935562 1-1-L1 M57 08/10-P 09/08-P

Pull Station 1st 1st Garage Office Room 6 Pull Station

45935563 1-1-L1 M50 08/10-P 09/08-P

Pull Station 1st 1st Garage North West Garage Bay Pull Station

45935554 1-1-L1 M53 08/10-P 09/08-P

Pull Station 1st 1st Garage South West Garage Bay Pull Station

45935560 1-1-L1 M55 08/10-P 09/08-P

Pull Station 1st 1st North Electrical Room 43810128 1-1--8 08/10-P 09/08-P

Device Total: 20 Return to Executive Summary

Page of 11 32

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Smoke Detector 34 34 0 34 34

Device Type Location ScanID Address Q3/24 Q3/25 Smoke Detector 1st 1st Garage Office Room 5 Smoke 45935569 1-1-L1 D54 08/10-P 09/08-P Smoke Detector 1st 1st North Electrical Room 43810126 1-1-D1 08/10-P 09/08-P Smoke Detector 1st 1st Garage Office Room 6 Smoke 45935565 1-1-L1 D50 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #2 Room 176 43810172 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #3 Room 179 43810175 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #1 Room 175 43810171 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Garage Office Room 7 Smoke 45935564 1-1-L1 D51 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #4 Room 180 43810178 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #20 Room 197 43810226 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #10 Room 186 43810196 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #12 Room 188 43810202 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #16 Room 193 43810214 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #14 Room 190 43810208 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Hall Exit By Room

43810230 1-1 08/10-P 09/08-P

Smoke Detector 1st 1st Northwest Hall By Room 180 43810232 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Hall By Room 182 43810233 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Hall Exit By Room

43810239 1-1 08/10-P 09/08-P

Smoke Detector 1st 1st Northwest Hall By Room 189 43810237 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Hall By Room 185 43810235 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Hall By Room 187 43810236 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #19 Room 196 43810223 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #18 Room 195 43810220 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #17 Room 194 43810217 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #15 Room 192 43810211 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #13 Room 189 43810205 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #6 Room 182 43810184 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #5 Room 181 43810181 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #11 Room 187 43810199 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #9 Room 185 43810193 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #8 Room 184 43810190 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Northwest Bed #7 Room 183 43810187 1-1 08/10-P 09/08-P Smoke Detector 1st 1st Garage Room 305 Garage 45935553 1-1-L1 D55 08/10-P 09/01-P

Page of 12 32

Vets Fire & Life Safety Download Date: 11/05/2025

Device Type Location ScanID Address Q3/24 Q3/25 Power Supply

Smoke Detector 1st 1st Garage Office Room 8 Smoke 45935566 1-1-L1 D52 08/10-P 09/01-P Smoke Detector 1st 1st southwest Mechanical Room

45935574 1-1 08/10-P 09/01-P

Device Total: 34 Return to Executive Summary

Page of 13 32

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Horn/Strobe 82 82 0 82 82

Device Type Location ScanID Address Q3/24 Q3/25 Horn/Strobe 1st 1st Northwest Bed #20 Room 197 43810227 1 08/10-P 09/08-P Horn/Strobe 1st 1st North Electrical Room 43810127 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Nurse Station 170A 45935579 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #10 Room 186 43810197 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #19 Room 196 43810224 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #14 Room 190 43810209 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #9 Room 185 43810194 1 08/10-P 09/08-P Horn/Strobe 1st 1st North Storage Room 43810131 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #2 Room 176 43810173 1 08/10-P 09/08-P Horn/Strobe 1st 1st North Laundry Room 154 43810157 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #19 Room 196

Bathroom 43810225 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #12 Room 188 43810203 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #11 Room 187

Bathroom 43810201 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #11 Room 187 43810200 1 08/10-P 09/08-P Horn/Strobe 1st 1st South Room 164 58237841 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #10 Room 186

Bathroom 43810198 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #20 Room 197 Bathroom

43810228 1 08/10-P 09/08-P

Horn/Strobe 1st 1st South Room 143 45935581 1 08/10-P 09/08-P Horn/Strobe 1st 1st North Storage Room 45935582 1 08/10-P 09/08-P Horn/Strobe 1st 1st courtyard Courtyard 45935580 1 08/10-P 09/08-P Horn/Strobe 1st 1st South Room 168 45935578 1 08/10-P 09/08-P Horn/Strobe 1st 1st North Mech Room 149 43810266 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Mech Room 178 43810254 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Hall Exit By Room

43810231 1 08/10-P 09/08-P

Horn/Strobe 1st 1st South Room 163 45935577 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Room 173 Fitness 45935573 1 08/10-P 09/08-P Horn/Strobe 1st 1st South East Exterior Wall Next to Entrance 45935572 1 08/10-P 09/08-P

Horn/Strobe 1st 1st North Mech Room 146 43810268 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Hall By Room 189 43810238 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Hall By Room 183 43810234 1 08/10-P 09/08-P

Page of 14 32

Vets Fire & Life Safety Download Date: 11/05/2025

Device Type Location ScanID Address Q3/24 Q3/25 Horn/Strobe 1st 1st Northwest Bed #18 Room 195

Bathroom 43810222 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #15 Room 192 Bathroom

43810213 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #13 Room 189 43810206 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #12 Room 188

Bathroom 43810204 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #18 Room 195 43810221 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #17 Room 194

Bathroom 43810219 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #17 Room 194 43810218 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #16 Room 193

Bathroom 43810216 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #16 Room 193 43810215 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #14 Room 190

Bathroom 43810210 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #15 Room 192 43810212 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #13 Room 189

Bathroom 43810207 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #9 Room 185 Bathroom

43810195 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #7 Room 183 Bathroom

43810189 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #2 Room 176 Bathroom

43810174 1 08/10-P 09/08-P

Horn/Strobe 1st 1st South Leroy Pond Grouproom

43810164 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #1 Room 175 Bathroom

43810170 1 08/10-P 09/08-P

Horn/Strobe 1st 1st South Staff Restroom 171 43810168 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #1 Room 175 43810169 1 08/10-P 09/08-P Horn/Strobe 1st 1st South Hall By Staff Restroom

17- 43810167 1 08/10-P 09/08-P

Horn/Strobe 1st 1st North Recreational Therapy Room 150

43810161 1 08/10-P 09/08-P

Horn/Strobe 1st 1st South Breakroom 169 43810163 1 08/10-P 09/08-P Horn/Strobe 1st 1st South Hall By Leroy Pond

Room 165 43810165 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #8 Room 184 Bathroom

43810192 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #3 Room 179 Bathroom

43810177 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #8 Room 184 43810191 1 08/10-P 09/08-P

Page of 15 32

Vets Fire & Life Safety Download Date: 11/05/2025

Device Type Location ScanID Address Q3/24 Q3/25 Horn/Strobe 1st 1st Northwest Bed #6 Room 182

Bathroom 43810186 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #7 Room 183 43810188 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #6 Room 182 43810185 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #5 Room 181

Bathroom 43810183 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #5 Room 181 43810182 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #4 Room 180

Bathroom 43810180 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northwest Bed #4 Room 180 43810179 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northwest Bed #3 Room 179 43810176 1 08/10-P 09/08-P Horn/Strobe 1st 1st North Hall By Housekeeping

Closet 158 43810162 1 08/10-P 09/08-P

Horn/Strobe 1st 1st North Hall By Resident Day Room 153

43810160 1 08/10-P 09/08-P

Horn/Strobe 1st 1st North Resident Day Room 153 43810159 1 08/10-P 09/08-P Horn/Strobe 1st 1st South Hall By Leroy Pond by room 165 43810156 1 08/10-P 09/08-P

Horn/Strobe 1st 1st South Hall Group Room 167 43810155 1 08/10-P 09/08-P Horn/Strobe 1st 1st South Hall Outpatient

Dayroom 136 43810154 1 08/10-P 09/08-P

Horn/Strobe 1st 1st South Hall By Hot Room 138 43810153 1 08/10-P 09/08-P Horn/Strobe 1st 1st Southeast Lobby Waiting Area 43810150 1 08/10-P 09/08-P Horn/Strobe 1st 1st North Hall By Room 108 43810136 1 08/06-P 09/08-P Horn/Strobe 1st 1st South Hall By Soiled Storage

Room 140 43810149 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Northeast Hall By Shower Room 141

43810148 1 08/10-P 09/08-P

Horn/Strobe 1st 1st North Hall By Room 111 43810134 1 08/10-P 09/08-P Horn/Strobe 1st 1st Northeast Hall By Womens

Staff Restroom R122 43810146 1 08/10-P 09/08-P

Horn/Strobe 1st 1st North Hall By Room 110 43810135 1 08/06-P 09/08-P Horn/Strobe 1st 1st North Storage Room 43810132 1 08/06-P 09/08-P Horn/Strobe 1st 1st North Hall By Room 106 43810137 1 08/06-P 09/08-P Horn/Strobe 1st 1st Southeast Lobby By Room

43810140 1 08/10-P 09/08-P

Horn/Strobe 1st 1st Southeast Hall By Room 132 43810141 1 08/10-P 09/08-P

Device Total: 82 Return to Executive Summary

Page of 16 32

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Strobe 10 10 0 10 10

Device Type Location ScanID Address Q3/24 Q3/25 Strobe 1st 1st Garage Room 304 Restroom

Strobe 45935559 1 08/10-P 09/08-P

Strobe 1st 1st Garage South East Garage Bay Strobe

45935561 1 08/10-P 09/08-P

Strobe 1st 1st Northeast Hall Restroom Room 120

43810143 1 08/10-P 09/08-P

Strobe 1st 1st Southeast Hall Restroom Room 127

43810142 1 08/10-P 09/08-P

Strobe 1st 1st Northeast Hall Womens Staff Restroom 122

43810145 1 08/10-P 09/08-P

Strobe 1st 1st Garage North West Garage BayStrobe

45935555 1 08/10-P 09/08-P

Strobe 1st 1st South Hall Men?s Restroom

43810151 1 08/10-P 09/08-P

Strobe 1st 1st Northeast Hall Break Room

43810147 1 08/10-P 09/08-P

Strobe 1st 1st South Hall Women?s Restroom 162

43810152 1 08/10-P 09/08-P

Strobe 1st 1st Northeast Hall Men?s Staff Restroom Room 121

43810144 1 08/10-P 09/08-P

Device Total: 10 Return to Executive Summary

Page of 17 32

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 05

Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)

Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-22 Table 14.4.3.2 (4)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Monitor Device 5 5 0 5 5

Device Type Location ScanID Address Q3/24 Q3/25 Monitor Device 1st 1st North FACP Room 43810120 1 08/10-P 09/08-P Monitor Device 1st 1st Northwest Mech Room 178

Power Supply 43810250 1 08/10-P 09/08-P

Monitor Device 1st 1st Northeast Mech Room 178 43810249 1 08/10-P 09/08-P Monitor Device 1st 1st Northeast Mech Room 178 43810248 1 08/10-P 09/08-P Monitor Device 1st 1st North FACP Room Power

Supply 43810272 1 08/10-P 09/08-P

Device Total: 5 Return to Executive Summary

Page of 18 32

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 05

Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)

Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-22 Table 14.4.3.2 (4)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Monitoring 2 2 0 2 2

Device Type Location ScanID Address Q3/24 Q3/25 Monitoring 1st 1st North FACP Room 43810118 1 08/10-P 09/08-P Monitoring 1st 1st North FACP Room 43810117 1 08/10-P 09/08-P

Device Total: 2 Return to Executive Summary

Page of 19 32

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment.

NFPA 90A (2024) 6.4.1

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(e)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Duct Detector 6 6 0 6 6

Device Type Location ScanID Address Q3/24 Q3/25 Duct Detector 1st 1st North Mech Room 146 45935576 1-1--2 08/06-P 09/08-P Duct Detector 1st 1st North Mech Room 146 43810269 1-1--2 08/06-P 09/08-P Duct Detector 1st 1st North Mech Room 149 43810262 1-1--3 08/06-P 09/08-P Duct Detector 1st 1st North Mech Room 149 43810261 1-1--5 08/06-P 09/08-P Duct Detector 1st 1st Northwest Mech Room 178 43810256 1-1--9 08/06-P 09/08-P Duct Detector 1st 1st Northwest Mech Room 178 43810255 1-1--10 08/06-P 09/08-P

Page of 20 32

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 02 Protected master fire alarm control panel

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Control Panel 1 1 0 1 1

Device Type Location ScanID Address Q3/24 Q3/25 Control Panel 1st 1st North Electrical Room 43810116 1 08/06-P 09/08-P

Page of 21 32

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-22 Table 14.4.3.2 (11)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Annunciator 3 3 0 3 3

Device Type Location ScanID Address Q3/24 Q3/25 Annunciator 1st 1st South Nurses Station 43810291 1 08/06-P 09/08-P Annunciator 1st 1st Garage Office Room 5

Annunciator 45935570 1 08/06-P 09/08-P

Annunciator 1st 1st North Hall By Room 106 43810138 1 08/06-F 09/08-P

Device Total: 3 Return to Executive Summary

Page of 22 32

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Battery 10 10 0 10 10

Device Type Location ScanID Address Q3/24 Q3/25 Battery 1st 1st Northwest Mech Room 178

Power Supply 58240822 1 08/06-F 09/08-P

Battery 1st 1st Northwest Mech Room 178 Power Supply

58240783 1 08/06-F 09/08-P

Battery 1st 1st Garage Room 305 Garage Power Supply

45935551 1 08/06-P 09/08-P

Battery 1st 1st Garage Room 305 Garage Power Supply

45935550 1 08/06-P 09/08-P

Battery 1st 1st Northwest Mech Room 178 Power Supply

43810253 1 08/06-F 09/08-P

Battery 1st 1st Northwest Mech Room 178 Power Supply

43810252 1 08/06-F 09/08-P

Battery 1st 1st North FACP Room Power Supply

43810125 1 08/06-P 09/08-P

Battery 1st 1st North FACP Room Power Supply

43810124 1 08/06-P 09/08-P

Battery 1st 1st North FACP Room Main FACP 43810122 1 08/06-F 09/01-P Battery 1st 1st North FACP Room Main FACP 43810121 1 08/06-F 09/01-P

Device Total: 10 Return to Executive Summary

Page of 23 32

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Test fire-gas detectors and other fire detectors as prescribed by the manufacturer and as necessary for the application. (NFPA 72-22 Table 14.4.3.2 (17)(3)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Initiating Device 6 6 0 6 6

Device Type Location ScanID Address Q3/24 Q3/25 Initiating Device 1st 1st Northwest Mech Room 178 43810257 1 08/10-P 09/08-P Initiating Device 1st 1st North Mech Room 146 45935575 1 08/10-P 09/08-P Initiating Device 1st 1st Northwest Mech Room 178 43810259 1 08/10-P 09/08-P Initiating Device 1st 1st North Mech Room 146 43810271 1 08/10-P 09/08-P Initiating Device 1st 1st North Mech Room 149 43810264 1 08/10-P 09/08-P Initiating Device 1st 1st North Mech Room 149 43810263 1 08/10-P 09/08-P

Page of 24 32

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Power Supply 3 3 0 3 3

Device Type Location ScanID Address Q3/24 Q3/25 Power Supply 1st 1st Garage next to Leroy pond

Room 305 Garage 45935549 1 08/10-P 09/08-P

Power Supply 1st 1st Northwest Mech Room 178 43810251 1 08/10-P 09/08-P Power Supply 1st 1st North FACP Room 43810123 1 08/10-P 09/08-P

Device Total: 3 Return to Executive Summary

Page of 25 32

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Programmable Relay 4 4 0 4 4

Device Type Location ScanID Address Q3/24 Q3/25 Programmable Relay 1st 1st North Mech Room 146 43810270 1 08/10-P 09/08-P Programmable Relay 1st 1st Northwest Mech Room 178 43810258 1 08/10-P 09/08-P Programmable Relay 1st 1st North Mech Room 149 43810265 1 08/10-P 09/08-P Programmable Relay 1st 1st North FACP Room 43810119 1 08/10-P 09/08-P

Device Total: 4 Return to Executive Summary

Page of 26 32 Service Summary

Vets Fire & Life Safety Download Date: 11/05/2025

Service Summary Generated by: BuildingReports.com

Building: Fayetteville VAMC Leroy Pond The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed Annunciator Tested 3 Battery Tested 10 Control Panel Tested 1 Duct Detector Battery Replaced 6 Heat Detector Tested 1 Horn/Strobe Tested 82 Initiating Device Tested 6 Monitor Device Tested 5 Monitoring Tested 2 Power Supply Tested 3 Programmable Relay Tested 4 Pull Station Tested 20 Smoke Detector Tested/Cleaned 34 Strobe Tested 10 Tamper Switch Annual 2 Waterflow Switch Annual 1

Total 190 Grand Total 190

Page of 27 32 Auxiliary Functions Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Auxiliary Functions Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Leroy Pond Control Panel: 1 - Notifier The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Passed Programmable Relay

1st 1st North FACP Room Passed 43810119 1st 1st North Mech Room 146 Passed 43810270 1st 1st North Mech Room 149 Passed 43810265 1st 1st Northwest Mech Room 178 Passed 43810258

Duct Detector AHU Shutdown 1st 1st North Mech Room 146 Passed 43810269 AHU Shutdown 1st 1st North Mech Room 146 Passed 45935576 AHU Shutdown 1st 1st North Mech Room 149 Passed 43810261 AHU Shutdown 1st 1st North Mech Room 149 Passed 43810262 AHU Shutdown 1st 1st Northwest Mech Room 178 Passed 43810255 AHU Shutdown 1st 1st Northwest Mech Room 178 Passed 43810256 javascript:editViewDevice('43810119');

javascript:editViewDevice('43810270');

javascript:editViewDevice('43810265');

javascript:editViewDevice('43810258');

javascript:editViewDevice('43810269');

javascript:editViewDevice('45935576');

javascript:editViewDevice('43810261');

javascript:editViewDevice('43810262');

javascript:editViewDevice('43810255');

javascript:editViewDevice('43810256');

Page of 28 32 Battery & Power Supply Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Leroy Pond

Control Panel: 1 - Notifier

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Passed Sealed Lead Acid 1st 1st Garage Room 305

Garage Power Supply 8 12 12.37

Sealed Lead Acid 1st 1st Garage Room 305 Garage Power Supply

8 12 12.30

Sealed Lead Acid 1st 1st North FACP Room Main FACP

55 12 13.38

Sealed Lead Acid 1st 1st North FACP Room Main FACP

55 12 13.38

Sealed Lead Acid 1st 1st North FACP Room Power Supply

8 12 12.48

Sealed Lead Acid 1st 1st North FACP Room Power Supply

8 12 12.33

Sealed Lead Acid 1st 1st Northwest Mech Room 178 Power Supply

8 12 12.56

Sealed Lead Acid 1st 1st Northwest Mech Room 178 Power Supply

8 12 12.55

Sealed Lead Acid 1st 1st Northwest Mech Room 178 Power Supply

12 12 12.48

Sealed Lead Acid 1st 1st Northwest Mech Room 178 Power Supply

12 12 12.33

Page of 29 32 Inventory & Warranty Report

Vets Fire & Life Safety Download Date: 11/05/2025

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Leroy Pond Control Panel: 1 - Notifier The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Annunciator Control 1.58% 3

Battery Control 5.26% 10

Control Panel Control 0.53% 1

Duct Detector Initiating 3.16% 6

Heat Detector Initiating 0.53% 1

Horn/Strobe Indicating 43.16% 82

Initiating Device Initiating 3.16% 6

Monitor Device Monitor 2.63% 5

Monitoring Monitor 1.05% 2

Power Supply Control 1.58% 3

Programmable Relay Auxiliary 2.11% 4

Pull Station Initiating 10.53% 20

Smoke Detector Initiating 17.89% 34

Strobe Indicating 5.26% 10

Tamper Switch Supervisory 1.05% 2

Waterflow Switch Initiating 0.53% 1

Type Qty Model # Description Install Date

In Service - 1 Year to 2 Years Notifier

Horn/Strobe 78 08/10/2024 Initiating Device 6 08/10/2024 Monitor Device 5 08/10/2024 Monitoring 2 08/10/2024 Power Supply 3 08/10/2024 Programmable Relay 4 08/10/2024 Pull Station 20 08/10/2024 Smoke Detector 34 Photoelectric 08/10/2024 Strobe 10 08/10/2024 Annunciator 2 08/06/2024 Annunciator 1 LCD Display 08/06/2024 Control Panel 1 08/06/2024 Duct Detector 6 08/06/2024 Heat Detector 1 08/06/2024

Page of 30 32 Inventory & Warranty Report

Vets Fire & Life Safety Download Date: 11/05/2025

Horn/Strobe 4 08/06/2024

Power Sonic Battery 10 Sealed Lead Acid 08/06/2024

In Service - 25 Years or Older Notifier

Tamper Switch 2 12/31/1969 Waterflow Switch 1 12/31/1969

Page of 31 32 Zone Address Report

Vets Fire & Life Safety Download Date: 11/05/2025

Zone Address Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Leroy Pond Control Panel: 1 - Notifier The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID 1 Smoke Detector 1st 1st Northwest Bed #1 Room 175 Photoelectric 43810171 1 Smoke Detector 1st 1st Northwest Bed #10 Room 186 Photoelectric 43810196 1 Smoke Detector 1st 1st Northwest Bed #11 Room 187 Photoelectric 43810199 1 Smoke Detector 1st 1st Northwest Bed #12 Room 188 Photoelectric 43810202 1 Smoke Detector 1st 1st Northwest Bed #13 Room 189 Photoelectric 43810205 1 Smoke Detector 1st 1st Northwest Bed #14 Room 190 Photoelectric 43810208 1 Smoke Detector 1st 1st Northwest Bed #15 Room 192 Photoelectric 43810211 1 Smoke Detector 1st 1st Northwest Bed #16 Room 193 Photoelectric 43810214 1 Smoke Detector 1st 1st Northwest Bed #17 Room 194 Photoelectric 43810217 1 Smoke Detector 1st 1st Northwest Bed #18 Room 195 Photoelectric 43810220 1 Smoke Detector 1st 1st Northwest Bed #19 Room 196 Photoelectric 43810223 1 Smoke Detector 1st 1st Northwest Bed #2 Room 176 Photoelectric 43810172 1 Smoke Detector 1st 1st Northwest Bed #20 Room 197 Photoelectric 43810226 1 Smoke Detector 1st 1st Northwest Bed #3 Room 179 Photoelectric 43810175 1 Smoke Detector 1st 1st Northwest Bed #4 Room 180 Photoelectric 43810178 1 Smoke Detector 1st 1st Northwest Bed #5 Room 181 Photoelectric 43810181 1 Smoke Detector 1st 1st Northwest Bed #6 Room 182 Photoelectric 43810184 1 Smoke Detector 1st 1st Northwest Bed #7 Room 183 Photoelectric 43810187 1 Smoke Detector 1st 1st Northwest Bed #8 Room 184 Photoelectric 43810190 1 Smoke Detector 1st 1st Northwest Bed #9 Room 185 Photoelectric 43810193 1 Smoke Detector 1st 1st Northwest Hall By Room 180 Photoelectric 43810232 1 Smoke Detector 1st 1st Northwest Hall By Room 182 Photoelectric 43810233 1 Smoke Detector 1st 1st Northwest Hall By Room 185 Photoelectric 43810235 1 Smoke Detector 1st 1st Northwest Hall By Room 187 Photoelectric 43810236 1 Smoke Detector 1st 1st Northwest Hall By Room 189 Photoelectric 43810237 1 Smoke Detector 1st 1st Northwest Hall Exit By Room 179 Photoelectric 43810230 1 Smoke Detector 1st 1st Northwest Hall Exit By Room 190 Photoelectric 43810239 1 Smoke Detector 1st 1st southwest Mechanical Room 178 Photoelectric 45935574

1--2 Duct Detector 1st 1st North Mech Room 146 43810269 1--2 Duct Detector 1st 1st North Mech Room 146 45935576 1--2 Pull Station 1st 1st South Hall By Staff Restroom 171 43810166 1--3 Duct Detector 1st 1st North Mech Room 149 43810262 1--4 Pull Station 1st 1st Southeast Entrance 43810139 1--5 Pull Station 1st 1st North Exit By Room 112 43810133 1--5 Duct Detector 1st 1st North Mech Room 149 43810261 javascript:editViewDevice('43810171');

javascript:editViewDevice('43810196');

javascript:editViewDevice('43810199');

javascript:editViewDevice('43810202');

javascript:editViewDevice('43810205');

javascript:editViewDevice('43810208');

javascript:editViewDevice('43810211');

javascript:editViewDevice('43810214');

javascript:editViewDevice('43810217');

javascript:editViewDevice('43810220');

javascript:editViewDevice('43810223');

javascript:editViewDevice('43810172');

javascript:editViewDevice('43810226');

javascript:editViewDevice('43810175');

javascript:editViewDevice('43810178');

javascript:editViewDevice('43810181');

javascript:editViewDevice('43810184');

javascript:editViewDevice('43810187');

javascript:editViewDevice('43810190');

javascript:editViewDevice('43810193');

javascript:editViewDevice('43810232');

javascript:editViewDevice('43810233');

javascript:editViewDevice('43810235');

javascript:editViewDevice('43810236');

javascript:editViewDevice('43810237');

javascript:editViewDevice('43810230');

javascript:editViewDevice('43810239');

javascript:editViewDevice('45935574');

javascript:editViewDevice('43810269');

javascript:editViewDevice('45935576');

javascript:editViewDevice('43810166');

javascript:editViewDevice('43810262');

javascript:editViewDevice('43810139');

javascript:editViewDevice('43810133');

javascript:editViewDevice('43810261');

Page of 32 32 Zone Address Report

Vets Fire & Life Safety Download Date: 11/05/2025

Address Device Type Location Type ScanID 1--5 Pull Station 1st 1st Northwest Hall Exit By Room 192 43810240 1--6 Pull Station 1st 1st North Storage Room 43810130 1--7 Pull Station 1st 1st North Mech Room 146 43810267 1--7 Pull Station 1st 1st Northwest Hall Exit By Room 179 43810229 1--8 Pull Station 1st 1st North Electrical Room 43810128 1--9 Pull Station 1st 1st North Mech Room 149 43810260 1--9 Duct Detector 1st 1st Northwest Mech Room 178 43810256 1--10 Pull Station 1st 1st North Resident Day Room 153 43810158 1--10 Duct Detector 1st 1st Northwest Mech Room 178 43810255 1--14 Pull Station 1st 1st Northwest Mech Room 178 43810247 1--16 Pull Station 1st 1st North Storage Room 43810129 1-D1 Smoke Detector 1st 1st North Electrical Room Photoelectric 43810126

1-L1 D50 Smoke Detector 1st 1st Garage Office Room 6 Smoke Photoelectric 45935565 1-L1 D51 Smoke Detector 1st 1st Garage Office Room 7 Smoke Photoelectric 45935564 1-L1 D52 Smoke Detector 1st 1st Garage Office Room 8 Smoke Photoelectric 45935566 1-L1 D54 Smoke Detector 1st 1st Garage Office Room 5 Smoke Photoelectric 45935569 1-L1 D55 Smoke Detector 1st 1st Garage Room 305 Garage Power

Supply Photoelectric 45935553

1-L1 M50 Pull Station 1st 1st Garage Office Room 6 Pull Station 45935563 1-L1 M51 Pull Station 1st 1st Garage Office Room 8 Pull Station 45935567 1-L1 M52 Pull Station 1st 1st Garage North East Garage Bay

Pull Station 45935568

1-L1 M53 Pull Station 1st 1st Garage North West Garage Bay Pull Station

45935554

1-L1 M54 Pull Station 1st 1st Garage Breakroom Pull Station 45935558 1-L1 M55 Pull Station 1st 1st Garage South West Garage Bay

Pull Station 45935560

1-L1 M56 Pull Station 1st 1st Garage Office Room 5 Pull Station 45935571 1-L1 M57 Pull Station 1st 1st Garage South East Garage Bay

Pull Station 45935562

D1-60 Heat Detector 1st 1st Garage Breakroom Heat 45935557 M1-12 Tamper Switch 1st 1st Northwest Riser in Outside Room

43810245

M1-12 Tamper Switch 1st 1st Northwest Riser in Outside Room

43810246

M1-13 Waterflow Switch 1st 1st Northwest Riser in Outside Room

43810243 javascript:editViewDevice('43810240');

javascript:editViewDevice('43810130');

javascript:editViewDevice('43810267');

javascript:editViewDevice('43810229');

javascript:editViewDevice('43810128');

javascript:editViewDevice('43810260');

javascript:editViewDevice('43810256');

javascript:editViewDevice('43810158');

javascript:editViewDevice('43810255');

javascript:editViewDevice('43810247');

javascript:editViewDevice('43810129');

javascript:editViewDevice('43810126');

javascript:editViewDevice('45935565');

javascript:editViewDevice('45935564');

javascript:editViewDevice('45935566');

javascript:editViewDevice('45935569');

javascript:editViewDevice('45935553');

javascript:editViewDevice('45935563');

javascript:editViewDevice('45935567');

javascript:editViewDevice('45935568');

javascript:editViewDevice('45935554');

javascript:editViewDevice('45935558');

javascript:editViewDevice('45935560');

javascript:editViewDevice('45935571');

javascript:editViewDevice('45935562');

javascript:editViewDevice('45935557');

javascript:editViewDevice('43810245');

javascript:editViewDevice('43810246');

javascript:editViewDevice('43810243');

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
Executive Summary
Notes & Recommendations
Inspection & Testing
Service Summary
Auxiliary Functions Testing
Battery & Power Supply Testing
Inventory & Warranty Report
Zone Address Report