Prepared By:
Chris Espartero Sr Field Service Representative
North America Service Operations
Houston, TX
USS-6 Substation PM
April 21, 2021
Work Order: 08391081
2 | P a g e
EXECUTIVE SUMMARY
Schneider Electric Services perform Transformer and Switchboard PM in accordance with project specification and applicable industry standard on USS-6 Substation located at VA loading duct tunnel 2002 Holcombe Blvd Houston, Texas 77030. The site contact for this project was Joe
Ceasar of VA Medical Center Electrical Power Distribution Department (713)806-7506.
USS-6 Main Breaker ground fault test trip time on A and B Phase is slightly higher than the maximum expected trip time of 2.42 seconds.
If there are any questions or concerns, please contact:
Chris Espartero
832-205-1547
Christopher.Espartero@se.com
USS-6_876101-G1_XD
Report Source DryTypeTransformer 4/20/2021 6:35:32 PMSession Test Date
Nameplate Company VA Medical Center Serial Number 876101-G1 Location 2002 Holcombe Blvd Houston, Texas Special ID USS-6
77030 Division Houston Circuit Designation USS-6 SUBSTATION Manufacturer Square D Electric Class Year Manufactured Type DryTypeTransformer Mfr Location USA Winding Insulation Open-Wound Coolant Select Coolant Weight 6460 Tank Type Select Tank Type BIL 110 kV Dry Tank Type Ventilated VA Rating 750 kV 12.47,0.48,* Insulation Material Nomex
Administration Test Date 4/20/2021 Test Time: 6:35 PM Weather Indoors Air Temperature 22.8°C Apparatus * Humidity 50 %
Temperature Tester C.Espartero Work Order Date Last Tested Verified Test Set Type M4000 Date Retested Verification Date 4/20/2021 Set Top Serial # Reason ROUTINE Last Sheet # Set Bottom Serial # Travel Time Purchase Order Ins. Book # Duration Copies Sheet # Crew Size 1
876101-G1 1 - 6
Session Notes
876101-G1 2 - 6
Bushing Nameplate Designation Serial # Manufacturer Type C1 %PF C1 Cap C2 %PF C2 Cap Rated kV Amps
H1 H1 * * * * * * H2 H2 * * * * * * H3 H3 * * * * * *
Overall Tests - 2K
876101-G1 3 - 6
# Insulation
CH+CHL
CH
CHL(UST)
CHL
CL+CHL
CL
CHL(UST)
CHL
Test kV 2.000 8.000 1.999
1.000 1.000 0.999 mA Watts 0.040 0.027 0.010 0.013 0.077 0.053 0.011 0.023
% PF Meas.
0.117 0.348 0.036 0.050 0.119 0.140 0.043 0.087
Cap (pF) 905.034 203.570 701.622 701.464 1713.918 1012.614 701.735 701.304
IR Man.
Good Good Good Good Good Good Good Good
3.412 0.767 2.645 2.644 6.461 3.818 2.646 2.644
LSR
LSR
LSR
LSR
LSR
LSR
LSR
LSR
mA: 3.412/3.412, 1/1 mA: 0.767/0.767, 1/1 mA: 2.645/2.645, 1/1 mA: 2.644/2.644, 1/1 mA: 6.461/6.461, 1/1 mA: 3.818/3.818, 1/1 mA: 2.646/2.646, 1/1 mA: 2.644/2.644, 1/1
Watts: 0.040/0.040, 1/1 Watts: 0.027/0.027, 1/1 Watts: 0.010/0.010, 1/1 Watts: 0.013/0.013, 1/1 Watts: 0.077/0.077, 1/1 Watts: 0.053/0.053, 1/1 Watts: 0.011/0.011, 1/1 Watts: 0.023/0.023, 1/1
Cap (pF): 905.034/905.034, 1/1 Cap (pF): 203.570/203.570, 1/1 Cap (pF): 701.622/701.622, 1/1 Cap (pF): 701.464/701.464, 1/1 Cap (pF): 1713.918/1713.918, 1/1 Cap (pF): 1012.614/1012.614, 1/1 Cap (pF): 701.735/701.735, 1/1 Cap (pF): 701.304/701.304, 1/1
Δ-
USS-6_876101-G1_XD
Overall Tests - LG
Winding Resistance
Winding Manufacturer Serial Number Configuration Winding Temperature Factory Factory
Temperature Rise Resistance Temperature (Ohms)
Y * * * *
High Voltage DETC LTC Phase Resistance Units Calculated Correction Corrected Percentage
Resistance Factor Resistance Deviation 3 A 308.6 milli Ohms * * * * 3 B 310 milli Ohms * * * * 3 C 303.5 milli Ohms * * * *
Low Voltage DETC LTC Phase Resistance Units Calculated Correction Corrected Percentage
Resistance Factor Resistance Deviation 3 A 577.2 micro Ohms * * * * 3 B 591.5 micro Ohms * * * * 3 C 582.1 micro Ohms * * * *
876101-G1 4 - 6
# Insulation
CH+CHL
CH
CHL(UST)
CHL
CL+CHL
CL
CHL(UST)
CHL
Test kV 10.005 10.004 10.004
0.999 1.000 1.000 mA Watts 0.041 0.026 0.011 0.015 0.070 0.050 0.011 0.019
% PF Meas.
0.122 0.345 0.041 0.057 0.108 0.132 0.040 0.072
Cap (pF) 904.515 203.406 701.318 701.108 1713.890 1012.601 701.711 701.290
Tip UP
-0.003 0.005
-0.008 -0.003
FRANK IR Man.
3.410 0.767 2.644 2.643 6.461 3.817 2.645 2.644
Good Investigate
Good
Investigate
LSR
LSR
LSR
LSR
LSR
LSR
LSR
LSR
mA: 3.410/3.410, 1/1 mA: 0.767/0.767, 1/1 mA: 2.644/2.644, 1/1 mA: 2.643/2.643, 1/1 mA: 6.461/6.461, 1/1 mA: 3.817/3.817, 1/1 mA: 2.645/2.645, 1/1 mA: 2.644/2.644, 1/1
Watts: 0.041/0.041, 1/1 Watts: 0.026/0.026, 1/1 Watts: 0.011/0.011, 1/1 Watts: 0.015/0.015, 1/1 Watts: 0.070/0.070, 1/1 Watts: 0.050/0.050, 1/1 Watts: 0.011/0.011, 1/1 Watts: 0.019/0.019, 1/1
Cap (pF): 904.515/904.515, 1/1 Cap (pF): 203.406/203.406, 1/1 Cap (pF): 701.318/701.318, 1/1 Cap (pF): 701.108/701.108, 1/1 Cap (pF): 1713.890/1713.890, 1/1 Cap (pF): 1012.601/1012.601, 1/1 Cap (pF): 701.711/701.711, 1/1 Cap (pF): 701.290/701.290, 1/1
LSR mA: 91.964/91.964, 1/1 Watts: 708.248/708.248, 1/1 Cap (pF): */*, 1/1 LSR mA: 91.736/91.736, 1/1 Watts: 709.370/709.370, 1/1 Cap (pF): */*, 1/1 LSR mA: 41.829/41.829, 1/1 Watts: 339.631/339.631, 1/1 Cap (pF): */*, 1/1
USS-6_876101-G1_XD
Exciting Current Tests Manufacturer Type Steps Boost % Buck % Position Found Position Left Oil Volume
DETC 3 3 *
Turns Ratio Tests Serial Number HV Winding LV Winding
Delta Wye Connections H3 - H1 H1 - H2 H2 - H3
Tap NP Volt Tap NP Volt Cal Ratio 1 Ratio 2 Ratio 3 Min. Lim Max. Lim FRANK Manual
3 12470 3 480 44.997 45.123 45.126 45.139 44.772 45.222 Good Good
876101-G1 5 - 6
DETC
LTC Test kV mA 91.964
H3 H1 Watts
708.248 X L
mA 91.736
H1 H2 Watts
709.370 X L
mA 41.829
H2 H3 Watts X
L FRANK Manual
Good339.631
Exciting Current Plot
876101-G1 6 - 6
TWO-WINDING DRY-TYPE TRANSFORMER
TEMPERATURE 73 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-6DESIGNATION
SUBSTATION BUILDING 100
4/20/2021 50
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
DRY TYPE TRANSFORMER
Chris Espartero
0086, 3137
N/A
N/A
VA Hospital WO-08391081
Acceptable
CONDITIONDescription CLEAN/LUBEDescription
N/A
Torqued
N/A N/A
N/A
N/A N/A
FANS
N/AAcceptable
Acceptable
N/A N/A N/A
N/A
N/AVENTILATION / FILTERS
N/A
PAINT Acceptable
INDOOR
CleanedAcceptable
N/A
MATCHES DWG OR SPEC
WEATHER
Cleaned
ENVIRONMENT
Acceptable
N/A
GAUGES
SUPPORT INSULATORS
N/ATorqued
N/A
Windings
Acceptable
N/A CABINET HEATERS
AUXILIARY DEVICES N/ATorqued
PRIMARY CONNECTIONS
TANK / FRAME GROUND
NEUTRAL GROUND
Description CONDITION
SEC. CONNECTIONS Acceptable
N/A
N/A
Acceptable
N/A Torqued
ARRESTERS
CORE GROUND
ALARMS / ANNUNCIATOR
CONTROLS
BUSHINGS
CLEAN/LUBE CLEAN/LUBECONDITION
TEMPERATURE GAUGES WERE RESETunavailable °CMAXIMUM WINDING TEMPERATURE (1)°CunavailableWINDING TEMPERATURE (1)
GAUGES
N/A
CLEAN
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
35 35
902902902
NAMEPLATE DATA
RATED CURRENT
RATED CURRENT
AMPERES
AMPERES/
11,846
3 4 5 kV PRI.
PRIMARY VOLTAGE
SECONDARY VOLTAGE 277 WYE
13,094
TAP POSITION/CONNECTION
12,782 12,158
CLASS
12,470
Phase 3876101-G1SERIAL NO.
kVA/
THERMAL RATINGS
DELTA
kV SEC.
IMPEDANCE
YEAR OF MANUF.N/A 1988
MANUFACTURER
SPECIFICATION NO. MANUF. LOCATION
TYPE AA K FACTOR N/A °CTEMPERATURE RISE
U.S.A
805.8
B.I.L. RATINGWINDING MATERIAL Cu
LB
DELTA480
TAP VOLTAGES
WINDING POLARITY SUBTRACTIVE
WYE
750 / 750
12,470
TOTAL WEIGHT
Dry
Square D
RANGE
INSPECTION
INSULATION RESISTANCE TEST
TESTED
PRIMARY TO
SECONDARY AND GROUND
SECONDARY TO
PRIMARY AND GROUND
VOLTAGE
(VOLTS DC)
(MEGOHMS)
Windings TEST RESISTANCE
PRIMARY TO
SECONDARY
1.0 MINUTE0.5 MINUTE 0.5 MIN. 20C 1.0 MIN. 20C
DIELECTRIC
ABSORPTION
RATIO
TEMPERATURE CORRECTION FACTOR TO 20°C, TCF 1.14
5,000
1,000
5,000
1,211,000 1,380,540 1,342,000 1,529,880
1,445,5201,268,0001,063,620933,000.0
445,000.0 507,300.0 644,000.0 734,160.0
1.11
1.36
1.45
Calculated PASS/FAIL Calculated
PASS/FAIL
TO
% DEVIATIONMeasured
TRANSFORMER TURNS RATIO TESTS
Calculated PASS/FAIL
CALC.
RATIO
Secondary
VOLTAGE
ENTER Primary
VOLTAGE
X1 - X0 X2 - X0
H1 - H3 H2 - H1 H3 - H2
X3 - X0
TAP TO
TEST
3 45.123 45.126 45.1390.29 % PASS 0.32 % PASSPASS44.996 0.28 %12,470 277
TWO-WINDING DRY-TYPE TRANSFORMER
PAGEDRY TYPE TRANSFORMERDEVICE N/ADBID
23210, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
H3-H1 X0-X3X0-X1
WINDING RESISTANCE
H2-H3
Meas. Corr.
TAP
POSITION
TEST
# (milliohms)H1-H2 (milliohms) (milliohms)
Corr.Meas. Corr.Meas.
(milliohms)
Corr. Corr.Meas. Corr.Meas.Meas.
X0-X2 (milliohms) (milliohms)
WINDING TESTED
(t = Equipment Temperature)
Values Corrected to: °C75
Aluminum windings
R(Corr) = R(Meas) * (234.5 + c) / (234.5 + t)Copper windings
R(Corr) = R(Meas) * (226 + c) / (226 + t)
(c = Corrected Temperature)
3 308.600 371.208 310.000 372.892 303.500 365.073 0.577 0.694 0.591 0.711 0.582 0.7001
Primary Secondary
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.
DEFICIENCIES:
ZONE INTLK
BREAKER TYPE
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-6DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT A
David Gordon
3284,3230
VA Hospital WO-08391081
800 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF836LSIG
N/AFUSE CAT. NO.
800 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
Acceptable
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
2 IN
10 7 10
.2
1 IN
.9
4 IN
2 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 800RATING PLUG:800 800
Overcurrent Settings
CT / SENSOR RATINGS:
1 IN 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
5,616
2.008
0.545
NT NT NT NT NT
4,200 1.6 2.6
800 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
3,200
8.971
SHORT TIME PICKUP
SHORT TIME DELAY 1.05
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.5
sec sec sec sec sec sec
AS LEFT
720 A A880
A A
AA
A A
3,600 4,400
6,1605,040
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
COMMENTS:
SE SWITCHBOARD / SWITCHGEAR INSPECTION
TEMPERATURE 73 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-6DESIGNATION
SUBSTATION BUILDING 100
04/24/2014 65
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
480 VOLT SWITCHGEAR
Chris Espartero
3230,3226
VA Hospital WO-08391081
480/277
N/A
MANUFACTURER
1600 AMP
BUS CONNECTIONS
EXTERIOR CONDITION
CLEAN/LUBE CLEAN/LUBECONDITION
Acceptable
Acceptable
N/A
Acceptable
Cleaned
CONDITION
N/A
Description
Cleaned
N/A
INDICATORS / LAMPS
N/A
MATCHES DWG OR SPEC N/A
FUNCTIONAL CHECKS
BUS INSULATION N/A N/A Cleaned
KEY / MECH. INTERLOCKS
N/A
PLC's / HMI's N/A
CONDITION
N/A
Acceptable
N/A
N/A
Acceptable
NAMEPLATE
21001, REVISED 10/20/2020(888) 778-2733 www.schneider-electric.us
WITHSTAND RATING
TYPE / STYLECURRENT RATING QED
SN / SO NO. SYSTEM VOLTAGE
MODEL / CATALOG
N/A
45-08000-62S
INSPECTION
Acceptable
PT'S AND CT'S
Acceptable Cleaned AcceptablePOWER CABLES
N/A N/A N/A INTERCONNECT WIRING N/ARACKING / LIFTING MECHANISMS
Acceptable N/ADOORS / COVERS / GASKETS
CPT AND CPT XFER CKT. ANCHORAGE
GROUNDING
PHASING CHECK
CONTROL WIRING
SPACE HEATERS
Description
N/A
CleanedINTERIOR SECTIONS / CUBICLES
N/A
PHASE BARRIERS
SEQUENCE OF OPERATION
Description
N/A
N/A
Cleaned
N/A
N/A
Square D
RANGE
BARRIERS / SHUTTERS
@1000VMEG-OHMS 20°C
1,276.0 1,454.6
TEST 1
TEST 2
INSULATION RESISTANCE IN: PHASE-PHASE
1,838.81,613.0
20°CACTUALACTUAL
A - B A-GND
PHASE-GROUND
B-GND
C-GND
B - C
C - A
1,712.0
1,027.0
450.0
1,019.0
513.0
1,951.7
1,170.8 1,161.7TEST 3
N-GNDTEST 4
1.14TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
INSULATION RESISTANCE TEST
SECTION 1 SECTION 2 16 15 16 15
NBAFROM TO
BUS SECTION TESTED RESISTANCE IN MICRO-OHMS
C
RESISTANCE IN MICRO-OHMS
G
N
BUSWORK CONNECTION RESISTANCE
CBAFROM TO
BUS SECTION TESTED
G
TECH NOTE(S):
COMMENTS: All results are satisfactory at this time.
20°C
MEDIUM VOLTAGE AIR SWITCH
TEMPERATURE 82 °C
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-6DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MV AIR SWITCH -RA
David Gordon
VA Hospital WO-08391081
C & L
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES Acceptable Cleaned CleanedINTERLOCKS Acceptable CleanedINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
44035-233-51
N/A
15 kv
N/A
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE POWER ZONE
95 KA
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
600 AMP
FUSE AMPS9F60BHH905FUSE MFG. GOUND FUSE CAT. NO. .5 amp
@1000VGIG-OHMS 20°C
0.0 0.0
TEST 1
TEST 3
17.48TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
0.0
0.0 0.0
0.0
15 kv
SQUARED
65KV
RANGE
(µ-ohms) 34
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at 10 A
POLE 1
36 30
10 AFUSE RESISTANCE at (m-ohms)
TECH NOTE(S): Did not test insulation resistance in the closed position due to feeder cables connected to the switch.
20°C
MEDIUM VOLTAGE AIR SWITCH
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-6DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MV AIR SWITCH -A1
David Gordon
VA Hospital WO-08391081
C & L
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
COUNTER READING AF/AL
ARCING CONTACTS
HEATER CIRCUIT
MAIN CONTACTS
CUBICLE
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
CONTROL CIRCUIT
FUSE HOLDERS
CONDITIONDescription CLEAN/LUBE
N/AN/A
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
ARC CHUTES Acceptable Cleaned CleanedINTERLOCKS Acceptable CleanedINS. LINKAGES / BRACES
OVERALL CONDITION Acceptable
CONDITION
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
SWITCH NAMEPLATE
INSPECTION
CONTROL WIRING
MEG-OHMS
06060, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
@500V
INSULATION RESISTANCE IN:
N/A
MANUFACTURER
RATED CURRENT INT. RATING
44035-234-51
N/A
15 kv
N/A
SN / SO NO.
RATED VOLTAGE
CATALOG NO.
MAX. VOLTAGE BIL RATING
TYPE / STYLE POWER ZONE
95 KA
N/A
ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE VOLT RANGE
PICKUP VOLTS
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
CLOSE COIL INFORMATION
N/A N/A VoltsVolts
PICKUP VOLTS
Volts
TRIP COIL INFORMATION
Volts
ADDITIONAL INFO
VOLT RANGE
N/A
OPTIONAL INFORMATION
TEST RESULTS
MANUF. DATE
800 AMP
FUSE AMPSA155F2DORO-65EFUSE MFG. FERRAZ SHAWMUT FUSE CAT. NO. 65E AMP
@1000VGIG-OHMS 20°C
0.0 0.0
TEST 1
TEST 3
1.4348TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
0.0
0.0 0.0
0.0
15 kv
SQUARED
65 KA
RANGE
(m-ohms) 29
POLE 2 POLE 3CONTACT RESISTANCE MEASUREMENTS
BYPASS CONTACT RESISTANCE at
POLE 1
49 34
21.4 21.221FUSE RESISTANCE at (m-ohms)
TECH NOTE(S): Did not test insulation resistanc due to feeder cables connected to the switch.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-6DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT C
David Gordon
3284,3230
VA Hospital WO-08391081
800 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF836LSIG
N/AFUSE CAT. NO.
800 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A Cleaned N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
1 IN
7 7 7
.2
1 IN
.9
4 IN
1 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 600RATING PLUG:800 800
Overcurrent Settings
CT / SENSOR RATINGS:
1 IN 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
2.022
0.536
NT NT NT NT NT
3,150 1.6 2.6
800 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
2,400
8.930
SHORT TIME PICKUP
SHORT TIME DELAY 1.05
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.5
sec sec sec sec sec sec
AS LEFT
540 A A660
A A
AA
A A
2,700 3,300
4,6203,780
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
TRIP UNIT TYPE
N/A
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 82 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-6DESIGNATION
SUBSTATION BUILDING 100
05/22/2021 96
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
BUS DUCT B
David Gordon
3284,3230
VA Hospital WO-08391081
800 AMP
N/A
N/A N/A
MATCHES DWG OR SPEC
GROUND CONNECTION
ONME
65K
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. MEF836LSIG
N/AFUSE CAT. NO.
800 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
N/A
N/A
Acceptable
N/A
N/A
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
N/AAcceptable
Description
N/A
C & L
N/AOPERATING MECHANISM Cleaned
PHASE BARRIERS Acceptable N/A
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS
OVERALL CONDITION Acceptable
CONDITION
N/A
N/A
N/A
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Square D
Micrologic N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
2 IN
10 7 10
.2
1 IN
.9
4 IN
2 IN
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 600RATING PLUG:800 800
Overcurrent Settings
CT / SENSOR RATINGS:
1 IN 4 IN
.4.2
AS FOUND
RANGE
MINIMUM MAXIMUM
NT
4,189
1.983
0.543
NT NT NT NT NT
3,150 1.6 2.6
800 0.5 0.6
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 15 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
2,400
8.928
SHORT TIME PICKUP
SHORT TIME DELAY 1.05
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2.5
sec sec sec sec sec sec
AS LEFT
540 A A660
A A
AA
A A
2,700 3,300
4,6203,780
288 352
POLE 1
FUNCTION
POLE 2TEST RESULTS BY SECONDARY INJECTION
TECH NOTE(S): Did not perform insulation resistance test due to other electrical equipment, cables or bus duct connected to breaker.
All tested functions passed at this time.
TRIP UNIT TYPE
27Y2887
BKR INT. RATING
MOUNTING
LOW VOLTAGE POWER CIRCUIT BREAKER
TEMPERATURE 76 °F
PAGE
END USER
CUSTOMER
2002 HOLCOMBE BLVD.
DEPARTMENT OF VETERAN AFFAIRS
SITE LOCATION
USS-6DESIGNATION
SUBSTATION BUILDING 100
4/20/21 45
JOB #
DBID
END USER ASSET/ID
HUMIDITYDATE
TESTED BYELEMENT
SUB-ELEMENT
DEVICE
EQUIPMENT USED
MAIN BREAKER
Javier Rojas, David Gordon
3230,3115,01025
VA Hospital WO-08391081
1600 AMP
Cleaned
C & L Cleaned
MATCHES DWG OR SPEC
GROUND CONNECTION
ONDS416
50 KVA
MANUFACTURER
FUSE MFR.
BKR CATALOG NO. N/A
N/AFUSE CAT. NO.
1600 AMP Off
B.I.
THERMAL MEMORY
SENSOR TAPS
FRAME SIZE
MAIN / ARCING CONTACTS
BATTERY STATUS
PRIMARY DISCONNECTS
CELL AND RACKING DEV.
CLEAN/LUBE Description CLEAN/LUBECONDITION
Acceptable
Acceptable
Acceptable
N/A
Cleaned
ARC CHUTES
SECONDARY DISCONNECT
CONDITIONDescription CLEAN/LUBE
CleanedAcceptable
Description
Cleaned
C & L
N/AOPERATING MECHANISM C & L
PHASE BARRIERS Acceptable Cleaned
N/AAUXILIARY DEVICES
BLOWN FUSE INDICATOR N/A N/A N/AINTERLOCKS N/A N/A
OVERALL CONDITION Acceptable
CONDITION
N/A
Acceptable
Acceptable
Acceptable
N/A
BREAKER NAMEPLATE
INSPECTION
TARGETS
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
D.O.
N/A
N/A
N/A
N/AMFR. DATE / CODE N/A
SN / SO NO.Westinghouse
AC PRO N/A
COUNTER READING AL N/A
FUSE AMPS N/A
COUNTER READING AF
RANGE
Volts
ADDITIONAL INFO ADDITIONAL INFO ADDITIONAL INFO
PICKUP VOLTS PICKUP VOLTS PICKUP VOLTS
ADDITIONAL INFO
VOLT RANGE
N/A
N/AVOLT RANGE N/AVOLT RANGE
PICKUP VOLTS
VOLT RANGE
VOLT RANGE
ADDITIONAL INFO
DROP-OUT VOLTS
CHARGING MOTOR INFORMATION
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
CLOSE COIL INFORMATION
N/A
N/A
N/A
N/A
TRIP COIL (1) INFORMATION
N/A
N/A
N/A
TRIP COIL (2) INFORMATION
N/A
N/A
Volts
UNDERVOLTAGE COIL INFORMATION
Volts
PICKUP VOLTS
Volts Volts
NT
CONTROL WIRING
20°C
INSULATION RESISTANCE IN:
MEG-OHMS @500V
@1000VGIG-OHMS 20°C
362.0 441.6
294.0 358.7
TEST 1
TEST 3
1.22TEMPERATURE CORRECTION FACTOR TO 20°C, TCF
TEST 2
INSULATION RESISTANCE IN: CLOSED: POLE-POLE
390.4320.0
20°C ACTUAL
PH A
ACTUALACTUAL
A - B A-GND
CLOSED: POLE-GROUND OPEN: LINE-LOAD
20°C
PH B
PH C
B-GND
C-GND
B - C
C - A
262.0
282.0
265.0
283.0
392.0
367.0323.3
319.6
447.7
344.0 345.3
478.2
CONTACT RESISTANCE - MICRO-OHMS
POLE 1
FUSE 2FUSE 1 FUSE 3
N/A N/A N/A
POLE 3POLE 2
7.0
.2
OFF 4000 OFF
.2
0.2
7.0
.2
LONG TIME DELAY
SHORT TIME PICKUP
SHORT TIME DELAY
INSTANTANEOUS PICKUP
GROUND FAULT PICKUP
GROUND FAULT DELAY
LONG TIME PICKUP
AS FOUND
SETTING
AS TESTED
SETTING
AS LEFT
SETTING I2T ON
AS TESTED
SETTING
AS LEFT
SETTING I*2 T ON
AS FOUND
SETTING
CT / SENSOR TAP: 1600 AMPRATING PLUG:1600 AMP 1600 AMP
Overcurrent Settings
CT / SENSOR RATINGS:
.2 0.4
480390
LOW VOLTAGE POWER CIRCUIT BREAKER
PAGEMAIN BREAKERDEVICE DBID
03001, REVISED 10/19/2020(888) 778-2733 www.schneider-electric.us
AS FOUND
RANGE
MINIMUM MAXIMUM
4,232
0.42
2.7
4,232
0.42
6,420
2.7
4,233
0.45
6,425
2.6
4,233
0.45
6,425
2.6
4,100
0.45
5,938
2.1
4,100
0.45
5,938
2.1
9,600 0.4 0.5
960 2 2.42
POLE 3
AS FOUNDAS FOUND AS LEFT AS LEFT
3 8.25 7.2 7.2 7.5 7.5
1,634 1,640 1,640 1,710 1,710
NT NT NT
CURRENT
MULTIPLE
TEST
AMPERES
sec 10 sec
LONG TIME PICKUP
LONG TIME DELAY
MILLIVOLT DROP
4,800 6
1,634
8.25
SHORT TIME PICKUP
SHORT TIME DELAY 1.5
INSTANTANEOUS PICKUP
INSTANTANEOUS DELAY
GROUND FAULT PICKUP
GROUND FAULT DELAY 2
sec sec sec sec sec sec
AS LEFT
1,440 A A1,760
A A
AA
A A
5,760 7,040
4,4003,600
452 528
POLE 1
FUNCTION
POLE 2TEST RESULTS BY PRIMARY INJECTION
TECH NOTE(S):
COMMENTS: Ground Fault test for A & B Phase is slightly higher than the maximum expected trip time.