2025-09-01_Fayetteville-VAMC-Bldg-6_FireScan.pdf

PDF 140 KB Posted

Attached to
J042--Fire Alarm Service
Solicitation number
36C25626Q0430
Issued by

About this file

This is a Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate for Fayetteville VAMC Building 6, completed on September 1, 2025, by Vets Fire & Life Safety. The inspection was performed in compliance with The Joint Commission/VHA Standards and the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards, with inspector Mike Gill conducting the evaluation at the facility located at 1100 N College Ave, Fayetteville, AR 72703, and Travis Ryan serving as the building contact.

The inspection examined 35 total fire alarm and life safety devices across multiple categories. Two backup batteries located in Basement 6B Storage failed load testing and require replacement on a time and materials basis, violating NFPA 72 Table 14.4.3.2 (9) standards for voltage and internal ohmic values. Of the devices tested in Q3 2025, two batteries failed while all other tested components passed, including eight smoke detectors, four pull stations, two heat detectors, ten horn/strobes, and eight strobes. Thirty-three devices remain untested year-to-date, including the power supply and various notification appliances throughout the basement, first, and second floors. All devices documented in the inventory were installed between August 7-10, 2024, falling within the one to two-year service window, and no manufacturer recalls or replacement programs were identified during the inspection.

View the file

Other files

File Type Posted
36C25626Q0430 0006.pdf PDF
36C25626Q0430 0006.docx DOCX document
P09 SOW Fire Alarm Service 41326 final.docx DOCX document
36C25626Q0430 0005.docx DOCX document
36C25626Q0430 0004.docx DOCX document
P09 SOW Fire Alarm Service Final 4426.docx DOCX document
Questions and answers for 36C25626Q0430 Post.docx DOCX document
36C25626Q0430 0003.docx DOCX document
564-18-135 Complete Dwgs Set.pdf PDF
P09_SOW Fire Alarm Service Revised.docx DOCX document
backflow information excel.xlsx XLSX spreadsheet
36C25626Q0430 0002.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-29_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-21_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-9_FireScan.pdf PDF
36C25626Q0430 EXHIBIT A.docx DOCX document
2025-09-08_Fayetteville-VAMC-Bldg-40_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-2_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-27_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-11_FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Leroy-Pond_FireScan.pdf PDF
Marmic Fire Sprinkler Inspection Report 1.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-44_FireScan.pdf PDF
36C25626Q0430 EXHIBIT B.docx DOCX document
combined fire alarm report.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-1_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-3_FireScan.pdf PDF
2025-08-27_Fayetteville-VAMC-Bldg-37_FireScan.pdf PDF
2025-09-01_Fayetteville-VAMC-Bldg-7_FireScan.pdf PDF
2025-08-27 Fayetteville-VAMC-Red-Barn FireScan.pdf PDF
2025-09-15_Fayetteville-VAMC-Bldg-34_FireScan.pdf PDF
2025-09-15 Fayetteville-VAMC-Bldg-8 FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Parking-Garage_FireScan.pdf PDF
36C25626Q0430 EXHIBIT C.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-4_FireScan.pdf PDF
FACTOR 2.docx DOCX document
2025-09-15_Fayetteville-VAMC-Bldg-10_FireScan.pdf PDF
2025-09-08_Fayetteville-VAMC-Bldg-5_FireScan.pdf PDF
FACTOR 1.docx DOCX document
36C25626Q0430 0001.docx DOCX document
WD 2015-5109.pdf PDF
P09_SOW Fire Alarm Service.docx DOCX document
36C25626Q0430_1.docx DOCX document
Show all 43

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate

For

Fayetteville VAMC Bldg 6 1100 N College Ave

Fayetteville, AR 72703 Veterans Fire and Life Safety has performed this inspection and testing service in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

Inspection Completion Date Sep 1, 2025

Building: Fayetteville VAMC Bldg 6 Company: Vets Fire & Life Safety Contact: Travis Ryan Contact: Mike Gill

Title: Safety Specialist Title: Inspector Fire Alarm Testing Report

Page of 1 18 Executive Summary

Vets Fire & Life Safety Download Date: 11/05/2025

Executive Summary Generated by: BuildingReports.com

Building Information Building: Fayetteville VAMC Bldg 6 Contact: Travis Ryan

Address: 1100 N College Ave Phone: 479-225-6412

Address: Fax:

City/State/ZIP Code: Fayetteville, AR 72703 Mobile:

Country: United States of America Email:

Inspection Performed By Company: Vets Fire & Life Safety Inspector: Mike Gill

Address: 7 Sherri Lane Phone: 636-543-0165

Address: Fax:

City/State/ZIP Code: St Peters, MO 63376 Mobile:

Country: United States of America Email: mike.gill@vflsc.com

Page of 2 18

Vets Fire & Life Safety Download Date: 11/05/2025

Inspection Completion Date: Sep 1, 2025 Building: Fayetteville VAMC Bldg 6 EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Heat Detector 0 0 0 0 2 2

Pull Station 0 0 0 0 4 4

Smoke Detector 0 0 0 0 8 8

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Horn/Strobe 0 0 0 0 10 10

Strobe 0 0 0 0 8 8

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Devices Tested This

Quarter Pass Fail Tested YTD

(2025) Untested YTD

(2025) Total

Quantity Battery 2 0 2 2 0 2

Power Supply 0 0 0 0 1 1

Total Device Count: 35

Page of 3 18

Vets Fire & Life Safety Download Date: 11/05/2025

Certification

Company: Vets Fire & Life Safety Building: Fayetteville VAMC Bldg 6

Inspector: Mike Gill Contact: Travis Ryan

Page of 4 18 Discrepancy Report

Vets Fire & Life Safety Download Date: 11/05/2025

Discrepancy Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 6 Control Panel: 1 The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty Items listed for Recall or Replacement/Upgrade

No items found during this inspection.

ScanID Location Problem Address Reference

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 Battery

4353226 Basement Basement 6B Storage Failed Test 1 NFPA72 Table

14.4.3.2 (9)

4353227 Basement Basement 6B Storage Failed Test 1 NFPA72 Table

14.4.3.2 (9)

Code References NFPA72 Table 14.4.3.2 (9) Replace any battery cell/unit if the temperature is greater than 18F above ambient. Replace the battery when any cell/unit measures a voltage less than 13.26 volts. Replace the battery when any cell/unit has an internal ohmic value outside of the acceptable range.

javascript:editViewDevice('4353226');

javascript:editViewDevice('4353227');

Page of 5 18 Proposed Solutions Report

Vets Fire & Life Safety Download Date: 11/05/2025

Proposed Solutions Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 6 Control Panel: 1 The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Battery 4353226 Basement Basement 6B Storage Replace Battery T/M 4353227 Basement Basement 6B Storage Replace Battery T/M

Internal WO/PO #: (none) T/M

Page of 6 18 Notes & Recommendations

Vets Fire & Life Safety Download Date: 11/05/2025

Notes & Recommendations Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 6 Control Panel: 1 The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.

Note Device Type Location Comment ScanID

EC 02.03.05 EP 03 Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

1 Pull Station Basement Basement 6A Entrance 4353249 Construction Area

2 Pull Station Basement Basement 6B Entrance 4353250 Construction Area

3 Smoke Detector Basement Basement 6A Bottom Of Stairs 4353253 Construction Area

4 Smoke Detector Basement Basement 6A Bottom Of Stairs Storage

4353254

Construction Area 5 Smoke Detector Basement Basement 6B Storage 4353255

Construction Area 6 Smoke Detector Basement Basement 6B Storage 4353256

Construction Area 7 Pull Station 1st 1st 6A Entrance 4353251

Construction Area 8 Pull Station 1st 1st 6B Entrance 4353252

Construction Area 9 Smoke Detector 1st 1st 6A Office On Left 4353257

Construction Area 10 Smoke Detector 1st 1st 6B Office On Right 4353258

Construction Area 11 Smoke Detector 2nd 2nd 6A Top Of Stairs 4353259

Construction Area 12 Smoke Detector 2nd 2nd 6B Top Of Stairs 4353260

Construction Area 13 Heat Detector 3rd 3rd 6A Attic 4353247

Construction Area 14 Heat Detector 3rd 3rd 6B Attic 4353248

Construction Area

EC 02.03.05 EP 04 Annual test of visual and audible fire alarms, including speakers and door releasing devices.

NFPA 72 (2022) Table 14.4.3.2 (22) 15 Horn/Strobe Basement Basement 6A Bottom of stairs 4353229

Construction Area javascript:editViewDevice('4353249');

javascript:editViewDevice('4353250');

javascript:editViewDevice('4353253');

javascript:editViewDevice('4353254');

javascript:editViewDevice('4353255');

javascript:editViewDevice('4353256');

javascript:editViewDevice('4353251');

javascript:editViewDevice('4353252');

javascript:editViewDevice('4353257');

javascript:editViewDevice('4353258');

javascript:editViewDevice('4353259');

javascript:editViewDevice('4353260');

javascript:editViewDevice('4353247');

javascript:editViewDevice('4353248');

javascript:editViewDevice('4353229');

Page of 7 18 Notes & Recommendations

Vets Fire & Life Safety Download Date: 11/05/2025

Note Device Type Location Comment ScanID 16 Horn/Strobe Basement Basement 6B Restroom 4353230

Construction Area 17 Horn/Strobe Basement Basement 6B Storage 4353231

Construction Area 18 Horn/Strobe Basement Basement 6B Storage 4353232

Construction Area 19 Horn/Strobe Basement Basement Office 6A Bottom of stairs 4353233

Construction Area 20 Strobe Basement Basement 6A Bottom Of Stairs 4353239

Construction Area 21 Strobe Basement Basement 6A Restroom 4353240

Construction Area 22 Strobe Basement Basement 6B By Stairs 4353241

Construction Area 23 Horn/Strobe 1st 1st 6A Office On Left 4353234

Construction Area 24 Horn/Strobe 1st 1st 6A Office On Right 4353235

Construction Area 25 Horn/Strobe 1st 1st 6B Office On Left 4353236

Construction Area 26 Horn/Strobe 1st 1st 6B Top Of Stairs 4353237

Construction Area 27 Strobe 1st 1st 6A Bottom Of Stairs 4353242

Construction Area 28 Strobe 1st 1st 6A Kitchen 4353243

Construction Area 29 Strobe 1st 1st 6B Bottom Of Stairs 4353244

Construction Area 30 Horn/Strobe 2nd 2nd 6A Top of stairs 4353238

Construction Area 31 Strobe 2nd 2nd 6A Restroom 4353245

Construction Area 32 Strobe 2nd 2nd 6B Restroom 4353246

Construction Area

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4 33 Power Supply Basement Basement 6B Storage 4353228

Construction Area javascript:editViewDevice('4353230');

javascript:editViewDevice('4353231');

javascript:editViewDevice('4353232');

javascript:editViewDevice('4353233');

javascript:editViewDevice('4353239');

javascript:editViewDevice('4353240');

javascript:editViewDevice('4353241');

javascript:editViewDevice('4353234');

javascript:editViewDevice('4353235');

javascript:editViewDevice('4353236');

javascript:editViewDevice('4353237');

javascript:editViewDevice('4353242');

javascript:editViewDevice('4353243');

javascript:editViewDevice('4353244');

javascript:editViewDevice('4353238');

javascript:editViewDevice('4353245');

javascript:editViewDevice('4353246');

javascript:editViewDevice('4353228');

Page of 8 18 Inspection & Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Inspection & Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 6 The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions. Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically.

(NFPA 72-22 Table 14.4.3.2 (17)(4)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Heat Detector 0 0 0 0 2

Device Type Location ScanID Address Q3/24 Q3/25 Heat Detector 3rd 3rd 6A Attic 4353247 1 08/07-P Heat Detector 3rd 3rd 6B Attic 4353248 1 08/07-P

Device Total: 2 Return to Executive Summary

Page of 9 18

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Pull Station 0 0 0 0 4

Device Type Location ScanID Address Q3/24 Q3/25 Pull Station Basement Basement 6A Entrance 4353249 1-1-18 08/07-F Pull Station Basement Basement 6B Entrance 4353250 1 08/07-P Pull Station 1st 1st 6A Entrance 4353251 1 08/07-P Pull Station 1st 1st 6B Entrance 4353252 1 08/07-P

Device Total: 4 Return to Executive Summary

Page of 10 18

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72- 22 Table 14.4.3.2 (17)(7)(a)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Smoke Detector 0 0 0 0 8

Device Type Location ScanID Address Q3/24 Q3/25 Smoke Detector Basement Basement 6A Bottom Of

Stairs 4353253 1 08/07-P

Smoke Detector Basement Basement 6A Bottom Of Stairs Storage

4353254 1 08/07-P

Smoke Detector Basement Basement 6B Storage 4353255 1 08/07-P Smoke Detector Basement Basement 6B Storage 4353256 1 08/07-P Smoke Detector 1st 1st 6A Office On Left 4353257 1 08/07-P Smoke Detector 1st 1st 6B Office On Right 4353258 1 08/07-P Smoke Detector 2nd 2nd 6A Top Of Stairs 4353259 1 08/07-P Smoke Detector 2nd 2nd 6B Top Of Stairs 4353260 1 08/07-P

Device Total: 8 Return to Executive Summary

Page of 11 18

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Horn/Strobe 0 0 0 0 10

Device Type Location ScanID Address Q3/24 Q3/25 Horn/Strobe Basement Basement 6A Bottom of stairs 4353229 1 08/10-P

Horn/Strobe Basement Basement 6B Restroom 4353230 1 08/10-P Horn/Strobe Basement Basement 6B Storage 4353231 1 08/10-P Horn/Strobe Basement Basement 6B Storage 4353232 1 08/10-P Horn/Strobe Basement Basement Office 6A

Bottom of stairs 4353233 1 08/10-P

Horn/Strobe 1st 1st 6A Office On Left 4353234 1 08/10-P Horn/Strobe 1st 1st 6A Office On Right 4353235 1 08/10-P Horn/Strobe 1st 1st 6B Office On Left 4353236 1 08/10-P Horn/Strobe 1st 1st 6B Top Of Stairs 4353237 1 08/10-P Horn/Strobe 2nd 2nd 6A Top of stairs 4353238 1 08/10-P

Device Total: 10 Return to Executive Summary

Page of 12 18

Vets Fire & Life Safety Download Date: 11/05/2025

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Strobe 0 0 0 0 8

Device Type Location ScanID Address Q3/24 Q3/25 Strobe Basement Basement 6A Bottom Of

Stairs 4353239 1 08/07-P

Strobe Basement Basement 6A Restroom 4353240 1 08/07-P Strobe Basement Basement 6B By Stairs 4353241 1 08/07-P Strobe 1st 1st 6A Bottom Of Stairs 4353242 1 08/07-P Strobe 1st 1st 6A Kitchen 4353243 1 08/07-P Strobe 1st 1st 6B Bottom Of Stairs 4353244 1 08/07-P Strobe 2nd 2nd 6A Restroom 4353245 1 08/07-P Strobe 2nd 2nd 6B Restroom 4353246 1 08/07-P

Device Total: 8 Return to Executive Summary

Page of 13 18

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Battery 2 0 2 2 2

Device Type Location ScanID Address Q3/24 Q3/25 Battery Basement Basement 6B Storage 4353226 1 09/01-F Battery Basement Basement 6B Storage 4353227 1 09/01-F

Device Total: 2 Return to Executive Summary

Page of 14 18

Vets Fire & Life Safety Download Date: 11/05/2025

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table

14.4.3.2 (2)(1)) Devices Tested Q3/25 Pass Q3/25 Fail Q3/25 Tested YTD (2025) Total Quantity Power Supply 0 0 0 0 1

Device Type Location ScanID Address Q3/24 Q3/25 Power Supply Basement Basement 6B Storage 4353228 1

Device Total: 1 Return to Executive Summary

Page of 15 18 Service Summary

Vets Fire & Life Safety Download Date: 11/05/2025

Service Summary Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 6 The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Failed/Other Battery Tested 2

Total 2

Untested Heat Detector 2 Horn/Strobe 10 Power Supply 1 Pull Station 4 Smoke Detector 8 Strobe 8

Total 33 Grand Total 35

Page of 16 18 Battery & Power Supply Testing

Vets Fire & Life Safety Download Date: 11/05/2025

Battery & Power Supply Testing Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 6 Control Panel: 1 The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Type Location Rated Ah

Rated Volts Pre Test

Post Test Min Ah Tested Ah

Battery

Failed/Other Sealed Lead Acid Basement Basement 6B

Storage 7 12 12.94 Failed

Sealed Lead Acid Basement Basement 6B Storage

7 12

Page of 17 18 Inventory & Warranty Report

Vets Fire & Life Safety Download Date: 11/05/2025

Inventory & Warranty Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 6 Control Panel: 1 The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity Battery Control 5.71% 2

Heat Detector Initiating 5.71% 2

Horn/Strobe Indicating 28.57% 10

Power Supply Control 2.86% 1

Pull Station Initiating 11.43% 4

Smoke Detector Initiating 22.86% 8

Strobe Indicating 22.86% 8

Type Qty Model # Description Install Date

In Service - 1 Year to 2 Years Horn/Strobe 10 08/10/2024 Battery 2 Sealed Lead Acid 08/07/2024 Heat Detector 2 08/07/2024 Power Supply 1 08/07/2024 Pull Station 4 08/07/2024 Smoke Detector 8 08/07/2024 Strobe 8 08/07/2024

Page of 18 18 Zone Address Report

Vets Fire & Life Safety Download Date: 11/05/2025

Zone Address Report Generated by: BuildingReports.com

Building: Fayetteville VAMC Bldg 6 Control Panel: 1 The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID 1-18 Pull Station Basement Basement 6A Entrance 4353249 javascript:editViewDevice('4353249');

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
Executive Summary
Discrepancy Report
Proposed Solutions Report
Notes & Recommendations
Inspection & Testing
Service Summary
Battery & Power Supply Testing
Inventory & Warranty Report
Zone Address Report