backflow information excel.xlsx
XLSX spreadsheet 13 KB Posted
- Attached to
- J042--Fire Alarm Service
- Solicitation number
- 36C25626Q0430
About this file
This file is a backflow prevention device identification inventory spreadsheet for the VA Medical Center (VAMC) Fayetteville. The document provides a comprehensive catalog of 51 existing fire protection and backflow prevention devices installed throughout the facility, organized by building number, floor, room location, and device identification. The inventory includes detailed specifications for each device, including the type of backflow preventer (Double Check or Reduced Pressure Principal), degree of hazard classification (Low or High Hazard), manufacturer, serial number, pipe size, and intended purpose such as fire protection, domestic water supply, HVAC cooling water feed, humidifier feed, and sterilization equipment.
The devices are distributed across 18 buildings within the VAMC campus, with the majority of inspections conducted in September 2016 and a few in February 2016. The inventory encompasses various manufacturers including Ames, Watts, Colt, Wilkins, Zurn-Wilkins, Febco, Combraco, and Apollo, with pipe sizes ranging from 3/4 inches to 8 inches. Low hazard devices are primarily Double Check units protecting fire suppression systems and meter bypass applications, while high hazard devices are predominantly Reduced Pressure Principal units safeguarding domestic water, HVAC systems, humidifiers, and other specialized equipment. This inventory appears to support the related federal contract opportunity for fire alarm inspection and services at the Veterans Health Administration facility.
View the file
Other files
Show all 43
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Table 1
| VAMC Fayetteville Existing Fire Protection (FP) & Backflow Prevention Device Identification | |||||||||||
| Building Number | Floor | Room Number | Device Number | Backflow Preventer Type | Protection Degree of Hazard | Device Manufacturer | Serial Number | Pipe Size (Inch) | Purpose | Drawing Reference Number | Date of Inspection |
| 1 | 1 | M1 2 | 003(FP) | Double Check Detector | Low Hazard | Ames | I-44379-1105 | 8" | Fire Protection | N/A | Sept. 2016 |
| 1 | 1 | M1 2 | 004(FP) | Double Check | Low Hazard | Watts | 47420 | 3/4" | Meter Bypass | N/A | Sept. 2016 |
| 3 | 1 | M4 | 001(FP) | Double Check Detector | Low Hazard | Ames DDC | JG-0577 | 4" | Fire Protection | N/A | Sept. 2016 |
| 3 | 1 | M4 | 002(FP) | Double Check | Low Hazard | Ames DDC | 16916 | 3/4" | Meter Bypass | N/A | Sept. 2016 |
| 4 | Basement | Crawl | 001(FP) | Double Check | Low Hazard | Watts | 2100065 | 4" | Fire Protection | N/A | Feb. 2016 |
| 8 | Ground | Sprinkler Room 2 | 001(FP) | Double Check Detector | Low Hazard | Colt 300BF | JG-0577 | 4" | Fire Protection | N/A | Sept. 2016 |
| 8 | Ground | Sprinkler Room 2 | 002(FP) | Double Check | Low Hazard | Watts | 16910 | 3/4" | Meter Bypass | N/A | Sept. 2016 |
| 9 | Basement | 001 | 002(FP) | Double Check Detector | Low Hazard | JG-0577 | 4" | Fire Protection | N/A | Sept. 2016 | |
| 9 | Basement | 001 | 003(FP) | Double Check | Low Hazard | Aames | 16910 | 3/4" | Fire Protection | N/A | Sept. 2016 |
| 27 | 1 | 1 | 001(FP) | Double Check Detector | Low Hazard | Wilkins | V-24220 | 4" | Fire Protection (Sprinkler) | N/A | Sept. 2016 |
| 27 | 1 | 1 | 002(FP) | Double Check | Low Hazard | Watts | 3336092 | 3/4" | Meter Bypass | N/A | Sept. 2016 |
| 29 | 1 | SP004 | 001(FP) | Double Check Detector | Low Hazard | Wilkins | V-24905 | 4" | Fire Protection (Sprinkler) | N/A | Sept. 2016 |
| 29 | 1 | SP004 | 002(FP) | Double Check | Low Hazard | Watts | 3217345 | 3/4" | Meter Bypass | N/A | Sept. 2016 |
| 34 | 1 | N/A | 001(FP) | Double Check Detector | Low Hazard | JC-0573 | 4" | Fire Protection | N/A | Sept. 2016 | |
| 34 | 1 | N/A | 002(FP) | Double Check | Low Hazard | 16956 | 3/4" | Fire Protection | N/A | Sept. 2016 | |
| 44 | 1 | 124B | 003(FP) | Double Check Detector | Low Hazard | 200266-0402 | 6" | Fire Protection | N/A | Sept. 2016 | |
| 44 | 1 | 124B | 004(FP) | Double Check | Low Hazard | 53261 | 3/4" | Fire Protection | N/A | Sept. 2016 | |
| 1 | Basement | MB05 | 001 | Red. Pressure Principal | High Hazard | Watts 757a | DC-0324 | 4" | Domestic Water | PL-101 | Sept. 2016 |
| 1 | Basement | MB10 | 001 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 375XL | L-69723 | 4" | Domestic Water | PL-110 | Sept. 2016 |
| 1 | Basement | MB10 | 002 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 975XL | 3534812 | 2" | Irrigation CW Feed w/ meter | PL-110 | Sept. 2016 |
| 1 | Basement | MB10 | 003 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 975XL | 3533236 | 1" | Humidifier CW Feed | PL-110 | Sept. 2016 |
| 1 | Basement | PC43 | 001 | Red. Pressure Principal | High Hazard | Watts 009 | 572274 | 3/4" | HVAC CW Feed | PL-101 | Sept. 2016 |
| 1 | 1 | M1 2 | 001 | Red. Pressure Principal | High Hazard | Febco | J-042986 | 3/4" | Humidifier CW Feed | PL-104 | Sept. 2016 |
| 1 | 1 | M1 2 | 002 | Red. Pressure Principal | High Hazard | Watts 009 | A15002 | 1" | HVAC CW Feed | PL-104 | Sept. 2016 |
| 1 | 1 | PC105 | 001 | Red. Pressure Principal | High Hazard | Combraco | W 3474 | 3/4" | HVAC CW Feed | PL-110 | Sept. 2016 |
| 1 | 2 | M2 1 | 001 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 975XL | 3431933 | 3/4" | Humidifier CW Feed | PL-105 | Sept. 2016 |
| 1 | 2 | M2 2 | 001 | Red. Pressure Principal | High Hazard | Zurn | 2919352 | 1" | HVAC CW Feed | PL-106 | Sept. 2016 |
| 1 | 2 | M2 3 | 001 | Red. Pressure Principal | High Hazard | Febco | J-092981 | 3/4" | Humidifier CW Feed | PL-106 | Sept. 2016 |
| 1 | 2 | 231 | 001 | Red. Pressure Principal | High Hazard | Zurn-Wilkins | 3837567 | 1" | Sterilization equip. | PL-105 | Sept. 2016 |
| 1 | 2 | 231 | 002 | Red. Pressure Principal | High Hazard | Zurn-Wilkins | 3794802 | 1" | Sterilization equip. | PL-105 | Sept. 2016 |
| 1 | 2 | 231 | 003 | Red. Pressure Principal | High Hazard | Zurn-Wilkins | 3632239 | 3/4" | Sterilization equip. | PL-105 | Sept. 2016 |
| 1 | 2 | M2 4 | 001 | Red. Pressure Principal | High Hazard | Febco 825Y | J-045238 | 3/4" | Humidifier CW Feed | PL-105 | Sept. 2016 |
| 1 | 4 | 407 | 001 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 975XL | 2419018 | 3/4" | HVAC CW Feed | PL-109 | Sept. 2016 |
| 1 | 4 | 418 | 001 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 975XL | 1358787 | 1" | CW to HVAC & Humidifier | PL-109 | Sept. 2016 |
| 1 | Attic | 502 | 001 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 375RP | A230854 | 3/4" | Humdifier CW feed | PL-109 | Sept. 2016 |
| 2 | 1 | 1127 | 001 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 375XL | L-28716 | 3" | Domestic Water | PL-114 | Sept. 2016 |
| 2 | 1 | 1127 | 002 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 375XL | L-29370 | 3" | Domestic Water | PL-114 | Sept. 2016 |
| 2 | 1 | 1127 | 003 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 975XL | 128825 | 1" | HVAC & Humidifier | PL-114 | Sept. 2016 |
| 2 | 1 | 1188 | 001 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 975XL | 3224461 | 1 1/4" | Emergency Supply | PL-111 | Sept. 2016 |
| 2 | 1 | 1188 | 002 | Red. Pressure Principal | High Hazard | Zurn-Wilkins 975XL2 | 4141228 | 3/4" | HVAC CW Feed | PL-111 | Sept. 2016 |
| 4 | Basement | MB1 | 001 | Red. Pressure Principal | High Hazard | Watts | 28166 | 3/4" | HVAC CW Feed | PL-117 | Feb. 2016 |
| 9 | Basement | 001 | 001 | Red. Pressure Principal | High Hazard | Zurn Wilkins 975XL | 3457437 | 1" | Feeding Bldg 40 | PL-123 | Sept. 2016 |
| 9 | Basement | 002 | 001 | Red. Pressure Principal | High Hazard | Zurn Wilkins 975XL | 2201503 | 2" | CW to wash water | PL-123 | Sept. 2016 |
| 10 | 1 | 001 | 001 | Red. Pressure Principal | High Hazard | Watts 909 | 182518 | 4" | Domestic CW Feed to Tower | PL-125 | Sept. 2016 |
| 10 | 1 | 001 | 002 | Red. Pressure Principal | High Hazard | Watts 909 | 182523 | 4" | Domestic CW Feed to Tower | PL-125 | Sept. 2016 |
| 10 | 1 | 001 | 003 | Red. Pressure Principal | High Hazard | Zurn Wilkins 975XL | W121976 | 2" | CW to soft water & fixtures | PL-125 | Sept. 2016 |
| 18 | 1 | 001 | 001 | Red. Pressure Principal | High Hazard | Zurn | 2784C | 3" | Non-Potable Water | PL-126 | Sept. 2016 |
| 21 | Lower Level | L220A | 001 | Red. Pressure Principal | High Hazard | Zurn-Wilkins | L70023 | 4" | Domestic feed | PL-130 | Feb. 2016 |
| 21 | Lower Level | L220A | 002 | Red. Pressure Principal | High Hazard | Zurn Wilkins | 3533240 | 1" | Dental Equip. | PL-130 | Feb. 2016 |
| 21 | 3 | Penthouse | 001 | Red. Pressure Principal | High Hazard | Zurn-Wilkins | 358519 | 1 1/2" | HVAC CW Feed | PL-137 | Feb. 2016 |
| 29 | 1 | SP001 | 001 | Red. Pressure Principal | High Hazard | Watts 909 | 122111 | 2-1/2" | Tower Cooling Make Up | PL-138 | Sept. 2016 |
| 29 | 1 | SP002 | 001 | Red. Pressure Principal | High Hazard | Apollo RP40 | 238644 | 2" | Chilled Water Make Up | PL-138 | Sept. 2016 |
| 40 | 1 | 001 | 001 | Double Check | High Hazard | 312302 | 1" | Incinerator | PL-140 | Sept. 2016 | |
| 44 | 1 | 124B | 001 | Red. Pressure Principal | High Hazard | Zurn-Wilkins | 1301532 | 1 1/4" | Hose Connection | PL-141 | Sept. 2016 |
| 44 | 1 | 124B | 002 | Red. Pressure Principal | High Hazard | Zurn-Wilkins | W035069 | 3/4" | Hose Connection | PL-141 | Sept. 2016 |