Prepared By:
Chris Espartero Sr Field Service Representative
North America Service Operations
Houston, TX
USS-8 Substation PM
April 27, 2021
Work Order: 08391081
2 | P a g e
EXECUTIVE SUMMARY
Schneider Electric Services perform Transformer and Switchboard PM in accordance with project specification and applicable industry standard on USS-8 Substation located at VA loading duct tunnel 2002 Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe
Ceasar of VA Medical Center Electrical Power Distribution Department (713)806-7506.
USS-8 480V Switchboard
USS-8 480V Switchboard Main Breaker trip unit failed to trip during breaker primary injection testing. The Main Breaker picked up 50% higher than the expected value on long time and it will intermittently trip during primary injection testing on long time delay test, short time delay test, and instantaneous testing. For this switchboard the customer did not have a spare breaker that will match the CT’s and Trip unit settings of USS-8 switchboard main breaker. The customer decided to put the existing main breaker in service. The circuit breaker was then replaced by the circuit breaker taken from USS-7 that was repaired on schneider electric breaker shop.
If there are any questions or concerns, please contact:
Chris Espartero
832-205-1547
Christopher.Espartero@se.com
USS-8_876101-F1_XD
DryTypeTransformerReport Source
4/27/2021 8:13:20 PMSession Test Date
Nameplate Company VA Medical Center Serial Number 876101-F1
Location 2002 Holcombe Blvd Houston, Texas 77030
Special ID USS-8 XFMR
Division Houston Circuit Designation USS-8 SUBSTATION
Manufacturer Square D Electric Class
Year Manufactured Type DryTypeTransformer
Mfr Location USA Winding Insulation Open-Wound
Coolant Select Coolant Weight 7710
Tank Type Select Tank Type BIL 110 kV
Dry Tank Type Ventilated VA Rating 750 kV 12.47,0.48,* Insulation Material Nomex
Administration Test Date 4/27/2021 Test Time: 8:13 PM Weather Indoors
Air Temperature 20°C Apparatus Temperature
* Humidity 61 %
Tester C.Espartero Work Order Date Last Tested
Verified Test Set Type M4000 Date Retested
Verification Date 4/27/2021 Set Top Serial # Reason ROUTINE
Last Sheet # Set Bottom Serial # Travel Time
Purchase Order Ins. Book # Duration
Copies Sheet # Crew Size 1
1 - 6876101-F1
Session Notes
2 - 6876101-F1
Bushing Nameplate Designation Serial # Manufacturer Type C1 %PF C1 Cap C2 %PF C2 Cap Rated kV Amps
H1 H1 * * * * * *
H2 H2 * * * * * *
H3 H3 * * * * * *
LSR mA: 3.381/3.381, 1/1 Watts: 0.042/0.042, 1/1 Cap (pF): 896.759/896.759, 1/1
LSR mA: 0.800/0.800, 1/1 Watts: 0.029/0.029, 1/1 Cap (pF): 212.197/212.197, 1/1
LSR mA: 2.582/2.582, 1/1 Watts: 0.009/0.009, 1/1 Cap (pF): 684.813/684.813, 1/1
LSR mA: 2.581/2.581, 1/1 Watts: 0.014/0.014, 1/1 Cap (pF): 684.562/684.562, 1/1
LSR mA: 6.400/6.400, 1/1 Watts: 0.054/0.054, 1/1 Cap (pF): 1697.638/1697.638, 1/1
LSR mA: 3.820/3.820, 1/1 Watts: 0.037/0.037, 1/1 Cap (pF): 1013.276/1013.276, 1/1
LSR mA: 2.582/2.582, 1/1 Watts: 0.010/0.010, 1/1 Cap (pF): 684.801/684.801, 1/1
LSR mA: 2.580/2.580, 1/1 Watts: 0.017/0.017, 1/1 Cap (pF): 684.362/684.362, 1/1
Overall Tests - 2K # Insulation Test kV mA Watts % PF Meas. Cap (pF) IR Man.
1 CH+CHL 2.000 3.381 0.042 0.126 896.759 Good
2 CH 2.000 0.800 0.029 0.357 212.197 Good
3 CHL(UST) 2.000 2.582 0.009 0.033 684.813 Good
4 CHL 0 2.581 0.014 0.054 684.562 Good
5 CL+CHL 1.000 6.400 0.054 0.085 1697.638 Good
6 CL 0.999 3.820 0.037 0.098 1013.276 Good
7 CHL(UST) 1.000 2.582 0.010 0.039 684.801 Good
8 CHL 0 2.580 0.017 0.065 684.362 Good
3 - 6876101-F1
LSR mA: 3.383/3.383, 1/1 Watts: 0.047/0.047, 1/1 Cap (pF): 897.308/897.308, 1/1
LSR mA: 0.802/0.802, 1/1 Watts: 0.031/0.031, 1/1 Cap (pF): 212.867/212.867, 1/1
LSR mA: 2.581/2.581, 1/1 Watts: 0.011/0.011, 1/1 Cap (pF): 684.548/684.548, 1/1
LSR mA: 2.580/2.580, 1/1 Watts: 0.016/0.016, 1/1 Cap (pF): 684.442/684.442, 1/1
LSR mA: 6.400/6.400, 1/1 Watts: 0.057/0.057, 1/1 Cap (pF): 1697.719/1697.719, 1/1
LSR mA: 3.820/3.820, 1/1 Watts: 0.039/0.039, 1/1 Cap (pF): 1013.318/1013.318, 1/1
LSR mA: 2.582/2.582, 1/1 Watts: 0.009/0.009, 1/1 Cap (pF): 684.835/684.835, 1/1
LSR mA: 2.580/2.580, 1/1 Watts: 0.018/0.018, 1/1 Cap (pF): 684.401/684.401, 1/1
Overall Tests - LG # Insulation Test kV mA Watts % PF Meas. Cap (pF) Tip UP FRANK™ IR Man.
1 CH+CHL 10.004 3.383 0.047 0.139 897.308 *
2 CH 10.004 0.802 0.031 0.389 212.867 0.032 Good
3 CHL(UST) 10.004 2.581 0.011 0.044 684.548 0.011 Investigate
4 CHL 0 2.580 0.016 0.062 684.442 *
5 CL+CHL 1.000 6.400 0.057 0.089 1697.719 *
6 CL 1.000 3.820 0.039 0.101 1013.318 0.003 Good
7 CHL(UST) 1.000 2.582 0.009 0.034 684.835 -0.006
8 CHL 0 2.580 0.018 0.070 684.401 * Investigate
Winding Resistance
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 323 milli Ohms * * * *
3 B 319.7 milli Ohms * * * *
3 C 320.3 milli Ohms * * * *
High Voltage
DETC LTC Phase Resistance Units Calculated Resistance
Correction Factor
Corrected Resistance
Percentage Deviation
3 A 607.9 micro Ohms * * * *
3 B 623.9 micro Ohms * * * *
3 C 608 micro Ohms * * * *
Low Voltage
Winding
Manufacturer Serial Number Configuration Winding Temperature
Temperature Rise
Factory Resistance
(Ohms)
Factory Temperature
Δ-Y * * * *
4 - 6876101-F1
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
H3 H1 H1 H2 H2 H3
DETC LTC Test kV mA Watts X mA Watts X mA Watts X FRANK™ Manual
3 5 93.317 717.824 L 86.071 695.763 L 44.132 353.285 L Good
LSR mA: 93.317/93.317, 1/1 Watts: 717.824/717.824, 1/1 Cap (pF): */*, 1/1
LSR mA: 86.071/86.071, 1/1 Watts: 695.763/695.763, 1/1 Cap (pF): */*, 1/1
LSR mA: 44.132/44.132, 1/1 Watts: 353.285/353.285, 1/1 Cap (pF): */*, 1/1
Turns Ratio Tests Serial Number HV Winding LV Winding
Delta Wye
Connections H3 - H1 H1 - H2 H2 - H3
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK™ Manual
3 12470 3 480 44.997 45.09 45.098 45.066 44.772 45.222 Good Good
5 - 6876101-F1
Exciting Current Plot
6 - 6876101-F1
ZONE INTLK
BREAKER TYPE
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-8DESIGNATION
SUBSTATION BUILDING 100
4/27/2021 48
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
ATS-45
JONATHAN DERDARI
3284,3230
VA Hospital WO-08391081
400 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65KA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF436LIG
N/AFUSE CAT. NO.
400 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
Poor
Not Checked
New
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
N/ARANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
139100
N/A
N/A
9 7 9
.2
1 IN
.9
N/A
N/A
N/A
N/A
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 400RATING PLUG:400 400
Overcurrent Settings
CT / SENSOR RATINGS:
1 IN 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
2,788
NT
NT
0.55
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
NT
400 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
1,600
8.914
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 1
sec sec sec sec sec sec
AS LEFT
360 A A440
A A
AA
A A
3,0802,520
144 176
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
COMMENTS:
DEFICIENCIES:
20°C
MEDIUM VOLTAGE AIR SWITCH
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-8DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MV AIR SWITCH RB
Steve O'Keefe
N/A
N/A
VA Hospital WO-08391081
Cleaned
Cleaned N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
N/A
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
Cleaned
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES Acceptable Cleaned N/AINTERLOCKS N/A N/AINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
N/A
Acceptable
Acceptable
Acceptable
Acceptable
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
N/A
44035-234-51
4.76 kv
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE N/A
95KV
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
FUSE AMPSA1550X50E-1FUSE MFG. GOULD FUSE CAT. NO. 50E
@5000VGIG-OHMS 20°C
0.0 0.0
0.0 0.0
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
0.00.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
0.0
0.0
0.0
0.0
0.0
0.00.0
0.0
0.0
0.0 0.0
0.0
15 kv
Allen Bradley
RANGE
(µ-ohms) 27
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10 A
POLE 1
23 29
TECH NOTE(S): Did not test insulation resistance due to feeder cables connected to the switch.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-8DESIGNATION
SUBSTATION BUILDING 100
4/27/2021 48
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
ATS-44
JONATHAN DERDARI
3284,3230
VA Hospital WO-08391081
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONMX
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF36400LSG
N/AFUSE CAT. NO.
400 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
4.5
.2 IN
10 5 10
.2
.2 IN
.2 IN
4.5
.2 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 400( APR100)RATING PLUG:400 400
Overcurrent Settings
CT / SENSOR RATINGS:
.2 IN .2 OUT
.35.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
2,004
1.202
0.172
NT NT NT NT NT
1,800 1.2 1.7
400 0.14 0.2
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 8 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
1,200
7.316
SHORT TIME PICKUP
SHORT TIME DELAY 1.125
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.87
sec sec sec sec sec sec
AS LEFT
360 A A440
A A
AA
A A
1,440 1,760
2,2001,800
120 154
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
SE SWITCHBOARD / SWITCHGEAR INSPECTION
TEMPERATURE 77 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-8DESIGNATION
SUBSTATION BUILDING 100
4/27/2021 48
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
480 VOLT SWITCHGEAR
CUONG HO
3230,3228
VA Hospital WO-08391081
480/277MANUFACTURER
1000 AMP
BUS CONNECTIONS
EXTERIOR CONDITION
CLEAN/LUBE CLEAN/LUBECONDITION
Acceptable
Acceptable
N/A
Acceptable
Cleaned
CONDITION
N/A
Description
Cleaned
N/A
INDICATORS / LAMPS
N/A
MATCHES DWG OR SPEC N/A
FUNCTIONAL CHECKS
BUS INSULATION N/A N/A N/A
KEY / MECH. INTERLOCKS
N/A
PLC's / HMI's N/A
CONDITION
N/A
Acceptable
N/A
N/A
Acceptable
NAMEPLATE
21001, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
WITHSTAND RATING
TYPE / STYLECURRENT RATING QED
SN / SO NO. SYSTEM VOLTAGE
MODEL / CATALOG
N/A
45-08000-65S
INSPECTION
Acceptable
PT'S AND CT'S
Acceptable N/A AcceptablePOWER CABLES
N/A N/A N/A INTERCONNECT WIRING Not CheckedRACKING / LIFTING MECHANISMS
Comment Not CheckedDOORS / COVERS / GASKETS
CPT AND CPT XFER CKT. ANCHORAGE
GROUNDING
PHASING CHECK
CONTROL WIRING
SPACE HEATERS
Description
N/A
C & LINTERIOR SECTIONS / CUBICLES
Cleaned
PHASE BARRIERS
SEQUENCE OF OPERATION
Description
N/A
N/A
N/A
N/A
N/A
Square D
RANGE
BARRIERS / SHUTTERS
@1000VGIG-OHMS 20°C
100.0 125.0
TEST 1
TEST 2
INSULATION RESISTANCE IN: PHASE-PHASE
272.5218.0
20°CACTUALACTUAL
A - B A-GND
PHASE-GROUND
B-GND
C-GND
B - C
C - A
267.0
274.0
160.0
265.0
200.0
333.8
342.5 331.3TEST 3
N-GNDTEST 4
1.25TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
INSULATION RESISTANCE TEST
SECTION 1 SECTION 2 29 32 30 29
NBAFROM TO
BUS SECTION TESTED RESISTANCE IN MICRO-OHMS
C
RESISTANCE IN MICRO-OHMS
G
N
BUSWORK CONNECTION RESISTANCE
CBAFROM TO
BUS SECTION TESTED
G
TECH NOTE(S): PASSED ALL THE TESTS
20°C
MEDIUM VOLTAGE AIR SWITCH
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-8DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MV AIR SWITCH B2
Steve O'Keefe
N/A
N/A
VA Hospital WO-08391081
Cleaned
Cleaned N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Comment
Acceptable
N/A
N/A
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
Cleaned
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES Acceptable Cleaned N/AINTERLOCKS N/A N/AINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
Acceptable
Acceptable
Acceptable
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
N/A
44035-233-51
15 kv
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE N/A
95KV
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
FUSE AMPSN/AFUSE MFG. N/A FUSE CAT. NO. N/A
@5000VGIG-OHMS 20°C
41.6 59.7
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
30.4
33.9 48.6
43.6
15 kv
Square D
RANGE
(µ-ohms) 101
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10 A
POLE 1
67 157
TECH NOTE(S): Did not test insulation resistance due to feeder cables connected to the switch.
COMMENTS: Contact resistance test on switch main contact is higher than the acceptable value on C-Phase.
TRIP UNIT TYPE
CNTJ99430
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 74 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-8DESIGNATION
SUBSTATION BUILDING 100
4/27/21 55
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MAIN BREAKER
Cuong Ho
3230,3115,01025
VA Hospital WO-08391081
1600 AMP
Cleaned
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
ONDS 416H
65 KVA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. N/A
N/AFUSE CAT. NO.
1600 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
CleanedAcceptable
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Deficiency
CONDITION
N/A
Acceptable
Acceptable
Deficiency
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Carriere N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VGIG-OHMS 20°C
357.7
323.9
TEST 1
TEST 3
1.165TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
357.7
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
351.8
312.2
308.7
362.3 381.0
206.2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
.70
2.5
3.0
.15
4 OFF 2 4 OFF
.3
.2
1.0
2.5
2.5
.15
.70
2.5
3.0
.15
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 1600 AMPRATING PLUG:1600 AMP 1600 AMP
Overcurrent Settings
CT / SENSOR RATINGS:
.2 .4
.4.3
AS FOUND
RANGE
MINIMUM MAXIMUM
0.45
0.45
4,150
0.45
4,150
0.45
3,001
4,130
0.47
3,001
4,130
0.47
7,200 0.08 0.18
960 0.38 0.5
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
3 41 36.30 36.30 24.87 24.87
1,612 1,690 1,690 1,620 1,620
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 12 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
4,800 7
1,612
SHORT TIME PICKUP
SHORT TIME DELAY 3
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 1.5
sec sec sec sec sec sec
AS LEFT
1,440 A A1,760
A A
AA
A A
3,600 4,400
3,5202,880
576 705
POLE 1
FUNCTION
POLE 2TEST RESULTS BY PRIMARY INJECTION
TECH NOTE(S):
COMMENTS: NEED TO REPLAMENT NEW TRIP UNITS
DEFICIENCIES: BREAKER FAIL ON PRIMARY INJECTION
TRIP UNIT TYPE
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 68 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-8DESIGNATION
SUBSTATION BUILDING 100
05/01/21 50
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MAIN BREAKER REPLACEMENT
Javier Rojas
VA Hospital WO-08391081
Cleaned
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
ONDS 416
50 KVA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. N/A
N/AFUSE CAT. NO.
1600 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
CleanedAcceptable
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS N/A N/A
OVERALL CONDITION Acceptable
CONDITION
N/A
Acceptable
Acceptable
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Westinghouse
AC PRO N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
@1000VGIG-OHMS 20°C
753.0 753.0
73.0 73.0
TEST 1
TEST 3
1TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
797.0797.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
826.0
690.0
433.0
406.0
104.0
874.0433.0
826.0
874.0
690.0 406.0
104.0
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
0.7
2.5
3.0
0.15
2 OFF 3200 2 OFF
0.3
.15
1.0
2.5
.4
1.0
2.5
3.0
.20
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 1600 AMPRATING PLUG:1600 AMP 1600 AMP
Overcurrent Settings
CT / SENSOR RATINGS:
.20 .4
320.2
AS FOUND
RANGE
MINIMUM MAXIMUM
3,337
0.22
0.41
3,337
0.22
5,081
0.41
3,392
0.21
5,140
0.45
3,392
0.21
5,140
0.45
3,307
0.21
5,174
0.44
3,307
0.21
5,174
0.44
6,000 0.08 0.18
960 0.38 0.5
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
3 10.43 1,043 1,043 10.38 10.38
1,638 1,624 1,624 1,642 1,642
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 12 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
4,800 7
1,638
10.43
SHORT TIME PICKUP
SHORT TIME DELAY 1.5
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 1.5
sec sec sec sec sec sec
AS LEFT
1,440 A A1,760
A A
AA
A A
4,320 5,220
3,5202,880
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY PRIMARY INJECTION
TECH NOTE(S): This spare breaker is from USS-7 Main circuit breaker. Breaker will be use to replaced USS-8 main breaker that failed on primary injection test.
COMMENTS: Installed new AC PRO retrofit kit. Performed preventive maintenance, repair, primary injected. All tests proved satisfactory.
TWO-WINDING DRY-TYPE TRANSFORMER
TEMPERATURE 68 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-8DESIGNATION
SUBSTATION BUILDING 100
4/27/2021 61
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
DRY TYPE TRANSFORMER
Chris Espartero
M4K
VA Hospital WO-08391081
Acceptable
CONDITIONDescription CLEAN/LUBEDescription
N/A
N/A
Acceptable N/A
N/A
N/A N/A
FANS
N/AAcceptable
Acceptable
N/A N/A N/A
N/A
N/AVENTILATION / FILTERS
N/A
PAINT Acceptable
INDOOR
CleanedAcceptable
N/A
MATCHES DWG OR SPEC
WEATHER
Cleaned
ENVIRONMENT
Acceptable
N/A
GAUGES
SUPPORT INSULATORS
N/AN/A
N/A
Windings
Acceptable
N/A CABINET HEATERS
AUXILIARY DEVICES N/ATorqued
PRIMARY CONNECTIONS
TANK / FRAME GROUND
NEUTRAL GROUND
Description CONDITION
SEC. CONNECTIONS Acceptable
N/A
N/A
Acceptable
N/A Torqued
ARRESTERS
CORE GROUND
ALARMS / ANNUNCIATOR
CONTROLS
BUSHINGS
CLEAN/LUBE CLEAN/LUBECONDITION
TEMPERATURE GAUGES WERE RESETunavailable °CMAXIMUM WINDING TEMPERATURE (1)°C35WINDING TEMPERATURE (1)
GAUGES
Acceptable
CLEAN
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
35 35
902902902
NAMEPLATE DATA
RATED CURRENT
RATED CURRENT
AMPERES
AMPERES/
11,846
3 4 5 kV PRI.
PRIMARY VOLTAGE
SECONDARY VOLTAGE 277 WYE
13,094
TAP POSITION/CONNECTION
12,782 12,158
CLASS
12,470
Phase 3876101-F1SERIAL NO.
kVA/
THERMAL RATINGS
DELTA
kV SEC.
IMPEDANCE
YEAR OF MANUF.NA 1988
MANUFACTURER
SPECIFICATION NO. MANUF. LOCATION
TYPE AA K FACTOR N/A °CTEMPERATURE RISE
USA
305.9
B.I.L. RATINGWINDING MATERIAL Cu
LB
DELTA480
TAP VOLTAGES
WINDING POLARITY SUBTRACTIVE
WYE
750 / 750
12,470
TOTAL WEIGHT
Dry
Square D
RANGE
INSPECTION
INSULATION RESISTANCE TEST
TESTED
PRIMARY TO
SECONDARY AND GROUND
SECONDARY TO
PRIMARY AND GROUND
VOLTAGE
(VOLTS DC)
(MEGOHMS)
Windings TEST RESISTANCE
PRIMARY TO
SECONDARY
1.0 MINUTE0.5 MINUTE 0.5 MIN. 20C 1.0 MIN. 20C
Acceptable
Acceptable
Acceptable
DIELECTRIC
ABSORPTION
RATIO
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF 2
5,000
1,000
5,000
369,000.0 738,000.0 599,000.0 1,198,000
294,000.0147,000.0262,000.0131,000.0
109,000.0 218,000.0 298,000.0 596,000.0
1.62
1.12
2.73
Calculated PASS/FAIL Calculated
PASS/FAIL
TO
% DEVIATIONMeasured
TRANSFORMER TURNS RATIO TESTS
Calculated PASS/FAIL
CALC.
RATIO
Secondary
VOLTAGE
ENTER Primary
VOLTAGE
X0 - X1 X0 - X2
H3 - H1 H1 - H2 H2 - H3
X0 - X3
TAP TO
TEST
3 45.090 45.098 45.0660.23 % PASS 0.16 % PASSPASS44.996 0.21 %12,470 277
TWO-WINDING DRY-TYPE TRANSFORMER
PAGEDRY TYPE TRANSFORMERDEVICE DBID
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
H3-H1 X0-X3X0-X1
WINDING RESISTANCE
H2-H3
Meas. Corr.
TAP
POSITION
TEST
# (milliohms)H1-H2 (milliohms) (milliohms)
Corr.Meas. Corr.Meas.
(milliohms)
Corr. Corr.Meas. Corr.Meas.Meas.
X0-X2 (milliohms) (milliohms)
WINDING TESTED
(t = Equipment Temperature)
Values Corrected to: °C75
Aluminum windings
R(Corr) = R(Meas) * (234.5 + c) / (234.5 + t)Copper windings
R(Corr) = R(Meas) * (226 + c) / (226 + t)
(c = Corrected Temperature)
3 323.000 370.941 319.700 367.151 320.300 367.840 0.607 0.697 0.623 0.715 0.608 0.6981
Primary Secondary
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.