2025-09-15 Fayetteville-VAMC-Bldg-8 FireScan.pdf
PDF 157 KB Posted
- Attached to
- J042--Fire Alarm Service
- Solicitation number
- 36C25626Q0430
About this file
This is a Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate for Fayetteville VAMC Building 8, completed by Veterans Fire and Life Safety on September 15, 2025. The inspection was performed in compliance with The Joint Commission/VHA Standards and the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards. Inspector Rod Davis conducted the annual inspection, with building contact Travis Ryan at 479-225-6412. The inspection covered 42 total devices across multiple categories including tamper switches, waterflow switches, pull stations, smoke detectors, speakers, strobes, speaker/strobes, batteries, power supplies, and programmable relays.
The inspection results identified two failed batteries (ScanID 7367563 and 89471371, both located at Ground level) that require replacement due to failed load tests, per NFPA 72 Table 14.4.3.2 (9) standards. All other devices tested passed their inspections. The passed devices included 3 tamper switches (annual test), 1 waterflow switch (semi-annual test), 7 pull stations, 1 smoke detector, 9 speakers, 3 speaker/strobes, 6 strobes, 4 passing batteries, 1 power supply, and 5 programmable relays. The Proposed Solutions Report indicates both failed batteries are available for replacement on a Time and Materials (T/M) basis with no specific model number or estimated cost provided. Testing was noted as performed by others for supervisory devices. The most recently installed devices date to August 6, 2024, while some supervisory devices (tamper switches and waterflow switch) have been in service for 25 years or longer.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
Fayetteville VAMC Bldg 8 1100 N College Ave
Fayetteville, AR 72703 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
Annual Inspection Inspection Completion Date Sep 15, 2025
Building: Fayetteville VAMC Bldg 8 Company: Vets Fire & Life Safety Contact: Travis Ryan Contact: Rod Davis
Title: Safety Specialist Title: Manager Fire Alarm Testing Report
Page of 1 22 Executive Summary
Vets Fire & Life Safety Download Date: 11/05/2025
Executive Summary Generated by: BuildingReports.com
Building Information Building: Fayetteville VAMC Bldg 8 Contact: Travis Ryan
Address: 1100 N College Ave Phone: 479-225-6412
Address: Fax:
City/State/ZIP Code: Fayetteville, AR 72703 Mobile:
Country: United States of America Email:
Inspection Performed By Company: Vets Fire & Life Safety Inspector: Rod Davis
Address: 7 Sherri Lane Phone: 314-696-7000
Address: Fax:
City/State/ZIP Code: St Peters, MO 63376 Mobile:
Country: United States of America Email: rod.davis@vflsc.com
Page of 2 22
Vets Fire & Life Safety Download Date: 11/05/2025
Inspection Completion Date: Sep 15, 2025 Building: Fayetteville VAMC Bldg 8 EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Tamper Switch 3 3 0 3 0 3
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Waterflow Switch 1 1 0 1 0 1
EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Pull Station 7 7 0 7 0 7
Smoke Detector 1 1 0 1 0 1
EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Speaker 9 9 0 9 0 9
Speaker/Strobe 3 3 0 3 0 3
Strobe 6 6 0 6 0 6
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Devices Tested This
Quarter Pass Fail Tested YTD
(2025) Untested YTD
(2025) Total
Quantity Battery 6 4 2 6 0 6
Power Supply 1 1 0 1 0 1
Programmable Relay 5 5 0 5 0 5
Total Device Count: 42
Page of 3 22
Vets Fire & Life Safety Download Date: 11/05/2025
Certification
Company: Vets Fire & Life Safety Building: Fayetteville VAMC Bldg 8
Inspector: Rod Davis Contact: Travis Ryan
Page of 4 22 Discrepancy Report
Vets Fire & Life Safety Download Date: 11/05/2025
Discrepancy Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 8 Control Panel: 1 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.
Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.
Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade
No items found during this inspection.
ScanID Location Problem Address Reference
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Battery
7367563 Ground Failed Test 1 NFPA72 Table
14.4.3.2 (9)
89471371 Ground Failed Test 1 NFPA72 Table
14.4.3.2 (9)
Code References NFPA72 Table 14.4.3.2 (9) Replace any battery cell/unit if the temperature is greater than 18F above ambient. Replace the battery when any cell/unit measures a voltage less than 13.26 volts. Replace the battery when any cell/unit has an internal ohmic value outside of the acceptable range.
javascript:editViewDevice('7367563');
javascript:editViewDevice('89471371');
Page of 5 22 Proposed Solutions Report
Vets Fire & Life Safety Download Date: 11/05/2025
Proposed Solutions Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 8 Control Panel: 1 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.
ScanID Location Solution Model # Cost Fix
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Battery 7367563 Ground Replace Battery T/M 89471371 Ground Replace Battery T/M
Internal WO/PO #: (none) T/M
Page of 6 22 Notes & Recommendations
Vets Fire & Life Safety Download Date: 11/05/2025
Notes & Recommendations Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 8 Control Panel: 1 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
EC 02.03.05 EP 01 Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;
water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
1 Tamper Switch Ground Ground Garage Restroom BF Valve
Passed 7367523
Testing Done By Others 2 Tamper Switch Ground Ground Garage Restroom BF Valve
Passed 7367524
Testing Done By Others 3 Tamper Switch Ground Ground South Lawn Passed 7367525
Testing Done By Others
EC 02.03.05 EP 02 Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table
14.4.3.2 (17)(10)(a) & (17)(11)
4 Waterflow Switch Ground Ground Garage Restroom Passed 7367526 Testing Done By Others javascript:editViewDevice('7367523');
javascript:editViewDevice('7367524');
javascript:editViewDevice('7367525');
javascript:editViewDevice('7367526');
Page of 7 22 Inspection & Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Inspection & Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 8 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device; water temperature supervisory; room temperature supervisory and other supervisory initiating devices. Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Tamper Switch 3 3 0 3 3
Device Type Location ScanID Address Q3/24 Q3/25 Tamper Switch Ground Ground Garage Restroom
BF Valve 1 7367523 1-1-L1 M17 08/20-P 09/15-P
Tamper Switch Ground Ground Garage Restroom BF Valve 2
7367524 1-1-L1 M17 08/20-P 09/15-P
Tamper Switch Ground Ground South Lawn 7367525 1-1-L1 M18 08/20-P 09/15-P
Device Total: 3 Return to Executive Summary
Page of 8 22
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table
14.4.3.2 (17)(11)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Waterflow Switch 1 1 0 1 1
Device Type Location ScanID Address Q3/24 Q3/25 Waterflow Switch Ground Ground Garage Restroom 7367526 1-1-L1 M16 08/20-P 09/15-P
Device Total: 1 Return to Executive Summary
Page of 9 22
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Pull Station 7 7 0 7 7
Device Type Location ScanID Address Q3/24 Q3/25 Pull Station Ground Ground 7367531 1-1-L1 M14 08/06-P 08/27-P Pull Station Ground Ground Plumbing Office 7367532 1-1-L1 M 08/06-P 08/27-P Pull Station Ground Ground Southwest Office Exit 7367533 1-1-L1 M15 08/06-P 08/27-P Pull Station 1st 1st 7367527 1-1-L1 M20 08/06-P 08/27-P Pull Station 1st 1st Southwest Mail Room 7367528 1-1-L1 M22 08/06-P 08/27-P Pull Station 1st 1st West Exit 7367530 1-1-L1 M29 08/06-P 08/27-P Pull Station 1st 1st West Exit 7367529 1-1-L1 M21 08/06-P 08/27-P
Device Total: 7 Return to Executive Summary
Page of 10 22
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Smoke Detector 1 1 0 1 1
Device Type Location ScanID Address Q3/24 Q3/25 Smoke Detector Ground Ground Plumbing Office 7367534 1-1 08/06-P 08/27-P
Page of 11 22
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker 9 9 0 9 9
Device Type Location ScanID Address Q3/24 Q3/25 Speaker Ground Ground 7367540 1-1 08/06-P 08/27-P Speaker Ground Ground 7367541 1-1 08/06-P 08/27-P Speaker Ground Ground 7367542 1-1 08/06-P 08/27-P Speaker Ground Ground Plumbing Office 7367543 1-1 08/06-P 08/27-P Speaker 1st 1st 7367538 1-1 08/06-P 08/27-P Speaker 1st 1st 7367537 1-1 08/06-P 08/27-P Speaker 1st 1st 7367539 1-1 08/06-P 08/27-P Speaker 1st 1st 7367535 1-1 08/06-P 08/27-P Speaker 1st 1st 7367536 1-1 08/06-P 08/27-P
Device Total: 9 Return to Executive Summary
Page of 12 22
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Speaker/Strobe 3 3 0 3 3
Device Type Location ScanID Address Q3/24 Q3/25 Speaker/Strobe 2nd By Room Room 217 7367560 1 08/06-P 08/27-P Speaker/Strobe 2nd Nurses Station 7367561 1 08/06-P 08/27-P Speaker/Strobe 2nd Reception 7367562 1 08/06-P 08/27-P
Device Total: 3 Return to Executive Summary
Page of 13 22
Vets Fire & Life Safety Download Date: 11/05/2025
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)
For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Strobe 6 6 0 6 6
Device Type Location ScanID Address Q3/24 Q3/25 Strobe Ground Ground 7367547 1-1 08/06-P 08/27-P Strobe Ground Ground 7367548 1-1 08/06-P 08/27-P Strobe Ground Ground Plumbing Office 7367549 1-1 08/06-P 08/27-P Strobe 1st 1st 7367546 1-1 08/06-P 08/27-P Strobe 1st 1st 7367545 1-1 08/06-P 08/27-P Strobe 1st 1st 7367544 1-1 08/06-P 08/27-P
Device Total: 6 Return to Executive Summary
Page of 14 22
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Battery 6 4 2 6 6
Device Type Location ScanID Address Q3/24 Q3/25 Battery Ground 7367563 1 08/10-P 08/27-F Battery Ground 89471371 1 08/10-P 08/27-F Battery Ground 7367550 1-1 08/06-P 08/27-P Battery Ground Ground 7367551 1-1 08/06-P 08/27-P Battery Ground Ground Amp Panel 7367552 1-1 08/06-F 08/27-P Battery Ground Ground Amp Panel 7367553 1-1 08/06-F 08/27-P
Device Total: 6 Return to Executive Summary
Page of 15 22
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table
14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Power Supply 1 1 0 1 1
Device Type Location ScanID Address Q3/24 Q3/25 Power Supply Ground Ground Plumbing Office 7367554 1-1 08/07-P 08/27-P
Page of 16 22
Vets Fire & Life Safety Download Date: 11/05/2025
LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Programmable Relay 5 5 0 5 5
Device Type Location ScanID Address Q3/24 Q3/25 Programmable Relay Ground Ground Plumbing Office 7367559 1-1-1 -42 08/07-P 08/27-P Programmable Relay Ground Ground Plumbing Office 7367557 1-1--43 08/07-P 08/27-P Programmable Relay Ground Ground Plumbing Office 7367558 1-1--41 08/07-P 08/27-P Programmable Relay Ground Ground Plumbing Office 7367556 1-1-1 -59 08/07-P 08/27-P Programmable Relay Ground Ground Plumbing Office 7367555 1-1-1 -40 08/07-P 08/27-P
Device Total: 5 Return to Executive Summary
Page of 17 22 Service Summary
Vets Fire & Life Safety Download Date: 11/05/2025
Service Summary Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 8 The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Failed/Other Battery Tested 2
Total 2
Passed Battery Tested 4 Power Supply Tested 1 Programmable Relay Tested 5 Pull Station Tested 7 Smoke Detector Tested/Cleaned 1 Speaker/Strobe Tested 3 Speaker Tested 9 Strobe Tested 6 Tamper Switch Annual 3 Waterflow Switch Annual 1
Total 40 Grand Total 42
Page of 18 22 Auxiliary Functions Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Auxiliary Functions Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 8 Control Panel: 1 The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed Programmable Relay
Ground Ground Plumbing Office Passed 7367559 Ground Ground Plumbing Office Passed 7367557 Ground Ground Plumbing Office Passed 7367558 Ground Ground Plumbing Office Passed 7367556 Ground Ground Plumbing Office Passed 7367555 javascript:editViewDevice('7367559');
javascript:editViewDevice('7367557');
javascript:editViewDevice('7367558');
javascript:editViewDevice('7367556');
javascript:editViewDevice('7367555');
Page of 19 22 Battery & Power Supply Testing
Vets Fire & Life Safety Download Date: 11/05/2025
Battery & Power Supply Testing Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 8 Control Panel: 1 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Type Location Rated Ah
Rated Volts Pre Test
Post Test Min Ah Tested Ah
Battery
Passed Sealed Lead Acid Ground 12 12 13.00 12 Sealed Lead Acid Ground Ground 12 12 12.97 12 Sealed Lead Acid Ground Ground Amp Panel 8 12 12.94 Sealed Lead Acid Ground Ground Amp Panel 8 12 12.97
Failed/Other Sealed Lead Acid Ground 18 12 13.38 2.6 Sealed Lead Acid Ground 18 12 12.68 7.4
Page of 20 22 Inventory & Warranty Report
Vets Fire & Life Safety Download Date: 11/05/2025
Inventory & Warranty Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 8 Control Panel: 1 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity Battery Control 14.29% 6
Power Supply Control 2.38% 1
Programmable Relay Auxiliary 11.90% 5
Pull Station Initiating 16.67% 7
Smoke Detector Initiating 2.38% 1
Speaker Indicating 21.43% 9
Speaker/Strobe Indicating 7.14% 3
Strobe Indicating 14.29% 6
Tamper Switch Supervisory 7.14% 3
Waterflow Switch Initiating 2.38% 1
Type Qty Model # Description Install Date
In Service - 1 Year to 2 Years Programmable Relay 5 08/07/2024 Battery 4 Sealed Lead Acid 08/06/2024 Power Supply 1 08/06/2024 Pull Station 7 08/06/2024 Smoke Detector 1 08/06/2024 Speaker 9 08/06/2024 Strobe 6 08/06/2024
Simplex Battery 2 Sealed Lead Acid 08/06/2024 Speaker/Strobe 3 08/06/2024
In Service - 25 Years or Older Tamper Switch 3 12/31/1969 Waterflow Switch 1 12/31/1969
Page of 21 22 Zone Address Report
Vets Fire & Life Safety Download Date: 11/05/2025
Zone Address Report Generated by: BuildingReports.com
Building: Fayetteville VAMC Bldg 8 Control Panel: 1 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID 1 Battery Ground Sealed Lead Acid 7367550 1 Battery Ground Ground Sealed Lead Acid 7367551 1 Speaker Ground Ground 7367540 1 Speaker Ground Ground 7367541 1 Speaker Ground Ground 7367542 1 Strobe Ground Ground 7367547 1 Strobe Ground Ground 7367548 1 Battery Ground Ground Amp Panel Sealed Lead Acid 7367552 1 Battery Ground Ground Amp Panel Sealed Lead Acid 7367553 1 Power Supply Ground Ground Plumbing Office 7367554 1 Smoke Detector Ground Ground Plumbing Office 7367534 1 Speaker Ground Ground Plumbing Office 7367543 1 Strobe Ground Ground Plumbing Office 7367549 1 Speaker 1st 1st 7367535 1 Speaker 1st 1st 7367536 1 Speaker 1st 1st 7367537 1 Speaker 1st 1st 7367538 1 Speaker 1st 1st 7367539 1 Strobe 1st 1st 7367544 1 Strobe 1st 1st 7367545 1 Strobe 1st 1st 7367546
1-1 -40 Programmable Relay Ground Ground Plumbing Office 7367555 1-1 -42 Programmable Relay Ground Ground Plumbing Office 7367559 1-1 -59 Programmable Relay Ground Ground Plumbing Office 7367556 1--41 Programmable Relay Ground Ground Plumbing Office 7367558 1--43 Programmable Relay Ground Ground Plumbing Office 7367557
1-L1 M Pull Station Ground Ground Plumbing Office 7367532 1-L1 M14 Pull Station Ground Ground 7367531 1-L1 M15 Pull Station Ground Ground Southwest Office Exit 7367533 1-L1 M16 Waterflow Switch Ground Ground Garage Restroom 7367526 1-L1 M17 Tamper Switch Ground Ground Garage Restroom BF
Valve 1 7367523
1-L1 M17 Tamper Switch Ground Ground Garage Restroom BF Valve 2
7367524
1-L1 M18 Tamper Switch Ground Ground South Lawn 7367525 javascript:editViewDevice('7367550');
javascript:editViewDevice('7367551');
javascript:editViewDevice('7367540');
javascript:editViewDevice('7367541');
javascript:editViewDevice('7367542');
javascript:editViewDevice('7367547');
javascript:editViewDevice('7367548');
javascript:editViewDevice('7367552');
javascript:editViewDevice('7367553');
javascript:editViewDevice('7367554');
javascript:editViewDevice('7367534');
javascript:editViewDevice('7367543');
javascript:editViewDevice('7367549');
javascript:editViewDevice('7367535');
javascript:editViewDevice('7367536');
javascript:editViewDevice('7367537');
javascript:editViewDevice('7367538');
javascript:editViewDevice('7367539');
javascript:editViewDevice('7367544');
javascript:editViewDevice('7367545');
javascript:editViewDevice('7367546');
javascript:editViewDevice('7367555');
javascript:editViewDevice('7367559');
javascript:editViewDevice('7367556');
javascript:editViewDevice('7367558');
javascript:editViewDevice('7367557');
javascript:editViewDevice('7367532');
javascript:editViewDevice('7367531');
javascript:editViewDevice('7367533');
javascript:editViewDevice('7367526');
javascript:editViewDevice('7367523');
javascript:editViewDevice('7367524');
javascript:editViewDevice('7367525');
Page of 22 22 Zone Address Report
Vets Fire & Life Safety Download Date: 11/05/2025
Address Device Type Location Type ScanID 1-L1 M20 Pull Station 1st 1st 7367527 1-L1 M21 Pull Station 1st 1st West Exit 7367529 1-L1 M22 Pull Station 1st 1st Southwest Mail Room 7367528 1-L1 M29 Pull Station 1st 1st West Exit 7367530 javascript:editViewDevice('7367527');
javascript:editViewDevice('7367529');
javascript:editViewDevice('7367528');
javascript:editViewDevice('7367530');
| Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate |
| Executive Summary |
| Discrepancy Report |
| Proposed Solutions Report |
| Notes & Recommendations |
| Inspection & Testing |
| Service Summary |
| Auxiliary Functions Testing |
| Battery & Power Supply Testing |
| Inventory & Warranty Report |
| Zone Address Report |
File details come from the government source that posted it. Updated .